A failure of this application — for whatever reason -- may leave an operating process without appropriate
protection and could result in possible damage to property or injury to persons. To protect against this, you
should review the need for additional backup equipment or provide alternate means of protection (such as
alarm devices, output limiting, fail-safe valves, relief valves, emergency shutoffs, emergency switches, etc.)
System Training
A well-trained workforce is critical to the success of your operation. Knowing how to correctly install, configure,
program, calibrate, and trouble-shoot your Emerson equipment provides your engineers and technicians with
the skills and confidence to optimize your investment. Remote Automation Solutions offers a variety of ways for
your personnel to acquire essential system expertise. Our full-time professional instructors can conduct
classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You
can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel
costs. For our complete schedule and further information, contact the Remote Automation Solutions Training
Department at 800-338-8158 or email us at education@emerson.com.
ControlWave Station Manager Configuration Manual
Contents
Chapter 1 – Getting Started 1-1
1.1 What is the Station Manager? ................................................................................................... 1-1
1.2 Before You Begin ...................................................................................................................... 1-2
1.3 Installing Station Manager Software ......................................................................................... 1-3
1.4 Starting Station Manager Software ........................................................................................... 1-7
1.4.1 Station Manager IP Startup ........................................................................................... 1-7
1.4.2 Station Manager Serial Startup ..................................................................................... 1-8
1.4.3 Logging Onto the ControlWave Micro ........................................................................... 1-8
1.5 Accessing Pages of the Station Manager Application .............................................................. 1-9
1.6 Entering Data in Fields of the Station Manager Application ..................................................... 1-9
1.7 Setting the Archive Mode ........................................................................................................ 1-10
1.7.1 Clearing Old Archive Files and Setting Other Archive Parameters Before You Set the
4.3.1 Data Storage Parameters dialog box ............................................................................ 4-4
4.3.2 Search Data Collection Criteria dialog box ................................................................... 4-5
4.4 Local History Analog Log .......................................................................................................... 4-6
4.5 List 29 ........................................................................................................................................ 4-8
4.6 Collect Local Logs ..................................................................................................................... 4-8
4.6.1 Selecting Archives or Audit for Collection ..................................................................... 4-8
4.6.2 Collecting a Single Archive or Audit .............................................................................. 4-9
6.4 List 29 ........................................................................................................................................ 6-8
6.5 Standard Recipe Control ........................................................................................................... 6-8
6.5.1 Changing the Floating Point Format in the Recipe ..................................................... 6-10
6.5.2 Saving the Recipe ....................................................................................................... 6-10
6.5.3 Recalling a Saved Recipe, and Sending Its Values to the Controller ......................... 6-11
6.6 User Defined Screen (legacy) ................................................................................................. 6-11
Appendix C - Measurement Canada Inspection C-1
Appendix E - Troubleshooting E-1
Issued: May-2019 Contents v
ControlWave Station Manager Configuration Manual
Appendix M – Modbus Register Maps M-1
Appendix X – Using the External Measurement (XT) Version X-1
Index IND-1
vi Contents Issued: May-2019
Chapter 1 – Getting Started
This chapter discusses how to install the Station Manager application
and provides some general information about how to use it.
In This Chapter
1.1 What is the Station Manager? ......................................................... 1-1
1.2 Before You Begin ............................................................................. 1-2
1.3 Installing Station Manager Software ................................................ 1-3
1.4 Starting Station Manager Software .................................................. 1-7
1.4.1 Station Manager IP Startup .................................................. 1-7
1.4.2 Station Manager Serial Startup ............................................ 1-8
1.4.3 Logging Onto the ControlWave Micro .................................. 1-8
1.5 Accessing Pages of the Station Manager Application ..................... 1-9
1.6 Entering Data in Fields of the Station Manager Application ............ 1-9
1.7 Setting the Archive Mode ............................................................... 1-10
1.7.1 Clearing Old Archive Files and Setting Other Archive Parameters
Before You Set the Archive Mode .................................... 1-11
1.7.2 Setting the Archive Mode ................................................... 1-13
1.8 Checking Status Information on the Page ..................................... 1-15
ControlWave Station Manager Configuration Manual
1.1 What is the Station Manager?
Station Manager is an application that allows the ControlWave Micro
controller to manage up to six (6) natural gas measurement stations that
include, among all the stations, up to:
Maximum of six (6) or eight (8) meter runs, depending on the
software version.
Eighteen (18) control valves.
Eight (8) PID loops per station for control. You can configure each
station for tube switching, and Station Manager supports indication
of bi-directional measurement for up to three (3) pairs of stations.
Three general purpose proportional integral derivative (PID) loops.
The Station Manager application consists of:
A ControlWave project file (*.PRO) pre-programmed for mult-run
multi-station natural gas measurement.
A customized flash configuration profile (*.FCP) file that configures
the ports, audit, and archive parameters of the ControlWave Micro
for the Station Manager.
A TechView session. This includes the TechView session file
(*.TVS), associated *.INI files, and a set of HTM menus customized
for the Station Manager application. You use these menus to
configure the application.
Issued: May-2019 Getting Started 1-1
ControlWave Station Manager Configuration Manual
Note: Two versions of Station Manager are available for purchase:
Station Manager 6-Run supports up to six meter runs and also
supports communication to HART® devices, and a Coriolis Modbus
interface. Station Manager 6-Run has Measurement Canada
approvals; see Appendix C for details.
Station Manager 8-Run supports up to eight meter runs, without
HART® support, and without the Coriolis Modbus interface.
The maximum number of meter runs also affects the number of
certain components you can define, for example the number of
ultrasonic flow meters (UFMs) or gas chromatographs (GC).
1.2 Before You Begin
You must install the ControlWave Micro controller on site and
connect field devices to its I/O modules. For information on
ControlWave Micro hardware, see document CI-ControlWave Micro.
For this version of Station Manager, your ControlWave Micro must
have 64MB of SDRAM and 5.60 firmware (or newer).
For full functionality, your ControlWave Micro should not use the
System Controller Module (SCM) used with the ControlWave EFM;
you should use a power supply sequence module (PSSM).
You must install OpenBSI software (5.9 or newer) including
TechView on your PC workstation. See the OpenBSI Utilities
Manual (D5081), the BSI_Config User’s Manual (D5128), and the
TechView User Manual (D5131) for details on installation
requirements.
For optimum results, you should set the screen resolution on your
PC to 1280 x 1024, your screen refresh rate to 60 Hz, and DPI to 96
(normal size).
You must connect the PC workstation to the ControlWave Micro
controller. You can communicate using a serial cable or an Ethernet
cable. Cable diagrams are included in CI-ControlWave Micro.
The ControlWave Micro must be running a flash configuration
profile file (*.FCP) compatible with Station Manager software. For
information on updating FCP files, see Chapter 5 of the OpenBSI Utilities Manual (D5081).
The ControlWave Micro must be running the ControlWave project
(*.PRO) file configured for the Station Manager. See Chapter 7 of
the OpenBSI Utilities Manual (D5081) for information on
downloading a ControlWave project (*.PRO) file.
Your Station Manager application must be properly licensed; if you
purchased a license dongle, you must run the Application Licensing
tool and install the dongle in your USB port. You must then reset
1-2 Getting Started Issued: May-2019
ControlWave Station Manager Configuration Manual
the ControlWave and perform a cold start. See the ControlWave
Designer Programmer’s Handbook (D5125) for more information.
Note: If you ordered your ControlWave Micro with Station Manager
software pre-installed, the FCP and PRO files are already loaded
when the unit ships from the factory.
1.3 Installing Station Manager Software
Notes:
Station Manager runs on the following Windows operating systems:
Windows XP and Windows 7
All Station Manager users must have modify privileges to the
\ProgramData\Bristol\StationManager\ folder.
1. Right-click on the Station Manager application’s icon and
choose Run as Administrator.
2. The Station Manager Installer Setup screen opens; allow it to run on
its own.
Figure 1-1. Station Manager Installer Setup Screen.
3. Click Next on the welcome screen of the installer.
Issued: May-2019 Getting Started 1-3
ControlWave Station Manager Configuration Manual
Figure 1-2. Station Manager Installer – Welcome Screen
4. You can look at the Read Me file to view information about this
release. Use the scroll bar to view portions not currently on
screen. Click Next to proceed.
Figure 1-3. Station Manager Installer – Read Me
5. Review the license agreement and click the I Agree button to
proceed with the installation or Cancel to abort the installation
process
1-4 Getting Started Issued: May-2019
ControlWave Station Manager Configuration Manual
Figure 1-4. License Agreement page
Figure 1-5. Selecting Application (8-Run Version ONLY)
The installation begins.
6. At the completion of the installation, click Next.
Issued: May-2019 Getting Started 1-5
ControlWave Station Manager Configuration Manual
Figure 1-6. Installation Completion
7. Now click Finish to exit the installer.
Figure 1-7. Exit the Installer
1-6 Getting Started Issued: May-2019
ControlWave Station Manager Configuration Manual
1.4 Starting Station Manager Software
You start the Station Manager software by invoking the proper
TechView file. There are two ways to do this:
Starting Station
Manager from the Start
Programs Menu
Starting Station
Manager from an icon
1.4.1 Station Manager IP Startup
For an IP connection, click: Start > Programs > StationManager >
SM_4_25_IP_tvs
For a serial connection, click: Start > Programs > StationManager >
SM_4_25_Serial_tvs
From a desktop icon, similar to those below, or from the
\Station_Manager\ SM_4_0\SUPPORT folder, double-click the IP or
serial TVS file, depending upon your type of connection.
Figure 1-8. Station Manager TVS file icons
For IP communication, see Section 1.4.1Station Manager IP Startup.
For serial communication see Section1.4.2Station Manager Serial
Startup.
Once you start the TVS file for IP operation, TechView opens the
Runtime Configuration Parameters dialog box:
Figure 1-9. IP Runtime Parameters
1. Leave the number of transmitters at the default value.
2. Enter the IP address of the ControlWave Micro IP port to
which you are connected.
3. Click OK.
4. Log onto the ControlWave Micro as described in Section 1.4.3.
Issued: May-2019 Getting Started 1-7
ControlWave Station Manager Configuration Manual
1.4.2 Station Manager Serial Startup
Once you start the TVS file for serial operation, TechView opens the
Runtime Configuration Parameters dialog box:
Figure 1-10. Serial Runtime Parameters
1. Leave the number of transmitters at the default of 12.
2. Enter the BSAP local address of the ControlWave Micro to
which you are connected.
3. Select the serial communication port on the PC which you are
using to communicate with the ControlWave Micro.
4. Select the baud rate on the serial communication line.
5. Click OK.
6. Log onto the ControlWave Micro as described in Section 1.4.3.
1.4.3 Logging Onto the ControlWave Micro
In the SignOn to RTU dialog box, enter a Username / Password
combination that allows full access to the ControlWave Micro, then
click the SignOn button.
Figure 1-11. Logging onto the ControlWave Micro
1-8 Getting Started Issued: May-2019
ControlWave Station Manager Configuration Manual
1.5 Accessing Pages of the Station Manager Application
To access various pages of the Station Manager application, click on the
tab for the function you want to configure, then click on the buttons
which appear on that tab. By default, the I/O tab appears first.
Click on the tab you want to access, then
click on any of the buttons for that tab
Tabs
Buttons
Figure 1-12. Tabs and Buttons in Station Manager
The next several chapters describe the functions available on each tab of
the application.
You need not configure all the features of the application; only those
that you need for your particular purpose and measurement needs.
1.6 Entering Data in Fields of the Station Manager Application
Whenever you select a field and enter data, or select from a drop-down
menu, you must press the [Enter] key to confirm and save your choice.
To exit a field without entering data, press the [Esc] key.
Issued: May-2019 Getting Started 1-9
ControlWave Station Manager Configuration Manual
1.7 Setting the Archive Mode
When you first start Station Manager, you may see a warning indicating
that the archive mode is not set (see Figure 1-13).
Figure 1-13. Archive Mode Not Set Warning
This warning tells you that until archiving is configured, Station
Manager cannot log data into archives.
You cannot mix older archive files with new archive files or change
Caution
archive file parameters after archive collection begins:
If you’ve never configured archives, and you plan to use the default
archive mode (Push Down) and no archives exist on this PC
workstation or in the ControlWave Micro, you can proceed to set the
archive mode as described in Section 1.7.2 Setting the Archive Mode.
If old archives already exist, and/or you plan to use Wrap Around
mode, or you want to change archiving parameters, you must first
follow the instructions in Section 1.7.1 Clearing Old Archive Files
and Setting Other Archive Parameters Before You Set the Archive
Mode.
You have three choices when you see this warning.
Field Description
Click to Hide
Disable warning for
one hour
Click to Set Archives
During initial configuration, the warning doesn’t really
matter, so you can click here to hide the warning. The
warning will not be present until you open another
TechView screen or restart TechView.
Check this box to disable the warning for one hour, or
until TechView is restarted, after which the warning
returns.
Click this button to set the archive mode. See
Section 1.7.2, below.
1-10 Getting Started Issued: May-2019
ControlWave Station Manager Configuration Manual
1.7.1 Clearing Old Archive Files and Setting Other Archive
Parameters Before You Set the Archive Mode
If you plan to use the default archive mode (Push Down) with default
archive parameters, and no older archive files exist on your PC
workstation or in the ControlWave Micro, you can skip this section and
proceed to Section 1.7.2.
