Fisher FIELDBUE DVC6200 Instruction Manual

Instruction Manual
D103557X012
DVC6200 SIS Digital Valve Controller
Fisher™ FIELDVUE™ DVC6200 SIS Digital Valve Controller
This manual applies to
Instrument Level SIS Device Type 130a Device Revision 1 & 2 Hardware Revision 2 Firmware Revision 4, 5 & 6 DD Revision 3, 4 & 5
Contents
Section 1 Introduction 3.................
Installation, Pneumatic and Electrical Connections,
and Initial Configuration 3.....................
Scope of Manual 3..............................
Conventions Used in this Manual 3................
Description 3..................................
Specifications 4................................
Related Documents 7...........................
Educational Services 8...........................
Section 2 Wiring Practices 9..............
Control System Requirements 9..................
HART Filter 9.................................
Voltage Available 9............................
Compliance Voltage 10........................
Auxiliary Terminal Wiring Length Guidelines 12....
Maximum Cable Capacitance 11.................
LCP100 Control Panel 13.........................
Installaton 13.................................
Electrical Connections 13.......................
Section 3 Configuration 15...............
Guided Setup 15...............................
Manual Setup 15...............................
Mode and Protection 17........................
Instrument Mode 17.......................
Write Protection 17........................
Instrument 17................................
Identification 17...........................
Serial Numbers 18.........................
Units 18..................................
Terminal Box 18...........................
Spec Sheet 18.............................
Edit Instrument Time 18....................
X0079
Travel/Pressure Control 19......................
End Point Pressure Control 19................
Characterization 19........................
Dynamic Response 21......................
Travel Cutoffs 21..........................
Tuning 21....................................
Travel Tuning 21...........................
Integral Settings 24........................
Valve and Actuator 24..........................
SIS/Partial Stroke Test 27.......................
Partial Stroke Test (PST) 27..................
SIS Options 30............................
Outputs 30...................................
Output Terminal Configuration 30............
Switch Configuration 31....................
HART Variable Assignments 31..............
Transmitter Output 31.....................
Burst Mode 31............................
Alert Setup 32.................................
Change to HART 5 / HART 7 34....................
April 2016
www.Fisher.com
DVC6200 SIS Digital Valve Controller
April 2016
Instruction Manual
D103557X012
Contents (continued)
Section 4 Calibration 35.................
Calibration Overview 35.........................
Travel Calibration 36...........................
Auto Calibration 36........................
Manual Calibration 37......................
Pushbutton Calibration 38..................
Sensor Calibration 39..........................
Pressure Sensors 39........................
Analog Input Calibration 40.................
Relay Adjustment 41...........................
Double‐Acting Relay 41.....................
Single‐Acting Relays 42.....................
PST Calibration 43.............................
Section 5 Device Information,
Diagnostics, and Alerts 45...............
Overview 45...................................
Status & Primary Purpose Variables 45............
Device Information 45.........................
Service Tools 46................................
Device Status 46..............................
Alert Record 46...............................
Electronics 46.............................
Pressure 48...............................
Travel 48.................................
Travel History 49..........................
Alert Record 50............................
Status 50.................................
Diagnostics 51................................
Stroke Valve 51............................
Partial Stroke Test 51.......................
Demand Mode Tests 53.....................
Solenoid Valve Health Monitoring 55.........
Variables 55...................................
Section 6 Maintenance and
Troubleshooting 57.....................
Replacing the Magnetic Feedback Assembly 58......
Module Base Maintenance 58.....................
Tools Required 58.............................
Component Replacement 59....................
Removing the Module Base 59..................
Replacing the Module Base 60...................
Submodule Maintenance 60......................
I/P Converter 61...............................
Printed Wiring Board (PWB) Assembly 63..........
Pneumatic Relay 64............................
Gauges, Pipe Plugs or Tire Valves 65..............
Terminal Box 65................................
Removing the Terminal Box 66..................
Replacing the Terminal Box 66...................
Troubleshooting 67.............................
Checking Voltage Available 67....................
Restart Processor 67............................
DVC6200 SIS Technical Support Checklist 70........
Section 7 Parts 71......................
Parts Ordering 71...............................
Parts Kits 71...................................
PWB Assembly 71.............................
Parts List 72...................................
Housing 72...................................
Common Parts 73.............................
Module Base 73...............................
I/P Converter Assembly 73......................
Relay 73.....................................
Terminal Box 73...............................
Feedback Connection Terminal Box 73............
Pressure Gauges, Pipe Plugs, or Tire
Valve Assemblies 74.........................
DVC6215 Feedback Unit 74.....................
HART Filter 74................................
Line Conditioner 74............................
Appendix A Principle of Operation 81......
HART Communication 81........................
DVC6200 SIS Digital Valve Controller 81............
Appendix B Field Communicator
Menu Tree 85........................
Glossary 93............................
Index 99..............................
The FIELDVUE DVC6200 SIS Digital Valve Controller is a core component of the PlantWeb™ digital plant architecture. The digital valve controller powers PlantWeb by capturing and delivering valve diagnostic data. Coupled with ValveLink™ software, the DVC6200 SIS provides users with an accurate picture of valve performance, including actual stem position, instrument input signal, and pneumatic pressure to the actuator. Using this information, the digital valve controller diagnoses not only itself, but also the valve and actuator to which it is mounted.
2
Instruction Manual
D103557X012
Introduction
April 2016
Section 1 Introduction
Installation, Pneumatic and Electrical Connections, and Initial Configuration
Refer to the DVC6200 Series Quick Start Guide (D103556X012) for DVC6200 SIS installation, connection, and initial configuration information. If a copy of this quick start guide is needed scan or click the QR code at the right, contact your Emerson
Process Management sales office, or visit our website at www.Fisher.com.
Scope of Manual
This instruction manual is a supplement to the DVC6200 Series Quick Start Guide (D103556X012) and safety manual
(D103601X012) that ship with every instrument. This instruction manual includes product specifications, reference
materials, custom setup information, maintenance procedures, and replacement part details.
Scan or click to access field support
This instruction manual describes using the 475 Field also use Fisher ValveLink software to setup, calibrate, and diagnose the valve and instrument. For information on using ValveLink software with the instrument refer to ValveLink software help or documentation.
Do not install, operate, or maintain a DVC6200 SIS digital valve controller without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage,
it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. If you have any questions about these instructions, contact your Emerson Process Management sales
office before proceeding.
Communicator to set up and calibrate the instrument. You can
Conventions Used in this Manual
Navigation paths and fast‐key sequences are included for procedures and parameters that can be accessed using the Field Communicator.
For example, to access Device Setup:
Field Communicator Configure > Guided Setup > Device Setup (2‐1‐1)
Refer to Appendix B for Field Communicator menu trees.
Description
DVC6200 SIS digital valve controllers (figure 1‐1) are HART communicating, microprocessorbased currenttopneumatic instruments. The DVC6200 SIS digital valve controller has three fundamental functions.
1. Modulate a pneumatic output to a valve actuator in response to a demand signal from a logic solver to move the valve to a safe state.
2. Perform periodic tests on a valve assembly to exercise the mechanical components that are prone to sticking.
3. Continuously monitor the health of the valve and report alerts.
3
Introduction
April 2016
Instruction Manual
Figure 1‐1. FIELDVUE DVC6200 SIS Digital Valve Controller Mounted on a Bettis Quarter-Turn Actuator
X0079
Specifications
D103557X012
WARNING
Refer to table 1‐1 for specifications. Incorrect configuration of a positioning instrument could result in the malfunction of the product, property damage or personal injury.
