Fluke 1742, 1746, 1748 Data Sheet

TECHNICAL DATA
Fluke-Direct
1742, 1746 and 1748 Three-Phase Power Quality Loggers
Troubleshoot, quantify energy usage and perform quality of service surveys easier than ever
The Fluke 1742, 1746 and 1748 Three-Phase Power Quality Loggers give you fast, easy access to the data you need to make critical power quality and energy decisions in real-time.
MEASURE ALL POWER QUALITY AND POWER PARAMETERS
1748 logs over 500 dif ferent parameters for each averaging period.
ONE-CLICK REPORTING
Create detailed reports according the most common power quality standards in seconds.
EASY TO USE
Auto-configuration check ensures every measurement campaign is right, the first time. Power the instrument from the measured line to simplify the connection process.
An optimized user interface, flexible current probes, and an intelligent measurement verification function that allows you to digitally verify and correct connections makes setup easier than ever and reduces measurement uncertainty. Minimize your time in potentially hazardous environments and reduce the hassle of suiting up in PPE by using a wireless connection (WiFi) to view data directly in the field.
.com
1.888.610.7664 info@Fluke-Direct.com
Hardware features
Fluke-Direct
Measure all three voltage and current
phases plus the neutral current: Three-phase
and neutral voltage leads and four flexible cur­rent probes.
Comprehensive logging: More than 20
separate logging sessions can be stored in the instrument. A comprehensive range of power and power quality variables are automatically logged so you never lose measurement trends.
Measure with premium accuracy: Meets the
rigorous IEC 61000-4-30 Class A Edition 3 standard for ‘Testing and measurement tech­niques—Power quality measurement methods.
Capture dips, swells and interruptions: The
1748 includes event waveform capture and RMS event profile, along with date, timestamp and severity information to help pinpoint potential root causes of power quality issues.
Measure key power quality parameters:
Measures harmonics and interharmonics for voltage and current, also includes unbalance, flicker and rapid voltage changes.
Optimized user interface: Capture the right
data every time with quick, guided, graphi­cal PC based application setup and reduce uncertainty about your connections with an intelligent verification feature and the only auto-correction function for a power quality logger. Connection errors are auto­matically indicated via an amber light on the units power button which turns green once corrected.
Flexible power supply: Powers directly from
the measured circuit with the widest available range for a power quality logger automatically going from 100 V to 500 V or from a wall line cord, so you can test anywhere.
Rugged and reliable: Designed to withstand
harsh installation environments with IP65 rating when used with IP65 voltage input adapter.
Two external USB ports: One for PC con-
nection and another for quick, simple data download to standard USB thumb drives, or other USB devices, allowing you to leave the measurement device in place without disrupt­ing logging.
Ethernet connectivity: Wired and wireless
connections for instrument setup and high­speed data download.
Compact size: Designed to fit in tight spaces
and panels with small 23cm x 18 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) footprint.
Highest safety rating in the industry: 600V
CAT IV/1000 V CAT III rated for use at the ser­vice entrance and downstream.
Optimized measurement accessories: Unique
tangle-free flat voltage cable and thin flexible current probes ensure easy installation even in tight spaces.
Battery life: Four-hour operating time (backup
time) per charge on lithium-ion battery to withstand temporary power disruptions.
Security: Safeguard your best asset from theft
with a standard chain or other security device.
Magnetic hanger kit: Conveniently stow the
instrument safely inside or outside of electri­cal panels; compatible with all models and included with 1748 model as standard.
2 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Harmonics Spectrum up to the 50th harmonic.
Fluke-Direct
Trend of the selec ted harmonic over time.
Detailed tabular view of every harmon ic.
Software features
“In-workshop“ or “in-the-field” setup
and download through PC application software: simple download using USB
memory stick, WiFi download, wired ether­net connection or via USB cable
Energy Analyze plus application soft-
ware: Download and analyze every
measured detail of energy consumption and power quality state-of-health with auto­mated reporting.
One touch reporting: Create standard-
ized reports according to commonly used standards like EN 50160, IEEE 519, GOST 33073 or export data in PQDIF or NeQual compatible format for use with third party software
Advanced analysis: Choose any available
logged parameter to create a highly cus­tomized view of logged measurements for advanced correlation of data
Applications
Measure all power quality and power parameters—Upgrades available
1742 174 6 174 8
Energy
Basic PQ Option
Advanced PQ Option Option
The Fluke 1748 logs over 500 different param­eters for each averaging period. This allows you to analyze power quality in detail and to correlate intermittent events with detailed waveform data, helping to identify the root cause of disturbances. For basic power quality logging, the Fluke 1746 captures all relevant power parameters for performing energy saving studies and electrical network planning with a full upgrade option to 1748 available. For simple load and energy stud­ies the Fluke 1742 offers optimal performance in a rugged package and can be upgraded to 1746 or complete 1748 functionality.
