While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke detectors may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power.
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.
Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LimWarLg.p65 01/10/2000
This digital communicator has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code
• CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This digital communicator complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Central Station Signaling Systems Protected Premises Unit
(Automatic, Manual and Waterflow), Local Fire Alarm Systems (Automatic, Manual, Waterflow
and Sprinkler Supervisory), Proprietary Fire Alarm Systems (Protected Premises Unit), Automatic
Fire Detectors, Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems and Inspection, Testing and Maintenance for Fire Alarm Systems.
FM Approved (with Ademco 685 Receiver)
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524M Standard for Installation of Fire Alarm Systems
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
C22.1, Canadian Electrical Code, Part I
C22.2 No. 0, General Requirements - Canadian Electrical Code, Part II
C22.2 No. 0.4, Bonding and Grounding of Electrical Equipment (Protective Grounding) - Canadian
C282, Emergency Electrical Power Supply for Buildings - Canadian
Requirements of the Local Authority Having Jurisdiction (LAHJ)
1.4: Digital Communicator................................................................................................................................. 9
1.7.2: Digital Communicator.......................................................................................................................11
1.7.3: Telephone Company Rights and Warnings: ......................................................................................11
1.7.4: For Canadian Applications................................................................................................................12
1.8: Modes and Special Functions......................................................................................................................13
1.8.1: Normal Mode ....................................................................................................................................13
1.8.2: Program Mode...................................................................................................................................13
1.8.3: Lamp Test Mode ...............................................................................................................................13
1.8.5: Type Mode.........................................................................................................................................13
3.1: Entering Program Mode ..............................................................................................................................27
4.1: Normal Mode...............................................................................................................................................40
4.2: Type Mode ...................................................................................................................................................44
4.2.1: Disabling of Zones or Points.............................................................................................................45
4.2.2: Zone or Point Supervisory.................................................................................................................45
4.4: Lamp Test Mode..........................................................................................................................................46
Appendix D: Point Assignments - MS-9200 ........................................................................................................56
Appendix E: Code Wheel Matching Point Assignments - MS-9200 .................................................................57
Appendix F: Point Assignments - MS-9600 .........................................................................................................58
F.1: Type Mode Programming ..........................................................................................................................58
F.1.1: For Zone Identification: ...................................................................................................................58
F.1.2: For Point Identification: ...................................................................................................................58
F.2.1: For Zone Reporting: .........................................................................................................................58
F.2.2: For Point Reporting: .........................................................................................................................58
F.3: Point Assignments ......................................................................................................................................59
Appendix G: Zone Assignments ...........................................................................................................................64
6
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
Product Description
CHAPTER 1Product Description
The Universal Digital Alarm Communicator/Transmitter (UDACT-F) may be used with the Fire•Lite MS-9200,
MS-9600 and Sensiscan 2000 FACPs (Fire Alarm Control Panels). The UDACT-F transmits system status to UL
listed Central Station Receivers via the public switched telephone network. The UDACT-F is compact in size and
may be mounted inside the host FACP or may mount externally in a separate enclosure. EIA-485 annunciator communications bus and 24 volt (nominal) connections are required. The UDACT-F is capable of reporting 198 points or
56 zones when used with the MS-9200, 636 points or 99 zones when used with the MS-9600 and 56 zones when used
with the Sensiscan 2000.
1.1Product Features
• Dual telephone lines
• Dual telephone line voltage detect
• UL recognized “Dialer Runaway” prevention
• Compact in size: 6.75" (17.145 cm) x 4.25" (10.795 cm)
• Built-in programmer
• Built-in four character red 7-segment LED display
• Manual test report function
• Manual master transmission clear function
• Mounts either inside control panel or in separate ABS-8RF or UBS-1F enclosure
• Communicates vital system status including:
✓Independent zone/point alarm
✓Independent zone/point trouble
✓Independent zone/point supervisory
✓AC (mains) power loss - programmable
✓Low battery and earth fault
✓System off-normal
✓12 or 24 hour test signal
✓Abnormal test signal per new UL requirements
✓Annunciation of UDACT-F troubles, including loss of phone lines, communication failure with either
Central Station and total communication failure
• Troubleshoot Mode converts keypad to DTMF touchpad
• Individual LEDs for:
✓Power
✓EIA-485 loss
✓Manual Test
✓Kissoff
✓Comm Fail
✓Primary Line Seize
✓Secondary Line Seize
• Open collector relay driver for Total Communication Failure or UDACT-F trouble
• Real Time Clock
• Extensive transient protection
• Simple EIA-485 interface to host panel
UBS-1F
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
7
Product Features
FIGURE 1-1:
24 VDC power in
(use power-limited
source)
EIA-485 connector
(use power-limited
source)
UDACT-F Assembly
Primary
Phone Line
Secondary
Phone Line
Modular Cables
P/N MCBL-7
(order separately)
Comm Fail Output
(power-limited)
24 VDC
(power-limited)
Connect to
J16 on MS-9200,
using supplied
ribbon cable
8
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
1.2Controls and Indicators
Controls and Indicators
Front Panel Switches
CLEARDigits 0 - 9
TESTA
MODEB
Up ArrowC
Down ArrowD
1st EVENTE
ENTER/STOREF
Displays
• EIA-485 - yellow LED
• COMM. FAIL - yellow LED
• KISS OFF - green LED
• POWER - green LED
• Four 7-Segment Displays - red
• Primary Phone Line Active - red LED
• Secondary Phone Line Active - red LED
• TEST - green LED
FIGURE 1-2:
Controls and Indicators
1.3Compatible Panels
The UDACT-F has been designed to be compatible with the following Fire•Lite control panels:
• Sensiscan 2000
• MS-9200
• MS-9600
1.4Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the
Primary and Secondary phone lines. Telephone line 'Primary and Secondary Active' red LEDs are provided as well as
a green 'Kissoff' LED. The integral digital communicator provides the following functions:
• Line Seizure - takes control of the phone lines disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) number - default is Touch-Tone
• For tone burst or touchtone type formats: Discern proper 'Ack' and 'Kissoff' tone(s) - the frequency and time
duration of the tone(s) varies with the transmission format. The UDACT-F will adjust accordingly.
• Communicate in the following formats (refer to “Compatible Receivers” on page 51, for a list of compatible
receivers):
✓6 Tone Burst Types: 20 pps (3+1 Standard & Express, 4+1 Standard & Express, 4+2 Standard &
The UDACT-F circuit board contains a CPU, other primary components and wiring interface connectors
1.5.1 Power Requirements
Operating voltage for the UDACT-F must be power-limited, filtered, nonresettable 21.2 to 28.2 volts. The 24 VDC
nominal operating power must be supplied by the control panel and is connected to TB1 of the UDACT-F.
Note: If the UDACT-F is installed in an MS-9200 FACP, power is provided directly through UDACT-F connector J10 which connects
via supplied ribbon cable to the MS-9200 main circuit board connector J16.
1.5.2 Communications
Communications between the UDACT-F and the host FACP is accomplished over a two-wire EIA-485 serial interface
which is power-limited and supervised by the control panel and the UDACT-F. The wiring connections are made to
the RS+, RS- and Shield terminals of TB1 on the UDACT-F.
The EIA-485 circuit cannot be T-tapped and must be wired in a continuous fashion from the control panel to the
UDACT-F and, if installed, an annunciator. The wire must be 12 AWG to 18 AWG (0.75 to 3.25 mm
2
) twisted,
shielded pair cable with a characteristic impedance of 120 ohms (+/- 20%). Limit the total wire resistance to 100
ohms on the EIA-485 circuit. Do not run cable adjacent to, or in the same conduit as, 120 VAC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 volts
, motor control circuits or
RMS
SCR power circuits.
Note: If the UDACT-F is installed in an MS-9200 FACP, the EIA-485 data line is supplied directly through UDACT-F connector J10
which connects via supplied ribbon cable to the MS-9200 main circuit board connector J16.
1.5.3 Primary and Secondary Phone Lines
Modular jacks are used to interface the primary and secondary phone lines to the public telephone network.
1.5.4 Communicator Fail Relay Driver
Relay driver output for Central Station communication failure is provided.
1.5.5 Earth Ground
Connect a separate earth ground wire to TB3 terminal 1 for transient protection. When mounted in the MS-9200 or
MS-9600, the UDACT-F receives an earth ground connection via the upper right corner mounting position.
1.6Specifications
DC Power - TB1, Terminals 1 & 2
24 VDC (nominal) filtered, nonresettable and power-limited. Voltage range is 21.2 to 28.2 volts. DC power TB1 Terminals 1(+), 2(-) 40 mA in standby, 75 mA maximum while communicating (for MS-9200 installation, use connector
J10) and 100 mA with the open collector output engaged and communicating.
Data Communications - TB1, Terminals 3 - 7
EIA-485 serial interface, TB1 Terminal 3 = RS+, 4 = RS-, 5 = Shield, 6 = future use, 7 = future use. Power-limited
source must be used. (For MS-9200 installation, use connector J10).
10
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Telephone Requirements and Warnings
Auxiliary Output - TB3, Terminals 2 & 3
TB3 Terminal 2 = Communicator Failure. Power-limited circuit. An open collector type output, normally high,
active low which sinks up to 40 mA. TB3 Terminal 3 = 21.2 to 28.2 volts, power-limited. Use UL listed relay P/N
MR-101/C or MR-201/C with this output.
Earth Ground - TB3, Terminal 1
TB3 Terminal 1 = Earth Ground connection. Connect this terminal to building earth ground using solid minimum 12
AWG (3.25 mm
2
) wire to provide lightning protection. This connection is not required when the UDACT-F is
mounted in an MS-9200 or MS-9600 since the upper right mounting hole provides an earth ground connection.
1.7Telephone Requirements and Warnings
1.7.1 Telephone Circuitry - PH1 & PH2
Ringer Equivalence Number (REN) = 0.6B
AC Impedance 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs
on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas,
the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to
the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the
calling area.
1.7.2 Digital Communicator
Before connecting the UDACT-F to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information if provided if required by the local telephone company:
Manufacturer:Fire•Lite Alarms, Inc.
One Firelite Place
Northford, CT 06472
Product Model Number: UDACT-F
FCC Registration Number: 1W6USA-20723-AL-E
Ringer Equivalence Number: 0.6B
1.7.3 Telephone Company Rights and Warnings:
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this digital communicator.
However, the telephone company is required to give advance notice of such changes or interruptions.
