Fire-Lite SLC User Manual

Page 1
PN 51309:K ECN 08-118
Intelligent Control Panel
S L C
Wiring Manual
Document 51309 2/14/2008 Rev:
K
Page 2
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise follow­ing the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These docu­ments can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Manage­ment Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens­ing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flam­ing fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.). Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com­prehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmis­sion systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the require­ments of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso­ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room tempera­ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Page 4
This Page Intentionally Left Blank
4 The SLC Wiring Manual PN 51309:K 2/14/08
Page 5
Introduction 8
Scope ............................................................................................................................8
Reference Documentation ..................................................................................... 9
Overview ................................................................................................................... 10
Polling Protocols ............................................................................ ..........................10
Available Protocols ......................................................................................... .... 10
Devices ....................................................................................................................... 10
Isolator Module ................................................................................................... 10
Monitor Modules .................................................................................................10
Control Modules ................................................................................................. 11
Relay Modules .................................................................................................... 11
Intelligent Detectors ............................................................................. ............... 11
Manual Pull Station .................................................................................... ......... 12
300 Series Addressable Devices ................................................................ ......... 12
SLC Performance ........................................................................... ..........................12
Surge Suppression .................................................................................................... 12
Wiring Requirements 13
Wire Sizing ............................................................... .................................. ............... 13
CLIP (Classic Loop Interface Protocol) Mode ................................................... 13
LiteSpeed Mode .................................................................................................. 13
Measuring Resistance & Length ............................................................................. 14
Two-Wire SLC - Style 4 (Class B) .....................................................................14
Loop Resistance ............................................................................... ............ 14
Total Wire Length ........................................................................................14
Four-Wire SLC Style 6 & 7 (Class A) ................................................................ 15
Loop Resistance ............................................................................... ............ 15
Total Wire Length ........................................................................................15
Shield Wire Termination ......................................................................................... 16
Control Panel Terminal Blocks ...............................................................................17
MS-9200 .............................................................................................................. 17
MS-9600, MS-9600LS, MS-9600LSC & MS-9600UDLS ................................. 17
MS-9200UD & MS-9200UDLS .................................................. ....................... 18
MS-9050UD ........................................................................................................ 18
Non-Isolated Circuits 19
Overview ................................................................................................................... 19
NFPA Style 4 SLC .................................................................................................... 19
NFPA Style 6 SLC .................................................................................................... 20
SLC Circuits with Isolators 21
Fault Isolator Module - I300 ...................................................................................21
Isolating an SLC Branch ..................................................................................... 21
Wiring an Isolator Module ..................................................................................21
NFPA Style 4 SLC Using an I300 Module .............................................................22
NFPA Style 6 SLC Using an I300 Module .............................................................23
NFPA Style 7 SLC Using an I300 Module .............................................................24
Monitor Modules 25
Descriptions ............................................................................................................... 25
MMF-300 Monitor Module ................................................................................25
MMF-302 Monitor Module ................................................................................25
MDF-300 Dual Monitor Module ........................................................................26
MMF-301 Monitor Module ................................................................................26
MMF-300-10 ....................................................................................................... 27
The SLC Wiring Manual PN 51309:K 2/14/08 5
Page 6
MMF-302-6 .........................................................................................................28
Installation .................................................................................................................29
Setting an SLC address for a Single Point Module .............................................29
Setting an SLC address for a Multi-Point Module ..............................................30
MMF-300 Wiring Diagrams ....................................................................................31
Wiring a NFPA Style B IDC with an MMF-300 ...............................................31
Wiring a NFPA Style D IDC with an MMF-300 ............................................... 32
MMF-300-10 Wiring Diagrams ............................................................................... 33
Wiring a NFPA Style B IDC with an MMF-300-10 .......................................... 33
Wiring a NFPA Style D IDC with an MMF-300-10 ..........................................34
MDF-300 Wiring Diagrams ..................................................................................... 35
Wiring a NFPA Style B IDC with an MDF-300 ................................................35
MMF-302 Wiring Diagrams ....................................................................................36
Wiring a NFPA Style B IDC with an MMF-302 ................................................36
Wiring a NFPA Style D IDC with an MMF-302 ................................................ 37
MMF-302-6 Wiring Diagrams .................................................................................38
Wiring a NFPA Style B IDC with an MMF-302-6 .............................................38
Wiring a NFPA Style D IDC with an MMF-302-6 .............................................39
Control Modules 40
Description ................................................................................................................ 40
CMF-300 Installation ...............................................................................................40
Setting an SLC address for an CMF-300 Module ............................................... 40
Wiring a Notification Appliance Circuit (NAC) with an CMF-300 ................... 40
Wiring a CMF-300 Module .....................................................................................41
Wiring a Style Y NAC (Two-Wire) ...................................................................41
Wiring a Style Z NAC (Four-Wire) ....................................................................42
CMF-300-6 Installation ............................................................................................ 43
Cabinet Installation .............................................................................................43
Setting an SLC address for an CMF-300-6 Module ........................................... 43
Setting NACs as Style Y or Style Z ....................................................................43
Disabling Unused Module Addresses .................................................................43
Short Circuit Protection ..................................................................................... ..43
Features Not Supported .......................................................................................44
Circuit Board Information .................................................................................44
Wiring a CMF-300-6 Module ..................................................................................45
Wiring a Style Y NAC (Two-Wire) ...................................................................45
Wiring a Style Z NAC (Four-Wire) ....................................................................46
Relay Modules 47
Description ................................................................................................................ 47
CRF-300 Installation & Wiring ..............................................................................47
Setting an SLC address for a CRF-300 Module ..................................................47
Wiring a CRF-300 Module (Form-C Relay) ....................................................... 47
CRF-300-6 Circuit Board Information .................................................................48
CRF-300-6 Installation & Wiring ........................................................................... 49
Cabinet Installation .............................................................................................49
Setting an SLC address for a CRF-300-6 Module .............................................. 49
Disabling Unused Module Addresses ................................................................49
Wiring a CRF-300-6 Module (Form-C Relay) ...................................................49
Intelligent Detector Bases 50
Description ................................................................................................................ 50
Installation and Wiring ............................................................................................50
Setting the Detector Address ...............................................................................50
6 The SLC Wiring Manual PN 51309:K 2/14/08
Page 7
Wiring a Detector Base ....................................................................................... 50
Addressable Beam Detectors 51
Description ................................................................................................................ 51
Installation and Wiring ............................................................................................ 51
Setting an SLC Address for a Beam Detector .....................................................51
Wiring a Beam Detector ..................................................................................... 51
Addressable Manual Pull Station 52
Description ................................................................................................................ 52
Installation ................................................................................................................ 52
Setting an SLC address .......................................................................................52
Wiring a Manual Pull Station .............................................................................. 52
Appendix A: Power Considerations 53
Supplying Power to 24 VDC Detectors .................................................................. 53
Resistance and Size ............................................................................................. 53
Supervising 24 VDC Power ..................................................................................... 54
Appendix B: Surge Suppression 55
Introduction .............................................................................................................. 55
Installation ................................................................................................................ 55
Wiring Diagram for MS-9200 ............................................................................. 56
DTK-2LVLP-F Connections ...................................................................... 56
PLP-42N Connections ................................................................................ 56
SLCP-030 Connections ............................................................................... 56
Wiring Diagram for MS-9600, MS-9600LS, MS-9600LSC, MS-9600UDLS,
MS-9200UD, MS-9200UDLS and MS-9050UD ................................................ 57
DTK-2LVLP-F Connections ...................................................................... 57
PLP-42N Connections ................................................................................ 57
SLCP-030 Connections ............................................................................... 57
Appendix C: Terminal Conversion Charts for New & Legacy Devices 58
CRF-300 .................................................................................................................... 58
CMF-300 and MMF-302 .......................................................................................... 59
MMF-300 ................................................................................................................... 60
The SLC Wiring Manual PN 51309:K 2/14/08 7
Page 8
Introduction Scope
Introduction
Scope
This document describes the operation, installation and wiring of various Signaling Line Circuit (SLC ) devices when used with the Fire•Lite MS-9200/MS-9200E, the Fire•Lite MS-9600/MS-9600E, the Fire­Lite MS-9600LS, the Fire-Lite MS-9600LSC, the Fire-Lite MS-9600LSE, the Fire-Lite MS-9600UDLS/ MS-9600UDLSE, the Fire•Lite MS-9200UD/MS-9200UDE, the Fire•Lite MS-9200UDLS/MS­9200UDLSE and the Fire-Lite MS-9050UD control panels. It also provides basic information that applies to Fire•Lite SLC loops in general, such as the branch resistance measurements.
Note: Any reference in this manual to the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS or MS­9600UDLS includes the MS-9200E, MS-9200UDE, MS-9200UDLSE, MS-9600E, MS-9600LSE or MS-9600UDLSE respectively.
Additional information about the specific control panel and the modules and detectors referenced in this document can be found in the respective installation manual as listed in Table 1, “Reference Documentation,” on page 9.
Currently, there are two styles of Modules available, legacy version and newer version. The obvious difference between the two styles is the orientation of the rotary dials. Refer to the diagram below for an example of each.
CMF-300
Legacy Version Module
(Vertical Rotary Dial)
Note: Only MMF-300, MMF-302, CRF-300 and CMF-300 modules are available as newer type modules. Both
the legacy and newer versions share the same part numbers. The newer version modules will be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the modules. Refer to "Appendix C: Terminal Conversion Charts for New & Legacy Devices" on page 58 for additional information.
