Fisher DVC2000 Quick Start Guide

Quick Start Guide
D103203X012
Fisher™ FIELDVUE™ DVC2000 Digital Valve Controller
Contents
Local Interface Flow Chart 2......................
Using this Guide 4..............................
Installation 4..................................
Electrical and Pneumatic Connections 15...........
Basic Setup and Calibration 18....................
Maintenance 29................................
Specifications 31...............................
June 2020
Scan or click to access field support
Note
This guide provides installation, connection, and basic setup and calibration information using the local operator interface.
Refer to the DVC2000 digital valve controller instruction manual (D103176X012 using a Field Communicator, maintenance and troubleshooting information, and replacement part details. This document is available from your Emerson sales office
www.Fisher.com
or at Fisher.com.
W8861-2
) for detailed configuration and calibration
June 2020
Local Interface Flow Chart
Quick Start Guide
D103203X012
Home Screen
TRAVEL = 66.8%
1
14.6 MA 0.92 BAR
Y
B
2
QUICK SETUP
Y
B
TRAVEL
3
CALIBRATION
Y
B
TUNING
4
Y
B
DETAILED SETUP
5
Y
B
ANALOG INPUT
6
CALIBRATION
Y
B
POSITION TRANSMITTER CAL
7
Y
B
LOCAL
8
CONTROL
Y
SHUTDOWN
Y
ACTIVATED
Y
VALVE WILL MOVE
Y
PRESS FOR 3 SEC
Y
CALIBRATION
Y
AUTOMATIC
Y
TUNING
Y
AUTOMATIC
Y
ZERO CTL SIGNAL VALVE CLOSED
Y
VALVE WILL MOVE
Y
PRESS FOR 3 SEC
Y
mA OUT WILL CHANGE PRESS FOR 3 SEC
Only when transmitter / limit switch hardware is installed.
Y
CONTROL ANALOG
Y
AUTOMATIC MANUAL
Y
AUTOMATIC MANUAL
CLOSED OPEN
ANALOG OR DIGITAL MANUAL
Y
Y
Y
Y
These items are identified by an alert icon on the default screen
TRAVEL DEVIATION
Y
FINDING 0% ...
Y
VALVE WILL MOVE PRESS FOR 3 SEC
VALVE WILL MOVE PRESS FOR 3 SEC
AUTO
VALVE MAY MOVE PRESS FOR 3 SEC
MANUAL
Y
PRESSURE UNITS BAR
BAR PSI KPA
Y
APPLY 4 mA THEN PRESS
Y
USE OR TO SEND 4 mA
Y
MANUAL SP = XXX TRAVEL = XXX
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
CHECK MOUNTING
FINDING 100% ...
FINDING 100% ...
AUTO
MOVE VALVE TO 100% TRAVEL
MANUAL
AUTOTUNING IN PROGRESS...
TUNING C
EXPERT, C,D,E,F,G H,I,J,K,L,M
INPUT RANGE LOW 4 mA
4 mA ... 19 mA
APPLY 20 mA THEN PRESS
USE OR TO SEND 20 mA
!
CHECK SUPPLY
Y
Y
FINDING 0% ...
Y
MOVE VALVE TO 0% TRAVEL
Y
AUTOTUNING COMPLETE
Y
AUTOTUNING FAILED USE MANUAL TUNING
Y
DAMPING NEUTRAL
+5 NEUTRAL
-5
Y
Y
INPUT RANGE HIGH 20 mA
5 mA ... 20 mA
Y
SAVE AND EXIT? PRESS
1
Y
Y
1
CHECK I/P CONVERTER
Y
FINDING 50% ...FINDING 0% ...
Y
FINDING 50% ...
Y
FINDING 50% ...
1
Y
SAVE AND EXIT? PRESS
Y
CHARACTERISTIC LINEAR
SAVE AND EXIT? EXIT W/O SAVING?
QUICK OPEN LINEAR EQUAL % CUSTOM
1
Y
SAVE AND EXIT? EXIT W/O SAVING?
Y
SAVE AND EXIT? PRESS
SAVE AND EXIT? EXIT W/O SAVING?
1
2
Quick Start Guide
D103203X012
Only when transmitter / limit switch
hardware is installed
June 2020
REPLACE MAIN BOARD
Y
QUICK SETUP COMPLETE
Y
CALIBRATION COMPLETE
Y
CALIBRATION FAILED
Y
SAVE AND EXIT? PRESS
Y
SWITCH1 = OPEN
Y
SWITCH 2 = CLOSED
1
1
1
1
SAVE AND EXIT? EXIT W/O SAVING?
