Instruction Manual Supplement
D104219X012
846 Transducer - FM
June 2017
FM Hazardous Area Approvals
Fisher
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installation in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the 846 instruction manual (D102005X012 available from your Emerson sales office, Local Business Partner, or Fisher.com
Always refer to the nameplate itself to identify the appropriate certification.
846 Current‐to-Pressure Transducer
),
.
WARNING
Failure to follow these conditions of safe‐use could result in personal injury or property damage from fire or explosion, and area re‐classification.
Special Conditions of Use
Intrinsically Safe, Explosion-proof, Non-Incendive
1. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.
Refer to table 1 for additional approval information.
Table 1. FM Hazardous Area Classifications
Certification Body Certification Obtained Entity Rating Temperature Code
Vmax = 30 VDC Imax = 100 mA Pmax = 1.0 W Ci = 0.016 mF Li = 20 mH
- - - T4 (Tamb ≤ 60_C)
T4 (Tamb ≤ 60_C)
FM
IS Intrinsically Safe  Class I, II, III Division 1 Groups A,B,C,D,E,F,G  per drawing GE59147 (see figure 1)
XP Explosion-proof  Class I Division 1 Groups B,C,D DIP Dust Ignition-proof  Class II, III Division I Groups EFG NI Non-incendive  Class I Division 2 Groups A,B,C,D
www.Fisher.com
846 Transducer - FM
June 2017
Figure 1. FM Installation Drawing GE59147
Instruction Manual Supplement
D104219X012
GE59147
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
2
E 2017 Fisher Controls International LLC. All rights reserved.