Fluke 753, 754 Service Guide

Process and temperature switch applications with the 740 Series DPCs
Application Note
This note discusses appli-
cations for process
switches and calibrating
temperature switches
using the Fluke 740 Series
Documenting Process
Calibrators (DPCs). Let’s
begin by looking at what a
process switch is and
what it does.
Process switches
A process switch is a device that can sense a process variable — such as temperature or pressure — and change the state of one or more sets of switch contacts when that variable reaches a predetermined value. This value is called a setpoint. A switch can have multiple setpoints. Let’s look at some important c how proc
pairs, and a pair is either nor mally open or normally closed. “Normally” means without ener-
ization — just the way the
g contacts would be on the shelf or if you disconnected the power
ires from the switch.
w
four sets of contacts — two normally open and two normally closed. But, there are many variations. A single switch may operate just one set of contacts, or it may operate multiple sets
ess switches work.
Contacts. Contacts come in
Many process switches have
onc
epts of
of normally open and normally closed contacts. You select which contacts to use based on the desired output for a given condi­tion and a given failsafe condition.
Control logic. You must think of switch actuation and contact state separately. Actuating the typical process switch means opening one set of contacts and closing another at the same time. Whether actuation opens or closes a set of contacts depends on whether you are using the normally open or normally closed contacts and whether the switch is in an activated or deactivated state during normal operation.
Failsafe operation is the first criterion to assess when deciding which set of contacts to use. For example, you should use normally closed contacts if breaking the circuit will result in a failsafe condition. Because loss of power and an open circuit (via a broken circuit wire, broken connection, or intentional operation) have the same effect on circuit operation, the normally open contacts would
­orrect ones to use. Upon
e the c
b loss of power, these contacts will open. So, you would want them to b operations and to open when operations go into alarm or
ontrol change c
c
a high level sw ily close c a high level condition. Good con­trol practic opposite.
e closed for normal
onditions
It is not true that, for example,
itch w
ontacts when you reach
es usually dictate the
.
ill nec
essar
What about actuation? You might want the switch to failsafe upon loss of level in a cooling tank. So, normal level would acti­vate the switch (compared to its shelf position). Upon loss of level, the switch deactivate — that is, it will assume the same state that it would be in if it were on the shelf. For an example of this control logic, look at a typical toggle-style light switch. You will notice the word “ON” under the toggle handle and the word OFF above it. To reveal the word “ON,” you must flip the switch up. If the toggle mechanism were to fail mechanically — which could happen if, for example, it were to melt due to arcing — the toggle handle would drop into the “OFF” position due to gravity. That is the failsafe position of these switches. It’s common to implement process switches the same way.
Setpoint. A switch may have multiple setpoints many level switches come with low-low, low, high, and high­high sets of contacts — each with its own setpoint.
But, it can get more c than that, depending on the required control scheme and the type of sw many ways to accommodate complex switching schemes — including the use of an analog transmitter serves as the input to
­a virtual switch (implemented in software).
. For example,
omplex
itch used. There are
From the Fluke Digital Library @ www.fluke.com/library
Deadband
Open
High Limit
Process
Variable
Low Limit
Setpoint
Reset
Closed
50
°C
20 °C
Deadband
Closed
Reset
Setpoint
Open
Figure 1. 2-point switch with settings for low and high setpoints.
