The ideal meter for commissioning and
troubleshooting modern electrical loads
With a bright color display to analyze the harmonic
spectrum, a low-pass filter to remove high frequency noise,
and a high EMC immunity design, the Fluke 345 is ideal for
measurements on switching loads such as variable frequency
drives, electronic lighting and UPS systems. Additionally, the
Hall Effect measurement system makes measurement of dc
current possible without the need to break the circuit, and
the internal memory enables long-term logging for analysis of
trends or intermittent problems.
Technical DataTechnical Data
AC/DC current: Clamp-on measurement of ac current up to 1400 A
•
rms and dc current up to 2000 A without breaking the circuit
Highest safety rating: 600 V CAT IV rated for use at
•
the service entrance
Accurate in noisy environments: Even with distorted
•
waveforms present on electronic loads with low-pass filter
Data logging: Identify intermittent faults by
•
logging any power parameters for minutes or
months, including harmonics
Verify batteries: Direct measurement of dc ripple
•
(%) for battery and dc systems
Troubleshoot harmonics: Analyze and log
•
harmonics digitally or graphically
Inrush current: Capture and analyze nuisance tripping,
•
from 3 seconds to 300 seconds
Easy to use: Easily confirm instrument setup with
•
large backlit color display of waveforms and trends
3-Phase power: Built in capability for balanced loads
•
View graphs and generate reports: With included
•
Power Log software
Page 2
Applications
Set up and troubleshoot variable frequency drives
and UPS systems - Verify correct operation by
measuring key parameters
Harmonics measurements - Uncover harmonic issues
that can damage or disrupt critical equipment
Inrush capture - Check start-up current where spurious
resets or nuisance circuit breaker tripping occurs
Load studies - Verify electrical system capacity
before adding loads
Log measured parameters
All voltage, current, power, and harmonic measurements
can be logged for minutes, hours, or months. Measurement
averaging periods from 1 second to 15 minutes can be selected
depending on the application.
Measured parameters can be logged into three separate
recording memory areas. If longer recordings are required, the
three areas may be combined into one. Stored measurements
can be recalled and displayed on-screen in normal screen
format or downloaded using the Power Log software package.
Image Placeholder
(application photo related to VFDs)
Log parameters over time to track
down intermittent faults.
Harmonics measurements—view key
harmonic factors such as distortion factor
and total harmonic distortion, as well
as individual harmonics up to the 30th
harmonic.
2 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Page 3
Flexible and easy to use
The 345 measures a wide range of electrical parameters and
can be used for many applications in today’s modern electrical
environment. Measuring mode is selected by a simple turn of
the rotary switch and the large color display presents data in
a clear, easy-to-understand way.
By default the display will show the most common
measurements, in very large format. If more detailed views
are required they are available with the press
of a single key (up to six measurements at once).
Equipment performance
measurement - power consumed
by single- and three-phase
balanced loads.
Analysis and reporting software
Designed to quickly view recorded data, the
included Power Log software displays all recorded
parameters on interactive trends. Generate
professional reports with the ‘Report Writer’
function, or copy and paste images into report
document manually.
Easy-to-use tabbed window format allows
•
quick data evaluation.
One-step download and display capability
•
Waveform, harmonics, and trend download
•
Simple data export to other applications
•
View recorded data
in simple graphs
and tables.
View waveforms for equipment
checking and setup.
Inrush current
Diagnose equipment start-ups with the inrush current mode.
A current trigger level is set prior to recording. Once the level
has been exceeded, the meter will begin capture. Recordings
from 3 seconds to 300 seconds may be captured, and up to
1000 inrush events may be stored in the instruments memory.
Screen captures and data logging
Any measurement can be stored in memory for later viewing,
or downloaded to a PC. Simply press ‘SAVE’ to capture the
active screen to memory – up to 50 screen shots can be
saved for quick and simple documentation. Additionally, over
150,000 individual measurements can be logged for later
review on the display or on a PC using Power Log software.
Easily customize
the report.
3 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Create professional
reports.
Page 4
General Specifications
Display
Color transmissive LCD 320 x 240 pixels (70 mm diagonal) with 2 level backlight
Power supply
Battery type 1.5 V Alkaline AA MN 1500 or IEC LR6 x 6
Battery life typically> 10 hours (backlight on full)
> 12 hours (backlight reduced)
Battery Eliminator BE345
Input110 V/230 V, 50/60 Hz
Output15 V dc, 300 mA
Ambient conditions (For indoor use only)
Reference conditionsAll accuracies stated at 23 °C ± 1 °C (73.4 °F ± 1.8 °F)
Operating temperature0 °C to 50 °C (32 °F to 122 °F)
Temperature coefficient of current
Temperature coefficient of voltage
Maximum relative humidity80 % for temperatures up to 31 °C (87 °F) decreasing linearly to 50 % relative humidity at
Maximum operating altitude2000 m
≤ ± 0.15 % of rdg per °C
≤ ± 0.15 % of rdg per °C
40 °C (104 °F)
Electrical safety
Safety IEC 61010-1 600 V CAT IV, double or reinforced insulation, pollution degree 2
Protection IP40; EN60529
Maximum safe working voltages
Current measurement 600 V ac rms or dc between uninsulated conductor and ground
Voltage measurement600 V ac rms or dc between either input terminal and ground, or 825 V between energized
phase voltages (delta power config.)
