1742, 1746 and 1748 Three-Phase
Power Quality Loggers
Troubleshoot, quantify energy usage and perform
quality of service surveys easier than ever
The Fluke 1742, 1746 and 1748 Three-Phase Power Quality
Loggers give you fast, easy access to the data you need to make
critical power quality and energy decisions in real-time.
Compact and rugged, the Fluke 1740 Series Three-Phase Power
Quality Loggers are designed specifically for technicians and
engineers who need the flexibility to troubleshoot, quantify
energy usage and analyze power distribution systems. Fully
compliant with international power quality standards such as
IEC 61000-4-30 and capable of simultaneously logging up to 500
parameters while also capturing events, the Fluke 1740 Series
helps uncover intermittent and hard-to-find power quality issues
more easily than ever. The included Energy Analyze plus software
quickly assesses the quality of power at the service entrance,
substation, or at the load, according to national and international
standards like EN 50160 and IEEE 519.
MEASURE ALL POWER QUALITY AND
POWER PARAMETERS
1748 logs over 500 dif ferent parameters for
each averaging period.
ONE-CLICK REPORTING
Create detailed reports according the
most common power quality standards
in seconds.
EASY TO USE
Auto-configuration check ensures every
measurement campaign is right, the
first time. Power the instrument from the
measured line to simplify the connection
process.
An optimized user interface, flexible current probes, and an
intelligent measurement verification function that allows you to
digitally verify and correct connections makes setup easier than
ever and reduces measurement uncertainty. Minimize your time in
potentially hazardous environments and reduce the hassle of
suiting up in PPE by using a wireless connection (WiFi) to view
data directly in the field.
.com
1.888.610.7664 info@Fluke-Direct.com
Hardware features
Fluke-Direct
• Measure all three voltage and current
phases plus the neutral current: Three-phase
and neutral voltage leads and four flexible current probes.
• Comprehensive logging: More than 20
separate logging sessions can be stored in the
instrument. A comprehensive range of power
and power quality variables are automatically
logged so you never lose measurement trends.
• Measure with premium accuracy: Meets the
rigorous IEC 61000-4-30 Class A Edition 3
standard for ‘Testing and measurement techniques—Power quality measurement methods.
• Capture dips, swells and interruptions: The
1748 includes event waveform capture and
RMS event profile, along with date, timestamp
and severity information to help pinpoint
potential root causes of power quality issues.
• Measure key power quality parameters:
Measures harmonics and interharmonics for
voltage and current, also includes unbalance,
flicker and rapid voltage changes.
• Optimized user interface: Capture the right
data every time with quick, guided, graphical PC based application setup and reduce
uncertainty about your connections with
an intelligent verification feature and the
only auto-correction function for a power
quality logger. Connection errors are automatically indicated via an amber light on the
units power button which turns green once
corrected.
•Flexible power supply: Powers directly from
the measured circuit with the widest available
range for a power quality logger automatically
going from 100 V to 500 V or from a wall line
cord, so you can test anywhere.
•Rugged and reliable: Designed to withstand
harsh installation environments with IP65
rating when used with IP65 voltage input
adapter.
•Two external USB ports: One for PC con-
nection and another for quick, simple data
download to standard USB thumb drives, or
other USB devices, allowing you to leave the
measurement device in place without disrupting logging.
•Ethernet connectivity: Wired and wireless
connections for instrument setup and highspeed data download.
• Compact size: Designed to fit in tight spaces
and panels with small 23cm x 18 cm x 5.4 cm
(9.1 in x 7.1 in x 2.1 in) footprint.
•Highest safety rating in the industry: 600V
CAT IV/1000 V CAT III rated for use at the service entrance and downstream.
• Optimized measurement accessories: Unique
tangle-free flat voltage cable and thin flexible
current probes ensure easy installation even in
tight spaces.
• Battery life: Four-hour operating time (backup
time) per charge on lithium-ion battery to
withstand temporary power disruptions.
• Security: Safeguard your best asset from theft
with a standard chain or other security device.