Here’s an example of a com­plex application. A level switch may allow a “normal” indication (such as a light) to display at any level up to 82 %. At 82 %, the switch causes normal indication to go off — placing the indication between a normal state and an alarm state. At 85 %, the switch
y trigger a high level alarm
ma light. At 90 %, the switch may trigger a high-high level alarm
t
light plus an audio alarm 93 %, it ma
y trigger a feed valve
. A
closure. At 95 %, it may trigger
7 %,
t 9
dump valve operation
y trigger drain pump opera
it ma tion. At 98 %, it may actuate
. A
isolation doors in the room c taining the tank
. And those actions are just for high level. This same sw might c
itch, or another,
ontrol low level opera­tions. In some configurations, you might ha
ve separate sw
each setpoint
.
itches for
on
-
Setpoint tolerance. This is the amount of error you can have between the desired setpoint and the one you actually set. It’s not always easy to calibrate a switch directly on the desired setpoint — for a variety of reasons. For example, if you must open a valve when the temperature reaches 3 point tolerance might allow you consider the switch calibrated if it trips w setpoint expressed in engineering units or
ent
in perc
-
ent, that normally means
perc percent of the control explain band b
ent of the setpoint value.
c
Direction. Switch actuation (and, therefore, c tional, due to hysteresis Sometimes, the hysteresis value can exc
e. For non-critical applications
anc with wide setpoint tolerances, you can probably ig
. But, standard practice is to
sis observe direction when calibrat­ing a setpoint calibrate a low level switch, you do so with the level dropping.
rees, your set
3 deg
1
ithin 5 deg
olerances may be
. T
. When expressed in
rees of the
elow), not in per
band (we
ontrol) is direc
.
eed the setpoint toler
nore hystere
. When you
When you calibrate a high level switch, you do so with the level rising. This is standard practice with all process variables, not just level — you get a more accu­rate calibration by accounting for hysteresis.
Trip. This is the value at which the switch will change the state of a given set of contacts. Where a switch trips is a function of its setpoint and direction. For a pressure switch with a setpoint of 500 PSI, the switch should trip at 500 PSI as pressure rises. Trip is also called “set.” The opposite of that is reset
.
Reset. Some switches reset automatically, while others require a manual reset
. In either case, the reset will not occur until the switch actuator has moved in the direction opposite its trigger­ing direction enough to overcome hysteresis (and/or deadband — see below) and allow the switch to change contact states back to normal. An exception to this is when the switch is used to indi­cate a normal condition. For such switches, reset is usually not an issue.
Hysteresis. This is the ten­dency of the switch to stay in the last position it was in. This means that when you are cali­brating a switch to trip at 500 PSI, the hysteresis of the switch may cause it to trip at 501 PSI
­when you are increasing pressure
and 499 PS
I when you are
decreasing pressure. If this is a
ontrol
high pressure sw
itch (c function requires a trip on rising pressure), you would calibrate it to trip at 500 PS
I on an increas
­ing pressure input and let the 498 PSI trip serve as the maxi-
­mum reset value.
Band.This is the area around
the setpoint where the switch is
­or exam
. F
ontrolling the proc
c ple, if the sw
-
tank to maintain a level between
ess
itch will control a
-
6 feet of water and 9 feet of water, it has a band of 3 feet
.
-
2 Fluke Corporation Process and temperature switch applications with the 740 Series DPCs
related to reset. Deadband pre-
ENTER
V
RTD
MEAS
SOURCE
mA
mA
RTD
V
30
0
V
MAX
30V MAX
TC
Fluke 741/743
To Limit
To Limit Switch
Thermocouple
Input
vents a switch from cycling around a setpoint. Hysteresis pro­vides some deadband, automatically. But for some proc enough to prevent undesirable on/off cycling. So, many switches have additional deadband inten­tionally designed into them. That deadband may be fixed, fixed selectable, or variable. For exam­ple, an electronic thermostat used for a heat pump may have a fixed selectable deadband of 1.5 deg
the low and high points of opera­tion will control a tank to maintain a level between 6 feet of water and 9 feet of water, it has a cali­bration range of 6 to 9 feet. The switch itself might have an actual range of 0 to 50 feet — this range would appear on the nameplate of the switch.