Newer Version Module
(Horizontal Rotary Dial)
8
CMF-300
The SLC Wiring Manual PN 51309:K 2/14/08
Page 9
Scope Introduction
Reference Documentation
The table below accommodates a list of document sources containing additional information regarding the devices used on a Signaling Line Circuit:
For information on... Refer to... Part Number
MS-9200/MS-9200E Instruction Manual 51003 MS-9600/MS-9600E Instruction Manual 51335 MS-9200UD/MS-9200UDE Instruction Manual 51906 MS-9200UDLS/MS-9200UDLSE Instruction Manual 52750 MS-9600LS/MS-9600LS(C/E) & MS-9600UDLS/MS9600UDLSE Instruction Mnual 52646 MS-9050UD Instruction Manual 52413 Compatible Devices Device Compatibility Document 15384 BG-12LX Pull Station Installation Instructions 51094 MMF-300 Monitor Module Installation Instructions F300-02-00 MMF-300-10 Monitor Module Installation Instructions F300-20-00 MMF-301 Mini Monitor Module Installation Instructions F300-05-00 MMF-302 Monitor Module Installation Instructions F300-03-00 MMF-302-6 Interface Module Installation Instructions F300-22-00 MDF-300 Dual Monitor Module Installation Instructions F300-09-00 CMF-300 Control Module Installation Instructions F300-07-00 CMF-300-6 Control Module Installation Instructions F300-21-00 CRF-300 Relay Module Installation Instructions F300-04-00 CRF-300-6 Relay Module Installation Instructions F300-19-00 I300 Isolator Module Installation Instructions F300-06-00 AD350 Multicriteria Detector Installation Instructions F300-17-00 AD355 Multicriteria Detector Installation Instructions F300-24-00 SD350 & SD350T Photo Detector Installation Instru ctions F300-14-00 SD355 & SD355T Photo Detector Installation Instru ctions F300-24-00 CP350 Ionization Detector Installation Instructions F300-15-00 CP355 Ionization Detector Installation Instructions F300-23-00 H350 Heat Detector Installation Instructions F300-12-00 H350R Heat Detector w/ROR Installation Instructions F300-13-00 H355 Heat Detector (135 H355R Heat Detector w/ROR Installation Instructions F300-25-00 H355HT Heat Detector (190 D350P Duct Detector Installation Instructions F300-10-00 D350PL(A) Duct Detector - low flow Installation Instructions F300-27-00 D350RP Duct Detector w/Relay Installation Instructions F300-11-00 D350RPL(A) Duct Detector w/Relay - low flow Installation Instructions F300-28-00 BEAM355(S) Addressable Beam Detector Installation Instructions F300-29-00 B350LP Plug-in Detector Base Installation Instructions F400-21-00 B501BH Sounder Detector Base Installation Instructions D650-03-00 B224RB Relay Detector Base Installation Instructions D450-16-01 B224BI Isolator Detector Base Installation Instructions D450-15-00
°)
°)
Table 1 Reference Documentation
Installation Instructions F300-25-00
Installation Inatructions F300-25-00
The SLC Wiring Manual PN 51309:K 2/14/08 9
Page 10
Introduction Overview
Overview
Communication between the control panel and intelligent addressable monitor and control devices takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of NFP A Style 4, Style 6, or Style 7.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to "Appendix B: Surge Suppression" on page
55.
Polling Protocols
The MS-9200UDLS/E, MS-9600LS(C/E) and MS-9600UDLS/E support LiteSpeed protocol or Classic Loop Interface Protocol (CLIP). The MS-9200/E, MS-9600/E, MS-9200UD/E and MS-9050UD support Classic Loop Interface Protocol (CLIP) only.
Available Protocols
LiteSpeed is a communication protocol that greatly enhances the speed of communication between analog intelligent devices. Only the MS-9200UDLS/E, MS-9600LS(C/E) and MS-9600UDLS/E are capable of operating in LiteSpeed mode.
CLIP (Classic Loop Interface Protocol) polls devices in sequential order. All Fire-Lite addressable fire alarm control panels can operate in CLIP mode. This is the default mode of operation for the FACPs.
Devices
Protocol Use
Use one of the following options with LiteSpeed/CLIP mode:
1. Program all modules and detectors on an FACP as LiteSpeed.
2. Program all modules and detectors on an FACP as CLIP.
Note: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP mode of operation. Communication protocols cannot be split between SLC loops.
Isolator Module
The I300 Isolator Module permits a zone of detectors and modules to be fault isolated from the remainder of the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator modules are required to meet the requirements of an NFPA Style 7 circuit.
Monitor Modules
Addressable modules that allow the control panel to monitor entire circuits of conventional alarm initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and supervisory devices.
MMF-300 - Monitors a Style B (Class B) or Style D (Class A) circuit of dry-contact input devises. MMF-300-10 - Monitors ten (10) Style B (Class B) or five (5) Style D (Class A) normally open contact
device circuits.
10
MMF-301 - Same as the MMF-300 except offered in a smaller package for mounting with Style B wired devices. This module does not have an LED.
MMF-302 - Monitors a single IDC of two-wire smoke detectors. MMF-302-6 - An addressable module that provides an interface between the control panel and six (6) Style
B (Class B) or three (3) Style D (Class A) IDCs of two-wire smoke detectors. MDF-300 - Similar to MMF-300, but provides for two independent Style B IDCs.
The SLC Wiring Manual PN 51309:K 2/14/08
Page 11
Control Modules
Through the CMF-300 addressable control module, the control panel can selectively activate a Notification Appliance Circuit (NAC).
CMF-300-6 - Similar in operation to the CMF-300, except it can activate six (6) Style Y (Class B) or three (3) Style Z (Class A) NACs.
Relay Modules
The CRF-300 addressable relay module provides the control panel with a dry-contact output for activating a variety of auxiliary devices.
CRF-300-6 - Similar in operation to the CRF-300, except it provides six (6) Form-C relays.
Intelligent Detectors
AD350 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its detection parameters and alarm threshold depending on the ambient conditions it samples in its environment.
AD355 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its detection parameters and alarm threshold depending on the ambient conditions it samples in its enviornment.
CP350 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle.’
CP355 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle.’
D350P - An addressable photoelectric duct detector. The D350RP includes an alarm relay. Air velocity rating is 500 to 4,000 feet per minute.
D350PL -An addressable low flow photoelectric duct detector (D350PLA for Canada). The D350RPL includes an alarm relay (D350RPLA for Canada). Low Flow refers to the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec.)
1
H350
- An addressable detector using a thermistor sensing circuit for fast response. H350R incorporates
a thermal rate of rise of 15°F (9.4°C)/minute.
1
- An addressable 135° fixed temperature heat detector using a thermistor sensing circuit for fast
H355 response. H355R incorporates a thermal rate of rise of 15° F (9.4° C)/minute.
H355HT
1
- An addressable 190° fixed temperature heat detector using a thermistor sensing circuit for fast
response. SD350 - An addressable photoelectric smoke detector which provides smoke sensing utilizing optical sense
technology. The SD350T includes a 135° F fixed thermal sensor. SD355 - An addressable photoelectric smoke detector which provices smoke sensing utilizing optical sense
technology. The SD355T includes a 135° F fixed thermal sensor. BEAM355 - An addressable long range projected beam smoke detector designed to provide open area
protection. The BEAM355S has an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics.
1
Addressable Heat Detectors are not compatible with the MS-9200(E).
The SLC Wiring Manual PN 51309:K 2/14/08 11
Page 12
Introduction SLC Performance
Manual Pull Station
The BG-12LX is a dual-action pull station that, when activated, provides an addressable identification and its location to the control panel. An addressable monitor module is mounted inside the pull station to facilitate servicing and replacement.
300 Series Addressable Devices
Fire•Lite’s 300 series of addressable devices are fully compatible with the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS(C/E), MS-9600UDLS/E and MS-9050UD FACPs. The devices must be configured for CLIP (Classic Loop Interface Protocol) Mode operation. The address of 300 series devices cannot be set above 99. Compatible devices include:
• SD300 Photo • M300 Monitor Module
• SD300T Photo w/Thermal • M301 Mini Monitor Module
• CP300 Ionization • M302 2-wire Monitor Module
• BG-10LX Pull Station • C304 Control/Relay Module
SLC Performance
SLC performance depends on the type of circuit (Style 4, Style 6, or Style 7) and the components on the circuit.
Note: SLC operation meeting Style 7 requirements isolates each device on the SLC from faults that may occur within other areas of the SLC.
Wiring style requirements are determined by national and local codes. Consult with the Authority Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-1999) lists the trouble conditions that result when a fault exists on an SLC.
Ty pe of Fault Style 4 Style 6 Style 7
Single Open Trouble Alarm, Trouble Alarm, Trouble Single Ground Alarm, Trouble
Short Trouble Trouble Alarm, Trouble Short and open Trouble Trouble Trouble Short and ground Trouble Trouble Alarm, Trouble Open and ground Trouble Alarm, Trouble Alarm, Trouble Communications
loss
• Trouble - The control panel will indicate a trouble condition for this type of fault.
• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.
Surge Suppression
Alarm, Trouble
(ground)
Trouble Trouble Trouble
(ground)
Alarm, Trouble (ground)
Table 2 SLC Performance
12
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to "Appendix B: Surge Suppression" on page 55.
The SLC Wiring Manual PN 51309:K 2/14/08
Page 13
Wire Sizing Wiring Requirements
Wiring Requirements
Wire Sizing
The SLC requires use of a specific wire type, depending on the mode of operation, to ensure proper circuit functioning. Wire size should be no smaller than 18 AWG (0.75 mm
2
mm
) wire. The wire size depends on the length of the SLC circuit. It is recommended that all SLC wiring
2
) and no larger than 12 AWG (3.25
be twisted-pair to minimize the ef fects of electrical interference.
