Fisher™ FIELDVUE™ DVC2000 Digital Valve
Controller
Contents
Local Interface Flow Chart2......................
Using this Guide4..............................
Installation4..................................
Electrical and Pneumatic Connections15...........
Basic Setup and Calibration18....................
Maintenance29................................
Specifications31...............................
June 2020
Scan or click
to access
field support
Note
This guide provides installation, connection, and basic setup and calibration information using the local operator interface.
Refer to the DVC2000 digital valve controller instruction manual (D103176X012
using a Field Communicator, maintenance and troubleshooting information, and replacement part details. This document is
available from your Emerson sales office
www.Fisher.com
or at Fisher.com.
W8861-2
) for detailed configuration and calibration
DVC2000 Digital Valve Controller
June 2020
Local Interface Flow Chart
Quick Start Guide
D103203X012
Home Screen
TRAVEL = 66.8%
1
14.6 MA 0.92 BAR
Y
B
2
QUICK SETUP
Y
B
TRAVEL
3
CALIBRATION
Y
B
TUNING
4
Y
B
DETAILED SETUP
5
Y
B
ANALOG INPUT
6
CALIBRATION
Y
B
POSITION
TRANSMITTER CAL
7
Y
B
LOCAL
8
CONTROL
Y
SHUTDOWN
Y
ACTIVATED
Y
VALVE WILL MOVE
Y
PRESS FOR 3 SEC
Y
CALIBRATION
Y
AUTOMATIC
Y
TUNING
Y
AUTOMATIC
Y
ZERO CTL SIGNAL
VALVE CLOSED
Y
VALVE WILL MOVE
Y
PRESS FOR 3 SEC
Y
mA OUT WILL CHANGE
PRESS FOR 3 SEC
Only when transmitter / limit switch hardware is installed.
Y
CONTROL
ANALOG
Y
AUTOMATIC
MANUAL
Y
AUTOMATIC
MANUAL
CLOSED
OPEN
ANALOG OR DIGITAL
MANUAL
Y
Y
Y
Y
These items are identified by an alert icon on the default screen
TRAVEL
DEVIATION
Y
FINDING 0% ...
Y
VALVE WILL MOVE
PRESS FOR 3 SEC
VALVE WILL MOVE
PRESS FOR 3 SEC
AUTO
VALVE MAY MOVE
PRESS FOR 3 SEC
MANUAL
Y
PRESSURE UNITS
BAR
BAR
PSI
KPA
Y
APPLY 4 mA
THEN PRESS
Y
USE OR
TO SEND 4 mA
Y
MANUAL SP = XXX
TRAVEL = XXX
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
CHECK
MOUNTING
FINDING 100% ...
FINDING 100% ...
AUTO
MOVE VALVE TO
100% TRAVEL
MANUAL
AUTOTUNING IN
PROGRESS...
TUNING
C
EXPERT,
C,D,E,F,G
H,I,J,K,L,M
INPUT RANGE
LOW 4 mA
4 mA
...
19 mA
APPLY 20 mA
THEN PRESS
USE OR
TO SEND 20 mA
!
CHECK
SUPPLY
Y
Y
FINDING 0% ...
Y
MOVE VALVE TO
0% TRAVEL
Y
AUTOTUNING
COMPLETE
Y
AUTOTUNING FAILED
USE MANUAL TUNING
Y
DAMPING
NEUTRAL
+5
NEUTRAL
-5
Y
Y
INPUT RANGE
HIGH 20 mA
5 mA
...
20 mA
Y
SAVE AND EXIT?
PRESS
1
Y
Y
1
CHECK I/P
CONVERTER
Y
FINDING 50% ...FINDING 0% ...
Y
FINDING 50% ...
Y
FINDING 50% ...
1
Y
SAVE AND EXIT?
PRESS
Y
CHARACTERISTIC
LINEAR
SAVE AND EXIT?
EXIT W/O SAVING?
QUICK OPEN
LINEAR
EQUAL %
CUSTOM
1
Y
SAVE AND EXIT?
EXIT W/O SAVING?
Y
SAVE AND EXIT?
PRESS
SAVE AND EXIT? EXIT
W/O SAVING?
1
2
Quick Start Guide
D103203X012
Only when transmitter / limit switch
hardware is installed
DVC2000 Digital Valve Controller
June 2020
REPLACE MAIN
BOARD
Y
QUICK SETUP
COMPLETE
Y
CALIBRATION
COMPLETE
Y
CALIBRATION
FAILED
Y
SAVE AND EXIT?
PRESS
Y
SWITCH1 = OPEN
Y
SWITCH 2 = CLOSED
1
1
1
1
SAVE AND EXIT? EXIT
W/O SAVING?
