Fire-Lite SLC User Manual

Intelligent Control Panel
SLC
Wiring Manual
Document 51309 10/12/2011 Rev:
P/N 51309:P1 ECN 11-788
P1
2 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Table of Contents

Section 1: Introduction.............................................................................................................8
1.1: Scope..............................................................................................................................................................8
1.1.1: Reference Documentation ...................................................................................................................9
1.2: Overview......................................................................................................................................................10
1.3: Polling Protocols .........................................................................................................................................10
1.3.1: Available Protocols............................................................................................................................10
1.3.2: Protocol Use ......................................................................................................................................10
1.4: Devices ........................................................................................................................................................11
1.4.1: Isolator Module..................................................................................................................................11
1.4.2: Monitor Modules ...............................................................................................................................11
1.4.3: Control Modules................................................................................................................................11
1.4.4: Relay Modules...................................................................................................................................11
1.4.5: Multiple Input/Output Modules.........................................................................................................11
1.4.6: Intelligent Detectors ..........................................................................................................................11
1.4.7: Manual Pull Station ...........................................................................................................................12
1.4.8: 300 Series Addressable Devices........................................................................................................12
1.5: SLC Capacity...............................................................................................................................................12
1.6: SLC Performance.........................................................................................................................................13
1.7: Surge Suppression........................................................................................................................................13
1.8: LED Operation.............................................................................................................................................13
Section 2: Wiring Requirements............................................................................................14
2.1: Wire Sizing ..................................................................................................................................................14
2.1.1: CLIP (Classic Loop Interface Protocol) Mode..................................................................................14
2.1.2: LiteSpeed Mode.................................................................................................................................14
2.2: Measuring Resistance & Length..................................................................................................................15
2.2.1: Two-Wire SLC - Style 4 (Class B)....................................................................................................15
2.2.2: Four-Wire SLC Style 6 & 7 (Class A) ..............................................................................................16
2.3: Shield Wire Termination ..............................................................................................................................17
2.4: Control Panel Terminal Blocks....................................................................................................................18
2.4.1: MS-9200 ............................................................................................................................................18
2.4.2: MS-9600, MS-9600LS, & MS-9600UDLS.......................................................................................18
2.4.3: MS-9200UDLS (Software Version 3.0)............................................................................................19
2.4.4: MS-9200UD & MS-9200UDLS (Versions 1 and 2) .........................................................................19
2.4.5: MS-9050UD ......................................................................................................................................20
Section 3: SLC Circuits without Isolators ............................................................................21
3.1: Overview......................................................................................................................................................21
3.2: NFPA Style 4 SLC .......................................................................................................................................21
3.3: NFPA Style 6 SLC .......................................................................................................................................22
Section 4: SLC Circuits with Isolators.................................................................................. 23
4.1: Fault Isolator Devices ..................................................................................................................................23
4.1.1: Isolating an SLC Branch....................................................................................................................23
4.1.2: Wiring an Isolator Module ................................................................................................................23
4.2: NFPA Style 4 SLC Using Isolator Modules ................................................................................................24
4.3: NFPA Style 6 SLC Using Isolator Modules ................................................................................................25
4.4: NFPA Style 7 SLC Using Isolator Modules ................................................................................................26
Section 5: Monitor Modules................................................................................................... 27
5.1: Descriptions .................................................................................................................................................27
5.1.1: Addressable Monitor Modules ..........................................................................................................27
5.1.2: Zone Interface Modules.....................................................................................................................29
5.1.3: Dual Monitor Module........................................................................................................................31
5.1.4: Mini Monitor Module........................................................................................................................31
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 5
Table of Contents
5.2: Installation....................................................................................................................................................31
5.2.1: Setting an SLC address for a Single Point Module ...........................................................................32
5.2.2: Setting an SLC address for a Multi-Point Module ............................................................................33
5.3: MMF-300 Wiring Diagrams ........................................................................................................................34
5.3.1: Wiring a NFPA Style B IDC with an MMF-300...............................................................................34
5.3.2: Wiring a NFPA Style D IDC with an MMF-300 ..............................................................................35
5.3.3: MMF-300 Wiring for Emergency Alarm System Applications ........................................................36
5.4: MMF-300-10 Wiring Diagrams...................................................................................................................37
5.4.1: Wiring a NFPA Style B IDC with an MMF-300-10 .........................................................................37
5.4.2: Wiring a NFPA Style D IDC with an MMF-300-10 .........................................................................38
5.5: MDF-300 Wiring Diagrams.........................................................................................................................39
5.5.1: Wiring a NFPA Style B IDC with an MDF-300 ...............................................................................39
5.6: MMF-302 Wiring Diagrams ........................................................................................................................40
5.6.1: Wiring a NFPA Style B IDC with an MMF-302...............................................................................40
5.6.2: Wiring a NFPA Style D IDC with an MMF-302 ..............................................................................41
5.7: MMF-302-6 Wiring Diagrams.....................................................................................................................42
5.7.1: Wiring a NFPA Style B IDC with an MMF-302-6 ...........................................................................42
5.7.2: Wiring a NFPA Style D IDC with an MMF-302-6 ...........................................................................43
Section 6: Control Modules ...................................................................................................44
6.1: Description...................................................................................................................................................44
6.2: CMF-300 Installation...................................................................................................................................44
6.2.1: Setting an SLC address for a CMF-300 Module ...............................................................................44
6.2.2: Wiring a Notification Appliance Circuit (NAC) with a CMF-300....................................................44
6.3: Wiring a CMF-300 Module .........................................................................................................................45
6.3.1: Wiring a Style Y NAC (Two-Wire) with Addressable Control Modules .........................................45
6.3.2: Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules .........................................46
6.4: CMF-300-6 Installation ...............................................................................................................................46
6.4.1: Cabinet Installation............................................................................................................................46
6.4.2: Setting an SLC address for an CMF-300-6 Module ..........................................................................46
6.4.3: Setting NACs as Style Y or Style Z...................................................................................................47
6.4.4: Disabling Unused Module Addresses................................................................................................47
6.4.5: Short Circuit Protection .....................................................................................................................47
6.4.6: Features Not Supported .....................................................................................................................48
6.4.7: Circuit Board Information .................................................................................................................48
6.5: Wiring a CMF-300-6 Module......................................................................................................................49
6.5.1: Wiring a Style Y NAC (Two-Wire) .................................................................................................49
6.5.2: Wiring a Style Z NAC (Four-Wire)...................................................................................................50
Section 7: Relay Modules ...................................................................................................... 51
7.1: Description...................................................................................................................................................51
7.2: CRF-300 Installation & Wiring ...................................................................................................................51
7.2.1: Setting an SLC address for a CRF-300 Module ................................................................................51
7.2.2: Wiring a CRF-300 Module (Form-C Relay) ....................................................................................51
7.3: CRF-300-6 Circuit Board Information .......................................................................................................52
7.4: CRF-300-6 Installation & Wiring................................................................................................................52
7.4.1: Cabinet Installation............................................................................................................................52
7.4.2: Setting an SLC address for a CRF-300-6 Module.............................................................................53
7.4.3: Disabling Unused Module Addresses................................................................................................53
7.4.4: Wiring a CRF-300-6 Module (Form-C Relay)..................................................................................53
Section 8: Multiple Input/Output Modules............................................................................ 54
8.1: Description...................................................................................................................................................54
8.2: CDRM-300 Installation & Wiring ...............................................................................................................54
8.2.1: Setting an SLC address for a CDRM-300 Module ............................................................................54
8.2.2: Wiring a CDRM-300 Module (Form-C Relay) ................................................................................55
6 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Table of Contents
Section 9: Intelligent Detector Bases....................................................................................56
9.1: Description...................................................................................................................................................56
9.2: Installation and Wiring ................................................................................................................................56
9.2.1: Setting the Detector Address .............................................................................................................56
9.2.2: Wiring a Detector Base......................................................................................................................57
9.2.3: Wiring an Isolator Base .....................................................................................................................58
9.2.4: Wiring a Relay Base..........................................................................................................................58
9.2.5: Wiring a Sounder Base......................................................................................................................59
Section 10: Addressable Manual Pull Station...................................................................... 60
10.1: Description.................................................................................................................................................60
10.2: Installation .................................................................................................................................................60
10.2.1: Setting an SLC address....................................................................................................................60
10.2.2: Wiring a Manual Pull Station ..........................................................................................................60
Appendix A: Power Considerations...................................................................................... 61
A.1: Supplying Power to 24 VDC Detectors and NACs ....................................................................................61
A.1.1: Resistance and Size...........................................................................................................................61
A.2: Supervising 24 VDC Power........................................................................................................................62
Appendix B: Surge Suppression...........................................................................................64
B.1: Introduction.................................................................................................................................................64
B.2: Installation...................................................................................................................................................64
B.2.1: Wiring Diagram for MS-9200 ..........................................................................................................65
B.2.2: Wiring Diagram for MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, and
MS-9050UD ................................................................................................................................................66
Appendix C: Terminal Conversion Charts for New & Legacy Devices.............................. 67
C.1: CRF-300......................................................................................................................................................67
C.2: CMF-300 and MMF-302 ............................................................................................................................68
C.3: MMF-300 ....................................................................................................................................................69
C.4: MDF-300.....................................................................................................................................................70
Appendix D: Intelligent Detector Base Layouts for Legacy Devices................................. 71
D.1: B350LP or B501 Detector Base..................................................................................................................71
D.2: B224BI Isolator Base.................................................................................................................................72
D.3: B224RB Relay Base ...................................................................................................................................72
D.4: B501BH(-2) and B501BHT(-2) Sounder Bases .........................................................................................73
Appendix E: Canadian Versions of SLC Devices ................................................................74
Index........................................................................................................................................ 76
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 7

1.1 Scope

CMF-300
Legacy Version Module
(Vertical Rotary Dial)
CMF-300
Newer Version Module
(Horizontal Rotary Dial)

Section 1: Introduction

This document describes the operation, installation and wiring of various Signaling Line Circuit (SLC) devices when used with the Fire-Lite MS-9200/MS-9200E, MS-9600/MS-9600E, MS­9600LS/MS-9600LSC/MS-9600LSE, MS-9600UDLS/MS-9600UDLSE, MS-9200UD/MS­9200UDE, MS-9200UDLS/MS-9200UDLSE/MS-9200UDLSC, and MS-9050UD/MS­9050UDC/MS-9050UDE control panels. It also provides basic information that applies to Fire•Lite SLC loops in general, such as the branch resistance measurements.
NOTE: Any reference in this manual to the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600UDLS, or MS-9050UD includes the MS-9200E, MS-9200UDE, MS-9200UDLSE, MS-9200UDLSC, MS-9600E, MS-9600LSE, MS-9600LSC, MS-9600UDLSE, MS-9050UDC, or MS-9050UDE respectively unless otherwise specified.
Additional information about the specific control panel and the modules and detectors referenced in this document can be found in the respective installation manual as listed in Table 1.1, “Reference Documentation,” on page 10.
Currently, there are two styles of modules available, legacy version and newer version. The obvious difference between the two styles is the orientation of the rotary dials. Refer to the diagram below for an example of each.
NOTE: Only the MMF-300, MMF-302, CRF-300, CMF-300, and MDF-300 modules are available as newer type modules. Both the legacy and newer versions share the same part numbers. The newer version modules will be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the modules. Refer to “Terminal Conversion Charts for New & Legacy Devices” on page 67 for additional information.
8 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Scope Introduction
Currently, there are two styles of detector bases available, legacy version and newer version. The obvious difference between the two styles is the orientation of the screw terminals. Refer to Section 9 and Appendix D for an illustration of each.
NOTE: Only the B501 Detector Base, B210LP Detector Base (replacement base for B350LP), B224RB Relay Base, and B224BI Isolator Base are available as newer type bases. Both the legacy and newer versions share the same part numbers. The newer version bases will be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the bases. Refer to “Intelligent Detector Base Layouts for Legacy Devices” on page 71 for additional information.