CLIP (Classic Loop Interface Protocol) Mode
All addressable F ACPs can operated in CLIP (Classic Loop Interface Protocol) mode. It is recommended that all SLC wiring be twisted-pair and shielded when operating in CLIP mode to reduce the effects of electrical interference. Use the table below to determine the specific wiring requirements for the SLC.
Wire Requirements Distance in Feet (meters) Wire Size Wire Type
2
Belden 9583, Genesis 4410,
)
Signal 98230, WPW D999
2
Belden 9581, Genesis 4408,
)
Signal 98430, WPW D995
2
Belden 9575, Genesis 4406,
)
& 4606, Signal 98630, WPW D991
2
Belden 9574, Genesis 4402 &
)
4602, Signal 98300, WPW D975
Twisted-pair, shielded
Untwisted, unshielded wire, inside conduit or not in conduit
10,000 feet (3,048 m)
8,000 feet (2,438 m)
4,875 feet (1,486 m)
3,225 feet (983 m)
MS-9200 = 1,000 feet (305 m) MS-9600, MS-9600LS(C) &
MS-9600UDLS = 3,000 feet (914 m) MS-9200UD & MS-9200UDLS =
3,000 feet (914 m) MS-9050UD = 3,000 feet (914 m)
12 AWG (3.1 mm
14 AWG (2.0 mm
16 AWG (1.3 mm
18 AWG (0.75 mm
12 to 18 A W G
Table 3 SLC Wiring Requirements in CLIP Mode
LiteSpeed Mode
The MS-9200UDLS, MS-9600LS(C) and MS-9600UDLS SLC can be programmed to operate in LiteSpeed mode for a quicker device response time. While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference. Use the following table to determine the specific wiring requirements for the SLC.
Wire Requirements Distance in Feet (meters) Wire Size Wire Type
2
Belden 5020UL & 6020UL,
)
Genesis WG-4315 & WG-4515
2
Belden 5120UL & 6120UL,
)
Genesis WG-4313 & WG-4513 Belden 5220UL & 6220UL,
Genesis WG-4311 & WG-4511
2
Belden 5320UL & 6320UL,
)
Genesis WG-4306 & WG-4506
Twisted-pair, unshielded
10,000 feet (3,048 m)
8,000 feet (2,438 m)
4,875 feet (1,486 m)
3,225 feet (983 m)
12 AWG (3.1 mm
14 AWG (2.0 mm
16 AWG (1.3 mm2)
18 AWG (0.75 mm
Table 4 SLC Wiring Requirements in LiteSpeed Mode
The SLC Wiring Manual PN 51309:K 2/14/08 13
Page 14
Wiring Requirements Measuring Resistance & Length
Measuring Resistance & Length
Two-Wire SLC - Style 4 (Class B)
Loop Resistance
T -tapping of the SLC wiring is permitted for 2-wire Style 4 configurations. The total DC resistance from the control panel to each branch end cannot exceed 40 ohms. Measure DC resistance as detailed and shown below:
1. With power removed, short the termination point of one branch at a time and measure the DC resistance from the beginning of the SLC to the end of that particular branch.
2. Repeat this procedure for all remaining branches in the SLC.
Short Point
SLC Out
Branch
SLC-meas1.cdr
Figure 1 Measuring DC Resistance of a Two-Wire SLC
Total Wire Length
The total wire length of all combined branches of one SLC cannot exceed the limits set forth in each system’s instruction manual. Determine the total length in each SLC by summing the wire lengths of all branches of one SLC.
In the following figure, the total length of the SLC is determined by adding the lengths of Branch A plus Branch B plus Branch C.
Branch A Branch B
SLC T erminal Block
Branch C
SLC-meas2.cdr
Figure 2 Measuring the Total Wire Length - Two-Wire SLC
14
The SLC Wiring Manual PN 51309:K 2/14/08
Page 15
Measuring Resistance & Length Wiring Requirements
Four-Wire SLC Style 6 & 7 (Class A)
Loop Resistance
The total DC resistance of the SLC pair cannot exceed 40 ohms. Measure DC resistance as detailed and shown below.
1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.
2. Short the two leads of SLC channel A (Return).
3. Measure the resistance across the SLC channel B (Out) leads.
SLC Out
Short Point
SLC Return
SLC-meas3.cdr
Figure 3 Measuring DC Resistance of a Four-Wire SLC
Total Wire Length
The total wire length in a four-wire SLC cannot exceed the limits set forth in each system’s instruction manual. The figure below identifies the output and return loops from SLC terminal on the control panel:
SLC channel B (output loop)
SLC T erminal Block
B+ B– A– A+
SLC channel A (return loop)
SLC-meas4.cdr
Figure 4 Measuring the Wire Length – Four-Wire SLC
The SLC Wiring Manual PN 51309:K 2/14/08 15
Page 16
Wiring Requirements Shield Wire Termination
Shield Wire Termination
The drawing below shows the method of proper termination of the shield. Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire through
the conduit, into the control box. The shield drain wire must be connected to the “shield” terminal on the SLC terminal block.
Note: Use of good wiring practice consistent with local electrical codes is expected.
CAUTION: Do not let the shield drain wire or the shield foil touch the system cabinet or be connected to earth ground at any point.
MS-9600 MS-9600LS MS-9600LSC MS-9600UDLS MS-9200UD MS-9200UDLS MS-9050UD
Shield Drain Wire
Cabinet
Shield Foil
MS-9200
Conduit
SLC-shieldterm.cdr
Figure 5 Shield Termination
16
The SLC Wiring Manual PN 51309:K 2/14/08
Page 17
Control Panel Terminal Blocks
The terminal blocks on the control panel circuit board that concern the SLC circuit are described below. For more information on this subject refer to the control panel’s Instruction Manual.
MS-9200
TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable. TB6 provides connections for the SLC wiring.
Unregulated Power
Nonresettable Power
TB4
Resettable Power
Connections for wire shield
SHIELD SLC SLC
TB6
SLC Out
Figure 6 MS-9200 Terminal Blocks
SLC-9200tb.cdr
SLC Return
MS-9600, MS-9600LS, MS-9600LSC & MS-9600UDLS
TB3 provides two types of 24 VDC power; Nonresettable and Resettable. TB8 provides connections for the SLC wiring.
Resettable Power
TB3
Nonresettable Power
TB8
SLC Out
Figure 7 MS-9600 Series Terminal Blocks
Connections for wire shield
SHIELDSLC SLC SLC SLC
SLC-9600tb.cdr
SLC Return
The SLC Wiring Manual PN 51309:K 2/14/08 17
Page 18
Wiring Requirements Control Panel Terminal Blocks
MS-9200UD & MS-9200UDLS
TB1 provides two types of 24 VDC power; Nonresettable and Resettable. TB10 provides connections for the SLC wiring.
Nonresettable Power
Resettable Power
Connections for wire shield
SLC
TB1
SLC Out
TB10
SLC Return
SLC Out
Figure 8 MS-9200UD & MS-9200UDLS Terminal Blocks
MS-9050UD
24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8. TB2 provides connections for the SLC wiring.
Connections for wire shield
SLC-9200udtb.cdr
18
SLC-9050udtb.cdr
SLC Return
SLC Out
Figure 9 MS-9050UD Terminal Block
The SLC Wiring Manual PN 51309:K 2/14/08
Page 19
Overview
This chapter concerns itself with the two styles of circuits that do not require isolation devices:
• NFPA Style 4
• NFPA Style 6
NFPA Style 4 SLC
NFPA Style 4 requirements can be met by using the diagram below.
• T-tapping of the SLC wiring is allowed for Style 4 configuration.
Non-Isolated Circuits
Two-wire Addressable Detector
Addressable Module
B+ B–
T-tapped Circuits
Control Panel SLC
SLC-style4.cdr
Figure 10 Basic NFPA Style 4 SLC
The SLC Wiring Manual PN 51309:K 2/14/08 19
Page 20
Non-Isolated Circuits NFPA Style 6 SLC
NFPA Style 6 SLC
NFPA Style 6 requirements can be met by using the diagram below.
• T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.
Two-wire Addressable Detector
SLC Out
Addressable Module
B+ B– A– A+
SLC Return
Control Panel SLC
SLC-style6.cdr
Figure 11 Basic NFPA Style 6 SLC
20
The SLC Wiring Manual PN 51309:K 2/14/08
Page 21
Fault Isolator Module - I300 SLC Circuits with Isolators
SLC Circuits with Isolators
Fault Isolator Module - I300
The I300 is used to protect critical elements of the SLC from faults on other SLC branches or segments A Fault Isolator Module on both sides of a device is required to comply with NFPA Style 7 requirements. A maximum of 25 addressable devices can be connected between isolator Modules. When more than 100 Isolator Modules are connected to an SLC loop, the address capacity of the loop is
reduced by two (2) addresses for every isolator device in excess of 100.
Isolating an SLC Branch
The module continuously monitors the circuit connected to terminals 3(–) and 4(+). Upon power-up, an integral relay is latched on. The module periodically pulses the coil of this relay. A short circuit on the SLC resets the relay. The module detects the short and disconnects the faulted SLC branch or segment by opening the positive side of the SLC (terminal 4). This isolates the faulty branch from the remainder of the loop preventing a communication problem with all other addressable devices on the remaining branches (labeled “Continuation of the SLC” in the figure below). During a fault condition, the control panel registers a trouble condition for each addressable device which is isolated on the SLC segment or branch. Once the fault is removed, the module automatically reapplies power to the SLC branch or segment.