• Magnetic hanger kit: Conveniently stow the
instrument safely inside or outside of electrical panels; compatible with all models and
included with 1748 model as standard.
2 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Harmonics Spectrum up to the 50th harmonic.
Fluke-Direct
Trend of the selec ted harmonic over time.
Detailed tabular view of every harmon ic.
Software features
• “In-workshop“ or “in-the-field” setup
and download through PC application
software: simple download using USB
memory stick, WiFi download, wired ethernet connection or via USB cable
• Energy Analyze plus application soft-
ware: Download and analyze every
measured detail of energy consumption and
power quality state-of-health with automated reporting.
•One touch reporting: Create standard-
ized reports according to commonly used
standards like EN 50160, IEEE 519, GOST
33073 or export data in PQDIF or NeQual
compatible format for use with third party
software
• Advanced analysis: Choose any available
logged parameter to create a highly customized view of logged measurements for
advanced correlation of data
Applications
Measure all power quality and power
parameters—Upgrades available
1742174 6174 8
Energy
Basic PQOption
Advanced PQOptionOption
The Fluke 1748 logs over 500 different parameters for each averaging period. This allows you
to analyze power quality in detail and to correlate
intermittent events with detailed waveform data,
helping to identify the root cause of disturbances.
For basic power quality logging, the Fluke 1746
captures all relevant power parameters for
performing energy saving studies and electrical
network planning with a full upgrade option to
1748 available. For simple load and energy studies the Fluke 1742 offers optimal performance in
a rugged package and can be upgraded to 1746
or complete 1748 functionality.
Calculates current harmonics limits
When downloading data from the Fluke 1748
Power Quality Loggers, Energy Analyze Plus, can
calculate the limits of current harmonics based on
installation parameters to predict overload of the
grid according to a wide range of international
standards. This powerful predictive maintenance
feature enables current harmonics to be observed
before distortion appears in the voltage allowing
you to prevent unexpected failures or non-compliance situations and increase system uptime.
Easy to use
Fluke power quality loggers are designed with
the technician in mind. The four current probes
are each connected separately allowing flexibility and simplicity, the instrument automatically
detects, scales and powers the probes so you
don’t have to worry about ensuring the measurements are correct.
•••
••
•
3 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Connection verification function shows whether the instr ument is connected correctly
Fluke-Direct
and automatically corrects issues at the press of a button.
The thin current probes are designed to easily
get through tight conductor spacing and include
a wide range (from 1.5 A to 6000 A depending
on selected probe) for high accuracy in each
application. An innovative tangle-free, flat, voltage lead makes connection simple and reliable.
The instrument’s intelligent ‘Verify Connection’
feature which can be accessed using the PC
Setup application automatically checks to make
sure the instrument is connected correctly and
can digitally correct connections without having
to disconnect measurement leads. In the event of
a connection error, the power button on the unit
will turn from green to amber indicating that the
connections should be verified before proceeding.
The loggers can also be conveniently and safely
powered directly from the measured circuit (up
to 500 V)—no more searching for power outlets
or having to run multiple extension cords to the
logging location, which is especially useful when
logging at a remote site and when installing
inside electrical panels.
Voltage and current trend g raph.
Calendar view shows hours, days, weeks as thumbnails for
quick overviews.
Analysis and reporting
Capturing logged data is just one part of the task.
Once you have the data, you need to create useful
information and reports that can be easily shared
and understood by your organization or customers. Fluke Energy Analyze plus software makes
that task as simple as possible. With powerful
analysis tools and the ability to create customized
reports in minutes you’ll be able to communicate
your findings and quickly solve problems so you
can optimize system reliability and savings. A
range of built-in report templates for industry
standards such as EN 50160, IEEE 519 and GOST
enable one-click reporting so you can create high
quality reports at the touch of a button. Reports
can be modified as standards evolve, or new versions become available.
The flexible data views quickly show details
of the measurement file in easy to understand
formats. The calendar view shown above enables
hour/hour, day/day and week/week comparisons simply by selecting the thumbnail views
required. Each selected thumbnail is automatically detailed in the lower window.
