This guide provides a quick reference to field set-up of the trip point and span of the FS10A flow monitor on units not pre-calibrated at the factory to
specific application parameters. The available PC or command line interface through the RS232 provides the most comprehensive means of setting
up the FS10A flow monitor (refer to operating manual for complete instructions). If that is not feasible, the buttons with LED feedback provide access
to all required functions for field set-up.
FS10 Button Controls
General Control Description
The FS10 control “functions” can be accessed through the two buttons by:
1. Entering “function selection”
2. Selecting the desired function to adjust
3. Adjusting the function control
4. Exiting to normal operation
1. To Enter “Function Selection” mode:
a. Press and hold both buttons down for 3 seconds
b. When “function selection” is entered, all the LEDs will flash “on”, then
c. The first function (LED # 1) will be illuminated
2. “Function Selection” mode:
Once the unit is in “function selection” mode, the buttons take on new controls:
• The “-“ and “+” buttons will step (increment down or up respectively) through the different functions. The current function number will be
indicated on the LED blinking at the slow rate.
• Holding either the “+” or “-“ for 3 seconds will “select” the current function to be adjusted.
3. When a Function has been selected for adjustment:
After selecting the desired function by pushing and holding either the “-” or “+” button for 3 seconds the LEDs will flash at a faster rate. The
pattern of the LEDs will either reflect the current value of the parameter being adjusted, or the “ready to capture” pattern for parameters to be
captured (see specific function descriptions for details).
The buttons will either increment or decrement the function parameter, or capture a value for the corresponding parameter.
4. To exit out of the current function, push and hold both buttons down for 3 seconds. The LEDs will indicate that you are once again in “function
election” mode, and the current mode will have incremented to the next function. To exit completely (into operational mode), press the two
buttons simultaneously for 3 seconds once again.
Note: Function #4 (load a bank) and function #15 (save to a bank), requires holding either button for 3 seconds to load or save.
Holding both buttons will exit either function without performing the operation.
Button Operation
1Enter “function selection”Push and hold both buttons simultaneously 3 seconds
2Select desired “function”Push “+” or “-“ to step through (LEDs indicate function #)
3a.Enter “function adjust”Push and hold either “-“ or “+” button 3 seconds
3b.Adjust within functionFollow instructions for particular function entry
4a.Exit “function adjust”Push and hold either “-” or “+” button 3 seconds (now in “function selection” opera-
tion)
[NOTE: Function #4 or #15 requires holding both buttons to exit into function select
operation]
4b.Exit “function selection”Push and hold both buttons simultaneously 3 seconds (now in normal operation)
Fluid Components International LLC 06EN003398 Rev. B
Bank Selection of Stored Parameters
The FS10A has 7 storage banks. Banks 1-6 are factory set defaults of common applications or specific factory calibrations. Bank 7 is available for
user saved parameters. Bank 0 is always the “operating” bank. Function 4 is used to move parameters from a selected bank to operational Bank 0.
Function 15 is used to store new field set-up parameters into Bank 7 for future retrieval.
Un-calibrated units are shipped with default parameters from Bank 1 active in the 0 Bank. The parameters permit operation over the entire range of
the meter as it may be applied to any gas or liquid.
Recommended Set-up Order
1. Scale the FS10A over the desired flow range — Adjustment of flow over useable range is recommended if possible. This span setting will be
reflected on the LEDs (1-10) as well as the 4-20 mA output (0% - 100%). If it is impossible to throttle the flow, it is recommended a span be
established initially with normal flow, then use the LEDs to set a trip-point below that value for low flow alarm. Dynamic Mode, FUNCTION 5,
automatically establishes the highest flow rate as the span and could be considered to aid in setup in these cases. Refer to Operating Manual
for complete instructions on using Dynamic Mode.
a. Set the Zero using Button FUNCTION 6 (no-flow full tube is suggested in liquid service) to capture the zero point.
b. Set the Span using Button FUNCTION 7. Capture this setting while simulating highest flow rate in the tube.