Wiring an Isolator Module
The figure below shows typical wiring of an Isolator Module:
Continuation of the SLC
IN IN
OUT
OUT
SLC
Figure 12 Wiring an I300 Module
SLC-isowire.cdr
Isolated branch of the SLC
The SLC Wiring Manual PN 51309:K 2/14/08 21
Page 22
SLC Circuits with Isolators NFPA Style 4 SLC Using an I300 Module
NFPA Style 4 SLC Using an I300 Module
A variation of a Style 4 operation using isolator modules to protect each branch of the SLC. Refer to Figure 12 on page 21 for I300 wiring.
B– B+
1 2
I300
3 4
1 2
I300
3 4
1 2
I300
3 4
Control Panel SLC
Two-wire Addressable Detector
Isolated Branch
Isolated Branch
Addressable Pull Station
Isolated Branch
Figure 13 NFPA Style 4 SLC using I300 modules
SLC-style4i300.cdr
22
The SLC Wiring Manual PN 51309:K 2/14/08
Page 23
NFPA Style 6 SLC Using an I300 Module
A variation of Style 6 operation using isolator modules to protect a section of the SLC. By flanking each group of devices with an I300 fault isolator module each group is protected from faults that may occur in the other groups. For example, a fault in Section B will not effect Sections A & C. The isolator modules on either side of Section B will open the loop. Section A will still operate from power on the SLC Out side and Section C will operate from the SLC Return side.
• A combination of isolator modules and isolat or bases may be used.
• T-tapping is NOT allowed within the Style 6 configuration.
• I300 modules shall be within 20 feet (6.1 meters) of device and use metal conduit.
123
I300
4
Two-wire Addressable Detector
Section A
SLC Out
Section B
Section C
Addressable
Pull Station
SLC Return
1
2
3
I300
4
3 4
I300
1 2
B– B+ A+ A–
Control Panel
2 1
I300
4 3
Cabinet or Enclosure
SLC-style6i300.cdr
Figure 14 NFPA Style 6 SLC using I300 modules
The SLC Wiring Manual PN 51309:K 2/14/08 23
Page 24
SLC Circuits with Isolators NFPA Style 7 SLC Using an I300 Module
NFPA Style 7 SLC Using an I300 Module
Style 7 operation requires using isolator modules before and after each device. Flanking each device with an isolator provides fault protection to all other devices on the loop.
• T-tapping is NOT allowed within the Style 7 wiring configuration.
• When a detector base or pull station is used, install I300 modules on both sides of the device.
• Connections between isolator modules and the device they isolate must be “close nippled” conduit,
within 3 feet (91.44 cm).
1
2
3
I300
4
1
2
3
I300
4
3 4
I300
1 2
3 4
I300
1 2
Two-Wire Addressable Detector
SLC Out
3 4
I300
1 2
Two-wire Addressable Detector
2 1
4 3
2 1
I300
4 3
Addressable
Pull Station
4 3
I300
2 1
SLC Return
I300
24
B– B+ A+ A–
Control Panel
SLC-style7i300.cdr
Figure 15 NFPA Style 7 SLC
The SLC Wiring Manual PN 51309:K 2/14/08
Page 25
Descriptions Monitor Modules
Monitor Modules
Descriptions
These addressable modules monitor conventional contact-type alarm initiating devices. You can configure module circuits as an NFP A Style B (Class B) or Style D (Class A) Initiating Device Circuits (IDC). There is no limit to the number of contact-type devices installed on a monitor module circuit.
Note: For more information on the individual module specifications refer to the Installation Instructions that are provided with these devices.
MMF-300 Monitor Module
An addressable module that monitors either a Style B (Class B) or Style D (Class A) circuit of dry-contact input devices.
IDC Return – IDC Return +
Areas used to record the device
address and SLC number.
SLC–
SLC+
IDC Out +
IDC Out -
FMMtpH.wmf
Rotary Switches
Figure 16 MMF-300 Monitor Module
MMF-302 Monitor Module
Similar to the MMF-300, except it is used to monitor a single IDC of UL listed compatible two-wire 24 volt conventional smoke detectors. Refer to the Device Compatibility Document.
24 VDC –
24 VDC + IDC Return – IDC Return +
IDC Out +
IDC Out -
SLC– SLC+
Rotary Switches
Areas used to record the device
address and SLC number.
FZMtpH.wmf
Figure 17 MMF-302 Module
The SLC Wiring Manual PN 51309:K 2/14/08 25
Page 26
Monitor Modules Descriptions
MDF-300 Dual Monitor Module
Similar to the MMF-300 but provides for two independent 2-wire IDCs at two separate, consecutive addresses.
Rotary Switches
Address +1
Base Address {
9 H–
{
8 H+
7L+
SLC– SLC+
6L–
Areas used to record the device
address and SLC number.
SLCDualMod-simplified.wmf
Figure 18 Dual Monitor Module
MMF-301 Monitor Module
Functionally and electrically identical to an MMF-300, but offered in a smaller package for mounting directly in the electrical box of the Style B (Class B) device being monitored.
Rotary Switches
IDC (+)
IDC (-)
15
1
14
9
8
TENS
2
3
LOOP
4
5
6
7
13 12 11
10
9
ONES
0
7
8
ADDRESS
0
Label – Use to record
1
the device address and
2
3
SLC number.
4
5
6
FMM-101.cdr
SLC (+)
SLC (-)
Figure 19 MMF-301 Module
26
The SLC Wiring Manual PN 51309:K 2/14/08
Page 27
Descriptions Monitor Modules
MMF-300-10
A monitor module intended to interface between the FACP and up to ten (10) Style B (Class B) or five (5) Style D (Class A) IDCs containing normally open contact devices.
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.
T5
– +
– +
– +
– +
– +– +
+
+
+
+
+
+
T0
T1
A/B SELECTCLDISABLE 1
DISABLE 2
T2
T3
J1
T4
4
3
2
5
1
0
15
14
0
6
BASE ADDRESS
7
8
9
13
10
12
11
SW1
4
3
2
5
1
6
7
8
9
+9
+0 +1
+2 +3
+4 +5
+6 +7
+8
Style Y or Style Z Select
Remove shunt for Style Z circuits
Disable Address
Place shunt in: Disable 1 position to disable highest module address
SLC Address
Set rotary switches to base (first) address of modules
Disable 2 position to disable highest two module addresses
Figure 20 MMF-300-10 Module
The SLC Wiring Manual PN 51309:K 2/14/08 27
Page 28
Monitor Modules Descriptions
MMF-302-6
A monitor module intended to interface between the FACP and a conventional alarm system with up to six (6) Style B (Class B) or three (3) Style D (Class A) IDCs containing normally open contact devices.
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installat ion into cabinet.
– +
– +
J1
T0
T1
T6
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T2
– +– +
+
T5
+
T3
+
+
T4
+
+
4
3
2
5
1
0
15
14
1
0
6
BASE ADDRESS
7
8
9
13
10
12
11
SW1
4
3
2
5
6
7 8
9
BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2
BASE ADDRESS +3
BASE ADDRESS +4 BASE ADDRESS +5
Style Y or Style Z Select
Remove shunt for Style Z circuits
Disable Address
Place shunt in: Disable 1 position to disable highest module address
SLC Address
Set rotary switches to base (first) address of modules
Disable 2 position to disable highest two module addresses
Figure 21 MMF-302-6 Module
28
The SLC Wiring Manual PN 51309:K 2/14/08
Page 29
Installation Monitor Modules
Installation
When installing any of these modules DO NOT mix the following services that the IDC provides:
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervision with norm ally open contact devices
Setting an SLC address for a Single Point Module
Each module can be set to one of 159 addresses (01-159) and is factory preset with an address of “00”.
Note: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD and MS-9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC and MS-9600UDLS can support module addresses 01 - 159.
T o set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired address. The module below is set at “35”. When finished, mark the address on the module face in the place provided.
Breakaway Tab - Modules come with
a raised breakaway tab on the TENS
rotary switch. This tab must be
removed when the module is on an
Legacy Version
Module Rorary
Switch
FACP that uses more than 99 addresses.
Newer Version Module Rotary
Switch
Figure 22 Setting SLC Address on a Single Point Module
Dual monitor modules: On dual monitor modules, only even numbers appear on the ONES rotary switch. The module takes both the selected address and the next-higher address.
SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
The SLC Wiring Manual PN 51309:K 2/14/08 29
Page 30
Monitor Modules Installation
Setting an SLC address for a Multi-Point Module
In Class B operation, each MMF-300-10, MMF-302-6, CMF-300-6 and CRF-300-6 module is set to a base address. The remaining module points are automatically assigned to the next higher SLC addresses. For example, if the base address of a MMF-300-10 is set to 28, the next module points will be addressed to 29, 30, 31, 32, 33, 34, 35, 36 and 37.
In Class A operation, alternate module points are paired together, resulting in a total of five module points. For example, if the base address of a MMF-300-10 is set to 28, then 30, 32, 34 and 36 will be automatically assigned to the remaining module points and 29, 31, 33, 35 and 37 are available for use by other modules.
Note: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD and MS-9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC and MS-9600UDLS can support module addresses 01 - 159 (the plastic stop located on the Tens switch must be removed to set addresses above 99).
T o set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. The module below is set at “28”.
4
3
2
Rotary Switches
1
0 15
14
1
0
13
5
6
7
TENS
8
9
10
12
11
4
3
2
5
6
8
9
7
Plastic Stop
ONES
multroty.cdr
Figure 23 Setting SLC Address on a Multi-Point Module
30
The SLC Wiring Manual PN 51309:K 2/14/08
Page 31
MMF-300 Wiring Diagrams Monitor Modules
MMF-300 Wiring Diagrams
Following are wiring diagrams that depict NFPA Style B (Class B) and D (Class A) Initiating Device Circuits (IDCs) using MMF-300 monitor modules.
The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamperes @ 24 VDC (nominal).