Specifications for DVC6200 SIS digital valve controllers are shown in table 1‐1. Specifications for the Field Communicator can be found in the product manual for the Field Communicator.
4
Instruction Manual
D103557X012
Table 1‐1. Specifications
Introduction
April 2016
Available Mounting
J Sliding‐stem linear applications J Quarter‐turn rotary applications J Integral mounting to Fisher rotary actuators J Integral mounting to the Fisher GX control valve
and actuator system DVC6200 SIS digital valve controllers can also be
mounted on other actuators that comply with IEC 60534‐6‐1, IEC 60534‐6‐2, VDI/VDE‐3845, and NAMUR mounting standards
Mounting the instrument vertically, with the vent at the bottom of the assembly, or horizontally, with the vent pointing down, is recommended to allow drainage of moisture that may be introduced via the instrument air supply
Communication Protocol
J HART 5 or J HART 7
Input Signal
Point-to-Point
Analog Input Signal: 4‐20 mA DC, nominal Minimum Voltage Available at Instrument Terminals
must be 9.5 VDC for analog control, 10 VDC for HART communication
Minimum Control Current: 4.0 mA Minimum Current w/o Microprocessor Restart: 3.5 mA Maximum Voltage: 30 VDC
Overcurrent protected Reverse Polarity protected
Multi-Drop
Instrument Power: 11 to 30 VDC at 10 mA Reverse Polarity protected
Supply Pressure
(1)
Minimum Recommended: 0.3 bar (5 psig) higher than maximum actuator requirements Maximum: 10.0 bar (145 psig) or maximum pressure rating of the actuator, whichever is lower Medium: Air or Natural Gas
Supply medium must be clean, dry and noncorrosive
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized
‐continued‐
Per ISO 8573-1
Maximum particle density size: Class 7 Oil content: Class 3 Pressure Dew Point: Class 3 or at least 10_C less than
the lowest ambient temperature expected
Output Signal
Pneumatic Output: up to full supply pressure Minimum Span: 0.4 bar (6 psig) Maximum Span: 9.5 bar (140 psig)Action: Double, Single Direct, or Single Reverse
Electronic Output
J
Integral 4‐20 mA Position Transmitter:
(2)
4‐20 mA output, isolated
Supply Voltage: 8‐30 VDC Fault Indication: offrange high or low Reference Accuracy: 1% of travel span Safety Accuracy: 5% of travel span
J Integral Switch:
One isolated switch, configurable throughout the calibrated travel range or actuated from a device alert
Off State: 0 mA (nominal) On State: up to 1 A Supply Voltage: 30 VDC maximum Reference Accuracy: 2% of travel span Safety Accuracy: 5% of travel span
Steady State Air Consumption
(3)(4)
Low Bleed Relay
At 1.4 bar (20 psig) supply pressure:
0.056 normal m3/hr (2.1 scfh), average
At 5.5 bar (80 psig) supply pressure:
0.184 normal m3/hr (6.9 scfh), average
Maximum Output Capacity
(3)(4)
At 1.4 bar (20 psig) supply pressure:
10.0 normal m3/hr (375 scfh) At 5.5 bar (80 psig) supply pressure:
29.5 normal m3/hr (1100 scfh)
Operating Ambient Temperature Limits
(1)(5)
-52 to 85_C (-62 to 185_F)
Independent Linearity
(6)
Typical Value: +/-0.50% of output span
5
Introduction
April 2016
Table 1‐1. Specifications (continued)
Instruction Manual
D103557X012
Electromagnetic Compatibility
Meets EN 61326‐1:2013 Immunity‐Industrial locations per Table 2 of the EN 61326‐1 standard. Performance is shown in table 1‐2 below. Emissions-Class A ISM equipment rating: Group 1, Class A
Vibration Testing Method
Tested per ANSI/ISA S75.13.01 Section 5.3.5
Input Load Impedance
An equivalent impedance of 500 ohms may be used. This value corresponds to 10V @ 20 mA.
Humidity Testing Method
Tested per IEC 61514‐2
Electrical Classification
Hazardous Area Approvals
CSA— Intrinsically Safe, Explosion-proof, Division 2,
Dust Ignition-proof
FM— Intrinsically Safe, Explosion-proof, Dust Ignition-proof, Non-Incendive
ATEX— Intrinsically Safe, Flameproof, Type n
IECEx— Intrinsically Safe, Flameproof, Type n
Auxiliary Terminal Contact: Nominal Electrical
Rating 5 V, <1 mA; It is recommended that the switch be sealed or have gold plated contacts to avoid corrosion
Electrical Housing
CSA— Type 4X, IP66
FM— Type 4X, IP66
ATEX— IP66
IECEx— IP66
‐continued‐
Other Classifications/Certifications
CUTR— Customs Union Technical Regulations (Russia, Kazakhstan, Belarus, and Armenia)
INMETRO— National Institute of Metrology, Quality, and Technology (Brazil)
KGS— Korea Gas Safety Corporation (South Korea) NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety Organisation - Chief Controller of Explosives (India)
Contact your Emerson Process Management sales
office for classification/certification specific
information
IEC 61010 Compliance Requirements
Power Source: The loop current must be derived from a separated extra‐low voltage (SELV) power source Environmental Conditions: Installation Category I
Connections
Supply Pressure: 1/4 NPT internal and integral pad for mounting Fisher 67CFR regulator
Output Pressure: 1/4 NPT internal Tubing: 3/8‐inch recommended Vent: 3/8 NPT internal Electrical: 1/2 NPT internal or M20
(7)
Actuator Compatibility
Stem Travel (Sliding-Stem Linear)
Minimum: 6.5 mm (0.25 inch) Maximum: 606 mm (23.875 inches)
Shaft Rotation (Quarter-Turn Rotary)
Minimum: 45_ Maximum: 90_
Weight
DVC6200 SIS
Aluminum: 3.5 kg (7.7 lbs) Stainless Steel: 8.6 kg (19 lbs)
DVC6205 SIS: 4.1 kg (9 lbs) DVC6215: 1.4 kg (3.1 lbs)
6
Instruction Manual
D103557X012
Table 1‐1. Specifications (continued)
Introduction
April 2016
Construction Materials
Housing, module base, and terminal box
Standard: A03600 low copper aluminum alloy Optional: Stainless steel
Cover: Thermoplastic polyester Elastomers: Fluorosilicone
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 – Process Instrument Terminology.
1. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
2. The electronic output is available with either the position transmitter or the switch.
3. Normal m3/hour – Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh – Standard cubic feet per hour at 60_F and 14.7 psia.
4. Values at 1.4 bar (20 psig) based on single‐acting direct relay; values at 5.5 bar (80 psig) based on double‐acting relay.
5. Temperature limits vary based on hazardous area approval.
6. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for digital valve controllers in long-stroke applications over 4-inch.
7. M20 electrical connections are only available with ATEX approvals.
8. 4‐conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator has been tested to 91 meters (300 feet). At 15 meters (50 feet) there was no performance degradation. At 91 meters there was minimal pneumatic lag.