Calculates current harmonics limits
When downloading data from the Fluke 1748 Power Quality Loggers, Energy Analyze Plus, can calculate the limits of current harmonics based on installation parameters to predict overload of the grid according to a wide range of international standards. This powerful predictive maintenance feature enables current harmonics to be observed before distortion appears in the voltage allowing you to prevent unexpected failures or non-compli­ance situations and increase system uptime.
Easy to use
Fluke power quality loggers are designed with the technician in mind. The four current probes are each connected separately allowing flexibil­ity and simplicity, the instrument automatically detects, scales and powers the probes so you don’t have to worry about ensuring the measure­ments are correct.
3 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Connection verification function shows whether the instr ument is connected correctly
Fluke-Direct
and automatically corrects issues at the press of a button.
The thin current probes are designed to easily get through tight conductor spacing and include a wide range (from 1.5 A to 6000 A depending on selected probe) for high accuracy in each application. An innovative tangle-free, flat, volt­age lead makes connection simple and reliable. The instrument’s intelligent ‘Verify Connection’ feature which can be accessed using the PC Setup application automatically checks to make sure the instrument is connected correctly and can digitally correct connections without having to disconnect measurement leads. In the event of a connection error, the power button on the unit will turn from green to amber indicating that the connections should be verified before proceeding.
The loggers can also be conveniently and safely powered directly from the measured circuit (up to 500 V)—no more searching for power outlets or having to run multiple extension cords to the logging location, which is especially useful when logging at a remote site and when installing inside electrical panels.
Voltage and current trend g raph.
Calendar view shows hours, days, weeks as thumbnails for quick overviews.
Analysis and reporting
Capturing logged data is just one part of the task. Once you have the data, you need to create useful information and reports that can be easily shared and understood by your organization or custom­ers. Fluke Energy Analyze plus software makes that task as simple as possible. With powerful analysis tools and the ability to create customized reports in minutes you’ll be able to communicate your findings and quickly solve problems so you can optimize system reliability and savings. A range of built-in report templates for industry standards such as EN 50160, IEEE 519 and GOST enable one-click reporting so you can create high quality reports at the touch of a button. Reports can be modified as standards evolve, or new ver­sions become available.
The flexible data views quickly show details of the measurement file in easy to understand formats. The calendar view shown above enables hour/hour, day/day and week/week compari­sons simply by selecting the thumbnail views required. Each selected thumbnail is automati­cally detailed in the lower window.
4 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
IP65 Rated voltage connector (optional).
Fluke-Direct
Advanced data communication and software:
View real-time measurements wirelessly from outside the panel
or from your office using the included Fluke Energy Analyze plus software
Download logged files directly to a USB flash drive that plugs
directly into the USB port of the instrument or by wired or WiFi connection to your PC
The export function of Energy Analyze plus enables export of
one or more logged values with a simple parameter selector
Rugged and reliable
The 1740 series products are built to withstand tough work­ing environments. The flexible current probes are IP65 rated and suitable for most installation situations; the optional IP65 voltage adapter ensures safe, reliable operation even in harsh conditions. Standard 2 m (6.6 ft) leads simplify connection on difficult to access conductors, and optional 5 m (16.5 ft) leads are useful when installing in difficult locations. With the capability of powering the instruments from the power line up to 500 V, installation is as simple as can be.
Thoughtful design
Fluke prides itself on thoughtful design that’s why 1740 series power quality loggers include simple but effective accessories like the MA-C8 adapter making powering the instrument with a line cord easy when not in the field. Ports that aren’t always needed in the field are IP65 protected including the Ethernet, USB, AUX and I/O ports protecting for both moisture and dirt ingress. The status LEDs give a quick and clear indication of what the instrument is doing without having to touch any controls. Its compact size means that in most cases it will fit into the available space without any problems.