Wiring a NFPA Style B IDC with an MMF-300
Connect the SLC wiring to the module terminals 1 (–) and 2 (+). Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required
SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 29. The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an
MMF-300 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• See "Appendix A: Power Considerations" on page 53 for information on supervising 24 VDC power.
From Supply
Manual pull station
SLC-idcB1tpH.wmf
Heat detector
24 VDC Four-wire Detector Base
47K ELR (supplied with module)
MMF-300
IDC
24 VDC Power Filtered, Regulated, Resettable
To Next IDC or Supervision Device
SLC
Figure 24 Typical Style B IDC Wiring with MMF-300
The SLC Wiring Manual PN 51309:K 2/14/08 31
Page 32
Monitor Modules MMF-300 Wiring Diagrams
Wiring a NFPA Style D IDC with an MMF-300
Connect the SLC wiring to the module terminals 1 (–) and 2 (+). Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required
SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 29. The figure below shows typical wiring for a supervised and power-limited NFP A S tyle D (Class A) IDC
using an MMF-300 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• See "Appendix A: Power Considerations" on page 53 for information on supervising 24 VDC power.
From Supply
24 VDC Four-wire Detector Base
Manual pull station
24 VDC Power Filtered, Regulated, Resettable
To Next IDC or Supervision Device
Heat detector
SLC
MMF-300
IDC
SLC-idcD1tpH.wmf
Figure 25 Typical Style D IDC Wiring with MMF-300
32
The SLC Wiring Manual PN 51309:K 2/14/08
Page 33
MMF-300-10 Wiring Diagrams Monitor Modules
MMF-300-10 Wiring Diagrams
Following are wiring diagrams that depict NFPA Style B (Class B) and D (Class A) Initiating Device Circuits (IDCs) using MMF-300-10 monitor modules.
The Initiating Device Circuit (IDC) is supervised and current-limited to 1.0 milliampere @ 24 VDC (nominal).
Wiring a NFPA Style B IDC with an MMF-300-10
Connect the SLC wiring to the module terminals T5 as shown below. Use the rotary switches on the module to set the base SLC address. Each module takes ten addresses on
the SLC. The remaining module points are automatically assigned to the next nine higher addresses. Refer to “Setting an SLC address for a Multi-Point Module” on page 30.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-9200UD and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an MMF-300-10 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• See "Appendix A: Power Considerations" on page 53 for information on supervising 24 VDC power.
+
+
24 VDC Four-wire Detector Base
47K ELR (supplied with module)
24 VDC Power Filtered, Regulated, Resettable
+
Heat
Detector
+
T3
SLC
T5
Manual Pull
Station
MMF-300-10
– +– +
+
+
+
+
+
T1T0
T2
Figure 26 Typical Style B IDC Wiring with MMF-300-10
+
+
T4
IDC Out
+
SLC-idcB4.cdr
The SLC Wiring Manual PN 51309:K 2/14/08 33
Page 34
Monitor Modules MMF-300-10 Wiring Diagrams
Wiring a NFPA Style D IDC with an MMF-300-10
Connect the SLC wiring to the module terminals T5 as shown below. Use the rotary switches on the module to set the base SLC address. Each module takes five alternating
addresses on the SLC. The remaining module points are automatically assigned to the next four higher addresses. (Example: 28, 30, 32, 34 and 36). Refer to “Setting an SLC address for a Multi-Point Module” on page 30.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-9200UD and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
The figure below shows typical wiring for a supervised and power-limited NFP A S tyle D (Class A) IDC using an MMF-300-10 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• See "Appendix A: Power Considerations" on page 53 for information on supervising 24 VDC power.
24 VDC Power Filtered, Regulated, Resettable
+
+
24 VDC Four-wire Detector Base
SLC
T5
Manual Pull
Station
MMF-300-10
– +– +
+
+
+
+
+
T1T0
T2
+
Detector
+
T3
Figure 27 Typical Style D IDC Wiring with MMF-300-10
Heat
IDC
Return
+
+
IDC Out
+
SLC-idcD3.cdr
T4
34
The SLC Wiring Manual PN 51309:K 2/14/08
Page 35
MDF-300 Wiring Diagrams
Following is a wiring diagrams that depict NFP A Style B (Class B) Initiating Device Circuits (IDCs) using MDF-300 dual monitor module.
Wiring a NFPA Style B IDC with an MDF-300
Connect the SLC wiring to the module terminals 1 (–) and 2 (+). Use the rotary switches on the module to set it to the SLC address. Each dual module takes two addresses
on the SLC. Circuit ‘L ’ corresponds to the address set on the rotary switches, which will be an even number. Circuit ‘H’ will automatically respond to the next higher address, which will be an odd number. Use caution to avoid duplicate addressing of modules on the system. Refer to “Setting an SLC address for a Single Point Module” on page 29.
Each IDC (H & L) is power limited to 230 microamperes @ 24 VDC. The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an
MDF-300 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• See "Appendix A: Power Considerations" on page 53 for information on supervising 24 VDC power.
SLC-idcB3fdm1.wmf
Manual Pull Station
Heat Detector
Base Address (IDC Circuit L)
Manual Pull Station
47K ELR
Base +1 Address (IDC Circuit H)
47K ELR
MDF-300
Figure 28 Typical Style B IDC Wiring with MDF-300
SLC
The SLC Wiring Manual PN 51309:K 2/14/08 35
Page 36
Monitor Modules MMF-302 Wiring Diagrams
MMF-302 Wiring Diagrams
Following are wiring diagrams that concern NFPA Style B (Class B) and D (Class A) Initiating Device Circuits (IDCs) using MMF-302 monitor modules.
Wiring a NFPA Style B IDC with an MMF-302
Connect the SLC wiring to the module terminals 1 (–) and 2 (+). Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required
SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 29. The IDC is supervised and power limited to 230 microamperes @ 24 VDC. The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an
MMF-302 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• 24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the module.
• See "Appendix A: Power Considerations" on page 53 for information on 24 VDC power.
24 VDC Resettable power.
Two-wire smoke detectors
3.9K ELR (supplied with module)
IDC
90 mA External 24 volt
supply required
MMF-302
Figure 29 Typical Style B IDC Wiring with MMF-302
SLC
SLC-idcB2tpH.wmf
36
The SLC Wiring Manual PN 51309:K 2/14/08
Page 37
MMF-302 Wiring Diagrams Monitor Modules
Wiring a NFPA Style D IDC with an MMF-302
Connect the SLC wiring to the module terminals 1 (–) and 2 (+). Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required
SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 29. The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC
using an MMF-302 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• 24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the module.
• See "Appendix A: Power Considerations" on page 53 for information on 24 VDC power.
Two-wire smoke detectors
24 VDC Resettable power. 90 mA External 24 volt supply required
MMF-302
IDC
3.9K ELR (supplied with module)
Figure 30 Typical Style D IDC Wiring with MMF-302
SLC
SLC-idcD2tpH.wmf
The SLC Wiring Manual PN 51309:K 2/14/08 37
Page 38
Monitor Modules MMF-302-6 Wiring Diagrams
MMF-302-6 Wiring Diagrams
Following are wiring diagrams that concern NFPA Style B (Class B) and D (Class A) Initiating Device Circuits (IDCs) using MMF-302-6 monitor modules.
Wiring a NFPA Style B IDC with an MMF-302-6
Connect the SLC wiring to the module terminals T0 as shown below. Use the rotary switches on the module to set the base SLC address. Each module takes six addresses on
the SLC. The remaining module points are automatically assigned to the next five higher addresses. Refer to “Setting an SLC address for a Multi-Point Module” on page 30.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for the MS-9200, MS-9200UD and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC using an MMF-302-6 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• 24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the module.
• See "Appendix A: Power Considerations" on page 53 for information on 24 VDC power.
+
+
SLC
3.9K ELR (supplied with module)
+
Figure 31 Typical Style B IDC Wiring with MMF-302-6
24 VDC resettable power
T1
T0
– +
– +
Two-wire smoke detectors
MMF-302-6
T2
+
+
+
+
IDC Out
T3
+
+
+
T4
+
SLC-idcB5.cdr
38
The SLC Wiring Manual PN 51309:K 2/14/08
Page 39
MMF-302-6 Wiring Diagrams Monitor Modules
Wiring a NFPA Style D IDC with an MMF-302-6
Connect the SLC wiring to the module terminals T0 as shown below. Use the rotary switches on the module to set it to the SLC addresses. Each module takes three alternating
addresses on the SLC. The remaining module points are automatically assigned to the next two higher addresses. (Example: 28, 30 and 32). Refer to “Setting an SLC address for a Multi-Point Module” on page
30.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for the MS-9200, MS-9200UD and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using an MMF-302-6 module.
• Refer to the Device Compatibility Document for compatible smoke detectors.
• 24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the module.
• See "Appendix A: Power Considerations" on page 53 for information on 24 VDC power.
Two-wire smoke detectors
+
+
SLC
24 VDC resettable power
+
MMF-302-6
– +
– +
T1
T0
+
+
T2
+
Figure 32 Typical Style D IDC Wiring with MMF-302-6
+
T3
+
Return
+
IDC
+
IDC Out
T4
+
SLC-idcD4.cdr
The SLC Wiring Manual PN 51309:K 2/14/08 39
Page 40
Control Modules Description
Control Modules
When using a Control Module as a Notification Appliance Circuit (NAC), the isolation described in the section titled SLC Circuits with Isolators which begins on page 21, is required or Riser Conductors must be installed in accordance with the survivability from attack by fire requirements in National Fire Alarm Code, NFPA 72.
Description
The CMF-300 and CMF-300-6 modules are addressable modules that can be used for monitoring and switching 24 VDC Notification Appliance Circuit (NAC) power for NFPA S tyle Y (Class B) and NFPA Style Z (Class A) circuits.