Y
Y
FW3:1, HW1:2 TUNING = C
Y
Y
PROTECTION OFF
OFF ON
1
+
INVERT DISPLAY 180
Note: Hold + for 3 to 10 seconds
+ CANCEL
(TAKES YOU TO THE HOME SCREEN)
Note: Hold + for 3 to 10 seconds
+ + +
LANGUAGE SELECTION
Note: Hold + + +
for 3 to 10 seconds
Y
TRANSMITTER 4 mA CLOSED
Only when transmitter / limit switch hardware is installed.
CLOSED OPEN
Y
SWITCH1
Y
TRIP POINT 90%
Y
SWITCH1 CLOSED
Y
ABOVE 90%
125% ...
-25%
Only when transmitter / limit switch hardware is installed
ABOVE BELOW DISABLED
Y
SWITCH2
Y
TRIP POINT 10%
125% ...
-25%
Y
SWITCH2 CLOSED
Y
BELOW 10%
BELOW ABOVE DISABLED
Y
SAVE AND EXIT? PRESS
Y
Y
EXIT W/O SAVING? PRESS
Y
VALVE MAY MOVE
Y
PRESS FOR 3 SEC
Y
Y
1
1
3
June 2020
Quick Start Guide
D103203X012
Using this Guide
This guide describes how to install the digital valve controller and setup and calibrate using the local operator interface. The interface consists of a liquid crystal display, four pushbuttons, and a switch for position transmitter configuration. The DVC2000 is supplied with one of three different language packs preinstalled, depending on the firmware revision and ordering option. Language pack options are shown in table 1 on page 19. To configure the language, follow the procedure outlined in the Basic Setup section. The instrument must be powered with at least 8.5 volts and 3.5 mA to operate the local interface. Certain procedures require up to 20 mA of current.
You can also setup and calibrate the instrument using a Field Communicator such as the AMS Trex Communicator, a personal computer with ValveLink
software, or AMS Suite: Intelligent Device Manager. For
Device
information on using the software with a FIELDVUE instrument, refer to the appropriate user guide or help.
Maintenance procedures for replaceable components are included on page 29.
Do not install, operate, or maintain a DVC2000 digital valve controller without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal
injury or property damage, it is important to carefully read, understand, and follow all contents of this quick start guide, including all safety cautions and warnings. Refer to the appropriate supplement listed
below for hazardous area approvals and special instructions for “safe use” and installations in hazardous locations. If you have any questions about these instructions, contact your your Emerson sales office before proceeding.
D CSA Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104224X012
D FM Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104225X012
D ATEX Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104226X012
D IECEx Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104227X012
)
)
)
)
Documents are available from your Emerson sales office or at Fisher.com.
Installation
Note
The DVC2000 is not designed to correct for significant stem rotation on sliding stem actuators.
WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before mounting the DVC2000 digital valve controller:
D Always wear protective clothing, gloves, and eyewear when performing any installation procedures.
D Do not remove the actuator from the valve while the valve is still pressurized.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the control valve.
D Use bypass valves or completely shut off the process to isolate the control valve from process pressure. Relieve process
pressure from both sides of the control valve.
4
Quick Start Guide
D103203X012
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
D Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression so the actuator is not
applying force to the valve stem; this will allow for the safe removal of the stem connector.
June 2020
WARNING
This product is intended for a specific range of application specifications, found in the Specifications table on page 31. Incorrect configuration and use of a positioning instrument could result in the malfunction of the product, property damage or personal injury.
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
Note
Refer to the appropriate Hazardous Area Approvals and Special Instructions for “Safe Use" and Installations in Hazardous Locations supplement for approval specific safe use and installation information (see page 4).
Valve / Actuator Mounting
If ordered as a part of a control valve assembly, the factory will mount the digital valve controller on the actuator and calibrate the instrument. If you purchased the digital valve controller separately, you will need a mounting kit to mount the digital valve controller on the actuator. The following procedures are general guidelines you should consider when mounting the digital valve controller. See the instructions that come with the mounting kit for detailed information on mounting the digital valve controller to a specific actuator model.
5
June 2020
Quick Start Guide
D103203X012
The DVC2000 housing is available in four different configurations, depending on the actuator mounting method and threaded connection style. Figure 1 shows the available configurations.
