Fisher Guide: ControlWave Flow Measurement Applications Guide (D5137) Manuals & Guides

s
User Manual
Part Number D301686X012
Document Number D5137
ControlWave Flow Measurement Applications Guide
Used with
ControlWave
GFC / GFC Plus
ControlWave
Corrector
ControlWave
EFM
ControlWave
XFC
Remote Automa ti on Solution
www.EmersonProcess.com/Remote
Be sure that these instructions are carefully read and understood before any operation is attempted. Improper use of this device in some applications may result in damage or injury. The user is urged to keep this book filed in a convenient location for future reference.
These instructions may not cover all details or variations in equipment or cover every possible situation to be met in connection with installation, operation or maintenance. Should problems arise that are not covered sufficiently in the text, the purchaser is advised to contact Emerson Process Management, Remote Automation Solutions for further information.
IMPORTANT! READ INSTRUCTIONS BEFORE STARTING!
EQUIPMENT APPLICATION WARNING
The customer should note that a failure of this instrument or system, for whatever reason, may leave an operating process without protection. Depending upon the application, this could result in possible damage to property or injury to persons. It is suggested that the purchaser review the need for additional backup equipment or provide alternate means of protection such as alarm devices, output limiting, fail-safe valves, relief valves, emergency shutoffs, emergency switches, etc. If additional information is required, the purchaser is advised to contact Remote Automation Solutions.
RETURNED EQUIPMENT WARNING
When returning any equipment to Remote Automation Solutions for repairs or evaluation, please note the following: The party sending such materials is responsible to ensure that the materials returned to Remote Automation Solutions are clean to safe levels, as such levels are defined and/or determined by applicable federal, state and/or local law regulations or codes. Such party agrees to indemnify Remote Automation Solutions and save Remote Automation Solutions harmless from any liability or damage which Remote Automation Solutions may incur or suffer due to such party's failure to so act.
ELECTRICAL GROUNDING
Metal enclosures and exposed metal parts of electrical instruments must be grounded in accordance with OSHA rules and regulations pertaining to "Design Safety Standards for Electrical Systems," 29 CFR, Part 1910, Subpart S, dated: April 16, 1981 (OSHA rulings are in agreement with the National Electrical Code).
The grounding requirement is also applicable to mechanical or pneumatic instruments that include electrically operated devices such as lights, switches, relays, alarms, or chart drives.
EQUIPMENT DAMAGE FROM ELECTROSTATIC DISCHARGE VOLTAGE
This product contains sensitive electronic components that can be damaged by exposure to an electrostatic discharge (ESD) voltage. Depending on the magnitude and duration of the ESD, this can result in erratic operation or complete failure of the equipment. Read supplemental document S14006 for proper care and handling of ESD-sensitive components.
ControlWave Flow Measurement Applications Guide
Contents
Chapter 1 – Introduction 1-1
1.1 Components of the ControlWave Standard Gas Flow Measurement Application .................... 1-1
1.2 Overview of the Standard Gas Flow Measurem ent Ap plica t ion ............................................... 1-2
1.2.1 Data Acquisition – Static Pressure, Differential Pressure, Temperature Variables ...... 1-2
1.2.2 Flow and Volume Calculations ...................................................................................... 1-3
1.2.3 Flow Rate and Flow Time Calculations (AGA3)............................................................ 1-3
1.2.4 Flow Rate and Flow Time Calculations (AGA7)............................................................ 1-3
1.2.5 Extension Calculation and Analog Averaging ............................................................... 1-4
1.2.6 Energy Calculation ........................................................................................................ 1-4
1.2.7 Volume and Energy Integration .................................................................................... 1-4
1.2.8 Downstream Pressure Tap ........................................................................................... 1-4
1.2.9 Historical Data Storage (Audit Records/ Archive Files) ................................................ 1-4
1.2.10 Run Switching ............................................................................................................... 1-6
1.2.11 Sampler and Odorizer ................................................................................................... 1-7
1.2.12 Chromatograph Interface .............................................................................................. 1-7
1.2.13 Nominations .................................................................................................................. 1-7
1.3 Scope of the Manual ................................................................................................................. 1-7
Chapter 2 – Getting Started 2-1
2.1 Before You Begin ...................................................................................................................... 2-1
2.2 Application Files ........................................................................................................................ 2-2
2.3 Starting the Application in TechView......................................................................................... 2-3
2.3.1 Startup Sequence for ControlWave GFC, GFC Plus, Corrector ................................... 2-3
2.3.2 Startup Sequence for ControlWave EFM ...................................................................... 2-3
2.3.3 Startup Sequence for ControlWave XFC ...................................................................... 2-3
2.4 TechView Screens .................................................................................................................... 2-3
2.4.1 Logging Onto the ControlWave Flow Computer (EFM/GFC/XFC) ............................... 2-4
2.5 Accessing Pages of the Flow Measurement Application .......................................................... 2-5
Chapter 3 – Using the Measurement Group Data Tab 3-1
3.1 Accessing the Data Tab ............................................................................................................ 3-1
3.2 Meter Run Overview ................................................................................................................. 3-2
3.3 Station Summary ....................................................................................................................... 3-6
3.3.1 Forward/Reverse Summary ........................................................................................ 3-11
Chapter 4 – Using the Measurement Group Config Tab 4-1
4.1 Accessing the Config Tab ......................................................................................................... 4-2
4.2 Meter Run I/O Configuration ..................................................................................................... 4-3
4.3 Alarm Configuration ................................................................................................................ 4-13
4.4 Analog Input/Output Configuration .......................................................................................... 4-19
4.5 Auto-Adjust Configuration ....................................................................................................... 4-22
4.6 Transmitter Configuration ........................................................................................................ 4-26
4.7 Basic Flow Setup..................................................................................................................... 4-28
4.7.1 Basic Flow Setup – AGA3TERM ................................................................................ 4-28
4.7.2 Basic Flow Setup – AGA3I .......................................................................................... 4-31
4.7.3 Basic Flow Setup – AGA7 ........................................................................................... 4-35
4.7.4 Basic Flow Setup – Coriolis ........................................................................................ 4-38
4.8 Flow Equation Selection and Details....................................................................................... 4-40
Issued: Oct-2014 Contents iii
ControlWave Flow Measurement Applications Guide
4.8.1 Differential Measurement – AGA3I (1992 equation) ................................................... 4-41
4.8.2 Differential Measurement – AGA3TERM (1985 equation).......................................... 4-45
4.8.3 Linear Measurement – AGA7 ..................................................................................... 4-48
4.8.4 Coriolis Measurement ................................................................................................. 4-51
4.9 Compressibility Setup ............................................................................................................. 4-53
4.10 GC Summary .......................................................................................................................... 4-57
4.11 Chromatograph Component Range Setup ............................................................................. 4-64
4.12 Sampler and Odorizer Output Configuration ........................................................................... 4-69
4.13 Mechanical Counter Configuration .......................................................................................... 4-72
4.14 Nominations ............................................................................................................................ 4-73
4.15 Flow Control and Valve Control .............................................................................................. 4-78
4.16 Run Switching ......................................................................................................................... 4-85
Chapter 5 – Using the Measurement Group Logs Tab 5-1
5.1 Accessing the Logs Tab ............................................................................................................ 5-1
5.2 Viewing Archives – Meter Run Archive Files / Alarms .............................................................. 5-1
5.2.1 Using the Float Format dialog box ................................................................................ 5-6
5.2.2 Working with the Archive Grid ....................................................................................... 5-7
5.3 View Audit Trail ......................................................................................................................... 5-8
5.4 Archive File Collection ............................................................................................................. 5-11
Chapter 6 – Using the Device Group Config Tab 6-1
6.1 Accessing the Config Tab ......................................................................................................... 6-1
6.2 Meter Run Save/Load Configuration ......................................................................................... 6-2
6.2.1 Creating a Recipe ......................................................................................................... 6-4
6.2.2 Saving the Recipe ......................................................................................................... 6-5
6.2.3 Recalling a Saved Recipe, and Sending Its Values to the ControlWave...................... 6-5
Chapter 7 – Using the Device Group Comm Tab 7-1
7.1 Accessing the Config Tab ......................................................................................................... 7-1
7.2 Radio Control ............................................................................................................................ 7-1
Chapter 8 – Using the Device Group Specials Tab 8-1
8.1 Accessing the Specials Tab ...................................................................................................... 8-1
8.2 RTU Date and Time .................................................................................................................. 8-1
Appendix M – Modbus Coil and Register Maps M-1
Index IND-1
iv Contents Issued: Oct-2014
Chapter 1 – Introduction
This manual focuses on how you can configure and use the standard gas measurement application program available with ControlWave flow computer products.
The ControlWave flow computer products include:
ControlWave Gas Flow Computer (GFC) ControlWave Gas Flow Computer Plus (GFC in enclosure) ControlWave Gas Flow Corrector ControlWave Electronic Flow Meter (EFM)ControlWave Explosion Proof Flow Computer (XFC)
This chapter provides an overview of the ControlWave flow computer application and details the structure of this manual.
In This Chapter
ControlWave Flow Measurement Applications Guide
1.1 Components of the ControlWave Standard Gas Flow Measurement
Application ................................................................................................ 1-1
1.2 Overview of the Standard Gas Flow Measurement Application ............... 1-2
1.2.1 Data Acquisition – Static Pressure, Differential Pressure,
Temperature Variables ................................................................ 1-2
1.2.2 Flow and Volume Calculations ...................................................... 1-3
1.2.3 Flow Rate and Flow Time Calculations (AGA3) ............................ 1-3
1.2.4 Flow Rate and Flow Time Calculations (AGA7) ............................ 1-3
1.2.5 Extension Calculation and Analog Averaging ................................ 1-4
1.2.6 Energy Calculation ........................................................................ 1-4
1.2.7 Volume and Energy Integration ..................................................... 1-4
1.2.8 Downstream Pressure Tap............................................................ 1-4
1.2.9 Historical Data Storage (Audit Records/ Archive Files) ................. 1-4
1.2.10 Run Switching ................................................................................ 1-6
1.2.11 Sampler and Odorizer ................................................................... 1-7
1.2.12 Chromatograph Interface .............................................................. 1-7
1.2.13 Nominations .................................................................................. 1-7
1.3 Scope of the Manual ................................................................................. 1-7
1.1 Components of the ControlWa ve St a nda rd Gas Flow Measurement Application
The ControlWave standard gas flow measurement application consists of: A ControlWave project file (*.PRO) pre-programmed for natural gas
measurement.
A customized flash configuration profile (*.FCP) file that configures
the ports, memory, audit, and archive parameters of the ControlWave GFC/GFC Plus/EFM/XFC/Corrector.
A TechView session. This includes the TechView session file
(*.TVS), associated *.INI files, and a set of HTM menus customized
Revised Oct-2014 Introduction 1-1
ControlWave Flow Measurement Applications Guide
for the gas measurement application. You use these menus to configure the application.
1.2 Overview of the Standard Gas Flow Measurement Application
The ControlWave standard gas flow measurement application collects static pressure, differential pressure and temperature data and computes flow, energy, and volume for a station.
A station typically refers to a single flow computer and all its associated meter runs. Each meter run refers to measurement of natural gas through a single pipeline.
There are certain variations in the application depending upon which ControlWave model you use. For example, the ControlWave EFM supports up to four meter runs, whereas other models are only configured to support one or two meter runs.
Note: If your ControlWave application requires more than four meter
runs, you should use the Station Manager application instead. See the ControlWave Station Manager Configuration Manual (D5136) for more information.
Similarly, certain input/output (I/O) options only apply to certain models. Common features for all versions of the application are discussed below:
1.2.1 Data Acquisition – Static Pressure, Differential Pressure, Temperature Variables
The application requires these process inputs for orifice measurement:
static pressure (SP) collected once per second differential pressure (DP) collected once per second flowing temperature (T) collected once per second
The application requires these process inputs for measurement using a positive displacement (PD), turbine, or ultrasonic meter:
static pressure (SP) collected once per secondfrequency input collected once per second flowing temperature (T) collected once per second
The application also collects self-test and compensation variables at intervals of four seconds or less.
Pressure data can come from any of the following sources: Analog pressure transmitters connected to analog input points on a
process I/O module in the ControlWave flow computer.
Built-in multivariable transducer. External multivariable transmitters (Bristol or Rosemount) using
BSAP or Modbus communications through an RS-485 communication port.
1-2 Introduction Revised Oct-2014
ControlWave Flow Measurement Applications Guide
1.2.2 Flow a nd V olume Calculations
Flow and volume calculations conform to American Petroleum Institute (API) and American Gas Association (AGA) standards.
Supported flow calculations include:
AGA3-1985/NX-19 AGA3-1992 with selectable AGA8 Gross or AGA8 Detail AGA7/NX-19 AGA7 with selectable AGA8 Gross or AGA8 Detail
Auto-adjust AGA7/NX-19 Auto-adjust AGA7 with selectable AGA8 Gross or AGA8 Detail
The application performs a complete flow calculation using the process variables every second. Each calculation includes instantaneous rate according to API 14.3, compressibility according to AGA 8 Detail or Gross method, and updates of all volumes, totals, and archive averages.
1.2.3 Flow Ra t e a nd Flow Time Cal c ulations (AGA3)
For orifice flow measurement, the application compares the differential pressure value to a low flow cutoff value every second. If the differential pressure falls below the low flow cutoff value, flow is considered to be zero for that second. Hourly and daily flow time is defined to be the number of seconds for which the differential pressure exceeded the cutoff value for the period.
The values for static and differential pressure and temperature are used as inputs to the flow equations. You can select API 14.3 (AGA3, 1992) and AGA8 calculations, with compressibility calculations according to AGA Report No. 8, 1992 (with 1993 errata). The application supports both the detail method and the two gross methods of characterization described in AGA 8. Users may also select the AGA3, 1995 and NX-19 flow equations to calculate the rate of flow.
1.2.4 Flow Ra t e a nd Flow Time Cal c ulations (AGA7)
When using PD meters, turbine meters or ultrasonic meters, the application calculates flow rate by applying the correction factor computed by the AGA7 calculations to the frequency of the input pulses. When the frequency drops below 1 Hz, the application sets the flow rate estimate to zero; however, volume calculations still accumulate. The flow time recorded is the time for which the flow rate is non-zero.
Revised Oct-2014 Introduction 1-3
ControlWave Flow Measurement Applications Guide
1.2.5 Extension Calc ulation and Analog Averaging
For orifice meters, the application calculates the flow extension every second. The extension is the square root of the product of the absolute upstream static pressure times the differential pressure. This extension is used in the flow rate calculation. When there is no flow, the application reports the arithmetic averages of static pressure and temperature. This allows you to monitor static pressure and temperature during shut-in periods.
1.2.6 Energy Calculation
The application offers the option of using a fixed volumetric heating value or calculating the energy content of the gas according to AGA Report No.
5.
1.2.7 Volume and Energy Integration
The application integrates and accumulates volume and energy at the end of every calculation cycle. The application calculates the volume for a cycle by multiplying the calculated rate by the flow time for that cycle. The application calculates the energy for a cycle by multiplying the volume at base conditions by the heating value.