The instructions in this section delete archive data files from your
Caution
ControlWave Micro and your OpenBSI workstation. Be sure you follow
the steps carefully, and in the order shown, so you can save those
archives, if you need to preserve them.
You cannot mix older archive files with different storage methods or
archive parameters with new archive files. Therefore, if older archive
files exist on your PC workstation, or you plan to use Wrap Around
mode for your archives or you want to change archive parameters, you
must follow these steps in the order shown, first:
Clearing Old
Archive Files
from Station
Manager AND
the ControlWave
Micro
1. If the ControlWave Micro holds existing archive files you have not yet
collected, follow the instructions in Chapter 4 of this manual, to collect
those archives.
Figure 1- 14 Collect Local Archives
2. To preserve the archive files you just collected,(and any other archives files
collected by Station Manager) go to Station Manager’s Log area, and copy
those files to a different location. By default, the log area is located in the
path \OpenBSI\Station Manager\Logs.
3. Now that you have a safe copy of the log files elsewhere (Step 2), delete all
files in the \Station Manager\Logs area.
4. Cold start the ControlWave Micro. To do this, click Start > Programs >
OpenBSI Tools > Debugging Tools > Reset ControlWave then log into
the unit, and click the Cold Start button. When the status message shows
“Restart Complete,” click Close.
Issued: May-2019 Getting Started 1-11
ControlWave Station Manager Configuration Manual
Figure 1-15. Reset ControlWave Unit
5. In TechView, clear all archives from the ControlWave Micro. To do this,
click Operations > Clear History. Then select Clear All Archive Files
and click Start. Answer the prompts to perform the deletion, and when the
status message says “Task Complete,” click Exit to close the Clear RTU
History utility.
Figure 1-16. Clear RTU History
Changing
Archive
Parameters
Now that you’ve deleted all existing archive files you can optionally
change archive parameters for Enron Modbus collections. These are set in
List 20 in the ControlWave Station Manager application. You can call List
20 up using DataView; right click on the RTU icon in TechView, choose
DataView from the pop-up menu. Once DataView opens, click the Remote
List icon and enter 20 in the Remote List Properties dialog box and
click OK; this opens list 20. You can then click on a value to change it.
1-12 Getting Started Issued: May-2019
ControlWave Station Manager Configuration Manual
Figure 1-17. – Calling Up DataView
You can change archive parameters through this list. For example, you
can change date formats (Parameter 6) for archive entries here through
the MB.ENRON_DTFORMAT variable. For details on these different
parameters, see the ACCOL3 function block online help in
ControlWave Designer for the CUSTOM function block and look up
Enron Modbus.
Figure 1-18. Enron Modbus Icon in ACCOL3 Function Block Help
You can now select the archive mode as described in Section 1.7.2
Setting the Archive Mode and begin to collect new archives.
1.7.2 Setting the Archive Mode
You may select one of two modes for the way archived data is stored for
retrieval via Enron Modbus.
Push Down – This is the default mode. In this mode a request for
archive record 1 returns the record with the oldest local sequence
number and the oldest timestamp. A request for the highest archive
record number (840 for the hourly archives, 62 for the daily archives)
Issued: May-2019 Getting Started 1-13
ControlWave Station Manager Configuration Manual
returns the record with the newest local sequence number and the most
recent timestamp.
Wrap Around – In this mode, a request for archive record 1 returns the
record in the archive with the newest data. A request for the highest
record number returns the record in the archive with the oldest data.
Figure 1-19. Verify Modbus Archive Mode selection
The Current State shows the currently active archive mode. To toggle
that to the other mode, click the desired Set To mode button. After you
have selected the Enron Modbus archive retrieval mode, click Next.
You must now select the archive storage mode. The selections are Push Down and Wrap Around, as defined above.
If the archive mode is left as Not Set, no archive records will be
generated. From this selection screen, once you select a mode, the
change will take effect immediately and cannot be changed until the
ControlWave Micro performs a cold start.
After selecting the archive mode, click Done to close this window.
Figure 1-20. Setting the Archive Storage Mode selection
1-14 Getting Started Issued: May-2019
ControlWave Station Manager Configuration Manual
1.8 Checking Status Information on the Page
On the top of most pages in the Station Manager application is the title
block. This provides certain status information about Station Manager
operation.
Show (+) or
hide (-) status
grid
Station Manager
page title
Show Station
Manager software
version
Figure 1-21. Title Block at Top of Screens
The title block shows the following:
The title of the current Station Manager page
The Station Manager software version (you can show/hide this by
clicking the question mark icon.
Show (+) or
hide (-)
scrolling block
of station data
Show (+) or hide (-) Status
Information for stations
and meter runs
Communication
Activity
Name of the site with
which you are
communicating
Maintenance
Mode Status
Flag
Questionable
Status Flag
Alarm Status
The name of the site to which you are communicating.
A communication activity “X” which rotates if communications are
good. If communication is lost it shows a red frowning face.
In addition, if you click the “+” between the “Q” and “M” you can view
status information on all stations and meter runs.
Stations (1-6) Meter Runs (1-8)
Red “Q” indicates one or more
stations/runs have questionable
status flags set.
Figure 1-22. Status Grid
Green “M” indicates no
stations/runs in Maintenance
Mode. Magenta “M” indicates one
or more runs/stations in
Maintenance Mode.
Issued: May-2019 Getting Started 1-15
ControlWave Station Manager Configuration Manual
The Q and M icons just above the grid summarize the system status:
A red “Q” indicates one or more runs/stations have a questionable
status.
A green “M” indicates no stations or runs are in Maintenance Mode.
A magenta “M” indicates at least one run/station is in Maintenance
Mode.
The U icons just above the grid shows the status of communication with
ultrasonic flow meters (UFMs).
A green “U” indicates communications with UFMs are good.
A red “U” indicates communications with at least one UFM have
failed.
This icon only shown in Station Manager 8-Run.
Table 1-1 shows the meaning of the different items in the status grid.
Table 1-1 Status Grid Icons
Line Stations (S1 to S6) Meter Runs (R1 to R8)
M (Maintenance)
Q (Questionable)
Sn = Station not in Maintenance Mode
(White background)
Sn = Station in Maintenance Mode
(Magenta background)
Q = Not questionable -OK (White
background)
Q = Unspecified questionable (Q) data
issue for this station.(Red
background)
DP = Differential pressure (DP) data is
questionable for this station. (Red
background)
SP = Static pressure (SP) data is
questionable for this station. (Red
background)
FT = Flowing temperature (FT) data is
questionable for this station. (Red
background)
** = Multiple (**) questionable data
issues for this station. (Red
background)
Rn = Run not in Maintenance
Mode(White background)
Rn = Run in Maintenance Mode
(Magenta background)
Q = Not questionable -OK (White
background)
Q = Unspecified questionable (Q) data
issue for this run. (Red
background)
DP = Differential pressure (DP) data is
questionable for this run. (Red
background)
SP = Static pressure (SP) data is
questionable for this run. (Red
background)
FT = Flowing temperature (FT) data is
questionable for this run. (Red
background)
** = Multiple (**) questionable data
issues for this run. (Red
background)
A (Alarm)
1-16 Getting Started Issued: May-2019
A = OK. No alarm reported. (White
background)
FP = Flow Permissive (FP) Mode active
for this station.(Yellow background)
DCP = Direction Change Permissive (DCP)
Mode active for this station. (Yellow
A = OK. No alarm reported. (White
background)
FP = Flow Permissive (FP) Mode active
for this run.(Yellow background)
DCP = Direction Change Permissive
(DCP) Mode active for this run.
ControlWave Station Manager Configuration Manual
Line Stations (S1 to S6) Meter Runs (R1 to R8)
background) (Yellow background)
If an item in the status grid has a non-white background color, you can
move your mouse over that location to view an explanatory Detail
message box.
Mouse cursor here
Figure 1-23. Viewing the Detail Message
Note: If you make changes to entries on a Station Manager screen,
the Detail pane must be visible for screen updates to occur.
Issued: May-2019 Getting Started 1-17
ControlWave Station Manager Configuration Manual
Chapter 2 – Configuring Inputs and Outputs (I/O Tab)
This chapter discusses configuring the Station Manager application to
accept field inputs and outputs (I/O). This is accomplished from the
Station Manager’s I/O tab.
2.10User Defined Screen ..................................................................... 2-58
2.11Coriolis Modbus Interface (6-Run Version ONLY) ......................... 2-65
Click the I/O tab to display the various I/O options you can configure.
We’ll discuss each of these in the sections that follow.
To configure an
I/O function or
feature, click on
its button.
Figure 2-1. I/O Tab in Station Manager
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-1
ControlWave Station Manager Configuration Manual
2.2 I/O Usage
When you click the button on
the I/O tab, the I/O Usage page displays a graphical representation of
the ControlWave Micro, showing each of the I/O modules detected by
the Station Manager. If Station Manager cannot detect a particular
module or an I/O slot is empty, its graphic shows “Not Present.”
CPU
Optional
ECOM
module
Click on the graphical
representation of a module
to configure its I/O.
When you move the cursor over the CPU module, an Expansion
Communication (ECOM) module, or any I/O module, you’ll see a
yellow box on the screen. To configure I/O, follow these steps:
1. From the I/O tab, click the I/O Usage button.
2. Position the cursor over the I/O module you want to configure; a
yellow box indicates the cursor position on any configurable
module.
2-2 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
3. Click on the module you want to configure. This opens a screen
showing the possible choices for I/O. The Mixed I/O Module
shows multiple types of I/O (see Figure 2-3).
Figure 2-3. Mixed I/O Module
4. Click in the Assignment field, and use the drop-down menu to
select the function in the Station Manager that you want to
connect to a particular I/O point. For example, if remote control
valve 1’s open limit switch field input is connected to discrete
input 1, select RCV 1 Open Limit for the Assignment. (See
Figure 2-5.) Press the [Enter] key to confirm and save your
choice.
Note: You may have noticed that when the cursor is left hovered over
an IO point, the graphics to the left display the applicable
connection points for direct and remote IO (see Figure 2-4).
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-3
ControlWave Station Manager Configuration Manual
Graphic displays
location of
physical I/O
connections for
an I/O point,
when you hover
the cursor over
the PNT.
Figure 2-4. Connection Points for Physical I/O
5. Continue assigning Station Manager functions to their applicable
field I/O points. See the sub-sections below for information on
the different I/O module types.
Notes:
Only assign a given function to one input I/O point. If you
subsequently assign the same function to a different input point,
Station Manager re-assigns it to your newer choice and disconnects
it from the earlier choice.
Depending upon your particular configuration, you might not use all
the inputs or outputs in a particular meter run or station.
If you have I/O that comes from an ultrasonic flow meter or a multi-
variable transmitter that communicates with the Station Manager
through a communication port, instead of an I/O module, you
configure it from the UFM or Transducer pages, discussed later in
this chapter.
To return to the I/O Usage page from any page underneath it, click
the button.
Figure 2-5. Assigning Discrete Input 1
2-4 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
g
Viewing
Communication Port
Configuration
To view the current port configuration, position the cursor over the
CPU or ECOM module (see Figure 2-2) and click; this displays the
current configuration of ports on the CPU or ECOM module. To alter
the configuration, you need to edit the flash configuration profile for
the ControlWave Micro. Note: Changes made to the flash
configuration profile are not reflected within Station Manager screens
until you restart the ControlWave Micro.
Figure 2-6. Viewing Configuration of Ports
2.2.1 Discrete Inputs (DI)
Discrete inputs (DIs) include the following fields:
Field Description
PNT This read-only field displays the I/O point number. The
INV If you check this box for a given I/O point, Station
Live This read-only field shows the actual ON/OFF status of
number varies depending upon the type of I/O module.
Manager inverts the real-live field value and uses the
inverted value as the process value. For example, if the
Live value of discrete I/O point 5 is OFF, and INV is
checked for that point, PV is set ON and that’s what
Station Manager uses for control and processing.
this discrete input point.
Points that are ON show in red.
Points that are OFF show in
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-5
reen.
ControlWave Station Manager Configuration Manual
g
y
y
PV This read-only field shows the value of the process
variable (PV) used in Station Manager. This matches
the Live value unless you invert the input using INV.
Points that are ON show in red.
Assignment Use the drop-down menu to select the function within
2.2.2 Discrete Outputs (DO)
Discrete outputs (DOs) include the following fields:
Field Description
PNT This read-only field displays the I/O point number. The
PV This read-only field shows the value of the process
Assignment Use the drop-down menu to select the function within
2.2.3 Analog Inputs (AI)
Analog inputs (AIs) include the following fields:
Field Description
PNT This read-only field displays the I/O point number. The
Points that are OFF show in
Station Manager that corresponds to this discrete input.
Press [Enter] to save
number varies depending upon the type of I/O module.
variable (PV) Station Manager will output to the field
device.
Station Manager that corresponds to this discrete
output. Press [Enter] to save
number varies depending upon the type of I/O module.
reen.
our selection.
our selection.
PV This read-only field shows the calculated value of the
analog input process variable (PV) based on the
configured Zero and Span.
If the value shows in red, the value is questionable
. This could indicate no connection, a
communication problem with the field device, data
timeout or some other problem that could cause the
value to be invalid.
