Fire-Lite XRM-24 Installation Manual

The XRM-24 is a 24 volt, 100VA transformer which, when installed, will provide maximum accessory power. The XRM-24 mounts on two studs located in the backbox below the factory installed standard transformer.
XRM-24 Transformer
Product Installation Drawing
Doc. # 50012, Rev B 04/07/05 ECN 05-198
Installation
1) Remove all sources of power from the panel, AC and DC
2) Mount the XRM-24 Transformer to the studs located beneath the factory installed transformer and secure with the supplied #6 Kep nuts (turn clockwise) as illustrated in Figure 1 below.
3) IMPORTANT! In some installations, the transformer mounts partially under the FACP circuit board. In these installations, the transformer must be insolated from the circuit board by installing the supplied insulating fish paper between the transformer and circuit board as illustrated in Figure 2 below.
4) Remove the protective locking connector which is labeled ‘CAUTION! HIGH VOLTAGE’ (located below the factory installed transformer connector).
5) Carefully align the XRM-24 connector with the mating connector on the main circuit board. Note the protective key in the XRM-24 connector.
6) Reapply power to the panel.
Ratings
Normal operating voltage = 24 volts DC. Maximum Current = 3.6 Amps Refer to appropriate product Technical Manual for maximum accessory power specifications.
FACP Backbox
Standard Transformer
#6 Kep nut
#6 Kep nut
Mounting Stud
XRM-24 Transformer
Mounting Stud
Figure 1: XRM-24 Installation
Top of FACP Backbox
Main Circuit Board
Bottom of FACP Backbox
Remove screw
FACP main circuit board
Fish Paper
Remove screw
Slide insulating fish paper between transformers and circuit board, position holes over circuit board mounting standoffs and secure with circuit board mounting screws.
Install screw
FACP main circuit board
Install screw
Figure 2: Fish Paper Installation
One Fire-Lite Place • Northford, CT 06472 • Tel (203) 484-7161 • Fax (203) 484-7118