Ratings for the relay contacts on the module are:
Load Description Application Maximum Voltage Current Rating
Resistive Non-Coded 30 VDC 3.0 A Resistive Coded 30 VDC 2.0 A Resistive Non-Coded 110 VDC 0.9 A Resistive Non-Coded 125 VAC (CMF-300)
70.7 VAC (CMF-300-6) Inductive (L/R = 5ms) Coded 30 VDC 0.5 A Inductive (L/R = 2ms) Coded 30 VDC 1.0 A Inductive (PF = 0.35) Non-Coded 125 VAC (CMF-300)
70.7 VAC (CMF-300-6)
0.9 A
0.5 A
Note: For more information on module specifications, refer to the Installation Instructions provided with these devices.
CMF-300 Installation
Setting an SLC address for an CMF-300 Module
Each module is factory preset with an address of “00”. To set an SLC address refer to "Setting an SLC address for a Single Point Module" on page 29.
Wiring a Notification Appliance Circuit (NAC) with an CMF-300
The figure below shows the connections to wire a module for powering a 24 VDC NAC:
24 VDC Nonresettable Power (–)* 24 VDC Nonresettable Power (+)*
Style Z NAC (+) Style Z NAC (–)
Style Y/Z NAC (–) Style Y/Z NAC (+)
NOTE: Module polarities are shown in alarm condition.
SLC (–) SLC (+)
40
SLCModule-simplified.wmf
Figure 33 CMF-300 Wiring Connections
The SLC Wiring Manual PN 51309:K 2/14/08
Page 41
Wiring a CMF-300 Module Control Modules
Wiring a CMF-300 Module
This section contains instructions and diagrams for wiring a Signaling Line Circuit with a CMF-300 as a Notification Appliance Circuit (NAC).
Wiring a Style Y NAC (Two-Wire)
A supervised and power-limited NFP A Style Y (Class B) NAC using a CMF-300 module. Polarized alarm notification appliances are shown connected to the module in a two-wire configuration.
Note: Refer to Device Compatibility Document for compatible notification appliances and relays.
• See "Appendix A: Power Considerations" on page 53 for information on monitoring 24 VDC power.
• Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns).
• 24 VDC power must be provided from a UL listed power supply for fire protecti on use.
• A power supervision relay is required only on the last module of the power run.
• Do not T-tap or branch a St yle Y circuit.
• Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt, P/N SSD A2143-00 (ELR-47K in Canada).
• Do not loop wiring under the screw te rminals of any notification appliance. To maintain supervision, break the wire run at each device
SLC
24 VDC Nonresettable power
ELR
47K, 1/2-watt
24 VDC Notification
Appliances
CMF-300
NOTE: A power supervision relay is required only on the last module of the power run.
NAC
Note: Module polarities are shown in alarm condition
Figure 34 NFPA Style Y Notification Appliance Circuit
SLC-nacY.wmf
The SLC Wiring Manual PN 51309:K 2/14/08 41
Page 42
Control Modules Wiring a CMF-300 Module
Wiring a Style Z NAC (Four-Wire)
A supervised and power-limited NFPA S tyle Z (Class A) NAC using a CMF-300 module. Polarized alarm notification appliances are shown connected to the module in a four-wire configuration.
Note: Refer to the Device Compatibility Document for compatible notification appliances and relays.
• See "Appendix A: Power Considerations" on page 53 for information on monitoring 24 VDC power.
• Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns).
• 24 VDC power must be provided from a UL listed power supply for fire protecti on use.
• A power supervision relay is required only on the last module of the power run.
• Do not T-tap or branch a Style Z circuit.
• Do not loop wiring under the screw te rminals of any notification appliance. To maintain supervision, break the wire run at each device.
NOTE: A power supervision relay is required only on the last module of the power.
24 VDC Nonresettable power
24 VDC notification appliances
NAC Return
NAC Out
Note: Module polarities are shown in alarm condition.
Figure 35 NFPA Style Z Notification Appliance Circuit
SLC
CMF-300
SLC-nacZtpH.wmf
42
The SLC Wiring Manual PN 51309:K 2/14/08
Page 43
CMF-300-6 Installation
Cabinet Installation
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabi net.
Setting an SLC address for an CMF-300-6 Module
In “Style Y” operation each CMF-300-6 module can be set to one of 154 base addresses (01-154). The remaining module points are automatically assigned to the next five higher SLC addresses. For example, if the base address is set to 28, the next five module points will be addressed to 29, 30, 31, 32 and 33.
In “Style Z” operation alternate module points are paired together, resulting in a total of three module points. For example, if the base address is set to 28, then 30 and 32 will be automatically assigned to the remaining module points and 29, 31 and 33 are available to be used for other modules on the SLC.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for MS-9200, MS-9200UD and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
Note: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD and MS-9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC and MS-9600UDLS can support module addresses 01 - 159.
T o set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. See Figure 36 on page 44.
Note: For use with MS-9600, MS-9600LS, MS-9600LSC and MS-9600UDLS, remove the stop on the upper rotary switch.
Setting NACs as Style Y or Style Z
To use this module for Style Y (Class B) operation ascertain that a small shunt is installed on the “A/B SELECT” set of pins. (As shipped).
T o use this module for St yle Z (Class A) operation remove the small shunt from the “A/B SELECT” set of pins. See drawing below and Figure 36 on page 44.
Disabling Unused Module Addresses
A shunt is used, in conjunction with a pin block, to disable a maximum of three (3) unused module addresses. If two module addresses are disabled, the lowest four addresses will be functional, while the highest two will be disabled. For example, if the shunt is placed on ‘DISABLE 2’ and the base address is set to 28, the module addresses will be assigned to 28, 29, 30 and 31.
In Style Z operation, placing a small shunt on ‘DISABLE 3’ will disable all three addresses. Placing it on ‘DISABLE 2’ will disable two out of three addresses.
To disable addresses, securely place one of the supplied small shunts onto the desired set of pins. See drawing and Figure 36 on page 44.
DISABLE 3
DISABLE 2
A/B SELECT
DISABLE 1
J1
Short Circuit Protection
Protection is disabled for each module address when there is a large shunt installed on the corresponding pins of the pin block (as shipped, all six addresses are disabled).
SLC-disable1.cdr
When enabled, the module will not switch power supply if a short circuit condition exists on a NAC. T o enable “Short Circuit Protection” for an address, remove the large shunt from the corresponding pins
of the pin block. See Figure 36 on page 44. Place unused shunts on single pin to store on board for future use.
The SLC Wiring Manual PN 51309:K 2/14/08 43
Page 44
Control Modules CMF-300-6 Installation
Features Not Supported
The “Synchronization” and “Power Supply Monitoring” features are not supported at this time.
Circuit Board Information
Status Indicators
Green LEDs are controlled by FACP to indicate status of each module address.
Synchronization Generator
-Not Supported. DO NOT
remove shunts.
T0
+0
T10
– +
– +
– +
– +
T1
+1
T12 T13
T11
ENABLE POWER SUPPLY MONITORS
A/B SELECT
DISABLE 1
DISABLE 2
DISABLE 3
DISABLE SHORT CIRCUIT PROTECTION
#1 #2 #3 #4 #5 #6
J1
BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2
– +
– +
T2
+2
SYNC GENERATOR
BASE ADDRESS +3
– +– +
T3
+3
Power Supply Monitors -
Not Supported. DO NOT remove shunts.
– +– +
T4 T5
+4
T14
T15
T16
4
3
2
1
0 15
14
13
12
11
4
3
2
1
0
BASE ADDRESS +4 BASE ADDRESS +5
– +– +
+5
5
6
7 8
9
10
SW1
5
6
7 8
9
BASE ADDRESS
CMF-300-6.cdr
44
Place shunt onto required pins.
Disable Address -
Select
Style Y (Class B) or
Style Z (Class A) -
Remove shunt for Style Z (Class A).
Figure 36 CMF-300-6 Control Module Settings
SLC Address
Set rotary switches to address required.
Short Circuit Protection - Remove shunt from the corresponding pins to enable. Shunt #1 for first address, #2 for second address, etc.
The SLC Wiring Manual PN 51309:K 2/14/08
Page 45
Wiring a CMF-300-6 Module
This section contains basic instructions and diagrams for wiring a Signaling Line Circuit with a CMF-300­6 as a Notification Appliance Circuit (NAC).
For more detailed information on wiring a CMF-300-6 Control Module refer to the Installation Instructions provided with the module. Included in these instructions are wiring diagrams concerning a single power supply being shared by multiple NACs and audio NAC configurations.
Wiring a Style Y NAC (Two-Wire)
A supervised and power-limited NFPA S tyle Y (Class B) NAC with a single power supply dedicated to a single NAC using a CMF-300-6 module. Polarized alarm notification appliances are shown connected to the module in a two-wire configuration.
Note: Refer to Device Compatibility Document for compatible notification appliances and relays.
• See "Appendix A: Power Considerations" on page 53 for information on monitoring 24 VDC power.
• Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load
(on mechanical bells and horns).
• 24 VDC power must be provided from a UL listed power supply for fire protecti on use.
• A power supervision relay is required only on the last module of the power run.
• Do not T-tap or branch a St yle Y circuit.
• Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt,
P/N SSD A2143-00 (ELR-47K in Canada).
• Do not loop wiring under the screw te rminals of any notification appliance. To maintain
supervision, break the wire run at each device.