If the digital communicator causes harm to the telephone network, the telephone company reserves the right to
temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not
practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct
any problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
11
Telephone Requirements and Warnings
When the digital communicator activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The digital communicator must be connected to the public switched telephone network upstream of any private
telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
1.7.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment
meets certain telecommunications network protective, operational and safety requirements as prescribed in the
appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the
equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The
customer should be aware that compliance with the above conditions may not prevent degradation of service in some
situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the
supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the
telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone
lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly
important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection
authority or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum
number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of
any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
Representative:NOTIFIER/FIRE-LITE, CANADA
24 Viceroy Road
Concord, Ontario L4K2L9
IC Certificate Number: 2132 6030 A
Ringer Equivalence Number (REN): 0.6B
Load Number: 3
12
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Modes and Special Functions
1.8Modes and Special Functions
1.8.1 Normal Mode
Normal Mode is the standard mode of operation. In this mode, the UDACT-F monitors host FACP status as well as
monitoring telephone line voltage. The UDACT-F reports system status information to UL listed Central Stations.
Information transmitted includes general alarm, trouble and supervisory. It also transmits either the number of zones
or points activated or the specific point(s) activated. Specific system trouble conditions and specific UDACT-F troubles are also transmitted.
1.8.2 Program Mode
Program Mode is used to program the UDACT-F. While the UDACT-F is in the program mode, it cannot receive host
FACP status information. Refer to “Programming Instructions” on page 27, for complete programming instructions.
1.8.3 Lamp Test Mode
This mode turns on all segments of the four character display plus all LEDs on the UDACT-F.
1.8.4 Troubleshoot Mode
Troubleshoot Mode may be used for testing the telephone line wiring. Connection from the UDACT-F's modular
jacks, through RJ31X jacks and into the telephone network may be easily checked. In this mode, the keypad acts similar to a telephone touchpad.
1.8.5 Type Mode
Type Mode is used to define the specific type of device (point) used or function of a zone. This mode is also used to
disable the alarm report for any zone/point in the system. The feature which disables the zone/point alarm report
must be used for zones/points programmed into the host FACP as remote silence, reset, drill or acknowledge
switches.
1.8.6 Clear Function
When the clear function is activated, it causes the UDACT-F to immediately stop transmissions, hang-up from the
telephone network, clear out any messages that were waiting for transmission and reset.
1.8.7 Manual Test Function
The manual test function allows for a test report message to be sent to both Central Stations upon activation.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
13
Installation
CHAPTER 2Installation
2.1Mounting Options
FIGURE 2-1:
ABS-8RF
The UDACT-F may be mounted in the control panel or mounted remotely in an
ABS-8RF or UBS-1F enclosure up to 6,000 feet (1,800 m) away from the control panel.
All power must be removed from the FACP before making any connections to prevent
circuit damage. The EIA-485 serial interface is connected between the control panel
and UDACT-F using twisted, shielded pair wire. Power should be wired from the control panel's 24 VDC (nominal) filtered, nonresettable output to TB1 on the UDACT-F
(except when mounted in the MS-9200).
2.2Panel Mounting
2.2.1 MS-9200
The MS-9200 must have firmware with a Part Number of 73580 or higher installed to allow use of the UDACT-F.
Remove all power from the MS-9200 by disconnecting AC and batteries. Install the supplied standoffs (three nylon
and one aluminum standoff) in the appropriate holes located on the right side of the MS-9200 main circuit board as
illustrated in Figure 2-2. Using the ribbon cable supplied with the UDACT-F, connect J10 on the UDACT-F to J16 on
the MS-9200. Note that the colored edge of the ribbon cable must be oriented toward the top edge of the UDACT-F
as illustrated in Figure 2-2. Carefully seat the UDACT-F on the nylon standoffs and secure to the aluminum standoff
with the supplied screw.
The EIA-485 circuit and 24 VDC power are provided directly from connector J16 of the MS-9200. Note that a 120
ohm EOL resistor is not required on the UDACT-F EIA-485 terminals when it is installed inside the MS-9200 cabinet. The EOL resistor is required at the last device on the EIA-485 line, external to the MS-9200.
FIGURE 2-2:
Aluminum standoff
with nut, required for
transient protection
UDACT-F Mounting to MS-9200
Supplied ribbon cable attached
as illustrated to the right.
Note position of colored edge.
J10
UDACT-F
14
MS-9200
UDACT-F
J16
MS-9200
Nylon standoffs
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Panel Mounting
FIGURE 2-3:
Supervised and power-limited EIA-485 and power connections
Nonresettable
External UDACT-F Mounting in ABS-8RF - MS-9200
24 VDC
Power
DO NOT USE
THESE TERMINALS
Ferrite Cores
P/N FBD-1
Install 120 ohm EOL resistor
(P/N 71244) on TB1 Terminals
3 & 4, if last or only device on
EIA-485 line.
MS-9200 cabinet
Solid Earth
Ground
Connection
To Phone
Lines
(Supervised)
UDACT-F in ABS-8RF
(shown with cover removed)
MS-9200
Notes:
This arrangement allows use of the UDACT-F simultaneously with the RTM-8F module
1.
Ferrite cores are recommended for all applications
2.
Recommended wire is 12 AWG to 18 AWG (0.75 to 3.25 mm2) twisted wire
3.
Shielded wire is not required (unless mandated by local AHJ)
4.
If shield wire is used, connect only one end of the shield:
✓shield may be connected to cabinet (earth ground) at fire alarm panel, or
✓shield may be connected to TB1 Terminal 5 (shield) at UDACT-F as shown in Figure 2-3. Note that the
shield end that is not connected should be insulated to prevent accidental grounding. Do not connect
both ends of the shield under any circumstance, since a ground fault may result.
Conduit is recommended for external wire runs. Consult local building codes
5.
Connect Ground Strap (supplied with ABS-8RF enclosure) from Earth Ground terminal on the UDACT-F to a
6.
solid building earth ground. Conduit alone will not provide a reliable earth ground.
UDACT-F may be located up to 6,000 feet (1,800 m) away from the host control panel
7.
Refer to “Specifications” on page 10, for power requirements
8.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
15
Panel Mounting
CAUTION: Connecting a UDACT-F to an MS-9200 which also has an ACM, AFM or LDM Series annunciator connected, will alter the assignments of the first eight yellow LEDs on the annunciator as follows:
TAB L E 2 - 1 : Annunciator LED Assignments (MS-9200)
Yellow Annunciator LED
1
2Signals SilencedSignals Silenced
3Not Used
4Not UsedSupervisory
5SupervisoryBell Trouble
6PrealarmPrealarm/Maintenance Alert
7AC FailLow Battery
8Panel TroubleAC Fail
Assignment
Without UDACT-F
System Trouble
(less AC loss)
Assignment
With UDACT-F
System Trouble
(less AC loss)
Program Mode
(panel off-normal)
16
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Panel Mounting
2.2.2 MS-9600
The UDACT-F may be mounted to a BRKT-9600 bracket inside the FACP cabinet (see MS-9600 instruction manual)
or mounted remotely in a UBS-1F or ABS-8RF enclosure (see Figure 2-3) and wired according to the diagram below.
FIGURE 2-4:
24 VDC
Nonresettable
Power
TB3
CUT TO
DISABLE
LOCAL
CHARGER
UDACT-F Wiring to MS-9600
JP3
J10
4XTM OPT BD
TB4
CUT TO
MONITOR 4X TM
J11
ALARM TRBL SUPV
TB5
JP6
JP5
MS-9600 Control Panel
TB6
+ –
TB7
TXR
I
I
D
O
O
G
N
N
T
C
U
U
N
–
+
R
V
T
T
D
+
–
shield
TB8
J10
+24V
GND
RS+
RS–
SHIELD
RS+
RS–
1
2
3
4
5
6
7
J5
Notes for External Applications:
Ferrite cores are recommended for all applications
1.
Recommended wire is 12 AWG to 18 AWG (0.75 to 3.25 mm2) twisted wire
2.
Shielded wire is not required (unless mandated by local AHJ)
3.
If shield wire is used, connect only one end of the shield:
✓shield may be connected to cabinet (earth ground) at fire alarm panel, or
✓shield may be connected to TB1 Terminal 5 (shield) at UDACT-F as shown in Figure 2-3. Note that the
shield end that is not connected should be insulated to prevent accidental grounding. Do not connect
both ends of the shield under any circumstance, since a ground fault may result.
Conduit is recommended for external wire runs. Consult local building codes
4.
Connect Ground Strap (supplied with ABS-8RF enclosure) from Earth Ground terminal on the UDACT-F to a
5.
solid building earth ground. Conduit alone will not provide a reliable earth ground.
UDACT-F may be located up to 6,000 feet (1,800 m) away from the host control panel
6.
Refer to “Specifications” on page 10, for power requirements
7.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
17
Panel Mounting
Connecting a UDACT-F to an MS-9600 which also has an ACM, AFM or LDM Series annunciator connected, will
not
alter the assignments of the first eight yellow LEDs on the annunciator.
TAB L E 2 - 2 : Annunciator LED Assignments (MS-9600)
Yellow Annunciator LED
1
2Signals Silenced
3
4Supervisory
5Bell Trouble
6Prealarm/Maintenance Alert
7Low Battery
8AC Fail
Assignment
With or Without UDACT-F
System Trouble
(less AC loss)
Program Mode
(panel off-normal)
18
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Panel Mounting
2.2.3 Sensiscan 2000
Remove all power from the control panel by disconnecting AC and batteries. Install the three supplied nylon support
posts for the top and bottom left of the UDACT-F, one aluminum/nylon and one aluminum standoff in the CHS-4
chassis slot in which the UDACT-F is to be installed (refer to Figure 2-5). Position the UDACT-F on the standoffs
and secure on the aluminum standoff with a #6-32 screw. Alternatively, the UDACT-F may be mounted remotely
using an ABS-8RF or UBS-1F enclosure. Ferrite cores are recommended for this application. Refer to Figure 2-3,
“External UDACT-F Mounting in ABS-8RF - MS-9200,” on page 15, and the accompanying notes for wiring alternatives.
Connect the communication line between the EIA-485 terminal block on the CPU-2000 and TB1 Terminals 3 & 4 on
the UDACT-F, making certain to observe polarity. Refer to Figure 2-6, “EIA-485 Connection Sensiscan 2000,” on
page 20. Recommended wire is 12 AWG to 18 AWG (0.75 to 3.25 mm
nected to the EIA-485 line, install a 120 ohm EOL resistor across the UDACT-F TB1 Terminals 3 & 4.
Connect the supplied Ground Strap from the UDACT-F Earth Ground terminal on TB3 to the CHS-4 chassis. Connect 24 VDC filtered, nonresettable power to TB1 Terminals 1 & 2 on the UDACT-F. Refer to Figure 2-7, “24 VDC
Power Connection to UDACT-F,” on page 21.
2
) twisted pair. If no other devices are con-
FIGURE 2-5:
CPU-2000
UDACT-F Mounting in CHS-4
UDACT-F
nylon support
posts
ground strap
CHS-4
aluminum
standoff and
screw
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
nylon &
aluminum
standoff
19
Panel Mounting
FIGURE 2-6:
EIA-485 Connection Sensiscan 2000
EIA-485 (super vised and power-limited)
+
Install 120 ohm EOL
resistor (P/N: 71244)
across Terminals 3
(RS+) & 4 (RS-) if
last or only device on
EIA-485 line. Note
that Terminals 6
(RS+) & 7 (RS-) are
not used at this time.