1.1.1 Reference Documentation

The table below accommodates a list of document sources containing additional information regarding the devices used on a Signaling Line Circuit:
For information on... Refer to... Part Number
MS-9200/MS-9200E Instruction Manual 51003
MS-9600/MS-9600E Instruction Manual 51335
MS-9200UD/MS-9200UDE Instruction Manual 51906
MS-9200UDLS/MS-9200UDLSE/MS-9200UDLSC Instruction Manual 52750
MS-9600LS/MS-9600LS(C/E) & MS-9600UDLS/MS9600UDLSE Instruction Manual 52646
MS-9050UD/MS-9050UDC/MS-9050UDE Instruction Manual 52413
Compatible Devices Device Compatibility Document 15384
BG-12LX Pull Station Installation Instructions I56-3655
MMF-300 Monitor Module Installation Instructions I56-1191 / I56-3653
MMF-300-10 Monitor Module Installation Instructions I56-1873
MMF-301 Mini Monitor Module Installation Instructions I56-1193 / I56-3654
MMF-302 Monitor Module Installation Instructions I56-1192 / I56-3652
MMF-302-6 Interface Module Installation Instructions I56-1900
MDF-300 Dual Monitor Module Installation Instructions I56-0013 / I56-3665
CMF-300 Control Module Installation Instructions I56-1189 / I56-3650
CMF-300-6 Control Module Installation Instructions I56-1874
CRF-300 Relay Module Installation Instructions I56-1190 / I56-3651
CRF-300-6 Relay Module Installation Instructions I56-1875
CDRM-300 Multiple Input/Output Module Installation Instructions I56-3726
I300 Isolator Module Installation Instructions I56-1381
AD350 Multicriteria Detector Installation Instructions F300-17-00
AD355 Multicriteria Detector Installation Instructions I56-3660
SD350 & SD350T Photo Detector Installation Instructions I56-0035
SD355 & SD355T Photo Detector Installation Instructions I56-3660
CP350 Ionization Detector Installation Instructions I56-0036
CP355 Ionization Detector Installation Instructions I56-3656
H350 Heat Detector Installation Instructions I56-0038
H350R Heat Detector w/ROR Installation Instructions I56-0037
H355 Heat Detector (135
H355R Heat Detector w/ROR Installation Instructions I56-3657
H355HT Heat Detector (190
D350P Duct Detector Installation Instructions F300-10-00
D350PL(A) Duct Detector - low flow Installation Instructions I56-1975
D350RP Duct Detector w/Relay Installation Instructions I56-0047
D350RPL(A) Duct Detector w/Relay - low flow Installation Instructions I56-1974
D355PL Duct Detector - low flow Installation Instructions I56-3255
°) Installation Instructions I56-3657
°) Installation Instructions I56-3657
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 9
Introduction Overview
For information on... Refer to... Part Number
BEAM355(S) Addressable Beam Detector Installation Instructions I56-2425
B210LP Plug-in Detector Base Installation Instructions I56-3739
B501 Detector Base Installation Instructions I56-0357 / I56-3738
B501BH Sounder Detector Base Installation Instructions I56-0491
B501BH-2 Sounder Detector Base Installation Instructions I56-2813
B501BHT Temporal Sounder Detector Base Installation Instructions I56-1367
B501BHT-2 Temporal Sounder Detector Base Installation Instructions I56-2819
B200SR Sounder Detector Base Installation Instructions I56-3387
B224RB Relay Detector Base Installation Instructions I56-2815 / I56-3737
B224BI Isolator Detector Base Installation Instructions I56-0725 / I56-3736
Table 1.1 Reference Documentation

1.2 Overview

Communication between the control panel and intelligent addressable monitor and control devices takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of NFPA Style 4, Style 6, or Style 7.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to “Surge Suppression” on page 64.

1.3 Polling Protocols

The MS-9200UDLS, MS-9600LS, and MS-9600UDLS support LiteSpeed protocol or Classic Loop Interface Protocol (CLIP). The MS-9200/E, MS-9600/E, MS-9200UD/E, and MS-9050UD support Classic Loop Interface Protocol (CLIP) only.

1.3.1 Available Protocols

LiteSpeed is a communication protocol that greatly enhances the speed of communication between analog intelligent devices. Only the MS-9200UDLS, MS-9600LS, and MS-9600UDLS are capable of operating in LiteSpeed mode. This is the default mode of operation for these FACPs.
CLIP (Classic Loop Interface Protocol) polls devices in sequential order. All Fire-LiteFireWarden addressable fire alarm control panels can operate in CLIP mode. This is the default mode of operation for all other FACPs.

1.3.2 Protocol Use

Use one of the following options with LiteSpeed/CLIP mode:
1. Program all modules and detectors on an FACP as LiteSpeed.
2. Program all modules and detectors on an FACP as CLIP.
NOTE: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP mode of operation. Communication protocols cannot be split between SLC loops.
When switching between polling protocols, the loop circuit must be powered down for at least 30 seconds to reset the devices.
10 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Devices Introduction

1.4 Devices

1.4.1 Isolator Module

The I300 Isolator Module permits a zone of detectors and modules to be fault isolated from the remainder of the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator modules are required to meet the requirements of an NFPA Style 7 circuit.

1.4.2 Monitor Modules

Addressable modules that allow the control panel to monitor entire circuits of conventional alarm initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and supervisory devices.
MMF-300 - Monitors a Style B (Class B) or Style D (Class A) circuit of dry-contact input devises.
MMF-300-10 - Monitors ten (10) Style B (Class B) or five (5) Style D (Class A) normally open
contact device circuits.
MMF-301 - Same as the MMF-300 except offered in a smaller package for mounting with Style B wired devices. This module does not have an LED.
MMF-302 - Monitors a single IDC of two-wire smoke detectors.
MMF-302-6 - An addressable module that provides an interface between the control panel and six
(6) Style B (Class B) or three (3) Style D (Class A) IDCs of two-wire smoke detectors.
MDF-300 - Similar to MMF-300, but provides for two independent Style B IDCs.

1.4.3 Control Modules

Through the CMF-300 addressable control module, the control panel can selectively activate a Notification Appliance Circuit (NAC).
CMF-300-6 - Similar in operation to the CMF-300, except it can activate six (6) Style Y (Class B) or three (3) Style Z (Class A) NACs.

1.4.4 Relay Modules

The CRF-300 addressable relay module provides the control panel with a dry-contact output for activating a variety of auxiliary devices.
CRF-300-6 - Similar in operation to the CRF-300, except it provides six (6) Form-C relays.

1.4.5 Multiple Input/Output Modules

The CDRM-300 addressable multiple input/output module monitors two (2) Style B input devices and provides two (2) independent Form-C relay contacts.

1.4.6 Intelligent Detectors

AD350 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its detection parameters and alarm threshold depending on the ambient conditions it samples in its environment.
AD355 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its detection parameters and alarm threshold depending on the ambient conditions it samples in its environment.
CP350 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle’.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 11
Introduction SLC Capacity
CP355 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle’.
D350P - An addressable photoelectric duct detector. The D350RP includes an alarm relay. Air velocity rating is 500 to 4,000 feet per minute.
D350PL -An addressable low flow photoelectric duct detector (D350PLA for Canada). The D350RPL includes an alarm relay (D350RPLA for Canada). Low Flow refers to the air velocity
rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
D355PL - An addressable non-relay photoelectric low flow smoke detector. Low Flow refers to the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
1
H350
- An addressable detector using a thermistor sensing circuit for fast response. H350R
incorporates a thermal rate of rise of 15°F (9.4°C)/minute.
1
H355
- An addressable 135° fixed temperature heat detector using a thermistor sensing circuit for
fast response. H355R incorporates a thermal rate of rise of 15° F (9.4° C)/minute.
H355HT
1
- An addressable 190° fixed temperature heat detector using a thermistor sensing circuit
for fast response.
SD350 - An addressable photoelectric smoke detector which provides smoke sensing utilizing optical sense technology. The SD350T includes a 135° F fixed thermal sensor.
SD355 - An addressable photoelectric smoke detector which provides smoke sensing utilizing optical sense technology. The SD355T includes a 135° F fixed thermal sensor. The SD355R is a low profile, intelligent, photoelectric sensor that is remote test capable.
BEAM355 - An addressable long range projected beam smoke detector designed to provide open area protection. The BEAM355S has an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics.
DNR(W) - Innovair Flex, intelligent, non-relay, low flow, photoelectric duct detector housing. This requires the SD355R photoelectric smoke detector. Accomodates the installation of the CRF­300 relay module. The DNRW is a watertight housing.

1.4.7 Manual Pull Station

The BG-12LX is a dual-action pull station that, when activated, provides an addressable identification and its location to the control panel. An addressable monitor module is mounted inside the pull station to facilitate servicing and replacement.

1.4.8 300 Series Addressable Devices

Fire•Lite’s 300 Series of addressable devices are fully compatible with the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS(C/E), MS-9600UDLS/E, and MS-9050UD FACPs. The devices must be configured for CLIP (Classic Loop Interface Protocol) Mode operation. The address of 300 series devices cannot be set above 99. Compatible devices include:
• SD300 Photo • M300 Monitor Module
• SD300T Photo w/Thermal • M301 Mini Monitor Module
• CP300 Ionization • M302 2-wire Monitor Module
• BG-10LX Pull Station • C304 Control/Relay Module

1.5 SLC Capacity

The protocol selected for an SLC loop determines the maximum number of devices that can be handled by the loop. See Section 1.3, “Polling Protocols”, on page 10. Within those limits, the individual control panel may have additional restrictions. See the specific installation manual for this information.
1. Addressable Heat Detectors are not compatible with the MS-9200(E).
12 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
SLC Performance Introduction

1.6 SLC Performance

SLC performance depends on the type of circuit (Style 4, Style 6, or Style 7) and the components on the circuit.
NOTE: SLC operation meeting Style 7 requirements isolates each device on the SLC from faults that may occur within other areas of the SLC.
Wiring style requirements are determined by national and local codes. Consult with the Authority Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-1999) lists the trouble conditions that result when a fault exists on an SLC.
Type of Fault Style 4 Style 6 Style 7
Single Open Trouble Alarm, Trouble Alarm, Trouble
Single Ground Alarm, Trouble (ground) Alarm, Trouble (ground) Alarm, Trouble (ground)
Short Trouble Trouble Alarm, Trouble
Short and open Trouble Trouble Trouble
Short and ground Trouble Trouble Alarm, Trouble
Open and ground Trouble Alarm, Trouble Alarm, Trouble
Communications loss Trouble Trouble Trouble
• Trouble - The control panel will indicate a trouble condition for this type of fault.
• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.

1.7 Surge Suppression

One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to “Surge Suppression” on page 64.

1.8 LED Operation

The table below lists the LED operation on the various devices on an SLC.
Device Standby Activated
Monitor Module Control Module Detector
Table 1.2 SLC Performance
Blinks RED Blinks GREEN Blinks RED
Steady RED Steady GREEN Steady RED
Table 1.3 LED Operation
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 13

Section 2: Wiring Requirements

2.1 Wire Sizing

The SLC requires use of a specific wire type, depending on the mode of operation, to ensure proper circuit functioning. Wire size should be no smaller than 18 AWG (0.75 mm AWG (3. 2 5 mm
2
) wire. The wire size depends on the length of the SLC circuit. It is recommended
2
) and no larger than 12
that all SLC wiring be twisted-pair to minimize the effects of electrical interference.