2. Set the trip point using either method below:
a. 10% increment method, Button FUCNTION 1, allows setting against the 10 LEDs on the display. Each LED represents 10% of the flow
range established in 1. Flashing LED confirms value of trip point.
b. Capture method, Button FUNCTION 2, allows setting the trip-point at precisely the flow rate through the tube at the time of capture.
Flashing LED indicates approximate value of trip point.
3. Final adjustments
a. Set Failsafe using Button FUNCTION 3; relay normally activated above trip point (default condition) or below trip point.
b. Other settings are available through the buttons if required, including hysteresis, time delay and filtering. Refer to the Operating Manual
for complete descriptions. After all adjustments are finalized, the new settings now in operational Bank 0 may be saved to Bank 7, 8 or 9
using Button FUNCTION 15.
Bank Default Values
Bank No.
0FS10 Current Active Parameters
1Universal Default Setting A - Low flow
sensitivity
2Air/Gas -40 °F to 250 °F (1/4 ″ tube and SP76
adapter)
3Universal Setting B - High flow gas,
liquids
4Water/Glycol -40 °F to 250 °F
Process FluidRange Setting
Un-calibrated output - low sensor excitation power setting
Full range gas or liquid
1 SFPS to 50 SFPS (200 cc/min to 10,000 cc/min, [0.4 SCFH to 20 SCFH] in
1/4 “ tube) – trend accuracy 10% full scale
Un-calibrated output – 1.5X sensor excitation power setting
Full range liquid and gas
0.02 SFPS to 0.5 SFPS (4 cc/min to 100 cc/min [0.001 GPM to 0.03 GPM] in
1/4” tube) – trend accuracy 10% full scale
5Reserved for custom calibration
6Reserved for custom calibration
7User defined and stored
Fluid Components International LLC 06EN003398 Rev. B
0 = LED off, 1 = LED on
Function #Function
Name
1
2
3Failsafe
4
Trip Point
Adjust
Trip Point
Capture
Bank
Selection
of Stored
Parameters
Button Controls
LED PatternParameter
1000000000
- +
1100000000
- +
1110000000
- +
1111000000
- +
RELAY_LIMIT
RELAY_LIMIT
RELAY_POLAR
CAL_DATA_INDEX
LED Pattern for
Parameter
1 – indicates current
value relative to full
scale
1 – indicates current
value relative to full
scale
0000011111 = “on”
above (default)
1111100000 = “on”
below
1 – indicates current
index (1..7)
Description
Button controls adjust relay trip point in
10% increments.
When entering this function the “ready
to capture” LED pattern will be presented
(0101010101). Pressing either button will
“capture” precisely the current flow value
as the new relay trip point.
Selects whether the relay is “on” (energized) if the flow value is above the relay
trip point, or if the relay is “on” (energized) when the flow value is below the
relay trip point. Pressing the buttons will
toggle between the two options (default
= “on” above trip point -- typical for low
flow alarm).
Select and load a bank of configuration
parameters. If the bank corresponding to
the selected index has not been set, the
“error pattern” (1100110011) will display.
Use “+” or “-” to move to a bank that has
desired parameters populated for loading
into active bank (0). **
Selects the output range function static/
1111100000 =
Static or
5
6
7
8
Dynamic
Range
Selection
Minimum
Flow Cap-
ture
Maximum
Flow Cap-
ture
Hysteresis
Applied
Above or
Below Trip
Point
1111100000
- +
1111110000
- +
1111111000
- +
1111111100
- +
DISPLAY_RANGE_MODE
CUST_FLOW_MIN
CUST_FLOW_MAX
RELAY_HYSTERESIS_
EFFECT
“static”
0000011111 =
“dynamic”
1 – indicates current
value relative to full
scale
1 – indicates current
value relative to full
scale
0000011111 = apply
above
1111100000= apply
below
dynamic. If “static” mode, then the output range is defined by the CUST_FLOW_
MIN and CUST_FLOW_MAX parameters.
