FloTech FT151, FT150, FT155, FT152 Instruction Manual

Instruction Manual 10159
Thermo-Optic Sensors and Thermistor Dummy
PRODUCT DESCRIPTIONS:
FloTech Thermo-Optic sensor and Thermistor Dummy are mechanically and functionally compatible with Civacon Thermistor, Thermo-Optic and Thermistor Dummy components.
These “Electronic” Thermistor sensors will provide reliable operation when installed as
replacements to conventional “Green Tipped” Thermistor sensors. FloTech Thermo-Optic sensors and electronic dummy provide high reliability, long life, and quick start up in cold weather. “Civacon” is a registered trademarks of Civacon / Dover Corporation.
INSTALLATION INSTRUCTIONS:
FloTech model FT151 can be mounted in a 2”NPT female pipe coupling or through a 2 3/8”
hole. When mounting in a 2 3/8” hole the gasket and lock nut provided are used to retain the
probe holder in the tank shell or manhole. After the sensor is mounted remove the cap.
Loosen the probe clamp screw and adjust the probe to the correct level point. This is typically 3% of compartment volume. It is not recommended cutting the standard 7” sensor to a shorter length. This will cause insufficient time to stop the flow of product within the load racks reaction time.
IMPORTANT: The actual sensing point adjustment should be determined by the total response time required to prevent a tank overfill condition. The FloTech sensor reaction time is one half second. The loading rack will also have a reaction time. Once the probe is adjusted to the proper height, tighten the clamp screw.
4740T Interstate Dr. Cincinnati, OH 45246
Rev: May 2017 PH: 513 874 8499 FX: 513 874 8399 Page 1
Dixon Bayco
WIRING INSTRUCTIONS:
It is highly recommended to use FloTech FT401 jacketed 7-conductor cable when wiring a new system. FloTech cable is designed to be oil, UV, and abrasion resistant. We incorporate a noble tin plated stranded copper wire which resist corrosion. These features will provide years of reliable service.
After all sensors are mounted in each compartment, align the conduit openings so they face the roll over rail. Thread in cable glands and pull a length of cable through the conduit openings between each sensor. Cut to length leaving approximately 8 inches extra length exiting the top of each probe holder.
All sensor wires must enter or leave the probe holder through one of the ½ NPT openings. Use FloTech FT402 ½ NPT cable glands to ensure a water tight seal. Unused conduit openings must have a ½ NPT pipe plug installed. Use pipe dope on all ½ NPT threads to ensure a water tight seal.
Wire the sensor according to diagram F1 below. Double check your wiring connection when complete. NOTE: It is highly recommended to use a small amount of Silicone RTV sealant in each crimp connection. Fill the FloTech butt end crimps with Silicone RTV sealant prior to inserting the wires then crimp. This will provide a watertight and vibration resistant connection.
When wiring is complete, replace each sensor cap and o-ring. CAUTION: Do not pinch a sensor wire when installing the cap.
Rev: May 2017 PH: 513 874 8499 FX: 513 874 8399 Page 2
4740T Interstate Dr. Cincinnati, OH 45246
Dixon Bayco
Diagram F1
Rev: May 2017 PH: 513 874 8499 FX: 513 874 8399 Page 3
Dixon Bayco
4740T Interstate Dr. Cincinnati, OH 45246
Loading...
+ 6 hidden pages