2.1.1 CLIP (Classic Loop Interface Protocol) Mode

All addressable FACPs can operate in CLIP (Classic Loop Interface Protocol) mode. It is recommended that all SLC wiring be twisted-pair and shielded when operating in CLIP mode to reduce the effects of electrical interference. Use the table below to determine the specific wiring requirements for the SLC.
Wire Requirements Distance in Feet (meters) Wire Size Wire Type
2
) Belden 9583, Genesis 4410,
Signal 98230, WPW D999
2
) Belden 9581, Genesis 4408,
Signal 98430, WPW D995
2
) Belden 9575, Genesis 4406, &
4606, Signal 98630, WPW D991
2
) Belden 9574, Genesis 4402 &
4602, Signal 98300, WPW D975
Twisted-pair, shielded
10,000 feet (3,048 m) 12 AWG (3.1 mm
8,000 feet (2,438 m) 14 AWG (2.0 mm
4,875 feet (1,486 m) 16 AWG (1.3 mm
3,225 feet (983 m) 18 AWG (0.75 mm
MS-9200 = 1,000 feet (305 m)
Untwisted, unshielded wire, inside conduit or not in conduit

2.1.2 LiteSpeed Mode

Wire Requirements Distance in Feet (meters) Wire Size Wire Type
Twisted-pair, unshielded
MS-9600, MS-9600LS(C) & MS-9600UDLS = 3,000 feet (914 m)
MS-9200UD & MS-9200UDLS = 3,000 feet (914
m)
MS-9050UD = 3,000 feet (914 m)
12 to 18 AWG
Table 2.1 SLC Wiring Requirements in CLIP Mode
The MS-9200UDLS, MS-9600LS, and MS-9600UDLS SLC can be programmed to operate in LiteSpeed mode for a quicker device response time. While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference. Use the following table to determine the specific wiring requirements for the SLC.
10,000 feet (3,048 m) 12 AWG (3.1 mm
8,000 feet (2,438 m) 14 AWG (2.0 mm
4,875 feet (1,486 m) 16 AWG (1.3 mm
3,225 feet (983 m) 18 AWG (0.75 mm
2
) Belden 5020UL & 6020UL,
Genesis WG-4315 & WG-4515
2
) Belden 5120UL & 6120UL,
Genesis WG-4313 & WG-4513
2
) Belden 5220UL & 6220UL,
Genesis WG-4311 & WG-4511
2
) Belden 5320UL & 6320UL,
Genesis WG-4306 & WG-4506
Table 2.2 SLC Wiring Requirements in LiteSpeed Mode
14 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Measuring Resistance & Length Wiring Requirements
SLC-meas1.wmf
SLC Out
Branch
Short Point
Figure 2.1 Measuring DC Resistance of a Two-Wire SLC
Branch A Branch B
Branch C
SLC-meas2.wmf
SLC Terminal Block
Figure 2.2 Measuring the Total Wire Length - Two-Wire SLC

2.2 Measuring Resistance & Length

2.2.1 Two-Wire SLC - Style 4 (Class B)

Loop Resistance
T-tapping of the SLC wiring is permitted for 2-wire Style 4 configurations. The total DC resistance from the control panel to each branch end cannot exceed 40 ohms. Measure DC resistance as detailed and shown below:
1. With power removed, short the termination point of one branch at a time and measure the DC resistance from the beginning of the SLC to the end of that particular branch.
2. Repeat this procedure for all remaining branches in the SLC.
Total Wire Length
The total wire length of all combined branches of one SLC cannot exceed the limits set forth in each system’s instruction manual. Determine the total length in each SLC by summing the wire lengths of all branches of one SLC.
In the following figure, the total length of the SLC is determined by adding the lengths of Branch A plus Branch B plus Branch C.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 15
Wiring Requirements Measuring Resistance & Length
SLC-meas3.wmf
SLC Out
SLC Return
Short Point
Figure 2.3 Measuring DC Resistance of a Four-Wire SLC
B+ B– A– A+
SLC-meas4.wmf
SLC channel B (output loop)
SLC channel A
(return loop)
SLC Terminal Block
Figure 2.4 Measuring the Wire Length – Four-Wire SLC

2.2.2 Four-Wire SLC Style 6 & 7 (Class A)

Loop Resistance
The total DC resistance of the SLC pair cannot exceed 40 ohms. Measure DC resistance as detailed and shown below.
1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.
2. Short the two leads of SLC channel A (Return).
3. Measure the resistance across the SLC channel B (Out) leads.
Total Wire Length
The total wire length in a four-wire SLC cannot exceed the limits set forth in each system’s instruction manual. The figure below identifies the output and return loops from SLC terminal on the control panel:
16 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Shield Wire Termination Wiring Requirements
!
Cabinet
SLC-shieldterm.wmf
Shield Drain Wire
Shield Foil
Conduit
MS-9600 MS-9600LS MS-9600UDLS MS-9200UD MS-9200UDLS MS-9050UD
MS-9200
Figure 2.5 Shield Termination

2.3 Shield Wire Termination

The drawing below shows the method of proper termination of the shield.
Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire through the conduit, into the control box. The shield drain wire must be connected to the “shield” terminal on the SLC terminal block.
NOTE: Use of good wiring practice consistent with local electrical codes is expected.
CAUTION: DO NOT LET THE SHIELD DRAIN WIRE OR THE SHIELD FOIL TOUCH THE SYSTEM CABINET OR BE CONNECTED TO EARTH GROUND AT ANY POINT.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 17
Wiring Requirements Control Panel Terminal Blocks
TB6
SHIELD SLC SLC
TB4
SLC-9200tb.wmf
SLC Return
SLC Out
Connections for wire shield
Unregulated Power
Nonresettable Power
Resettable Power
Figure 2.6 MS-9200 Terminal Blocks
TB8
SHIELDSLC SLC SLC SLC
TB3
SLC Return
SLC Out
Connections for wire shield
Nonresettable Power
Resettable Power
SLC-9600tb.wmf
Figure 2.7 MS-9600 Series Terminal Blocks

2.4 Control Panel Terminal Blocks

The terminal blocks on the control panel circuit board that concern the SLC circuit are described below. For more information on this subject refer to the control panel’s Instruction Manual.

2.4.1 MS-9200

TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable.
TB6 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).

2.4.2 MS-9600, MS-9600LS, & MS-9600UDLS

TB3 provides two types of 24 VDC power; Nonresettable and Resettable.
TB8 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules) while operating in CLIP mode. 318 addresses are available per loop (159 detectors and 159 modules) while operating in LiteSpeed mode.
18 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Control Panel Terminal Blocks Wiring Requirements
TB10
SLC
TB1
SLC Out
Connections for wire shield
Resettable Power­jumper selectable by JP6
Nonresettable Power- jumper selectable by JP4
SLC-9200udtb.wmf
SLC Return
Figure 2.8 MS-9200UDLS (Rev 3) Terminal Blocks
TB10
SLC
TB1
SLC Out
Connections for wire shield
Resettable Power
Nonresettable Power
SLC-9200udtb.wmf
SLC Return
Figure 2.9 MS-9200UD & MS-9200UDLS (Rev 1 & 2) Terminal Blocks

2.4.3 MS-9200UDLS (Software Version 3.0)

TB1 provides two types of 24 VDC power; Nonresettable and Resettable, jumper selectable by JP4 and JP6.
TB10 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).

2.4.4 MS-9200UD & MS-9200UDLS (Versions 1 and 2)

TB1 provides two types of 24 VDC power; Nonresettable and Resettable.
TB10 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 19
Wiring Requirements Control Panel Terminal Blocks
SLC Out
Connections for wire shield
SLC-9050udtb.wmf
SLC Return
Figure 2.10 MS-9050UD Terminal Block

2.4.5 MS-9050UD

24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8.
TB2 provides connections for the SLC wiring.
50 addresses are available (any combination of detectors and modules).
20 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Section 3: SLC Circuits without Isolators

SLC-style4.wmf
Two-wire Addressable Detector
Addressable Module
T-tapped Circuits
Control Panel SLC
B+ B–
Figure 3.1 Basic NFPA Style 4 SLC

3.1 Overview

This chapter concerns itself with the two styles of circuits that do not require isolation devices:
NFPA Style 4
NFPA Style 6

3.2 NFPA Style 4 SLC

NFPA Style 4 requirements can be met by using the diagram below.
T-tapping of the SLC wiring is allowed for Style 4 configuration.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 21
SLC Circuits without Isolators NFPA Style 6 SLC
Control Panel SLC
Two-wire Addressable Detector
Addressable Module
SLC-style6.cdrwmf
SLC Return
SLC Out
B+ B– A– A+
Figure 3.2 Basic NFPA Style 6 SLC

3.3 NFPA Style 6 SLC

NFPA Style 6 requirements can be met by using the diagram below.
T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.
22 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Section 4: SLC Circuits with Isolators

!
(-)
(+)
(-)
(+)
SLC
Isolated branch
of the SLC
SLC-isowire2.wmf
Continuation of the SLC
OUT
OUT
IN
IN
Figure 4.1 Wiring an I300 Module

4.1 Fault Isolator Devices

There are two isolator devices used to protect critical elements of the SLC from faults on other SLC branches or segments.
Fault Isolator Module I300
Isolator Detector Base B224BI
A Fault Isolator Module on both sides of a device, or the combination of Isolator Base and Isolator Module is required to comply with NFPA Style 7 requirements.
CAUTION: MAXIMUM ADRESSABLE DEVICES
If relay or sounder bases are not used, a maximum of 25 addressable devices can be
connected between Isolator Modules and/or Bases. When relay or sounder bases are used, the maximum number of addressable devices that can be connected between Isolators is reduced to seven. Isolator modules will not function properly when these limits are exceeded.
When more than 100 Isolator Modules are connected to an SLC loop, the address capacity
of the loop is reduced by two (2) addresses for every isolator device in excess of 100.

4.1.1 Isolating an SLC Branch

The module continuously monitors the circuit connected to terminals 3(–) and 4(+). Upon power­up, an integral relay is latched on. The module periodically pulses the coil of this relay. A short cir­cuit on the SLC resets the relay. The module detects the short and disconnects the faulted SLC branch or segment by opening the positive side of the SLC (terminal 4). This isolates the faulty branch from the remainder of the loop preventing a communication problem with all other address­able devices on the remaining branches (labeled “Continuation of the SLC” in the figure below). During a fault condition, the control panel registers a trouble condition for each addressable device which is isolated on the SLC segment or branch. Once the fault is removed, the module automati­cally reapplies power to the SLC branch or segment.