EMC
EmissionIEC/EN 61326-1:1997 class B
ImmunityIEC/EN 61326-1:1997
Mechanical
Dimensions (length x width x depth)300 mm x 98 mm x 52 mm (12 in x 3.75 in x 2 in)
Weight including batteries820 g/1.8 lb
Jaw opening60 mm
Jaw capacity58 mm diameter
CleaningThe unit can be cleaned with an Isopropanol impregnated cloth. Do not use abrasives or
other solvents.
4 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Page 5
Specifications
Electrical data
All accuracies stated at 23 °C ± 1 °C (73.4 °F ± 1.8 °F). See Ambient conditions specifications for temperature coefficients.
Current measurement (dc, dc rms, ac rms)
Measuring range0 to 2000 A dc or 1400 ac rms
Autorange facility40 A/400 A/2000 A
Resolution10 mA in 40 A range
≤ H30
All measurements up to 30th harmonic (40th harmonic for 15 Hz to 22 Hz)
Frequency range F0 15 Hz to 22 Hz and 45 Hz to 65 Hz
V
> 1V
acrms
± 3 % rdg ± 5 digits
± 5 % rdg ± 5 digits
± 3 % rdg ± 5 digits
± 5 % rdg ± 2 digits
± 10 % rdg ± 2 digits
6 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Page 7
Watts measurement (single- and three-phase) (dc, dc rms, ac rms)
Measuring range0 to 1650 kW dc or 1200 kW ac
Autoranging facility4 kW, 40 kW, 400 kW, 1650 kW ac
Resolution1 W in 4 kW
10 W in 40 kW
100 W in 400 kW
1 kW in 1200 kW
Accuracy2.5 % rdg ± 5 digits
W1Ø < 2 kW ± 0.08 kW
W3Ø < 4 kW ± 0.25 kW
VA measurement (single- and three-phase) (dc, dc rms, ac rms)
Measuring range0 to 1650 kVA dc or 1200 kVA ac
Autorange facility4 kVA, 40 kVA, 400 kVA, 1650 kVA
Resolution1 VA in 4 kVA
10 VA in 40 kVA
100 VA in 400 kVA
1 kVA in 1200 kVA
Accuracy
VA > 2 kVA2.5 % rdg ± 5 digits
VA < 2 kVA± 0.08 kVA
VAR measurement (single- and three-phase)
Measuring range0 to 1250 kVAR
Autorange facility4 kVAR, 40 kVAR, 400 kVAR, 1200 kVAR
Resolution1 VAR in 4 kVAR
10 VAR in 40 kVAR
100 VAR in 400 kVAR
1 kVAR in 1200 kVAR
Accuracy
VAR > 4 kVAR± 2.5 % rdg ± 5 digits
VAR < 4 kVAR± 0.25 kVAR
Power factor range0.3 < PF < 0.99
Power factor (single- and three-phase)
Power factor
Measuring range0.3 capacitive and 1.0 to 0.3 inductive (72.5° capacitive and 0° to 72.5° inductive)
Resolution0.001
Accuracy± 3°
Frequency range15 Hz to 1 kHz
Displacement power factor
Measuring range0.3 capacitive and 1.0 to 0.3 inductive (72.5° capacitive and 0° to 72.5° inductive)
Resolution0.001
Accuracy
Frequency range15 Hz to 22 Hz and 45 Hz to 65 Hz
± 3°
7 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Frequency rangeDC and 15 Hz to 1 kHz
Current range10 A to 1400 A rms
Voltage range1 V to 825 V rms
Maximum input825 V rms/1400 A rms
Maximum overload1000 V rms/10,000 A
Frequency measurement (from current or voltage sources)
Measuring range15 Hz to 1 kHz
Resolution0.1 Hz
Accuracy15 to 22 Hz ± 0.5 % rdg
40 Hz to 70 Hz ± 0.5 % rdg
15 Hz to 1000 Hz ± 1% rdg
Current range10 A to 1400 A rms
Voltage range1 V to 825 V rms
Scope function
Current measurement
Ranges10 A/20 A/40 A/100 A/200 A/400 A/1000 A/2000 A
Resolution1 A in 40 A
10 A in 400 A
50 A in 2000 A
Accuracy± 3 % rdg ± 1 pixel
Maximum overload
Voltage measurement
Ranges4 V/10 V/20 V/40 V/100 V/200 V/400 V/1000 V
Resolution100 mV in 4 V
Accuracy± 2 % rdg ± 1 pixel
Maximum overload
Frequency rangeDC and 15 Hz to 600 Hz
Time base2.5 ms, 5 ms, 10 ms, 25 ms, 50 ms/div
Refresh rate0.5 seconds
Maximum sampling rate15.625 kHz
10,000 A
1 V in 40 V
10 V in 400 V
31.25 V in 1000 V
1000 V rms
8 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Page 9
Inrush current function
Ranges40 A, 400 A, and 2000 A
Resolution10 mA in 40 A range