Figure 1. Housing Variations
HOUSING FOR LINEAR AND ROTARY ACTUATORS,
FISHER 657 SIZE 30i - 70i, AND 667 SIZE 30i - 76i
CONNECTIONS AVAILABLE:
M20 CONDUIT AND G1/4 PNEUMATIC 1/2 NPT CONDUIT AND 1/4 NPT PNEUMATIC
CONDUIT CONNECTIONS
PNEUMATIC CONNECTIONS
W9015
LINEAR, M8
ROTARY NAMUR, M6
HOUSING FOR FISHER GX ACTUATORS
CONNECTIONS AVAILABLE:
M20 CONDUIT AND G1/4 PNEUMATIC 1/2 NPT CONDUIT AND 1/4 NPT PNEUMATIC
W9591
CAPTIVE MOUNTING BOLTS, M8
The feedback system for the DVC2000 digital valve controller utilizes a magnetic field for true linkage‐less, non‐contacting position measurement. In order to prevent inadvertent stem movement while the instrument is in operation, magnetic tools (such as a magnetic‐tipped screwdriver) should not be used.
CAUTION
The magnet material has been specifically chosen to provide a long‐term stable magnetic field. However, as with any magnet, care must be taken when handling the magnet assembly. Another high powered magnet placed in close proximity (less than 25 mm) can cause permanent damage. Potential sources of damaging equipment include, but are not limited to: transformers, DC motors, stacking magnet assemblies.
CAUTION
General Guidelines for use of High Power Magnets with Positioners
Use of high power magnets in close proximity to any positioner which is operating a process should be avoided. Regardless of the positioner model, high power magnets can affect the positioner’s ability to control the valve.
Use of Magnetic Tools with the DVC2000
D Magnetic Tip Screw Drivers – Magnetic tip screw drivers should not be brought in close proximity to the DVC2000 or the
magnetic assembly (located at the back of the instrument) during process operations.
D Calibrator Strap Magnets
Normally, these calibrators would not be used while an instrument is controlling the process. High power magnets should be kept at least 15 cm (6 inches) from the DVC2000.
– These are high power magnets used to hold 4-20 ma calibrators.
6
Quick Start Guide
D103203X012
June 2020
Note
As a general rule, do not use less than 50% of the magnet assembly for full travel measurement. Performance will decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor (on the back of the DVC2000 housing) has to remain within this range throughout the entire valve travel. See figure 2.
The linear magnet assemblies are symmetrical. Either end may be up.
There are a variety of mounting brackets and kits that are used to mount the DVC2000 to different actuators. However, despite subtle differences in fasteners, brackets, and connecting linkages, the procedures for mounting can be categorized as follows:
D Air‐to‐open sliding‐stem (linear) actuators
D Air‐to‐close sliding‐stem (linear) actuators
D Air‐to‐open 667 size 30i - 76i or Fisher GX actuator
D Air‐to‐close 657 size 30i - 70i or GX actuator
D Rotary actuators with travel up to 90 degrees
See figure 3 for the different travel feedback magnet assemblies.
Figure 3. Magnet Assemblies
Figure 2. Travel Range
VALID TRAVEL RANGE 50 mm (2 INCH) SHOWN
MAGNET ASSEMBLY (ATTACHED TO VALVE STEM)
W8830
INDEX MARK
LINEAR 7, 19, OR 25 mm (1/4, 3/4, 1 INCH)
LINEAR 38, 50, 110, OR 210 mm (1‐1/2, 2, 4-1/8, OR 8-1/4 INCH)
ARCED 13 TO 30 DEGREE ROTATION
RSHAFT END ASSEMBLY 90 DEG
7
June 2020
Quick Start Guide
D103203X012
Sliding-Stem (Linear) Actuators
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
2. Attach the mounting bracket to the actuator.
3. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners because fine adjustment is required.
CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the magnet assembly moving outside the range of the index mark in the feedback slot of the DVC2000 housing.
4. Using the alignment template (supplied with the mounting kit), position the magnet assembly inside the retaining slot.
5. Align the magnet assembly as follows:
DFor air‐to‐open actuators (e.g. Fisher 667) vertically align the magnet assembly so that the center line of the
alignment template is lined up as close as possible with the upper
extreme of the valid travel range on the
magnet assembly. See figure 4.
DFor air‐to‐close actuators (e.g. Fisher 657) vertically align the magnet assembly so that the center line of the
alignment template is lined up as close as possible with the lower
extreme of the valid travel range on the
magnet assembly. See figure 5.