4.1.2 Wiring an Isolator Module

The figure below shows typical wiring of an Isolator Module:
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 23
SLC Circuits with Isolators NFPA Style 4 SLC Using Isolator Modules
Figure 4.2 NFPA Style 4 SLC Using Isolator Modules
Two-wire Addressable Detector
Addressable Pull Station
SLC-style4iso.wmf
Control Panel SLC
B– B+
Isolated Branch
Isolator Module
Isolator Module
Isolator Module
Isolated Branch
Isolated Branch

4.2 NFPA Style 4 SLC Using Isolator Modules

A variation of a Style 4 operation using isolator modules to protect each branch of the SLC is shown below. Refer to Figure 4.1 for I300 wiring and to Section 4.1 for limitations.
24 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
NFPA Style 6 SLC Using Isolator Modules SLC Circuits with Isolators
Figure 4.3 NFPA Style 6 SLC Using Isolator Modules
SLC Out SLC Return
SLC-style6iso.wmf
Control Panel
Two-wire Addressable Detector
Section B
Section C
Section A
Isolator Module
Isolator Module
Isolator Module
Additional isolator module required when first device in the
section is more than 20 feet from the control panel.
Isolator Module
Isolator Module
Isolator Module
Addressable
Pull Station

4.3 NFPA Style 6 SLC Using Isolator Modules

A variation of Style 6 operation using isolator modules to protect a section of the SLC. By flanking each group of devices with an I300 fault isolator module each group is protected from faults that may occur in the other groups. For example, a fault in Section B will not effect Sections A & C. The isolator modules on either side of Section B will open the loop. Section A will still operate from power on the SLC Out side and Section C will operate from the SLC Return side.
A combination of isolator modules and isolator bases may be used.
T-tapping is NOT allowed within the Style 6 configuration.
Isolator modules shall be within 20 feet (6.1 meters) of device and must be enclosed in metal conduit.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 25
SLC Circuits with Isolators NFPA Style 7 SLC Using Isolator Modules
2
1
3
4
3
4
3
4
1
3
1
32121
SLC-style7iiso.wmf
SLC Out
SLC Return
Two-Wire Addressable Detector
Addressable
Pull Station
Control Panel
Two-wire
Addressable
Detector
Figure 4.4 NFPA Style 7 SLC Using Isolator Modules
Isolator Module
Isolator Module
Isolator Module
Isolator Module
Isolator Module
Isolator Module
Isolator Module
Isolator Module

4.4 NFPA Style 7 SLC Using Isolator Modules

Style 7 operation requires using isolator modules (or a combination of isolator modules and isolator bases) before and after each device. Flanking each device with an isolator provides fault protection to all other devices on the loop.
T-tapping is NOT allowed within the Style 7 wiring configuration.
When a detector base or pull station is used, install isolator modules on both sides of the device.
Connections between isolator modules and the device they isolate must be “close-nippled” conduit, within 3 feet (91.44 cm).
26 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Section 5: Monitor Modules

SLC– SLC+
IDC Return – IDC Return +
IDC Out +
IDC Out -
Rotary Switches
Areas used to record the device
address and SLC number.
FMMtpH.wmf
Figure 5.1 MMF-300 Monitor Module

5.1 Descriptions

These addressable modules monitor conventional contact-type alarm initiating devices. You can configure module circuits as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Cir­cuits (IDC). There is no limit to the number of contact-type devices installed on a monitor module circuit.
NOTE: For more information on the individual module specifications refer to the Installation Instructions that are provided with these devices.

5.1.1 Addressable Monitor Modules

MMF-300 Monitor Module
This is an addressable module that monitors either a Style B (Class B) or Style D (Class A) circuit of dry-contact input devices. This module is capable of participating in degraded mode where sup­ported by the FACP.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 27
Monitor Modules Descriptions
Disable Address
Place shunt in: Disable 1 position to disable highest module address Disable 2 position to disable highest two module addresses
Style Y or Style Z Select
Remove shunt for Style Z circuits
SLC Address
Set rotary switches to base (first) address of modules
Figure 5.2 MMF-300-10 Monitor Module
m
m
f
-
3
0
0
-
1
0
.
w
m
f
MMF-300-10 Monitor Module
This is an addressable monitor module intended to interface between the FACP and up to ten (10) Style B (Class B) or five (5) Style D (Class A) IDCs containing normally open contact devices.
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into a cabinet.
28 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Descriptions Monitor Modules
FZMtpH.wmf
Rotary Switches
SLC– SLC+
24 VDC –
24 VDC + IDC Return – IDC Return +
IDC Out +
IDC Out -
Areas used to record the device
address and SLC number.
Figure 5.3 MMF-302 Interface Module

5.1.2 Zone Interface Modules

MMF-302 Module
Similar to the MMF-300, this module is used to monitor a single IDC of UL listed compatible two­wire 24 volt conventional smoke detectors. Refer to the Device Compatibility Document.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 29
Monitor Modules Descriptions
– +
– +
T6
J1
BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2
BASE ADDRESS +3
BASE ADDRESS +4 BASE ADDRESS +5
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T1
T0
T2
T3
T4
T5
SW1
BASE ADDRESS
0
1
2
3
4
5
6
7 8
9
10
11
13
14
15
12
0
1
2
3
4
5
6
7 8
9
– +
– +
– +
– +
– +
– +
– +
– +
Disable Address
Place shunt in: Disable 1 position to disable highest module address Disable 2 position to disable highest two module addresses
Style Y or Style Z Select
Remove shunt for Style Z circuits
SLC Address
Set rotary switches to base (first) address of modules
Figure 5.4 MMF-302-6 Interface Module
MMF-302-6 Interface Module
This monitor module is intended to interface between the FACP and a conventional alarm system with up to six (6) Style B (Class B) or three (3) Style D (Class A) IDCs containing normally open contact devices.
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.
30 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Installation Monitor Modules
fmmtph.wmf
Rotary Switches
SLC–
SLC+
9 H– 8 H+
7L+ 6L–
Address +1
{
Base Address {
Areas used to record the device
address and SLC number.
Figure 5.5 MDF-300 Dual Monitor Module
FMM-101.wmf
Label – Use to record the device address and SLC number.
Rotary Switches
IDC (+)
IDC (-)
SLC (+)
SLC (-)
Figure 5.6 MMF-301 Mini Monitor Module

5.1.3 Dual Monitor Module

MDF-300 Module
The MDF-300 is similar to the MMF-300 but provides for two independent 2-wire IDCs at two separate, consecutive addresses.

5.1.4 Mini Monitor Module

MMF-301 Monitor Module
The MMF-301 is functionally and electrically identical to an MMF-300, but is offered in a smaller package for mounting directly in the electrical box of the Style B (Class B) device being monitored.

5.2 Installation

When installing any of these modules DO NOT mix the following services that the IDC provides:
Fire alarm service
Automatic and manual waterflow alarm service with normally open contact devices
Sprinkler supervision with normally open contact devices
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 31
Monitor Modules Installation
TENS
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
ONES
8
9
0
1
2
3
4
5
6
7
Breakaway Tab - Modules come with
a raised breakaway tab on the TENS
rotary switch. This tab must be
removed when the module is on an FACP that uses more than 99 addresses.
SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
Dual monitor modules: On dual monitor modules, only even numbers appear on the ONES rotary switch. The module takes both the selected address and the next-higher address.
Modules with
Rotary Switches
in vertical
position
Modules with Rotary
Switches in
horizontal position
Figure 5.7 Setting an SLC Address on a Single Point Module

5.2.1 Setting an SLC address for a Single Point Module

Each module can be set to one of 159 addresses (01-159) and is factory preset with an address of “00”.
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS­9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS­9600UDLS can support module addresses 01 - 159. The plastic stop located on the Tens switch must be removed to set addresses above 99.
To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired address. The module below is set at “35”. When finished, mark the address on the module face in the place provided.
32 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Installation Monitor Modules
0
1
2
3
4
5
6
7 8
9
10
11
13
14
15
12
0
1
2
3
4
5
6
7 8
9
multroty.wmf
Rotary Switches
Plastic Stop
TENS
ONES
Figure 5.8 Setting an SLC Address on a Multi-Point Module

5.2.2 Setting an SLC address for a Multi-Point Module

The SLC address of a multi-point module is set in the same fashion as a single-point module.
In Class B operation, each MMF-300-10, MMF-302-6, CMF-300-6, and CRF-300-6 module is set to a base address. The remaining module points are automatically assigned to the next higher SLC addresses. For example, if the base address of a MMF-300-10 is set to 28, the next module points will be addressed to 29, 30, 31, 32, 33, 34, 35, 36 and 37.
In Class A operation, alternate module points are paired together, resulting in a total of five module points. For example, if the base address of a MMF-300-10 is set to 28, then 30, 32, 34 and 36 will be automatically assigned to the remaining module points and 29, 31, 33, 35 and 37 are available for use by other modules.
NOTE: The MS-9050UDNFW-50 can support addresses 01 - 50. The MS-9200, MS-9200UD and MS-9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-9600UDLS can support module addresses 01 - 159 (the plastic stop located on the Tens switch must be removed to set addresses above 99).
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. The module below is set at “28”.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 33
Monitor Modules MMF-300 Wiring Diagrams
47K ELR (supplied with module)
Heat detector
SLC
MMF-300
IDC
24 VDC Power Filtered, Regulated, Resettable
24 VDC Four-wire Detector Base
Manual pull station
From Supply
To Next IDC or Supervision Device
SLC-idcB1tpH.wmf
Figure 5.9 Typical Style B IDC Wiring with an MMF-300

5.3 MMF-300 Wiring Diagrams

Following are wiring diagrams that depict NFPA Style B (Class B) and D (Class A) Initiating Device Circuits (IDCs) using MMF-300 monitor modules.
The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamperes @ 24 VDC (nominal).

5.3.1 Wiring a NFPA Style B IDC with an MMF-300

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an MMF-300 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See “Power Considerations” on page 61 for information on supervising 24 VDC power.
34 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
MMF-300 Wiring Diagrams Monitor Modules
SLC-idcD1tpH.wmf
24 VDC Four-wire Detector Base
Heat detector
SLC
MMF-300
IDC
24 VDC Power Filtered, Regulated, Resettable
From Supply
To Next IDC or Supervision Device
Manual pull station
Figure 5.10 Typical Style D IDC Wiring with an MMF-300

5.3.2 Wiring a NFPA Style D IDC with an MMF-300

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using an MMF-300 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See “Power Considerations” on page 61 for information on supervising 24 VDC power.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 35
Monitor Modules MMF-300 Wiring Diagrams
++-
-
47K ELR (supplied
with module)
SLC
MMF-300 Module
programmed for Tornado,
Hazard, or Medical operation.
Refer to the control panel
installation manual.
IDC
UL-listed Signaling applicance such as the Fire-Lite FSS-2400E
SLC-emer.wmf
Figure 5.11 Emergency Signaling Wiring with an MMF-300

5.3.3 MMF-300 Wiring for Emergency Alarm System Applications

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.
The figure below shows typical wiring for a supervised and power-limited Emergency Signaling circuit using an MMF-300 module.
See “Power Considerations” on page 61 for information on supervising 24 VDC power.
See Section 6, “Control Modules” for instructions on using control modules as NACs on an SLC.
For compatible output devices refer to the Device Compatibility Document #15384.
36 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
MMF-300-10 Wiring Diagrams Monitor Modules
24 VDC Power Filtered, Regulated, Resettable
24 VDC Four-wire Detector Base
Manual Pull
Station
Heat
Detector
MMF-300-10
SLC
47K ELR (supplied with module)
IDC Out
SLC-idcB4.wmf
Figure 5.12 Typical Style B IDC Wiring with an MMF-300-10

5.4 MMF-300-10 Wiring Diagrams

Following are wiring diagrams that depict NFPA Style B (Class B) and D (Class A) Initiating Device Circuits (IDCs) using MMF-300-10 monitor modules.
The Initiating Device Circuit (IDC) is supervised and current-limited to 1.0 milliampere @ 24 VDC (nominal).

5.4.1 Wiring a NFPA Style B IDC with an MMF-300-10

Connect the SLC wiring to the module terminals T5 as shown below.
Use the rotary switches on the module to set the base SLC address. Each module takes ten addresses on the SLC. The remaining module points are automatically assigned to the next nine higher addresses. Refer to “Setting an SLC address for a Multi-Point Module” on page 33.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS­9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an MMF-300-10 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See “Power Considerations” on page 61 for information on supervising 24 VDC power.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 37
Monitor Modules MMF-300-10 Wiring Diagrams
24 VDC Power Filtered, Regulated, Resettable
24 VDC Four-wire Detector Base
Manual Pull
Station
Heat
Detector
IDC Out
MMF-300-10
SLC
IDC
Return
SLC-idcD3.cdwmf
Figure 5.13 Typical Style D IDC Wiring with an MMF-300-10

5.4.2 Wiring a NFPA Style D IDC with an MMF-300-10

Connect the SLC wiring to the module terminals T5 as shown below.
Use the rotary switches on the module to set the base SLC address. Each module takes five alternat­ing addresses on the SLC. The remaining module points are automatically assigned to the next four higher addresses. (Example: 28, 30, 32, 34 and 36). Refer to “Setting an SLC address for a Multi­Point Module” on page 33.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS­9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using an MMF-300-10 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See “Power Considerations” on page 61 for information on supervising 24 VDC power.
38 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
MDF-300 Wiring Diagrams Monitor Modules
T11
T10
T9 T8 T7 T6
T1 T2 T3 T4 T5
SLC-idcB3fdm1tph.wmf
Heat Detector
Manual Pull Station
SLC
MDF-300
Base +1 Address (IDC Circuit H)
Base Address (IDC Circuit L)
47K ELR
47K ELR
Manual Pull Station
Figure 5.14 Typical Style B IDC Wiring with an MDF-300

5.5 MDF-300 Wiring Diagrams

Following is a wiring diagrams that depict NFPA Style B (Class B) Initiating Device Circuits (IDCs) using MDF-300 Dual Monitor Modules.