MA-C8 adapter for powering with line cord
Ether net and USB ports
5 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Specifications
Fluke-Direct
Accuracy
Parameter Range Max. Resolution Intrinsic accuracy at reference conditions
Voltage 1000 V 0.1 V ± 0.1 % of nominal voltage
Current i17xx-flex 1500IP 24” 1500 A 150 A
i17xx-flex 3000IP 24” 3000 A 300 A
i17xx-flex 6000IP 36” 6000 A 600 A
i40s-EL clamp 4 A
Frequency 42.5 Hz to 69 Hz 0.01 H z ± (0.1 %)
Aux input ± 10 V dc 0.1 mV ± (0.2 % + 0.02 %)
Voltage min/max 1000 V 0.1 V ± 0.2 % of nominal input voltage
Current min/max defined by accessor y defined by accessory ± (5 % + 0.2 %)
THD on voltage 1000 % 0.10 % ± 2.5 %
THD on current 1000 % 0.10 % ± 2.5 %
Voltage harmonics 2nd … 50th 1000 V 0.1 V ≥ 1 V: ± 5 % of reading
Current harmonics 2nd … 50th Defined by accessory Defined by accessory ≥ 3 % of current range: ± 5 % of reading
Flicker PLT, P
ST
150 0 A
3000 A
6000 A
40 A
0 to 20 0.01 5 %
0.01 A (min. 1.5A)3
0.1 A
0.01 A (min. 3.0 A)3
0.1 A
0.01 A (min. 6.0 A)3
0.1 A
1 mA 10 m A
(% of reading + % of range)
1, 2
± (1 % + 0.02 %) ± (1 % + 0.02 %)
± (1 % + 0.03 %) ± (1 % + 0.03 %)
± (1.5 % + 0.03 %) ± (1.5 % + 0.03 %)
± (0.7 % + 0.02 %) ± (0.7 % + 0.02 %)
2
1
< 1 V: ± 0.05 V
< 3 % of current range: ± 0.15 % of range
Parameter Influence
Active Power P Active Energy Ea
Apparent Power S Apparent Energy Eap
Reactive Power Q Reactive Energy Er
Power Factor PF Displacement Power FactorDPF/cosφ
Additional uncertainty in % of range
1) In the range of 100 V … 500 V; also known as Udin
2) 0 °C … 45 °C: Int rinsic accuracy x 2, outside of 0 °C … 45 °C: Intrinsic accuracy x 3
3) Consult operators manual for details
Reference conditions:
Environmental: 23 °C ± 5 °C, inst rument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 %
Input conditions: Cos
Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V
Input current: I > 10 % of I range
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
φ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %.
quantity
PF ≥ 0.99 1.2 %
0 ≤ PF ≤ 1 1.2 %
0 ≤ PF ≤ 1 2.5 % of measured apparent power
- ± 0.025
VP-N > 250 V 0.015 % 0.023 % 0.023 % 0.015 %
iFlex1500IP-24 150A/1500A
+ 0.005 %
+ 0.005 %
iFlex3000IP-24 300A/3000A
1.2 % + 0.0075%
1.2 % + 0.0075%
iFlex6000IP-36 600/6000A
1.7 % + 0.0075 %
1.7 % + 0.0075 %
i40s-EL 4A/40 A
1.2 % + 0.005 %
1.2 % + 0.005 %
6 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Electrical specifications
Fluke-Direct
Power supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency ≥ 68.2 % (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ± 15 %
Battery Li-ion 3.7 V, 9.2 Wh, customer-replaceable
On-battery runtime Typically 4 hours
Charging time < 6 hours
Data acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-φ, 1- φ IT, split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel
Data storage Internal flash memory (not user replaceable)
Memory size Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Basic interval
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF,
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC 61000-4-30
Demand interval (Energy Meter Mode)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power quality measurements
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, volt-
Averaging interval 10 min for all parameters
Individual harmonics 2nd to 50th harmonic
Interharmonics 1st to the 50th interharmonic Total harmonic distortion Calculated on 50 voltage harmonics Events Voltage: dips, swells, interruptions, current: inrush current
Triggered recordings RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s
Inrush RMS profile based on 1/2 cycle RMS steady state triggering Flicker In accordance with IEC 61000-4-15 and IEEE 1453 Mains signaling Two user defined frequencies up to 3 kHz PQ Health Summarizes power quality measurements in one table. Detailed data available for each parameter EN 50160 Compliance with standard Programmable PQ limits Enables user defined limits for local standards compliance
(2-element delta), 3-φ delta open leg, currents only (load studies)
energy
Aux, Power: 200 ms)
age interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
2 hrs (long term Flicker 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
1748: mains signaling, transients (low frequency)
(URMS1/2 according to IEC 61000-4-30) Waveform of voltage and current up to 200 ms, 10/12 cycles Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s
P
)
LT
7 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Electrical specifications cont.