Zero Enter the value that the process variable should read
when the AI field input is 4mA. Press [Enter] to save
your selection.
Span Enter the value that, when added to the Zero value,
represents what the process variable should display
when the AI field input is 20mA. Press [Enter] to save
your selection.
2-6 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
Units The engineering units for this process
Assignment Use the drop-down menu to select the function within
2.2.4 Analog Outputs (AO)
ControlWave Station Manager Configuration Manual
For example, if Zero is 5 and Span is 20, then:
If the AI field input is: PV will be:
4mA 5
20mA 25
12mA 15
variable. Click in the field and select
the proper units from the drop-down
menu. Press [Enter] to save your
selection.
Station Manager that corresponds to this analog input.
Press [Enter] to save the selection.
Analog outputs (AOs) include the following fields:
Field Description
PNT This read-only field displays the I/O point number. The
number varies depending upon the type of I/O module.
PV This read-only field shows the calculated value of the
analog output process variable (PV) based on the
configured Zero and Span. This value will be sent to
the field device.
Zero Enter the value that the process variable should read
when the AO field output is 4mA. Press [Enter] to save
your selection.
Span Enter the value that, when added to the Zero value,
represents what the process variable should display
when the AO field output is 20mA. Press [Enter] to
save your selection. For example, if Zero is 5 and Span
is 20, then:
If PV is: The AO field output is:
5 4mA
25 20mA
10 8mA
Units The engineering units for this process variable. Click in
the field and select the proper units from the drop-down
menu. Press [Enter] to save your selection.
Assignment Use the drop-down menu to select the function within
Station Manager that corresponds to this analog output.
Press [Enter] to save the selection.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-7
ControlWave Station Manager Configuration Manual
2.2.5 High Speed Counters (HSC)
High speed counters (HSC) include the following fields:
Field Description
PNT This read-only field displays the I/O point number. The
Counts This read-only field displays the number of counts since
Time Stamp This read-only field displays the timestamp of the last
Assignment Use the drop-down menu to select the function within
2.2.6 Multi-variable Transmitters (Transducers)
number varies depending upon the type of I/O module.
the last power cycle.
sample from the HSC module. The timestamp is the
number of milliseconds since boot.
Station Manager that corresponds to this high speed
counter input. Press [Enter] to save the selection.
If you have one or more multi-variable transmitters, click the
button on the top of the I/O tab to call up the
Transducers page.
The following MVTs have been tested with Station Manager:
The Transducers page shows the first three multi-variable transmitters
(MVTs) for the station; if you want to view a different group of three
MVTs, click the tab corresponding to the range of MVTs you want to
see.
2-8 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
Field Description
Enabled/Disabled Click this button to enable communication from this
MVT to the Station Manager.
Communication
Protocol
(BSAP/MODBUS)
Port Use the dropdown menu to specify the ControlWave
Address Enter the address of the MVT here. Press [Enter] to
Xmtr Type Use the drop-down menu to select the type of data
Register Set This field applies only to MODBUS communication.
Comm Stats % Good This read-only field shows the percentage of
Click the BSAP/MODBUS button to toggle the method
used to communicate with this MVT between BSAP
protocol and MODBUS protocol.
Micro serial communication port which connects to this
MVT. Press [Enter] to save the selection.
save the selection.
coming from this MVT. Choose either:
Type: Data from this type:
GP/T gage pressure and temperature
DP/P/T differential pressure, static pressure, and
temperature
T temperature
Press [Enter] to save your selection.
Click either 7xxx or 4xxxx to select the MODBUS
re
ister set used by this MVT.
successful communication transactions with this MVT.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-9
ControlWave Station Manager Configuration Manual
(
Good Polls This read-only field shows the number of good poll
Bad Polls This read-only field shows the number of bad poll
Reset This button resets the communication statistics in the
Current Status These read-only fields display the most recent status
Tag Name
Serial Number This read-only field shows the serial number from this
Time Stamp This read-only field shows the time stamp of the most
DP This read-only field shows the most recent differential
SP This read-only field shows the most recent static
FT This read-only field shows the most recent
Units This read-only field shows the engineering units for
Zero This read-only field shows the value for this variable
Span This read-only field shows the value that, when added
messages in communications with this MVT.
messages in communications with this MVT.
%Good, Good Polls, and Bad Polls fields.
messages from this MVT.
This read-only field shows the tag name from this
MVT. (BSAP only)
MVT.
MODBUS only)
recent value received from this MVT.
pressure reading from this MVT.
pressure reading from this MVT.
temperature reading from this MVT.
this variable.
when the MVT receives a 4mA field input.
to the Zero value, represents what the process
variable should display when the field input to the MVT
is 20mA.
2.2.7 HART Transmitters (6-Run Version ONLY)
To configure wired HART transmitters, click on the graphical
representation of the HART/BTI module in the I/O Usage screen. This
calls up the HART Configuration page.
2-10 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
2
-
Figure 2-8. HART Configuration
Field Description
General
Number Select the HART transmitter number (from 1 to 18).
Enable/Disable Click Enable to activate communications with the
transmitter or click Disable to turn off
communications with the transmitter. When the
communication state changes, the Current Status
field updates to show the change, and the label on
the button toggles to the opposite title. After
disabling the transmitter, a cold/warm start of the
CPU is necessary to stop the continuous polling of
the transmitter.
Type Shows the transmitter type:
DP = Differential Pressure
SP = Static Pressure
FT = Flowing Temperature
MVT = Multi-Variable Transducer
Device If HART communications is through the HART/BTI
module, specify the I/O slot in the ControlWave Micro
that holds the HART/BTI module. Only slots 1 and 2
are supported. If HART communication is through a
communication port, specify the ControlWave Micro
COM port number used for HART.
Channel Specify the channel number on the HART/BTI module
associated with the transmitter.
Comm Mode Select whether HART transmitter data comes from the
HART/BTI module or from a COM port.
HART
Tag Shows the tag name read from the HART transmitter.
Device ID Shows the Device ID read from the HART transmitter.
Status
Comm Shows the HART communication status code. Valid
codes are shown in Table
1.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-11
ControlWave Station Manager Configuration Manual
2
-
2
Table 2-1. HART Communication Status Codes
Binary Dec Hex Description
10000000 28 0x80 When this bit is clear the remaining bits represent the command status
response from the device. When this bit is set it indicates there is a
communications error defined by the remaining bits.
01000000 64 0x40 The parity of one or more of the bytes received by the device was not odd.
00100000 32 0x20 At least one byte of received data was not processed fast enough and was
overwritten before it could be read.
00010000 16 0x10 An expected stop bit for one or more bytes received was not detected.
00001000 8 0x08 The longitudinal parity calculated by the device did not match the check byte at
the end of the message.
00000100 4 0x04 Reserved – set to 0.
00000010 2 0x02 The message was too long for the receive buffer of the device.
00000001 1 0x01 Reserved – set to 0.
Device Shows the status code for the HART transmitter.
Valid codes are in Table
.
Table 2-2. HART Device Status Codes
Binary Dec Hex Description
10000000 128 0x80 The device detected a serious error or failure that compromises device
operation.
01000000 64 0x40 An operation was performed that changed the device’s configuration.
00100000 32 0x20 A power failure or device reset has occurred.
00010000 16 0x10 More status information is available; use command48 to read the additional
status information.
00001000 8 0x08 The loop current is being held at a fixed value and is not responding to process
variations.
00000100 4 0x04 The loop current has reached its upper (or lower) endpoint limit and cannot
increase (or decrease) any further.
00000010 2 0x02 A device variable not mapped to the PV is beyond its operating limits.
00000001 1 0x01 The primary variable is beyond its operating limit.
Comm Failure Shows “Okay” in green when communications
are working or “FAIL” in red when there is a
communication failure with the HART
2-12 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
g
transmitter.
Device
Descriptor The descriptive text for this HART transmitter.
Message The message text read from the HART transmitter.
PV
Value Shows the process value read from the HART
transmitter.
Units Shows the engineering units read from the HART
transmitter for the
Range
Upper Shows the upper range for the process variable read
from the HART transmitter.
Lower Shows the lower range for the process variable read
from the HART transmitter.
Units Shows the engineering units for the process variable
read from the HART transmitter.
iven process value.
2.2.8 WirelessHART Transmitters (6-Run Version ONLY)
To configure wireless WirelessHART transmitters, click on the
graphical representation of the IEC62591 module in the I/O Usage
screen. This calls up the Wireless HART Configuration page.
Figure 2-9. Wireless HART Configuration
Field Description
General
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-13
ControlWave Station Manager Configuration Manual
2
-
2
-
g
Number Select the WirelessHART transmitter number (from 1
Enable/Disable Click Enable to activate communications with the
Type Shows the transmitter type:
HART
Tag Shows the tag name read from the WirelessHART
Device ID Shows the Device ID read from the WirelessHART
Status
Comm Shows the WirelessHART communication status code.
Device Shows the status code for the WirelessHART
Device
to 18).
transmitter or click Disable to turn off
communications with the transmitter. When the
communication state changes, the Current Status
field updates to show the change, and the label on
the button toggles to the opposite title.
DP = Differential Pressure
SP = Static Pressure
FT = Flowing Temperature
MVT = Multi-Variable Transducer
transmitter.
transmitter.
Valid codes are listed in Table
transmitter. Valid codes are listed in Table
1.
2.
Descriptor The descriptive text for this WirelessHART transmitter.
Message The message text read from the WirelessHART
transmitter.
Battery DaysShows the number of days of battery life remaining.
PV
Value Shows the process value read from the WirelessHART
transmitter.
Units Shows the engineering units read from the
WirelessHART transmitter for the
Span
Zero Shows the lowest value for the process variable read
from the WirelessHART transmitter.
Span Shows the value which, when added to the Zero value,
represents the full range for the process variable read
from the WirelessHART transmitter.
iven process value.
2-14 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
Notes:
You must specify the Network ID and Join Key for the wireless
network in a text file called whart_key.ini. The first four lines of
the file represent the Join Key, the fifth line is the Network ID. Once
you download the whart_key.ini file into the ControlWave Micro
flash, Station Manager reads the file and then deletes it for added
security. You use the Flash File Access utility in OpenBSI to
download the whart_key.ini file into the ControlWave Micro flash.
The information from the ini file is retained internally across cold
starts so if you ever need to change these parameters, you must
download a new whart_key.ini file.
12345678
00000000
00000000
00000000
13684
Figure 2-10. Sample WHART_KEY.INI file
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-15
ControlWave Station Manager Configuration Manual
g
2.3 Local DLM
Notes:
The local Data Line Monitor (DLM) provides details about low-
level communication messages sent through a selected serial port
used by the Station Manager.
Typically, you would only use the local DLM if you are a very
advanced user and need to perform communication troubleshooting
for a particular port.
The local DLM only displays the first 80 characters of a message.
The local DLM only captures messages approximately every half
second, therefore, it can miss some messages.
Click the button on the I/O tab to
activate the Data Line Monitor function. The DLM includes the
following fields:
Field Description
Monitor Port Use the dropdown menu to select the ControlWave
TX Data This read-only field shows the most recent message
Micro serial communication port you want the DLM to
monitor. Press [Enter] to save the selection.
Note: After you collect the data, if you select “None”
for the monitor port, you can copy data from the
window to the clipboard. You can then paste this data
into another file for off-line review.
transmitted through this port.
RX Data This read-only field shows the most recent message
received through this port.
window The window shows successive messages detected by
the DLM. Most recent messages appear at the top;
you can use the scroll bar to adjust the window to
show earlier messa
es.
2-16 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
2.4 Customer Modbus Slave
Station Manager supports up to five customer Modbus slave sessions
you can configure for the controller. The Station Manager controller
then serves as a Modbus slave to those devices.
Click the button on the I/O tab to bring up
the Customer Modbus Slave pages.
Figure 2-11. Local DLM
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-17
ControlWave Station Manager Configuration Manual
You can
view either
coils or
registers in
the Signal
List grid.
Figure 2-12. Customer Slave Page
These pages include the following fields:
Field Description
Settings
Communications Port
Modbus communications can use either serial or IP
communications.
Serial Click the Serial button to use serial Modbus
communication, and specify the port you want to
use. (See Port).
2-18 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
Field Description
Port Specify the serial communication port on the
ControlWave Micro you want to use for Modbus slave
communication. Use the following code:
Enter this: To select this serial CW Micro port:
1 COM1
2 COM2
3 COM3
4 COM4
5 COM5
6 COM6
7 COM7
8 COM8
9 COM9
10 COM10
11 COM11
Press [Enter] to save the selection.
IP Click the IP button to use IP Modbus (Open Modbus)
communication.
Protocol
Modbus Click this button to configure Modbus
communication.
BSAP Do NOT choose this when configuring Modbus
communication.
Modbus Slave Address
Modbus Type
Enron If you want to communicate using Enron Modbus,
Gould If you want to communicate using Gould Modbus,
Enter the Modbus slave address. If the local slave
address you enter has already been assigned to
either the SCADA Enron Modbus slave interface, or
any of the other Customer Modbus Slave sessions,
you will see a Loc Addr Conflict message. Modify
the Modbus Slave Address as required to resolve
the conflict.
click this button.
click this button.