4 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
IP65 Rated voltage connector (optional).
Fluke-Direct
Advanced data communication and software:
• View real-time measurements wirelessly from outside the panel
or from your office using the included Fluke Energy Analyze plus
software
• Download logged files directly to a USB flash drive that plugs
directly into the USB port of the instrument or by wired or WiFi
connection to your PC
• The export function of Energy Analyze plus enables export of
one or more logged values with a simple parameter selector
Rugged and reliable
The 1740 series products are built to withstand tough working environments. The flexible current probes are IP65 rated and
suitable for most installation situations; the optional IP65 voltage
adapter ensures safe, reliable operation even in harsh conditions.
Standard 2 m (6.6 ft) leads simplify connection on difficult to
access conductors, and optional 5 m (16.5 ft) leads are useful when
installing in difficult locations. With the capability of powering
the instruments from the power line up to 500 V, installation is as
simple as can be.
Thoughtful design
Fluke prides itself on thoughtful design that’s why 1740 series
power quality loggers include simple but effective accessories like
the MA-C8 adapter making powering the instrument with a line
cord easy when not in the field. Ports that aren’t always needed in
the field are IP65 protected including the Ethernet, USB, AUX and
I/O ports protecting for both moisture and dirt ingress. The status
LEDs give a quick and clear indication of what the instrument is
doing without having to touch any controls. Its compact size means
that in most cases it will fit into the available space without any
problems.
MA-C8 adapter for powering with
line cord
Ether net and USB ports
5 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Specifications
Fluke-Direct
Accuracy
ParameterRangeMax. ResolutionIntrinsic accuracy at reference conditions
Voltage 1000 V 0.1 V ± 0.1 % of nominal voltage
Currenti17xx-flex 1500IP 24” 1500 A150 A
i17xx-flex 3000IP 24” 3000 A300 A
i17xx-flex 6000IP 36” 6000 A600 A
i40s-EL clamp4 A
Frequency 42.5 Hz to 69 Hz 0.01 H z± (0.1 %)
Aux input ± 10 V dc 0.1 mV± (0.2 % + 0.02 %)
Voltage min/max 1000 V 0.1 V ± 0.2 % of nominal input voltage
Current min/max defined by accessor ydefined by accessory± (5 % + 0.2 %)
THD on voltage1000 %0.10 %± 2.5 %
THD on current 1000 %0.10 %± 2.5 %
Voltage harmonics 2nd … 50th1000 V 0.1 V≥ 1 V: ± 5 % of reading
Current harmonics 2nd … 50thDefined by accessory Defined by accessory ≥ 3 % of current range: ± 5 % of reading
Flicker PLT, P
ST
150 0 A
3000 A
6000 A
40 A
0 to 200.015 %
0.01 A (min. 1.5A)3
0.1 A
0.01 A (min. 3.0 A)3
0.1 A
0.01 A (min. 6.0 A)3
0.1 A
1 mA
10 m A
(% of reading + % of range)
1, 2
± (1 % + 0.02 %)
± (1 % + 0.02 %)
± (1 % + 0.03 %)
± (1 % + 0.03 %)
± (1.5 % + 0.03 %)
± (1.5 % + 0.03 %)
± (0.7 % + 0.02 %)
± (0.7 % + 0.02 %)
2
1
< 1 V: ± 0.05 V
< 3 % of current range: ± 0.15 % of range
Parameter Influence
Active Power P
Active Energy Ea
Apparent Power S
Apparent Energy Eap
Reactive Power Q
Reactive Energy Er
Power Factor PF
Displacement Power
FactorDPF/cosφ
Additional uncertainty
in % of range
1) In the range of 100 V … 500 V; also known as Udin
2) 0 °C … 45 °C: Int rinsic accuracy x 2, outside of 0 °C … 45 °C: Intrinsic accuracy x 3
3) Consult operators manual for details
Reference conditions:
Environmental: 23 °C ± 5 °C, inst rument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 %
Input conditions: Cos
Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V
Input current: I > 10 % of I range
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
φ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %.