5.5.1 Wiring a NFPA Style B IDC with an MDF-300

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Use the rotary switches on the module to set it to the SLC address. Each dual module takes two addresses on the SLC. Circuit ‘L’ corresponds to the address set on the rotary switches, which will be an even number. Circuit ‘H’ will automatically respond to the next higher address, which will be an odd number. Use caution to avoid duplicate addressing of modules on the system. Refer to “Set­ting an SLC address for a Single Point Module” on page 32.
Each IDC (H & L) is power limited to 230 microamperes @ 24 VDC.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an MDF-300-10 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See “Power Considerations” on page 61 for information on supervising 24 VDC power.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 39
Monitor Modules MMF-302 Wiring Diagrams
SLC
IDC
SLC-idcB2tpH.wmf
MMF-302
Two-wire smoke detectors
3.9K ELR (supplied with module)
24 VDC Resettable power.
90 mA External 24 volt
supply required
Figure 5.15 Typical Style B IDC Wiring with an MMF-302

5.6 MMF-302 Wiring Diagrams

Following are wiring diagrams that concern NFPA Style B (Class B) and D (Class A) Initiating Device Circuits (IDCs) using MMF-302 Zone Interface Modules.

5.6.1 Wiring a NFPA Style B IDC with an MMF-302

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.
The IDC is supervised and power limited to 230 microamperes @ 24 VDC.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an MMF-302 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the module.
See “Power Considerations” on page 61 for information on 24 VDC power.
40 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
MMF-302 Wiring Diagrams Monitor Modules
SLC
Two-wire smoke detectors
3.9K ELR (supplied with module)
IDC
MMF-302
SLC-idcD2tpH.wmf
24 VDC Resettable power. 90 mA External 24 volt supply required
Figure 5.16 Typical Style D IDC Wiring with an MMF-302

5.6.2 Wiring a NFPA Style D IDC with an MMF-302

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using an MMF-302 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the module.
See “Power Considerations” on page 61 for information on 24 VDC power.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 41
Monitor Modules MMF-302-6 Wiring Diagrams
Two-wire smoke detectors
IDC Out
MMF-302-6
24 VDC resettable power
3.9K ELR (supplied with module)
SLC-idcB5.wmf
SLC
Figure 5.17 Typical Style B IDC Wiring with an MMF-302-6

5.7 MMF-302-6 Wiring Diagrams

Following are wiring diagrams that concern NFPA Style B (Class B) and D (Class A) Initiating Device Circuits (IDCs) using MMF-302-6 monitor modules.

5.7.1 Wiring a NFPA Style B IDC with an MMF-302-6

Connect the SLC wiring to the module terminals T0 as shown below.
Use the rotary switches on the module to set the base SLC address. Each module takes six addresses on the SLC. The remaining module points are automatically assigned to the next five higher addresses. Refer to “Setting an SLC address for a Multi-Point Module” on page 33.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS­9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an MMF-302-6 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the module.
See “Power Considerations” on page 61 for information on 24 VDC power.
42 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
MMF-302-6 Wiring Diagrams Monitor Modules
+
+
+
– +
– +
SLC-idcD4.wmf
Two-wire smoke detectors
24 VDC resettable power
MMF-302-6
IDC Out
SLC
IDC
Return
Figure 5.18 Typical Style D IDC Wiring with an MMF-302-6

5.7.2 Wiring a NFPA Style D IDC with an MMF-302-6

Connect the SLC wiring to the module terminals T0 as shown below.
Use the rotary switches on the module to set it to the SLC addresses. Each module takes three alter­nating addresses on the SLC. The remaining module points are automatically assigned to the next two higher addresses. (Example: 28, 30 and 32). Refer to “Setting an SLC address for a Multi­Point Module” on page 33.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS­9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using an MMF-302-6 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the module.
See “Power Considerations” on page 61 for information on 24 VDC power.
+
T2
+
T1
T0
+
+
T3
+
+
+
T4
+
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 43
When using a Control Module as a Notification Appliance Circuit (NAC), the isolation described in
FCMFZMtph.wmf
NOTE: Module polarities are shown in alarm condition.
Style Z NAC (+) Style Z NAC (–)
Style Y/Z NAC (–) Style Y/Z NAC (+)
24 VDC Nonresettable Power (–) 24 VDC Nonresettable Power (+)
SLC (–)
SLC (+)
Figure 6.1 CMF-300 Wiring Connections
the section titled Section 4, “SLC Circuits with Isolators” which begins on page 23, is required or Riser Conductors must be installed in accordance with the survivability from attack by fire require­ments in National Fire Alarm Code, NFPA 72.

6.1 Description

The CMF-300 and CMF-300-6 modules are addressable modules that can be used for monitoring and switching 24 VDC Notification Appliance Circuit (NAC) power for NFPA Style Y (Class B) and NFPA Style Z (Class A) circuits.
Ratings for the relay contacts on the module are:
Load Description Application Maximum Voltage Current Rating
Resistive Non-Coded 30 VDC 3.0 A
Resistive Coded 30 VDC 2.0 A
Resistive Non-Coded 110 VDC 0.9 A
Resistive Non-Coded 125 VAC (CMF-300)
Inductive (L/R = 5ms) Coded 30 VDC 0.5 A
Inductive (L/R = 2ms) Coded 30 VDC 1.0 A
Inductive (PF = 0.35) Non-Coded 125 VAC (CMF-300)

Section 6: Control Modules

0.9 A
70.7 VAC (CMF-300-6)
0.5 A
70.7 VAC (CMF-300-6)
NOTE: For more information on module specifications, refer to the Installation Instructions provided with these devices.

6.2 CMF-300 Installation

6.2.1 Setting an SLC address for a CMF-300 Module

Each module is factory preset with an address of “00”. To set an SLC address refer to “Setting an SLC address for a Single Point Module” on page 32.

6.2.2 Wiring a Notification Appliance Circuit (NAC) with a CMF-300

The figure below shows the connections to wire a module for powering a 24 VDC NAC:
44 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Wiring a CMF-300 Module Control Modules
CMF-300
NAC
24 VDC Nonresettable power
SLC
SLC-nacY.wmf
Note: Module polarities are shown in alarm condition
NOTE: A power
supervision relay is required only on the last module of the power run.
ELR
47K, 1/2-watt
24 VDC Notification
Appliances
Figure 6.2 NFPA Style Y Notification Appliance Circuit

6.3 Wiring a CMF-300 Module

This section contains instructions and diagrams for wiring a Signaling Line Circuit with a CMF-300 as a Notification Appliance Circuit (NAC).

6.3.1 Wiring a Style Y NAC (Two-Wire) with Addressable Control Modules

A supervised and power-limited NFPA Style Y (Class B) NAC using a CMF-300 module. Polar­ized alarm notification appliances are shown connected to the module in a two-wire configuration. Refer to the Device Compatibility Document for compatible notification appliances and relays.
See “Power Considerations” on page 61 for information on monitoring 24 VDC power.
Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Y circuit.
Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt, P/N SSD A2143-00 (ELR-47K in Canada).
Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each device.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 45
Control Modules CMF-300-6 Installation
24 VDC notification appliances
CMF-300
NAC Out
24 VDC Nonresettable power
SLC
SLC-nacZtpH.wmf
NAC Return
Note: Module polarities are shown in alarm condition.
NOTE: A power supervision relay is required only
on the last module of the power.
Figure 6.3 NFPA Style Z Notification Appliance Circuit

6.3.2 Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules

A supervised and power-limited NFPA Style Z (Class A) NAC using a CMF-300 module. Polarized alarm notification appliances are shown connected to the module in a four-wire configuration.
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and relays.
See “Power Considerations” on page 61 for information on monitoring 24 VDC power.
Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Z circuit.
Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each device.

6.4 CMF-300-6 Installation

6.4.1 Cabinet Installation

This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.

6.4.2 Setting an SLC address for an CMF-300-6 Module

In “Style Y” operation each CMF-300-6 module can be set to one of 154 base addresses (01-154). The remaining module points are automatically assigned to the next five higher SLC addresses. For example, if the base address is set to 28, the next five module points will be addressed to 29, 30, 31, 32 and 33.
46 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
CMF-300-6 Installation Control Modules
J1
A/B SELECT
DISABLE 1
DISABLE 2
DISABLE 3
SLC-disable1.wmf
In “Style Z” operation alternate module points are paired together, resulting in a total of three mod­ule points. For example, if the base address is set to 28, then 30 and 32 will be automatically assigned to the remaining module points and 29, 31 and 33 are available to be used for other mod­ules on the SLC.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for the MS-9200, MS­9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS­9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS can support module addresses 01 - 159.
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. See Figure 6.4 on page 48.
NOTE: For use with the MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the stop on the upper rotary switch.

6.4.3 Setting NACs as Style Y or Style Z

To use this module for Style Y (Class B) operation ascertain that a small shunt is installed on the “A/B SELECT” set of pins. (As shipped).
To use this module for Style Z (Class A) operation remove the small shunt from the “A/B SELECT” set of pins. See drawing below and Figure 6.4 on page 48.

6.4.4 Disabling Unused Module Addresses

A shunt is used, in conjunction with a pin block, to disable a maximum of three (3) unused module addresses. If two module addresses are disabled, the lowest four addresses will be functional, while the highest two will be disabled. For example, if the shunt is placed on ‘DISABLE 2’ and the base address is set to 28, the module addresses will be assigned to 28, 29, 30 and 31.
In Style Z operation, placing a small shunt on ‘DISABLE 3’ will disable all three addresses. Placing it on ‘DISABLE 2’ will disable two out of three addresses.
To disable addresses, securely place one of the supplied small shunts onto the desired set of pins. See drawing and Figure 6.4 on page 48.

6.4.5 Short Circuit Protection

Protection is disabled for each module address when there is a large shunt installed on the corre­sponding pins of the pin block (as shipped, all six addresses are disabled).
When enabled, the module will not switch power supply if a short circuit condition exists on a NAC.
To enable “Short Circuit Protection” for an address, remove the large shunt from the corresponding pins of the pin block. See Figure 6.4 on page 48. Place unused shunts on single pin to store on board for future use.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 47
Control Modules CMF-300-6 Installation
CMF-300-6.wmf
Synchronization Generator -
Not Supported. DO NOT remove shunts.
Power Supply Monitors -
Not Supported. DO NOT remove shunts.
Disable Address -
Place shunt onto required pins.
Select
Style Y (Class B) or
Style Z (Class A) -
Remove shunt for Style Z (Class A).
Short Circuit Protection - Remove shunt from the corresponding pins to enable. Shunt #1 for first address, #2 for second address, etc.
#1 #2 #3 #4 #5 #6
SLC Address
Set rotary switches to address required.
Status Indicators
Green LEDs are controlled by FACP to indicate status of each module address.
Figure 6.4 CMF-300-6 Control Module Settings

6.4.6 Features Not Supported

The “Synchronization” and “Power Supply Monitoring” features are not supported at this time.