Y
Y
FW3:1, HW1:2
TUNING = C
Y
Y
PROTECTION
OFF
OFF
ON
1
+
INVERT DISPLAY 180
Note: Hold + for 3 to 10 seconds
+
CANCEL
(TAKES YOU TO THE HOME SCREEN)
Note: Hold + for 3 to 10 seconds
+ + +
LANGUAGE SELECTION
Note: Hold + + +
for 3 to 10 seconds
Y
TRANSMITTER
4 mA CLOSED
Only when transmitter / limit
switch hardware is installed.
CLOSED
OPEN
Y
SWITCH1
Y
TRIP POINT 90%
Y
SWITCH1 CLOSED
Y
ABOVE 90%
125%
...
-25%
Only when transmitter / limit switch hardware is installed
ABOVE
BELOW
DISABLED
Y
SWITCH2
Y
TRIP POINT 10%
125%
...
-25%
Y
SWITCH2 CLOSED
Y
BELOW 10%
BELOW
ABOVE
DISABLED
Y
SAVE AND EXIT?
PRESS
Y
Y
EXIT W/O SAVING?
PRESS
Y
VALVE MAY MOVE
Y
PRESS FOR 3 SEC
Y
Y
1
1
3
DVC2000 Digital Valve Controller
June 2020
Quick Start Guide
D103203X012
Using this Guide
This guide describes how to install the digital valve controller and setup and calibrate using the local operator
interface. The interface consists of a liquid crystal display, four pushbuttons, and a switch for position transmitter
configuration. The DVC2000 is supplied with one of three different language packs preinstalled, depending on the
firmware revision and ordering option. Language pack options are shown in table 1 on page 19. To configure the
language, follow the procedure outlined in the Basic Setup section. The instrument must be powered with at least 8.5
volts and 3.5 mA to operate the local interface. Certain procedures require up to 20 mA of current.
You can also setup and calibrate the instrument using a Field Communicator such as the AMS Trex
Communicator, a personal computer with ValveLink
™
software, or AMS Suite: Intelligent Device Manager. For
™
Device
information on using the software with a FIELDVUE instrument, refer to the appropriate user guide or help.
Maintenance procedures for replaceable components are included on page 29.
Do not install, operate, or maintain a DVC2000 digital valve controller without being fully trained and
qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal
injury or property damage, it is important to carefully read, understand, and follow all contents of this
quick start guide, including all safety cautions and warnings. Refer to the appropriate supplement listed
below for hazardous area approvals and special instructions for “safe use” and installations in hazardous
locations. If you have any questions about these instructions, contact your your Emerson sales office
before proceeding.
D CSA Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104224X012
D FM Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104225X012
D ATEX Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104226X012
D IECEx Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104227X012
)
)
)
)
Documents are available from your Emerson sales office or at Fisher.com.
Installation
Note
The DVC2000 is not designed to correct for significant stem rotation on sliding stem actuators.
WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before mounting
the DVC2000 digital valve controller:
D Always wear protective clothing, gloves, and eyewear when performing any installation procedures.
D Do not remove the actuator from the valve while the valve is still pressurized.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the control valve.
D Use bypass valves or completely shut off the process to isolate the control valve from process pressure. Relieve process
pressure from both sides of the control valve.
4
Quick Start Guide
D103203X012
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
D Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression so the actuator is not
applying force to the valve stem; this will allow for the safe removal of the stem connector.
DVC2000 Digital Valve Controller
June 2020
WARNING
This product is intended for a specific range of application specifications, found in the Specifications table on page 31.
Incorrect configuration and use of a positioning instrument could result in the malfunction of the product, property
damage or personal injury.
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed
by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
Note
Refer to the appropriate Hazardous Area Approvals and Special Instructions for “Safe Use" and Installations in Hazardous Locations
supplement for approval specific safe use and installation information (see page 4).
Valve / Actuator Mounting
If ordered as a part of a control valve assembly, the factory will mount the digital valve controller on the actuator and
calibrate the instrument. If you purchased the digital valve controller separately, you will need a mounting kit to
mount the digital valve controller on the actuator. The following procedures are general guidelines you should
consider when mounting the digital valve controller. See the instructions that come with the mounting kit for detailed
information on mounting the digital valve controller to a specific actuator model.
5
DVC2000 Digital Valve Controller
June 2020
Quick Start Guide
D103203X012
The DVC2000 housing is available in four different configurations, depending on the actuator mounting method and
threaded connection style. Figure 1 shows the available configurations.