ELR 47K, 1/2-watt
Power Supervision Relay (EOLR-1)
SLC
24 VDC nonresettable power
24 VDC notification appliances
+
NAC Out
– +– +
+
T15
– +– +
T5
+5
T16
Relay Connector Assembly
CMF-300-6
T0 +0
– +
– +
T10
– +
– +
T1
+1
T11
T12
– +– +
T2
+2
T13
– +– +
T3 T4
+3 +4
T14
Figure 37 NFPA Style Y Notification Appliance Circuit
The SLC Wiring Manual PN 51309:K 2/14/08 45
SLC-nacY2.cdr
Page 46
Control Modules Wiring a CMF-300-6 Module
Wiring a Style Z NAC (Four-Wire)
A supervised and power-limited NFPA Style Z (Class A) NAC with a single power supply dedicated to a single NAC using a CMF-300-6 module. Polarized alarm notification appliances are shown connected to the module in a four-wire configuration.
Note: Refer to the Device Compatibility Document for compatible notification appliances and relays.
• See "Appendix A: Power Considerations" on page 53 for information on monitoring 24 VDC power.
• Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns).
• 24 VDC power must be provided from a UL listed power supply for fire protecti on use.
• A power supervision relay is required only on the last module of the power run.
• Do not T-tap or branch a Style Z circuit.
• Do not loop wiring under the screw te rminals of any notification appliance. To maintain supervision, break the wire run at each device.
Power Supervision Relay (EOLR-1)
24 VDC nonresettable power
+
+
24 VDC notification appliances
T0 +0
SLC
T10
– +
– +
CMF-300-6
– +
– +
T1
+1
T12
T11
Power Supply Jumper
– +
T2
+2
– +
T13
Relay Connector Assembly
NAC
Return
+
– +– +
T3 T4
+3 +4
T14
Figure 38 NFPA Style Z Notification Appliance Circuit
– +– +
NAC
Out
+
T15
T16
– +– +
T5
+5
+
SLC-nacZ3.cdr
46
The SLC Wiring Manual PN 51309:K 2/14/08
Page 47
Description
Relay Modules
The CRF-300 and the CRF-300-6 modules are addressable modules that provides Form-C relay contacts. Ratings for the relay contacts on the module are:
Load Description Application
Resistive Non-Coded 30 VDC 3.0 A Resistive Coded 30 VDC 2.0 A Resistive Non-Coded 110 VDC 0.9 A Resistive Non-Coded 125 VAC 0.9 A Inductive (L/R = 5ms) Coded 30 VDC 0.5 A Inductive (L/R = 2ms) Coded 30 VDC 1.0 A Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A Inductive (PF = 0.35) Non-Coded 125 VAC 0.5 A
Note: For more information on the module specifications refer to the Installation Instructions provided with these devices.
CRF-300 Installation & Wiring
Setting an SLC address for a CRF-300 Module
Each module is factory preset with an address of “00.” To set an SLC address refer to "Setting an SLC address for a Single Point Module" on page 29.
Wiring a CRF-300 Module (Form-C Relay)
The figure below shows a CRF-300 module wired to the Control Panel:
CRF-300
Maximum
Voltage
SLC
Current
Rating
C
NC
NO
C
NC
NO
SLC-frmCtpH.wmf
Figure 39 CRF-300 Wiring Connections
The SLC Wiring Manual PN 51309:K 2/14/08 47
Page 48
Relay Modules CRF-300-6 Circuit Board Information
A A
A A
CRF-300-6 Circuit Board Information
T102
– +– +
4
3
2
5
1
14
1
6
B
7
8
SE
9
13
10
12
11
4
3
2
SW1
5
9
DDRESS
6
7 8
Disable Address
Place shunt onto required pins.
J1
THREE
NONE
TWO
ONE
DIS
DDRESS
BLE
0
15
0
Status Indicators
Green LEDs are controlled by FACP to indicate status of each module address.
SLC Address
Set rotary switches to address required.
48
Figure 40 CRF-300-6 Control Relay Module
The SLC Wiring Manual PN 51309:K 2/14/08
Page 49
CRF-300-6 Installation & Wiring
Cabinet Installation
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabi net.
Setting an SLC address for a CRF-300-6 Module
Each CRF-300-6 module can be set to one of 154 base addresses (01-154). The remaining module points are automatically assigned to the next five higher SLC addresses. For example, if the base address is set to 28, the next five module points will be addressed to 29, 30, 31, 32 and 33.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for MS-9200, MS-9200UD and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
Note: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD and MS-9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC and MS-9600UDLS can support module addresses 01 - 159. T o set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. See Figure 36 on page 44.
Note: For use with a MS-9600, MS-9600LS, MS-9600LSC and MS-9600UDLS, remove the stop on the upper rotary switch.
Disabling Unused Module Addresses
A shunt is provided on the circuit board to disable a maximum of three (3) unused module addresses. If two module addresses are disabled, the lowest four addresses will be functional, while the highest two will be disabled. For example, if the shunt is placed on ‘TWO’ and the base address is set to 28, the module addresses will be assigned to 28, 29, 30 and 31.
T o disable addresses, remove the shunt from it’s storage location and securely place it onto the desired set of pins. See illustration.
Wiring a CRF-300-6 Module (Form-C Relay)
The figure below shows a CRF-300-6 module wired to the Control Panel.
SLC Out
+
SLC In
+
Relay Connections
CRF-300-6
J1
SLC-disable2.cdr
Shunt Storage Location
– +
– +
SLC-fmC1.cdr
Figure 41 CRF-300-6 Wiring Connections
The SLC Wiring Manual PN 51309:K 2/14/08 49
Page 50
Description
Intelligent Detector Bases
The following bases provide connection between the SLC and these detector heads:
• AD350 and AD355 Multicriteria Photoelectric Smoke Det ector
• CP350 and CP355 Ionization Smoke Detector
• H350, H350R, H355, H355R and H355HT Thermal Detector
• SD350, SD350T, SD355 and SD355T Photoelectric Smoke Detector
The B350LP Detector Base is a standard plug-in base provided with each detector head. The B501BH Sounder Detector Base includes a horn that will sound when the sensor’s visible LEDs are
latched on for approximately 10 seconds.
On the MS-9200 control panel, the sounder will activate when the sensor’s visible LEDs are latched on for approximately 10 seconds (Alarm Verification does not delay sounder).
If the MS-9600, MS-9600LS, MS-9600LSC, MS-9600UDLS, MS-9200UD, MS-9200UDLS or MS-9050UD control panel is set with Alarm Verification ON , the sounder will activate at the end of the verification cycle, providing an alarm is verified, approximately 10 seconds after the sensor’s LEDs are latched on. If Alarm Verification is OFF, the sounder will activate when the sensor’s visible LEDs are latched on for approximately 10 seconds.
The B224RB Relay Detector Base includes Form-C latching relay contacts for the control of an auxiliary function. The relay operates 12 seconds (nominally) after activation of the sensor head remote annunciator output.
The B224RI Isolator Detector Base prevents an entire communications loop from being disabled when a short circuit occurs.
Note: For more information refer to the Installation Instructions document provided with these devices.
Installation and Wiring
Setting the Detector Address
Each intelligent detector is factory preset with an address of “00.” To set an SLC address, use a common screwdriver to adjust the rotary switches on the detector to the desired address (see "Setting an SLC address for a Single Point Module" on page 29). When finished, mark the address in the place provided on the base and the detector.
Wiring a Detector Base
T ypical wiring of a detector base (B350LP shown) connected to an SLC is shown in the figure below. An optional RA400Z Remote LED Annunciator is shown connected to the detector.
+ –
From Control Panel SLC
2(+)
3
1(–)
To Next Device on SLC
+
RA400Z
+ –
SLC-B350LPwiredr
Figure 42 Detector Terminal Block Wiring
50 The SLC Wiring Manual PN 51309:K 2/14/08
Page 51
Description Addressable Beam Detectors
Addressable Beam Detectors
Description
The BEAM355 and BEAM355S are intelligent, addressable projected beam smoke detectors, designed for protecting open areas with high and sloping ceilings and wide-open areas, where spot type smoke detectors are difficult to install and maintain. The BEAM355S has an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics.
Note: This section provides basic wiring and addressing information. For critical information on device installation, operation and alignment, refer to the Installation Instructions document provided with these devices.
Installation and Wiring
Setting an SLC Address for a Beam Detector
Each beam detector is factory preset with an address of “00.” To set an SLC address, use a common screwdriver to adjust the address rotary code switches on the detector to the desired address (refer to "Setting an SLC address for a Single Point Module" on page 29).
Wiring a Beam Detector
Typical wiring of a beam detector connected to an SLC is illustrated in the figure below.
Alignment Mirror Alignment Gunsight Alignment Position Indicator
Optics Lock-down Screws
ONES T ENS
ADDRESSING CODE
SWITCHE S
Style 7 Isolator Shunts
Test Option (-)
Test Option (+)
not used not used
Digital Signal Strength Readout
Horizontal Adjustment
Alignment Switch
Sensitivity Switch
T est Switch
Vertical Adjustment
Reset Switch
Remote Alarm Out
Reset Input
Test Input
Aux (-)
SLC (-) to next device SLC (+) to next device SLC (-) from panel or previous device SLC (+) from panel or previous device
RTS451/KEY Connections
Figure 43 Beam Detector Terminal Block Wiring
The SLC Wiring Manual PN 51309:K 2/14/08 51
Page 52
Addressable Manual Pull Station Description
Addressable Manual Pull Station
Description
The BG-12LX is an addressable manual pull station with a key-lock reset feature.
Note: For more information refer to the Installation Instructions document provided with this device.
Installation
Setting an SLC address
Each unit is factory preset with an address of “00.” To set an SLC address refer to "Setting an SLC address for a Single Point Module" on page 29.