+
-
TB1
Terminal 3 RS+
Terminal 4 RS-
CPU-2000
UDACT-F
20
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Panel Mounting
FIGURE 2-7:
24 VDC Power Connection to UDACT-F
Power (supervised and power-limited)
TB3-3 +
- TB3-4
TB1-1 +
TB1-2 -
UDACT-F
MPS-24AF
TB2-1 +
Power (supervised and power-limited)
- TB2-2
Cut jumper JP1 to make
output nonresettable for
use with UDACT-F
TB1-1 +
TB1-2 -
MPS-24BF
Power for the UDACT-F must be 24 VDC filtered, nonresettable
Note:
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
UDACT-F
21
Panel Mounting
CAUTION: Connecting a UDACT-F to a Sensiscan 2000, which also has an AFM or LDM series annunciator
connected, will alter the assignments of the first eight yellow LEDs on the annunciator as follows:
TAB L E 2 - 3 : Sensiscan 2000 Annunciator LED Assignments
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited
circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or
conduits. A typical wiring diagram for the UDACT-F is shown below.
FIGURE 2-8:
Typical Wiring Diagram for UL Power-limited Requirements
Use power-limited source
Use power-limited source
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
23
Output Circuits
2.4Output Circuits
2.4.1 Telephone Circuits
Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 (Primary)
and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection. The RJ31X jacks must be ordered separately.
Note that it is critical that the UDACT-F be located as the first device on the incoming telephone circuit to properly
function.
FIGURE 2-9:
Wiring Phone Jacks
(Primary Lines)
Incoming Telco
Phone Lines
Green Wire
Tip
Red Wire
Ring
Primary Phone Line PH-1
To premises phones
Ring
Tip
Note: Shorting bars inside
RJ31X Jack removed during
male plug insertion
7 foot
cable
(MCBL-7)
order separately
Tip
Ring
Green Wire
Red Wire
(Secondary Lines)
Incoming Telco
Phone Lines
Ring
To premises phones
Tip
Secondary Phone Line PH-2
24
Male Plug Connectors
Modular Female Connectors
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Output Circuits
2.4.2 Relay Driver
The UDACT-F's open collector output on TB3, Terminal 2, is provided for Communicator Failure and UDACT-F
trouble. It can be used to drive UL listed relay MR-101/C or MR-201/C. The output is rated for 40 mA. The normal
condition for the output is Off (deenergized).
Communicator Failure occurs when the maximum number of attempts to reach both Central Stations has taken place
or when both phone lines are disconnected. UDACT-F trouble conditions include loss of telephone line voltage to the
primary and/or secondary phone lines, communication failure to the primary or secondary Central Stations or total
communication failure.
Wiring from the UDACT-F terminal block TB3 to the relay must be in the same room no more than 20 feet (6 m) in
length and enclosed in conduit. Wiring from the relay output contacts must also remain in the same room as the
UDACT-F.
When the UDACT-F is programmed as 'Receive Only' (typically when annunciators are also used and are set for
'Receive/Transmit'), the relay output is used to provide a UDACT-F trouble input to the host control panel. For
MS-9200 and MS-9600 applications, use a monitor module to supervise the relay closure (refer to Figure 2-11). Program the adjective and noun fields for 'UDACT-F Trouble'. For Sensiscan 2000 applications, wire the relay output to
the annunciator trouble input circuit or use the relay to trigger zone trouble.
When the UDACT-F is programmed as 'Receive/Transmit', EIA-485 supervision and UDACT-F trouble status are
automatically handled by the host control panel.
FIGURE 2-10:
Relay Driver Connections
All wiring to relay must be in the
same room within 20 feet of the
UDACT-F and in conduit.
Relay Energized LED
DPDT Contacts
10 amps
@115 VAC
Connections must be in the
same room as the UDACT-F.
Relay Energized LED
DPDT Contacts
10 amps
@115 VAC
Note: The MR-101/C and MR-201/C include an enclosure.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
25
Output Circuits
FIGURE 2-11:
SLC Loop to Fire
Alarm Control Panel
Monitoring for UDACT-F Trouble
MMF-300 Series
Monitor Module
Wiring in
same room as
UDACT-F
All wiring to relay must be in the same room
within 20 feet of the UDACT-F and in conduit.
3.9K ohm EOL
resistor
(supplied)
Earth Grnd
Comm Fail
+24 VDC
UDACT-F
MR-101/C
(MR-201/C may also be used)
MMF-300 Series Monitor Module is used to supervise Normally Closed output of MR-101/C. On UDACT-F trouble and Comm. Fail, MR-101/
Note:
C relay contact will open, causing M300 to transmit trouble condition to the FACP.
26
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Programming Instructions
CHAPTER 3Programming Instructions
Programming of the UDACT-F is possible at any time including while the UDACT-F is communicating with a Central
Station. The UDACT-F has been designed for many different types of applications. After examining your specific
application, review the programming options and choose the entries best suited for your system.
The UDACT-F has a built-in programmer. All programming selections are stored in nonvolatile Electrically-Erasable
Programmable Read-Only Memory (EEPROM). This ensures that the UDACT-F will retain all entries made in
Programming Mode even if power is removed.
The user must
program the primary and secondary phone numbers, account numbers and 24 hour test report times for
each Central Station account and the current time. The UDACT-F comes with factory chosen options/features already
programmed. Other options/features may be programmed if desired. If all factory default settings are acceptable,
programming is complete.
3.1Entering Program Mode
To enter the Program Mode, press the MODE key once (the display will go blank). The user then has ten seconds to
start entering the code 7764.
®
☛ 7764 spells PROG on a Touch-Tone
If an incorrect key is entered, reenter the proper 4-digit code before
the information is entered into the UDACT-F, the digits scroll across the display from right to left.
___7
__77
_776
7764
The user is allowed a pause of up to 10 seconds in between each key stroke while entering the code. After pressing
the [ENTER/STORE] key, the UDACT-F will be in Program Mode and display 00_F. The user is allowed up to ten
minutes of idle time at this point before starting the programming, otherwise, the UDACT-F will return to Normal
Mode. The user also has a maximum of 10 minutes between any key stroke. All entries made prior to the 10 minute
time-out are valid and stored.
phone
pressing the [ENTER/STORE] key. Note that as
Once in Programming Mode, the UDACT-F will:
• Ignore the Test and Clear keys
• Continue to communicate any events not previously acknowledge at the Central Station prior to entering
Programming Mode
Location 56 is factory set to '0' for UDACT-F communications disabled. This setting keeps the communicator off until
location 56 is changed to 1, 2, 3, 4, 5 or 6. Refer to program selection for address 56 in this section. Once location
56 is changed from 0 to 1, 2, 3, 4, 5 or 6 and a valid phone number is entered, transmission of the 'UDACT-F Off Normal' report will occur.
Throughout Programming Mode, the first three locations on the left of the display represent the memory address
which can range from 00 to 208 (alpha characters are not used). The last location (farthest right) represents the
contents of the memory address. The first address displayed is shown below:
00_F
(address)(data)
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
27
Switch (Key) Functions
3.2Switch (Key) Functions
The function of each switch (key) in Program Mode is illustrated in Figure 3-1.
FIGURE 3-1:
UDACT-F Keypad
No function in Program Mode
Address entry keys are 0 to 9
Data entry keys are 0 to 9 and A to F
3.3Programming Options
Select operating mode
Increment memor y address
Decrement memory address
1st press = First memory address
2nd press = Enter any address
Save data, go to next address
Primary Phone Number (00-15)
The first sixteen addresses are factory set to 'F' (from 00_F to 15_F). Programming is typically done as follows:
✓If the phone number to be entered is 484-7161, press 4
✓The display will read 00_4
✓Press the [ENTER/STORE} key to save the entry to memory and increment to the next address 01_F
✓Enter the remaining numbers in their respective addresses as shown below:
48 4 7 16 1 FFF FFFFFF
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha digits (A - F) representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds, then dial anyway
D = three second pause
E = five second pause
F = end of phone number (F must be entered)
28
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Programming Options
Primary Number Communication Format (16)
One location is needed to select the Communication Format to the primary phone number. Address 16 is used for this
purpose. The default (factory setting) for this address is 16_A, which is 4+2 Standard, 1800 Hz 'Carrier', 2300 Hz
'ack'. The user may enter 0, 1, 2, 4, 6, 8, C or E in place of the default, then press the [ENTER/STORE] key. Choose
from the list of formats below:
Note: Consult the Central Station for proper selection or consult the factory representatives. For any format chosen, the UDACT-F
automatically programs all of the event codes. Refer to Table 3-2 on page 34, Table 3-3 on page 35, Table 3-4 on page 36, Table 3-5
on page 37, Table 3-6 on page 38 and Table 3-7 on page 39.
Primary Number Account Code (17-20)
The Account Code if provided by the Central Station. Four locations at addresses 17 - 20 which default to all '0s'
must be changed to the supplied Account Code. Valid entries are 0 - 9 and A - F. The number of digits entered must
match the format selection. If programming '2' or '4' into address 16, enter the three digit code (location 20 is
ignored). If programming '0, 1, 6, 8, A, C or E' into address 16, enter the four digit code.
Primary Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four locations (addresses 21 - 24). The default is 00:00 (12:00 midnight). The limits for each location are as follows:
21 = 0 to 2
22 = 0 to 9
23 = 0 to 5
24 = 0 to 9
Do not use 'A - F' as entries in these addresses.
Primary Number 24/12 Hour Test Time Interval (25)
The test report sent to the primary phone number may be sent every 12 or 24 hours. If the message is to be sent every
24 hours, leave the factory default entry of '0'. If a 12 hour test report time is needed, enter '1' for 12 hours.
Secondary Phone Number (26-41)
The sixteen addresses are factory set to 'F' (from 26_F to 41_F). Programming is typically done as follows:
✓If the phone number to be entered is 484-7161, press 4
✓The display will read 26_4
✓Press the [ENTER/STORE] key to save the entry to memory and increment to the next address 27_F
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
29
Programming Options
✓Enter the remaining numbers in their respective addresses as shown below:
48 4 7 16 1 FFF FFFFFF
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha digits (A - F) representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds, then dial anyway
D = three second pause
E = five second pause
F = end of phone number (F must be entered)
Secondary Number Communication Format (42)
One location is needed to select the Communication Format to the secondary phone number. Address 42 is used for
this purpose. The default (factory setting) for this address is 42_A, which is 4+2 Standard, 1800 Hz 'Carrier', 2300
Hz 'ack'. The user may enter 0, 1, 2, 4, 6, 8, C or E in place of the default, then press the [ENTER/STORE] key.
Choose from the list of formats below:
Note: Consult the Central Station for proper selection or consult the factory representatives. For any format chosen, the UDACT-F
automatically programs all of the event codes. Refer to Table 3-2 on page 34, Table 3-3 on page 35, Table 3-4 on page 36, Table 3-5
on page 37, Table 3-6 on page 38 and Table 3-7 on page 39.