1.2.8 Downstream Pressure Tap
The multivariable transducer typically measures static pressure from an integral tap on the upstream, high-pressure leg of the differential pressure connection. The transducer can also measure static pressure at the downstream pressure tap, with the measurement taken from the low­pressure side to the high-pressure side. In this installation, the differential signal from the transducer is negative. If, while using the integral smart multivariable transmitter (MVT) or an external MVT, you select the downstream tap location during MVT configuration, the MVT firmware changes the sign of the differential pressure to provide a positive DP value.
1.2.9 Historical Data Storage (Audit Records/ Archive Files)
The ControlWave supports two distinct types of historical data storage – audit records and archive files.
Where feasible, both forms of archive data conform to the requirements of the API Chapter 21. Specifically, the averages of the process variables stored in the data archive are for flowing periods, appropriate to their usage in the equations, and any gas-related parameter designated an event that is changed by an operator either remotely or locally causes an entry in the audit log.
1-4 Introduction Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Audit Records (Alarms and Events)
The audit system maintains a history of alarms and certain events that have an impact on the calculated and reported gas flow rates and volumes.
The application stores 500 e entries. to prevent recurring alarms from overwriting events
The following circumstances
   
You can view audit records on See the
help on interpreting
Archive Files (Averages, totals, and other values
Archive files store the value of process variables and other calculated variables at specified intervals entry When archive files fill up, new values overwrite the oldes files.
The application displays archive file data in hourly, data, and periodic logs you can view on screen.
Log Breaks
)
the most recent 500 alarms and the most recent
vents. As new alarms/events arrive, they overwrite the oldest
Internally, the ControlWave stores alarms and events separately
configuration audit data
. The application reports alarms and events in the same log.
generate an audit record:
Any operator change to a configuration variable Any change in the state of an alarm variable A system restart Certain other system events
-screen in the audit log.
Supplement to OpenBSI 5.8 Service Pack 1 documentation for
audit records.
along with the date and time of each
. This includes flow rates, volumes and other calculated values.
t entries in the
You can configure the application to support the "breaking" of a log period when an operator-changes a parameter. When this occurs, the log period in process closes out to make a log, and a new log begins.
Hourly Historical Data Log
Each meter run maintains an hourly data log that holds one record for every contract hour. Hourly logs hold 840 entries or 35 days; this ensures that the previous period of hourly data is always resident in flash memory.
The hourly data log stores the following items:
corrected volume uncorrected volume accumulated energy average static pressure average temperatureaverage differential pressure
Revised Oct-2014 Introduction 1-5
ControlWave Flow Measurement Applications Guide
average specific gravityaverage heating valueflow timeuncorrected count
Daily Historical Data Log
Each meter run maintains a daily data log that holds one record for every contract gas day. You can change the contract hour the contract gas day starts at some time other than midnight. The daily log holds 62 entries; this ensures that the previous calendar month of daily data is always resident in flash memory.
The daily data log stores the following items:
corrected volume uncorrected volume accumulated energyaverage static pressureaverage temperatureaverage differential pressureaverage specific gravityaverage heating valueflow timeuncorrected count
Periodic Historical Data Log
Each meter run maintains a periodic data log that holds one record for every log interval. Each log interval is 15 minutes. The periodic historical data log holds 1440 records, or four days of 15 minute data.
The periodic historical data log stores the following items:
flowing differential pressure flowing static pressure flowing temperature frequency
1.2.10 Run Switc hing
If you use multiple meter runs in the application, you can configure run switching. Run switching (also known as meter run staging or tube switching) allows changes to the number of meter runs currently active to meet the gas flow demand for the station. See Section 4.15 for more information.
1-6 Introduction Revised Oct-2014
1.2.11 Sampler and Odorizer
Config Tab
Provides information on the various
Logs Tab
Samplers are external devices which measure the quality of the gas stream. Because natural gas is odorless and colorless, devices called odorizers
inject an additive to the gas stream that allows people to detect the presence of natural gas in the event of a gas leak.
For information on configuring the application to work with a sampler or odorizer, see Section 4.11.
1.2.12 Chromatograph Interface
If you use a chromatograph to measure gas component information you can integrate this into the application. You can also specify fixed gas component percentages to use if the chromatograph fails. See Section 4.10 for more information.
1.2.13 Nominations
Nominations allow you to configure the ControlWave flow computer to allocate precise amounts of gas flow during specific time periods, called nomination periods. See Section 4.13 for more information.
ControlWave Flow Measurement Applications Guide
1.3 Scope of the Manual
This manual contains the following chapters:
Chapter 1 Introduction
Chapter 2 Getting Started
Chapter 3 Using the Measurement Group Data tab
Chapter 4 Using the Measurement Group
Chapter 5 Using the Measurement Group
Chapter 6 – Using the Device Group Config Tab
Chapter 7 – Using the Device Group Comm Tab
Provides an overview of the features supported by the ControlWave standard gas flow measurement application.
Provides general information on software installation and how to start the application.
Provides information on viewing the summary pages for the station and the meter run.
configuration pages.
Provides information on viewing archive and audit data on screen.
Provides information on saving/retrieving recipe values.
Provides instructions for setting up radio communication.
Revised Oct-2014 Introduction 1-7
ControlWave Flow Measurement Applications Guide
Chapter 8 – Using the Specials Tab
Provides instructions for setting the ControlWave flow computer’s clock.
1-8 Introduction Revised Oct-2014
Chapter 2 – Getting Started
This chapter discusses the prerequisites for running the application, and tells you how to start the software.
In This Chapter
2.1 Before You Begin ...................................................................................... 2-1
2.2 Application Files ........................................................................................ 2-2
2.3 Starting the Application in TechView ........................................................ 2-3
2.3.1 Startup Sequence for ControlWave GFC, GFC Plus, Corrector ... 2-3
2.3.2 Startup Sequence for ControlWave EFM ...................................... 2-3
2.3.3 Startup Sequence for ControlWave XFC ...................................... 2-3
2.4 TechView Screens .................................................................................... 2-3
2.4.1 Logging Onto the ControlWave Flow Computer (EFM/GFC/XFC) 2-4
2.5 Accessing Pages of the Flow Measurement Application ......................... 2-5
2.1 Before You Begin
You must install the ControlWave flow computer (GFC, GFC Plus,
Corrector, EFM, XFC) on site and connect field devices to its I/O module(s) or ports. For information on ControlWave hardware, see the appropriate document:
ControlWave Flow Measurement Applications Guide
CI-ControlWave EFM CI-ControlWave GFC CI-ControlWave GFC Plus CI-ControlWave Corrector CI-ControlWave XFC
You must install OpenBSI software including TechView on your PC
workstation. See the OpenBSI Utilities Manual (D5081), the BSI_Config User’s Manual (D5128), and the TechView User Manual (D5131) for details.
You must connect a serial communication cable between the PC
workstation and the Control flow computer.
The ControlWave flow computer (EFM /GFC /GFC Plus /Corrector
/XFC) must be running a flash configuration profile file (*.FCP) compatible with the gas measurement application. For information on updating FCP files, see Chapter 5 of the OpenBSI Utilities Manual (D5081).
The ControlWave flow computer must be running the standard
ControlWave project (*.PRO) file configured for the gas measurement application. See Chapter 7 of the OpenBSI Utilities Manual (D5081) for information on downloading a ControlWave project (*.PRO) file.
If you need to calibrate the pressure/temperature sensors of the
ControlWave flow computer, you can do this through TechView. See the TechView User Manual (D5131) for details.
Revised Oct-2014 Installation and Initial Configuration 2-1
ControlWave Flow Measurement Applications Guide
Note: If you ordered your ControlWave flow computer with the standard
gas measurement application pre-installed, the FCP and PRO files are already loaded when the unit ships from the factory.
2.2 Application Files
If you ordered your ControlWave with the application pre-installed, you can skip to Section 2.3.
If you purchased the application after you got the ControlWave hardware you will need to download the appropriate PRO and FCP files to your hardware as mentioned in Section 2.1. See Table 2-1 to locate the proper files.
Table 2-1. Application Files
ControlWave Platform
ControlWave
GFC
ControlWave
GFC Plus
ControlWave
EFM
ControlWave
Corrector
OpenBSI Folder Path Use this
ControlWave Project (*.PRO)
\openbsi\webGFC\config\ mgfcx_xx.PRO mgfcx_xx.FCP CwaveGFC.TVS
\openbsi\webGFC\config\ mgfcx_xx.PRO mgfcx_xx.FCP CwaveGFC.TVS
\openbsi\webEFM\config\ mefmx_xx.PRO mefmx_xx.FCP CwaveEFM.TVS
\openbsi\webGFC\config\ mgfcx_xx.PRO mgfcx_xx.FCP CwaveGFC.TVS
Use this Flash Configuration Profile (*.FCP)
Use this TechView Session File (*.TVS)
ControlWave
XFC
2-2 Installation and Initial Configuration Revised Oct-2014
\openbsi\webXFC\config\ mxfcx_xx.PRO mxfcx_xx.FCP CwaveXFC.TVS
ControlWave Flow Measurement Applications Guide
Notes:
The ControlWave GFC, GFC Plus, and Corrector share the same set of
application files.
You must replace the x_xx shown in filenames with the version
number. For example, for XFC version 1.58 the mxfcx_xx.pro becomes mxfc1_58.pro.
2.3 Starting the Application in TechView
You start the application by accessing the appropriate TVS file from the Start Program menu:
2.3.1 Startup Sequence for ControlWave GFC, GFC Plus, Corrector
Click: Start>Programs > OpenBSI Tools > Calibration & Configuration> CWave GFC Setup
2.3.2 Startup Sequence for ControlWave EFM
Click: Start>Programs > OpenBSI Tools > Calibration & Configuration> CWave EFM Setup
2.3.3 Startup Sequence for ControlWave XFC
Click: Start>Programs > OpenBSI Tools > Calibration & Configuration> CWave XFC Setup
2.4 TechView Screens
Once you start the TVS file for serial operation, TechView opens the Runtime Configuration Parameters dialog box:
Figure 2-1. Serial Runtime Parameters
Revised Oct-2014 Installation and Initial Configuration 2-3
ControlWave Flow Measurement Applications Guide
1. Leave the number of transmitters at the default of 12.
2. Enter the BSAP local address of the ControlWave flow computer
to which you are connected.
3. Select the serial communication port on the PC which you are
using to communicate with the ControlWave flow computer.
4. Select the baud rate on the serial communication line.
5. Click OK.
6. Log onto the ControlWave flow computer as described in Section
2.4.1.
2.4.1 Logging Onto the ControlWave Flow Computer (EFM/GFC/XFC)
In the SignOn to RTU dialog box, enter a Username / Password combination that allows full access to the ControlWave flow computer, then click the SignOn button.
Figure 2-2. Logging onto the ControlWave Flow Computer
2-4 Installation and Initial Configuration Revised Oct-2014
ControlWave Flow Measurement Applications Guide
2.5 Accessing Pages of the Flow Measurement Application
The flow measurement application uses two different group icons within TechView – the Measurement Group and the Device Group. By default, the application opens on the Measurement group.
1. To select a group different than the one displayed, click on its icon
to bring up the different group menu.
2. On the group menu, click on the desired tab.
3. Click on a button to bring up a page.
Click on tabs to bring up other buttons to access additional pages in this group.
Click on a button to open its associated page.
Measurement Group icon
Device Group icon
Figure 2-3. Calling Up Menus
Notes:
The remaining sections of this manual discuss the flow measurement
application pages within the Measurement and Device groups.
For information on other groups (On-Line Edits or Calibration) see the
TechView User Manual (D5131).
Revised Oct-2014 Installation and Initial Configuration 2-5
This page is intentionally left blank
ControlWave Flow Measurement Applications Guide
Data tab
Measurement group icon
Chapter 3 – Using the Measurement Group Data Tab
This chapter discusses the Data tab in the Measurement group. The Data tab lets you view details on the meter run and the station.
In This Chapter
3.1 Accessing the Data Tab ............................................................................ 3-1
3.2 Meter Run Overview ................................................................................. 3-2
3.3 Station Summary ...................................................................................... 3-6
3.1 Accessing the Data Tab
1. Within TechView, if you are in any group other than the
3.3.1 Forward/Reverse Summary ........................................................ 3-11
Measurement group, click the Measurement group icon.
2. Click the Data tab.
Issued Oct-2014 Measurement Group Data Tab 3-1
Figure 3-1. Measurement Group Data tab
ControlWave Flow Measurement Applications Guide
Calling up this Menu
Field
Description
Meter Run Overview for Run#
Select the number of the meter run for which you want to view data.
Time
The current time, in 24-hour format, reported by the flow computer.
Pipe Diameter
Shows the diameter of the pipe for this meter run.
Orifice Diameter
Shows the diameter of the orifice for this meter run.
3.2 Meter Run Overview
The Meter Run Overview page displays current flow and energy rates as well as accumulated volume and energy totals for the current/previous hour and current/previous day.
Click
Note: The very first time you click this button after installation; the
application prompts you to select the flow measurement equation, and automatically re-directs you to the flow measurement selection and detail pages. See Section 4.8.
Figure 3-2. Meter Run Overview
3-2 Measurement Group Data Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
DP
Shows the current differential pressure reading for this meter run.
SP
Shows the current static pressure reading for this meter run.
T
Shows the current temperature reading for this meter run.
Hz
Shows the current frequency reading for this meter run.
Meter ID
Enter an identifying name for the meter (ControlWave flow computer.) Typically this would be the node name, but that is not required.
Active Flow Calculation
Shows the currently selected flow calculation for this meter run.
Flow Rate
Shows the current corrected flow rate of gas for this meter run.
Corrected Flow Rate
Shows the current corrected flow rate of gas for this meter run.
Uncorrected Flow Rate
Shows the current uncorrected flow rate of gas for this meter run.
Contract Hour
Shows the hour of the day (0 to 23) which marks the beginning of the contract “gas day.”
Current Heating Value
Shows the current calculated heating value for the gas for this meter run.
Energy Rate
Shows the current calculated energy rate for the gas for this meter run.
Current Hour
Accumulated Volume
Shows the accumulated volume of gas for this meter run for the current hour.
Corrected Volume
Shows the corrected volume of gas for this meter run for the
Uncorrected Volume
Shows the uncorrected volume of gas for this meter run for the current hour.
Accumulate d E ner gy
Shows the accumulated energy of gas for this meter run for the current hour.
(Shown only for orifice type meters.)
(Shown only for linear type meters.)
(Shown only for linear type meters.)
Issued Oct-2014 Measurement Group Data Tab 3-3
(Shown only for orifice type meters.)
current hour. (Shown only for linear type meters.)
(Shown only for linear type meters.)
ControlWave Flow Measurement Applications Guide
Flow Time
Shows the amount of time gas is flowing for the current hour for this meter run.
Current Day
Accumulated Volume
Shows the accumulated volume of gas for this meter run for the current day.
Corrected Volume
Shows the corrected volume of gas for this meter run for the current day.
Uncorrected Volume
Shows the uncorrected volume of gas for this meter run for the current day.
Accumulate d E ner gy
Shows the accumulated energy of gas for this meter run for the current day.
