Fluke 753, 754 Service Guide

Process and temperature switch applications with the 740 Series DPCs
Application Note
This note discusses appli-
cations for process
switches and calibrating
temperature switches
using the Fluke 740 Series
Documenting Process
Calibrators (DPCs). Let’s
begin by looking at what a
process switch is and
what it does.
Process switches
A process switch is a device that can sense a process variable — such as temperature or pressure — and change the state of one or more sets of switch contacts when that variable reaches a predetermined value. This value is called a setpoint. A switch can have multiple setpoints. Let’s look at some important c how proc
pairs, and a pair is either nor mally open or normally closed. “Normally” means without ener-
ization — just the way the
g contacts would be on the shelf or if you disconnected the power
ires from the switch.
w
four sets of contacts — two normally open and two normally closed. But, there are many variations. A single switch may operate just one set of contacts, or it may operate multiple sets
ess switches work.
Contacts. Contacts come in
Many process switches have
onc
epts of
of normally open and normally closed contacts. You select which contacts to use based on the desired output for a given condi­tion and a given failsafe condition.
Control logic. You must think of switch actuation and contact state separately. Actuating the typical process switch means opening one set of contacts and closing another at the same time. Whether actuation opens or closes a set of contacts depends on whether you are using the normally open or normally closed contacts and whether the switch is in an activated or deactivated state during normal operation.
Failsafe operation is the first criterion to assess when deciding which set of contacts to use. For example, you should use normally closed contacts if breaking the circuit will result in a failsafe condition. Because loss of power and an open circuit (via a broken circuit wire, broken connection, or intentional operation) have the same effect on circuit operation, the normally open contacts would
­orrect ones to use. Upon
e the c
b loss of power, these contacts will open. So, you would want them to b operations and to open when operations go into alarm or
ontrol change c
c
a high level sw ily close c a high level condition. Good con­trol practic opposite.
e closed for normal
onditions
It is not true that, for example,
itch w
ontacts when you reach
es usually dictate the
.
ill nec
essar
What about actuation? You might want the switch to failsafe upon loss of level in a cooling tank. So, normal level would acti­vate the switch (compared to its shelf position). Upon loss of level, the switch deactivate — that is, it will assume the same state that it would be in if it were on the shelf. For an example of this control logic, look at a typical toggle-style light switch. You will notice the word “ON” under the toggle handle and the word OFF above it. To reveal the word “ON,” you must flip the switch up. If the toggle mechanism were to fail mechanically — which could happen if, for example, it were to melt due to arcing — the toggle handle would drop into the “OFF” position due to gravity. That is the failsafe position of these switches. It’s common to implement process switches the same way.
Setpoint. A switch may have multiple setpoints many level switches come with low-low, low, high, and high­high sets of contacts — each with its own setpoint.
But, it can get more c than that, depending on the required control scheme and the type of sw many ways to accommodate complex switching schemes — including the use of an analog transmitter serves as the input to
­a virtual switch (implemented in software).
. For example,
omplex
itch used. There are
From the Fluke Digital Library @ www.fluke.com/library
Deadband
Open
High Limit
Process
Variable
Low Limit
Setpoint
Reset
Closed
50
°C
20 °C
Deadband
Closed
Reset
Setpoint
Open
Figure 1. 2-point switch with settings for low and high setpoints.
Here’s an example of a com­plex application. A level switch may allow a “normal” indication (such as a light) to display at any level up to 82 %. At 82 %, the switch causes normal indication to go off — placing the indication between a normal state and an alarm state. At 85 %, the switch
y trigger a high level alarm
ma light. At 90 %, the switch may trigger a high-high level alarm
t
light plus an audio alarm 93 %, it ma
y trigger a feed valve
. A
closure. At 95 %, it may trigger
7 %,
t 9
dump valve operation
y trigger drain pump opera
it ma tion. At 98 %, it may actuate
. A
isolation doors in the room c taining the tank
. And those actions are just for high level. This same sw might c
itch, or another,
ontrol low level opera­tions. In some configurations, you might ha
ve separate sw
each setpoint
.
itches for
on
-
Setpoint tolerance. This is the amount of error you can have between the desired setpoint and the one you actually set. It’s not always easy to calibrate a switch directly on the desired setpoint — for a variety of reasons. For example, if you must open a valve when the temperature reaches 3 point tolerance might allow you consider the switch calibrated if it trips w setpoint expressed in engineering units or
ent
in perc
-
ent, that normally means
perc percent of the control explain band b
ent of the setpoint value.
c
Direction. Switch actuation (and, therefore, c tional, due to hysteresis Sometimes, the hysteresis value can exc
e. For non-critical applications
anc with wide setpoint tolerances, you can probably ig
. But, standard practice is to
sis observe direction when calibrat­ing a setpoint calibrate a low level switch, you do so with the level dropping.
rees, your set
3 deg
1
ithin 5 deg
olerances may be
. T
. When expressed in
rees of the
elow), not in per
band (we
ontrol) is direc
.
eed the setpoint toler
nore hystere
. When you
When you calibrate a high level switch, you do so with the level rising. This is standard practice with all process variables, not just level — you get a more accu­rate calibration by accounting for hysteresis.
Trip. This is the value at which the switch will change the state of a given set of contacts. Where a switch trips is a function of its setpoint and direction. For a pressure switch with a setpoint of 500 PSI, the switch should trip at 500 PSI as pressure rises. Trip is also called “set.” The opposite of that is reset
.
Reset. Some switches reset automatically, while others require a manual reset
. In either case, the reset will not occur until the switch actuator has moved in the direction opposite its trigger­ing direction enough to overcome hysteresis (and/or deadband — see below) and allow the switch to change contact states back to normal. An exception to this is when the switch is used to indi­cate a normal condition. For such switches, reset is usually not an issue.
Hysteresis. This is the ten­dency of the switch to stay in the last position it was in. This means that when you are cali­brating a switch to trip at 500 PSI, the hysteresis of the switch may cause it to trip at 501 PSI
­when you are increasing pressure
and 499 PS
I when you are
decreasing pressure. If this is a
ontrol
high pressure sw
itch (c function requires a trip on rising pressure), you would calibrate it to trip at 500 PS
I on an increas
­ing pressure input and let the 498 PSI trip serve as the maxi-
­mum reset value.
Band.This is the area around
the setpoint where the switch is
­or exam
. F
ontrolling the proc
c ple, if the sw
-
tank to maintain a level between
ess
itch will control a
-
6 feet of water and 9 feet of water, it has a band of 3 feet
.
-
2 Fluke Corporation Process and temperature switch applications with the 740 Series DPCs
Loading...
+ 3 hidden pages