Data Parameters
Word Order Choose the data word order to match the data word
order used by the Modbus Master that
communicates with this Modbus Slave.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-19
ControlWave Station Manager Configuration Manual
Field Description
High Word First Click this to specify that the high word is first.
Low Word First Click this to specify that the low word is first.
Byte OrderChoose the data byte order to match the data byte
High Byte First Click this to specify that the high byte is first.
Low Byte First Click this to specify that the low byte is first.
Bit OrderChoose the data bit order to match the data bit order
High Bit First Click this to specify that the high bit is first.
order used by the Modbus Master that
communicates with this Modbus Slave.
used by the Modbus Master that communicates with
this Modbus Slave.
Low Bit First Click this to specify that the low bit is first.
Data Size Select the appropriate data format for Modbus
Register data from the drop down menu. The
available selections are:
Single Bit – Each Register will include a single bit
Byte Data – Each Register will include a single byte
16 Bit Integer – Each Register will include a single
16-bit integer
32 Bit Int., 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit double integer.
32 Bit Float, 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit floating point number
32 Bit Int., 2 Reg., Cnt*2, Adr*2 – Two registers will
be used for each 32-bit double integer. The
MODBUS Master must poll two registers for each 32
bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*2 – Two registers
will be used for each 32-bit floating point number.
The MODBUS Master must poll two registers for
each 32 bit number.
32 Bit Int., 2 Reg., Cnt*2, Adr*1 - Two registers will
be used for each 32-bit double integer. The
MODBUS Master must poll a single register for each
32 bit integer.
2-20 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
A
i
g
Field Description
32 Bit Float, 2 Reg., Cnt*2, Adr*1 - Two registers
will be used for each 32-bit floating point number.
The MODBUS Master must poll a single register for
each 32 bit number.
Press [Enter] to save the selection.
If you don’t make a selection, the field shows Not Set.
RTS Delay Mode Select from one of two modes for the Ready-to-Send
(RTS) delay mode.
Message Delay Mode raises RTS, a delay timer starts. The length of the
delay is determined by the value in the Delay Time
field. No message is sent until after this delay
expires. The value of CTS does not affect the
operation of this mode.
CTS Timeout Mode - After the Modbus slave port
raises RTS, it uses the Delay Time value as the
maximum time to wait for CTS to be received from
the master. If the Modbus slave port receives CTS at
any time before this time expires, the port starts to
transmit the message. If the Modbus slave port does
not receive a CTS from the master prior to the
expiration of the Delay Time, it does not respond to
the master and instead reports an error.
Press [Enter] to save the selection.
Delay Time msec Specify the Delay Time (in milliseconds) used by the
RTS Delay Mode and CTS Timeout Mode.
Coils List 12 Each Modbus slave session has two dedicated lists,
one for Modbus Registers and the other for Modbus
Coils. To display coils in the signal list grid, click this
button. See Section2.4.1 for instructions on using
the signal list grid.
fter the Modbus Slave port
Register List 13 Each Modbus slave session has two dedicated lists,
one for Modbus Registers and the other for Modbus
Coils. To display registers in the signal list grid, click
this button. See Section2.4.1 for instructions on
using the signal list grid.
Push to Initialize List /
Initializing
Modbus Status This read-only field displays a status code indicating
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-21
Click Push to InitializeList to set all coils in list 12
to FALSE or all registers in list 13 to 0.0, depending
upon which list you are viewing in the grid The
button shows “Initializing” while this is in progress.
the health of the Modbus slave communications.
If you see any code other than 0 here or see an error
message above the code, see Appendix E – Errors
and Troubleshoot
n
for more information.
ControlWave Station Manager Configuration Manual
Field Description
The fields below are only visible when using BSAP
protocol, which makes the ControlWave Micro
running Station Manager into a BSAP slave.
BSAP Slave Address
Modbus Status
BSAP Server ID Specify the ID for the server function block in your
BSAP Send List 12 Click this to display the send list in the signal list grid.
BSAP Receive List 13 Click this to display the receive list in the signal list
BSAP Status Shows BSAP communication status messages.
2.4.1 Signal List Grid
The Signal List grid displays lists of variables included in the Station
Manager application.
The ControlWave Micro’s BSAP slave address.
ControlWave Micro Station Manager application.
This list holds outgoing data sent to the BSAP
master.
grid. This list holds incoming data received from the
BSAP master.
Figure 2-13. Signal List Grid Control
Field Description
Signal List Information
Number Specifies the number of the list. In some cases,
Max Signals to Collect Specifies the number of list items to retrieve into the
2-22 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
The list window shows the contents of lists within the
application.
pushing a button elsewhere on the page fills in this
number; in other cases, you must enter a list number
directly.
grid control. Depending upon how many list items
are collected, you may need to use a scroll bar to
view them.
ControlWave Station Manager Configuration Manual
Field Description
Display Descriptors If the application programmer configured descriptors
for this list, check this box to view them instead of
variable names in the Signal Name field.
Start Index Normally, the signal list grid displays variables
beginning with the first variable in the list. If you want
to skip further into the list, enter the number of the
first list item you want to see in this field, and the grid
starts displaying from that item forward.
Collect List Click this button to force the Signal List grid to collect
the specified list now.
Floating Point Format Click this to specify the Floating Point Format dialog
box. See Figure 2-14
Signal Name Shows the variable name for this list item, or its
descriptor.
Data Type Shows the variable type, such as Real or Boolean.
Alarm If this variable is an alarm, and this shows “AI” it
indicates the variable is alarm inhibited. If this shows
“AE” it indicates that the variable is alarm enabled.
Control If this shows “CI” it indicates the variable is control
inhibited. If this shows “CE” it indicates that the
variable is control enabled.
Manual If this shows “MI” it indicates the variable is manual
inhibited. If this shows “ME” it indicates that the
variable is manual enabled.
Value Shows the current value of the variable.
Units Shows the engineering units (if specified) for this
variable.
Signals Collected Displays a count of the number of variables collected
into the signal list grid.
2.4.2 Floating Point Format
The floating point format is the way floating point (real) numbers
display within a screen in the Station Manager application.
To change this format, you click the button on a
page, to call up the Float Format dialog box.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-23
ControlWave Station Manager Configuration Manual
Figure 2-14. Floating Point Format dialog box
Field Description
Width Choose the total number of characters in the field
Precision Choose the number of places to the right of the
(including the decimal point) used to display a
floating point number.
decimal point which the floating point number should
show.
2.5 Ultrasonic Data
Exponent
OK Click this to save your entries and exit the dialog
Cancel Click this to discard your entries and exit the dialog
Select one of these formats:
e show number in exponential notation
f show number in floating point notation
g allow application to choose the “best fit” format
for this number.
box.
box.
To access this page, click the
button on the I/O tab.
The data displayed for the ultrasonic tests is not the raw Modbus data
from the ultrasonic flow meter (UFM). The data is run through a
filtering process before being displayed. The displayed data is the
rolling output from the filtering process. The filtering process eliminates
false alarms caused by variability in the process.
Customers have used the following UFMs with Station Manager:
2-24 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
y
k
y
f
Daniel MARK III
Instromet Q.Sonic 3/4/5/6 Path, CheckSonic 1/2 Path,
CheckSonicVx 3/6 Path Series VI and S.Sonic Series III
Number Select the ultrasonic meter number for which
Enable/Disable Click Enable to enable communications from
Current State Shows the current enable/disable state o
If you are running the 6-run version of Station
Manager, you will only have 6 items to choose
from for man
you want to view status data.
Station Manager to the specified UFM. Clic
Disable to disable communications to the
specified UFM.
Note: Whenever you change an
communication settings, you must first disable
communications; then when you’ve completed
all communication setting changes, re-enable
communications.
communications to the UFM.
Description
of these fields.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-25
ControlWave Station Manager Configuration Manual
f
(
r
g
Port Use the dropdown menu to specify the
Address Specify the address of the UFM.
Time Out Specify the maximum length of time (in
Type Use the drop-down menu to select the type of
Com Select IP/Serial Choose the method of communication to the
Current Mode Shows the current method of communication
IP Address When communicating to the UFM via IP, enter
Generic Modbus (base 0) / Sick
Modbus (base 1)
Current State Shows the current Modbus base offset Station
Alarms Alarms may be generated from the UFM.
Enable/Disable Click Enable to turn on alarming for this UFM.
Current State Shows whether alarming is currently enabled
Consecutive Failures Shows the number of consecutive failures
Checksum If checksum changes, some configuration
Delay You can optionally set up a delay period at the
Enable/DisableClick Enable to apply a delay during which
ControlWave Micro serial communication port
which connects to this UFM.
milliseconds) for a UFM to respond to the
ControlWave Micro before a communication
failure is declared. If you leave this value at 0,
Station Manager uses a default timeout o
3000 ms
UFM.
UFM. Click IP to select IP communication o
Serial to select serial communication.
with the UFM, either Serial or IP.
its IP address here.
Click here to identify for Station Manager the
Modbus base offset it should use when
collecting data from a Sick UFM. The button
label indicates what offset you will use and the
Current State updates to reflect your choice.
(Sick UFM only.)
Manager uses when collecting data from a
Sick UFM. (Sick UFM only.)
Click Disable to turn off alarming for this UFM.
or disabled.
required to trigger an alarm from the UFM.
change occurred.
start of polling during which the system ignores
alarms from the UFM.
alarms are i
3 seconds).
nored at the start of polling.
2-26 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
r
t
A
t
t
g
Click Disable to turn off the delay.
Current StateShows whether the delay is enabled o
disabled.
Startup DelaySpecifies the delay in minutes during which
alarms from this UFM are ignored at the star
of polling.
Auto Alarm Based on velocity min and max values, the
auto alarm chooses which ranges to use.
Enable/DisableClick Enable to turn on the auto-alarm
function.
Click Disable to turn off the auto-alarm
function.
Current StateShows whether the auto-alarm function is
currently enabled or disabled.
Data
Valid Shows the data valid alarm status from the
UFM.
Low Flow Cutoff Specifies a flow limit below which the data valid
alarm is disabled.
UFM Status/Meter Status
Meter Status
The results of the analysis are displayed as
a binary number in the bottom left corner.
The binary status is calculated as follows:
larm
1 Meter performance orange alarm (a
least one path orange)
2 SoS fingerprint alarm
4 SoS comparisons alarm
8 Gas profile analysis alarm
16 Zero flow alarm
32 Meter performance red alarm (at leas
one path red)
64 ACF comparisons alarm
128 Checksum alarm
256 Modbus Comm % alarm
Meter Head Config
The ControlWave polls the meter for the configuration
checksums and compares the checksum to values
stored in the ControlWave. If the values do not match
the appropriate checksum the light is set to red and
the Meter Head Configuration Box light is set to red
Filter Statistics
The filter statistics section displays the results from
the last output of the rolling data filter. The size of the
filter is configurable and set on the UFM
Confi
uration 1 tab. The filter should default to 20
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-27
ControlWave Station Manager Configuration Manual
g
Comm %
Stable Flow %
Meter Performance %
Meter Performance
which means that the displayed data is the results of
the last 20 communications to the meter.
The Comm % illustrates the percent of successful
Modbus communications to the meter during the last
set of data. Stable flow yields good USM data analysis
results.
If the Comm % for any set of rolling filter data is less
than the limit then the Comm % box is set to red and
the Filter Statics Box light is set to red as shown
below:
The Stable Flow % illustrates the percent of the last
set of data on which analysis was performed (see the
SoS Fingerpirnt Analysis and Gas Profile Analysis
boxes). Flow is considered stable when the average
velocity from one poll to the next changes by less than
1 ft/s) and all the paths are OK, and the corrected gas
velocity and SoS are OK.
The Meter Performance % illustrates the percent of
the last set of data where all the path performances
were good (Since Stable Flow % depends on Meter
Performance %, Stable Flow must be less than or
equal to Meter Performance %).
The Meter Performance Box analyzes the meter’s
online diagnostics to determine the health of the meter
(not the meter system.)
For each data set that makes up a rolling filter, the
path diagnostics are examined. If the path velocity or
SoS is outside the limits or the path binary status
indicates a failed path then that set of path data is
discarded from the rolling filter results. After examining
all the data sets the percentage of successful data is
calculated and the successful path data processed.
Colors are used to indicate the success/failure of
individual path parameters and the health of the meter.
Green
Indicates path data passed all tests.
Orange
Indicates a minor failure.
Red
Indicates a major failure. If the Meter Performance
Box is red then the SoS Fin
2-28 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
erprint Analysis, the
ControlWave Station Manager Configuration Manual
t
r
SoS Comparisons, and the Velocity Profile Analysis
box lights are turned to grey and the interior values
set to gray to indicate that the test is not being
performed due to the failed meter performance.
PathnIf this path’s data passes all the tests then the status ligh
is set to green. If the path data fails a test then the status
light turns orange and the offending parameter’s box turns
orange.
VelShows the average velocity for this path. If this is outside
the configured limits, data for this path is discarded from
the rolling filter results.
SoSShows the average speed of sound for this path. If this is
outside the configured limits, data for this path is
discarded from the rolling filter results.
Gain Shows the average gain for this path.
S/N Shows the average signal to noise ratio for this path.
Perform Shows the average performance for this path.
The path binary status is set to a 16 if all the binary
status in the rolling average indicated that the path is
failed or all the velocities or SoS are outside the
limits.
TurbShows the average turbulence for this path.