Flow Time
Shows the amount of time gas is flowing for the current day for this meter run. Previous Hour
Accumulated Volume
Shows the accumulated volume of gas for this meter run for the previous hour. meters
Corrected Volume
Shows the corrected volume of gas for this meter run for the previous hour.
Uncorrected Volume
Shows the uncorrected volume of gas for this meter run for the previous hour.
.)
Accumulate d E ner gy
Shows the accumulated energy of gas for this meter run for the previous hour.
Avg Static Pressure
Shows the average static pressure of gas for this meter run for the previous hour.
Avg Temperature
Shows the average temperature of gas for this meter run for the previous hour.
Avg Diff. Pressure
Shows the average differential pressure of gas for this meter run for the previous hour. type meters
Avg Spec. Gravity
Shows the average specific gravity of gas for this meter run for the previous hour.
Avg Heating Va lue
Shows the average heating value of gas for this meter run for the previous hour.
Avg FPV
Shows the average supercompressibility factor (FPV) of gas for this meter run for the previous hour.
.)
(Shown only for orifice type meters.)
(Shown only for linear type meters.)
(Shown only for linear type meters.)
(Shown only for orifice type
(Shown only for linear type meters.)
.)
(Shown only for linear type meters
(Shown only for orifice
3-4 Measurement Group Data Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Avg CO2
Shows the average carbon dioxide (CO2) within the gas for this meter run for the previous hour.
Avg N2
Shows the average nitrogen (N2) within the gas for this meter run for the previous hour.
Flow Time
Shows the amount of time gas is flowing for the previous hour for this meter run.
Previous Day
Accumulated Volume
Shows the accumulated volume of gas for this meter run for the previous day.
Corrected Volume
Shows the corrected volume of gas for this meter run for the previous day.
Uncorrected Volume
Shows the uncorrected volume of gas for this meter run for the previous day.
Accumulate d E ner gy
Shows the accumulated energy of gas for this meter run for the previous day.
Avg Static Pressure
Shows the average static pressure of gas for this meter run for the previous day.
Avg Temperature
Shows the average temperature of gas for this meter run for the previous day.
Avg Diff. Pressure
Shows the average differential pressure of gas for this meter run for the previous day. type meters
Avg Spec. Gravity
Shows the average specific gravity of gas for this meter run for the previous day.
Avg Heating Va lue
Shows the average heating value of gas for this meter run for the previous day.
Avg FPV
Shows the average supercompressibility factor (FPV) of gas for this meter run for the previous day.
Avg CO2
Shows the average carbon dioxide (CO2) within the gas for this meter run for the previous day.
Avg N2
Shows the average nitrogen (N2) within the gas for this meter run for the previous day.
Flow Time
Shows the amount of time gas is flowing for the previous day for this meter run.
Reset Meter Run’s Measurement Type
If you chose the wrong flow equation type, click this button to re
.)
(Shown only for orifice type meters.)
(Shown only for linear type meters.)
(Shown only for linear type meters.)
(Shown only for orifice
Issued Oct-2014 Measurement Group Data Tab 3-5
-select the flow equation.
ControlWave Flow Measurement Applications Guide
The Station Summary page presents flow and energy data for the
Calling up this Menu
3.3 Station Summary
station for the current hour, current day, previous hour, and previous day.
Click
3-6 Measurement Group Data Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Field
Description
Station Identification
Firmware Major
Shows the major version number for the ControlWave system firmware currently installed in the ControlWave flow computer.
Firmware Minor
Shows the minor version number for the ControlWave system firmware currently installed in the ControlWave flow computer.
Station ID
Click in this field and type in a name to the station. This could be the flow computer node name, a geographic location, or other name you decide.
Program Name
Shows the name of the ControlWave project (*.PRO) file exec
Program Revision
Shows the revision level of the ControlWave project (*.PRO) file executing in the ControlWave flow computer.
Web Page Version
Shows the revision level of the ControlWave application HTML pages running on your PC.
System Voltage Input
This field shows the voltage coming to the power supply for the Corrector.
Note: The ControlWave GFC has two system voltage
Figure 3-3. Station Summary page
uting in the ControlWave flow computer.
Issued Oct-2014 Measurement Group Data Tab 3-7
ControlWave EFM, GFC, XFC, or
ControlWave Flow Measurement Applications Guide
inputs.
Ram Backup Battery Status
Displays the status of the SRAM backup battery in the ControlWave flow computer. If the SRAM backup battery fails and there is a power failure or reboot of the unit, the ControlWave flow computer loses configuration parameters, retain data, static memor data, and pending alarm messages
Station Totals
Station totals encompass all meter runs for this station.
Corrected Flow Rate
This field displays the current corrected flow rate of gas the correct units fo
Uncorrected Flow Rate
This field displays the current uncorrected flow rate of gas applied. units fo
Energy Rate
This field displays the current energy rate for gas at this correct units for the energy rate.
Corrected Volume Non­Resetting A ccu mula tor
This field shows the running total corrected volume since the last the last time you clicked
Uncorrected Volume Non Accumulator
This field shows the running total uncorrected volume since the last the last time you clicked
Energy Non-Resetting Accumulator
This field shows the running total energy since the last the last time you clicked
Reset Non-Resetting Accumulato rs Pus h to Reset
The accumulators do not reset to zero automatically at the end of the hour or day. They reset only when you manually reset them.
Click the zero for all of this station’s non
Go to Forward/Reverse Totals
Click here to go to the Forward/Reverse Summary menu.
Current Hour
This section shows readings for the current “gas hour.”
Corrected Volume
This field displays the corrected volume of gas for this station for the current hour.
Uncorrected Volume
This field displays the uncorrected volume of gas for this station for the current hour.
y
.
for this station. Click in the field at right to specify
r the corrected flow rate.
for this station before any correction factors are
Click in the field at right to specify the correct
r the uncorrected flow rate.
-Resetting
station. Click in the field at right to specify the
Push to Reset.
Push to Reset button to reset the totals to
-resetting accumulators.
Push to Reset.
Push to Reset.
3-8 Measurement Group Data Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Accumulate d E ner gy
This field displays the accumulated energy of gas for this station for t
Current Day
This section shows readings for the current “gas day.”
Corrected Volume
This field displays the corrected volume of gas for this station for the current
Uncorrected Volume
This field displays the uncorrected volume of gas for this station for the current day.
Accumulate d E ner gy
This field displays the accumulated energy of gas for this station for the current day.
Previous Hour
This section shows readings for the previous “gas hour.”
Corrected Volume
This field displays the corrected volume of gas for this station for the previous hour.
Uncorrected Volume
This field displays the uncorrected volume of gas for this station for the previous hour.
Accumulate d E ner gy
This field displays the accumulated energy of gas for this station f
Previous Day
This section shows readings for the previous “gas day.”
Corrected Volume
This field displays the corrected volume of gas for this station for the
Uncorrected Volume
This field displays the uncorrected volume of gas for this station for the previous day.
Accumulate d E ner gy
This field displays the accumulated energy of gas for this station for the previous day.
Meter Run x
The number of meter runs varies depending upon the ControlWave type. ControlW four meter runs; ControlWave Corrector/GFC/GFC Plus and XFC default to two meter runs.
ID
This field shows the name assigned to this meter run.
Corrected Flow Rate
This field displays the current corrected flow rate of gas for this meter run.
Uncorrected Flow Rate
This field displays the current uncorrected flow rate of gas for this meter run.
Prev. Hour Corrected Volume
This field displays the corrected volume of gas for this meter run for
he current hour.
day.
or the previous hour.
previous day.
ave EFM supports up to
Issued Oct-2014 Measurement Group Data Tab 3-9
the previous hour.
ControlWave Flow Measurement Applications Guide
Prev. Hour Uncorrected Volume
This field displays the uncorrected volume of gas for this meter run for the previous hour.
Prev. Hour Accumulated Ener
This field displays the accumulated energy of gas for this meter run for the previous hour.
Prev. Day Corrected Volume
This field displays the corrected volume of gas for this meter run for the previous day.
Prev. Day Uncorrected Volume
This field displays the uncorrected volume of gas for this meter run for the previous day.
Prev. Day Accumulated Energy
This field displays the accumulated energy of gas for this meter run for the previous day.
Runs x and y Bi­Directional Support Enabled/Disabled
This button only shows for even-numbered meter runs. Its label shows the current state for bi-directional support. When you click the button you toggle the state.
Click which gas can flow in both forward and reverse directions through the pipe. The
Enabled
numbered meter runs.
Click button now displays
Corrected Volume Non­Resetting A ccu mula tor
This field shows a running total of the corrected volume since the last time you clicked the
Reset
Uncorrected Volume Non Accumulato
This field shows a running total of the uncorrected volume since the last time you clicked the
Reset
Energy Non-Resetting Accumulator
This field shows a running total of the energy since the last time you clicked the
Reset Non-Resetting Accumulato r P ush to Reset
Click the Push to Reset button to reset the totals to zero for all this meter run’s non accumulators.
gy
Disabled to activate bi-directional support in
. Reverse direction only applies to even-
button now displays
-Resetting
3-10 Measurement Group Data Tab Revised Oct-2014
Enabled to turn off bi-directional support. The
Disabled.
button.
r
button.
Push to Reset button.
-resetting
Push to
Push to
ControlWave Flow Measurement Applications Guide
Calling up this Menu
Field
Description
Station Totals
Forward Corrected Flow Rate
This field displays the current corrected flow rate of gas in the forward direction for this station.
Forward Uncorrected Flow Rate
This field displays the current uncorrected flow rate of gas in the forward direction for this station.
Forward Energy R ate
This field displays the current energy rate of gas in the forward direction for this station.
Reverse Corrected Flow Rate
This field displays the current corrected flow rate of gas in the reverse direction for this station.
3.3.1 Forward/Reverse Summary
Click > Forward/Reverse Totals
Figure 3-4. Forward/Reverse Summary
Issued Oct-2014 Measurement Group Data Tab 3-11
ControlWave Flow Measurement Applications Guide
Reverse Uncorrected Flow Rate
This field displays the current uncorrected flow rate of gas in the reverse direction for this station.
Reverse Energy Rate
This field displays the current energy rate of gas in the reverse direction for this station.
Back to Station Summary
Click here to return to the
page.
Forward Current Hour
Forward Corrected Volume
This field displays the corrected volume of gas in the forward direction for this station for the current hour.
Forward Uncorrected Volume
This field displays the uncorrected volume of gas in the forward hour.
Forward Accumu late d Energy
This field displays the accumulated energy of gas in the forward direction for this hour.
Reverse Current Hour
Reverse Corrected Volume
This field displays the corrected volume of gas in the reverse direction for this
Reverse Uncorrected Volume
This field displays the uncorrected volume of gas in the reverse direction for this station for the current hour.
Reverse Accumulated Energy
This field displays the accumulated energy of gas in the reverse direction for this station for the current hour.
Forward Previous Hour
Forward Corrected Volume
This field displays the corrected volume of gas in the forward direction for this station for the previous hour.
Forward Uncorrected Volume
This field displays the uncorrected volume of gas in the forward direction for this station for the previous hour.
Forward Accumu late d Energy
This field displays the accumulated energy of gas in the forward direction for this station for the previous hour.
Reverse Previous Hour
Station Summary
direction for this station for the current
station for the current
station for the current hour.
3-12 Measurement Group Data Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Reverse Corrected Volume
This field displays the corrected volume of gas in the reverse direction for this station for the previous hour.
Reverse Uncorrected Volume
This field displays the uncorrected volume of gas in the reverse direction for this station for the previous hour.
Reverse Accumulated Energy
This field displays the accumulated energy of gas in the reverse direction for this station for the previous hour.
Forward Current Day
Forward Corrected Volume
This field displays the corrected volume of gas in the forward direction for this station for the current day.
Forward Uncorrected Volume
This field displays the uncorrected volume of gas in the forward direction for this station for the current day.
Forward Accumu late d Energy
This field displays the accumulated energy of gas in the forward direction for this station for the current day.
Reverse Current Day
Reverse Corrected Volume
This field displays the corrected volume of gas in the reverse direction for this station for the current day.
Reverse Uncorrected Volume
This field displays the uncorrected volume of gas in the reverse direction for this station for the current day.
Reverse Accumulated Energy
This field displays the accumulated energy of gas in the reverse direction for this station for the current day.
Forward Previous Day
Forward Corrected Volume
This field displays the corrected volume of gas in the forward direction for this station for the previous day.
Forward Uncorrected Volume
This field displays the uncorrected volume of gas in the forward direction for this station for the previous day.
Forward Accumu late d Energy
This field displays the accumulated energy of gas in the forward direction for this station for the previous day.
Reverse Previous Day
Reverse Corrected Volume
This field displays the corrected volume of gas in the reverse direction for this station for the previous day.
Issued Oct-2014 Measurement Group Data Tab 3-13
ControlWave Flow Measurement Applications Guide
Reverse Uncorrected Volume
This field displays the uncorrected volume of gas in the reverse direction for this station for the previous day.
Reverse Accumulated Energy
This field displays the accumulated energy of gas in the reverse direction for this station for the previous day.
Forward Accumulator
Forward Corrected Volume
This field displays a running total of the corrected volume in the forward direction since that last time the accumulator was reset.
Forward Uncorrected Volume
This field displays a running total of the uncorrected volume in the forward direction since that last time the accumulator was reset.
Forward Accumu late d Energy
This field displays a running total of the energy in the forward direction since that last time the accumulator was reset.
Reverse Accumulator
Reverse Corrected Volume
This field displays a running total of the corrected volume in the reverse direction since that last time the accumulator was reset.
Reverse Uncorrected Volume
This field displays a running total of the uncorrected volume in the reverse direction since that last time the accumulator was reset.
Reverse Accumulated Energy
This field displays a running total of the energy in the reverse direction since that last time the accumulator was reset.
3-14 Measurement Group Data Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Chapter 4 – Using the Measurement Group Config Tab
This chapter discusses various flow measurement application configuration pages for your ControlWave EFM, GFC, GFC Plus, Corrector, or XFC.
In This Chapter
4.1 Accessing the Config Tab ............................................................................................ 4-2
4.2 Meter Run I/O Configuration ........................................................................................ 4-3
4.3 Alarm Configuration ................................................................................................... 4-13
4.4 Analog Input/Output Configuration ............................................................................. 4-19
4.5 Auto-Adjust Configuration .......................................................................................... 4-22
4.6 Transmitter Configuration ........................................................................................... 4-26
4.7 Basic Flow Setup........................................................................................................ 4-28
4.7.1 Basic Flow Setup – AGA3TERM ............................................................ 4-28
4.7.2 Basic Flow Setup – AGA3I ..................................................................... 4-31
4.7.3 Basic Flow Setup – AGA7 ...................................................................... 4-35
4.7.4 Basic Flow Setup – Coriolis .................................................................... 4-38
4.8 Flow Equation Selection and Details ......................................................................... 4-40
4.8.1 Differential Measurement – AGA3I (1992 equation) .............................. 4-41
4.8.2 Differential Measurement – AGA3TERM (1985 equation) ..................... 4-45
4.8.3 Linear Measurement – AGA7 ................................................................. 4-48
4.8.4 Coriolis Measurement ............................................................................. 4-51
4.9 Compressibility Setup ................................................................................................ 4-53
4.10 GC Summary .............................................................................................................. 4-57
4.11 Chromatograph Component Range Setup ................................................................ 4-64
4.12 Sampler and Odorizer Output Configuration.............................................................. 4-69
4.13 Mechanical Counter Configuration ............................................................................. 4-72
4.14 Nominations ............................................................................................................... 4-73
4.15 Flow Control and Valve Control ................................................................................. 4-78
4.16 Run Switching ............................................................................................................ 4-85
Revised Oct-2014 Measurement Group Config Tab 4-1
ControlWave Flow Measurement Applications Guide
4.1 Accessing the Config Tab
1. Within TechView, if you are in any group other than the
Measurement group, click the Measurement group icon.