6.4.7 Circuit Board Information

48 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Wiring a CMF-300-6 Module Control Modules
+
+
– +
– +
– +
– +
– +
– +
– +
– +
– +
– +
– +
– +
T10
T1
+1
+2
+3
+4
+5
T0 +0
T2
T3
T4
T5
T11
T12
T13
T14
T15
T16
24 VDC notification appliances
NAC Out
24 VDC nonresettable power
SLC-nacY2.wmf
Power Supervision Relay (EOLR-1)
SLC
CMF-300-6
ELR 47K, 1/2-watt
Relay Connector Assembly
Figure 6.5 NFPA Style Y Notification Appliance Circuit

6.5 Wiring a CMF-300-6 Module

This section contains basic instructions and diagrams for wiring a Signaling Line Circuit with a CMF-300-6 as a Notification Appliance Circuit (NAC).
For more detailed information on wiring a CMF-300-6 Control Module refer to the Installation Instructions provided with the module. Included in these instructions are wiring diagrams concern­ing a single power supply being shared by multiple NACs and audio NAC configurations.

6.5.1 Wiring a Style Y NAC (Two-Wire)

A supervised and power-limited NFPA Style Y (Class B) NAC with a single power supply dedi­cated to a single NAC using a CMF-300-6 module. Polarized alarm notification appliances are shown connected to the module in a two-wire configuration.
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and relays.
See “Power Considerations” on page 61 for information on monitoring 24 VDC power.
Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Y circuit.
Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt, P/N SSD A2143-00 (ELR-47K in Canada).
Do not loop wiring under the screw terminals of any notification appliance. To maintain super­vision, break the wire run at each device.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 49
Control Modules Wiring a CMF-300-6 Module
Power Supervision Relay (EOLR-1)
24 VDC notification appliances
24 VDC nonresettable power
NAC
Out
CMF-300-6
NAC
Return
SLC
SLC-nacZ3.cwmf
Power Supply Jumper
Relay Connector Assembly
Figure 6.6 NFPA Style Z Notification Appliance Circuit

6.5.2 Wiring a Style Z NAC (Four-Wire)

A supervised and power-limited NFPA Style Z (Class A) NAC with a single power supply dedi­cated to a single NAC using a CMF-300-6 module. Polarized alarm notification appliances are shown connected to the module in a four-wire configuration.
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and relays.
See “Power Considerations” on page 61 for information on monitoring 24 VDC power.
Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Z circuit.
Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each device.
50 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

7.1 Description

SLC
SLC-frmCtpH.wmf
CRF-300
NO
C
NC
NO
C
NC
Figure 7.1 CRF-300 Wiring Connections
The CRF-300 and the CRF-300-6 modules are addressable modules that provides Form-C relay contacts.
Ratings for the relay contacts on the module are:

Section 7: Relay Modules

Load Description Application
Resistive Non-Coded 30 VDC 3.0 A
Resistive Coded 30 VDC 2.0 A
Resistive Non-Coded 110 VDC 0.9 A
Resistive Non-Coded 125 VAC 0.9 A
Inductive (L/R = 5ms) Coded 30 VDC 0.5 A
Inductive (L/R = 2ms) Coded 30 VDC 1.0 A
Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A
Inductive (PF = 0.35) Non-Coded 125 VAC 0.5 A
NOTE: For more information on the module specifications refer to the Installation Instructions provided with these devices.

7.2 CRF-300 Installation & Wiring

7.2.1 Setting an SLC address for a CRF-300 Module

Each module is factory preset with an address of “00”. To set an SLC address, refer to “Setting an SLC address for a Single Point Module” on page 32.
Maximum
Vol tag e
Current
Rating

7.2.2 Wiring a CRF-300 Module (Form-C Relay)

The figure below shows a CRF-300 module wired to the Control Panel:
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 51
Relay Modules CRF-300-6 Circuit Board Information
– +– +
T102
J1
SW1
A
A
A
A
Disable Address
Place shunt onto required pins.
SLC Address
Set rotary switches to address required.
Status Indicators
Green LEDs are controlled by FACP to indicate status of each module address.
Figure 7.2 CRF-300-6 Control Relay Module

7.3 CRF-300-6 Circuit Board Information

THREE
NONE
TWO
ONE
DIS
DDRESS
BLE

7.4 CRF-300-6 Installation & Wiring

7.4.1 Cabinet Installation

This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.
4
3
2
5
1
0
15
14
1
0
6
B
7 8
SE
9
13
10
12
11
4
3
2
DDRESS
5
6
7 8
9
52 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
CRF-300-6 Installation & Wiring Relay Modules
J1
Shunt Storage Location
SLC-disable2.wmf
+
+
– +
– +
SLC In
Relay Connections
SLC-fmC1.wmf
CRF-300-6
SLC Out
Figure 7.3 CRF-300-6 Wiring Connections

7.4.2 Setting an SLC address for a CRF-300-6 Module

Each CRF-300-6 module can be set to one of 154 base addresses (01-154). The remaining module points are automatically assigned to the next five higher SLC addresses. For example, if the base address is set to 28, the next five module points will be addressed to 29, 30, 31, 32 and 33.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for the MS-9200, MS­9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS­9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS­9600UDLS can support module addresses 01 - 159. To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. See Figure 6.4 on page 48. For use with an MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the stop on the upper rotary switch.

7.4.3 Disabling Unused Module Addresses

A shunt is provided on the circuit board to disable a maximum of three (3) unused module addresses. If two module addresses are disabled, the low­est four addresses will be functional, while the highest two will be dis­abled. For example, if the shunt is placed on ‘TWO’ and the base address is set to 28, the module addresses will be assigned to 28, 29, 30 and 31.
To disable addresses, remove the shunt from it’s storage location and securely place it onto the desired set of pins. See illustration.

7.4.4 Wiring a CRF-300-6 Module (Form-C Relay)

The figure below shows a CRF-300-6 module wired to the Control Panel.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 53

Section 8: Multiple Input/Output Modules

8.1 Description

The CDRM-300 is an addressable module that functions as two individual relay control modules (two isolated sets of Form-C relay contacts) and two Class B monitor modules.
Ratings for the relay contacts on the module are:
Load Description Application
Inductive (PF = 0.35) Non-Coded 25 VAC 2.0 A
Resistive Non-Coded 30 VDC 3.0 A
Resistive Coded 30 VDC 2.0 A
Inductive (L/R = 20ms) Non-Coded 30 VDC 0.46 A
Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A
Resistive Non-Coded 125 VDC 0.9 A
Inductive (PF = 0.75) Non-Coded 125 VAC 0.5 A
Inductive (PF = 0.35) Non-Coded 125 VAC 0.3 A
NOTE: For more information on the module specifications refer to the Installation Instructions provided with these devices.
Maximum
Vol tag e

8.2 CDRM-300 Installation & Wiring

8.2.1 Setting an SLC address for a CDRM-300 Module

Each module is factory preset with an address of “00”. To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired address. Each module can use up to four (4) addresses. The base address selected via the rotary address switches will be assigned to relay output #1 from 00 to 156. The module will automatically assign the next three addresses as appropriate to monitored input #1, relay output #2, and monitored input #2.
Current
Rating
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 54
CDRM-300 Installation & Wiring Multiple Input/Output Modules
SLC
fdrm-1.wmf
CDRM-300
IDC 1 (+) IDC 1 (-) IDC 2 (+) IDC 2 (-)
NC
C NO NC
C NO
Figure 8.1 CDRM-300 Wiring Connections
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open

8.2.2 Wiring a CDRM-300 Module (Form-C Relay)

The figure below shows a CDRM-300 module wired to the Control Panel
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 55

Section 9: Intelligent Detector Bases

9.1 Description

The following bases provide connection between the SLC and these detector heads:
AD350 and AD355 Multicriteria Photoelectric Smoke Detector
CP350 and CP355 Ionization Smoke Detector
H350, H350R, H355, H355R and H355HT Thermal Detector
SD350, SD350T, SD355 and SD355T Photoelectric Smoke Detector
The B501 and B210LP bases are standard plug-in detector bases.
The B501BH, B501BHT, B501BH-2, B501BHT-2, and B200SR Sounder Detector Bases include a horn that will sound when the sensor’s visible LEDs are latched on for approximately 10 seconds.
On the MS-9200 Control Panel, the sounder will activate when the sensor’s visible LEDs are latched on for approximately 10 seconds (Alarm Verification does not delay sounder).
If the MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, or MS-9050UD Control Panel is set with Alarm Verification ON, the sounder will activate at the end of the verification cycle, providing an alarm is verified, approximately 10 seconds after the sensor’s LEDs are latched on. If Alarm Verification is OFF, the sounder will activate when the sensor’s visible LEDs are latched on for approximately 10 seconds.
The B224RB Relay Detector Base includes Form-C latching relay contacts for the control of an auxiliary function. The relay operates 12 seconds (nominally) after activation of the sensor head remote annunciator output.
The B224BI Isolator Detector Base prevents an entire communications loop from being disabled when a short circuit occurs.
NOTE: For more information, refer to the Installation Instructions provided with these devices.

9.2 Installation and Wiring

9.2.1 Setting the Detector Address

Each intelligent detector is factory preset with an address of “00.” To set an SLC address, use a common screwdriver to adjust the rotary switches on the detector to the desired address (see “Set­ting an SLC address for a Single Point Module” on page 32). When finished, mark the address in the place provided on the base and the detector.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 56
Installation and Wiring Intelligent Detector Bases
+ –
+ –
+
SLC-B5012wire.wmf
RA100Z /
RA400Z
Remote LED
Annunciator
(Optional)
To Next Device on SLC
From Control Panel SLC
Figure 9.1 Wiring a B210LP or B501 Detector Base

9.2.2 Wiring a Detector Base

Typical wiring of a detector base (B501 shown) connected to an SLC is shown in the figure below. An optional RA100Z/RA400Z Remote LED Annunciator is shown connected to the detector.
NOTE: The B210LP base wiring is identical to the B501. B501 is the flangeless model.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 57
Intelligent Detector Bases Installation and Wiring
– +
– +
SLC Out
SLC In
Conduit
I300 Isolator Module
s
l
c
-
2
2
4
b
i
2
w
i
r
e
.
w
m
f
Figure 9.2 Wiring of a B224BI Isolator Base Mounting Plate
Note: The “grid” pattern on the
redesigned B224BI mounting plate has been removed for illustration purposes only.
+ -
+ -
s
l
c
-
b
2
2
4
r
b
2
w
i
r
e
.
w
m
f
Figure 9.3 Wiring of a B224RB Relay Base Mounting Plate
To next device
on SLC
SLC
Normally Closed Common Normally Open
Note: The “grid” pattern on the redesigned B224RB mounting plate has been removed for illustration purposes only.

9.2.3 Wiring an Isolator Base

The B224BI Isolator Base will isolate its detector from short circuits that occur on the SLC con­nected at terminals 2 and 3. It will not isolate its installed detector from short circuits that occur on the SLC connected at terminals 1 and 2. In Style 7 applications, the loss of a single detector during a short circuit is not acceptable, and an isolator module must be installed as shown in the figure below.
58 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

9.2.4 Wiring a Relay Base

Figure 9.3 shows typical wiring of a B224RB plug-in relay detector base connected to an SLC.
Installation and Wiring Intelligent Detector Bases
+ -
+ -
+ -
s
l
c
-
b
2
0
0
s
r
w
i
r
e
.
w
m
f
Figure 9.4 Wiring of a B200SR Sounder Base
To next device
on SLC
SLC
Note: The “grid” pattern on the B200SR has been removed for illustration purposes only.
UL-Listed
24V Power
Supply
Optional Sounder Interconnect

9.2.5 Wiring a Sounder Base

Figure 9.4 shows typical wiring of the B200SR Sounder Base.
NOTE: For more detailed wiring on the sounder base, refer to the device’s installation instructions.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 59

Section 10: Addressable Manual Pull Station

+
+
US PAT 4440991
SLC
To next device on SLC
S
L
C
-
b
g
1
2
l
x
2
.
w
m
f
Figure 10.1 Wiring of a BG-12LX Pull Station to an SLC

10.1 Description

The BG-12LX is an addressable manual pull station with a key-lock reset feature.
NOTE: For more information refer to the Installation Instructions provided with this device.