9. The position monitor (transmitter or switch) with the remote mount construction is not safety certified.
Options
J Supply and output pressure gauges or tire valves J Integral mounted filter regulator J Energize to trip J Standard Bleed Relay J Remote mount
J
LCP100 local control panel J Fisher LC340 line
conditioner
J Stainless steel
(8)(9)
Table 1‐2. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level
Electrostatic discharge (ESD) IEC 61000‐4‐2
Enclosure
I/O signal/control
Performance criteria: +/- 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
Radiated EM field IEC 61000‐4‐3
Rated power frequency magnetic field
Burst IEC 61000‐4‐4 1 kV A Surge IEC 61000‐4‐5 1 kV B Conducted RF IEC 61000‐4‐6 150 kHz to 80 MHz at 3 Vrms A
IEC 61000‐4‐8 30 A/m at 50/60Hz A
4 kV contact 8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% 2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
Performance
Criteria
A
A
(1)
Related Documents
This section lists other documents containing information related to the DVC6200 SIS digital valve controller. These documents include:
D Bulletin 62.1:DVC6200 SIS - Fisher FIELDVUE DVC6200 SIS Digital Valve Controller (D103555X012)
D Bulletin 62.1:DVC6200(S1) Fisher FIELDVUE DVC6200 Digital Valve Controller Dimensions (D103543X012)
D Fisher FIELDVUE DVC6200 Series Digital Valve Controller Quick Start Guide (D103556X012)
D FIELDVUE DVC6200 SIS Safety Manual (D103601X012)
D HART Field Device Specification for FIELDVUE DVC6200 SIS (D103638X012)
D Partial Stroke Test using 475/375 Field Communicator (D103320X012)
D Partial Stroke Test using ValveLink Software (D103274X012)
D Pre-Commissioning Installation / Setup Guidelines using ValveLink Software (D103285X012)
D Bulletin 62.1:LCP100 (D103604X012)
7
Introduction
April 2016
D Fisher LCP100 Instruction Manual (D103272X012)
D Fisher LC340 Instruction Manual (D102797X012)
D Fisher HF340 Filter Instruction Manual (D102796X012)
D 475 Field Communicator User's Manual
D ValveLink Software Help or Documentation
All documents are available from your Emerson Process Management sales office. Also visit our website at www.FIELDVUE.com.
Instruction Manual
D103557X012
Educational Services
For information on available courses for the DVC6200 SIS digital valve controller, as well as a variety of other products, contact:
Emerson Process Management Educational Services - Registration Phone: +1-641‐754‐3771 or +1-800‐338‐8158 E‐mail: education@emerson.com http://www.emersonprocess.com/education
8
Instruction Manual
D103557X012
Wiring Practices
April 2016
Section 2 Wiring Practices22
Logic Solver or Control System Requirements
There are several parameters that should be checked to ensure the logic solver or control system is compatible with the DVC6200 SIS digital valve controller.
HART Filter / Line Conditioner
Depending on the logic solver or control system and operational mode of the DVC6200 SIS digital valve controller, a line conditioner or HART filter may be required.
Operational Mode
4-20 mA
Point-to-Point Loop
24 VDC
Multi-Drop Loop
Control System
or Logic Solver
PROVOX™, RS3™,
DeltaV™, Ovation™
All Others Consult Sales Office No
All No Yes
HART Filter
Required?
No No
Line Conditioner
Required?
The HF340 HART filter and LC340 Line Conditioner are passive devices that are inserted in the field wiring of the HART loop. A filter or line conditioner is normally installed near the field wiring terminals of the system I/O (see figure 2‐1). Its purpose is to effectively isolate the system output from modulated HART communication signals and raise the impedance of the system to allow HART communication. For more information, refer to the HF340 HART filter
(D102796X012) or LC340 Line Conditioner (D102797X012) instruction manual.
Voltage Available
The voltage available at the DVC6200 SIS digital valve controller must be at least 10 VDC. The voltage available at the instrument is not the actual voltage measured at the instrument when the instrument is connected. The voltage measured at the instrument is limited by the instrument and is typically less than the voltage available.
As shown in figure 2‐1, the voltage available at the instrument depends upon:
D The logic solver or control system compliance voltage
D if a line conditioner filter or intrinsic safety barrier is used, and
D the wire type and length.
The compliance voltage is the maximum voltage at the logic solver or control system output terminals at which the system can produce maximum loop current.
The voltage available at the instrument may be calculated from the following equation:
Voltage Available = [Compliance Voltage (at maximum current)] - [line conditioner/filter voltage drop] - [total cable resistance maximum current] - [barrier resistance x maximum current].
The calculated voltage available should be greater than or equal to 10 volts DC.
9
Wiring Practices
April 2016
Figure 2‐1. Determining Voltage Available at the Instrument
TOTAL LOOP CABLE RESISTANCE
CONTROL SYSTEM
COMPLIANCE VOLTAGE
+
-
LINE CONDITIONER OR HART FILTER (if used)
INTRINSIC SAFETY BARRIER (if used)
Instruction Manual
D103557X012
R
VOLTAGE AVAILABLE AT THE
+
INSTRUMENT
-
Calculate Voltage Available at the Instrument as follows:
Logic solver or control system compliance voltage
– Line conditioner or filter voltage drop (if used)
1
Example Calculation
18.5 volts (at 21.05 mA for Honeywell TDC2000)
– 2 volts
– Intrinsic safety barrier resistance (if used) x maximum loop current – 2.55 volts (121 ohms x 0.02105 amps)
– Total loop cable resistance x maximum loop current
= Voltage available at the instrument
2
– 1.01 volts (48 ohms x 0.02105 amps for 1000 feet of Belden 9501 cable)
= 15.49 volts, available—if safety barrier (2.55 volts) is not used
NOTES:
Obtain filter voltage drop. The measured drop will be different than this value. The measured filter voltage drop
1
depends upon control system output voltage, the intrinsic safety barrier (if used), and the instrument. See note 2.
The voltage available at the instrument is not the voltage measured at the instrument terminals. Once the instrument is
2
connected, the instrument limits the measured voltage to approximately 8.0 to 9.5 volts.
Compliance Voltage
If the compliance voltage of the logic solver or control system is not known, perform the following compliance voltage test.
1. Disconnect the field wiring from the system and connect equipment as shown in figure 2‐2 to the system terminals.
Figure 2‐2. Voltage Test Schematic
CIRCUIT UNDER TEST
A6192‐1
10
VOLTMETER
kW POTENTIOMETER
1
MILLIAMMETER
Instruction Manual
D103557X012
Wiring Practices
April 2016
2. Set the system to provide maximum output current.
3. Increase the resistance of the 1 kW potentiometer, shown in figure 2‐2, until the current observed on the milliammeter begins to drop quickly.
4. Record the voltage shown on the voltmeter. This is the compliance voltage.
For specific parameter information relating to your control system, contact your Emerson Process Management sales
office.
Maximum Cable Capacitance
The maximum cable length for HART communication is limited by the characteristic capacitance of the cable. Maximum length due to capacitance can be calculated using the following formulas:
Length(ft) = [160,000 - C
Length(m) = [160,000 - C
master
master
(pF)] [C
(pF)] [C
cable
cable
(pF/ft)]
(pF/m)]
where:
160,000 = a constant derived for FIELDVUE instruments to ensure that the HART network RC time constant will be no greater than 65 μs (per the HART specification).
C
C
The following example shows how to calculate the cable length for a Foxboro
= the capacitance of the control system or HART filter
master
= the capacitance of the cable used (see table 2‐1)
cable
t
I/A control system (1988) with a C
master
of 50, 000 pF and a Belden 9501 cable with characteristic capacitance of 50pF/ft.
Length(ft) = [160,000 - 50,000pF] [50pF/ft]
Length = 2200 ft.