Secondary Number Account Code (43-46)
Four locations at addresses 43 - 46 default to all '0s'. Valid entries are 0 - 9 and A - F. The number of digits entered
must match the format selection. If programming '2' or '4' into address 42, enter three digits (location 46 is ignored).
If programming '0, 1, 6, 8, A, C or E' into address 42, enter four digits.
30
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Programming Options
Secondary Number 24 Hour Test Time (47-50)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 2 takes up four locations (addresses 47 - 50). The default is 00:00 (12:00 midnight). The limits for each location are as follows:
47 = 0 to 2
48 = 0 to 9
49 = 0 to 5
50 = 0 to 9
Do not use 'A - F' as entries in these addresses.
Secondary Number 24/12 Hour Test Time Interval (51)
The test report sent to the secondary phone number may be sent every 12 or 24 hours. If the message is to be sent
every 24 hours, leave the factory default entry of '0'. If a 12 hour test report time is needed, enter '1' for 12 hours.
Start Monitoring Address (52-53)
The entries in these addresses indicate the first group of zones or points to be monitored and reported to the Central
Station. The factory default entry is '01'. The only valid entry is '01' (S2000 or MS-9200) or ‘20’ (MS-9600). Refer
to Table 3-1 .
End Monitoring Address (54-55)
The entries in these addresses indicate the last group of zones or points to be monitored and reported to the Central
Station. The factory default entry is '01'. Valid entries are '01' and '04' (S2000 or MS-9200) or ‘20’ to ‘32’ (MS-
9600). Refer to Table 3-1 .
Note that the Start and End Monitoring Address programming locations are used to set the reporting range of the
UDACT-F.
TABLE 3-1:
MS-9200
MS-9600
S2000
1 = Report status of 56 software zones
2 = Report status of 99 software zones
3 = Report status of 56 zones
Note: For additional information on the starting and ending addresses, refer to the host FACP Technical Manual.
Start and End Monitoring Address
Zone Reporting (factory default)Point Reporting
START
Address 52-53
1
01
2
20
3
01
END
Address 54-55
01MS-9200
32MS-9600
START
Address 52-53
1
01
2
20
01S2000N/AN/A
1 = Report status of 198 points
2 = Report status of 636 points
END
Address 54-55
1
04
2
32
UDACT-F Communication Selection (56)
Leaving address 56 at '0' disables communications to the Central Station(s). Enter '1' for zone reporting receive only,
'2' for zone reporting receive/transmit, '3' for consecutive point reporting receive only, '4' for consecutive point reporting receive/transmit, '5' for code wheel matching point reporting receive only or '6' for code wheel matching point
reporting receive/transmit. Refer to “Type Mode” on page 44 and “Point Reporting” on page 50 for additional information on code wheel match reporting.
Note: Use receive only selections when using remote annunciators. Be certain to set one of the annunciators for receive/transmit for
EIA-485 communications bus supervision. Use the receive/transmit entries when annunciators are not installed or when the UDACTF receive/transmit function is to be used to supervise the EIA-485 communication bus. For additional information on the receive/
transmit function, refer to the specific annunciator technical manuals.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
31
Programming Options
Backup Reporting (57)
Leaving address 57 at '0' means that reports will be transmitted to the secondary phone number only if attempts to
communicate to the primary phone number are unsuccessful. Programming a '1' causes all reports to be transmitted
to the secondary phone number.
Touchtone/Rotary Select (58)
A '0' programmed in this address by the factory triggers Touchtone dialing over both phone lines. Enter '1' for rotary
dialing.
Make/Break Ratio (59)
An entry must be made in this address only if address 58 is set to '1'. Address 59 is factory set to '0' which is a 67/33
ratio, but may be changed to '1' which is 62/38 ratio.
Address (60)
Leave factory default of '0'.
Address (61)
Leave factory default of '0'.
AC Loss Reporting Delay (62)
The factory default entry of '1' causes a 6 hour time delay for AC loss reporting. A '0' entry causes immediate reporting of AC loss. Valid entries are '0 to 9' and 'A to F' corresponding to the following reporting delay times:
1 = 6 hours9 = 17 hours
2 = 7 hoursA = 18 hours
3 = 8 hoursB = 19 hours
4 = 9 hoursC = 20 hours
5 = 10 hoursD = 21 hours
6 = 11 hoursE = 22 hours
7 = 15 hoursF = 23 hours
8 = 16 hours
Host Panel ID (63)
Enter one of the following digits corresponding to the control panel in which the UDACT-F is installed. A correct
entry is essential for proper operation.
0 = MS-92005 = MS-9600
1 = Do not use6 = Do not use
2 = Sensiscan 20007 = Do not use
3 = Do not use8 = Do not use
4 = Do not use9 = Do not use
Loop Number (64-65)
This address is used for Contact ID format only. The factory default setting is '00'. Refer to “Reporting Formats” on
page 47.
Sensor Number (66-68)
This address is used for Contact ID format only. The factory default setting is '000'. Refer to “Reporting Formats” on
page 47.
32
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Programming Options
Programming Event Codes (69-208)
The type of reports and 'event codes' that are sent to the Central Station are referenced in Table 3-2 on page 34, Table
3-3 on page 35, Table 3-4 on page 36, Table 3-5 on page 37, Table 3-6 on page 38 and Table 3-7 on page 39. The
selections made for the Primary Central Station Number communication Format (address 16) and the Secondary Central Station Number Communication Format (address 42) automatically program addresses 69-208 with factory
default selections.
Any of the event codes may be changed. Consult the Central Station prior to altering the event codes. For the 3+1,
4+1 and 4+1 Express formats, entering an event code of '0' will cause the communicator to NOT transmit the report.
Enter '00' for 4+2 and 4+2 Express formats to NOT transmit the report. For Ademco Contact ID format, enter '000'.
Transmission of reports to either or both Central Station phone numbers may be disabled.
Note the special 'System Abnormal Test Report' event code. This report was added per UL DACT requirements. This
report is generated in place of the normal test report when an alarm and/or trouble condition exists at the time the test
report is due to be sent.
Programming the Real-Time Clock
Entering an address greater than 209 will cause a display of the current time. On initial power-up, the clock will start
running from the factory setting of 00:01 (military time). The far left digit will be flashing, indicating that this is the
first digit to be programmed.
Hours and Minutes
To set the hour, select a digit then press the [ENTER/STORE] key. The digit 2nd from the left will start flashing.
Select a digit then press the [ENTER/STORE] key. The hours setting is completed. With the digit 2nd from the
right flashing, select a digit for the minutes then press the [ENTER/STORE] key. The digit on the far right will start
flashing. Select a digit then press the [ENTER/STORE] key. The minutes setting is completed.
End Programming
Exit Programming Mode by pressing the MODE key, followed by the 4-digit code corresponding to an alternate
mode of operation, then press the [ENTER/STORE] key. During Program Mode, if no key is pressed within 10 minutes, the UDACT-F will revert to Normal Mode.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
33
Programming Options
3+1, 4+1 Express and 4+1 Standard Formats
If '0, 2, 4, 6 or 8' is entered for address 16, the following data is automatically programmed for the Primary Phone
number event codes. Enter a '0' for the data setting to disable the report.
TAB L E 3 - 2 : Primary Number Event Codes - 3+1, 4+1 Express and 4+1 Standard
AddressDescriptionSetting
69Primary # General Alarm Code1
70Primary # Zone/Point Alarm Code0
71Primary # General Supervisory Code8
72Primary # Zone/Point Supervisory Code0
73Primary # General Fault CodeF
74Primary # AC Fault CodeF
75Primary # Zone/Point Fault Code0
76Primary # Low Battery Fault CodeF
77Primary # Telco Primary Line Fault CodeF
78Primary # Telco Secondary Line Fault CodeF
79Primary # NAC Fault CodeF
80Primary # Communication Trouble Primary # CodeF
81Primary # Communication Trouble Secondary # CodeF
82Primary # 485 Communication Trouble CodeF
83Primary # System Off Normal CodeF
84Primary # UDACT-F Off Normal CodeF
85Primary # General Alarm Restore CodeE
86Primary # Zone/Point Alarm Restore Code0
87Primary # General Supervisory Restore CodeE
88Primary # Zone/Point Supervisory Restore Code0
89Primary # General Fault Restore CodeE
90Primary # AC Fault Restore CodeE
91Primary # Zone/Point Fault Restore Code0
92Primary # Low Battery Fault Restore CodeE
93Primary # Telco Primary Line Fault Restore CodeE
94Primary # Telco Secondary Line Fault Restore CodeE
95Primary # NAC Fault Restore CodeE
96Primary # Communication Trouble Primary Number Restore CodeE
97Primary # Communication Trouble Secondary Number Restore CodeE
98Primary # 485 Communication Trouble Restore CodeE
99Primary # System Off Normal Restore CodeE
100Primary # UDACT-F Off Normal Restore CodeE
101Primary # System 24 Hour Test9
102Primary # System 24 Hour Test with Active EventF
103Primary # Manual Test9
Note: Zero entries prevent the transmission of the report to the Central Station
34
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Programming Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' is entered for address 16, the following data is automatically programmed for the Primary Phone number event codes. Enter a '0' for the data setting to disable the report.
TABLE 3-3: Primary Number Event Codes - 4+2 Standard and 4+2 Express
AddressDescriptionSetting
69 - 70Primary # General Alarm Code11
71 - 72Primary # Zone/Point Alarm Code00
73 - 74Primary # General Supervisory Code81
75 - 76Primary # Zone/Point Supervisory Code00
77 - 78Primary # General Fault CodeF1
79 - 80Primary # AC Fault CodeF6
81 - 82Primary # Zone/Point Fault Code00
83 - 84Primary # Low Battery Fault CodeF8
85 - 86Primary # Telco Primary Line Fault CodeFA
87 - 88Primary # Telco Secondary Line Fault CodeFB
89 - 90Primary # NAC Fault CodeFC
91 - 92Primary # Communication Trouble Primary # CodeFD
93 - 94Primary # Communication Trouble Secondary # CodeFE
117 - 118Primary # Telco Primary Line Fault Restore CodeEA
119 - 120Primary # Telco Secondary Line Fault Restore CodeEB
121 - 122Primary # NAC Fault Restore CodeEC
123 - 124Primary # Communication Trouble Primary Number Restore CodeED
125 - 126Primary # Communication Trouble Secondary Number Restore CodeEE
127 - 128Primary # 485 Communication Trouble Restore CodeEE
129 - 130Primary # System Off Normal Restore CodeEF
131 - 132Primary # UDACT-F Off Normal Restore CodeEF
133 - 134Primary # System 24 Hour Test99
135 - 136Primary # System 24 Hour Test with Active Event91
137 - 138Primary # Manual Test92
Note: Zero entries prevent the transmission of the report to the Central Station
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
35
Programming Options
Ademco Contact ID Format
If 'E' is entered for address 16, the following data is automatically programmed for the Primary phone number event
codes. Enter '000' for the data setting to disable the report.