2. Click the Config tab.
Config
Measurement group icon
Figure 4-1. Measurement Group Config tab
4-2 Measurement Group Config Tab Revised Oct-2014
4.2 Meter Run I/O Configuration
The Meter Run I/O Configuration page lets you specify the flow direction of the meter run, and assign process I/O module points or transmitter values to the pressure and temperature process variables.
ControlWave Flow Measurement Applications Guide
Calling up this Menu
Click
Figure 4-2. Meter Run I/O Configuration page
Revised Oct-2014 Measurement Group Config Tab 4-3
ControlWave Flow Measurement Applications Guide
Field Description Meter Run I/O
Configuration for Run#
Flow Direction
Direction Source
Alarm Configuration
Select the number of the meter run for which you want to configure I/O.
Use this button to specify, for the application, the direction that gas flows through the pipe.
The label on this button shows the current configured direction of gas flow. When you click the button you toggle the direction.
Click Forward to specify a reverse flow direction. The button now displays Reverse.
Click Reverse to specify a forward flow direction. The button now displays Forward.
Use this field to specify, for the application, the source that determines the direction of gas flow through the pipe.
Note: The EFM does not support this field; only the GFC/XFC.
Choices are:
DP/HSC The application uses differential
DI The application uses a discrete input Master The application switches direction based
Click here to bring up the Alarm Configuration page. See Section 4.3.
pressure (DP) or frequency to switch direction.
(DI) to switch direction. on commands from the master node’s
Station Manager application.
Differential Pressure
Source
4-4 Measurement Group Config Tab Revised Oct-2014
Select the source for differential pressure data for this meter run. The choices are:
Analog Input Data comes from a pressure transmitter
connected to a 4 to 20mA (or 1 to 5V) analog input (AI) on the process I/O module. You must identify the Point ID on the process I/O module to which the transmitter is connected.
Wet End Data comes from an internal differential
pressure (DP) sensor. “Wet” refers to the portion of the sensor in physical contact with the gas.
BSAP Data comes from an external Bristol
transmitter (3808 or 3508) via an RS­485 communication port.
ControlWave Flow Measurement Applications Guide
Modbus Data comes from an external transmitter
via an RS-485 communication port. This function supports the register list of the Rosemount 3095 multivariable transmitter. Note: This function
requires the ControlWave EFM with an Expansion Communication Module (ECOM).
Point ID
Zeros & Spans Click here to go to the Analog Input/Output Configuration
BSAP Transmitter #
Modbus Transmitter #
Live Input Value
For the EFM: Specify the analog input (AI) point ID for differential pressure on the process I/O module. For other units, this shows the fixed point ID.
page. See Section 4.4.
Specify the number of the BSAP transmitter. Click on the link to open the Transmitter Configuration page, see
Section 4.6.
Specify the number of the Modbus transmitter. Click on the link to open the Transmitter Configuration page, see
Section 4.6.
Shows the current differential pressure reading coming from the specified Source.
OOR Shows OOR (out-of-range) if the differential pressure live
input is out of range. Otherwise this shows NORMAL.
Input Control (Live/Override)
Value in Use
Units
Static Pressure
The label on this button shows whether the differential pressure used by the application is a live input reading or an override value you specify. When you click the button you toggle between these two cases.
Click LIVE to force the application to use the override specified by Value in Use. The button now displays OVERRIDE.
Click OVERRIDE to force the application to use the live input reading for differential pressure. The button now displays LIVE.
You can specify an override value here. To force the override, you must set Input Control to OVERRIDE.
Shows the engineering units for differential pressure.
Source
Revised Oct-2014 Measurement Group Config Tab 4-5
Select the source for static pressure data for this meter run. The choices are:
ControlWave Flow Measurement Applications Guide
Analog Input Data comes from a pressure transmitter
Wet End Data comes from an internal static
BSAP Data comes from an external Bristol
Modbus Data comes from an external transmitter
Point ID
Zeros & Spans Click here to go to the Analog Input/Output Configuration
For EFM: Specify the analog input (AI) point ID for static pressure on the process I/O module. For other units, this shows the fixed point ID.
page. See Section 4.4.
connected to a 4 to 20mA (or 1 to 5V) analog input (AI) on the process I/O module. You must identify the Point ID on the process I/O module to which the transmitter is connected.
pressure (SP) sensor.
transmitter (3808 or 3508) via an RS­485 communication port.
via an RS-485 communication port. This function supports the register list of the Rosemount 3095 multivariable transmitter. Note: This function
requires the ControlWave EFM with an Expansion Communication Module (ECOM).
BSAP Transmitter #
Modbus Transmitter #
Live Input Value
OOR Shows OOR (out-of-range) if the static pressure live input
Input Control (Live/Override)
Specify the number of the BSAP transmitter. Click on the link to open the Transmitter Configuration page, see
Section 4.6.
Specify the number of the Modbus transmitter. Click on the link to open the Transmitter Configuration page, see
Section 4.6.
Shows the current static pressure reading coming from the specified Source.
is out of range. Othewise this shows NORMAL.
The label on this button shows whether the static pressure used by the application is a live input reading or an override value you specify. When you click the button you toggle between these two cases.
Click LIVE to force the application to use the override specified by Value in Use. The button now displays OVERRIDE.
Click OVERRIDE to force the application to use the live input reading for static pressure. The button now displays
4-6 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
LIVE.
Value in Use
Units
Temperature
Source
Point ID
Zeros & Spans Click here to go to the Analog Input/Output Configuration
You can specify an override value here. To force the override, you must set Input Control to OVERRIDE.
Shows the engineering units for static pressure.
Select the source for temperature data for this meter run. The choices are:
Analog Input Data comes from a temperature
transmitter connected to a 4 to 20mA (or 1 to 5V) analog input (AI) on the process I/O module. You must identify the Point ID on the process I/O module to which the transmitter is connected.
Wet End Data comes from a temperature sensor.
BSAP Data comes from an external Bristol
transmitter (3808 or 3508) via an RS­485 communication port.
Modbus Data comes from an external transmitter
via an RS-485 communication port. This function supports the register list of the Rosemount 3095 multivariable transmitter. Note: This function
requires the ControlWave EFM with an Expansion Communication Module (ECOM).
For EFM: Specify the analog input (AI) point ID for temperature on the process I/O module. For other units, this shows the fixed point ID.
page. See Section 4.4.
BSAP Transmitter #
Modbus Transmitter #
Live Input Value
Revised Oct-2014 Measurement Group Config Tab 4-7
Specify the number of the BSAP transmitter. Click on the link to open the Transmitter Configuration page, see
Section 4.6.
Specify the number of the Modbus transmitter. Click on the link to open the Transmitter Configuration page, see
Section 4.6.
Shows the current temperature reading coming from the specified Source.
ControlWave Flow Measurement Applications Guide
OOR Shows OOR (out-of-range) if the temperature live input is
out of range. Otherwise this shows NORMAL.
Input Control (Live/Override)
Value in Use
Units
Frequency Input
Source
Units
The label on this button shows whether the temperature used by the application is a live input reading or an override value you specify. When you click the button you toggle between these two cases.
Click LIVE to force the application to use the override specified by Value in Use. The button now displays OVERRIDE.
Click OVERRIDE to force the application to use the live input reading for temperature. The button now displays LIVE.
You can specify an override value here. To force the override, you must set Input Control to OVERRIDE.
Shows the engineering units for temperature.
The label on this button shows whether the frequency input comes from a high speed counter (pulse input) or an auto-adjust turbine meter. When you click the button you toggle between these two cases.
Click High Speed Counter to force the application to use the auto-adjust turbine meter as the frequency source. The button now displays Auto Adjust Module.
Click Auto Adjust Module to force the application to use the high speed counter (pulse input) as the frequency source. The button now displays High Speed Counter.
Shows the engineering units for frequency.
Value in Use (Frequency)
Pulse Input
Point ID
Low Frequency
4-8 Measurement Group Config Tab Revised Oct-2014
Shows the frequency value in use, whether the live value or an override value.
For EFM: Specify the point ID for the pulse input on the process I/O module. For other units, this shows the fixed point ID.
The label on this button shows whether the frequency input that comes from the high speed counter (pulse input) is high frequency or low frequency. When you click the button you toggle between these two cases.
Click ENABLED to specify for the application that the
Input Control (Live/Override)
# of Samples (2-50)
ControlWave Flow Measurement Applications Guide
input is high frequency. The button now displays DISABLED.
Click DISABLED to specify for the application that the input is low frequency. The button now displays ENABLED.
The label on this button shows whether the frequency input used by the application is a live input reading or an override value you specify. When you click the button you toggle between these two cases.
Click LIVE to force the application to use the override specified by Override Value (Frequency). The button now displays OVERRIDE.
Click OVERRIDE to force the application to use the live input reading for frequency. The button now displays LIVE.
Specify the number of samples (from 2 to 50) used by the pulse input.
Live Input Value (Counts)
Deadband (sec)
Override Value (Frequency)
LF Filter
Threshold (%)
Shows the number of counts registered by the pulse input.
Specify the deadband (in seconds). If there are no pulses during this time, the application assumes the pulse count is zero.
If you want to override the live input reading for the pulse input, enter a desired value for the frequency here and toggle the Input Control LIVE/OVERRIDE button to OVERRIDE.
The label on this button shows whether the low frequency (LF) filter is active for the pulse input. When you click the button you toggle between these two cases.
Click ENABLED to specify for the application that the low frequency (LF) filter in inactive. The button now displays DISABLED.
Click DISABLED to specify for the application that the low frequency (LF) filter in active. The button now displays ENABLED.
Shows the allowable percentage above the average time for the pulse.
Auto-Adjust Input The auto-adjust input uses both high speed counter
inputs, one for the main rotor, the other for the sense rotor.
Revised Oct-2014 Measurement Group Config Tab 4-9
ControlWave Flow Measurement Applications Guide
Configuration
Main Rotor Point ID
Input Control (Live/Override)
Live Input Value (Frequency)
Override Value (Frequency)
Sensor Rotor Point ID
Input Control (Live/Override)
Live Input Value (Counts)
Click this link to call up the Auto-Adjust Configuration page. See Section 4.5.
For EFM: Specify the point ID for the pulse input connected to the turbine meter’s main rotor. For other units, this shows the fixed point ID.
The label on this button shows whether the pulse input used by the application for the main rotor is a live input or an override value you specify. When you click the button you toggle between these two cases.
Click LIVE to force the application to use the override specified by Override Value (Frequency). The button now displays OVERRIDE.
Click OVERRIDE to force the application to use the live pulse input for frequency. The button now displays LIVE.
Shows the current frequency reading coming from the main rotor.
If you want to override the live input reading for this pulse input, enter a desired value for the frequency here and toggle the Input Control LIVE/OVERRIDE button to OVERRIDE.
For EFM: Specify the point ID for the pulse input connected to the turbine meter’s sense rotor. For other units, this shows the fixed point ID.
The label on this button shows whether the pulse input used by the application for the sense rotor is a live input or an override value you specify. When you click the button you toggle between these two cases.
Click LIVE to force the application to use the override specified by Override Value (Frequency). The button now displays OVERRIDE.
Click OVERRIDE to force the application to use the live pulse input for frequency. The button now displays LIVE.
Shows the current frequency reading coming from the sense rotor.
Override Value (Frequency)
Heating Value
4-10 Measurement Group Config Tab Revised Oct-2014
If you want to override the live input reading for this pulse input, enter a desired value for the frequency here and toggle the Input Control LIVE/OVERRIDE button to OVERRIDE.
ControlWave Flow Measurement Applications Guide
Source
AGA5 Value When Source is AGA5, shows the heating value as
AGA5 Units
Select the source for heating value data for this meter run. The choices are:
Analog Input The heating value comes from a 4 to
20mA (or 1 to 5V) analog input (AI) on the process I/O module. You must identify the Point ID on the process I/O module which provides the heating value. Note: This option is only
available for the EFM.
AGA5 The heating value comes from AGA5
calculations performed by the ControlWave flow computer. To use this you must enter component mole percent values on the Chromatograph Setup page. See Section 4.11.
Chromatograph The heating value comes from an
external chromatograph using Modbus communications.
Manual Entry You enter the heating value directly in
the Manual Entry Value field.
calculated based on the AGA5 equation with component mole percent data for the chromatograph.
Shows the engineering units for the calculated AGA5 heating value.
Value in Use
Units
Point ID If the Source of the heating value is an Analog Input,
Zeros & Spans
Value
Units
Shows the heating value currently used by the application, which could be from any of the four sources.
Shows the engineering units for the heating value currently in use.
specify the point ID for the analog input on the process I/O module. Note: This field is only available for the
EFM.
Click here to go to the Analog Input/Output Configuration page. See Section 4.4. Note: This field is only available
for the EFM.
Shows the heating value as provided by the analog input. Note: This field is only available for the EFM.
Shows the engineering units for the heating value from the analog input. Note: This field is only available for
the EFM.
Revised Oct-2014 Measurement Group Config Tab 4-11
ControlWave Flow Measurement Applications Guide
Chromatograph Value When Source is Chromatograph, shows the heating
value as provided by the chromatograph.
Units
Manual Entry
Value When Source is Manual Entry, enter the known heating
Units
Specify the engineering units for the heating value from the chromatograph.
value in this field.
Specify the engineering units for the heating value here.
4-12 Measurement Group Config Tab Revised Oct-2014
4.3 Alarm Configuration
The Alarm Configuration page lets you configure the alarm limits and deadbands for the pressure, temperature, frequency, and flow rate variables used in this meter run.
ControlWave Flow Measurement Applications Guide
Calling up this Menu
Click > Alarm Configuration
Figure 4-3. Alarm Configuration page
Field Description Alarm Configuration for
Run#
Differential Pressure
Differential Pressure Enable/Disable
Revised Oct-2014 Measurement Group Config Tab 4-13
Select the meter run number for which you want to configure alarms.
The label on this button shows whether alarming is enabled for the differential pressure variable. When you click the button you toggle between these two cases.
Click Enabled to disable alarming for the differential
ControlWave Flow Measurement Applications Guide
Differential Pressure Units
pressure variable. The button now displays Disabled.
Click Disabled to enable alarming for the differential pressure variable. The button now displays Enabled.
Shows the engineering units for the differential pressure variable.
Differential Pressure Current Value
Differential Pressure HIHI Alarm Limit
Differential Pressure HI Alarm Limit
Differential Pressure High Deadband
Differential Pressure Low Deadband
Differential Pressure Lo Alarm Limit
Shows the current value of the differential pressure variable.