Testing a temperature switch
The switch in the following example is a temperature switch with a type K thermocouple input and a low temperature setpoint of 20 °C. This switch functions in much the same way as the ther­mostat in your home. The Low Limit example in Figure 1 illus­trates the terminology.
open contacts of this switch. These c switch actuation, which will occur with a drop in temperature. This sw adjustable reset. The contacts will re-open upon automatic reset, which oc perature moves back up and past the setpoint in an amount greater than its deadband is a minimum of 1 °C and maxi­mum of 3 °C across the range of the sw
DPC to calibrate the switch, follow these step-by-step instruc tions. Keystroke entries for the DPC are surrounded by quotation mark
Deadband. This is closely
1. Beginning in the power up state of the calibrator, or Measure mode, depress the “ohms/continuity” key twice to enable continuity mode.
esses, hysteresis is not
2. Simulate the temperature input.
a. Depress the
“MEAS/SOURCE” key once to obtain the Source mode.
b. Depress the “TC/RTD”
key, move the cursor with the “
” key to “K” and
NTER” to select
rees or 3 degrees.
Range. This is specified with
. For example, if the switch
depress “E a type K thermocouple.
c. Depress “ENTER” again to
select “Linear T.”
d. Enter a temperature out-
put of “25” and depress “ENTER.”
e. Depress the
“MEAS/SOURCE” key to obtain the split screen display. The display of the 74X should be as per Figure 2.
3. Connect the DPC, per Figure 3.
4. Take As Found measurements.
a. Select the “As Found”
softkey. b. Move the cursor to “1 Pt. c. Switch Test” with the “
key and depress “ENTER.”
You should now see the
switch test setup screen.
.
We will be using the normally
ontacts w
ill close upon
Enter the setpoint
5. a. Depress “Enter” and enter
a setpoint of “20” °C, then depress “ENTER” again. The Setpoint Type is set for low and the Set State
itch does not ha
ve
is a short by default — perfect for this particular test. (If these conditions
curs as the tem
-
were different, we would change them here.). These setup conditions
. The deadband
describe a switch that has a setpoint of 20 °C and closes a set of contacts as
itch.
To set up the Fluke 740 Series
-
s.
3 Fluke Corporation Process and temperature switch applications with the 740 Series DPCs
long as the input temper­ature to the switch is below 20 °C.
b. Depress the “Done”
softkey.
Figure 2. MEASURE/SOURCE split screen, contacts open.
Figure 3. Connecting the DPC.
6. Enter the setpoint tolerance and deadband settings. a. Move the cursor to tolerance and enter a
setpoint tolerance of “1” °C.
b. Move the cursor to Deadband Min and
enter a minimum deadband of “1” °C. Move the cursor to D
.
c
eadband Max and enter a maximum deadband value of 3 The test setup screen should now be as
” softkey
ure 4. D
per Fig
Figure 4. Test setup screen.
epress the “D
one
.
C
°
.
Figure 5. MEASURE/SOURCE split screen, contacts reset.
7. You should now see the split screen (Figure 5). Select the “Auto Test” softkey and the “Continue” softkey. The DPC will now ramp the simulated thermocouple potential into the limit switch back and forth past the nominal setpoint and record the sourced temperature values for the actual setpoint, and then show that value in the upper left-hand corner of the DPC display. Once that is done, the DPC will then test the reset point of the switch by ramping the simulated thermocouple potential into the switch back and forth past the nominal (21 °C - 23 °C) expected reset value. Once that value is recorded, you should be presented with a post test summary similar to that in Figure 6. Errors exceeding test tolerance are recorded in inverse video.
8. Enter Tag information. a. Depress the “Done” soft-
key and enter the Tag information for your test.
b. Depress the “Done” soft-
key when tag entry is complete.