10.2 Installation

10.2.1 Setting an SLC address

Each unit is factory preset with an address of “00.” To set an SLC address refer to “Setting an SLC address for a Single Point Module” on page 32.

10.2.2 Wiring a Manual Pull Station

Figure 10.1 shows typical wiring for a BG-12LX Manual Pull Station to an SLC:
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 60

Appendix A: Power Considerations

A.1 Supplying Power to 24 VDC Detectors and NACs

A.1.1 Resistance and Size

To determine the minimum resistance that can be tolerated in supplying power to 24 VDC 4-wire devices and NACs, use the calculation below. Use this resistance to select the proper gauge wire for the power run from the manufacturers specifications for the desired wire.
For Four-Wire Detectors:
(Vms - Vom)
Rmax =
(N)(Is) + (Na)(Ia) + (Ir)
For NACs:
(Vms - Vom)
Rmax =
(Nb)(Ib)
Where:
Rmax = maximum resistance of the 24 VDC wires Vms = minimum supply voltage Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts N = total number of detectors on the 24 VDC supply circuit Is = detector current in standby Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia = detector current in alarm Ir = end-of-line relay current Nb = number of Notification Appliance Devices Ib = Notification Appliance current when activated
NOTE: This simplified equation assumes that the devices are at the end of a long wire run.
The minimum supply voltages produced by Fire•Lite power supplies are listed below:
FACP Vms Power Supply Vms
MS-9200 16.0 FCPS-24F 19.1
MS-9600 16.0 FCPS-24FS6/FCPS-24FS8 19.1
MS-9200UD/MS-9200UDLS 19.05
MS-9050UD 18.75
Table A.1 Minimum Supply Voltage
61 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Power Considerations Supervising 24 VDC Power
S
L
C
-
p
s
r
t
p
H
.
c
d
r
24 VDC Power from Control Panel or Power Supply
Power Supervision
Relay
(EOLR-1)
Supervised NAC
ELR 47K
Last device on the SLC loop
Figure A.1 Supervised 24 VDC Circuit

A.2 Supervising 24 VDC Power

Power used to supply 24 VDC detectors, notification appliances (using the CMF-300), and two wire detectors (using the MMF-302) can be supervised with a power supervision relay. This relay, energized by the 24 VDC power itself, is installed at the end of each respective power run and wired in-line with the supervised circuit of any intelligent module.
24 VDC power must be provided from a UL-listed power supply for fire protection use.
When power is removed from the relay, the normally closed contacts open the supervised circuit, generating a trouble condition. Therefore, the relay needs to be installed at the end of the super­vised circuit, so it will not disrupt the operating capability of all the devices on that circuit. The relay can be installed in-line with any leg (+ or –) of the supervised NAC circuit, either a Style B (Class B) or a Style D (Class A) circuit.
The drawing below illustrates this concept.
62 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Supervising 24 VDC Power Power Considerations
CMF-300
MMF-300
Power Supervision Relay (EOLR-1)
Supervised NAC
ELR 47K
24 VDC Power from Control Panel or Power Supply
S
L
C
-
p
s
r
-
2
a
d
d
r
e
s
s
t
p
H
.
w
m
f
ELR 47K
Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit
An alternate method is shown below.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 63

Appendix B: Surge Suppression

Primary devices meet NEC Requirements
Secondary devices meet UL1459 (UL1950)
S
L
C
-
s
s
b
u
i
l
d
1
.
w
m
f
Building #2
Building #1
P = Primary S = Secondary
Surge Suppressor
FACP
P
P
P
P
S
S

B.1 Introduction

NOTE: Surge protection is not required in Canadian applications.
There are three (3) primary surge protectors that are approved for use with the MS-9200, MS­9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600UDLS, and MS-9050UD.
DTK-2LVLP-F Diversified Technology Group, Inc. 1720 Starkey Rd. Largo, FL 33771 (727) 812-5000
SLCP-30 EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
PLP-42N Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019 (800) 727-9119
NOTE: For detailed information, refer to the Installation Instructions supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building.
Install primary protection only as shown in this document.
Refer to NEC Article 800 and local building code requirements.

B.2 Installation

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 64
Additional primary surge suppressors may be added as required by the NEC. Add these additional suppressors in series with the SLC wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring con­nected to the surge suppressor input may be routed outside the building as shown below.
Mounting of the surge suppressor must be inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use.
Locate on an available stud and secure with nut.
Unit is connected in series with the SLC Loop to protect the Control Panel.
Provide a common ground to eliminate the possibility of a differential in ground potentials.
Installation Surge Suppression
– +
SLC Loop
SLC Terminal Block
S
L
C
-
l
v
l
p
1
.
w
m
f
Optional Four-wire Return Loop Style 6 (Class A)
2LVLP-F
2LVLP-F
IN OUT
IN OUT
A­B­A+ B+ A Shield B Shield
– +
INPUT
OUTPUT
L1 L2 L3 L4
L1 L2 L3 L4
GRND
INPUT
OUTPUT
L1 L2 L3 L4
L1 L2 L3 L4
GRND
S
L
C
-
p
l
p
n
1
.
w
m
f
SLC Loop
SLC Terminal Block
Optional Four-wire Return Loop Style 6 (Class A)
PLP-42N
PLP-42N
A­B­A+ B+ A Shield B Shield
+
S
L
C
-
s
l
c
p
1
.
w
m
f
SLC Terminal Block
SLC Loop
Optional Four-wire Return Loop Style 6 (Class A)
2LCP-30
IN OUT
A­B­A+ B+ A Shield B Shield
IN OUT
2LCP-30

B.2.1 Wiring Diagram for MS-9200

DTK-2LVLP-F Connections
PLP-42N Connections
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect
the unit’s ground terminal to equipment ground. Wire length must be minimized to provide best protection.
SLCP-30 Connections
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 65
Surge Suppression Installation
+
SLC Loop
SLC Terminal Block
S
L
C
-
l
v
l
p
4
.
w
m
f
Optional 4-wire Return Loop Style 6 (Class A)
2LVLP-F
2LVLP-F
IN OUT
IN OUT
B+ A+ B­A­A Shield B Shield
+
INPUT
OUTPUT
L1 L2 L3 L4
L1 L2 L3 L4
GRND
INPUT
OUTPUT
L1 L2 L3 L4
L1 L2 L3 L4
GRND
S
L
C
-
p
l
p
n
4
.
w
m
f
SLC Loop
SLC Terminal Block
Optional 4-wire Return Loop Style 6 (Class A)
PLP-42N
PLP-42N
B+ A+ B­A­A Shield B Shield
+
S
L
C
-
s
l
c
p
4
.
w
m
f
SLC Terminal Block
SLC Loop
Optional 4-wire Return Loop Style 6 (Class A)
2LCP-30
IN OUT
IN OUT
2LCP-30
B+ A+ B­A­A Shield B Shield
B.2.2 Wiring Diagram for MS-9600, MS-9600LS, MS-9600UDLS,
MS-9200UD, MS-9200UDLS, and MS-9050UD
DTK-2LVLP-F Connections
PLP-42N Connections
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect
the unit’s ground terminal to equipment ground. Wire length must be minimized to provide best protection.
SLCP-30 Connections
66 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Appendix C: Terminal Conversion Charts for New &
Newer Module
(H-Type)
SLC ­SLC +
Common 2
Closed 2
Open 2
Common 1
Closed 1
Open 1
Legacy Module
(V-Type)
Common 2
Closed 2
Open 2
Common 1
Closed 1
Open 1
SLC ­SLC +
Legacy Devices

C.1 CRF-300

Legacy Module Terminal Number
(V-Type)
1SLC -1
2SLC +2
3Unused3
4 Normally Open (1) 5
5 Normally Closed (1) 6
6 Relay Common (1) 7
7 Normally Open (2) 8
8 Normally Closed (2) 9
9 Relay Common (2) 10
N/A Unused 4
N/A Unused 11
Table C.1 CRF-300Terminal Conversions
Terminal Function
Newer Module Terminal Number
(H-Type)
67 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Terminal Conversion Charts for New & Legacy Devices CMF-300 and MMF-302
Newer Module
(H-Type)
SLC ­SLC +
VDC -
VDC +
A-
A+
B/A +
B/A -
SLC ­SLC + VDC ­VDC +
A-
A+
B/A +
B/A -
Legacy Module
(V-Type)

C.2 CMF-300 and MMF-302

All module polarities are shown in standby condition, which reflects the labels on the new mod­ules.
Legacy Module Terminal Number
(V-Type)
1SLC - 1
2SLC + 2
3VDC - 11
4 VDC + 10
5Unused 5
6 Solenoid B/A - 6
7 Solenoid B/A + 7
8 Solenoid A + 8
9 Solenoid A - 9
N/A Unused 3
N/A Unused 4
Table C.2 CMF-300 and MMF-302 Terminal Conversions
Terminal Function
Newer Module Terminal Number
(H-Type)
68 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
MMF-300 Terminal Conversion Charts for New & Legacy Devices
Newer Module
(H-Type)
Class A Supervision ­Class A Supervision+
Class A/B Supervision +
Class A/B Supervision -
SLC ­SLC +
SLC ­SLC +
Class A Supervision -
Class A Supervision+
Class A/B Supervision +
Class A/B Supervision -
Legacy Module
(V-Type)

C.3 MMF-300

Legacy Module Terminal Number
(V-Type)
1SLC - 1
2SLC + 2
3 Unused 3
4 Unused 4
5 Unused 5
6 Class A/B Supervision - 6
7 Class A/B Supervision + 7
8 Class A Supervision + 8
9 Class A Supervision - 9
N/A Unused 10
N/A Unused 11
Table C.3 MMF-300 Terminal Conversions
Terminal Function
Newer Module Terminal Number
(H-Type)
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 69
Terminal Conversion Charts for New & Legacy Devices MDF-300
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
TENS
LOOP
LOOP
ADDRESS
ADDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
8
9
10
11 12
13
14
15
0
1
2
3
4
5
6
7
ONES
ONES
0
2
4
6
8
0
2
4
6
8
Newer Module
(H-Type)
Address +1 (H) -
Address +1 (H) +
Base Address (L) +
Base Address (L) -
SLC ­SLC +
SLC ­SLC +
Address +1 (H) -
Address +1 (H) +
Base Address (L) +
Base Address (L) -
Legacy Module
(V-Type)

C.4 MDF-300

Legacy Module Terminal Number
(V-Type)
1SLC - 1
2SLC + 2
3 Unused 3
4 Unused 4
5 Unused 5
6 Base Address (L) - 6
7 Base Address (L) + 7
8 Address +1 (H) + 8
9 Address +1 (H) - 9
N/A Unused 10
N/A Unused 11
Table C.4 MDF-300 Terminal Conversions
Terminal Function
Newer Module Terminal Number
(H-Type)
70 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Appendix D: Intelligent Detector Base Layouts for
1(–)
2(+)
+ –
+
3
+ –
To next device on SLC
SLC
S
L
C
-
B
5
0
1
w
i
r
e
.
w
m
f
RA100Z/
RA400Z
Remote LED
Annunciator
(Optional)
B501 only: For connection of
cable shield
Use a female disconnect to wire the RA100Z/RA400Z (–) to Terminal 1 (–).
Figure D.1 Wiring the Legacy B350LP or B501 Detector Base
Legacy Devices

D.1 B350LP or B501 Detector Base

NOTE: The B350LP base wiring is identical to the B501, except there is no shield terminal.
71 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Intelligent Detector Base Layouts for Legacy Devices B224BI Isolator Base
SLC In
SLC Out
S
L
C
-
2
2
4
B
I
w
i
r
e
.
w
m
f
Conduit
I300 Isolator Module
Figure D.2 Wiring the Legacy B224BI Isolator Base
SLC
b
2
2
4
r
b
.
w
m
f
To next device
on SLC
For connection of cable shield
3
R
e
l
a
y
C
o
m
m
o
n
2
N
o
r
m
a
l
l
y
O
p
e
n
1
N
o
r
m
a
l
l
y
C
l
o
s
e
d
Figure D.3 Wiring the Legacy B224RB Relay Base