TAB L E 3 - 4 : Ademco Contact ID Primary Number
110
1
Sensor Number
2
000
4
Note
000
Note
Note
3
2
3
3
AddressDescriptionSetting
69 - 71Primary # General Alarm Code110
72 - 74Primary # Zone/Point Alarm Code
75 - 77Primary # General Supervisory Code200
78 - 80Primary # Zone/Point Supervisory Code200
81 - 83Primary # General Fault Code300
84 - 86Primary # AC Fault Code301
87 - 89Primary # Zone/Point Fault Code380
90 - 92Primary # Low Battery Fault Code302
93 - 95Primary # Telco Primary Line Fault Code351
96 - 98Primary # Telco Secondary Line Fault Code352
99 - 101Primary # NAC Fault Code321
102 - 104Primary # Communication Trouble Primary # Code354
105 - 107Primary # Communication Trouble Secondary # Code354
108 - 110Primary # 485 Communication Trouble Code300
111 - 113Primary # System Off Normal Code308
114 - 116Primary # UDACT-D Off Normal Code350
117 - 119Primary # System 24 Hour Test602
120 - 122Primary # System 24 Hour Test with Active Event608
123 - 125Primary # Manual Test Message601
Notes:
Zero entries prevent the transmission of the report to the Central Station
1.
Refer to Contact ID program locations 64 - 68
2.
The identification of the zone/sensor number is automatically transmitted by the UDACT-F and is added to the
3.
main event code. Refer to Table A-3, “Ademco Contact ID Reporting Structure,” on page 49, for additional
information
Factory default for this report is 110 (110 is transmitted for modules, however, 111 will automatically be trans-
4.
mitted for smoke detectors). Use Type Mode (refer to “Type Mode” on page 44) to change this report per zone
or point
36
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Programming Options
3+1, 4+1 Express and 4+1 Standard Formats
If '0, 2, 4, 6 or 8' is entered for address 42, the following data is automatically programmed for the Secondary Phone
number event codes. Enter a '0' for the data setting to disable the report.
TABLE 3-5: Secondary Number Event Codes - 3+1, 4+1 Express and 4+1 Standard
AddressDescriptionSetting
139Secondary # General Alarm Code1
140Secondary # Zone/Point Alarm Code0
141Secondary # General Supervisory Code8
142Secondary # Zone/Point Supervisory Code0
143Secondary # General Fault CodeF
144Secondary # AC Fault CodeF
145Secondary # Zone/Point Fault Code0
146Secondary # Low Battery Fault CodeF
147Secondary # Telco Primary Line Fault CodeF
148Secondary # Telco Secondary Line Fault CodeF
149Secondary # NAC Fault CodeF
150Secondary # Communication Trouble Primary # CodeF
151Secondary # Communication Trouble Secondary # CodeF
163Secondary # Telco Primary Line Fault Restore CodeE
164Secondary # Telco Secondary Line Fault Restore CodeE
165Secondary # NAC Fault Restore CodeE
166Secondary # Communication Trouble Primary Number Restore CodeE
167Secondary # Communication Trouble Secondary Number Restore CodeE
168Secondary # 485 Communication Trouble Restore CodeE
169Secondary # System Off Normal Restore CodeE
170Secondary # UDACT-F Off Normal Restore CodeE
171Secondary # System 24 Hour Test9
172Secondary # System 24 Hour Test with Active EventF
173Secondary # Manual Test9
Note: Zero entries prevent the transmission of the report to the Central Station
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
37
Programming Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' is entered for address 42, the following data is automatically programmed for the Secondary Phone number event codes. Enter a '0' for the data setting to disable the report.
TAB L E 3 - 6 : Secondary Number Event Codes - 4+2 Standard and 4+2 Express
187 - 188Secondary # Telco Primary Line Fault Restore CodeEA
189 - 190Secondary # Telco Secondary Line Fault Restore CodeEB
191 - 192Secondary # NAC Fault Restore CodeEC
193 - 194Secondary # Communication Trouble Primary Number Restore CodeED
195 - 196Secondary # Communication Trouble Secondary Number Restore CodeEE
197 - 198Secondary # 485 Communication Trouble Restore CodeEE
199 - 200Secondary # System Off Normal Restore CodeEF
201 - 202Secondary # UDACT-F Off Normal Restore CodeEF
203 - 204Secondary # System 24 Hour Test99
205 - 206Secondary # System 24 Hour Test with Active Event91
207 - 208Secondary # Manual Test92
Note: Zero entries prevent the transmission of the report to the Central Station
38
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Programming Options
Ademco Contact ID Format
If 'E' is entered for address 42, the following data is automatically programmed for the Secondary phone number
event codes. Enter '000' for the data setting to disable the report.
163 - 165Secondary # Telco Primary Line Fault Code351
166 - 168Secondary # Telco Secondary Line Fault Code352
169 - 171Secondary # NAC Fault Code321
172 - 174Secondary # Communication Trouble Primary # Code354
175 - 177Secondary # Communication Trouble Secondary # Code354
178 - 180Secondary # 485 Communication Trouble Code300
181 - 183Secondary # System Off Normal Code308
184 - 186Secondary # UDACT-D Off Normal Code350
187 - 189Secondary # System 24 Hour Test602
190 - 192Secondary # System 24 Hour Test with Active Event608
193 - 195Secondary # Manual Test Message601
Notes:
Zero entries prevent the transmission of the report to the Central Station
1.
Refer to Contact ID program locations 64 - 68
2.
The identification of the zone/sensor number is automatically transmitted by the UDACT-F and is added to the
3.
main event code. Refer to Table A-3, “Ademco Contact ID Reporting Structure,” on page 49, for additional
information
Factory default for this report is 110 (110 is transmitted for modules, however, 111 will automatically be trans-
4.
mitted for smoke detectors). Use Type Mode (refer to “Type Mode” on page 44) to change this report per zone
or point
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
39
Operating Instructions
CHAPTER 4Operating Instructions
4.1Normal Mode
The UDACT-F has five modes of operation:
•Normal Mode
• Type Mode
• Program Mode
• Lamp Test Mode
• Troubleshoot Mode
Upon initial power-up, the system will be in Normal Mode. This section describes the operation of the UDACT-F in
the Normal Mode.
4.1.1 Keypad Functions
Clear
The Clear function will cause the UDACT-F to :
• cease transmissions
• clear any active or pending transmissions
• reset and return to normal system processing
To perform the Clear function, press the CLEAR key followed by 2532 and then press the [ENTER/STORE] key.
☛ 2532 spells CLEA on a Touch-Tone
®
phone.
Te s t
If the TEST key is pressed three times in rapid succession, the UDACT-F will transmit a test message to both Central
Stations. The message reported is the same as the automatic test message for all formats except Ademco Contact ID.
Mode
Pressing the MODE key followed by a valid 4-digit numerical code and pressing the [ENTER/STORE] key selects
one of the five modes of operation. To enter Normal Mode from any other mode, press the MODE key followed by
6676 and then the [ENTER/STORE] key.
®
phone.
40
☛ 6676 spells NORM on a Touch-Tone
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Normal Mode
1st Event
The 1st Event key along with the up arrow and down arrow keys are used to display UDACT-F fault conditions. Press
the 1st Event key at any time to display the first event that occurred.
Down Arrow
The down arrow key can be used to view UDACT-F fault events (older) that have occurred and are active (not
cleared).
Up Arrow
The up arrow key can be used to view UDACT-F fault events (newer) that have occurred and are active (not cleared).
[Enter/Store]
See individual mode descriptions in the following sections.
4.1.2 Displays
Four 7-segment red LED characters provide visual annunciation of UDACT-F trouble conditions. A list of messages
that may appear on the display in Normal Mode is shown below:
PH_1Primary Number Communication Fault
PH_2Secondary Number Communication Fault
no_1Primary Phone Line Fault
no_2Secondary Phone Line Fault
Individual LEDs are provided for:
EIA-485
A yellow LED that turns on steady when a fault on the EIA-485 circuit is detected.
Comm. Fail
This yellow LED turns on to indicate the loss of both telephone lines or that the maximum number of attempts to
communicate with both Central Stations had been unsuccessful. During a comm. fail, the display will show either a
PH1 and PH2 or no1 and no2.
Power On
A green LED that remains on while DC power is supplied to the UDACT-F. If this indicator fails to light under normal conditions, service the system immediately.
Kissoff
A green LED that blinks when the Central Station has acknowledged receipt of each transmitted message.
Te st
A green LED that turns on to indicate that a manual test message is being transmitted.
Primary Line Active
A red LED that indicates the primary phone line is active
Secondary Line Active
A red LED that indicates the secondary phone line is active.
Modem
A green LED that stays on steady during modem types of communications.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
41
Normal Mode
FIGURE 4-1:
UDACT-F Phone Connectors and LEDs
Primary Active
LED
Modem LED
Phone Line
Primary
Secondary
Phone Line
Secondary
Active LED
Kissoff LED
4.1.3 Normal Mode Operation
Normal Mode is the standard mode of operation. In this mode, the UDACT-F monitors host FACP status, power
input, EIA-485 communications and telephone line voltage. The four character 7-segment display is normally off and
does not annunciate events that are being transmitted. The display will only annunciate UDACT-F trouble conditions
in the Normal Mode.
The UDACT-F transmits zone/point and system status reports to a Central Station via the public switched telephone
network. Two supervised telephone line connections are made to interface the UDACT-F to the telephone lines.
The UDACT-F supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault in
either phone line connection is reported as a trouble. When a fault is detected, the four character display will show
either 'no1' for a Primary Line fault or 'no2' for a Secondary Line fault and the trouble condition will be reported to
the Central Station over the remaining good phone line.
The UDACT-F comes with line seizure capability provided for both the primary and secondary telephone line interfaces. Any time that the UDACT-F needs to make a call to the Central Station, line seizure will disconnect any local
premises phones sharing the same telephone line.
All transmissions to the Central Station will be sent over the Primary phone line. In the event of noisy phone lines,
transmissions will be sent over the backup Secondary phone line.
Two phone numbers must be programmed, the Primary phone number and the Secondary phone number. All system
reports will be transmitted to the primary phone number. Reports will automatically be sent to the secondary phone
number if attempts to transmit to the primary phone number are unsuccessful. If 10 total attempts to communicate
are unsuccessful, the Communicator Failure output will be turned on (TB3, Terminal 2). Note that as an option, all
reports may also be sent to the secondary phone number. Refer to “Programming Instructions” on page 27.
The UDACT-F meets NFPA 72 for Remote Station Protective Signaling Service and Central Station Signaling Service reporting requirements for:
• the type of signal
• condition
• location of the reporting premises
42
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Normal Mode
Since higher priority events take precedence over lower priority events, the UDACT-F will transmit higher priority
events before sending the lower priority events. Priorities are as follows:
Event Activations
General Alarm
1.