The HART communication cable length is limited by the cable characteristic capacitance. To increase cable length, select a wire with lower capacitance per foot. Contact your Emerson Process Management sales office for specific information relating to your control system.
Table 2‐1. Cable Characteristics
pF/Ft
(1)
Capacitance
Cable Type
BS5308/1, 0.5 sq mm 61.0 200 0.022 0.074
BS5308/1, 1.0 sq mm 61.0 200 0.012 0.037
BS5308/1, 1.5 sq mm 61.0 200 0.008 0.025
BS5308/2, 0.5 sq mm 121.9 400 0.022 0.074
BS5308/2, 0.75 sq mm 121.9 400 0.016 0.053
BS5308/2, 1.5 sq mm 121.9 400 0.008 0.025
BELDEN 8303, 22 awg 63.0 206.7 0.030 0.098
BELDEN 8441, 22 awg 83.2 273 0.030 0.098
BELDEN 8767, 22 awg 76.8 252 0.030 0.098
BELDEN 8777, 22 awg 54.9 180 0.030 0.098
BELDEN 9501, 24 awg 50.0 164 0.048 0.157
BELDEN 9680, 24 awg 27.5 90.2 0.048 0.157
BELDEN 9729, 24 awg 22.1 72.5 0.048 0.157
BELDEN 9773, 18 awg 54.9 180 0.012 0.042
BELDEN 9829, 24 awg 27.1 88.9 0.048 0.157
BELDEN 9873, 20 awg 54.9 180 0.020 0.069
1. The capacitance values represent capacitance from one conductor to all other conductors and shield. This is the appropriate value to use in the cable length calculations.
2. The resistance values include both wires of the twisted pair.
Capacitance
pF/m
(1)
Resistance
Ohms/ft
(2)
Resistance
(2)
Ohms/m
11
Wiring Practices
April 2016
Instruction Manual
D103557X012
Auxiliary Terminal Wiring Length Guidelines
The Auxiliary Input Terminals of a DVC6200 SIS can be used with an LCP100 local control panel or a locally‐mounted switch for initiating a partial stroke test. Some applications require that the switch or local control panel be installed remotely from the DVC6200 SIS.
The length for wiring connected to the Auxiliary Input Terminals is limited by capacitance. For proper operation of the Auxiliary Input Terminals capacitance should not exceed 100,000 pF. As with all control signal wiring, good wiring practices should be observed to minimize adverse effect of electrical noise on the Aux Switch function.
Example Calculation: Capacitance per foot or per meter is required to calculate the length of wire that may be connected to the Aux switch input. The wire should not exceed the capacitance limit of 100,000 pF. Typically the wire manufacturer supplies a data sheet which provides all of the electrical properties of the wire. The pertinent parameter is the highest possible capacitance. If shielded wire is used, the appropriate number is the “Conductor to Other Conductor & Shield” value.
Example — 18AWG Unshielded Audio, Control and Instrumentation Cable
Manufacturer's specifications include:
Nom. Capacitance Conductor to Conductor @ 1 KHz: 26 pF/ft Nom. Conductor DC Resistance @ 20 Deg. C: 5.96 Ohms/1000 ft Max. Operating Voltage - UL 200 V RMS (PLTC, CMG),150 V RMS (ITC) Allowable Length with this cable = 100,000pF /(26pF/ft) =3846 ft
Example — 18AWG Shielded Audio, Control and Instrumentation Cable
Manufacturer's specifications include:
Nom. Characteristic Impedance: 29 Ohms Nom. Inductance: .15 μH/ft Nom. Capacitance Conductor to Conductor @ 1 KHz: 51 pF/ft Nom. Cap. Cond. to other Cond. & Shield @ 1 KHz 97 pF/ft Allowable Length with this cable = 100,000pF /(97pF/ft) = 1030 ft
The AUX switch input passes less than 1 mA through the switch contacts, and uses less than 5 V, therefore, neither the resistance nor the voltage rating of the cable are critical. Ensure that switch contact corrosion is prevented. It is generally advisable that the switch have gold‐plated or sealed contacts.
12
Instruction Manual
D103557X012
Wiring Practices
April 2016
LCP100 Local Control Panel
Installation
The Fisher LCP100 Local Control Panel has four (4) mounting holes for on‐site mounting of the device. The LCP100 must be installed so that the wiring connections are on the bottom to prevent accumulation of moisture inside the box.
When installing the cover tighten the screws evenly in a criss‐cross pattern to a torque of 2.8 N•m (25 lbf•in) to help ensure the cover is properly installed.
Electrical Connections
WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous location, ingress protection, and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval. Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or explosion.
LCP100 protection and wiring methods are defined in table 2‐2. Refer to the LCP100 instruction manual, available from your Emerson Process Management sales office
or at www.FIELDVUE.com, for installation wiring diagrams.
Table 2‐2. Fisher LCP100 Protection and Wiring Methods
LCP100 Protection Method LCP100 Power Source
Ex e mb [ib] IIC Ex tb IIIC
Ex ic IIC Ex tb IIIC
Ex ia IIB Ex tb IIIC
LOOP
24 VDC DVC6200 SIS then LCP100
LOOP
24 VDC DVC6200 SIS then LCP100
LOOP
Note
Factory default for the DIP switch power selector is 24VDC.
Wiring Order from
Logic Solver
DVC6200 SIS then LCP100
LCP100 then DVC6200 SIS
DVC6200 SIS then LCP100
LCP100 then DVC6200 SIS
DVC6200 SIS then LCP100
LCP100 then DVC6200 SIS
DVC6200 SIS Mode
(Current or Voltage)
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
Point-to-Point
Multi-Drop
13
Wiring Practices
April 2016
Instruction Manual
D103557X012
14
Instruction Manual
D103557X012
Configuration
April 2016
Section 3 Configuration
Guided Setup
Field Communicator Configure > Guided Setup (2‐1)
To quickly setup the instrument, the following procedures will guide you through the process.
DDevice SetupThis procedure is used to configure actuator and valve information, calibrate the valve assembly, and
assign the tuning set for the valve assembly.
DPerformance TunerThis procedure executes a simple step response test and then calculates a recommended set of
gain values based on the response of the control valve. See page 22 for additional information.
Manual Setup33
Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel cutoffs and limits. You can also restart the instrument and set the protection.
Refer to table 3‐2 for possible configurations for a digital valve controller operated by a 4‐20 mA input current (point‐to‐point mode), and table 3‐3 for possible configurations for a digital valve controller operated by a 0‐24 VDC power supply (multi‐drop mode).
Table 3‐1. Default Detailed Setup Parameters
Setup Parameter Default Setting
Restart Control Mode Resume Last
Instrument Configuration
Dynamic Response and Tuning
Deviation & Other Alerts
1. The settings listed are for standard factory configuration. DVC6200 SIS instruments can also be ordered with custom configuration settings. Refer to the order requisition for custom settings.
2. Adjust to bar, kPa, or Kg/cm
Polling Address 0 Burst Mode Enable No Burst Command 3 Input Characterization Linear Travel Limit High 125% Travel Limit Low -25% Travel/Pressure Cutoff High 50% Travel/Pressure Cutoff Low 50% Integrator Enable Yes Integral Gain 9.4 repeats/minute Integral Deadzone 0.26% Travel Deviation Alert Enable Yes Travel Deviation Alert Point 5% Travel Deviation Time 9.99 sec Pressure Deviation Alert Enable Yes Pressure Deviation Alert Point 5 psi Pressure Deviation Alert Time 9.99 sec Drive Signal Alert Enable Yes Supply Pressure Alert Enable Yes
2
if necessary.