If “dynamic” mode the CUST_FLOW_
MAX will adjust if the flow value is
greater than the current maximum value.
Default value is “static.”
When entering this function the “ready
to capture” LED pattern will be presented
(0101010101). Pressing either button will
“capture” the current flow value as the
new display “zero” point.
When entering this function the “ready
to capture” LED pattern will be presented
(0101010101). Pressing either button will
“capture” the current flow value as the
new display “maximum flow” point. Note:
this mode is only valid if the DISPLAY_
RANGE_MODE (5) is “static.”
Selects whether the hysteresis is to be
applied above (default) or below the
relay trip point. Pressing the buttons will
toggle between the two options.
06EN003398 Rev. B Fluid Components International LLC
1 – indicates current
Maximum
9
Hysteresis
Value
1111111110
- +
RELAY_HYSTERESIS
value relative to
maximum 10%
hysteresis (MAX_
HYSTERESIS)
Buttons adjust the value of the dead
band effect. Increments in 1 percent
of trip-point value. Default setting is
2% of trip-point. Button range 0-10%.
Wider range available through RS232
interface.
10
11
12
13
Time Delay
to
Activate
Relay or
Binary Pulse
Time Delay
to
De-activate
Relay or
Binary Pulse
Alarm
Simulation
Keypad
Lockout
1111111111
- +
1000000001
- +
1100000001
- +
1110000001
- +
RELAY_TURN_ON_
DELAY
RELAY_TURN_OFF_
DELAY
BTN_ENTER_TIMEOUT
1 – indicates current
value relative to
maximum delay
(MAX_DELAY)
1 – indicates current
value relative to
maximum delay
(MAX_DELAY)
0000011111= output
“max”
1111100000= output
“min”
1111100000 = 3
seconds
0000011111= 10
seconds
Time delay from when flow
measurement is greater/less than relay
trip point, to turn on relay. Increments
and decrements in 1 second steps [Max
default setting 10 seconds when using
buttons].*
Time delay from when flow
measurement is greater/less than relay
trip point, to turn off relay. Increments
and decrements in 1 second steps [Max
default setting 10 seconds when using
buttons].*
Alarm simulation mode. Pressing the “+”
button forces “maximum” (corresponds
to A_OUT_DAC_COUNT_100) 4-20 mA
output. Pressing “-” forces “minimum”
(corresponds to A_OUT_DAC_COUNT_0)
4-20 mA output.
Relay output will correspond with
RELAY_POLAR setting.
Keypad lockout time. Pressing the
buttons toggles between either 3
seconds or 10 seconds to hold both
buttons to enter “function selection”
mode.
14
Filter
Setting1111000001
- +
INPUT_FILTER_COUNT
LED 1 on = setting 3
LEDs 1-3 on = 18
LEDs 1-5 on = 30
LEDs 1-7 on = 50
LEDs 1-10 on = 100
User preset. Save current active
parameters (in 0 bank) to user bank
location 7. (Hint- use “-” button to
quickly move to FUNCTION 15 from
15
Save To
Bank
1111100001
- +
1111111000=7
FUNCTION position 1). **
* Maximum time delay may be up to 65,000 seconds when using RS232 command line or PC interface.
** Function #4 (load a bank) and function #15 (save to a bank), requires holding either button for 3 seconds to load or save.
Holding both buttons will exit either function without performing the operation.
This document contains confidential technical data, including trade secrets and proprietary information which is the property of Fluid Components International LLC (FCI). Disclosure
of this data to you is expressly conditioned upon your assent that its use is limited to use within your company only (and does not include manufacture or processing uses). Any
other use is strictly prohibited without the prior written consent of FCI.
Notice of Proprietary Rights
Fluid Components International LLC 06EN003398 Rev. B
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.