Figure 1. Housing Variations
HOUSING FOR LINEAR AND ROTARY ACTUATORS,
FISHER 657 SIZE 30i - 70i, AND 667 SIZE 30i - 76i
CONNECTIONS AVAILABLE:
M20 CONDUIT AND G1/4 PNEUMATIC
1/2 NPT CONDUIT AND 1/4 NPT PNEUMATIC
CONDUIT CONNECTIONS
PNEUMATIC CONNECTIONS
W9015
LINEAR, M8
ROTARY NAMUR, M6
HOUSING FOR FISHER GX ACTUATORS
CONNECTIONS AVAILABLE:
M20 CONDUIT AND G1/4 PNEUMATIC
1/2 NPT CONDUIT AND 1/4 NPT PNEUMATIC
W9591
CAPTIVE MOUNTING BOLTS, M8
The feedback system for the DVC2000 digital valve controller utilizes a magnetic field for true linkage‐less,
non‐contacting position measurement. In order to prevent inadvertent stem movement while the instrument is in
operation, magnetic tools (such as a magnetic‐tipped screwdriver) should not be used.
CAUTION
The magnet material has been specifically chosen to provide a long‐term stable magnetic field. However, as with any
magnet, care must be taken when handling the magnet assembly. Another high powered magnet placed in close proximity
(less than 25 mm) can cause permanent damage. Potential sources of damaging equipment include, but are not limited to:
transformers, DC motors, stacking magnet assemblies.
CAUTION
General Guidelines for use of High Power Magnets with Positioners
Use of high power magnets in close proximity to any positioner which is operating a process should be avoided. Regardless
of the positioner model, high power magnets can affect the positioner’s ability to control the valve.
Use of Magnetic Tools with the DVC2000
D Magnetic Tip Screw Drivers – Magnetic tip screw drivers should not be brought in close proximity to the DVC2000 or the
magnetic assembly (located at the back of the instrument) during process operations.
D Calibrator Strap Magnets
Normally, these calibrators would not be used while an instrument is controlling the process.
High power magnets should be kept at least 15 cm (6 inches) from the DVC2000.
– These are high power magnets used to hold 4-20 ma calibrators.
6
Quick Start Guide
D103203X012
DVC2000 Digital Valve Controller
June 2020
Note
As a general rule, do not use less than 50% of the magnet assembly for full travel measurement. Performance will decrease as the
assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor
(on the back of the DVC2000 housing) has to remain within this range throughout the entire valve travel. See figure 2.
The linear magnet assemblies are symmetrical. Either end may be up.
There are a variety of mounting brackets and kits that
are used to mount the DVC2000 to different actuators.
However, despite subtle differences in fasteners,
brackets, and connecting linkages, the procedures for
mounting can be categorized as follows:
D Air‐to‐open sliding‐stem (linear) actuators
D Air‐to‐close sliding‐stem (linear) actuators
D Air‐to‐open 667 size 30i - 76i or Fisher GX actuator
D Air‐to‐close 657 size 30i - 70i or GX actuator
D Rotary actuators with travel up to 90 degrees
See figure 3 for the different travel feedback magnet
assemblies.
Figure 3. Magnet Assemblies
Figure 2. Travel Range
VALID TRAVEL RANGE
50 mm (2 INCH) SHOWN
MAGNET ASSEMBLY
(ATTACHED TO VALVE STEM)
W8830
INDEX MARK
LINEAR
7, 19, OR 25 mm
(1/4, 3/4, 1 INCH)
LINEAR
38, 50, 110, OR 210 mm
(1‐1/2, 2, 4-1/8, OR 8-1/4 INCH)
ARCED
13 TO 30 DEGREE ROTATION
RSHAFT END
ASSEMBLY 90 DEG
7
DVC2000 Digital Valve Controller
June 2020
Quick Start Guide
D103203X012
Sliding-Stem (Linear) Actuators
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure
that the above measures stay in effect while you work on the equipment.
2. Attach the mounting bracket to the actuator.
3. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners
because fine adjustment is required.
CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the
magnet assembly moving outside the range of the index mark in the feedback slot of the DVC2000 housing.
4. Using the alignment template (supplied with the mounting kit), position the magnet assembly inside the retaining
slot.
5. Align the magnet assembly as follows:
DFor air‐to‐open actuators (e.g. Fisher 667) vertically align the magnet assembly so that the center line of the
alignment template is lined up as close as possible with the upper
extreme of the valid travel range on the
magnet assembly. See figure 4.
DFor air‐to‐close actuators (e.g. Fisher 657) vertically align the magnet assembly so that the center line of the
alignment template is lined up as close as possible with the lower
extreme of the valid travel range on the
magnet assembly. See figure 5.