SoS Fingerprint Analysis The SoS Fingerprint Analysis box displays the maximum
difference between each path and all the other paths. Fo
example, if there are four paths (S1 through S4) S1 Diff is
the maximum of s1-s2, s1-s3, s1-s4, where the sign is
kept. For example if s1-s2 = 0.23 and s1-s3 = -0.41 and
s1-s4 = 0.11 the S1 Diff should be displayed as -0.41
Sn DiffIf the diff is positive the bar should be dark blue. It the
difference is negative it should be light blue. If any of the
differences are greater than the limit (the red line) then the
SoS Fingerprint Analysis light is turned to red.
Swirl Angle
Swirl Angle
Gas Profile Analysis
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-29
This is gas profile data read from the UFM.
The Gas Profile Analysis Box displays the path velocity
ratios. The path ratios are calculated by dividing each
path velocity by the average velocity calculated as
follows:
ControlWave Station Manager Configuration Manual
g
Daniel SS= (v1+v4)*0.1382 + (v2+v3)*0.3618
Daniel X = (v1+v2+v3+v4)/4
Sick = (v1+v4)*0.1382 + (v2+v3)*0.3618
Q5 = 0.85/3*(v1+v3+v5)+0.15/2*(v2+v4)
Q3 = 0.15*v2+0.85/2*(v1+v3)
These equations are used to make the ratios
independent of the flow calibration. For a Daniel
SeniorSonic the Profile ratio, Symmetry ratio, and
Cross flow are also displayed and tested. If a ratio fails
the test then the ratio box light is turned to red and the
Gas Profile Analysis Box light is also turned to red.
If any of the path velocities average less than 0.05 ft/s
then the other velocities are tested to make sure they
are also close to zero (check for zero bias). When this
condition is true V1, V2, V3, V4 show the actual
velocities (not the ratios described above) with positive
velocities in dark blue and negative velocities in light
blue. The velocities are then tested as follows:
Daniel or Sick: if any velocity is less than 0.05
ft/s then the average of all four must be less
than 0.1 ft/s
Instromet: if any velocity is less than 0.05 ft/s
then all the other velocities must be less than
0.1 ft/s
The average velocity in the Sick or Daniel Test or the
maximum velocity calculated in the Instromet test is
displayed in the box next to the Zero Flow Test and the
value is graphically displayed with the limit.
Vn This represents the ratio of the path velocity to the
average velocity, or the actual path velocity if they all
average less than 0.05 ft/sec.
Profile Factor Shows the profile factor of this UFM.
Symm Factor Shows the symmetry factor of this UFM.
Cross Factor Shows the cross factor of this UFM.
Zero Flw Test Shows the zero flow test value for this UFM.
Graph
The list box above the graph lets you perform various
operations:
NOTE: This list box
applies to Station
Manager 8-Run only.
None Do not show any graph.
Path Velocities
Add Graph Choose a path and column
(Default) – Select this to show
the path velocities.
heading (as you would when
addin
a pen) then select Add
2-30 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
t
w
A
r
t
Graph to add a graph.
Make a Default
Graph
Remove Graph
Note: Station Manager stores graph information in a tex
file that gets overwritten each time you make a ne
default graph.
Low LimitSpecify the minimum value the system should display on
the graph.
High LimitSpecify the maximum value the system should display on
the graph.
Graph Time Span
Add Pen Click this button to add an additional pen to the graph in
llows you to specify the number of seconds of data
displayed in the graph window.
the Pen Configuration dialog box:
To assign the current graph as
the default when you open the
page, select Make a Default Graph.
To delete the current graph
select Remove Graph.
Pen Color Click here to bring up the color palette to
select a color for the pen.
Signal Specify the name of the ControlWave
variable which drives this pen; the
variable must have been marked PDD.
Descriptor Optionally specify a name to appea
next to this pen’s controls underneath
the graph.
Delete Pen Click here to delete this pen.
Save Click here to save the pen configuration
entries.
Cancel Click here to exit the dialog box withou
saving changes.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-31
ControlWave Station Manager Configuration Manual
t
r
g
g
Current value
Descriptor
For information on adding pens for specific path
parameters, see Adding Pens for Specific PathParameters.
Edit Graph Click here to open the Format Graph dialog box.
Pen Controls
Set pen color
Open Pen
Configuration
dialog box
6.
Delete Pen
Background Color
Click here to bring up the color palette to
select a color for the background.
Grid Line Color Click here to bring up the color palette to
select a color for the grid lines.
.
Grid Text Color Click here to bring up the color palette to
select a color for the grid text.
Y-Axis Lines Specify the number of grid line markers
to appear along the Y-axis.
Save Click here to save the graph
configuration entries.
Cancel Click here to exit the dialog box withou
saving changes.
Flag ChangesIf you check this, the graph will show a red vertical dashed
line at the time position on the graph where a setting fo
the graph changed.
Auto Scale If you check this, Station Manager tries to do a “best fit”
raph within the range specified.
Range Limit Specifies the maximum range of values to show on the
graph. For example, if the Range Limit is 100, Station
Manager averages the values and displays a range 50
above and below the avera
e value.
2-32 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
t
Update If you change the Range Limit, click the Update button
to activate the new upper and lower limits. Station
Manager only changes the limits on an update to preven
continually changing the upper and lower limits.
Adding Pens to the Graph for Specific Path Parameters
If there is a specific path parameter that you want to include on the
graph, click the path name on the left of the Meter Performance area so
it is highlighted, then click the desired parameter, so it is highlighted.
This adds a pen to the graph for that variable.
Click the path name, then click the parameter name to add a
pen for that parameter to the graph.
Figure 2-16. Adding Pens
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-33
ControlWave Station Manager Configuration Manual
g
r
t
f
r
UFM Configuration 1
Figure 2-17. UFM Configuration 1 page
Filter Statistics
Comm % Min Enter the minimum communication percentage
Monitor Count for Comm %
Min
Push to Reset Click here to reset the communication attempt counte
Gas Velocity Analysis
Maximum Zero Flow
Velocity
Maximum Average Velocity
Delta
Velocity and SoS Limits These limits are used to check velocity and speed o
SoS Min Specify the minimum speed of sound alarm limit.
SoS Max Specify the maximum speed of sound alarm limit.
Velocity Min Specify the minimum velocity alarm limit.
Velocity Max Specify the maximum velocity alarm limit.
setting for UFM statistics.
Specify the number of communication attempts used
to calculate the communication percenta
to 0.
Enter the maximum zero flow velocity.
This is the alarm setting for the maximum difference
(delta) of the average gas velocity between differen
paths.
sound.
e.
Comm Failure Alarm Delay If communication with this UFM fails, this field
specifies the number of seconds the Station Manage
application waits before generating a communication
failure alarm.
2-34 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
y
y
y
y
UFM Configuration 2
Figure 2-18. UFM Configuration 2 page
Velocity Ranges
Velocity Min The columns represent velocity ranges and allow the
Velocity Max The columns represent velocity ranges and allow the
Meter Performance
Outside Gain Max Define the maximum outside gain allowed for this
Inside Gain Max Define the maximum inside gain allowed for this UFM.
S/N Min Define the minimum signal to noise ratio for this UFM.
Performance Min Define the minimum performance value for this UFM.
Outside Turbulence Max Define the maximum outside turbulence for this UFM.
user to tune the parameter limits to the velocity range.
Velocity Min defines the lower end of the velocit
range. The 10 ranges allow the user to select 5 ranges
in both the positive and negative direction or 10
ranges in a single direction. If a parameter is left empt
on the screens then the test should not be performed
for that velocity range.
user to tune the parameter limits to the velocity range.
Velocity Max defines the upper end of the velocit
range. The 10 ranges allow the user to select 5 ranges
in both the positive and negative direction or 10
ranges in a single direction. If a parameter is left empt
on the screens then the test should not be performed
for that velocity range.
UFM.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-35
ControlWave Station Manager Configuration Manual
t
f
Inside Turbulence Max
Alarm Limit The current alarm limit in use for auto-alarm. If you
SoS Fingerprint Comparison
Difference MaxThe maximum allowable difference in the speed o
Define the maximum inside turbulence for this UFM.
disable auto-alarm, you enter your own alarm limi
here.
sound fingerprint calculation.
2-36 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
y
y
y
y
UFM Configuration 3
Figure 2-19. UFM Configuration 1 page
Velocity Ranges
Velocity Min The columns represent velocity ranges and allow the
Velocity Max The columns represent velocity ranges and allow the
Velocity Profile
Profile Factor Max Specify the maximum profile factor for this UFM.
Profile Factor Min Specify the minimum profile factor for this UFM.
Symmetry Factor Max Specify the maximum symmetry factor for this UFM.
Symmetry Factor Min Specify the minimum symmetry factor for this UFM.
Cross Flow Factor Max Specify the maximum cross flow factor for this UFM.
Cross Flow Factor Min Specify the minimum cross flow factor for this UFM.
Alarm Limit Shows the current alarm limit in use.
user to tune the parameter limits to the velocity range.
Velocity Min defines the lower end of the velocit
range. The 10 ranges allow the user to select 5 ranges
in both the positive and negative direction or 10
ranges in a single direction. If a parameter is left empt
on the screens then the test should not be performed
for that velocity range.
user to tune the parameter limits to the velocity range.
Velocity Max defines the upper end of the velocit
range. The 10 ranges allow the user to select 5 ranges
in both the positive and negative direction or 10
ranges in a single direction. If a parameter is left empt
on the screens then the test should not be performed
for that velocity range.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-37
ControlWave Station Manager Configuration Manual
2.6 Load/Save Configuration
The Load/Save Configuration function provides a way to save and
restore Station Manager configuration files. It uses the ControlWave
ScriptTool utility to launch various utilities to accomplish the read/write
operations.
Do not manually rename the files you save with the Load/Save function.
Caution
Doing so may prevent the Load/Save function from recognizing the
proper file type and could result in an invalid restore.
Notes:
If you plan to restore arrays related to a UFM or GC RF you should
restore the associated recipes for those arrays first before you
attempt to restore the arrays. This ensures the control knows which
arrays are available. If you restore arrays and recipes together in the
same Load operation, the software restores them in the proper order
for you.
If you plan to restore batch edits you should restore the associated
recipes for the application first, before you attempt to restore the
batch edits. If you restore batch edits and recipes together in the
same Load operation, the software restores them in the proper order
for you.
Depending on the version of Station Manager you are using, the
number of items may vary (six for six runs, or eight for eight runs).
While a load/save operation is in progress, TechView is locked until
the ScriptTool operation finishes or is stopped.
Click the button on the I/O
tab to activate the Load/Save Configuration page.
To prevent confusion, the page is divided into two tabs, one for saving
configuration files from the RTU, the other for loading configuration
files into the RTU. Both tabs share most of the same fields.
2-38 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
Figure 2-20. Load/Save Configuration – Save Configuration tab
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-39
File Settings The File Settings section applies only to the Save tab.
File Save PathSpecify the folder on your PC where you want to save
the files retrieved from the RTU.
Site Name Shows the site name as configured in the
Status/Configuration pages of the measurement tab.
The Site name and year format are used to create the
default root filename.
Year Format Specify the date format you want to use. The field
turns red if you make an invalid entry. This format and
the site name are used to create the default roo
filename. If you don’t want to include a date in the roo
filename, you can blank out this field.
Root Name Use the default root filename (made up of the site
name and date format) or specify a different roo
filename here.
Load Directory The Load Directory section applies only to the Load
tab.
File Load Path Specify the folder on your PC which contains the files
you want to load into the RTU.
Advanced Configuration Boot Project File The boot project (BootFile.pro) is the ControlWave
pro
ect boot file.
2-40 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
t
t
k
t
k
k
k
Note: By default, the boot project file is not checked
to prevent you from accidentally overwriting an
existing boot file on your RTU or on the PC. You mus
specifically check the box if you want to save or load
it.
On the Save Configuration tab: This field shows the
name of the boot project residing in the RTU.
Check the box if you want to save the boo
project when you save the configuration.
If you don’t want to save the bootproject when
you save the configuration, either unchec
the section, or click to erase the name.
If you want to restore the name you cleared,
click .
On the Load Configuration tab: This field shows the
path and name of the boot project residing on your PC
that you want to load into the RTU. You can use the
button to locate and specify the file.
Check the box if you want to load the boo
project when you load the configuration.
If you don’t want to load the bootproject when
you load the configuration, either uncheck the
box, or click to erase the name. If you
want to restore the name you cleared, clic
.
Flash Configuration File The flash configuration profile (*.FCP) file holds
various configuration parameters for the
ControlWave.
On the Save Configuration tab: This field shows the
name of the FCP file residing in the RTU.
Check the box if you want to save the FCP
file when you save the configuration.
If you don’t want to save the FCP when you
save the configuration, either uncheck the
box, or click to erase the name. If you
want to restore the name you cleared, clic
.
On the Load Configuration tab: This field shows the
path and name of the FCP file residing on your PC
that you want to load into the RTU. You can use the
button to locate and specify the file.
Check the box if you want to load the FCP
file when you load the configuration.
If you don’t want to load the FCP file when
you load the configuration, either uncheck the
box, or click to erase the name. If you
want to restore the name you cleared, clic
.