9. Adjust setpoints or reset points. a. If the switch failed any of
the test parameters, it is necessary to adjust the set and/or reset points. To do that, first select the “adjust” softkey.
b. Depress the “Step Size”
softkey, then enter a step size of “.1” °C.
c. Depress the “Done”
softkey.
d. Depress the “
” key until
the DPC source value is 20 °C (the setpoint).
e. Slowly adjust the setpoint
on the limit switch until the measure screen tog­gles from reset to set. Depress the “
” key until
the DPC measure screen toggles to Reset. If the DPC toggles from set to reset between 21 °C and 23 °C, the deadband should be correctly set. If it does not toggle prop­erly, adjust the reset point until it toggles within that band.
f. Verify the set and reset
points toggle correctly, by depressing the “ “
” keys to slew the DPC
” and
source temperature across the set and reset values.
g. Once that is complete,
depress the “Done” softkey.
10. Confirm the As Left settings. a. Depress the “As Left”
softkey. b. Confirm the test settings. c. Depress the “Done”, “Auto
Test” and “Continue” soft-
keys. Monitor the DPC as
it performs the As Left
evaluation. d. Once the post test sum-
mary is displayed, review
the results. If all results
are in normal video (as in
Figure 7), the As Left test
passes. e. Depress the “Done” soft-
key, and “D ne
” again to
save the Tag information.
. If there were inverse
f
ideo indications of a fail-
v
ure, repeat the
adjustments performed in
Step 9 until a passing
result is obtained.
11. Review results in memory, a. Depress the “Done”
and “Review Memory” softkeys.
b. Move the cursor to the tag
entry associated with this test and depress “ENTER.”
c. Move the cursor to the As
Found entry and depress “Enter” to review your As Found result.
d. Depress the “Done”
softkey.
e. Move the cursor to the As
Left entry and depress “Enter” to review that
.
result
f. Depress the “Done” soft-
key, then depress the “Tag” softkey to review your Tag information.
Figure 6. Post-test summary, with reverse video.
4 Fluke Corporation Process and temperature switch applications with the 740 Series DPCs
Figure 7. Post-test summary, with all results normal.
Other switch tests
In the preceding step by step description, the switch has been removed from its operational cir­cuit and the switch contact closure is monitored to determine state change.
You can perform this test with the switch installed in its circuit. In this instance, the switch con­tacts will open and close and you can use the 740 Series DPC to measure the presence or absence of system voltage (e.g. 120VAC) as switch contacts change state. A typical example would be measur­ing the voltage applied to a heater as controlled by the output of the switch. The 740 series DPCs can work with dc voltage in addition to the continuity and ac voltage examples previously described.
Our examples in this applica­tion note have been for temperature switches. The 740 series DPCs allow you to test pressure switches, too — in fact, in 11 different engineering units. Pressure switch tests are similar to temperature switch tests — you vary the process variable (source) at the input, and monitor for a change of state at the output. You need to use a hand pump to source pressure into a pressure module and the switch. You can manually document the results by depressing the “Accept Point” soft key when the test has been completed.
With the 740 series DPCs, you can source and measure many key variables. And these tools are useful for calibrating any process switch. Of course, you will need to supply your own inputs for many types of process variables — such as level, flow, and pH. The principles of switch operation out­lined here apply universally.
For detailed information on
calibrating pressure switches,
reference Fluke Application
Note 2069058.
Fluke. Keeping your world
K
.
E or
up and running
Fluke Corporation
PO Box 9090, Everett, WA USA 98206 Fluke Europe B.V.
PO Box 1186, 5602 BD Eindhoven, The N
For more information call: In the U.S.A. (800) 443-5853 or
ax (425) 446-5116
F In Europe/M-East/Africa (31 40) 2 675 200 or Fax (31 40) 2 675 222 In Canada (8 Fax (905) 890-6866 From other c
ax +1 (425) 446-5
F Web access: http://www.fluke.com
©2004 Fluke Corporation. All rights reserved. Printed in U
etherlands
LU
F
00) 36-
ountries +1 (425) 446-5500 or
6
1
1
/2004 1263879 A-US-N Rev D
. 7
.A
.S
5 Fluke Corporation Process and temperature switch applications with the 740 Series DPCs
Loading...