quantity
PF ≥ 0.99 1.2 %
0 ≤ PF ≤ 1 1.2 %
0 ≤ PF ≤ 1 2.5 % of measured apparent power
- ± 0.025
VP-N > 250 V0.015 %0.023 %0.023 %0.015 %
iFlex1500IP-24
150A/1500A
+ 0.005 %
+ 0.005 %
iFlex3000IP-24
300A/3000A
1.2 %
+ 0.0075%
1.2 %
+ 0.0075%
iFlex6000IP-36
600/6000A
1.7 %
+ 0.0075 %
1.7 %
+ 0.0075 %
i40s-EL
4A/40 A
1.2 %
+ 0.005 %
1.2 %
+ 0.005 %
6 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Electrical specifications
Fluke-Direct
Power supply
Voltage range100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
Power consumptionMaximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency≥ 68.2 % (in accordance with energy efficiency regulations)
Maximum no-load consumption< 0.3 W only when powered using IEC 60320 input
Mains power frequency50/60 Hz ± 15 %
BatteryLi-ion 3.7 V, 9.2 Wh, customer-replaceable
On-battery runtimeTypically 4 hours
Charging time< 6 hours
Data acquisition
Resolution16-bit synchronous sampling
Sampling frequency10.24 kHz at 50/60 Hz, synchronized to mains frequency
Measured parameterVoltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, volt-
Averaging interval10 min for all parameters
Individual harmonics2nd to 50th harmonic
Interharmonics1st to the 50th interharmonic
Total harmonic distortionCalculated on 50 voltage harmonics
EventsVoltage: dips, swells, interruptions, current: inrush current
Triggered recordingsRMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s
InrushRMS profile based on 1/2 cycle RMS steady state triggering
Flicker In accordance with IEC 61000-4-15 and IEEE 1453
Mains signalingTwo user defined frequencies up to 3 kHz
PQ HealthSummarizes power quality measurements in one table. Detailed data available for each parameter
EN 50160Compliance with standard
Programmable PQ limitsEnables user defined limits for local standards compliance
(2-element delta), 3-φ delta open leg, currents only (load studies)
energy
Aux, Power: 200 ms)
age interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over
deviation
2 hrs (long term Flicker
150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Grouping according to IEC 61000-4-7 user configurable depending on application:
Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
1748: mains signaling, transients (low frequency)
(URMS1/2 according to IEC 61000-4-30)
Waveform of voltage and current up to 200 ms, 10/12 cycles
Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s
P
)
LT
7 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Electrical specifications cont.
Fluke-Direct
Standards compliance
HarmonicsIEC 61000-4-7: Class 1
IEEE 519 (short time and very short time harmonics)
Power qualityIEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
PowerIEEE 1459
Power quality complianceEN 50160
SafetyGeneral: IEC 61010-1: Pollution Degree 2
USB-AFile transfer via USB flash drive, firmware updates, max. supply current: 120 mA
WiFiFile transfer and remote control via direct connection or WiFi infrastructure
BluetoothRead auxiliary measurement data from Fluke Connect® 3000 series modules
USB-mini-BData download device to PC
Voltage inputs
Number of inputs4 (3 phases referenced to neutral)
Maximum input voltage1000 Vrms, CF 1.7
Input impedance10 M Ω
Bandwidth42.5 Hz to 3.5 kHz
Scaling1:1 and variable
Measurement category1000 V CAT III/600 V CAT IV
Current inputs
Number of inputs4 (3 phases and neutral), mode selected automatically for attached sensor
Range1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24”
Bandwidth42.5 Hz to 3.5 kHz
Scaling1:1 and variable
Auxiliary inputs
Number of inputs2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input range0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s