(1)
(2)
15
Configuration
April 2016
Instruction Manual
D103557X012
Table 3‐2. Possible Configurations for a FIELDVUE DVC6200 SIS Digital Valve Controller operated by 4‐20 mA
Device Setup Configuration Operating Conditions Status Monitoring
Relay Type
A or C
Partial Stroke
Start Point
Open
Close
Zero Power
Condition
Close
(1)
Open
(1)
Close
Open
Input Current Actual Valve Travel
Common Application
20 mA Open 100% 100%
Less Common Application
4 mA Open 100% 100%
Less Common Application
4 mA Close 0% 0%
Common Application
20 mA Close 0% 0%
Travel Set
Point
Travel
(1)
Close
Open
Open
B
Close
Close
1. These configurations are not available when the Hardware Shutdown Switch is Enabled.
Open
(1)
20 mA Open 100% 100%
4 mA Open 100% 100%
4 mA Close 0% 0%
20 mA Close 0% 0%
Less Common Application
Common Application
Common Application
Less Common Application
Note
DVC6200 SIS instruments in PT-PT mode require the Hardware Shutdown Switch be Enabled for FMEDA failure rates to be valid during 420 mA operation.
Table 3‐3. Possible Configurations for a FIELDVUE DVC6200 SIS Digital Valve Controller operated by 0‐24 VDC
Device Setup Configuration Operating Conditions Status Monitoring
Relay Type
A or C
Partial Stroke
Start Point
Open
Close
Zero Power
Condition
Close
(1)
Open
(1)
Close
Open
Power Supply Actual Valve Travel
Common Application
24 VDC Open 100% 100%
Less Common Application
24 VDC Open 100% 100%
Less Common Application
24 VDC Close 0% 0%
Common Application
24 VDC Close 0% 0%
Travel Set
Point
Travel
Close
Open
B
Close
1. In these configurations, the DVC6200 SIS is used as a diagnostic device, the safety function is provided by other devices in the pneumatic loop, e.g. a solenoid valve.
16
Open
Close
Open
(1)
(1)
24 VDC Open 100% 100%
24 VDC Open 100% 100%
24 VDC Close 0% 0%
24 VDC Close 0% 0%
Less Common Application
Common Application
Common Application
Less Common Application
Instruction Manual
D103557X012
Configuration
April 2016
Mode and Protection
Field Communicator Configure > Manual Setup > Mode and Protection (2‐2‐1)
Instrument Mode
There are two instrument modes for the DVC6200 SIS; In Service or Out of Service. In Service is the normal operating mode such that the instrument follows the 420 mA or 24 VDC control signal. Out of Service is required in some cases to modify configuration parameters or to run diagnostics.
Note
Some changes that require the instrument to be taken Out Of Service will not take effect until the instrument is placed back In Service or the instrument is restarted.
Write Protection
There are two Write Protection modes for the DVC6200 SIS: Not Protected or Protected. Protected prevents configuration and calibration changes to the instrument. The default setting is Not Protected. Write Protection can be changed to Protected remotely. However, to change Write Protection to Not Protected, you must have physical access to the instrument. The procedure will require you to press a button ( ) on the terminal box as a security measure.
Instrument
Field Communicator Configure > Manual Setup > Instrument (2‐2‐2)
Follow the prompts on the Field Communicator display to configure the following Instrument parameters:
Identification
DHART TagA tag name up to 8 characters is available for the instrument. The HART tag is the easiest way to
distinguish between instruments in a multi‐instrument environment. Use the HART tag to label instruments electronically according to the requirements of your application. The tag you assign is automatically displayed when the Field Communicator establishes contact with the digital valve controller at power‐up.
D HART Long Tag (HART Universal Revision 7 only)—A tag name up to 32 characters is available for the instrument.
D Description—Enter a description for the application with up to 16 characters. The description provides a longer
user‐defined electronic label to assist with more specific instrument identification than is available with the HART tag.
DMessageEnter any message with up to 32 characters. Message provides the most specific user‐defined means for
identifying individual instruments in multi‐instrument environments.
DPolling Address—If the digital valve controller is used in point‐to‐point operation, the Polling Address is 0. When
several devices are connected in the same loop, such as for split ranging, each device must be assigned a unique polling address. The Polling Address is set to a value between 0 and 63 for HART 7 and 0 and 15 for HART 5. To change the polling address the instrument must be Out Of Service.
17
Configuration
April 2016
For the Field Communicator to be able to communicate with a device whose polling address is not 0, it must be configured to automatically search for all or specific connected devices.
Instruction Manual
D103557X012
Serial Numbers
D Instrument Serial Number—Enter the serial number on the instrument nameplate, up to 12 characters.
D Valve Serial Number—Enter the serial number for the valve in the application with up to 12 characters.
Units
D Pressure UnitsDefines the output and supply pressure units in either psi, bar, kPa, or kg/cm2.
D Temperature Units—Degrees Fahrenheit or Celsius. The temperature measured is from a sensor mounted on the
digital valve controller's printed wiring board.
D Analog Input Units—Permits defining the Analog Input Units in mA or percent of 4-20 mA range.
Terminal Box
DCalibration (CAL) Button—This button is near the wiring terminals in the terminal box and provides a quick means to
autocalibrate the instrument. The button must be pressed for 3 to 10 seconds. Autocalibration will move the valve through the full range of travel whether the Instrument Mode is In Service or Out of Service. However, if the Write Protection is Protected, this button will not be active. To abort, press the button again for 1 second. The calibration button is disabled by default.
DAuxiliary Terminal Action—These wire terminals can be configured to initiate a partial stroke test upon detection of
a short across the (+) and (-) terminals. The terminals must be shorted for 3 to 10 seconds. Alternatively, the auxiliary terminals can be configured to support the local control panel.
Spec Sheet
The Spec Sheet provides a means to store the entire control valve specifications on board the DVC6200 SIS.
Edit Instrument Time
Permits setting the instrument clock. When alerts are stored in the alert record, the record includes the time and date. The instrument clock uses a 24‐hour format.
18
Instruction Manual
D103557X012
Configuration
April 2016
Travel/Pressure Control
Field Communicator Configure > Manual Setup > Travel/Pressure Control (2‐2-3)
End Point Pressure Control (EPPC)
DEPPC Enable—Select Yes or No. End Point Pressure Control allows the digital valve controller to pull back from
saturation of the pneumatic output after reaching the travel extreme. Rather than having the instrument provide full supply pressure (saturation) continuously at the travel extreme, the digital valve controller switches to an End Point Pressure Control where the output pressure (pressure controller set point) to the actuator is maintained at a certain value. This value is configured through the Upper Operating Pressure feature. Because the digital valve controller is constantly in control and not allowed to reach a dormant or saturated state, it is constantly testing its own pneumatic system. If there is an output pressure deviation, for example, the instrument will issue an alert. To ensure there is an alert when an output pressure deviation occurs, setup the alert as described under Pressure Deviation Alert.
DEPPC Set Point—Used in conjunction with End Point Pressure Control, End Point Pressure Control Set Point allows
the user to select a pressure to be delivered by the instrument at the travel extreme. For a fail‐closed valve, this pressure must be sufficient to maintain the fully open position. For a fail‐open valve, this pressure (which is automatically set to supply pressure) must be sufficient to fully close the valve and maintain its rated shutoff classification. For double‐acting spring return actuators, this is the differential pressure required to either maintain the fully open or fully closed position, depending on the valve and actuator configuration. For a double‐acting actuator without springs with a fail‐close valve, this is 95% of the supply pressure. If the valve is fail‐open, the upper operating pressure for all actuator is set to the supply pressure.