Figure 4. Air‐to‐Open Magnet Assembly Alignment
ALIGNMENT
TEMPLATE
RETAINING
SLOT
LINE UP WITH
UPPER
EXTREME
OF VALID TRAVEL
RANGE
Figure 5. Air‐to‐Close Magnet Assembly Alignment
RETAINING
SLOT
LINE UP WITH
LOWER
EXTREME
OF VALID TRAVEL
RANGE
ALIGNMENT
TEMPLATE
W9718
8
W9719
Quick Start Guide
D103203X012
DVC2000 Digital Valve Controller
June 2020
6. Tighten the fasteners and remove the alignment template.
Note
Use a flat end hex key to tighten the magnet assembly fasteners to a torque of 2.37 N•m (21 in•lbf) for 4 mm screws, and
5.08 N•m (45 in•lbf) for 5 mm screws. For added security, especially in vibrating services, blue (medium) threadlocker may be
used on the fasteners.
7. Mount the digital valve controller to the mounting bracket, using the mounting bolts. See figure 6.
8. Check for clearance between the magnet assembly and the DVC2000 feedback slot. The magnet assembly should
be positioned so that the index mark in the feedback slot of the DVC2000 housing is within the valid range on the
magnet assembly throughout the range of travel. See figure 2.
9. Install tubing between the actuator casing and the pneumatic positioner output connection that has the arrow
pointing away from the opening. See figure 7.
Figure 6. Mounting Holes for Linear Actuators
M8 THREADED
MOUNTING HOLES
W9015
Figure 7. Conduit and Pneumatic Thread Variations
ARROW P0INTING
AWAY FROM PORT =
OUTPUT TO ACTUATOR
1/4 NPT
PNEUMATIC
ARROW P0INTING
TOWARDS THE PORT =
AIR SUPPLY IN
W9016
CONNECTIONS
G1/4
PNEUMATIC
CONNECTIONS
9
DVC2000 Digital Valve Controller
June 2020
Quick Start Guide
D103203X012
Integral Mounted Fisher Actuators
The DVC2000 digital valve controller mounts directly on the 657 size 30i - 70i, 667 size 30i - 76i, and the GX actuator
without the need for a mounting bracket.
However, in applications where the process temperature exceeds 80_C (176_F), it may be necessary to apply an
insulating gasket between the actuator yoke of the GX and the DVC2000, as shown in figure 8. The heat conducted
from the process line will transmit through the valve body and actuator and ultimately to the DVC2000. Temperature
seen at the DVC2000 is a function of the ambient temperature as well as the process temperature. Guidelines on when
to apply the high temperature gasket set are shown in figure 9.
Figure 8. Mounting to Fisher GX Actuator with Insulating Gasket and O‐Ring.
Figure 9. Guidelines for Applying High Process Temperature Solutions to the Fisher GX and FIELDVUE DVC2000
100
80
60
40
20
AMBIENT TEMP (C)
0
-20
-40
-100
NOTES
ZONE 1: STANDARD GX BONNET AND STANDARD DVC2000 MOUNTING APPLY.
ZONE 2: REQUIRES GX EXTENSION BONNET OR HIGH TEMPERATURE DVC2000 GASKET SET.
-50
0
Note
The GX extension bonnet option is an alternate way to address the high process temperature influence on the DVC2000. However,
if the extension bonnet is used, the high temperature DVC2000 mounting kit is not required.
50100150200250300
PROCESS TEMP (C)
10
Quick Start Guide
D103203X012
If the process and ambient temperatures exceed the limits indicated by zone 2, then the DVC2000 high temperature mounting kit
can not be used. If temperatures exceed zone 2, you must use an extension bonnet or bracket mounted instrument.
DVC2000 Digital Valve Controller
June 2020
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure
that the above measures stay in effect while you work on the equipment.
2. For the GX actuator, identify the yoke side to mount the DVC2000 digital valve controller based on the actuator fail
mode. Refer to the GX Control Valve and Actuator System instruction manual (D103175X012
).
3. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners
because fine adjustment is required.
CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the
magnet assembly moving outside the range of the index mark in the feedback slot of the DVC2000 housing.
4. Using the alignment template (supplied with the mounting kit), position the magnet assembly inside the retaining
slot.
5. Align the magnet assembly as follows:
DFor air‐to‐open 667 size 30i - 76i and GX actuators vertically align the magnet assembly so that the center line of
the alignment template is lined up as close as possible with the upper
extreme of the valid travel range on the
magnet assembly. See figure 10.
DFor air‐to‐close 657 size 30i -70i and GX actuators vertically align the magnet assembly so that the center line of
the alignment template is lined up as close as possible with the lower
extreme of the valid travel range on the
magnet assembly. See figure 11.
Figure 10. Air‐to‐Open Magnet Assembly Alignment
ALIGNMENT TEMPLATE
RETAINING
SLOT
LINE UP WITH
UPPER
EXTREME
OF VALID TRAVEL
RANGE
Figure 11. Air‐to‐Close Magnet Assembly Alignment
ALIGNMENT TEMPLATE
RETAINING
SLOT
LINE UP WITH
LOWER
EXTREME
OF VALID TRAVEL
RANGE
11
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.