49
235. (11101011) Phase 6 - Lid Lock Short Circuit
Lid Lock fault, not activated when instructed to by the Motor Control
Module.
Primary Fault: Lid Lock mechanism has jammed or failed.
Action: Check resistance across the connections,
should be around 73 ohms. If not within 5
ohms, replace the Lid Lock.
236. (11101100) Phase 6 - Incompatible EEPROM Version
Failure to start and fault immediately displayed.
Primary Fault: Motor Control Module is the wrong one.
Action: Replace Motor Control Module.
237. (11101111) Phase 6 - Temperature Sensor Error
The electronics have picked up a continuity problem, same as fault
code 10 or 41.
Primary Fault: The sensor has failed either in the harness or
connection to the thermistor.
Action: Replace the Thermistor (temperature sensor).
Secondary Source: Motor Control Module has failed to read the
temperature. Check connections.
Action: Replace Motor Control Module if connections
look fine and the fault still occurs.
238. (11101110) Phase 6 - Lid Lock Fail In-line Test (1)
Final on line tests, final check before going to the field.
239. (11101111) Phase 6 - Lid Lock Fail In-line Test (2)
Final on line tests, final check before going to the field.
240. (11110000) Phase 6 - Hall Out of Order. RPS Fault
Same as previous Hall Error faults, just an extra fault code for Phase
6. See fault codes 130 and 131 for directions.