DEPPC Saturation Time—End Point Pressure Control Saturation Time is the time the digital valve controller stays in
hard cutoff before switching to pressure control. Default is 45 seconds.
Characterization
DInput Characterization
Input Characterization defines the relationship between the travel target and ranged set point. Ranged set point is the input to the characterization function. If the zero power condition equals closed, then a set point of 0% corresponds to a ranged input of 0%. If the zero power condition equals open, a set point of 0% corresponds to a ranged input of 100%. Travel target is the output from the characterization function.
To select an input characterization, select Input Characterization from the Characterization menu. You can select from the three fixed input characteristics shown in figure 3‐1 or you can select a custom characteristic. Figure 3‐1 shows the relationship between the travel target and ranged set point for the fixed input characteristics, assuming the Zero Power Condition is configured as closed.
You can specify 21 points on a custom characteristic curve. Each point defines a travel target, in % of ranged travel, for a corresponding set point, in % of ranged set point. Set point values range from -6.25% to 106.25%. Before modification, the custom characteristic is linear.
DCustom Characterization
To define a custom input character, from the Characterization menu select Custom Characterization. Select the point you wish to define (1 to 21), then enter the desired set point value. Press Enter then enter the desired travel target for the corresponding set point. When finished, select point 0 to return to the Characterization menu.
With input characterization you can modify the overall characteristic of the valve and instrument combination. Selecting an equal percentage, quick opening, or custom (other than the default of linear) input characteristic
19
Configuration
April 2016
Instruction Manual
D103557X012
modifies the overall valve and instrument characteristic. However, if you select the linear input characteristic, the overall valve and instrument characteristic is the characteristic of the valve, which is determined by the valve trim (i.e., the plug or cage).
Figure 3‐1. Travel Target Versus Ranged Set Point, for Various Input Characteristics (Zero Power Condition = Closed)
125
100
Travel Target, %
0
-25
-25 0 125100
Ranged Set Point, %
Input Characteristic = Linear
125
100
125
100
Travel Target, %
0
-25
-25 0 125100
Ranged Set Point, %
Input Characteristic = Equal Percentage
20
A6535‐1
Travel Target, %
0
-25
-25 0 125100
Ranged Set Point, %
Input Characteristic = Quick Opening
Instruction Manual
D103557X012
Configuration
April 2016
Dynamic Response
DSP Rate Open—Maximum rate (% of valve travel per second) at which the digital valve controller will move to the
open position regardless of the rate of input current change. A value of 0 will deactivate this feature and allow the valve to stroke open as fast as possible. In firmware 4 this parameter should be set to 0.
DSP Rate Close—Maximum rate (% of valve travel per second) at which the digital valve controller will move to the
close position regardless of the rate of input current change. A value of 0 will deactivate this feature and allow the valve to stroke close as fast as possible. In firmware 4 this parameter should be set to 0.
DSet Point Filter Time (Lag Time)—The Set Point Filter Time (Lag Time) slows the response of the digital valve
controller. A value ranging from 0.2 to 10.0 can be used for noisy or fast processes to improve closed loop process control. Entering a value of 0.0 will deactivate the lag filter. In firmware 4 this parameter should be set to 0.
Travel Cutoffs
DHi Cutoff Point—This is the point within the calibrated travel range above which the cutoff is in effect. When using
cutoffs, a Cutoff Hi of 50% is recommended to ensure valve goes fully open.
DLo Cutoff Point—This is the point within the calibrated travel range below which the cutoff is in effect. When using
cutoffs, a Cutoff Lo of 50% is recommended to help ensure maximum shutoff seat loading.
Tuning
Field Communicator Configure > Manual Setup > Tuning (2‐2-4)
Travel Tuning
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
DTravel Tuning Set
There are eleven tuning sets to choose from. Each tuning set provides a preselected value for the digital valve controller gain settings. Tuning set C provides the slowest response and M provides the fastest response.
Table 3‐4 lists the proportional gain, velocity gain and minor loop feedback gain values for preselected tuning sets.
Table 3‐4. Gain Values for Preselected Travel Tuning Sets
Tuning Set Proportional Gain Velocity Gain Minor Loop Feedback Gain
C D E F G
H
I
J K L
M
X (Expert) User Adjusted User Adjusted User Adjusted
4.4
4.8
5.5
6.2
7.2
8.4
9.7
11.3
13.1
15.5
18.0
3.0
3.0
3.0
3.1
3.6
4.2
4.85
5.65
6.0
6.0
6.0
35 35 35 35 34
31 27 23 18 12 12
21
Configuration
April 2016
Instruction Manual
D103557X012
In addition, you can specify Expert tuning and individually set the proportional gain, velocity gain, and minor loop feedback gain. Individually setting or changing any tuning parameter or running the Performance Tuner or Stabilize/Optimize routine will automatically change the tuning set to X (expert).
Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize or Performance Tuner may be used to achieve the desired results more rapidly than manual Expert tuning.
Table 3‐5 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are only recommended starting points. After you finish setting up and calibrating the instrument, you may have to select either a higher or lower tuning set to get the desired response. You can use the Performance Tuner to optimize tuning.
DProportional Gain—the proportional gain for the travel control tuning set. Changing this parameter will also change
the tuning set to Expert.
DVelocity Gain—the velocity gain for the travel control tuning set. Changing this parameter will also change the
tuning set to Expert.
DMLFB Gain—the minor loop feedback gain for the travel control tuning set. Changing this parameter will also change
the tuning set to Expert.
DIntegral Enable—Yes or No. Enable the integral setting to improve static performance by correcting for error that
exists between the travel target and actual travel. Travel Integral Control is enabled by default.
DIntegral Gain—Travel Integral Gain is the ratio of the change in output to the change in input, based on the control
action in which the output is proportional to the time integral of the input.
DPerformance Tuner
WARNING
During performance tuning the valve may move, causing process fluid or pressure to be released. To avoid personal injury and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid.
The Performance Tuner is used to determine digital valve controller tuning. It can be used with digital valve controllers mounted on most sliding‐stem and rotary actuators, including Fisher and other manufacturers' products. Moreover, because the performance tuner can detect internal instabilities before they become apparent in the travel response, it can generally optimize tuning more effectively than manual tuning. Typically, the performance tuner takes 3 to 5 minutes to tune an instrument, although tuning instruments mounted on larger actuators may take longer.
22
Instruction Manual
D103557X012
Table 3‐5. Actuator Information for Initial Setup
Actuator
Manufacturer
Fisher
Baumann
NOTE: Refer to figure table 3‐6 for feedback connection (magnet assembly) information.
1. X = Expert Tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
2. Travel Sensor Motion in this instance refers to the motion of the magnet assembly.
3. Values shown are for Relay A and C. Reverse for Relay B.
Actuator Model Actuator Size Actuator Style
Piston Dbl w/ or w/o Spring. See actuator
instruction manual and
nameplate.