Fluke-Direct
Standards compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time and very short time harmonics)
Power quality IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
Power IEEE 1459
Power quality compliance EN 50160
Safety General: IEC 61010-1: Pollution Degree 2
USB-A File transfer via USB flash drive, firmware updates, max. supply current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect® 3000 series modules
USB-mini-B Data download device to PC
Voltage inputs
Number of inputs 4 (3 phases referenced to neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 M Ω
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Current inputs
Number of inputs 4 (3 phases and neutral), mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Range 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24”
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Auxiliary inputs
Number of inputs 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input range 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s
Scale factor Format: mx + b (gain and offset) user configurable
Displayed units User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Bluetooth connection (check for availability)
Number of inputs 2
Supported modules Fluke Connect® 3000 series
Acquisition 1 reading/s
Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V Power Supply: Overvoltage Category IV, Pollution Degree 2 Li-ion Battery: IEC 62133
(requires supported USB to BLE or WiFi/BLE adapter, check for availability)
Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24” 6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36” 40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
8 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Environmental specifications
Fluke-Direct
Operating temperature -25 °C to +50 °C (-13 °F to 122 °F)
Storage temperature Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with batter y: -20 °C to +50 °C (−4 °F to 122 °F)
Operating humidity IEC 60721-3-3: 3K6:
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000 m
Enclosure IEC 60529: IP50
Vibration IEC 60721-3-3 / 3M2
Electromagnetic compatibility (EMC)
General specifications
Warranty Two-years (battery not included)
Dimensions 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in)
Weight Instrument: 1 kg (2.2 lb)
Tamper protection Accept securing cables (max. φ 6mm)
1
Warm up t he product to -10 °C (+14 °F) before you power t he unit on
-25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 % 40 °C (104 °F): 55 % 50 °C (122 °F): 35 %
IEC 60529: IP65 with IP65 rated voltage connector
EN 61326-1: Industrial CISPR 11: Group 1, Class A IEC 61000-6-5 Power station environment Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Accessories: one-year Calibration cycle: two-years
1
Flexible Current Probe specifications
Measuring ranges 1 to 150 A ac
Probe cable length 610 mm (24 in) 610 mm (24 in) 915 mm (36 in)
Probe cable diameter 7.5 mm (0.3 in) 7.5 mm (0.3 in) 7.5 mm (0.3 in)
Weight 170 g (0.38 lb) 170 g (0.38 lb) 190 g (0.42 lb)
Minimum bending radius 38 mm (1.5 in)
Nondestructive current 100 kA (50/60 Hz)
Temperature coefficient over operating temperature range
Working voltage 1000 V CAT III, 600 V CAT IV
Output cable length 2.5 m (8.2 ft)
Probe cable material TPR
Coupling material POM + ABS/PC
Output cable TPR/PVC
Operating temperature -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating 15 % to 85 % non-condensing
IP rating IEC 60529: IP65
Warranty One-year
i17XX- FLEX1.5 K I P i17XX-FLEX3KIP i17X X - F L E X 6 K I P
10 to 1500 A ac
0.05 % of reading/°C (0.028 % of reading/°F)
1 to 300 A ac 10 to 3000 A ac
1 to 600 A ac 10 to 6000 A ac
9 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Model features
Fluke-Direct
1742 Power
Quality Loggers
1746 Power
Quality Loggers
1748 Power
Quality Loggers
Functions
Voltage, current, power, power factor, frequency
Energy forward/reverse
Peak Demand
THD
Voltage and current harmonics (to 50th)
1
Flicker
Unbalance
Rapid voltage change events
Interharmonics (to 50th)
1
1
1
Dips, swells, interruption and transient events tables
Mains signaling
Inrush current
1
1
Transients (low frequency)/Waveform deviation events
1
2
Recording
Trend
Waveform snapshots
RMS profile
2
2
Communication
Ethernet
USB (mini B)
WiFi download Instrument to device
Wifi download via WiFi hub (requires registration) Opt. Opt. Opt.
Included accessories
Flexible current probe not /B version not /B version not /B version
USB stick
USB cable
3PHVL-1730 3-Phase + neutral voltage test lead
Test lead set red/black 0.18 m
Test lead set red/black 1.5 m
Alligator clips 4 4 4
173 x /174 x S o f t C a s e
Cable marker kit
MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black) Opt. 1 1
174x-Hanger Kit Opt. Opt.