Batch edits Batch edits refers to a file of changes which occur
together. If you are restoring individual sections,
always restore recipe files before you restore batch
edits.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-41
ControlWave Station Manager Configuration Manual
r
r
r
r
t
r
t
r
y
Standard Configuration Files
List 10 Recipe The List 10 recipe specifies several important Station
IO Array Section On the Save Configuration tab: this field shows the
On the Save Configuration tab: This field shows the
name of the batch edits file residing in the RTU.
Check the box if you want to save the batch
edits file when you save the configuration.
If you don’t want to save the batch edits file
when you save the configuration, eithe
uncheck the box, or click to erase the
name. If you want to restore the name you
cleared, click .
On the Load Configuration tab: This field shows the
path and name of the batch edits file residing on you
PC that you want to load into the RTU. You can use
the button to locate and specify the file.
Check the box if you want to load the batch
edits file when you load the configuration.
If you don’t want to load the batch edits file
when you load the configuration, eithe
uncheck the box, or click to erase the
name. If you want to restore the name you
cleared, click .
Manager parameters. If you are restoring individual
sections separately, you need to restore this recipe
before you restore UFM arrays, GC RF arrays, o
batch edits.
On the Save Configuration tab: This field shows the
name of the List 10 recipe file residing in the RTU.
Check the box if you want to save the Lis
10 recipe file when you save the
configuration.
If you don’t want to save the List 10 recipe file
when you save the configuration, eithe
uncheck the box, or click to erase the
name. If you want to restore the name you
cleared, click .
On the Load Configuration tab: This field shows the
path and name of the List 10 recipe file residing on
your PC that you want to load into the RTU. You can
use the button to locate and specify the file.
Check the box if you want to load the Lis
10 recipe file when you load the configuration.
If you don’t want to load the List 10 recipe file
when you load the configuration, eithe
uncheck the box, or click to erase the
name. If you want to restore the name you
cleared, click .
name of the IO array file residing in the RTU.
Check the box if you want to save the IO
array file when you save the configuration.
ou don’t want to save the IO array fi le whe n
If
2-42 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
k
k
r
y
t
w
r
f
w
r
y
Math Function Arrays
Section
Turbine Linearization Arrays
Section
you save the configuration, either unchec
the box, or click to erase the name. If
you want to restore the name you cleared,
click .
the Load Configuration tab: This field shows the
path and name of the IO array file residing on your PC
that you want to load into the RTU. You can use the
button to locate and specify the file.
Check the box if you want to load the IO
array file when you load the configuration.
If you don’t want to load the IO array file when
you load the configuration, either uncheck the
box, or click to erase the name. If you
want to restore the name you cleared, clic
.
On the Save Configuration tab: These fields show
the names of the math function array files residing in
the RTU.
Check the box if you want to save all (o
some) of the math function array files when
you save the configuration.
If there are one or more math function arra
files you don’t want to save, but you are
saving at least one, click to erase the
name of any math function array file you don’
want to save. If you want to restore the name
you cleared, click .
On the Load Configuration tab: These fields sho
the paths and names of the math function array files
residing on your PC that you want to load into the
RTU. You can use the buttons to locate and
specify each file.
Check the box if you want to load one o
more of the math function array files when
you load the configuration.
If you don’t want to load one or more of the
math function array files when you load the
configuration, click to erase its name. I
you want to restore the name you cleared,
click .
The linearization configuration arrays are used with
turbine meters.
On the Save Configuration tab: These fields sho
the names of the turbine linearization array files
residing in the RTU.
Check the box if you want to save all (o
some) of the turbine linearization array files
when you save the configuration.
If there are one or more turbine linearization
array files you don’t want to save, but you are
saving at least one, click to erase the
name of an
turbine linearization array file
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-43
ControlWave Station Manager Configuration Manual
w
r
r
r
r
w
r
t
t
g
GC Array Section
UFM Arrays Section The UFM arrays are used with ultrasonic flow meters.
you don’t want to save. If you want to restore
the name you cleared, click .
On the Load Configuration tab: These fields sho
the paths and names of the turbine linearization array
files residing on your PC that you want to load into the
RTU. You can use the buttons to locate and
specify each file.
Check the box if you want to load one o
more of the turbine linearization array files
when you load the configuration.
If you don’t want to load one or more of the
turbine linearization array files when you load
the configuration, click to erase its
name. If you want to restore the name you
cleared, click .
On the Save Configuration tab: This field shows the
name of the gas chromatograph (GC) array file
residing in the RTU.
Check the box if you want to save the GC
array file when you save the configuration.
If you don’t want to save the GC array file
when you save the configuration, eithe
uncheck the box, or click to erase the
name. If you want to restore the name you
cleared, click .
On the Load Configuration tab: This field shows the
path and name of the GC array file residing on you
PC that you want to load into the RTU. You can use
the button to locate and specify the file.
Check the box if you want to load the GC
array file when you load the configuration.
If you don’t want to load the GC array file
when you load the configuration, eithe
uncheck the box, or click to erase the
name. If you want to restore the name you
cleared, click .
If you are restoring individual sections, always restore
recipe files before you restore UFM arrays.
On the Save Configuration tab: These fields sho
the names of the UFM array files residing in the RTU.
Check the box if you want to save all (o
some) of the UFM array files when you save
the configuration.
If there are one or more UFM array files you
don’t want to save, but you are saving at leas
one, click to erase the name of any UFM
array file you don’t want to save. If you wan
to restore the name you cleared, click .
On the Load Confi
uration tab: These fields show
2-44 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
r
f
w
r
t
k
w
r
f
the paths and names of the UFM array files residing
on your PC that you want to load into the RTU. You
can use the buttons to locate and specify each
file.
Check the box if you want to load one o
more of the UFM array files when you load
the configuration.
If you don’t want to load one or more of the
UFM array files when you load the
configuration, click to erase its name. I
you want to restore the name you cleared,
click .
GC RF Arrays Section The GC RF arrays are used with gas chromatographs.
If you are restoring individual sections, always restore
recipe files before you restore GC RF arrays.
On the Save Configuration tab: These fields sho
the names of the GC RF array files residing in the
RTU.
Check the box if you want to save all (o
some) of the GC RF array files when you
save the configuration.
If there are one or more GC RF array files you
don’t want to save, but you are saving at leas
one, click to erase the name of any GC
RF array file you don’t want to save. If you
want to restore the name you cleared, clic
.
On the Load Configuration tab: These fields sho
the paths and names of the GC RF array files residing
on your PC that you want to load into the RTU. You
can use the buttons to locate and specify each
file.
Check the box if you want to load one o
more of the GC RF array files when you load
the configuration.
If you don’t want to load one or more of the
GC RF array files when you load the
configuration, click to erase its name. I
you want to restore the name you cleared,
click .
Save Configuration Click this button to save the specified files on your PC.
See Section 2.6.1 for more information.
Load Configuration Click this button to load the specified files into the
RTU.
2.6.1 Save Configuration (From RTU)
The Save Configuration (From RTU) tab lets you save the ControlWave
boot project, flash configuration profile (FCP) file, as well as various
array files and recipe files used by the Station Manager application.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-45
ControlWave Station Manager Configuration Manual
1. Go to the Save Configuration (From RTU) tab.
2. To view the items to be saved in a section, click “+” to expand
that section.
3. Use the Browse button in the File Save Path field to specify the
path on your PC where you want to save the configuration files.
4. Optionally use the Year Format field to specify the date format
used in the root filenames which you will save.
5. Optionally edit the Root Name to specify the base filename used
for the configuration files which you will save.
6. If you want to save the boot project, FCP, and batch edit files, go
to the Advanced Configuration box, and check those files.
7. In the Standard Configuration Files section check the box for
any groups of files you want to save.
8. If there are certain files in a group that you do not want to save,
and they don’t have their own check box for you to un-check,
click the Clear button for each of the files you don’t want to
save; this erases their name so they won’t be saved at the PC. If
you accidentally clear the wrong one, click Load to restore its
name.
9. Click the Save Configuration button. This activates the
ControlWave ScriptTool which in turn sequentially retrieves all
of the specified files from your RTU, and saves them on your
PC.
Note: Depending upon which files you choose to save, this process
could take several minutes. Allow the ScriptTool to run by itself
until the script finishes.
Once you’ve saved the files, do not manually rename them (for example,
Caution
in Windows Explorer). Doing so may prevent the Load/Save function from
recognizing the proper file type and could result in an invalid restore.
2-46 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
Figure 2-22. ControlWave ScriptTool Performs File Save Operations
2.6.2 Load Configuration (To RTU)
The Load Configuration (To RTU) tab lets you load the ControlWave
boot project, flash configuration profile (FCP) file, as well as various
array files and recipe files used by the Station Manager application into
the ControlWave Micro controller. This is useful if, for example, you
took the controller out of service to replace a component and now you
want to restore its configuration.
Note: If you restore multiple files, the software restores them in the
proper order for you. If you choose to restore individual files
separately, be sure you always restore recipes prior to restoring
batch edits, GC RF arrays, or UFM arrays.
1. In the Load Directory field, use the Browse button to specify
the folder on your PC which contains the files you want to load
into the RTU. Alternatively, you can choose an existing ZIP file
containing configuration files. In either case, the utility
automatically populates fields based on the contents of the folder
or ZIP file. If a section is unchecked, it won’t be populated. If
filenames don’t match the expected name pattern, they are
highlighted in red; this could indicate a potential mismatch in
file types.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-47
ControlWave Station Manager Configuration Manual
2. Click “+” to expand any sections into which you want to load
individual files. You must expand a section to load all files in a
section. If a section is unchecked, no files will be loaded from
that section.
3. If you want to load the boot project (*.PRO), flash configuration
profile files (*.FCP), and batch edit files, go to the Advanced
Configuration box and check those files.
4. In the Standard Configuration Files section check the box for
any group of files you want to load.
5. If there are certain files in a group that you do not want to load,
and they don’t have their own check box for you to un-check,
click the Clear button for each of the files you don’t want to
load; this erases their name so they won’t be saved at the PC. If
you accidentally clear the wrong one, click Load to restore its
name.
6. Click the Load Configuration button. This activates the
ControlWave ScriptTool which in turn sequentially retrieves all
of the specified files from the Load Directory on your PC (or
from the zip file) and loads them into the RTU. If you are
restoring advanced files, you will be required to provide a valid
user/password combination.
Notes:
Depending upon which files you choose to save, this process could
take several minutes. Allow the ScriptTool to run by itself until the
script finishes. The screen updates to show the progress of the script.
ScriptTool always loads the recipe files first. When loading
individual sections separately, you must load recipes before loading
GC RF arrays, UFM arrays, or batch edits.
2-48 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
2.7 Generic Modbus Master
Click the button on the I/O tab to
activate the Generic Modbus page. There are multiple pages for Modbus
Master 1 (MB1) to Modbus Master 5 (MB5). You click on a tab to call
up the appropriate Modbus Master.
ControlWave Station Manager Configuration Manual
Figure 2-23. Generic Modbus Master
This page includes the following fields:
Field Description
Settings
Communications Port
Serial Click the Serial button to use serial Modbus
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-49
Modbus communications can use either serial or IP
communications.
communication, and specify the port you want to
use. (See Port).
ControlWave Station Manager Configuration Manual
Field Description
Port Specify the serial communication port on the
IP Click the IP button to use IP Modbus (Open Modbus)
ControlWave Micro you want to use for Modbus
master communication. Use the following code:
Enter this: To select this serial CW Micro port:
1 COM1
2 COM2
3 COM3
4 COM4
5 COM5
6 COM6
7 COM7
8 COM8
9 COM9
10 COM10
11 COM11
Press [Enter] to save the selection.
communication.
IP Address
Protocol
Modbus Click this button to configure Modbus
BSAP Do NOT choose this when configuring Modbus
Data Parameters
Word Order Choose the data word order to match the data word
High Word First Click this to specify that the high word is first.
Low Word First Click this to specify that the low word is first.
Byte OrderChoose the data byte order to match the data byte
High Byte First Click this to specify that the high byte is first.
If you want to use IP Modbus (Open Modbus), enter
the IP address of the port used by this master.
communication.
communication.
order used by the Modbus Slave that communicates
with this Modbus Master.
order used by the Modbus Slave that communicates
with this Modbus Master.
2-50 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
Field Description
Low Byte First Click this to specify that the low byte is first.
Bit Order Choose the data bit order to match the data bit order
used by the Modbus Slave that communicates with
this Modbus Master.
High Bit First Click this to specify that the high bit is first in a byte
of data..
Low Bit First Click this to specify that the low bit is first in a byte of
data.
Data Size Select the appropriate data format for Modbus
Register data from the drop down menu. The
available selections are:
Single Bit – Each Register will include a single bit
Byte Data – Each Register will include a single byte
16 Bit Integer – Each Register will include a single
16-bit integer
32 Bit Int., 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit double integer.
32 Bit Float, 1 Reg., Cnt*1, Adr*1 – Each Register
will include a 32-bit floating point number
32 Bit Int., 2 Reg., Cnt*2, Adr*2 – Two registers will
be used for each 32-bit double integer. The
MODBUS Master must poll two registers for each 32
bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*2 – Two registers
will be used for each 32-bit floating point number.
The MODBUS Master must poll two registers for
each 32 bit number.
32 Bit Int., 2 Reg., Cnt*2, Adr*1 - Two registers will
be used for each 32-bit double integer. The
MODBUS Master must poll a single register for each
32 bit integer.