585C & 585CR
25 50 60
68, 80
100, 130
30
34, 40
657
45, 50
Spring & Diaphragm
46, 60, 70, 76, &
80‐100
30
34, 40
667
45, 50
Spring & Diaphragm
46, 60, 70, 76, &
80‐100
20, 30
1051 & 1052
33 40
Spring & Diaphragm
(Window‐mount)
60, 70
30
1061
40 60
Piston Dbl w/o Spring
68, 80, 100, 130
1066SR
2052
20
27, 75
1 2 3
Piston Sgl w/Spring
Spring & Diaphragm
(Window‐mount)
30, 30E
3024C
34, 34E, 40, 40E
Spring & Diaphragm
45, 45E
225
GX
750 K
Spring & Diaphragm
1200 M
Air to Extend
Air to Retract Away from the top of the instrument
Rotary
16 32 54
10 25
Spring & Diaphragm
54
Starting
Tuning Set
E
I J
L
M
H
K L
M H
K L
M H
I
K
M
J K L
M
G
L
H
J
M
E
H
K
(1)
X
C E
H
E
H
J
Configuration
April 2016
Travel Sensor Motion
Relay A or C
User Specified
Away from the top of the instrument
Towards the top of the instrument
Away from the top of the instrument
Depends upon pneumatic connections. See
description for Travel Sensor Motion
Mounting Style Travel Sensor Motion
A
B
C
Towards the top of the
Towards the top of the
D
Away from the top of the instrument
For Po operating mode (air opens): Towards the top of the instrument For P
operating mode (air closes):
s
Away from the top of the instrument
Air to Open
Towards the top of
the instrument
Towards the top of the instrument
Specify
(2)
(3)
Away from the top of
the instrument
instrument
instrument
Away from the top of
the instrument
Air to Close
Away from the top of
the instrument
23
Configuration
April 2016
Instruction Manual
D103557X012
DStabilize/Optimize
WARNING
During Stabilize/Optimize the valve may move, causing process fluid or pressure to be released. To avoid personal injury and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid.
Stabilize/Optimize permits you to adjust valve response by changing the digital valve controller tuning. During this routine, the instrument must be out of service; however, the instrument will respond to setpoint changes.
If the valve is unstable, select Decrease Response to stabilize valve operation. This selects the next lower tuning set (e.g., F to E). If the valve response is sluggish, select Increase Response to make the valve more responsive. This selects the next higher tuning set (e.g., F to G).
If after selecting Decrease Response or Increase Response the valve travel overshoot is excessive, select Decrease Damping to select a damping value that allows more overshoot. Select Increase Damping to select a damping value that will decrease the overshoot. When finished, select done.
Integral Settings
DIntegral Dead Zone—A window around the Primary Setpoint in which integral action is disabled. This feature is used
to eliminate friction induced limit cycles around the Primary Setpoint when the integrator is active. The Dead Zone is configurable from 0% to 2%, corresponding to a symmetric window from 0% to +/-2% around the Primary Setpoint. Default value is 0.25%.
DIntegrator Limit—The Integrator Limit provides an upper limit to the integrator output. The high limit is configurable
from 0 to 100% of the I/P drive signal.
Valve and Actuator
Field Communicator Configure > Manual Setup > Valve and Actuator (2‐2‐5)
Valve StyleEnter the valve style, rotary or sliding‐stem
Actuator StyleEnter the actuator style, spring and diaphragm, piston double‐acting without spring, piston
single‐acting with spring, or piston double‐acting with spring.
Feedback Connection—Refer to table 3‐6 for Feedback Connection options. Choose the assembly that matches the actuator travel range.
Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor (on the back of the DVC6200 SIS housing) has to remain within this range throughout the entire valve travel. The linear magnet assemblies are symmetrical. Either end may be up.
24
Instruction Manual
D103557X012
Configuration
April 2016
Table 3‐6. Feedback Connection Options
Magnet Assembly
SStem #7 4.2-7 0.17-0.28 -
SStem #19 8-19 0.32-0.75 -
SStem #25 20-25 0.76-1.00 -
SStem #38 26-38 1.01-1.50 -
SStem #50 39-50 1.51-2.00 -
SStem #110 51-110 2.01-4.125 -
SStem #210 110-210 4.125-8.25
SStem #1 Roller  210  8.25 60-90_
RShaft Window #1 - - 60-90_
RShaft Window #2 - - 60-90_
RShaft End Mount - - 60-90_
mm Inch Degrees
Travel Range
Relay Type—There are three categories of relays that result in combinations from which to select. Relay Type: The relay type is printed on the label affixed to the relay body. A = double‐acting or single‐acting B = single‐acting, reverse C= single‐acting, direct Special App: This is used in single‐acting applications where the “unused” output port is configured to read the pressure downstream of a solenoid valve. Lo Bleed: The label affixed to the relay body indicates whether it is a low bleed version.
Zero Power Condition—The position of the valve (open or closed) when the electrical power to the instrument is removed. Zero Power Condition (ZPC) is determined by relay type, as shown in figure 3‐2.
Figure 3‐2. Zero Power Condition
A
Loss of Electrical Power
Port A pressure to zero.
Port A pressure to zero. Port B pressure to full supply.
Port B pressure to full supply.
X077-SIS
Relay Type
Single‐Acting Direct (Relay A or C)
Double‐Acting (Relay A)
B
Single‐Acting Reverse (Relay B)
Travel Sensor Motion
WARNING
If you answer YES to the prompt for permission to move the valve when determining travel sensor motion, the instrument will move the valve through a significant portion of its travel range. To avoid personal injury and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid.
25
Configuration
April 2016
Instruction Manual
D103557X012
Select Clockwise/Toward Bottom, or Counterclockwise/Toward Top. Travel Sensor Motion establishes the proper travel sensor rotation. For quarter‐turn actuators determine rotation by viewing the rotation of the magnet assembly from the back of the instrument.
Note
Travel Sensor Motion in this instance refers to the motion of the magnet assembly. Note that the magnet assembly may be referred to as a magnetic array in user interface tools.
DFor instruments with Relay A and C: If increasing air pressure at output A causes the magnet assembly to move
down or the rotary shaft to turn clockwise, enter CW/To Bottom Inst. If it causes the magnet assembly to move up, or the rotary shaft to turn counterclockwise, enter CCW/To Top Inst.
DFor instruments with Relay B: If decreasing air pressure at output B causes the magnet assembly to down, or the
rotary shaft to turn clockwise, enter CW/To Bottom Inst. If it causes the magnet assembly to move up, or the rotary shaft to turn counterclockwise, enter CCW/To Top Inst.
Maximum Supply Pressure
Enter the maximum supply pressure that is required to fully stroke the valve.
26
Instruction Manual
D103557X012
Configuration
April 2016
SIS/Partial Stroke Test
Field Communicator Configure > Manual Setup > SIS/Partial Stroke (2-2-6)
Partial Stroke Test (PST)
DPST Pressure Limit This defines the actuator pressure at which a partial stroke test will abort. This prevents the
DVC6200 SIS from exhausting (or building) excessive pressure to the actuator in an attempt to move a stuck valve. During Device Setup or Auto Travel Calibration, the Partial Stroke Pressure Limit will be set automatically as follows:
Single Acting Actuators - For those actuators that exhaust pressure from the partial test start point, the Pressure Limit will be a minimum value. For those actuators that build pressure from the partial test start point, the Pressure Limit will be a maximum value.
Double Acting Actuators - The Pressure Limit will be set to a negative value for actuators where the partial stroke start point is opposite of the Zero Power Condition (e.g., Partial Stroke Start Point = Open and Zero Power Condition = Closed) and to a positive valve for actuators where the partial stroke start point is the same as the Zero Power Condition.
The pressure signal used to determine this parameter depends on relay type and is summarized below.