Zone/Point Alarm #N
2.
General Supervisory
3.
Zone/Point Supervisory #N
4.
General System Trouble
5.
AC Power Loss
6.
Zone/Point Trouble #N
7.
Low Battery
8.
Telco Primary Line Fault
9.
Telco Secondary Line Fault
10.
NAC Fault Code
11.
Communication Trouble, Primary Number
12.
Communication Trouble, Secondary Number
13.
EIA-485 Communication Bus Trouble
14.
System Off Normal Code
15.
System Automatic Test Report
16.
System Abnormal Automatic Test Report
17.
Manual Activated Test Report
18.
Event Restorals
General Alarm Restoral
19.
Zone/Point Alarm #N Restoral
20.
General Supervisory Restoral
21.
Zone/Point Supervisory #N Restoral
22.
General System Trouble Restoral
23.
AC Power Loss Restoral
24.
Zone/Point Trouble #N Restoral
25.
Low Battery Restoral
26.
Telco Primary Line Fault Restoral
27.
Telco Secondary Line Fault Restoral
28.
NAC Fault Code Restoral
29.
Communication Trouble, Primary Number Restoral
30.
Communication Trouble, Secondary Number Restoral
31.
EIA-485 Communication Bus Trouble Restoral
32.
System Off Normal Code Restoral
33.
Note: #N represents the number of zones or devices in alarm or trouble. This is valid for all formats except
Ademco Contact ID.
For all formats, the 'general' reports are always transmitted (unless disabled). The zone or point information may follow the general report if enabled.
For all pulsed formats and both Ademco Express formats, the zone/point report is repeated per the total number of
zones or points activated once factory default entries of zero are removed. See Table 3-2 on page 34, Table 3-3 on
page 35, Table 3-4 on page 36, Table 3-5 on page 37, Table 3-6 on page 38 and Table 3-7 on page 39. When Ademco
Contact ID format is used, the actual zone or point activated is identified in the report.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
43
Type Mode
The UDACT-F is supplied factory programmed with the reports identified above as item numbers 2, 4, 7, 20, 22 and
25 set to zero, preventing the reports from being transmitted for the pulsed and Ademco Express formats. These
reports are factory programmed for active transmission when using the Ademco Contact ID.
4.1.4 Key Report Descriptions
UDACT-F Off Normal Report
Removing the UDACT-F from Normal Mode and placing it into Program or Troubleshoot Mode causes the transmission of a 'UDACT-F Off Normal' fault message. Returning the UDACT-F to Normal Mode causes a transmission of a
'UDACT-F Return to Normal' restoral message.
Panel Off Normal Report
The UDACT-F will report a 'System Off Normal' report when the host FACP temporarily shuts down the EIA-485
communications bus during various aspects of system programming or during Walktesting. When the host FACP is
returned to normal, restoring the fire protection, the UDACT-F will report a 'System Off Normal Restoral' report.
System Test Report
The UDACT-F will transmit a test message to both Central Stations at programmed intervals (typically every 24
hours). Should there exist an abnormal condition in the fire alarm system (such as an alarm, trouble or supervisory
condition) at the time when the test report is due to be transmitted, the UDACT-F will report the 'System Abnormal
Test Report'. If the system is normal, the report transmitted will be the normal 'System Test Report'.
EIA-485 Communications Trouble Report
The UDACT-F supervises the integrity of the information received from the FACP via the EIA-485 communications
bus. Should the communications bus malfunction, the UDACT-F transmits the report '485 Comm Trouble'. When the
communications bus returns to proper operation, the UDACT-F will report '485 Comm Trouble Restoral'.
4.2Type Mode
Type Mode may be used to disable reports by zone or point and to identify the specific functionality of each zone or
point in the system. Factory default for all zones/points is Fire Alarm. Use Type Mode to identify the function of
each zone or point as follows:
• General Fire Alarm
• Supervisory
• Pull Stations
• Heat Detectors
• Waterflows
• Duct Detectors
• Flame Sensor
•Smoke Zone
To access Type Mode, press the MODE key followed by the 4-digit code 8973 and then press the [ENTER/STORE]
key. The UDACT-F will display three digits. For example, initial entry will display 01 0.
44
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Type Mode
The characters to the left identify the zone or point number. In the preceding example, 01 identifies zone 01 or point
address 01. The character to the right (0 in this example) identifies the type of zone or point as defined in the
following:
0 = Zone or point defined as fire alarm
1 = Disable zone or point report
2 = Zone or point defined as supervisory
3 = Zone or point defined as pull station
4 = Zone or point defined as heat detector
5 = Zone or point defined as waterflow
6 = Zone or point defined as duct detector
7 = Zone or point defined as flame sensor
8 = Zone or point defined as smoke zone
(Use MMF-302 modules monitoring conventional smoke detectors. In point reporting, addressable
detectors automatically report as detectors eliminating the need for Type Mode entry).
Factory default is all zones or points set to '0' for fire alarm. Zone reporting allows the mixing of types of devices on
a single zone. To change the type definition of the zone or point from the factory default, select '2' to '8' corresponding to the type of device(s) used (do not mix device types for these settings), or select '1' to disable alarm reporting of
any zone or point. The digit entered will appear on the far right display. Next, press the [ENTER/STORE] key. This
stores the entry into E
2
memory and increments to the next higher address.
Use the Up arrow, Down arrow and 1st Event keys to move through the list of zones or points (refer to Appendices
D and E), similar to the method described in the programming section of this manual. For MS-9200 applications,
when address 56 is programmed as a '3' or '4' for point reporting, detectors are reported as points 001 to 099 and modules are reported as points 101 to 199. When address 56 is programmed as a '5' or '6' for code wheel matching point
reporting, detectors and modules report as 001 - 099 (the actual device address).
To define all zones or points as fire alarm (return to original factory default settings), enter zone or point 999 and then
press the [ENTER/STORE] key. The display will change to 01 0, indicating a return to the factory default settings.
4.2.1 Disabling of Zones or Points
This feature is primarily used when system points have been defined as remote reset, acknowledge, silence or drill
switches. Refer to the FACP technical manual for additional information. Activation of remote switches appear as
alarms on the EIA-485 bus while in point type of annunciation. The UDACT-F will report these points as fire alarm
points unless disabled in the Type Mode.
Disabling zones or points also prohibits the activation (shorted or alarm
activated condition) from being reported by the UDACT-F. Disabling of the zone or point does not affect the reporting of the zone or point trouble condition.
4.2.2 Zone or Point Supervisory
A zone or point must be defined as supervisory to allow the UDACT-F to identify the correct report to transmit to the
Central Station. Follow the programming instructions in the FACP manual to program a zone or point as supervisory.
Next program the zone or point as a code '2' for supervisory. Use the charts in the Appendices to enter point and zone
definitions. Note that the UDACT-F fire protection and reporting capabilities are inactive while in Type Mode.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
45
Troubleshoot Mode
4.3Troubleshoot Mode
To enter Troubleshoot Mode, press the MODE key. Enter the code 8768 and press the [ENTER/STORE] key.
®
☛ 8768 spells TROU on a Touch-Tone
Once in Troubleshoot Mode, the UDACT-F will:
• transmit the 'UDACT-F Off Normal' message to the Central Station(s)
• continue to communicate any events not yet acknowledged at the Central Station prior to entering
Troubleshoot Mode
The Up arrow, Down arrow and 1st Event keys do not function in this mode.
Telephone Line Testing
Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/STORE] causes seizure of the Primary phone line, which in turn, lights the red LED signifying Primary phone line active. After a delay of three seconds, the UDACT-F goes off-hook to acquire a dial tone.
The UDACT-F keypad may be used as a telephone touchpad for number dialing. Once the first digit is pressed, the
display will move the C or D character one position to the left, while placing the digit to be dialed on the farthest right
display position. Continue to enter the phone numbers to be dialed. Successive depressions of the [ENTER/STORE] key hangs up and picks up the phone (places the phone on or off the hook).
phone.
The secondary phone line may be tested by pressing the E key for touchtone dialing or the F key for rotary dialing
and then following the same procedure used for the primary phone line.
A handset may be temporarily connected across transformer T1 as indicated in Figure 4-2. The handset, when connected across T1, may be used only as an amplifier/speaker or telephone with the UDACT-F used for number dialing.
FIGURE 4-2:
Handset/Speaker Connection
Both Primary and Secondary Lines
4.4Lamp Test Mode
To perform a Lamp Test, press the MODE key and then enter the code 5267. Next, press the [ENTER/STORE] key
to test all system LEDs. The LEDs will stay on for five seconds, then the UDACT-F will return to Normal Mode.
®
phone.
46
☛ 5267 spells LAMP on a Touch-Tone
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Reporting Formats
Appendix AReporting Formats
Table A-1 shows the data reporting structure for each of the pulsed formats as well as the Ademco Express formats.
Ademco Express formats allow a typical data message to be transmitted to the Central Station in under five seconds.
Pulsed formats typically require 15 to 20 seconds in comparison. Table A-2 on page 48, defines each letter code used
in Table A-1 . Table A-3 on page 49, describes the data reporting structure used for Ademco Contact ID format.
TAB L E A - 1 : Data Reporting Structure
Format #
0, 2, 4, 6, 8
Report
AlarmSSS(S) ASSSS AA2
Alarm RestoreSSS(S) RASSSS RARA2
Zone Trouble
(Zone Open)
Zone Trouble RestoreSSS(S) RTZSSSS RTZRTZ2
System TroubleSSS(S) TSSSSS TSTS2
System Trouble RestoreSSS(S) RTSSSSS RTSRTS2
Low BatterySSS(S) LSSSS LL2
Low Battery RestoreSSS(S) RLSSSS RLRL2
AC LossSSS(S) PSSSS PP2
AC Loss RestoreSSS(S) RPSSSS RPRP2
Supervisory ConditionSSS(S) VSSSS VV2
Supervisory Condition RestoreSSS(S) RVSSSS RVRV2
3+1/4+1/Standard
4+1 Express
SSS(S) RTZSSSS TZTZ2
Format #
1, A, C
4+2/Standard
4+2 Express
Test ReportSSS(S) XSSSS XX2
Abnormal Test ReportSSS(S) XASSSS XAXA2
Notes:
Refer to Table A-2 on page 48, for an explanation of each letter code in Table A-1 .