1
Included with 1742-6/UPGRADE option
2
Included wit h 1742-8/UPGRADE or 1746-8/UPGRA DE option
10 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Optional accessories
Fluke-Direct
Item Description
1742-6/UPGRADE Upgrade 1742 to 1746 functionality (includes magnetic probes)
1742-8/UPGRADE Upgrade 1742 to 1748 functionality (includes magnetic probes and hanger kit)
1746-8/UPGRADE Upgrade 1746 to 1748 functionality (includes hanger kit)
IEEE519/REPORT Software license for IEEE 519 reporting
3PHVL-1730-5M Cable Assembly, voltage test lead 3-phase+N 5M
i17XX-FLEX1.5KIP FLUKE-17XX IP65 iFlex 1.5KA 24 IN/60CM
i17XX-FLEX1.5KIP/3PK FLUKE-17XX IP65 iFlex 1.5KA 24 IN/60CM, 3 pack
i17XX-FLEX1.5KIP/4PK FLUKE-17XX IP65 iFlex 1.5KA 24IN/60CM, 4 pack
i17XX-FLEX3KIP FLUKE-17XX IP65 iFlex 3KA 24 IN/60CM
i17XX-FLEX3KIP/3PK FLUKE-17XX IP65 iFlex 3KA 24 IN/60CM, 3 pack
i17XX-FLEX3KIP/4PK FLUKE-17XX IP65 iFlex 3KA 24 IN/60CM, 4 pack
i17XX-FLEX6KIP FLUKE-17XX IP65 iFlex 6KA 36 IN/90CM
i17XX-FLEX6KIP/3PK FLUKE-17XX IP65 iFlex 6KA 36 IN/90CM, 3 pack
i17XX-FLEX6KIP/4PK FLUKE-17XX IP65 iFlex 6KA 36 IN/90CM, 4 pack
i17XX-FLEX5M-EXT FLUKE-17XX IFLEX Extension Cable 5M
i40S-EL FLUKE-1730 I40S-EL Clamp-On Current Transformer
i40S-EL/3pk FLUKE-17XX I40S-EL Clamp-On Current Transformer, 3 pack
IP65 VOLT CONN IP65 Rated Voltage Connector
FLU K E -17X X AU X Auxiliary Input Adapter, 17XX
FLUKE-17XX-TL 0.18M Test Lead Set; 1000 V CAT III, non-stack conn; 0.18m; red/blk
FLUKE-MA-C8 IEC 60320 C7 Line Power Cord to 4 mm plugs
FTP165X / U K Fused Probe Set for 165x/uk,red/blu/grn
MP1-3R/1B Magnet Probe 1, 3 x red, 1 x black
FLUKE-174X GPS-REC GPS Receiver Antenna
F17XX CABLE MARKERS Cable Marker Kit For 174X
11 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Ordering information
Fluke-Direct
Standard accessories per model
Model WiFi/BLE Adapter* i17XX-flex1500 24”
FLUKE-1742/15/EUS
FLU K E -1742/30/EUS
FLU K E -1742/ B/ E U S
FLUKE-1742/15/INTL EU/US/UK/CN-AUS/BR
FLU K E -1742/30/I N T L EU/US/UK/CN-AUS/BR
FLUKE-1742/B/INTL EU/US/UK/CN-AUS/BR
FLU K E -174 6 /15/EUS
FLU K E -174 6 /30/E U S EU/US/UK
FLUKE-1746/B/EUS
FLU K E -174 6 /15/I N T L EU/US/UK/CN-AUS/BR
FLU K E -174 6 /30/I N T L EU/US/UK/CN-AUS/BR
FLUKE-1746/B/INTL EU/US/UK/CN-AUS/BR
FLU K E -174 8 /15/E U S EU/US/UK
FLU K E -174 8 / 3 0/ E U S
FLU K E -174 8 / B / E US
FLU K E -174 8 /15/I N T L EU/US/UK/CN-AUS/BR
FLU K E -174 8 / 3 0/ I N TL EU/US/UK/CN-AUS/BR
FLUKE-1748/B/INTL EU/US/UK/CN-AUS/BR
Current Probe (x4)
EU/US/UK
EU/US/UK
i17XX-flex3000 24”
Current Probe (x4)
EU/US/UK
EU/US/UK
Power Cords supplied with MA-C8 adapter
EU/US/UK
EU/US/UK
EU/US/UK
* The WiFi/BLE adapter enables connection to WiFi networks and devices. Connections can be made directly from laptop or WiFi network for direct downloading of data.