When the differential pressure variable rises above this limit, it triggers a High-High alarm state.
When the differential pressure variable rises above this limit, it triggers a High alarm state.
This deadband is a value that, when subtracted from the high and high-high alarm limits, defines a range within which the alarm state remains active, even though the value falls below the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
This deadband is a value that, when added to the low and low-low alarm limits, defines a range within which the alarm state remains active, even though the value rises above the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
When the differential pressure variable falls below this limit, it triggers a Low alarm state.
Differential Pressure LoLo Alarm Limit
Static Pressure
Static Pressure Enable/Disable
Static Pressure Units
4-14 Measurement Group Config Tab Revised Oct-2014
When the differential pressure variable falls below this limit, it triggers a Low-Low alarm state.
The label on this button shows whether alarming is enabled for the static pressure variable. When you click the button you toggle between these two cases.
Click Enabled to disable alarming for the static pressure variable. The button now displays Disabled.
Click Disabled to enable alarming for the static pressure variable. The button now displays Enabled.
Shows the engineering units for the static pressure variable.
ControlWave Flow Measurement Applications Guide
Static Pressure Current Value
Static Pressure HIHI Alarm Limit
Static Pressure HI Alarm Limit
Static Pressure High Deadband
Static Pressure Low Deadband
Static Pressure Lo Alarm Limit
Shows the current value of the static pressure variable.
When the static pressure variable rises above this limit, it triggers a High-High alarm state.
When the static pressure variable rises above this limit, it triggers a High alarm state.
This deadband is a value that, when subtracted from the high and high-high alarm limits, defines a range within which the alarm state remains active, even though the value falls below the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
This deadband is a value that, when added to the low and low-low alarm limits, defines a range within which the alarm state remains active, even though the value rises above the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
When the static pressure variable falls below this limit, it triggers a Low alarm state.
Static Pressure LoLo Alarm Limit
Temperature
Temperature Enable/Disable
Temperature Units
Temperature Current Value
Temperature HIHI Alarm Limit
When the static pressure variable falls below this limit, it triggers a Low-Low alarm state.
The label on this button shows whether alarming is enabled for the temperature variable. When you click the button you toggle between these two cases.
Click Enabled to disable alarming for the temperature variable. The button now displays Disabled.
Click Disabled to enable alarming for the temperature variable. The button now displays Enabled.
Shows the engineering units for the temperature variable.
Shows the current value of the temperature variable.
When the temperature variable rises above this limit, it triggers a High-High alarm state.
Temperature HI Alarm Limit
Revised Oct-2014 Measurement Group Config Tab 4-15
When the temperature variable rises above this limit, it triggers a High alarm state.
ControlWave Flow Measurement Applications Guide
Temperature High Deadband
Temperature Low Deadband
Temperature Lo Alarm Limit
Temperature LoLo Alarm Limit
Frequency
Frequency Enable/Disable
Frequency Units
This deadband is a value that, when subtracted from the high and high-high alarm limits, defines a range within which the alarm state remains active, even though the value falls below the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
This deadband is a value that, when added to the low and low-low alarm limits, defines a range within which the alarm state remains active, even though the value rises above the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
When the temperature variable falls below this limit, it triggers a Low alarm state.
When the temperature variable falls below this limit, it triggers a Low-Low alarm state.
The label on this button shows whether alarming is enabled for the frequency variable. When you click the button you toggle between these two cases.
Click Enabled to disable alarming for the frequency variable. The button now displays Disabled.
Click Disabled to enable alarming for the frequency variable. The button now displays Enabled.
Shows the engineering units for the frequency variable.
Frequency Current Value
Frequency HIHI Alarm Limit
Frequency HI Alarm Limit
Frequency High Deadband
Frequency Low Deadband
4-16 Measurement Group Config Tab Revised Oct-2014
Shows the current value of the frequency variable.
When the frequency variable rises above this limit, it triggers a High-High alarm state.
When the frequency variable rises above this limit, it triggers a High alarm state.
This deadband is a value that, when subtracted from the high and high-high alarm limits, defines a range within which the alarm state remains active, even though the value falls below the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
This deadband is a value that, when added to the low and low-low alarm limits, defines a range within which the alarm state remains active, even though the value rises above the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by
ControlWave Flow Measurement Applications Guide
minor changes in the variable.
Frequency Lo Alarm Limit
Frequency LoLo Alarm Limit
Flow Rate
Flow Rate Enable/Disable
Flow Rate Units
Flow Rate Current Value
When the frequency variable falls below this limit, it triggers a Low alarm state.
When the frequency variable falls below this limit, it triggers a Low-Low alarm state.
The label on this button shows whether alarming is enabled for the flow rate variable. When you click the button you toggle between these two cases.
Click Enabled to disable alarming for the flow rate variable. The button now displays Disabled.
Click Disabled to enable alarming for the flow rate variable. The button now displays Enabled.
Shows the engineering units for the flow rate variable.
Shows the current value of the flow rate variable.
Flow Rate HIHI Alarm Limit
Flow Rate HI Alarm Limit
Flow Rate High Deadband
Flow Rate Low Deadband
Flow Rate Lo Alarm Limit
Flow Rate LoLo Alarm Limit
When the flow rate variable rises above this limit, it triggers a High-High alarm state.
When the flow rate variable rises above this limit, it triggers a High alarm state.
This deadband is a value that, when subtracted from the high and high-high alarm limits, defines a range within which the alarm state remains active, even though the value falls below the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
This deadband is a value that, when added to the low and low-low alarm limits, defines a range within which the alarm state remains active, even though the value rises above the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
When the flow rate variable falls below this limit, it triggers a Low alarm state.
When the flow rate variable falls below this limit, it triggers a Low-Low alarm state.
Revised Oct-2014 Measurement Group Config Tab 4-17
ControlWave Flow Measurement Applications Guide
Battery Alarm Configuration
DO Point
Battery HIHI Alarm Limit Setting
Battery HI Alarm Limit Setting
Battery High Deadband Setting
Battery Low Deadband Setting
Battery Lo Alarm Limit Setting
Select the discrete output (DO) that will serve as a battery voltage alarm.
When the battery voltage rises above this limit, it triggers a High-High alarm state.
When the battery voltage rises above this limit, it triggers a High alarm state.
This deadband is a value that, when subtracted from the high and high-high alarm limits, defines a range within which the alarm state remains active, even though the value falls below the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
This deadband is a value that, when added to the low and low-low alarm limits, defines a range within which the alarm state remains active, even though the value rises above the limit. The purpose of the deadband is to avoid fluctuations in and out of the alarm state by minor changes in the variable.
When the battery voltage falls below this limit, it triggers a Low alarm state.
Battery LoLo Alarm Limit Setting
When the battery voltage falls below this limit, it triggers a Low-Low alarm state.
4-18 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
4.4 Analog Input/Output Configuration
The Analog Input/Output Configuration page allows you to configure zeros and spans for analog I/O variables.
Calling up this Menu
(3 ways)
Click > Zeros & Spans Click > Zeros & Spans Click > AO Zero & Span
Figure 4-4. Analog Input/Output Configuration
Field Description
Input x
The number of input variables varies depending upon
the type of ControlWave device. ControlWave EFM can have up to four inputs, other units can have three.
Live Value
OOR Alarm
Zero
Span Enter the value that, when added to the Zero value,
Revised Oct-2014 Measurement Group Config Tab 4-19
The current value of the analog input.
Shows ON when I/O hardware indicates this analog input is out-of-range (OOR). Otherwise shows OFF.
Enter the value that this analog input process variable should read when the AI field input is 4mA.
represents what the process variable should display when the AI field input is 20mA.
ControlWave Flow Measurement Applications Guide
Units
OOR (Software) Alarm % Below Zero/Above Span
Output
Variable
Live Value
The engineering units for this analog input.
If you enter a positive value here, it specifies the percentage below zero or above span which constitutes an out-of-range condition for the analog input.
If you enter zero here, it specifies that the hardware detects the out-of-range (OOR) condition, instead of using a value you specify.
Choose which variable you want to assign to the analog output (AO).
The current value of the analog output.
Zero
Span Enter the value that, when added to the Zero value,
Integrated Wet End Inputs
Damping
Raw Value
Alarm Shows ON if this variable is in an alarm state.
Enter the value that this analog output process variable should read when the AO field output is 4mA.
represents what the process variable should display when the AO field output is 20mA.
These are the ControlWave’s integrated sensors for differential pressure, static pressure, and temperature.
The label on this button shows the current state of the damping function for the differential pressure input. When you click the button you toggle the state.
Click Disabled to start damping. The button now displays Enabled.
Click Enabled to turn off damping. The button now displays Disabled.
Shows the value from the sensor without any damping applied.
4-20 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Value in Use
Units
Digital Inputs These fields are not available for the ControlWave
Digital Input x
Digital Outputs
Digital Output x
Shows the value used in gas calculations. This may differ from the raw value either because it reflects damping of the input or an override is in effect.
The engineering units for this analog input.
EFM.
These fields show the current value of the associated discrete input.
These fields are not available for the ControlWave EFM.
These fields show the current value of the associated discrete output.
Revised Oct-2014 Measurement Group Config Tab 4-21
ControlWave Flow Measurement Applications Guide
4.5 Auto-Adjust Configuration
The Auto-Adjust Configuration page lets you enter configuration data for using the application with an auto-adjust turbine meter.
Calling up this Menu
Click > Auto-Adjust Input Configuration
Figure 4-5. Auto-Adjust Configuration page
Field Description Auto-Adjust
Configuration for Run#
4-22 Measurement Group Config Tab Revised Oct-2014
Select the meter run number for which you want to configure an auto-adjust turbine meter.
ControlWave Flow Measurement Applications Guide
Inputs
Main Rotor Accum. Count
Sense Rotor Accum. Count
Main Rotor Override
Sense Rotor Override
Status There are four different status values.
Status 1
Shows the current accumulated count for the main rotor of the auto-adjust turbine meter. The main rotor is the upstream rotor and has a greater
blade angle to the flow of gas.
Shows the current accumulated count for the sense rotor of the auto-adjust turbine meter. The sense rotor is the downstream rotor and has a shallower blade angle to the flow of gas.
Specify the frequency the main rotor of the auto-adjust turbine meter should use when override is active.
Specify the frequency the sensor rotor of the auto­adjust turbine meter should use when override is active.
This status is for the AUTOADJUST function block within the application.
Value Explanation
0 Successful execution
Status 2
Status 3
-4 Invalid data type in AUTOADJUST function block
-6 Required input not configured for AUTOADJUST function block
-17 Required input data not valid for AUTOADJUST function block
-16001 No memory available
-16002 LIST for AUTOADJUST function block is missing required parameters
-16003 Non-steady flow
Value Explanation
0 Successful execution
-16004 Delta A is outside normal limits
-16005 Delta A is outside abnormal limits
Value Explanation
0 Successful execution
-16005 Delta A is outside abnormal limits
Stat us 4 Value Explanation
0 Successful execution
-16006 No flow or loss of main and sensor pulses
Revised Oct-2014 Measurement Group Config Tab 4-23
ControlWave Flow Measurement Applications Guide
Calibration Data
-16007 Leakage or resonant no net flow (with ABN=
-16005)
-16008 No main rotor pulses or leakage or resonant no net flow
-16009 No sensor rotor pulse
Blade-Tip Sensor Factor
Main Rotor Factor
Sensor Rotor Factor
Average Relative Adjustment
Configuration Data
Abnormal delta-Abar high limit in percent
Abnormal delta-Abar low limit in percent
Normal delta-Abar high limit in percent
Normal delta-Abar low limit in percent
The blade tip sensor factor (BTSF) should be 1.0 for slot sensors.
The main rotor is the upstream rotor and has a greater blade angle to the flow of gas.
The sense rotor is the downstream rotor and has a shallower blade angle to the flow of gas.
The expected deviation (average relative adjustment) between main and sense rotors.
This is the high alarm limit for an abnormal deviation between the main and sense rotors.
This is the low alarm limit for an abnormal deviation between the main and sense rotors.
This is the high alarm limit for a normal deviation between the main and sense rotors.
This is the low alarm limit for a normal deviation between the main and sense rotors.
Adjusted and un­adjusted flow total scaling factor
Mechanical output factor
Calculated Factors
Adjusted volume rate in CF per second
Adjusted Main rotor rate in CF per second
Adjusted Sensor rotor rate in CF per second
4-24 Measurement Group Config Tab Revised Oct-2014
Specify a scaling factor which the software applies to the adjusted and un-adjusted flow totals to present the flow in the desired engineering units.
Used to determine unadjusted volume totals with only main rotor pulses. Set to 0 if these are not needed.
Shows the adjusted volume rate in cubic feet (CF) per second.
Shows the adjusted main rotor rate in cubic feet (CF) per second.
Shows the adjusted sensor rotor rate in cubic feet (CF) per second.
ControlWave Flow Measurement Applications Guide
A
Main rotor adjusted volume
Sensor rotor adjusted volume
Internal 60 second timer
Internal 512 second timer
Internal count of Main rotor pulses
Main rotor frequency in pulses per second
Sensor rotor frequency in pulses per second
Shows the main rotor adjusted volume.
Shows the sensor rotor adjusted volume.
This count increments only when main rotor frequency is less than 3 times the blade tip sensor factor (BTSF).
When the Main rotor frequency is below 48 Hz (i.e. more than 512 seconds to accumulate 25,000 counts) this parameter reaches 512 and rolls over, which forces a check of the sensor rotor frequency, and clears the Internal count of Main rotor pulses.
t 25,000 counts this rolls over which forces a check of the Sensor rotor frequency and clears the internal 512 second timer.
Shows the frequency of the main rotor in pulses per second.
Shows the frequency of the sensor rotor in pulses per second.
Delta time between function block executions
Calculated Outputs
Adjusted Flow rate in CF per hour
Unadjusted Main rotor rate in CF per second
Unadjusted Sensor rotor rate in CF per second
Calculated deviation of Abar from calibration in percent
Adjusted volume change since the last function block execution
Total adjusted volume
Shows the time between executions of the AUTOADJUST function block in the ControlWave project.
Shows the adjusted flow rate in cubic feet (CF) per hour.
Shows the unadjusted main rotor rate in cubic feet (CF) per second.
Shows the unadjusted sensor rotor rate in cubic feet (CF) per second.
The application calculates how much the meter has changed from factory calibration.
Shows the change in the adjusted volume since the last execution of the AUTOADJUST function block in the ControlWave project.
Shows the total adjusted volume.
Total unadjusted volume
Shows the total unadjusted volume.
Revised Oct-2014 Measurement Group Config Tab 4-25
ControlWave Flow Measurement Applications Guide
4.6 Transmitter Configuration
The Transmitter Configuration page lets you specify which transmitters provide process variable inputs to the application.
Calling up this Menu
Click > Transmitter
Figure 4-6. Transmitter Configuration page (only transmitters 1 and 2 visible)
Field Description
Transmitter x
Status
BSAP Enabled/Disabled
Shows the transmitter type which could be:
DP/PT/TEMP, PT/TEMP, or TEMP. Shows NOT CONFIGURED if this transmitter has not been
configured. You can view data for up to four transmitters on this page.