Figure 4. Air‐to‐Open Magnet Assembly Alignment
ALIGNMENT TEMPLATE
RETAINING SLOT
LINE UP WITH UPPER
EXTREME OF VALID TRAVEL RANGE
Figure 5. Air‐to‐Close Magnet Assembly Alignment
RETAINING SLOT
LINE UP WITH LOWER
EXTREME OF VALID TRAVEL RANGE
ALIGNMENT TEMPLATE
W9718
8
W9719
Quick Start Guide
D103203X012
June 2020
6. Tighten the fasteners and remove the alignment template.
Note
Use a flat end hex key to tighten the magnet assembly fasteners to a torque of 2.37 Nm (21 inlbf) for 4 mm screws, and
5.08 Nm (45 inlbf) for 5 mm screws. For added security, especially in vibrating services, blue (medium) threadlocker may be used on the fasteners.
7. Mount the digital valve controller to the mounting bracket, using the mounting bolts. See figure 6.
8. Check for clearance between the magnet assembly and the DVC2000 feedback slot. The magnet assembly should be positioned so that the index mark in the feedback slot of the DVC2000 housing is within the valid range on the magnet assembly throughout the range of travel. See figure 2.
9. Install tubing between the actuator casing and the pneumatic positioner output connection that has the arrow pointing away from the opening. See figure 7.
Figure 6. Mounting Holes for Linear Actuators
M8 THREADED MOUNTING HOLES
W9015
Figure 7. Conduit and Pneumatic Thread Variations
ARROW P0INTING AWAY FROM PORT = OUTPUT TO ACTUATOR
1/4 NPT PNEUMATIC
ARROW P0INTING TOWARDS THE PORT = AIR SUPPLY IN
W9016
CONNECTIONS
G1/4 PNEUMATIC CONNECTIONS
9
June 2020
Quick Start Guide
D103203X012
Integral Mounted Fisher Actuators
The DVC2000 digital valve controller mounts directly on the 657 size 30i - 70i, 667 size 30i - 76i, and the GX actuator without the need for a mounting bracket.
However, in applications where the process temperature exceeds 80_C (176_F), it may be necessary to apply an insulating gasket between the actuator yoke of the GX and the DVC2000, as shown in figure 8. The heat conducted from the process line will transmit through the valve body and actuator and ultimately to the DVC2000. Temperature seen at the DVC2000 is a function of the ambient temperature as well as the process temperature. Guidelines on when to apply the high temperature gasket set are shown in figure 9.
Figure 8. Mounting to Fisher GX Actuator with Insulating Gasket and O‐Ring.
Figure 9. Guidelines for Applying High Process Temperature Solutions to the Fisher GX and FIELDVUE DVC2000
100
80
60
40
20
AMBIENT TEMP (C)
0
-20
-40
-100
NOTES ZONE 1: STANDARD GX BONNET AND STANDARD DVC2000 MOUNTING APPLY. ZONE 2: REQUIRES GX EXTENSION BONNET OR HIGH TEMPERATURE DVC2000 GASKET SET.
-50
0
Note
The GX extension bonnet option is an alternate way to address the high process temperature influence on the DVC2000. However, if the extension bonnet is used, the high temperature DVC2000 mounting kit is not required.
50 100 150 200 250 300
PROCESS TEMP (C)
10
Quick Start Guide
D103203X012
If the process and ambient temperatures exceed the limits indicated by zone 2, then the DVC2000 high temperature mounting kit can not be used. If temperatures exceed zone 2, you must use an extension bonnet or bracket mounted instrument.
June 2020
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
2. For the GX actuator, identify the yoke side to mount the DVC2000 digital valve controller based on the actuator fail mode. Refer to the GX Control Valve and Actuator System instruction manual (D103175X012
).
3. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners because fine adjustment is required.
CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the magnet assembly moving outside the range of the index mark in the feedback slot of the DVC2000 housing.
4. Using the alignment template (supplied with the mounting kit), position the magnet assembly inside the retaining slot.
5. Align the magnet assembly as follows:
DFor air‐to‐open 667 size 30i - 76i and GX actuators vertically align the magnet assembly so that the center line of
the alignment template is lined up as close as possible with the upper
extreme of the valid travel range on the
magnet assembly. See figure 10.
DFor air‐to‐close 657 size 30i -70i and GX actuators vertically align the magnet assembly so that the center line of
the alignment template is lined up as close as possible with the lower
extreme of the valid travel range on the
magnet assembly. See figure 11.
Figure 10. Air‐to‐Open Magnet Assembly Alignment
ALIGNMENT TEMPLATE
RETAINING SLOT
LINE UP WITH UPPER
EXTREME OF VALID TRAVEL RANGE
Figure 11. Air‐to‐Close Magnet Assembly Alignment
ALIGNMENT TEMPLATE
RETAINING SLOT
LINE UP WITH LOWER
EXTREME OF VALID TRAVEL RANGE
11
Loading...
+ 23 hidden pages