100 mA in 400 A range
1 A in 2000 A range
Accuracy
I > 10 A± 5 % rdg ± 1 pixel
I < 10 A± 0.5 A
All measurements dc and 15 Hz to 1 kHz
Maximum overloadMaximum overload 10,000 A or rms x frequency < 400,000
Amps rms is a true-rms measurement (ac + dc)
Capture time1 s, 3 s, 10 s, 30 s, 100 s, and 300 s
Maximum sampling rate15.625 kHz
Interface
USB Interface to a PC
Power Log software for download, analysis, and reporting
345 Upgrade Utility for installing a new firmware version
Logging Memory
Logging areasThree areas that can be used individually or combined into one large area
Averaging periods1 s, 2 s, 5 s, 10 s, 30 s, 1 min, 5 min, 10 min, 15 min, and custom
9 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Page 10
Logging times
Volts and current mode
Average timeLogging time (1 area)Logging time (3 areas)
1 s1 h 49 m5 h 12 m
2 s3 h 38 m10 h 24 m
5 s9 h 06 m1 d 2 h 00 m
10 s18 h 12 m2 d 04 h 00 m
30 s2 d 06 h 36 m6 d 12 h 01 m
1 min4 d 13 h 12 m13 d 00 h 03 m
5 min22 d 18 h 00 m65 d 00 h 15 m
10 min45 d 12 h 00 m130 d 00 h 30 m
15 min68 d 06 h 00 m195 d 00 h 45 m
V & A harmonics mode
Average timeLogging time (1 area)Logging time (3 areas)
1 s0 h 34 m1 h 38 m
2 s1 h 08 m3 h 16 m
5 s2 h 52 m08 h 11 m
10 s5 h 44 m16 h 23 m
30 s17 h 13 m2 d 01 h 11 m
1 min1 d 10 h 26 m4 d 02 h 23 m
5 min7 d 04 h 10 m20 d 11 h 25 m
10 min14 d 08 h 20 m81 d 0 h 50 m
15 min21 d 12 h 30 m121 d 13 h 15 m
single- and three-phase power mode
Average TimeLogging Time (1 area)Logging Time (3 areas)
1 s1 h 40 m4 h 47 m
2 s3 h 21 m9 h 34 m
5 s8 h 22 m23 h 57 m
10 s16 h 45 m1 d 23 h 54 m
30 s2 d 02 h 17 m5 d 23 h 42 m
1 min4 d 04 h 35 m11 d 23 h 25 m
5 min20 d 22 h 55 m59 d 21 h 05 m
10 min41 d 21 h 50 m119 d 18 h 10 m
15 min62 d 20 h 45 m179 d 15 h 15 m
10 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Page 11
Ordering information
Fluke-345 Power Quality Clamp Meter
Includes Soft carrying case
Power Log software
Test leads
Alligator clips
Test probes
USB cable
International ac adapter / battery eliminator
Printed English language user manual
Multi-language manual CD
Recommended Accessories:
TP220 SureGrip™ Industrial Test Probes - One pair (red,
black) of Industrial test probes. Sharp, 12 mm stainless steel tip
provides reliable contact. Use with TL224 test leads.
AC220 SureGrip™ Alligator Clips - One pair (red, black) of
small, insulated, nickel plated jaws. Blunt tip grabs round screw
heads up to 9.5 mm. Use with TL224 test leads.
TP1 Slim Reach Test Probes - One pair (red, black) of slender probe bodies for
probing closely spaced or recessed terminals. Hard stainless steel probe tips with
flat blade design to hold securely in blade type electrical wall sockets.
L200 Probe Light - Small, rugged, and light the L200 easily attaches to any Fluke
test probe. Bright white LED illuminates contact area and frees hands for work.
L210 Probe Light and Probe Extenders - Includes L200 Probe Light and TP280
Test Probe Extenders to keep hands away from live circuits and light work area
C550 Tool Bag - Steel reinforced frame with heavy duty hardware and large
zippered storage compartment includes 25 pockets. Allows you to carry all your
tools to the job site.
TLK291 - Fused Test Leads provide extra safety with retractable sheath protecting
contact points.
Fluke. Keeping your world
up and running.™
11 Fluke Corporation Fluke 345 Power Quality Clamp Meter
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800) 36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com