Shows a status code value from the transmitter. See the ControlWave Designer online help for the CUSTOM function block for information on possible status values.
The label on this button shows whether BSAP communication is enabled for this transmitter variable. When you click the button you toggle between these two cases.
Click Enabled to disable alarming for the temperature variable. The button now displays Disabled.
4-26 Measurement Group Config Tab Revised Oct-2014
4088B/3808
BSAP Address
ControlWave Flow Measurement Applications Guide
Click Disabled to enable alarming for the temperature variable. The button now displays Enabled.
The label on this button shows that the type of device (3808 or 4088B) for which the application is configured. Click the button to toggle between these choices.
Click 4088B to configure the application to communicate with a Bristol 3808. The button now displays 3808.
Click 3808 to configure the application to communicate with a Rosemount 4088B. The button now displays 4088B.
Enter the BSAP local address assigned to this transmitter.
Value From Transmitter
Units Shows the engineering units for the associated Value
Modbus Port
Modbus Address
Transmitters can display data from up to three variables. Typically these are differential pressure, static pressure, and temperature.
From Transmitter.
For EFM: Enter the number of the port used for Modbus communication. For other units shows the fixed port.
Enter the Modbus address for this transmitter.
Revised Oct-2014 Measurement Group Config Tab 4-27
ControlWave Flow Measurement Applications Guide
4.7 Basic Flow Setup
The Basic Flow Setup pages let you modify the most important parameters for the flow measurement equation, and view various current values.
Note: This menu varies in appearance depending upon the flow equation
you select. If you have not previously selected the flow measurement equation, this button will automatically re-direct you to the flow measurement selection and detail pages. See Section
4.8.
Calling up this Menu
Click
4.7.1 Basic Flow Setup – AGA3TERM
There are two different AGA3 equations supported, the AGA3I equation from the 1992 AGA report, and the AGA3TERM equation from the 1985 AGA report.
Figure 4-7. Basic Flow Setup – AGA3TERM
Notes:
If you want to choose the AGA3I calculation, instead of the
AGA3TERM calculation, click the Click Here to Select AGA3I (1992) button.
4-28 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
If you chose differential measurement by mistake, and need to choose
either linear measurement or coriolis measurement instead, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
Field Description Basic Flow For Run#
Inputs
Select the meter run number for which you want to configure AGA3 term measurement.
Pressure Tap
Low Flow Cutoff
Orifice Diam.
Pipe Diam.
Orifice Const. K
Adjust Press.
Station Elevation
Local Press.
Click this button to change the specified location of the pressure tap. The pressure tap can be either upstream or downstream of the meter.
Enter the low flow cutoff here. This the minimum value for differential pressure where the application performs measurements. If the differential pressure drops below this value, the measured flow goes to zero. Select the units for the low flow cutoff.
Enter the orifice bore diameter here and select the proper units.
Enter the inside diameter of the pipe here and select the proper units.
Specify the combined orifice constant K. This is typically the value for orifice thermal expansion unless other corrections are required.
Specify the average barometric pressure and select the proper units.
Specify the station elevation above sea level and choose the appropriate units. The default units are feet.
Show the local atmospheric pressure calculated based on inputs including the station elevation.
Use Adjust or Local Press.
Revised Oct-2014 Measurement Group Config Tab 4-29
The label on this button shows whether you use the calculated local pressure or the adjusted pressure. When you click the button you toggle between these two cases.
Click Adjust to specify that the application should use local pressure. The button now displays Local.
Click Local to specify that the application should use adjusted pressure. The button now displays Adjust.
ControlWave Flow Measurement Applications Guide
Base Temp.
Base Press.
Contract Hour
Status
Flow
Diff. Press
Static Press.
Temperature
Specify the required (contract) base temperature of the flowing gas and the associated engineering units.
Specify the base or contract pressure of the gas and the associated units.
Specify the hour (0 to 23) which marks the beginning of the “gas day.”
Shows the current calculated flow reading.
Shows the differential pressure across the orifice plate.
Shows the upstream or downstream static pressure.
Shows the temperature of the flowing gas.
Low Flow Cut Off Shows Cutoff if the flow is too low and so the low flow
cut off is currently active. Shows Flowing when cutoff is not active.
Selected Compressibility Calculation
Click to Select NX19/AGA8 Detail/AGA8 Gross
Stream x Shows Raw/GC if there are no errors. Shows Fixed if
BTU
Shows the currently selected type of compressibility calculation.
Click the NX-19 button to select NX-19 as the compressibility calculation.
Click the AGA8 Detail button to select AGA8 Detail as the compressibility calculation.
Click the AGA8 Gross button to select AGA8 Gross as the compressibility calculation.
the calculation is using fixed values for components of the gas stream, typically because of a chromatograph failure.
Shows the current British Thermal Units (BTU) for this gas stream.
Gravity
Shows the gravity value for this gas stream.
4-30 Measurement Group Config Tab Revised Oct-2014
4.7.2 Basic Flow Setup – AGA3I
There are two different AGA3 equations supported, the AGA3I equation from the 1992 AGA report, and the AGA3TERM equation from the 1985 AGA report.
ControlWave Flow Measurement Applications Guide
Figure 4-8. Basic Flow Setup – AGA3I
Notes:
If you want to choose the AGA3TERM calculation, instead of the
AGA3I calculation, click the Click Here to Select AGA3TERM (1985) button.
If you chose differential measurement by mistake, and need to choose
either linear measurement or coriolis measurement instead, you can reset the equation type to undefined, so you can re-select it. To do this, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
Revised Oct-2014 Measurement Group Config Tab 4-31
ControlWave Flow Measurement Applications Guide
Field Description Basic Flow For Run#
Inputs
Select the meter run number for which you want to configure AGA3 iterative measurement.
Pressure Tap
Low Flow Cutoff
Orifice Diam.
Pipe Diam.
Orifice Material
Pipe Material
Isentropic Exponent
Atmospheric Press.
Click this button to change the specified location of the pressure tap. The pressure tap can be either upstream or downstream of the meter.
Enter the low flow cutoff here. This the minimum value for differential pressure where the application performs measurements. If the differential pressure drops below this value, the measured flow goes to zero. Select the units for the low flow cutoff.
Enter the orifice bore diameter here and select the proper units.
Enter the inside diameter of the pipe here and select the proper units.
The label on this button shows the type of steel used for the orifice. When you click the button you toggle between these two cases.
Click CARBON to specify that stainless steel is the orifice material. The button now displays STNLESS.
Click STNLESS to specify that carbon steel is the orifice material. The button now displays CARBON.
The label on this button shows the type of steel used for the pipe. When you click the button you toggle between these two cases.
Click CARBON to specify that stainless steel is the pipe material. The button now displays STNLESS.
Click STNLESS to specify that carbon steel is the pipe material. The button now displays CARBON.
Specify the fluid Isentropic exponent. This value is used in the calculation of the expansion factor, Y. Typically you should enter 1.3 here, which is the value given in the 1992 American Gas Association (AGA-3)
Report.
Specify the atmospheric pressure value that the application should use for calculations.
4-32 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Station Elevation
Local Press.
Use Adjust or Local Press.
Base Temp.
Base Press.
Specify the station elevation above sea level and choose the appropriate units. The default units are feet.
Show the local atmospheric pressure calculated based on inputs including the station elevation.
The label on this button shows whether you use the calculated local pressure or the adjusted pressure. When you click the button you toggle between these two cases.
Click Adjust to specify that the application should use local pressure. The button now displays Local.
Click Local to specify that the application should use adjusted pressure. The button now displays Adjust.
Specify the base temperature of the gas.
Specify the base pressure. This is used to calculate the pressure base factor
Viscosity
Contract Hour
Status
Flow
Diff. Press
Static Press.
Temperature
Low Flow Cut Off Shows Cutoff if the flow is too low and so the low flow
Selected Compressibility Calculation
Specify the dynamic viscosity of the gas at flowing conditions. Viscosity is used to calculate the Reynolds number.
Specify the hour (0 to 23) which marks the beginning of the “gas day.”
Shows the current calculated flow reading.
Shows the differential pressure across the orifice plate.
Shows the upstream or downstream static pressure.
Shows the temperature of the flowing gas.
cut off is currently active. Shows Flowing if flow is sufficient that the low flow cut off is not active.
Shows the currently selected type of compressibility calculation.
Revised Oct-2014 Measurement Group Config Tab 4-33
ControlWave Flow Measurement Applications Guide
Click to Select NX19/AGA8 Detail/AGA8 Gross
Stream x Shows Raw/GC if there are no errors. Shows Fixed if
BTU
Gravity
Click the NX-19 button to select NX-19 as the compressibility calculation.
Click the AGA8 Detail button to select AGA8 Detail as the compressibility calculation.
Click the AGA8 Gross button to select AGA8 Gross as the compressibility calculation.
the calculation is using fixed values for components of the gas stream, typically because of a chromatograph failure.
Shows the current British Thermal Units (BTU) for this gas stream.
Shows the gravity value for this gas stream.
4-34 Measurement Group Config Tab Revised Oct-2014
4.7.3 Basic Flow Setup – AGA7
The AGA7 Basic Flow Setup page lets you configure linear flow measurement for this meter run.
ControlWave Flow Measurement Applications Guide
Figure 4-9. Basic Flow Setup – AGA7
Note: If you chose linear measurement by mistake, and need to choose
either differential measurement or coriolis measurement instead, you can reset the equation type to undefined, so you can re-select it. To do this, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
Field Description Basic Flow Setup for
Run#
Inputs
Flow Density
Revised Oct-2014 Measurement Group Config Tab 4-35
Select the meter run number for which you want to configure AGA7 linear measurement.
Specify the density of the flowing gas as measured by a densitometer.
ControlWave Flow Measurement Applications Guide
Base Density
K Factor Units
K Factor
Low Flow Cutoff
Adjust Press.
Station Elevation
Local Press.
Use Adjust or Local Press.
Base Temp.
Specify the contract base density of the gas as measured by a densitometer.
Specify the desired units for the output.
Specify a scale factor to adjust the output to your desired units.
The low flow cutoff is the minimum frequency that will still be considered valid for flow measurement. If the frequency of the inputs from the high speed counter fall below this number, volume will not be measured.
Enter the average barometric pressure here.
Specify the station elevation above sea level and choose the appropriate units. The default units are feet.
Show the local atmospheric pressure calculated based on inputs including the station elevation.
The label on this button shows whether you use the calculated local pressure or the adjusted pressure. When you click the button you toggle between these two cases.
Click Adjust to specify that the application should use local pressure. The button now displays Local.
Click Local to specify that the application should use adjusted pressure. The button now displays Adjust.
Specify the contract base temperature and associated units.
Base Press.
Meter Factor
Contract Hour
Status
Flow
Frequency
4-36 Measurement Group Config Tab Revised Oct-2014
Specify the contract base pressure and associated units.
Specify an optional meter calibration factor here. The AGA7 calculation uses this factor to correct for known variations in the measuring equipment.
Specify the hour (0 to 23) which marks the beginning of the “gas day.”
Shows the calculated flow rate at base conditions.
Shows the live frequency input.
ControlWave Flow Measurement Applications Guide
Static Press.
Temperature
Low Flow Cut Off Shows Cutoff if the flow is too low and so the low flow
Selected Compressibility Calculation
Click to Select NX19/AGA8 Detail/AGA8 Gross
Stream x Shows Raw/GC if there are no errors. Shows Fixed if
BTU
Shows the static gauge pressure of the flowing gas.
Shows the temperature of the flowing gas.
cut off is currently active. Shows Flowing if flow is sufficient that the low flow cut off is not active.
Shows the currently selected type of compressibility calculation.
Click the NX-19 button to select NX-19 as the compressibility calculation.
Click the AGA8 Detail button to select AGA8 Detail as the compressibility calculation.
Click the AGA8 Gross button to select AGA8 Gross as the compressibility calculation.
the calculation is using fixed values for components of the gas stream, typically because of a chromatograph failure.
Shows the current British Thermal Units (BTU) for this gas stream.
Gravity
Shows the gravity value for this gas stream.
Revised Oct-2014 Measurement Group Config Tab 4-37
ControlWave Flow Measurement Applications Guide
4.7.4 Basic Flow Setup – Coriolis
The Basic Flow Setup for Coriolis page lets you configure gas flow measurement using a coriolis meter.
Figure 4-10. Basic Flow Setup – Coriolis
Note: If you chose coriolis measurement by mistake, and need to choose
either differential measurement or linear measurement instead, you can reset the equation type to undefined, so you can re-select it. To do this, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
Field Description Basic Flow Setup for
Run#
Inputs
Air Density
K Factor Units
Select the meter run number for which you want to configure coriolis measurement.
Shows the density of air constant.
Select the engineering units for the coriolis meter.
K Factor
4-38 Measurement Group Config Tab Revised Oct-2014
Specify the correction factor (K) for the coriolis meter. This information is available from the coriolis meter data plate.
ControlWave Flow Measurement Applications Guide
Contract Hour
Status
Flow
Frequency
Static Press.
Temperature
Stream x Shows Raw/GC if there are no errors. Shows Fixed if
BTU
Specify the hour (0 to 23) which marks the beginning of the “gas day.”
Shows the calculated flow rate.
Shows the current frequency from the high speed counter input connected to the coriolis meter.
Shows the static pressure of the flowing gas.
Shows the temperature of the flowing gas.
the calculation is using fixed values for components of the gas stream, typically because of a chromatograph failure.
Shows the current British Thermal Units (BTU) for this gas stream.
Gravity
Shows the gravity value for this gas stream.
Revised Oct-2014 Measurement Group Config Tab 4-39
ControlWave Flow Measurement Applications Guide
4.8 Flow Equation Selection and Details
For each meter run, you must select the type of flow measurement equation you want to use.
Calling up this Menu
Selecting the Type of
Measurement
Click
For a particular meter run, you have a choice of one of three possible types of measurement: Click the button that corresponds to the type of meter you use on this meter run.
Differential Measurement - Select this if you have an orifice type
meter for this meter run. This uses either the 1992 AGA3 equation (see Section 4.8.1) or the 1985 AGA3 equation (see Section 4.8.2).
Linear Measurement - Select this if you have a linear type meter
(ultrasonic, turbine, auto-adjust, or positive displacement) for this meter run. This uses the AGA7 equation (see Section 4.8.3).
Coriolis Measurement - Select this if you have a coriolis meter for
this meter run (see Section 4.8.4).
Figure 4-11. Selecting the Type of Measurement
Notes:
Once you select the equation type, these buttons subsequently open up
the equation configuration page for the chosen equation.
If you inadvertently choose the wrong equation type, you can reset the
equation type to undefined, so you can re-select it. To do this, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
4-40 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
4.8.1 Differential Measurement – AGA3I (1992 equation)
There are two different AGA3 equations supported, the AGA3I equation from the 1992 AGA report, and the AGA3TERM equation from the 1985 AGA report.
Figure 4-12. Differential Measurement – AGA3I page
Notes:
If you want to choose the AGA3TERM calculation, instead of the
AGA3I calculation, click the Click Here to Select AGA3TERM (1985) button.