Scale factorFormat: mx + b (gain and offset) user configurable
Displayed unitsUser configurable (7 characters, for example, °C, psi, or m/s)
Wireless Bluetooth connection (check for availability)
Number of inputs2
Supported modulesFluke Connect® 3000 series
Acquisition1 reading/s
Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V
Power Supply: Overvoltage Category IV, Pollution Degree 2
Li-ion Battery: IEC 62133
(requires supported USB to BLE or WiFi/BLE adapter, check for availability)
Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4
all at nominal probe range
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24”
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36”
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
8 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Environmental specifications
Fluke-Direct
Operating temperature-25 °C to +50 °C (-13 °F to 122 °F)
Storage temperatureWithout battery: -25 °C to +60 °C (-13 °F to 140 °F), with batter y: -20 °C to +50 °C (−4 °F to 122 °F)
Operating humidityIEC 60721-3-3: 3K6:
Operating altitude2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude12,000 m
Enclosure IEC 60529: IP50
VibrationIEC 60721-3-3 / 3M2
Electromagnetic compatibility
(EMC)
General specifications
WarrantyTwo-years (battery not included)
Dimensions23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in)
Warm up t he product to -10 °C (+14 °F) before you power t he unit on
-25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 %
40 °C (104 °F): 55 %
50 °C (122 °F): 35 %
IEC 60529: IP65 with IP65 rated voltage connector
EN 61326-1: Industrial CISPR 11: Group 1, Class A
IEC 61000-6-5 Power station environment
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
i40S-ELFLUKE-1730 I40S-EL Clamp-On Current Transformer
i40S-EL/3pkFLUKE-17XX I40S-EL Clamp-On Current Transformer, 3 pack
IP65 VOLT CONNIP65 Rated Voltage Connector
FLU K E -17X X AU XAuxiliary Input Adapter, 17XX
FLUKE-17XX-TL 0.18M Test Lead Set; 1000 V CAT III, non-stack conn; 0.18m; red/blk
FLUKE-MA-C8IEC 60320 C7 Line Power Cord to 4 mm plugs
FTP165X / U KFused Probe Set for 165x/uk,red/blu/grn
MP1-3R/1BMagnet Probe 1, 3 x red, 1 x black
FLUKE-174X GPS-RECGPS Receiver Antenna
F17XX CABLE MARKERSCable Marker Kit For 174X
11 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Ordering information
Fluke-Direct
Standard accessories per model
ModelWiFi/BLE Adapter*i17XX-flex1500 24”
FLUKE-1742/15/EUS
FLU K E -1742/30/EUS
FLU K E -1742/ B/ E U S
FLUKE-1742/15/INTL• EU/US/UK/CN-AUS/BR
FLU K E -1742/30/I N T L• EU/US/UK/CN-AUS/BR
FLUKE-1742/B/INTLEU/US/UK/CN-AUS/BR
FLU K E -174 6 /15/EUS
FLU K E -174 6 /30/E U S• • EU/US/UK
FLUKE-1746/B/EUS
FLU K E -174 6 /15/I N T L• EU/US/UK/CN-AUS/BR
FLU K E -174 6 /30/I N T L•EU/US/UK/CN-AUS/BR
FLUKE-1746/B/INTLEU/US/UK/CN-AUS/BR
FLU K E -174 8 /15/E U S• • EU/US/UK
FLU K E -174 8 / 3 0/ E U S
FLU K E -174 8 / B / E US
FLU K E -174 8 /15/I N T L•EU/US/UK/CN-AUS/BR
FLU K E -174 8 / 3 0/ I N TL•EU/US/UK/CN-AUS/BR
FLUKE-1748/B/INTLEU/US/UK/CN-AUS/BR
•
•
•
•
•
•
•
Current Probe (x4)
• EU/US/UK
• EU/US/UK
i17XX-flex3000 24”
Current Probe (x4)
• EU/US/UK
• EU/US/UK
Power Cords
supplied with
MA-C8 adapter
EU/US/UK
EU/US/UK
EU/US/UK
* The WiFi/BLE adapter enables connection to WiFi networks and devices. Connections can
be made directly from laptop or WiFi network for direct downloading of data.
12 Fluke Corporation 1742, 1746 and 1748 Three-Phase Power Quality Loggers
.com
1.888.610.7664 info@Fluke-Direct.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.