Valve position feedback is very important to control valve performance. The DVC6200 HW2 digital valve controller
provides a unique feature to detect position feedback issues and automatically revert from travel control to pressure
control (I/P transducer mode) to keep the valve operational. This can help avoid costly unplanned spurious trips that
can affect plant operation.
Notes
The DVC6200 HW2, instrument level AD, PD, or ODV, can fallback into pressure control mode only if the unit is direct- or
reverse-acting single output. The pressure fallback feature will not work on dual outputs that are required for double-acting piston
actuators.
The DVC6200 HW2 can fallback from travel control mode to pressure control mode based on the following parameter
settings:
D Fallback on Sensor Failure—When the instrument detects a travel sensor failure it will fall back into pressure
control mode. The instrument will disregard the travel feedback and control based on output pressure.
D Fallback on Sensor Failure or Deviation—Pressure fallback will occur when the instrument detects a travel sensor
failure or if the configured deviation between travel target and actual travel have exceeded the travel deviation
time.
D Fallback Recovery—If the instrument has fallen into pressure control and the feedback problem is resolved,
recovery to travel control can occur automatically or with manual intervention. To return to travel control when
Manual Recovery is selected, change the Fallback Recovery to Auto Recovery, and then back to Manual Recovery.
In the DVC6200 HW2, the Travel/Pressure configuration parameter allows for choosing the control mode:
Travel
Pressure
Fallback on Sensor Failure (Auto or Manual recovery)
Fallback on Sensor Failure or Deviation (Auto or Manual recovery)
www.Fisher.com

DVC6200 HW2 Digital Valve Controller
October 2021
Instruction Manual Supplement
D104713X012
Advantages of Travel Control/Pressure Fallback
Travel Control/Pressure Fallback can help you avoid plant trips due to a failure of the travel sensor, allowing you to
maximize plant availability.
Travel Control/Pressure Fallback can be used during hot cutover applications, which can result in considerable
operating cost savings.
Miscellaneous
D The Travel Calibration procedure calibrates the instrument for both travel and pressure control mode; it allows
the instrument to operate in Travel as the default mode, but revert to pressure control when the Travel/Pressure
Select parameter is configured as such.
D In the case of the travel sensor failure, the change from travel to pressure control mode is bumpless.
D When the DVC6200 HW2 is configured for auto recovery, it will revert to Travel Control once the travel sensor
issue has been rectified and the deviation limit settings are back to their normal range.
D The Travel Deviation Pressure Fallback and Travel Deviation Pressure Fallback time parameters configure the
instrument to detect when the travel sensor is out of the specified range and revert to pressure control mode.
D Refer to the DVC6200 HW2 instruction manual, in Related Documents below, for detailed set up information.
D This option is also available on DVC6200f and DVC6200p digital valve controllers. Refer to the appropriate
instruction manual in Related Documents below.
Related Documents
Refer to the DVC6200 Series Quick Start Guide, D103556X012, for installation, connection, and initial configuration
information. Refer to the instruction manual, listed below, for all other information pertaining to the digital valve
controller, including product specifications, reference materials, custom setup information, maintenance procedures,
and replacement part details.
D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103605X012
D DVC6200f Digital Valve Controller Instruction Manual (D103412X012)
D DVC6200p Digital Valve Controller Instruction Manual (D103563X012
Documents are available from your Emerson sales office
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson
Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
or at Fisher.com.
)
)
2
E 2021 Fisher Controls International LLC. All rights reserved.