If you chose differential measurement by mistake, and need to choose
either linear measurement or coriolis measurement instead, you can reset the equation type to undefined, so you can re-select it. To do this, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
Field Description 1992 AGA3 Equation
Configuration for Run#
Inputs
Select the meter run number for which you want to configure AGA3 iterative measurement.
Revised Oct-2014 Measurement Group Config Tab 4-41
ControlWave Flow Measurement Applications Guide
Pressure Tap
Low Flow Cutoff
Orifice Diam.
Pipe Diam.
Orifice Material
Pipe Material
Isentropic Exponent
Adjust Press.
Station Elevation
Local Press.
Click this button to change the specified location of the pressure tap. The pressure tap can be either upstream or downstream of the meter.
Enter the low flow cutoff here. This the minimum value for differential pressure where the application performs measurements. If the differential pressure drops below this value, the measured flow goes to zero. Select the units for the low flow cutoff.
Enter the orifice bore diameter here and select the proper units.
Enter the inside diameter of the pipe here and select the proper units.
The label on this button shows the type of steel used for the orifice. When you click the button you toggle between these two cases.
Click Carbon to specify that stainless steel is the orifice material. The button now displays Stainless.
Click Stainless to specify that carbon steel is the orifice material. The button now displays Carbon.
The label on this button shows the type of steel used for the pipe. When you click the button you toggle between these two cases.
Click Carbon to specify that stainless steel is the pipe material. The button now displays Stainless.
Click Stainless to specify that carbon steel is the pipe material. The button now displays Carbon.
Specify the fluid Isentropic exponent. This value is used in the calculation of the expansion factor, Y. Typically you should enter 1.3 here, which is the value given in the 1992 American Gas Association (AGA-3)
Report.
Specify the site barometric pressure and select the proper units. This value is added to the value shown for the Static Press. to obtain absolute pressure.
Specify the station elevation above sea level and choose the appropriate units. The default units are feet.
Show the local atmospheric pressure calculated based on inputs including the station elevation.
4-42 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Use Adjust or Local Press.
Diff. Press
Static Press.
Temperature
Spec. Gravity
Z Flowing
The label on this button shows whether you use the calculated local pressure or the adjusted pressure. When you click the button you toggle between these two cases.
Click Adjust to specify that the application should use local pressure. The button now displays Local.
Click Local to specify that the application should use adjusted pressure. The button now displays Adjust.
Shows the differential pressure across the orifice plate.
Shows the upstream or downstream static pressure.
Shows the temperature of the flowing gas.
Shows the specific gravity of the gas at standard conditions.
Shows the flowing compressibility factor.
Z Base
Base Temp.
Base Press.
Viscosity
Outputs
Flow
Flow Units
Low Flow Cut Off Shows Cutoff if the flow is too low and so the low flow
C Prime The C Prime factor is:
Shows the base compressibility factor.
Shows the base temperature of the gas.
Specify the base pressure. This is used to calculate the pressure base factor
Specify the dynamic viscosity of the gas at flowing conditions. Viscosity is used to calculate the Reynolds number.
Shows the current calculated flow reading.
Shows the engineering units for the calculated flow reading.
cut off is currently active. Shows Flowing if flow is sufficient that the low flow cut off is not active.
Fn * CD * Y * Fpb * Ftb * Ftf * Fgr * Fpv where: Fn is the numeric conversion factor
Revised Oct-2014 Measurement Group Config Tab 4-43
ControlWave Flow Measurement Applications Guide
Fn
CD is the orifice coefficient of discharge Y is the expansion factor Fpb is the pressure base factor Ftb is the temperature base factor Ftf is the flowing temperature factor Fpv is the supercompressibility factor
Shows a numeric conversion factor which includes the velocity of approach factor.
CD
E
Y
Fpb
Ftb
Ftf
Fgr
FPV
Shows the Orifice coefficient of discharge, which is the sum of the orifice calculation factor, Fc and the orifice slope factor Fsl.
Shows the velocity of approach factor.
Shows the expansion factor.
Shows the pressure base factor.
Shows the temperature base factor.
Shows the flowing temperature factor.
Shows the specific gravity factor.
Shows the supercompressibility factor, computed as Zb / Zf..
Fm
Extension
Reynolds Number
BCF
Shows the internal meter correction factor, Fm , to compensate for external equipment calibration error or local variations in conditions such as gravity, or Downstream tap compressibility.
Shows the extension factor for the AGA3I calculation.
Shows the pipe Reynolds number as computed by iteration as part of the CD (coefficient of discharge) calculation.
Shows the base correction (Zb/Zs) for Zb other than AGA report Zs value, where Zb is the base compressibility factor and Zs is the standard compressibility for gas in use.
4-44 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
4.8.2 Differential Measurement – AGA3TERM (1985 equation)
There are two different AGA3 equations supported, the AGA3I equation from the 1992 AGA report, and the AGA3TERM equation from the 1985 AGA report.
Figure 4-13. Differential Measurement – AGA3TERM page
Notes:
If you want to choose the AGA3I calculation, instead of the
AGA3TERM calculation, click the Click Here to Select AGA3I (1992) button.
If you chose differential measurement by mistake, and need to choose
either linear measurement or coriolis measurement instead, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
Field Description 1985 AGA3 Equation
Configuration for Run#
Inputs
Pressure Tap
Select the meter run number for which you want to configure AGA3 term measurement.
Click this button to change the specified location of the pressure tap. The pressure tap can be either upstream or downstream of the meter.
Revised Oct-2014 Measurement Group Config Tab 4-45
ControlWave Flow Measurement Applications Guide
Low Flow Cutoff
Orifice Diam.
Pipe Diam.
Fm / Fl
Adjust Press.
Station Elevation
Local Press.
Enter the low flow cutoff here. This the minimum value for differential pressure where the application performs measurements. If the differential pressure drops below this value, the measured flow goes to zero. Select the units for the low flow cutoff.
Enter the orifice bore diameter here and select the proper units.
Enter the inside diameter of the pipe here and select the proper units.
Enter the combined orifice constant here.
Specify the average barometric pressure and select the proper units.
Specify the station elevation above sea level and choose the appropriate units. The default units are feet.
Show the local atmospheric pressure calculated based on inputs including the station elevation.
Use Adjust or Local Press.
Diff. Press
Static Press.
Temperature
Spec. Gravity
FPV
The label on this button shows whether you use the calculated local pressure or the adjusted pressure. When you click the button you toggle between these two cases.
Click Adjust to specify that the application should use local pressure. The button now displays Local.
Click Local to specify that the application should use adjusted pressure. The button now displays Adjust.
Shows the differential pressure across the orifice plate.
Shows the upstream or downstream static pressure.
Shows the temperature of the flowing gas.
Shows the specific gravity of the flowing gas.
Shows the supercompressibility factor of the gas.
Base Temp.
Specify the required (contract) base temperature of the flowing gas and the associated engineering units.
4-46 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Base Press.
Outputs
Flow
Flow Units
Low Flow Cut Off Shows Cutoff if the flow is too low and so the low flow
C Prime The C Prime factor is:
Fb
Specify the base or contract pressure of the gas and the associated units.
Shows the current calculated flow reading.
Shows the engineering units for the calculated flow reading.
cut off is currently active. Shows Flowing if flow is sufficient that the low flow cut off is not active.
Fn * CD * Y * Fpb * Ftb * Ftf * Fgr * Fpv where: Fn is the numeric conversion factor CD is the orifice coefficient of discharge Y is the expansion factor Fpb is the pressure base factor Ftb is the temperature base factor Ftf is the flowing temperature factor Fpv is the supercompressibility factor
Show the base orifice factor.
Fr
Y
Fpb
Ftb
Ftf
Fg
Extension
Orif. Const. K
Shows the Reynolds number factor.
Shows the expansion factor.
Shows the pressure base factor.
Shows the temperature base factor.
Shows the flowing temperature factor.
Shows the specific gravity factor.
Shows the extension factor for the AGA3TERM calculation.
Shows the combined orifice constant K. This is typically the value for orifice thermal expansion unless other corrections are required.
Revised Oct-2014 Measurement Group Config Tab 4-47
ControlWave Flow Measurement Applications Guide
4.8.3 Linear Measurement – AGA7
The AGA7 Equation Configuration page lets you configure linear flow measurement for this meter run.
Figure 4-14. AGA7 Calculation page
Note: If you chose linear measurement by mistake, and need to choose
either differential measurement or coriolis measurement instead, you can reset the equation type to undefined, so you can re-select it. To do this, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
4-48 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Field Description AGA7 Equation
Configuration for Run#
Inputs
Select the meter run number for which you want to configure AGA7 linear measurement.
Flow Density
Base Density
Spec. Gravity
FPV
K Factor Units
K Factor
Frequency Input
Low Flow Cutoff
Static Pressure
Specify the density of the flowing gas as measured by a densitometer.
Specify the contract base density of the gas as measured by a densitometer.
Specify the specific gravity of the gas as measured by a gravitometer.
Shows the supercompressibility factor.
Specify the desired units for the output.
Specify a scale factor to adjust the output to your desired units.
Shows the live frequency input.
The low flow cutoff is the minimum frequency that will still be considered valid for flow measurement. If the frequency of the inputs from the high speed counter fall below this number, volume will not be measured.
Shows the static gauge pressure of the flowing gas.
Temperature
Pressure Adjust
Station Elevation
Local Press.
Use Adjust or Local Press.
Revised Oct-2014 Measurement Group Config Tab 4-49
Shows the temperature of the flowing gas.
Enter the average barometric pressure here.
Specify the station elevation above sea level and choose the appropriate units. The default units are feet.
Show the local atmospheric pressure calculated based on inputs including the station elevation.
The label on this button shows whether you use the calculated local pressure or the adjusted pressure. When you click the button you toggle between these two cases.
ControlWave Flow Measurement Applications Guide
Base Pressure
Click Adjust to specify that the application should use local pressure. The button now displays Local.
Click Local to specify that the application should use adjusted pressure. The button now displays Adjust.
Specify the contract base pressure and associated units.
Base Temperature
Meter Factor
Outputs
Flow
Flow Units
K Factor Used
Low Flow Cut Off Shows Cutoff if the flow is too low and so the low flow
Specify the contract base temperature and associated units.
Specify an optional meter calibration factor here. The AGA7 calculation uses this factor to correct for known variations in the measuring equipment.
Shows the calculated flow rate at base conditions.
Shows the engineering units for the calculated flow rate reading.
Shows the value of the K factor used in the calculation.
cut off is currently active. Shows Flowing if flow is sufficient that the low flow cut off is not active.
4-50 Measurement Group Config Tab Revised Oct-2014
4.8.4 Coriolis Measurement
The Coriolis Equation Configuration page lets you configure gas flow measurement using a coriolis meter.
ControlWave Flow Measurement Applications Guide
Figure 4-15. Coriolis Calculation page
Note: If you chose coriolis measurement by mistake, and need to choose
either differential measurement or linear measurement instead, you can reset the equation type to undefined, so you can re-select it. To do this, click the Reset Meter Run’s Measurement Type button on the Meter Run Overview page. See Section 3.2.
Field Description Coriolis Equation
Configuration for Run#
Inputs
Air Density
Spec. Gravity
Select the meter run number for which you want to configure coriolis measurement.
Specify the density of air constant.
Shows the specific gravity of the gas.
Revised Oct-2014 Measurement Group Config Tab 4-51
ControlWave Flow Measurement Applications Guide
K Factor Units
K Factor
Frequency Input
Static Pressure
Temperature
Outputs
Flow
Flow Units
Select the engineering units for the coriolis meter.
Specify the correction factor (K) for the coriolis meter. This information is available from the coriolis meter data plate.
Shows the current frequency from the high speed counter input connected to the coriolis meter.
Shows the static pressure of the flowing gas.
Shows the temperature of the flowing gas.
Shows the calculated flow rate.
Shows the engineering units for the calculated flow rate reading.
K Factor Used
Shows the value of the K factor used in the calculation.
4-52 Measurement Group Config Tab Revised Oct-2014
4.9 Compressibility Setup
The Supercompressibility Configuration page lets you enter parameters to enable supercompressibility calculations.
ControlWave Flow Measurement Applications Guide
Calling up this Menu
Click
Figure 4-16. Supercompressibility Configuration page
Field Description Supercompressibility
Configuration for Run#
Selected Compressibility Calculation
Click to Select NX19/AGA8 Detail/AGA8 Gross
Revised Oct-2014 Measurement Group Config Tab 4-53
Select the meter run number for which you want to configure supercompressibility calculations.
Shows the currently selected type of compressibility calculation.
Click the NX-19 button to select NX-19 as the compressibility calculation.
Click the AGA8 Detail button to select AGA8 Detail as the compressibility calculation.
Click the AGA8 Gross button to select AGA8 Gross
ControlWave Flow Measurement Applications Guide
Inputs
as the compressibility calculation.
Gross Mode
Static Pressure
Base Pressure
Temperature
The label on this button shows whether you use gross Mode 1 or gross Mode 2. When you click the button you toggle between these two cases.
Mode 1 uses the heating value (in BTU), the relative density (specific gravity) and the mole fraction percent
.
of CO
2
Mode 2 uses the relative density (specific gravity) and the mole fraction percent of N
and CO2.
2
Click Mode 1 to specify that the application should use Mode 2. The button now displays Mode 2.
Click Mode 2 to specify that the application should use Mode 1. The button now displays Mode 1.
Shows the static pressure of the flowing gas.
Specify the contract base pressure.
Shows the temperature of the flowing gas.
Base Temp.
BTU
Spec. Gravity.
CH4
N2
CO2
C2
Specify the contract base temperature.
Shows the heat in British Thermal Units (BTU)
Shows the specific gravity of the gas. There are no units for specific gravity.
Shows the mole fraction percentage of methane in the gas.
Shows the mole fraction percentage of nitrogen in the gas.
Shows the mole fraction percentage of carbon dioxide in the gas.
Shows the mole fraction percentage of ethane in the gas.
4-54 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
C3
IC4
NC4
IC5
NC5
NC6
NC7
NC8
Shows the mole fraction percentage of propane in the gas.
Shows the mole fraction percentage of I-butane in the gas.
Shows the mole fraction percentage of N-butane in the gas.
Shows the mole fraction percentage of I-pentane in the gas.
Shows the mole fraction percentage of N-pentane in the gas.
Shows the mole fraction percentage of N-hexane in the gas.
Shows the mole fraction percentage of N-heptane in the gas.
Shows the mole fraction percentage of N-octane in the gas.
H2O
H2S
H2
CO
O2
NC9
NC10
He2
Specify the mole fraction percentage of water in the gas.
Specify the mole fraction percentage of hydrogen sulfide in the gas.
Specify the mole fraction percentage of hydrogen in the gas.
Specify the mole fraction percentage of carbon monoxide in the gas.
Specify the mole fraction percentage of oxygen in the gas.
Specify the mole fraction percentage of n-nonane in the gas.
Specify the mole fraction percentage of n-decane in the gas.
Specify the mole fraction percentage of helium in the gas.
Ar
Revised Oct-2014 Measurement Group Config Tab 4-55
Specify the mole fraction percentage of argon in the gas.