32 Bit Float, 2 Reg., Cnt*2, Adr*1 - Two registers
will be used for each 32-bit floating point number.
The MODBUS Master must poll a single register for
each 32 bit number.
Press [Enter] to save the selection.
If you don’t make a selection, the field shows Not Set.
Function Code Select the Modbus function from the drop-down menu.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-51
ControlWave Station Manager Configuration Manual
Field Description
Modbus Slave Address
RTS Delay Mode Select from one of two modes for the Ready-to-Send
Press [Enter] to save the selection.
Enter the Modbus slave address. If the local slave
address you enter has already been assigned to
either the SCADA Enron Modbus slave interface, or
any of the other Customer Modbus Slave sessions,
you will see a Loc Addr Conflict message. Modify
the Modbus Slave Address as required to resolve
the conflict.
(RTS) delay mode.
Message Delay Mode - After the Modbus Master
port raises RTS, a delay timer starts. The length of
the delay is determined by the value in the Delay
field. No message is sent until after this delay
expires. The value of CTS does not affect the
operation of this mode.
CTS Timeout Mode - After the Modbus Master port
raises RTS, it uses the Delay value as the maximum
time to wait for CTS to be received from the slave. If
the Modbus Master port receives CTS at any time
before this time expires, the port starts to transmit
the message. If the Modbus master port does not
receive a CTS from the slave prior to the expiration
of the Delay it does not respond to the slave and
instead reports an error.
Press [Enter] to save the selection.
Delay msec Specify the Delay (in milliseconds) used by the RTS
Delay Mode and CTS Timeout Mode. Press [Enter]
to save the selection.
Time Out msec Specify the time (in milliseconds) that the Modbus
master must wait for a response from the Modbus
slave before the master declares that the slave timed
out. Press [Enter] to save the selection.
Collection Rate msec
2-52 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
Specify the interval (in milliseconds) between poll
attempts by the Modbus master. Press [Enter] to
save the selection.
ControlWave Station Manager Configuration Manual
Field Description
Start Register
Register Count
Disabled/Enabled If this shows Disabled, click on it to enable the
Status This read-only field displays a message regarding
BSAP Parameters The fields below are only visible when using BSAP
Specify the starting address for coil or register
operations. The address transmitted to the Slave is
one less than the value specified here. For example,
the address 7031 is sent as 7030 for Function code
3. Press [Enter] to save the selection.
Specify the number of coils or registers the Master
should read. The value can range from 1 to 2000 for
coils or 1 to 125 for 16-bit registers, or 1 to 62 for 32bit registers. Press [Enter] to save the selection.
Modbus Master.
the health of the Modbus master communications.
protocol, which makes the ControlWave Micro
running Station Manager into a BSAP master.
BSAP Server ID Status Specify the number of the Server function block in
the BSAP slave.
Mode Choose Read Only if you only want to receive data
from the slave; choose Write Only if you only want
to send data to the slave; choose Read/Write if you
want to read and write.
Time Out Specify how long (in tenths of seconds) to wait for a
response from the Server function block in the BSAP
slave.
Send List Specify the number of the send list here.
BSAP Server List # Shows the number of the list in the BSAP slave from
which data is sent/received.
Item Count Not applicable in BSAP mode
BSAP Slave Address The BSAP slave address of the slave device.
BSAP Receive List Click this to display the receive list in the signal list
grid. This list holds incoming data received from the
BSAP slave.
BSAP Send List Click this to display the send list in the signal list grid.
This list holds outgoing data sent to the BSAP slave.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-53
ControlWave Station Manager Configuration Manual
g
2.8 Time Set/Daylight Saving Time
Click the button on the I/O tab to
open the Time Set/Daylight Saving Time page.
Figure 2-24. Time Set/Daylight Saving Time page
Field Description
Current RTU Date and
Time
Current PC Date and
Time
Clear Registers Click this button to set all six time registers (Year,
Load Registers with
the RTUs Date/Time
Load Registers with
the PCs Date/Time
Year This time register holds a year value. You can set it
Month This time register holds a month value. You can set
This read-only field shows the current date and time
settin
at the controller.
This read-only field shows the current date and time
at the PC workstation.
Month, Day, Hour, Minutes and Seconds) to zero.
Click this button to store the controller time in the six
time registers.
Click this button to store the PC workstation time in the
six time registers.
by typing in a value, or you can load it by one of the
buttons.
it by typing in a value, or you can load it by one of
the buttons.
2-54 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
g
Field Description
Day This time register holds a day value. You can set it
by typing in a value, or you can load it by one of the
buttons.
Hours This time register holds an hour value. You can set it
by typing in a value, or you can load it by one of the
buttons.
Minutes This time register holds a minute value. You can set
it by typing in a value, or you can load it by one of
the buttons.
Seconds This time register holds a seconds value. You can
set it by typing in a value, or you can load it by one
of the buttons.
Set RTU Date/Time with
Register Values
Daylight Saving Time
Beginning Date Shows the calculated beginning date for daylight
Month Select the month in which Daylight Saving Time
Click this button to update the controller’s date and
time with the values currently in the time registers.
saving time, based on the Month and Sunday rules
defined above it.
starts here. Press [Enter] to save your selection.
Sunday Select the Sunday of the month at which Daylight
Saving Time starts here. Press [Enter] to save your
selection.
Ending Date Shows the calculated ending date for daylight saving
time, based on the Month and Sunday rules defined
above it.
Month Select the month in which Daylight Saving Time
ends here. Press [Enter] to save your selection.
Sunday Select the Sunday of the month at which Daylight
Saving Time ends here. Press [Enter] to save your
selection.
Daylight Saving Time
Enabled/Disabled
Current Time State This read-only field displays the time state setting to
Click this button to toggle between Daylight Saving
Time and Standard Time.
show whether you are in Daylight Saving Time or
Standard Time based on the other entries on the
pa
e.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-55
ControlWave Station Manager Configuration Manual
2.9 Virtual Ports
UFMs can optionally communicate using virtual ports. A virtual port is
a software construct that re-directs messages out an IP port. This allows
you to use a terminal server for a communication port. This can be
useful when you’re working with UFMs, chromatographs, or other
third-party devices.
To access the Virtual Ports page, click the
button on the I/O tab.
Figure 2-25. Virtual Ports page
2-56 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
Field Description
Virtual Port n
Status Shows the virtual port status code. See the
ControlWave Designer online help for VIRT_PORT
function block to see what these codes mean.
Port Shows the virtual port number.
Active Shows whether the virtual port is currently active.
Receive Counts Shows a count of messages received on the virtual
port.
Transmit CountsShows a count of messages transmitted on the virtual
port.
IP Destination Shows the IP address of the remote destination.
Protocol Shows the communication protocol in use on the
virtual port.
Poll Period (Seconds) Shows the polling period in seconds for the virtual
port.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-57
ControlWave Station Manager Configuration Manual
2.10 User Defined Screen
This section discusses the mechanics of developing custom TechView
screens. You can add or view screens that display signal data to the
TechView Session. You can make custom screens with any PDD signal
from the Station Manager Application Load.
To create your own customized Station Manager screens, you need the
following tools:
Web page editor (HTML) – You can use any standard HTML
development environment (Dreamweaver, Microsoft Visual Web
Developer 20xx Express Edition, etc.) to develop TechView Web pages.
JavaScript – You can use any standard JavaScript development
environment (Dreamweaver, Microsoft Visual Web Developer 20xx
Express Edition, etc.) to develop the JavaScript used in the TechView
Web pages.
WebBSI SignalView Grids – Use SigGen_*.js (an Emerson-provided
helper tool) to configure tables of WebBSI SignalView grids. This
configures the tables and creates the SignalView ActiveX controls using
a comma separated variable (CSV) file as the source for defining the
contents of each cell within a table.
Using this tool provides a level of consistency between developers in
the way tables are laid out, the appearance of the tables, and defaults for
the WebBSI SignalView controls.
Note: You can locate the *.js, *.htm, and *.css files referenced in this
appendix in your Station Manager folder.
To access the User Defined Screens page, click the
Note: See Chapter 6 for information on using the legacy User Defined
Screen feature.
Web Page Development Tutorial
This section is a tutorial to introduce the techniques used to build the
TechView Web pages.
For this tutorial, we are going to build a simple display with a table of
data that will look this when we are done:
button on the Measurement tab.
2-58 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
HTML
ControlWave Station Manager Configuration Manual
Figure 2-26. User Defined Page
For developing most web pages, the HTML consists mostly of calling
JavaScript functions, which create the HTML tables and populates the
tables with text and/or WebBSI ActiveX controls.
Review the UDS_V2.htm file.
Observe the first two lines of the file:
<!DOCTYPE html PUBLIC "-//W3C//DTD XHTML 1.0
Transitional//EN" "http://www.w3.org/TR/xhtml1/DTD/xhtml1transitional.dtd">
<html xmlns="http://www.w3.org/1999/xhtml" >
These two lines should be left as is. There is no reason to edit them.
Observe that the HTML Head section has been declared as follows:
<head>
<title>User Defined Screen</title>
<link href= "Stylesheets/WebBSI.css" rel="stylesheet"
type="text/css">
</head>
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-59
ControlWave Station Manager Configuration Manual
The only thing that should be modified in the Head section is the text
between the html tags <title></title>. This should be modified to be an
appropriate title for the html page. The other line is where the
WebBSI.css (cascading style sheet) is referenced, and should not be
modified, unless a new style sheet file is required.
The next two lines reference external JavaScript files that contain
functions common to all web pages.
Review this section and read the comments to understand what each
section of the JavaScript is doing.
The body section, between the <body> and </body> html tags, is where
the web page layout is defined. The opening body tag (<body>) is
shown here:
<body onload="PageInit(); " class="main">
On every web page, there will be a need to call an initialization script. It
is recommended that this initialization script be named PageInit, and
called with an ‘onLoad’ function, within the <body> tag,
In addition, we want to apply the same styles to the body of every web
page. This is done by referencing the class “main” in the <body> tag.
The class “main” is defined in the WebBSI.css cascading style sheet.
After the opening <body> tag, we have the next two lines:
<p align="left" class="title">User Defined Page</p>
<p class="tablehead">User AI Points</p>
The formats “title” and “tablehead” are defined in the WebBSI.css
cascading style sheet. When creating a page, it is recommended you use
the “title” for the page title, and the “tablehead” if you want to add a
label above a table.
2-60 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
These two lines will look like this on a web page:
Next, we have a division (<div>) tag:
<div align="left" id="DivSelect">
We are aligning everything in this division to the left, we also assigned
an id, “DivSelect”, to it so that it can be referenced elsewhere if desired.
<option value="0"> Choose a Different Screen</option>
</select>
<p> </p>
</div>
This is a standard selection box. In this example, we are choosing to
pass a parameter with a value of 0 to n, where n is any number of pages
added by the user. The figure shows 0 to 2 pages to select. This will
look like this on the page:
Next, we have the following lines:
<script type="text/javascript">
var AliasArray = new Array(0);
var SymbolArray = new Array(0);
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-61
The WriteTableWithObjs function is a function that will read a comma
separated variable file, and return a fully formatted HTML table,
including static text and live values from the ControlWave Micro.
The CSV file is created using the following rules:
A new table is indicated by starting a line with an asterisk (*). A new
cell is created after each comma. If column labels are required, they may
be entered in this line. The cell width will be defined in this line. If you
want to include both a column label and a width, separate the two with a
semicolon.
Example:
*User AI Point;width=150,Value;width=200,;width=15,User AI
Point;width=150,Value;width=200,;width=15,User AI
Point;width=150,Value;width=200
The above CSV data will create an eight column table. The first row of
this table will look like this:
When adding additional lines to the table, the following rules apply:
No other line in the table can start with an asterisk (*), because that
indicates a new table.
If a cell contains just a label, add the text as you wish it to appear.
If you want to include a SignalView ActiveX control in a cell, the
cell must start with the dollar sign ($) followed immediately by the
ControlWave signal name.
If you want to change the default SignalView ActiveX control
properties, the properties must be separated by a semi-colon. Any of
2-62 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
the SignalView ActiveX control properties may be set in the CSV
file.
Example:
User AI 1
,$IO_1.HWAIs_1.HWAI_86;rights=8;BackColor=000000;ForeColor
=16777215;Format=0;BackColor=000000;ForeColor=16777215,,
User AI 2
,$IO_1.HWAIs_1.HWAI_87;rights=8;BackColor=000000;ForeColor
=16777215;Format=0;BackColor=000000;ForeColor=16777215,,
User AI 3
,$IO_1.HWAIs_1.HWAI_88;rights=8;BackColor=000000;ForeColor
=16777215;Format=0;BackColor=000000;ForeColor=16777215
Note: At this time, the WriteTableWithObjs function does not support
breaking a line in the CSV file. The above line is wrapped in this
document. However, in the original CSV file, this is a single line.
The above CSV (in conjunction with the Table header line) looks like
this:
After the end division tag (</div>) we have the remaining code:
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-63
ControlWave Station Manager Configuration Manual
This generates the link at the bottom of the page.
Figure 2-27. Example – Links added to page
In our example, it just reopens the UDS_V2.htm page.
