Fluke 434 II, 435 I, 435 II, 437, 437 II Service Guide

...
Troubleshooting
commercial
lighting loads
Lighting is a major load for many large facilities. Evaluating these circuits is important for both energy conservation and power quality. Keep in mind that commercial lighting loads are wired single phase, with the loads connected from phase to neutral. Typically, the phase-to-phase voltage is 480 V, with the phase-to-neutral voltage at 277 V. Measurements must be taken at the lighting panel, on all phases, since power consumption and Power Factor could vary on each phase.
Application Note
1. Power consumption
Excessive phase unbalance can cause voltage unbalance, which in turn can affect three-phase motor loads. For example, in this three-phase reading, phase A is considerably higher than B and C, when all three phases should be equal.
2. Power Factor
Ballast with low PF might have lower cost-of-purchase but higher cost-of-operation. This phasor diagram illustrates the unbalance along with the power factor.
Measurements on commercial lighting loads
ook for
Measurement
1. Power consumption (kW) Balance among three phases.
actor (DPF and PF)
er F
ow
2. P
otal Harmonic Distortion (%THD)
3. T
4. Voltage Stability Unstable voltage can cause lights to flicker.
L
ve low DPF. Electronic ballast may have low total PF, although new
netic ballast w
Mag generations of ballast often ha
Current %T
ill ha
HD <20 % is desirable.
ve harmonic mitigation built-in
3. Total Harmonic Distortion
Current THD should be consid­ered when selecting ballast, especially if there is a possibility of transformer overloading. The bar graph pinpoints the 5th and 7th harmonics as the larger contributors.
.
From the Fluke Digital Library @ www.fluke.com/library
The Fluke 43B P
Ø1
Ø2 Ø3
N
Lighting Panel
ABC
277 V Phase-to-Neutral
480 V Phase-to-Phase
voltage (top) and current (b ously. Current swells/ inrush caused voltage sags, indicating that a load downstream from the measurement point is the cause of the disturbanc
ower Quality Analyzer trends
ottom) simultane-
e.
Single phase analyzers measure each ballast separately, requiring manual calculations. Three phase analyzers measure all three phases simultaneously and perform the calcula­tions automatically.
4. Voltage stability
The sags and swells mode of power quality analyzers is especially useful for recording repetitive voltage sags which can show up as flickering lights. Both current and voltage are moni­tored simultaneously. This helps us tell if sags are downstream of the measuring point (load­related) or upstream (source­related). For example, if voltage
downstream current inrush likely caused the sag. If both voltage and current sag, some event upstream caused the sags
e an upstream load
ould b
It c
like a motor on a parallel branch
ircuit which drew dow
c feeder voltage. Or it c source voltage-related, for example, a lightning strike or breaker trip/reclosure on the utility distribution system.
sags while current swells, a
2 Fluke Corporation Troubleshooting commercial lighting loads
.
n the
ould be
The Fluke 430 Series Power Quality Analyzers trend all three phases and compares interac­tion between the loads.
eping your world
Fluke. K
e
up and running.
Fluke Corporation
O Box 9
P Fluke Europe B.V.
PO Box 1186, 5602 BD Eindhoven, The N
For more information call: In the U.S.A. (800) 443-5853 or
ax (425) 446-5
F In Europe/ Fax (31 40) 2 675 222 In Canada (800) 36-FLUKE or
ax (9
F From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com
©2004 Fluke Corporation Printed in U.S.A. 10/2004 2403043 A-US-N Rev A
0
05) 89
9
M
0, Everett, W
etherlands
6
1
1
Africa (3
East/
-
0-6866
A USA 98206
7
1 40) 2 6
. All rights reserved.
5 200 or
Loading...