ControlWave Flow Measurement Applications Guide
Outputs
FPV
Z Base
Z Flowing
Shows the calculated supercompressibility factor of the gas.
Shows the base compressibility factor.
Shows the flowing compressibility factor.
4-56 Measurement Group Config Tab Revised Oct-2014
4.10 GC Summary
ControlWave Flow Measurement Applications Guide
Calling up this Menu
Click
Figure 4-17. GC Summary page
Field Description Chromatograph Setup
for Run#
Communications Settings
Mode Disabled/Enabled
Revised Oct-2014 Measurement Group Config Tab 4-57
Select the meter run for which you want to configure a chromatograph.
Use this button to specify, for the application, whether a chromatograph is present (enabled) and providing gas component data or not present (disabled) in which
ControlWave Flow Measurement Applications Guide
Status
Common Fixed Data
Port Number
Serial or IP
case the application uses fixed values for gas component data.
The label on this button shows the current configured state of the chromatograph. When you click the button you toggle the direction.
Click Disabled to specify that the chromatograph is present and providing gas component data. The button now displays Enabled.
Click Enabled to specify that the chromatograph is not present and that the application should use fixed gas component data values. The button now displays Disabled.
Non-zero values indicate an error. See the ControlWave Designer online help CUSTOM function block odiStatus parameter value for the Modbus Master communication protocol you use with the chromatograph.
Use this button to specify, for the application, whether the fixed component values you enter for stream 1 should apply to all four streams (Common) or whether each stream should use its own fixed component value (Individual).
The label on this button shows the current choice. When you click the button you toggle the choice.
Click Individual to specify that the application should use the gas component data specified for stream 1 for all four streams. The button now displays Common.
Click Common to specify that the application should use individual gas component values specified for each stream instead of using the stream 1 value for all four streams. The button now displays Individual.
When a chromatograph is present, this is the port number on the ControlWave flow computer to which the chromatograph connects.
Use this button to specify, for the application, whether the ControlWave flow computer communicates with the chromatograph using a serial Modbus protocol or an IP communication protocol.
The label on this button shows the current configured choice of protocol. When you click the button you toggle the protocol.
Click IP to specify that the flow computer uses a serial Modbus protocol to communicate with the chromatograph. The button now displays Serial..
4-58 Measurement Group Config Tab Revised Oct-2014
Modbus Address
f
IP Address
ControlWave Flow Measurement Applications Guide
Click Serial to specify that the flow computer uses IP protocol to communicate with the chromatograph. The button now displays IP.
If the ControlWave communicates with the chromatograph using a serial Modbus communication protocol, enter the chromatograph’s Modbus Address
246),
(1-
If you communicate with the chromatograph using IP, specify its IP address here.
Stream Assignment
GC Run Status
C6+/C9+ Mode
On Chromatograph Failure Stream x should
Select the chromatograph gas stream you want to assign to the current meter run. The current meter run is the one you selected at the top of the menu with the Chromatograph Setup for Run# field.
Possible status messages include: OK operating okay DISABLED in disabled mode OUT OF RANGE ERROR value out of range based on
the limits set GC FAILURE the chromatograph failed BAD RUN# Improper GC configuration for this
meter run
Use this button to specify, for the application, whether your chromatograph supports C6+ or C9+.
The label on this button shows the current configured choice. When you click the button you toggle the choice.
Click C6+ to specify that the chromatograph supports C9+. The button now displays C9+..
Click C9+ to specify that the chromatograph supports C6+. The button now displays C6+.
Use this button to specify, for each stream, what gas component values the application should use if the chromatograph fails. The application can either use the last known good value from the chromatograph, or a fixed value you enter on this page.
The label on this button shows the current configured choice of what gas components to use for this stream i the chromatograph fails. When you click the button you toggle the choice.
Click Use Fixed Values to specify that the flow computer should use the last known component values received from the chromatograph for this stream if the chromatograph fails. The button now
Revised Oct-2014 Measurement Group Config Tab 4-59
ControlWave Flow Measurement Applications Guide
Analysis Data
displays Use Last Values.
Click Use Last Values to specify that the flow computer should use the fixed component values entered on this page for this stream if the chromatograph fails. The button now displays Use
Fixed Values.
Stream x BTU Raw
Shows the most recent BTU value received from the chromatograph for gas stream x.
Stream x BTU Fixed
Enter a fixed BTU value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Stream x Gravity Raw
Shows the most recent gravity value received from the chromatograph for gas stream x.
Stream x Gravity Fixed
Enter a fixed gravity value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Gas Components
Stream x CH
(Methane) Raw
*
Stream x CH
(Methane) Fixed
*
4
4
Shows the most recent methane value received from the chromatograph for gas stream x.
Enter a fixed methane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Stream x N Raw
(Nitrogen)
2 *
Shows the most recent nitrogen value received from the chromatograph for gas stream x.
Stream x N Fixed
(Nitrogen)
2 *
Enter a fixed nitrogen value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Stream x CO
2 *
Raw
Shows the most recent carbon dioxide value received from the chromatograph for gas stream x.
Stream x CO
Fixed
2 *
Enter a fixed carbon dioxide value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
4-60 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Stream x C
2 *
Raw
Stream x C
2 *
Fixed
Stream x C
2 *
Raw
Stream x C
3 *
Fixed
Stream x IC
4 *
Raw
Stream x IC
4 *
Fixed
Stream x NC Butane) Raw
(Ethane)
(Ethane)
(Propane)
(Propane)
(I-Butane)
(I-Butane)
(N-
4 *
Shows the most recent ethane value received from the chromatograph for gas stream x.
Enter a fixed ethane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent propane value received from the chromatograph for gas stream x.
Enter a fixed propane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent I-butane value received from the chromatograph for gas stream x.
Enter a fixed I-butane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent N-butane value received from the chromatograph for gas stream x.
Stream x NC
(N-
4 *
Butane) Fixed
Stream x IC
(I-
5 *
Pentane) Raw
Stream x IC5*(I-Pentane) Fixed
Stream x NC
(N-
5 *
Pentane) Raw
Stream x NC
(N-
5 *
Pentane) Fixed
Enter a fixed N-butane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent I-pentane value received from the chromatograph for gas stream x.
Enter a fixed I-pentane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent N-pentane value received from the chromatograph for gas stream x.
Enter a fixed N-pentane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Revised Oct-2014 Measurement Group Config Tab 4-61
ControlWave Flow Measurement Applications Guide
Stream x C
Stream x C
Stream x NC
6+ *
6+ *
6 *
Raw
Fixed
Hexane) Raw
Stream x NC
6 *
Hexane) Fixed
Stream x NC
7 *
Heptane) Raw
Stream x NC
7 *
Heptane) Fixed
Stream x NC
8 *
Octane) Raw
(N-
(N-
(N-
(N-
(N-
Shows the most recent C
value received from the
6+
chromatograph for gas stream x.
Enter a fixed C
value the application can use if the
6+
chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent N-hexane value received from the chromatograph for gas stream x.
Enter a fixed N-hexane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent N-heptane value received from the chromatograph for gas stream x.
Enter a fixed N-heptane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent N-octane value received from the chromatograph for gas stream x.
Stream x NC
8 *
Octane) Fixed
Stream x C
Stream x C
Stream x NC
9+ *
9+ *
9 *
Nonane) Raw
Stream x NC
9 *
Nonane) Fixed
(N-
Raw
Fixed
(N-
(N-
Enter a fixed N-octane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent C
value received from the
9+
chromatograph for gas stream x.
Enter a fixed C
value the application can use if the
9+
chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Shows the most recent N-nonane value received from the chromatograph for gas stream x.
Enter a fixed N-nonane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
4-62 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Stream x NC
10 *
Decane) Raw
Stream x NC
10 *
Decane) Fixed
(N-
(N-
Shows the most recent N-decane value received from the chromatograph for gas stream x.
Enter a fixed N-decane value the application can use if the chromatograph fails for gas stream x. The application only uses this value if the chromatograph fails and you specified that it should Use Fixed Values for this stream.
Stream x Raw Totals
Shows the sum of the gas component values in the raw column as a percentage.
Stream x Fixed Totals
Shows the sum of the gas component values in the fixed column as a percentage.
Stream x Out of Range Shows OOR if the raw gas stream total is out of range
of the Component Total Sum Limits defined on the Chromatograph Component Range Setup page (see Section 4.11), or Normal if the raw gas stream total is within these limits.
Used
This column shows the gas component values currently in use in calculations for the current meter run. This could be either the fixed value or the raw value. The current meter run is the one you selected at the top of the menu with the Chromatograph Setup for Run# field.
Revised Oct-2014 Measurement Group Config Tab 4-63
ControlWave Flow Measurement Applications Guide
4.11 Chromatograph Component Range Setup
On the Chromatograph Component Range Setup page, you specify the minimum and maximum percentages for particular gas components in each gas stream.
If a component percentage goes outside these limits, operation is governed by the chromatograph failure settings on the GC Summary page.
Calling up this Menu
Click
Range Setup
> Component
Figure 4-18. Component Range Setup page
4-64 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Field Description
Component Out of Range Limits
Chromatograph Out of Range Limits Individual/Common button
Stream x C
(Ethane)
2 *
Max Limit
Stream x C
(Ethane)
2 *
Min Limit
Use this button to specify, for the application, whether the component out of range limits you enter for stream 1 should apply to all four streams (Common) or whether each stream should use its own individual out of range limits (Individual).
The label on this button shows the current choice. When you click the button you toggle the choice.
Click Individual to specify that the application should use the out of range limits specified for stream 1 for all four streams. The button now displays Common.
Click Common to specify that the application should use out of range limits specified for each stream instead of using the stream 1 limits for all four streams. The button now displays Individual.
Specify the maximum percentage of ethane allowed in gas stream x.
Specify the minimum percentage of ethane allowed in gas stream x.
Stream x C
(Propane)
3 *
Max Limit
Stream x C
(Propane)
3 *
Min Limit
Stream x CH
(Methane) Max Limit
*
Stream x CH
(Methane) Min Limit
*
Stream x CO
4
4
(Carbon
2 *
Dioxide) Max Limit
Stream x CO
(Carbon
2 *
Dioxide) Min Limit
Stream x IC
(I-Butane)
4 *
Max Limit
Specify the maximum percentage of propane allowed in gas stream x.
Specify the minimum percentage of propane allowed in gas stream x.
Specify the maximum percentage of methane allowed in gas stream x.
Specify the minimum percentage of methane allowed in gas stream x.
Specify the maximum percentage of carbon dioxide allowed in gas stream x.
Specify the minimum percentage of carbon dioxide allowed in gas stream x.
Specify the maximum percentage of I-butane allowed in gas stream x.
Revised Oct-2014 Measurement Group Config Tab 4-65
ControlWave Flow Measurement Applications Guide
Stream x IC
(I-Butane)
4 *
Min Limit
Stream x IC5*(I-Pentane) Max Limit
Stream x IC5*(I-Pentane) Min Limit
Stream x N2*(Nitrogen) Max Limit
Stream x N2*(Nitrogen) Min Limit
Stream x NC4*(N­Butane) Max Limit
Stream x NC4*(N­Butane) Min Limit
Stream x NC5*(N­Pentane) Max Limit
Specify the minimum percentage of I-butane allowed in gas stream x.
Specify the maximum percentage of I-pentane allowed in gas stream x.
Specify the minimum percentage of I-pentane allowed in gas stream x.
Specify the maximum percentage of nitrogen allowed in gas stream x.
Specify the minimum percentage of nitrogen allowed in gas stream x.
Specify the maximum percentage of N-butane allowed in gas stream x.
Specify the minimum percentage of N-butane allowed in gas stream x.
Specify the maximum percentage of N-pentane allowed in gas stream x.
Stream x NC5*(N­Pentane) Min Limit
Stream x NC6*(N­Hexane) Max Limit
Stream x NC6*(N­Hexane) Min Limit
Stream x C
( Max
6+*
Limit
Stream x C
( Min Limit
6+*
Stream x NC7*(N­Heptane) Max Limit
Stream x NC7*(N­Heptane) Min Limit
Stream x NC8*(N­Octane) Max Limit
Specify the minimum percentage of N-pentane allowed in gas stream x.
Specify the maximum percentage of N-hexane allowed in gas stream x.
Specify the minimum percentage of N-hexane allowed in gas stream x.
Specify the maximum percentage of C
allowed in gas
6+
stream x.
Specify the minimum percentage of C
allowed in gas
6+
stream x.
Specify the maximum percentage of N-heptane allowed in gas stream x.
Specify the minimum percentage of N-heptane allowed in gas stream x.
Specify the maximum percentage of N-octane allowed in gas stream x.
Stream x NC8*(N­Octane) Min Limit
Specify the minimum percentage of N-octane allowed in gas stream x.
4-66 Measurement Group Config Tab Revised Oct-2014
ControlWave Flow Measurement Applications Guide
Stream x C
( Max
9+*
Limit
Stream x C
( Min Limit
9+*
Stream x NC9*(N­Nonane) Max Limit
Stream x NC9*(N­Nonane) Min Limit
Stream x NC
10*
(N-
Decane) Max Limit
Stream x NC
10*
(N-
Decane) Min Limit
Stream x Gravity Max Limit
Stream x Gravity Min Limit
Specify the maximum percentage of C
allowed in gas
9+
stream x.
Specify the minimum percentage of C
allowed in gas
9+
stream x.
Specify the maximum percentage of N-nonane allowed in gas stream x.
Specify the minimum percentage of N-nonane allowed in gas stream x.
Specify the maximum percentage of N-decane allowed in gas stream x.
Specify the minimum percentage of N-decane allowed in gas stream x.
Specify the maximum gravity allowed in gas stream x.
Specify the minimum gravity allowed in gas stream x.
Stream x BTU Max
Specify the maximum BTUs allowed in gas stream x.
Limit
Stream x BTU Min Limit
Component Total Sum Limit
Max Percentage Limits (Common to all Streams)
Specify the minimum BTUs allowed in gas stream x.
Specify a maximum value for the total percentage of gas components allowed in a single gas stream. This same value is used for each one of the four gas streams.
Min Percentage Limits (Common to all Streams)
Specify a minimum value for the total percentage of gas components allowed in a single gas stream. This same value is used for each one of the four gas streams.
C6+/C9+ Factors The gas chromatograph reports a single value for
either C6+ or C9+. The percentage applied to each component (C6, C7, C8, C9 and C10) will be how the number reported by the gas chromatograph is distributed across the components.
Stream x NC6*(N-
Specify the percentage applied to the C6 component.
Hexane) Factor %
Revised Oct-2014 Measurement Group Config Tab 4-67
ControlWave Flow Measurement Applications Guide
Stream x NC7*(N­Heptane) Factor %
Stream x NC8*(N­Octane) Factor %
Stream x NC9*(N­Nonane) Factor %
Stream x NC
10*
(N-
Decane) Factor %
Specify the percentage applied to the C7 component.
Specify the percentage applied to the C8 component.
Specify the percentage applied to the C9 component.
Specify the percentage applied to the C10 component.
4-68 Measurement Group Config Tab Revised Oct-2014
Loading...