As the comment states, the CreateFooterLinks is a JavaScript function
in the SignalGen.js file. This function has the following parameters -
obj, LinksArray)
obj is the document object id, (i our example it is the division tag id -
<div id="Footer"> or Footer). This is where the Html is returned.
LinksArray is an array of fully-formed Html Links – in our example:
We pass links into the LinksArray, so that we can have a variable
number of Links at the bottom of the page. Although we can pass any
number of Links into the LinksArray object, the maximum practical
number of links is 10, based on web page sizing and table sizing.
The </body> and </html> tags are the end tags required to close the body
of the page and the html section of the page.
2-64 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
2.11 Coriolis Modbus Interface (6-Run Version ONLY)
Click the button to open this
page.
Customers have used the following Coriolis meters with Station
Manager:
Micro Motion Series 1000 Transmitters
Micro Motion Series 2000 Transmitters
Figure 2-28. Coriolis tab
Field Description
Device Settings
Coriolis Number
Enable/Disable
Current State
Port
Address
Status
Select the Coriolis meter number for which you want to view
Modbus data.
Click Enable to enable communications with the coriolis meter.
Click Disable to disable communications with the coriolis meter.
Shows the whether communications with the coriolis meter are
enabled or disabled.
Shows the port used by the coriolis meter.
Shows the address for this coriolis meter.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-65
ControlWave Station Manager Configuration Manual
r
r
T
T
r
r
T
r
r
r
r
r
r
r
T
Comm Status
Status 1
Status 2
Status 3
Alarm
High Severity
Status A
Status B
Status C
Shows the communication status of the specified coriolis meter.
Status of Modbus communications for data block 1.
Status of Modbus communications for data block 2.
Status of Modbus communications for data block 3.
High severity alarm status from Modbus coil address 0069.
Shows the status code from Modbus register address 0419.
Bit Number
Bit #0(E)EPROM checksum error, core processo
Bit #1RAM test error, core processo
Bit #2Not used
Bit #3Sensor not vibrating
Bit #4
Bit #5Calibration failure
Bit #6Other failure occurred
Bit #7
Bit #8Primary variable out of limits
Bit #9Non-primary variable out of limits
Bit #10Not used
Bit #11Not used
Bit #12Watchdog erro
Bit #13Cold start occurred
Bit #14
Bit #15High-severity alarm(s) active
Description
emperature sensor out of range
ansmitter initializing/warming up
ansmitter configuration changed (HART bit)
Shows the status code from Modbus register address 0420.
ter 3 – Bit
ter 4 – Description
Number
Bit #0Primary mA output saturated
Bit #1Secondary mA output saturated
Bit #2Primary mA output fixed
Bit #3Secondary mA output fixed
Bit #4Density ove
Bit #5Drive ove
Bit #6Not used
Bit #7External input failure
Bit #8(E)EPROM checksum failure, core processo
Bit #9RAM diagnostic failure, core processo
Bit #10Sensor not responding (no tube interrupt)
Bit #11
Bit #12Input overrange
Bit #13Frequency/pulse output saturated
Bit #14Transmitter not characterized (flow calibration factor or sensor
Bit #15Not used
emperature sensor out of range
type)
ange
ange
Shows the status code from Modbus register address 0421.
Bit Number Description
Bit #0
Bit #1Power reset occurred
Burst mode enable
2-66 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
T
r
T
r
A
r
r
T
r
r
r
r
r
r
r
T
r
T
T
T
T
Status D
Status E
Status F
Bit #2
Bit #3Sensor/transmitter communication failure (A28)
Bit #4Paper out
Bit #5Event 2 ON
Bit #6Event 1 ON
Bit #7Sensor/transmitter communication failure (A26)
Bit #8Calibration failure
Bit #9Zero value too low
Bit #10Zero value too high
Bit #11Zero too noisy
Bit #12
Bit #13Data loss possible
Bit #14Calibration in progress
Bit #15Slug flow
ansmitter initializing/warming up
ansmitter electronics failure
Shows the status code from Modbus register address 0422.
Bit Number Description
Bit #0
API: Temperature outside standard range
Bit #1
Bit #2“Line RTD” temperature out of range
Bit #3“Meter RTD” temperature out of range
Bit #4Flow direction (0=Forward or Zero flow, 1=Reverse)
Bit #5Not used
Bit #6Enhanced density: Unable to fit curve data
Bit #7Last measured value ove
Bit #8Enhanced density extrapolation alarm
Bit #9
Bit #10(E)EPROM checksum erro
Bit #11RAM test error in transmitte
Bit #12Invalid/unrecognized sensor type (K1 value)
Bit #13(E)EPROM database corrupt in core processo
Bit #14
Bit #15(E)EPROM program co
PI: Density outside standard range
ide active
ansmitter not configured (flow calibration factor)
(E)EPROM power down totals corrupt in core processor
upt in core processo
Shows the status code from Modbus register address 0423.
Bit Number Description
Bit #0Core processor boot sector fault
Bit #1
Bit #2Frequency output fixed
Bit #3Not used
Bit #4DO1 status (0=OFF, 1=ON)
Bit #5DO2 status (0=OFF, 1=ON)
Bit #6
Bit #7
Bit #8DO3 status (0=OFF, 1=ON)
Bit #9Not used
Bit #10
Bit #11
Bit #12Flowing density calibration in progress
Bit #13High-density calibration in progress
Bit #14Low-density calibration in progress
Bit #15Flowmeter zeroing in progress
ansmitter software upgrade recommended
-Series D3 calibration in progress
-Series D4 calibration in progress
emperature slope calibration in progress
emperature offset calibration in progress
Shows the status code from Modbus register address 0420.
Bit Number Description
Bit #0Discrete input 1 status (0=OFF, 1=ON)
Bit #1Discrete input 2 status (0=OFF, 1=ON)
Bit #2Discrete output 1 fixed
Bit #3Discrete output 2 fixed
Bit #4Discrete output 3 fixed
Bit #5Not used
Bit #6Security breach
Bit #7Frequency input saturatedBit #8Batch/fill timeout
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-67
ControlWave Station Manager Configuration Manual
r
r
Bit #9Batch/fill in progress
Bit #10Batch end warning
Bit #11Batch ove
Bit #12Batch pump
Bit #13Batch/fill primary valve
Bit #14Batch/fill secondary valve
Bit #15Not used
Status Code
Details
Shows additional information based on the error codes.
un
Data From Meter
Mass Flow Rate
Density
Temperature
Volume Flow
Rate
Pressure
Mass Total
Pressure Input
Zero
Density
Calibration
The mass flow rate from Modbus register pair 0247/0248.
The density from Modbus register pair 0249/0250.
The temperature from Modbus register pair 0251/0252.
The volume flow rate from Modbus register pair 0253/0254.
The internally derived pressure from Modbus register pair
0257/0258.
The mass total from Modbus register pair 0259/0260.
The pressure input at 4 mA from Modbus register pair
0273/0274.
The density for flowing density calibration from Modbus register
pair 0277/0278.
Mass From
Frequency
Volume From
Frequency
Left Pick Off
Voltage
Mass Flow Live
Zero
Volume Total
Mass Inventory
The mass flow rate meter factor from Modbus register pair
0279/0280.
The volume flow rate meter factor from Modbus register pair
0281/0282.
The left pickoff voltage (in millivolts) from Modbus register pair
0287/0288.
The mass flow live zero flow from Modbus register pair
0293/0294.
The volume total from Modbus register pair 0261/0262.
The mass inventory from Modbus register pair 0263/0264.
2-68 Configuring Inputs and Outputs (I/O Tab) Issued: May-2019
ControlWave Station Manager Configuration Manual
Volume
Inventory
Pressure
Corrected Flow
Rate
Pressure
Corrected
Density
Flow Calibration
Pressure
Pressure Input
Span
Density From
Frequency
Raw Tube
Frequency (Hz)
Drive Gain
The volume inventory from Modbus register pair 0265/0266.
The pressure correction factor for flow from Modbus register pair
0267/0268.
The pressure correction factor for density from Modbus register
pair 0269/0270.
The flow calibration pressure from Modbus register pair
0271/0272.
The pressure input at 20 mA from Modbus register pair
0275/0276.
The density meter factor from Modbus register pair 0283/0284.
The raw tube frequency (in Hz) from Modbus register pair
0285/0286.
The drive gain (in %) from Modbus register pair 0291/0292.
Right Pick Off
Voltage
The right pickoff voltage (in millivolts) from Modbus register pair
0289/0290.
Issued: May-2019 Configuring Inputs and Outputs (I/O Tab) 2-69
ControlWave Station Manager Configuration Manual
Chapter 3 – Configuring Stations, Runs, and Valves
(Measurement Tab)
This chapter discusses configuring the stations and meter runs for the
Station Manager application as well as all the measurement functions for
the various meter runs. This is accomplished from the Station Manager’s
Measurement tab.
Click the Measurement tab to display the measurement options you can
configure. We’ll discuss each of these in the sections that follow.
Click on the
button to
configure or view
a particular
function
Figure 3-1. Measurement Tab
3-2 Configuring Stations, Runs, and Valves (Measurement Tab) Issued: May-2019
3.2 Status/Configuration
When you click the button on the
Measurement tab, Station Manager opens up a tree structure with icons
showing the site along with the various station, meter run, and control
valves you can potentially configure in the Station Manager.
Which ones you configure vary depending upon your site requirements,
the type and number of meter runs, and other local characteristics of your
system.
Note: The Status/Configuration button allows you to fully configure a
ControlWave Station Manager Configuration Manual
station, meter run, or control valve. The screens it opens are
slightly modified versions of those available in previous releases of
Station Manager. Modifications were made to reduce screen clutter
and improve the ease of configuration in Windows 7. If you have
Windows XP, you can also use these screens, or you can continue
to use the older Status/Configuration screens accessible through the
Legacy Controls tab. The older Status/Configuration screens on
the Legacy Controls tab do not support use under Windows 7.
Icons represent each potential
station, meter run, or control
valve you can configure in the
Station Manager.
Figure 3-2. Configuration Tree Structure
Issued: May-2019 Configuring Stations, Runs, and Valves (Measurement Tab) 3-3
ControlWave Station Manager Configuration Manual
g
y
y
y
y
The tree structure includes several different icons, and icons can change
based on your configuration choices. Table 3-1 shows the icons you may
encounter.
Table 3-1. Icons Used in the Configuration Tree
Icon Represents Usage
Site The site icon is for the geographic or
Station Each station controls one or more meter
Runs section of the
tree
Run with undefined
measurement type
Orifice meter run If you configure the meter type as Orifice
Linear meter run If you configure any of these meter types,
Coriolis meter run If you configure the meter type as Coriolis
Annubar If you configure the meter type as Annubar
Venturi meter run If you configure the meter type as Venturi
Plus Sign Click on to expand the tree item to show
Minus Sign Click on to hide tree branches to show less
organizational site associated with this copy
of the Station Manager. The “S” in the icon
distin
uishes it from the station icon.
runs, and typically, one or more control
valves. Station Manager supports up to six
different stations at a site.
The different meter runs you can define
appear underneath this branch of the tree.
Until you specify a meter type, the run icon
is a question mark.
ou’ll see this icon.
you’ll see this icon.
Turbine (turbine meter)
Auto-adjust
(autoadjust turbine
meter)
Ultrasonic (ultra-sonic meter)
PD (positive
displacement
meter)
ou’ll see this icon.
ou’ll see this icon.
ou’ll see this icon.
more branches of information for an item.
information.
Assigning Runs or
Valves to a Station
using Drag and Drop
Meter runs and control valves cannot exist independently within the
Station Manager; you must assign them to a particular station. There
are different ways to assign meter runs or control valves to a particular
station. One way to do that is to drag and drop the icon for the run or
valve onto the station name to which you want to assign it. When you
3-4 Configuring Stations, Runs, and Valves (Measurement Tab) Issued: May-2019
drag, you’ll see a valve or run icon, and you drag it right onto the
station name.
Figure 3-3. Assigning a Run or Valve to a Station Using Drag and Drop
Calling Up Menus
ControlWave Station Manager Configuration Manual
Drag the icon for a run
(or valve) onto the
station name to which
you want to assign it.
There are different ways you can access pages.
To call up the first page for a particular site, station, run, or control valve,
you can just click on its icon, and the first menu opens. Then you can click
on page tabs to bring up other configuration pages associated with that
site, station, run, or control valve.
Click on a Site, Station, Run, or Control Valve icon to open its first menu page
Click on tabs to bring up subsequent pages for this site, station, run, or valve
Issued: May-2019 Configuring Stations, Runs, and Valves (Measurement Tab) 3-5
ControlWave Station Manager Configuration Manual
Figure 3-4. Opening Menus by Clicking on a Station
You can also call up the same pages if you right-click on the icon for a
site, station, run, or control valve, and select an option from the pop-up
menus.
Figure 3-5.Selecting Pages From Pop-up Menus
Showing / Hiding Sections of the Page
The Flowing Units, Gas
Chromatograph and
Averaging sections are
hidden when you first
open the page.
Some pages include sections that are initially hidden to reduce screen
clutter and allow you to focus on the most important items for the current
task at hand.
For example, on the Station Configuration page, the Flowing Units, Gas
Chromatograph, and Averaging sections are hidden when you first open
the page.
Figure 3-6. Hidden Sections on the Page
3-6 Configuring Stations, Runs, and Valves (Measurement Tab) Issued: May-2019
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.