D.2 B224BI Isolator Base

D.3 B224RB Relay Base

72 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
B501BH(-2) and B501BHT(-2) Sounder Bases Intelligent Detector Base Layouts for Legacy Devices
+ -
s
l
c
-
b
5
0
1
b
h
w
i
r
i
n
g
.
w
m
f
Figure D.4 Wiring the Legacy B501BH(-2) and B501BHT(-2) Sounder Bases
SLC -SLC +
UL-Listed
24V Power
Supply
Optional
Sounder
Interconnect

D.4 B501BH(-2) and B501BHT(-2) Sounder Bases

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 73

Appendix E: Canadian Versions of SLC Devices

UL-listed SLC Device ULC-listed SLC Device Description
AD350/AD355 AD350A/AD355A Intelligent detector that combines a photoelectric sensing chamber
and fixed temperature heat detection (135°F/57.2°C).
CP350/CP355 CP350A/CP-355A Addressable, intelligent smoke detector that incorporates an
ionization sensing chamber. Designed to provide open area protection.
SD350/SD355 SD350A/SD355A Addressable intelligent smoke detector that uses a photoelectric
sensing chamber. Listed for use in ducts. Designed to provide open area protection.
SD350T/SD355T SD350TA/SD355TA Adds thermal sensors that will alarm at a fixed temperature of
H350/H355 H350A/H355A Intelligent thermistor sensing circuit for fast response. Designed to
H350R/H355R H350RA/H355RA Incorporates a thermal rate of rise of 15°F (9.4°C).
H355HT H355HTA High temperature sensor with 190°F (87.8°C) fixed temperature
Bases
B210LP B210LPA Standard U.S. Low-Profile base (6", 15.24 cm).
B501 B501A Standard European flangeless base (4", 10.16 cm).
B501BH, B501BHT B501BHA, B501BHTA Sounder base, includes Sounder base with temporal sounder (UL
B501BH-2, B501BHT-2 N/A Sounder base, includes Sounder base with temporal sounder (UL
B224RB B224RBA Low Profile Intelligent relay base.
B224BI B224BIA Low Profile Intelligent isolator base.
B200SR B200SRA Intelligent sounder base, temporal or steady.
Monitor and Zone Interface Modules
MMF-300 MMF-300A Used for normally open contact alarm initiating devices, such as
MMF-302 MMF-302A Used to interface with two-wire smoke detectors in addition to
MDF-300 MDF-300A Two independent 2-wire Initiating Device Circuits (IDCs) at two
MMF-301 MMF-301A Functionally similar to the MMF-300 Monitor Module, but offered in
BG-12LX BG-12LX An addressable manual pull station with key-lock reset feature. The
Control Modules
CMF-300 CMF-300A Control Module, NAC: Addressable Control Module used as
135°F (57°C).
provide open area protection with 50 foot spacing capability. A fixed temperature sensor with 135°F fixed temperature alarm.
alarm.
Photoelectric Duct Detector, Low-flow. Requires SD350(A)/SD355(A) detector.
8th Edition).
9th Edition).
manual pull stations, four-wire smoke detectors, heat detectors, waterflow, and supervisory devices.
normally open contacts.
separate, consecutive addresses. Wire supervised IDCs as NFPA Style B (Class B) or Style D (Class A) circuits. The modules come with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
a smaller package for mounting directly in the electrical box of the device being monitored. (Class B input circuit only.)
addressable module is housed within the pull station.
Notification Appliance Circuits (NACs) to power and supervise compatible, UL-listed notification appliances. Wired supervised NACs as NFPA Style Y (Class B) or Style Z (Class A). The modules come with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
74 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Canadian Versions of SLC Devices
UL-listed SLC Device ULC-listed SLC Device Description
CRF-300 CRF-300A Relay Control Module is similar to the CMF-300(A) except used as
a Form-C control relay module.
Fault Isolator Module
I300 I300A The Fault Isolator Module protects the system against wire-to-wire
short circuits on the SLC. It should be placed between groups of sensors in a Style 6 or Style 7 SLC to isolate short- and open-circuit problems and protect the rest of the loop so it can continue to operate normally. It is not addressable, but listed here due to its use in an SLC.
Multi-input/output modules
MMF-300-10 MMF-300-10A Supervises ten Class-B addressable Initiating Device Circuits (IDC)
which monitor normally open contact initiating devices.
MMF-302-6 MMF-302-6A Monitors six zones of conventional two-wire detectors.
CDRM-300 CDRM-300A Dual Class B monitor / Form-C relay module.
CMF-300-6 CMF-300-6A Similar in operation to the CMF-300, except it can activate six (6)
Style Y (Class B) or three (3) Style Z (Class A) NACs.
CRF-300-6 CRF-300-6A Similar in operation to the CRF-300, except it provides six (6) Form-
C relays.
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 75

Index

Numerics
24 VDC detectors 61 24 VDC NAC power 24 VDC power
MS-9200, MS-9600
44
18
A
AD350 Detector 11 AD355 Detector address capacity addressable
modules
addressable devices Addressable Modules (Overview) Addressable Monitor Modules Alarm Verification analog intelligent devices Authority Having Jurisdiction auxiliary devices
11, 56
23
11, 27
23
74
27
56
10
13
11
B
B200SR Sounder Detector Base 56 B210LP B224BI Isolator Detector Base B224RB Relay Detector Base B350LP Detector Base B501 Detector Base B501BH Sounder Detector Base B501BH-2 Sounder Detector Base B501BHT Temporal Sounder Detector Base B501BHT-2 Temporal Sounder Detector Base base BEAM355 BEAM355S BG-12LX building entry/exit
56
23, 56
56
71
56, 71
56
56
57, 58, 59
12
12
12, 60
64
C
CDRM-300 54 CDRM-300 Multiple Input/Output Module
wiring
55
circuit fault Classic Loop Interface Protocol CLIP (Classic Loop Interface Protocol) CLIP Mode close nippled conduit CMF-300 Control Module
CMF-300-6 Control Module
11
12
installation wiring
address disabling
44
45
10
10
26
11, 44, 45, 46
11, 44, 49, 50
47
56
56
address setting circuit board installation short circuit protection Style selection wiring
49
common ground communication protocol conduit, close nippled connectors, crimp-on Control Modules
Overview control panel CP350 Detector CP355
12
CP355 Detector CRF-300 Relay Module
wiring
51
CRF-300-6 Relay Module
address disabling
address setting
circuit board
wiring
52, 53
46
48
46
47
47
64
10
26
65, 66
11
74
8
11
56
11, 51
11, 51
53
53
52
D
D350P Detector 12 D350RP Detector D355PL detector DC resistance detector bases detector bases, wiring of detectors
devices
document sources drain wire dry-contact DTK-2LVLP-F Dual Monitor Module
56
detector bases
listing
addressable
auxiliary
maximum number between isolators
supervised
12
12 15, 16 56
57
74
11, 74
23 11
62
9
17
11
64
31
E
electrical interference 14 emergency signaling circuit End-of-Line Resistor
36
45, 49
23
76 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Index F–P
F
fault 13, 25 fault condition Fault Isolator Module FCPS-24F Fire alarm service foil
17
Form-C contacts Form-C relay contacts four-wire configuration
23
23
61
31
54
11, 51, 56
46, 50
G
ground terminal 65, 66
H
H350 Detector 12 H350R Detector H355 Detector H355HT Detector H355R Detector Heat Detector
12
12, 56
12
12
56
I
I300 Isolator Module 11, 23 Initiating Device Circuits integral relay Ionization Detector isolator base isolator base, wiring of Isolator Module
how it works wiring of
23
23
11, 25, 26
23
27, 34, 37, 39
56
58
23
K
key-lock reset 60
L
LEDs 56 LiteSpeed local building code loop resistance loops
10
64
15, 16
16
MMF-301 Mini Monitor Module MMF-302 Zone Interface Module
wiring
40
MMF-302-6 Interface Module
wiring
42
module circuits modules
addressable control isolator monitor relay
Monitor Modules
Overview Multicriteria Detector multiple input/output module Multi-Point Module
27
11
11
11
11
11
11, 27
74
56
33
11, 31
11, 29, 40, 41
11, 30, 42, 43
54
N
NAC 11 NAC power NAC wiring NEC Article 800 NFPA Style 4
NFPA Style 6
NFPA Style 7
NFPA Style B
NFPA Style D
NFPA Style Y
NFPA Style Z
Nonresettable power normally closed contacts Notification Appliance Circuit
44, 62
44
64
wiring of
with I300
wiring of
with I300
21
24
22
25
23
with isolator modules
IDC wiring
IDC wiring
34, 37, 39, 40, 42
35, 38, 41, 43
44
wiring of
45, 49 44
wiring of
46, 50
18
62
26
11
O
older version and newer version modules 8, 9
M
MDF-300 Dual Monitor Module 11, 31, 39
wiring
39
metal conduit Mini Monitor Module minimum resistance MMF-300 Monitor Module
wiring
MMF-300-10 Monitor Module
wiring
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 77
17, 25
31
61
11, 27, 34, 35, 36
34
11, 28, 37, 38
37
P
performance 13 Photoelectric Detector PLP-42N Polling Protocols power run power supervision relay power supplies proper gauge wire
64
10
61, 62
61
61
56
45, 46, 49, 50, 62
R–Z Index
pull station 12, 26
wiring of
60
R
RA100Z 57 RA400Z rate of rise ratings, relay contact relay base
relay contact ratings Relay Module relays
Remote LED Annunciator Resettable power resistance rotary switches
57
12
23
wiring of
Form-C
15, 16
44, 51, 54
58
44, 51, 54
11
11
18
32, 38, 39, 40, 41, 42, 43, 56
S
SD350 Detector 12 SD350T Detector SD355 Detector SD355R Detector SD355T Detector sensing circuit, thermistor short circuit Signaling Line Circuit Single Point Module SLC address, setting of SLC connections SLC terminal block SLC wiring
43
SLCP-30 Smoke Detectors sounder base sounder base, wiring of Sprinkler supervision supervised
supplying power suppressors, surge surge protector switching
64
circuit devices
44
12
12, 56
12
12
23
10
32
32, 56
18
17
34, 35, 36, 37, 38, 39, 40, 41, 42,
56
23
59
31
62
62
61
64
10, 13, 64
57
12
two-wire configuration two-wire detectors
45, 49
62
U
Unregulated power 18
V
verification cycle 56
W
Waterflow alarm service, automatic and manual
31
wire length wire size wiring
wiring pair wiring requirements wiring style requirements
15, 16
14
I300
23
MDF-300
MMF-300
MMF-300-10
MMF-302
MMF-302-6
NACs
39
34
40
44
64
37
42
14
13
Z
Zone Interface Module 29
T
terminal blocks 18 termination of shield Thermal Detector thermistor sensing circuit trouble conditions T-tapping twisted-pair shielded wiring
78 FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
15, 21, 22, 25, 26
17
56
12
13, 23
14
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009). The Products manufactured and sold by Manufacturer are date stamped at the time of production. Manufacturer does not warrant Products that are not manufactured by it in its Northford, Connecticut facility but assigns to its Distributor, to the extent possible, any warranty offered by the manufacturer of such product. This warranty shall be void if a Product is altered, serviced or repaired by anyone other than Manufacturer or its authorized Distributors. This warranty shall also be void if there is a failure to maintain the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS, TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION, INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its products and replaces all previous warranties and is the only warranty made by Manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. Manufacturer does not represent that its products will prevent any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion, each part returned by its authorized Distributor and acknowledged by Manufacturer to be defective, provided that such part shall have been returned to Manufacturer with all charges prepaid and the authorized Distributor has completed Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.
Warn-HL-08-2009.fm
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011 79
World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.firelite.com
Loading...