Refer to Table B-1 on page 51, for a list of compatible receivers.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
47
Reporting Formats
TAB L E A - 2 :
Letter Code Definitions for Table A-1
Where:
SSS or SSSS=Subscriber ID
A=Alarm (1st digit)
A2=Alarm (2nd digit)
RA=Alarm Restore (1st digit)
RA2=Alarm Restore (2nd digit)
TZ=Zone Trouble (1st digit)
TZ2=Zone Trouble (2nd digit)
RTZ=Zone Trouble Restore (1st digit)
RTZ2=Zone Trouble Restore (2nd digit)
TS=System Trouble (1st digit)
TS2=System Trouble (2nd digit)
RTS=System Trouble Restore (1st digit)
RTS2=System Trouble Restore (2nd digit)
L=Low Battery (1st digit)
L2=Low Battery (2nd digit)
RL=Low Battery Restore (1st digit)
RL2=Low Battery Restore (2nd digit)
P=AC Loss (1st digit)
P2=AC Loss (2nd digit)
RP=AC Loss Restore (1st digit)
RP2=AC Loss Restore (2nd digit)
V=Supervisory Condition (1st digit)
V2=Supervisory Condition (2nd digit)
RV=Supervisory Condition Restore (1st digit)
RV2=Supervisory Condition Restore (2nd digit)
X=Test Report (1st digit)
X2=Test Report (2nd digit)
XA=Abnormal Test Report (1st digit)
XA2=Abnormal Test Report (2nd digit)
48
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
The reporting structure for the Ademco Contact ID format is as follows:
Reporting Formats
TAB L E A - 3 :
where
SSSS=Four digit Subscriber ID (addresses 17 - 20 and 43 - 46)
18=Identifies transmission of Contact ID to the receiver at the Central Station
Q=Event Qualifier
XYZ=Event code (shown in Table 3-4 on page 36 and Table 3-7 on page 39)
GG=Group number or Loop number
CCC=Zone or Sensor number
Ademco Contact ID Reporting Structure
SSSS 18 QXYZ GG CCC
E = New Event
R = New Restore
For general reports (alarm, trouble and supervisory), the GG and CCC fields are transmitted as 00 and 000 unless
changes to addresses 64 - 65 and 66 - 68 are made.
64 - 65 = Loop number (GG), factory default if 00
66 - 68 = Sensor number (CCC) for General Alarm, Fault or Supervisory messages - factory default is 000.
A typical printout of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows:
TimeDateRcvr/Line IDSSSSQXYZGGCCCC
11:2803/25117777E11000CCCC - general alarm
11:2803/25117777E11000C046 - alarm SD46
11:2803/25117777E30000CCCC - general trouble
11:2803/25117777E38000C046 - trouble SD46
11:2803/25117777R11000CCCC - general alarm restore
11:2803/25117777R11000C046 - alarm SD46 restore
11:2803/25117777R30000CCCC - general trouble restore
11:2803/25117777R38000C046 - trouble SD46 restore
Notes:
In the sample report, SD46 refers to smoke detector at address 46 or on zone 46. Refer to the charts on the fol-
1.
lowing page as well as “Point Assignments - MS-9200” on page 56 and “Code Wheel Matching Point Assignments - MS-9200” on page 57, for further clarification
, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
2. 18
alarm and trouble report
, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or
3. Q
R
for New Restore
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
49
Reporting Formats
Point Reporting
By using the Type Mode feature with address 56 set to 3, 4, 5 or 6, identification of each type of activated device is
possible. Note that addressable detectors report as code 111. It should also be noted that the meaning of the first digit
of the three digit zone/sensor number will depend on the Type Mode programmed in address 56 (i.e. Type 2, Device
address 1 in the tables below, when 5 or 6 is programmed in address 56, C001 will be reported for both modules and
detectors. When 3 or 4 is programmed in address 56, C101 will be reported for modules while C001 will be reported
for detectors). Module points are programmable.
The following table provides examples of reporting structures for addressable modules.
TAB L E A - 4 : Addressable Module Reporting Structure
Type ID#Activated Device
Module
Point
Report
Address 56 = 5 or 6
Report
Address 56 = 3 or 4
2Supervisory Alarm1E200 00 C001E200 00 C101
8
Smoke Zone Alarm
(conventional)
1
2E111 00 C002E111 00 C102
3Pull Station Alarm3E115 00 C003E115 00 C103
4Heat Sensor Alarm4E114 00 C004E114 00 C104
5Waterflow Alarm5E113 00 C005E113 00 C105
6
Duct Detector Alarm
(conventional)
1
6E116 00 C006E116 00 C106
7Flame Sensor Alarm7E117 00 C007E117 00 C107
.......................... through ........................
8
Use of M302 Monitor Module for conventional smoke and duct detectors
1.
99 relates to MS-9200; 159 and 259 relates to MS-9600
2.
Smoke Zone Alarm
(conventional)
1
99 or 159
2
E111 00 C099 or
E111 00 C159
2
E111 00 C259
E111 00 C199 or
The following table provides an example of the reporting structure for addressable smoke detectors.
Type IDActivated Device
Automatically set to
smoke detector (8)
300 or 350 Series
Detectors
Addressable
Detector Point #
001 to 099 or 159
Address 56 = 3, 4, 5 or 6
1
E111 00 C099 or E111 00 C159
Report
E111 00 C001 to
2
1
99 relates to MS-9200; 159 relates to MS-9600
1.
Zone Reporting
By using the Type Mode feature with address 56 set to 1 or 2, identification of the function of each software zone is
possible. The following table provides examples of zone reporting structures.
TAB L E A - 5 : Zone Reporting Structure
Type ID #Zone FunctionZone #Report
8Smoke Zone1E111 00 C001
5Waterflow Zone2E113 00 C002
2Supervisory Zone3E200 00 C003
3Pull Stations4E115 00 C004
............... through ...................
5Waterflow Zone
56 relates to MS-9200; 99 relates to MS-9600
1.
50
1
56 or 99
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
E113 00 C056 or
E113 00 C099
1
Appendix BCompatible Receivers
The chart below shows UL listed receivers compatible with the UDACT-F.
TAB L E B - 1 : Compatible UL Listed Receivers
Compatible Receivers
Format #
(Addresses 16 & 42)
04+1 Ademco Express
14+2 Ademco Express
23+1/Standard/1800/2300
3Not Used
43+1/Standard/1900/1400
5Not Used
64+1/Standard/1800/2300
7Not Used
84+1/Standard/1900/1400
9Not Used
A4+2/Standard/1800/2300
BNot Used
C4+2/Standard/1900/1400
DNot Used
EAdemco Contact ID
FNot Used
685 (1)
Ademco
Silent Knight
ITI
9000 (2)
CS-4000 (3)
FBI
CP220FB
Surguard
Radionics
6000/6500 (5)
Osborne Hoffmann
Quick Alert Models 1 & 2
3000R (7)
Linear/Sescoa
MLR-2 (9)
✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
(4)
(4)
(4)
(4)
(4)
(4)
(8)
✔✔
(5, 6)
✔✔
✔
✔✔✔
✔✔
(5)
✔✔
✔✔✔
✔✔
(5)
✔✔
✔✔✔
✔✔✔✔
(1) With 685-8 Line Card with Rev 4.4d software
(2) With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A software
(3) Rev. 4.0 software
(4) FBI CP220FB Rec-11 Line Card with Rev 2.6 software and a memory card with Rev 3.8 software
(5) Model 6500 with Rev 600 software
(6) Model 6000 with Rev 204 software
(7) With Rev B control card at Rev 1.4 software and Rev C line card at Rev 1.5 software
(8) Model 2 only
(9) Version 1.62 software
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
51
Programming Reference Sheets
Appendix CProgramming Reference Sheets
...To enter Programming Mode, press the
MODE
key, the code
and then the
7764
[ENTER/STORE]
key...
❐00❐01❐02❐03❐04❐05❐06❐07❐08❐09❐10❐11❐12❐13❐14❐
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number. Default all Fs
Primary Communication Format: Enter 0 - F.
❐
16
❐17❐18❐
19 ❐20
❐21❐22❐23❐
Primary Number Test Time Interval. Enter default '0' for 24 hr.; '1' for 12 hr.
❐
25
Primary Account Code: Valid entries are '0 - F'. Default is '0000'.
Primary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
24
❐26❐27❐28❐29❐30❐31❐32❐33❐34❐35❐36❐37❐38❐39❐40❐
Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number. Default all Fs
Secondary Communication Format: Enter 0 - F.
❐
42
❐43❐44❐45❐
❐47❐48❐49❐
Secondary Number Test Time Interval. Enter default '0' for 24 hr.; '1' for 12 hr.
❐
51
❐52❐
❐54❐
❐
56
receive only communication; '2' for zone reporting receive/transmit communication; '3' for point reporting receive
only communication; '4' for point reporting receive/transmit communication; '5' for code wheel matching reporting,
receive only; '6' for code wheel matching point reporting, receive/transmit.
Start Monitoring Address.
53
End Monitoring Address.
55
UDACT-F Communication Selection. Enter '0' to disable UDACT-F communication; '1' for zone reporting
Secondary Account Code: Valid entries are '0 - F'.
46
Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
50
15
41
Backup Reporting. Enter '0' to have secondary phone number act as backup only; '1' to have secondary phone
❐
57
number receive all reports and messages along with primary phone number.
Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.
❐
58
Make/Break Ratio. If rotary dialing is selected in Address 58; enter '0' for a 67/73 make/break ratio; '1' for a
❐
59
62/38 make/break ratio.
Leave default of '0'.
❐
60
Leave default of '0'
❐
61
AC Loss Delay. Enter '0' for no time delay after AC loss; '1' for 6 hours; '2' for 7 hours; '3' for 8 hours; '4' for
❐
62
9 hours; '5' for 10 hours; '6' for 11 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for
19 hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours. Default is '0'.
Host Panel ID. Enter '0' for MS-9200; ‘2’ for Sensiscan 2000; ‘5’ for MS-9600; all other entries are invalid.
❐
63
❐64❐
❐66❐67❐
Loop Number for General Reports. Factory set to '00'.
65
Sensor Number for General Reports. Factory set to '000'.
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number.
A
❐
16
000 0
❐17❐18❐
000 0
❐21❐22❐23❐
0
❐
25
FFF FFF FFF FFFFFFF
❐26❐27❐28❐29❐30❐31❐32❐33❐34❐35❐36❐37❐38❐39❐40❐
Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number.
A
❐
42
000 0
❐43❐44❐45❐
000 0
❐47❐48❐49❐
0
❐
51
01
❐52❐
01
❐54❐
0
❐
56
0
❐
57
0
❐
58
0
❐
59
0
❐
60
0
❐
61
1
❐
62
0
❐
63
00
❐64❐
000
❐66❐67❐
...To enter Programming Mode, press the
Primary Communication Format: (4+2 Standard, 1800/2300).
19 ❐20
Primary Number Test Time Interval. '0' for 24 hr.
Secondary Communication Format: (4+2 Standard, 1800/2300)
Secondary Number Test Time Interval. '0' for 24 hr.
Start Monitoring Address.
53
End Monitoring Address.
55
UDACT-F Communication Selection. '0' to disable UDACT-F communication.
Backup Reporting. '0' to have secondary phone number act as backup only.
Touchtone/Rotary Select. '0' for touchtone dialing.
Make/Break Ratio. '0' for a 67/73 make/break ratio.
Leave default of '0'.
