Fluid Components International CMF User Manual

Fluid Components Intl
4. Installation of sensor
4.1 Location
4.2 Cavitation
Installation of sensor
To ensure the optimum function of measuring equipment it is important that the installation instructions are followed closely, point by point.
The flowmeter can be located both indoors and outdoors, but the following conditions must be observed:
Liquid temperature: -58 to 356°F (-50 to +180°C). The grade of enclosure can be choosen from IP 20 up to IP 67.
When the temperature difference between a liquid and the surroundings is large, the sen­sor must be insulated to prevent 2-phase flow and thereby measuring inaccuracy. This ap­plies especially in the case of low flow.
Important!
The sensor must always be completely filled with a homogeneous liquid or gas in single phase, otherwise measuring errors will occur.
Avoid cavitation in the system, i.e. sucking in or releasing air into the system, because this may produce errors.
Static back pressure minimum 0.1 - 0.2 bar.
4.3 Air bubbles
4.4 Mounting
Avoid large quantities of air collecting in the sensor because these will disturb measure­ment. Homogeneous mixtures of air and sol­ids, however, will not disturb measurement. When there is air in the liquid, installation of an air trap ahead of the meter is recommended.
If there is air/gas in the liquid or liquids which are volatile, horizontal sensor mounting is recommended.
The unit must be mounted on a flat wall or steel frame (vibration-free).
FlexCOR Model CMF Series 22
Document 06EN003327 Rev. -
4.5 Vibrations
4.6 Cross-talk
Fluid Components Intl
Locate the flowmeter as far away as possible from components that generate mechanical vibration in the piping.
Or ensure that there is no direct connection with them e.g. by using flexible connections. The flowmeter can also be located after a bend.
Installation of sensor
4.7 Magnetic fields
4.8 Transportation/ storage
Document 06EN003327 Rev. -
If the flowmeters are located close to each other, e.g. in the same pipe section, the meters may disturb each other in measurement, especially with low flow. Locate the meters with a flexible connection instead of a permanent connection. Avoid mounting the meter on the same steel frame. i.e. insulate the meters mechanically.
Locate the sensor a minimum of 10 inches (25 cm) from strong magnetic fields (motors, transformers, electrically operated valves, etc.).
The sensor is a fragile piece of equipment and shall be placed in its storage carton when transported or stored. If this is not possible, the sensor must be packed so the packing enclosure can withstand the hazards from transportation or storage.
23 FlexCOR Model CMF Series
Fluid Components Intl
4.9 Horizontal mounting in pipe CMF B-F
Locate the sensor low in the pipe system in order to avoid low pressure in the sensor and consequent air separation in the liquid.
If the flowmeter is mounted horizontally it is self-emptying.
With low flow, horizontal mounting is recommended, any air bubbles are easier to remove.
Flow direction
Installation of sensor
0-point adjustment
Static back pressure
Valve
Forward Normal
Valve
Reverse Inverse
The arrow on the sensor indicates the direction of flow defined as “positive” (the meter is able to measure flow in both directions). If possible, the liquid should flow in the forward direction to avoid partial emptying of the sensor, especially with low flow. In addition there should be a valve (check/solenoid) that closes when the flow is zero so that the liquid does not flow back and causes partial emptying of the sensor.
To facilitate 0-point adjustment, a valve with a good shut-off should always be mounted near the sensor.
- The sensor should be completely filled with liquid.
- The valve must be closed.
- Wait a few minutes to let the flow stabilize at zero.
- Activate the 0-point adjustment, see Chapter 7 "Setting the 0-point".
FlexCOR Model CMF Series 24
Document 06EN003327 Rev. -
Loading...
+ 6 hidden pages