Relay Type Pressure Signal
A or C Port A - Port B B Port B - Port A B Special App. Port B C Special App. Port A
To manually set the partial stroke pressure limit, you must examine current partial stroke test results using ValveLink software. The following steps will guide you through the process:
1. Connect the DVC6200 SIS to a system running ValveLink software.
2. Disable the following parameters:
D Travel Deviation Alert - set to 125%.
D End Point Pressure Control - disable
D Partial Stroke Pressure Limit - disable by setting the appropriate value shown in table 3‐7.
Table 3‐7. Values for Disabling Partial Stroke Pressure Limit
Actuator Type Relay Type Zero Power Condition Partial Stroke Start Point Partial Stroke Pressure Limit (Disabled)
Closed
A or C
Open
Single Acting
Closed
B
Open
Open 0.0
Closed Psupply
Open Psupply
Closed 0.0
Open Psupply
Closed 0.0
Open 0.0
Closed Psupply
Double Acting A
Closed
Open
Open -Psupply
Closed Psupply
Open Psupply
Closed -Psupply
27
Configuration
April 2016
Instruction Manual
D103557X012
3. Run a partial stroke test.
4. Select the Press/Time radio button on the partial stroke graph (refer to the example in figure 3‐3, bottom plot). If the actuator pressure starts high and moves low, find the minimum actuator pressure (Pmin). If the actuator pressure starts low and moves high, find the maximum actuator pressure (Pmax). Doubleacting actuators will display differential pressure. Use table 3‐8 to estimate the partial stroke pressure limit.
Table 3‐8. Estimates for Partial Stroke Pressure Limits
Actuator Style Relay Type Zero Power Condition PST Starting Point Partial Stroke Pressure Limit
Open Pmin - 0.25 * (Bench Set High - Bench Set Low)
Closed Pmax + 0.25 * (Bench Set High - Bench Set Low)
Open Pmax + 0.25 * (Bench Set High - Bench Set Low)
Closed Pmin - 0.25 * (Bench Set High - Bench Set Low)
Open Pmax + 0.25 * (Bench Set High - Bench Set Low)
Closed Pmin - 0.25 * (Bench Set High - Bench Set Low)
Open Pmin - 0.25 * (Bench Set High - Bench Set Low)
Closed Pmax + 0.25 * (Bench Set High - Bench Set Low)
Open 0.5 * Pmin
Closed Pmax + 0.5 * (Psupply - Pmax)
Open Pmax + 0.5 * (Psupply - Pmax)
Closed 0.5 * Pmin
Open Pmax + 0.5 * (Psupply - Pmax)
Closed 0.5 * Pmin
Open 0.5 * Pmin
Closed Pmax + 0.5 * (Psupply - Pmax)
Open Pmin - 0.5 * (Psupply + Pmin)
Closed Pmax + 0.5 * (Psupply - Pmax)
Open Pmax + 0.5 * (Psupply - Pmax)
Closed Pmin - 0.5 * (Psupply + Pmin)
A or C
Spring and
Diaphragm
A or C
Single Acting Piston
Double Acting Piston A
Closed
Open
Closed
B
Open
Closed
Open
Closed
B
Open
Closed
Open
(1)
5. Enable the parameters that were previously disabled:
D Travel Deviation Alert - set to 1.5x the maximum travel deviation between travel set point and travel.
D End Point Pressure Control - enable
D Partial Stroke Pressure Limit - calculate the value using table 3‐8.
PST Enable—Yes or No. This enables or disables the Partial Stroke Test.
PST Start Point—Valve Open or Valve Closed. This defines the travel stop that the valve needs to be at before a partial
stroke test can be initiated. This also defines the travel stop for end point pressure control. Setting this value to Not Configured will disable partial stroke tests and end point pressure control.
PST Variables—Follow the prompts on the Field Communicator display to enter or view information for following PST Variables:
DMax Travel Movement— This is the percentage of total span that the valve moves away from its normal operating
state towards its tripped state during the test. The default value is 10%.
D Test Speed—This is the rate at which the valve will move during the test. The default value is 0.25%/second.
D Pause Time—This is the pause time between the up and down strokes of the test. The default value is 5 seconds.
28
Instruction Manual
D103557X012
Figure 3‐3. Example Time Series Plots of Travel Set Point, Travel, Error, and Actuator Pressure
TEST START POINT
ACTUAL TRACE FROM TEST (TYPICAL)
TEST SPEED (% / SEC)
TEST PAUSE
TIME (SEC)
Configuration
MAX. TRAVEL
MOVEMENT (5%)
April 2016
TVL SET POINT, TRAVEL (%)ERROR (%)
TRAVEL DEVIATION ALERT PT.
PRESSURE (%)
MAXIMUM DEVIATION
MINIMUM PRESSURE (Pmin)
TIME (SEC)
ACTUAL TRACE FROM TEST (TYPICAL)
TIME (SEC)
ACTUAL TRACE FROM TEST (TYPICAL)
PARTIAL STROKE PRESSURE LIMIT
TIME (SEC)
29
Configuration
April 2016
Instruction Manual
D103557X012
SIS Options
DAuto Test Interval—This is the interval of time (in days) between partial stroke tests that are automatically run by the
digital valve controller, subject to the device being powered up. A value of 0 disables this feature.
DLoopInitiated PST—When this feature is enabled, the digital valve controller will run a partial stroke test if the loop
current is set to within +/0.5% of the PST trip point. The loop current must remain at that point for the duration of the test. To abort the test, the loop current must be returned to the normal or tripped current. This feature is disabled by default. This feature is not available when a looppowered local control panel is installed.
PST Trip Point (ETT) - This is the point at which the loop current must be set to run a partial stroke test for energizetotrip applications. This value is not configurable.
PST Trip Point (DETT) - This is the point at which the loop current must be set to run a partial stroke test for deenergizetotrip applications. This value is not configurable.
DDevice Power Up Reset—This defines the power up behavior of the DVC6200 SIS. Auto Reset allows the valve to
track the command signal when power is applied to the device. Manual Reset will lock the device in its safety position until the digital valve controller is reset.
If Manual Reset is selected, its state can be determined from the status monitor by monitoring the Locked In Safety Position alert.
When Auxiliary Terminal Action is set to SIS Local Control Panel, Device Power Up is set to Manual Reset and cannot be changed to Auto Reset.
The reset signal depends on how the AUX terminals are configured. If configured for SIS Local Control Panel, the digital valve controller can be reset by pressing the button next to the green light on the LCP100. If configured as Push Button Partial Stroke, the digital valve controller can be reset by shorting the AUX terminals for more than 3 seconds but less than 10 seconds. The device cannot be reset from the AUX terminals if they are configured otherwise.
DAction on Failed Test—This displays the action taken by the instrument if a communication timeout occurs. Values
are Ramp Back or Step Back.
Outputs
Field Communicator Configure > Manual Setup > Outputs (2-2-6)
Output Terminal Configuration
DOutput Terminal Enable—If using the output terminal for a Position Transmitter or Switch output, this must be
Enabled.
D Function—The output terminals can be configured as one of the following:
Transmitter - 420 mA output that represents 0100% of the calibrated valve travel.
Limit Switch - Discrete switch (1A max) that trips at a configurable point within 0100% of calibrated valve travel.
Alert Switch - Discrete switch (1A max) that trips based on a configurable device alert.
DFail Signal—Should the output circuit fail to operate properly; the output will attempt to drive to a known state.
Depending on the nature of the failure, the circuit may or may not be able to achieve this fail state. When
30
Loading...
+ 78 hidden pages