Leave default of '0'
AC Loss Delay. '1' for 6 hour delay.
Host Panel ID. '0' for MS-9200.
Loop Number. For Ademco Contact ID, only loop number = '00'.
65
68
Primary Account Code:
Primary 24-Hour Test Time. 0000 = 12:00 midnight.
24
Secondary Account Code:
46
Secondary 24-Hour Test Time. 0000 = 12:00 midnight.
50
Sensor Number. For Ademco Contact ID, only sensor number = '000'.
MODE
key, the code
and then the
7764
[ENTER/STORE]
key...
15
41
54
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Programming Reference Sheets
Programming Reference Sheet Factory Default
11008100F1F60
❐69❐70❐71❐72❐73❐74❐75❐76❐77❐78❐79❐80❐
0 F8 F AF BFCFDF E
❐82❐83❐84❐85❐86❐87❐88❐89❐90❐91❐92❐93❐
FEFFFFE100E20
❐95❐96❐97❐98❐99❐
0E3E600E8EAEB
❐
❐
❐
❐
❐
108
ECEDEEEEEFEF9
❐
121
9919211008100
❐
134
F1F600F8FAFBF
❐
147
109
122
135
148
❐
❐
❐
❐
110
123
136
149
❐
❐
❐
❐
111
124
137
150
❐
❐
❐
❐
112
125
138
151
❐
❐
❐
❐
100
113
126
139
152
❐
❐
❐
❐
❐
101
114
127
140
153
❐
❐
❐
❐
❐
102
115
128
141
154
❐
❐
❐
❐
❐
103
116
129
142
155
❐
❐
❐
❐
❐
104
117
130
143
156
❐
❐
❐
❐
❐
105
118
131
144
157
❐
❐
❐
❐
❐
106
119
132
145
158
❐
❐
❐
❐
❐
81
94
107
120
133
146
159
CFDFEFEFFFFE1
❐
❐
❐
❐
❐
160
00E200E3E600E
❐
173
8EAEBECEDEEEE
❐
186
EFEF999192
❐
199
161
174
187
200
❐
❐
❐
❐
162
175
188
201
❐
❐
❐
❐
163
176
189
202
❐
❐
❐
❐
164
177
190
203
❐
❐
❐
❐
165
178
191
204
❐
❐
❐
❐
166
179
192
205
❐
❐
❐
❐
167
180
193
206
❐
❐
❐
❐
168
181
194
207
❐
❐
❐
❐
169
182
195
208
❐
❐
❐
170
183
196
❐
❐
❐
171
184
197
❐
❐
❐
172
185
198
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
55
Point Assignments - MS-9200
Appendix DPoint Assignments - MS-9200
(Program Address 56 = 3 or 4)
Use chart to carefully identify all points in the system. Leading zero (0) in point number signifies detectors and leading one (1) signifies modules. Take special precaution with any supervisory points and remote switches in the system.
Use Type Mode to match the function of remaining points in the system for proper reporting (see "Type Mode" on
page 44).
Use chart to carefully identify all points in the system. Take special precaution with any supervisory points and
remote switches in the system. Use Type Mode to match the function of remaining points in the system for proper
reporting (see "Type Mode" on page 44).
To disable or identify a zone or point in Type Mode (refer to “Type Mode” on page 44), the following Entries/
Addresses are used:
F.1.1 For Zone Identification:
Zones 1 - 99 are programmed by Entries/Addresses 01 - 99. The factory default code is 'fire alarm’ (see “Zone
Assignments” on page 64).
F.1.2 For Point Identification:
Loop 1, Modules 1 - 64 are programmed by Type Mode Entries/Addresses 001 - 064
Loop 2, Modules 1 - 64 are programmed by Type Mode Entries/Addresses 065 - 128
Loop 1, Modules 65 - 128 are programmed by Type Mode Entries/Addresses 129 - 192
Loop 2, Modules 65 - 128 are programmed by Type Mode Entries/Addresses 193 - 256
Loop 1, Modules 129 - 159 are programmed by Type Mode Entries/Addresses 257 - 287 (288 not used)
Loop 2, Modules 129 - 159 are programmed by Type Mode Entries/Addresses 289 - 319 (320 not used)
Loop 1, Detectors 1 - 64 are programmed by Type Mode Entries/Addresses 321 - 384
Loop 2, Detectors 1 - 64 are programmed by Type Mode Entries/Addresses 385 - 448
Loop 1, Detectors 65 - 128 are programmed by Type Mode Entries/Addresses 449 - 512
Loop 2, Detectors 65 - 128 are programmed by Type Mode Entries/Addresses 513 - 576
F.2Event Code/Report Transmission
Via Ademco Contact ID Format Only
F.2.1 For Zone Reporting:
Zones 1 - 99 report as zone numbers 01 - 99 (see “Zone Assignments” on page 64).
F.2.2 For Point Reporting:
Loop 1, Modules 1 - 64 report as device numbers 001 - 064
Loop 2, Modules 1 - 64 report as device numbers 065 - 128
Loop 1, Modules 65 - 128 report as device numbers 129 - 192
Loop 2, Modules 65 - 128 report as device numbers 193 - 256
Loop 1, Modules 129 - 159 report as device numbers 257 - 287 (288 is not used)
Loop 2, Modules 129 - 159 report as device numbers 289 - 319 (320 is not used)
Loop 1, Detectors 1 - 64 report as device numbers 321 - 384
Loop 2, Detectors 1 - 64 report as device numbers 385 - 448
Loop 1, Detectors 65 - 128 report as device numbers 449 - 512
Loop 2, Detectors 65 - 128 report as device numbers 513 - 576
Loop 1, Detectors 129 - 159 report as device numbers 577 - 607 (608 is not used)
Loop 2, Detectors 129 - 159 report as device numbers 609 - 639 (640 is not used)
58
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Point Assignments - MS-9600
F.3Point Assignments
Use chart to carefully identify all points in the system. Take special precaution with any supervisory or non-fire points
and remote switches in the system. Use Type Mode to match the function of remaining points in the system for proper
reporting (see "Type Mode" on page 44).
Type of Device:
Point
001033065097
002034066098
003035067099
004036068100
005037069101
006038070102
007039071103
008040072104
009041073105
010042074106
011043075107
012044076108
013045077109
014046078110
015047079111
016048080112
Module Loop 1Point
Type of Device:
Module Loop 1Point
Type of Device:
Module Loop 2Point
Type of Device:
Module Loop 2
017049081113
018050082114
019051083115
020052084116
021053085117
022054086118
023055087119
024056088120
025057089121
026058090122
027059091123
028060092124
029061093125
030062094126
031063095127
032064096128
Continued on the next page...
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
59
Point Assignments - MS-9600
Point Assignments continued:
Point
Type of Device:
Module Loop 1Point
Type of Device:
Module Loop 1Point
Type of Device:
Module Loop 2Point
129161193225
130162194226
131163195227
132164196228
133165197229
134166198230
135167199231
136168200232
137169201233
138170202234
139171203235
140172204236
141173205237
142174206238
143175207239
144176208240
Type of Device:
Module Loop 2
145177209241
146178210242
147179211243
148180212244
149181213245
150182214246
151183215247
152184216248
153185217249
154186218250
155187219251
156188220252
157189221253
158190222254
159191223255
160192224256
Continued on the next page...
60
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Point Assignments continued:
Point Assignments - MS-9600
Point
Type of Device:
Module Loop 1Point
Type of Device:
Module Loop 2Point
Type of Device:
Detector Loop1Point
257289321353
258290322354
259291323355
260292324356
261293325357
262294326358
263295327359
264296328360
265297329361
266298330362
267299331363
268300332364
269301333365
270302334366
271303335367
272304336368
Type of Device:
Detector Loop 1
273305337369
274306338370
275307339371
276308340372
277309341373
278310342374
279311343375
280312344376
281313345377
282314346378
283315347379
284316348380
285317349381
286318350382
287319351383
288Not Used320Not Used352384
Note: Addressable detectors on Loops 1 and 2 may be disabled using Type Mode. The Event Code cannot be altered.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
Continued on the next page...
61
Point Assignments - MS-9600
Point Assignments continued:
Point
Type of Device:
Detector Loop 2Point
Type of Device:
Detector Loop 2Point
Type of Device:
Detector Loop1Point
385417449481
386418450482
387419451483
388420452484
389421453485
390422454486
391423455487
392424456488
393425457489
394426458490
395427459491
396428460492
397429461493
398430462494
399431463495
400432464496
Type of Device:
Detector Loop 1
401433465497
402434466498
403435467499
404436468500
405437469501
406438470502
407439471503
408440472504
409441473505
410442474506
411443475507
412444476508
413445477509
414446478510
415447479511
416448480512
Note: Addressable detectors on Loops 1 and 2 may be disabled using Type Mode. The Event Code cannot be altered.
62
Continued on the next page...
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Point Assignments continued:
Point Assignments - MS-9600
Point NoType of Device:
Detector Loop 2
Point NoType of Device:
Detector Loop 2
Point NoType of Device:
Detector Loop1
Point NoType of Device:
513545577609
514546578610
515547579611
516548580612
517549581613
518550582614
519551583615
520552584616
521553585617
522554586618
523555587619
524556588620
525557589621
526558590622
527559591623
528560592624
Detector Loop 2
529561593625
530562594626
531563595627
532564596628
533565597629
534566598630
535567599631
536568600632
537569601633
538570602634
539571603635
540572604636
541573605637
542574606638
543575607639
544576608Not Used640Not Used
Note: Addressable detectors on Loops 1 and 2 may be disabled using Type Mode. The Event Code cannot be altered.
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
63
Zone Assignments
Appendix GZone Assignments
Use chart to carefully identify all zones in the system. Take special precaution with any supervisory or non-fire zones
in the system. Use Type Mode to match the function of remaining points in the system for proper reporting (see "Type
Mode" on page 44).
ZoneZone FunctionZoneZone FunctionZoneZone Function
013467
023568
033669
043770
053871
063972
074073
084174
094275
104376
114477
124578
134679
144780
154881
164982
175083
185184
195285
205386
215487
225588
235689
245790
255891
265992
276093
286194
296295
306396
316497
326598
336699
64
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Document #50049 Rev. E0 01/22/01 P/N 50049:E0
65
66
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Limited Warranty
The manufacturer warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service. Products
are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer
is to repair or replace, at its option, free of charge for parts and labor, any part which is
defective in materials or workmanship under normal use and service. For products not under
the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of
original purchase by the manufacturer's distributor unless the installation instructions or catalog
sets forth a shorter period, in which case the shorter period shall apply. This warranty is void
if the product is altered, repaired, or serviced by anyone other than the manufacturer or its
authorized distributors, or if there is a failure to maintain the products and systems in which
they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our customer service department. Return product, transportation
prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its
products. The manufacturer does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they are
installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes
no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse,
abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER
NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S
PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR
AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the
manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.
LimWarLg.p65 01/10/2000
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.