Wiring a Manual Pull Station
Typical wiring for a BG-12LX Manual Pull Station to an SLC:
+
SLC
To next device on SLC
+
SLC-bg12lx.cdr
Figure 44 Wiring of an BG-12LX Pull Station to an SLC
52
The SLC Wiring Manual PN 51309:K 2/14/08
Page 53
Supplying Power to 24 VDC Detectors Appendix A: Power Considerations
Appendix A: Power Considerations
Supplying Power to 24 VDC Detectors
Resistance and Size
T o determine the minimum resistance that can be tolerated in supplying power to 24 VDC 4-wire detectors, use the calculation below . Use this resistance to select the proper gauge wire for the power run from the manufacturers specifications for the desired wire.
Rmax =
Where:
Rmax = maximum resistance of the 24 VDC wires Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts N = total number of detectors on the 24 VDC supply circuit Is = detector current in standby Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia = detector current in alarm Ir = end-of-line relay current
(18.1 - Vom)
(N)(Is) + (Na)(Ia) + (Ir)
The SLC Wiring Manual PN 51309:K 2/14/08 53
Page 54
Supervising 24 VDC Power
Power used to supply 24 VDC notification appliances (using the CMF-300) can be supervised with a power supervision relay . This relay, energized by the 24 VDC power itself, is installed at the end of each respective power run and wired in-line with the supervised circuit of any intelligent module.
• 24 VDC power must be provided from a UL listed power supply for fire protecti on use.
When power is removed from the relay, the normally closed contacts open the supervised circuit, generating a trouble condition. Therefore, the relay needs to be installed at the end of the supervised circuit, so as to not disrupt the operating capability of all the devices on that circuit. The relay can be installed in-line with any leg (+ or –) of the supervised NAC circuit, either a Style B (Class B) or a Style D (Class A) circuit.
The drawing below illustrates this concept.
24 VDC Power from Control Panel or Power Supply
Power Supervision
Relay
(EOLR-1)
Last device on the SLC loop
ELR 47K
Supervised NAC
ELR 47K
Power Supervision Relay (EOLR-1)
ELR 47K
SLC-psrtpH.cdr
Figure 45 Supervised 24 VDC Circuit
24 VDC Power from Control Panel or Power Supply
CMF-300
Supervised NAC
MMF-300
SLC-psr-2addresstpH.wmf
Figure 46 Alternate: 2-Address Method of Supervising a 24 VDC Circuit
54 The SLC Wiring Manual PN 51309:K 2/14/08
Page 55
Introduction Appendix B: Surge Suppression
Appendix B: Surge Suppression
Introduction
There are three (3) primary surge protectors that are approved for use with the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600LSC, MS-9600UDLS and MS-9050UD.
DTK-2LVLP-F Diversified Technology Group, Inc. 1720 Starkey Rd. Largo, FL 33771 (727)
812-5000
SLCP-030 EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
PLP-42N Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019 (800)
727-9119
Note: For detailed information refer to the installation documentation supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building.
• Install primary protection only as shown in this document .
• Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional suppressors in series with the SLC wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input may be routed outside the building as shown below.
Building #2
Building #1
Installation
P
P = Primary S = Secondary
PP
Surge Suppressor
Primary devices meet NEC Requirements
P
FACP
S
S
SLC-ssbuild1.cdr
Secondary devices meet UL1459 (UL1950)
Mounting of the surge suppressor must be inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use.
• Locate on an available stud and secure with nut.
• Unit is connected in series with the SLC Loop to protect the Control Panel.
• Provide a common ground to eliminate the possibility of a differential in ground potent ials.
The SLC Wiring Manual PN 51309:K 2/14/08 55
Page 56
Appendix B: Surge Suppression Installation
Wiring Diagram for MS-9200
DTK-2LVLP-F Connections
2LVLP-F
Optional 4-wire Return Loop Style 6 (Class A)
OUT
SLC Terminal Block
2LVLP-F
+
SLC Loop
ININOUT
SLC-lvlp1.cdr
PLP-42N Connections
PLP-42N
GRND
INPUT
L1 L2 L3 L4
OUTPUT
L1 L2 L3 L4
Optional 4-wire Return Loop Style 6 (Class A)
SLC Terminal Block
PLP-42N
+
SLC Loop
Note: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the unit’s ground terminal to equipment ground. Wire length must be minimized to provide best protection.
SLCP-030 Connections
INPUT
L1 L2 L3 L4
SLCP-30
GRND
OUTPUT
L1 L2 L3 L4
SLC-plpn1.cdr
Optional 4-wire Return Loop Style 6 (Class A)
56
SLC Loop
– +
OUT
SLCP-30
ININOUT
SLC Terminal Block
SLC-slcp1.cdr
The SLC Wiring Manual PN 51309:K 2/14/08
Page 57
Installation Appendix B: Surge Suppression
Wiring Diagram for MS-9600, MS-9600LS, MS-9600LSC, MS-9600UDLS, MS-9200UD, MS-9200UDLS and MS-9050UD
DTK-2LVLP-F Connections
2LVLP-F
Optional 4-wire Return Loop Style 6 (Class A)
OUT
SLC Terminal Block
2LVLP-F
+
SLC Loop
ININOUT
SLC-lvlp4.cdr
PLP-42N Connections
PLP-42N
GRND
INPUT
OUTPUT
L1 L2 L3 L4
L1 L2 L3 L4
Optional 4-wire Return Loop Style 6 (Class A)
SLC Terminal Block
PLP-42N
+
INPUT
L1 L2 L3 L4
SLCP-30
SLCP-30
GRND
OUTPUT
L1 L2 L3 L4
SLC-plpn4.cdr
Optional 4-wire Return Loop Style 6 (Class A)
OUT
SLC Terminal Block
SLC Loop
Note: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the unit’s ground terminal to equipment ground. Wire length must be minimized to provide best protection.
SLCP-030 Connections
SLC Loop
+ –
ININOUT
The SLC Wiring Manual PN 51309:K 2/14/08 57
SLC-slcp4.cdr
Page 58
Appendix C: Terminal Conversion Charts for New & Legacy Devices CRF-300
Appendix C: Terminal Conversion Charts for New &
Legacy Devices
CRF-300
Common 2
Closed 2
Open 2
Common 1
Closed 1
Legacy Module
Legacy Module Terminal Number Terminal Function Newer Module Terminal Number
1SLC -1 2SLC +2 3 Unused 3 4 Normally Open (1) 5 5 Normally Closed (1) 6 6 Relay Common (1) 7 7 Normally Open (2) 8 8 Normally Closed (2) 9
SLC ­SLC +
Open 1
Common 2
Closed 2
Open 2
Common 1
Closed 1
Newer Module
SLC ­SLC +
Open 1
9 Relay Common (2) 10 N/A Unused 4 N/A Unused 11
Table 5 CRF-300 Terminal Conversions
58
The SLC Wiring Manual PN 51309:K 2/14/08
Page 59
CMF-300 and MMF-302 Appendix C: Terminal Conversion Charts for New & Legacy Devices
CMF-300 and MMF-302
Note: All module polarities are shown in standby condition, which reflects the labels on the new modules.
A-
A+
B/A +
B/A -
SLC ­SLC + VDC ­VDC +
Legacy Module
VDC -
VDC +
A-
A+
B/A +
B/A -
Newer Module
SLC ­SLC +
Legacy Module Terminal Number Terminal Function Newer Module Terminal Number
1SLC -1 2SLC +2 3VDC -11 4VDC +10 5 Unused 5 6 Solenoid B/A - 6 7 Solenoid B/A + 7 8 Solenoid A + 8 9 Solenoid A - 9 N/A Unused 3 N/A Unused 4
Table 6 CMF-300 and MMF-302 Terminal Conversions
The SLC Wiring Manual PN 51309:K 2/14/08 59
Page 60
MMF-300
Class A Supervision -
Class A Supervision+
Class A/B Supervision +
Class A/B Supervision -
Legacy Module
SLC ­SLC +
Class A Supervision ­Class A Supervision+
Class A/B Supervision +
Class A/B Supervision -
Newer Module
SLC ­SLC +
Legacy Module Terminal Number Terminal Function Newer Module Terminal Number
1SLC -1 2SLC +2 3Unused3 4Unused4 5Unused5 6 Class A/B Supervision - 6 7 Class A/B Supervision + 7 8 Class A Supervision + 8 9 Class A Supervision - 9 N/A Unused 10 N/A Unused 11
Table 7 MMF-300 Terminal Conversions
60 The SLC Wiring Manual PN 51309:K 2/14/08
Page 61
Index
Numerics
24 VDC detectors 53 24 VDC NAC power 40 24 VDC power
MS-9200, MS-9600 17
A
AD350 Detector 11, 50 AD355 11 address capacity 21 addressable
devices 21
modules 10, 25 Alarm Verification 50 analog intelligent devices 10 Authority Having Jurisdiction 12 auxiliary devices 11
B
B224 RB Relay Detector Base 50 B224 RI Isolator Detector Base 50 B350LP Detector Base 50 B501BH Sounder Detector Base 50 Bases, detector 50 BEAM355 11, 51 BEAM355S 11, 51 BG-12LX 12, 52 building entry/exit 55
C
circuit fault 10 Classic Loop Interface Protocol 10 CLIP (Classic Loop Interface Proto­col) 10 CLIP Mode 12 close nippled conduit 24 CMF-300 Control Module 11 CMF-300 module 40, 41, 42
installation 40
wiring 41 CMF-300-6
address disabling 43 CMF-300-6 Control Module 11 CMF-300-6 module 40, 45, 46
address setting 43
circuit board 44
installation 43
short circuit protection 43
Style selection 43
wiring 45 common ground 55 communication protocol 10 conduit, close nippled 24 connectors, crimp-on 56, 57 Control Modules 11 control panel 8 CP350 Detector 11, 50
CP355 11 CRF-300 module, wiring of 47 CRF-300 Relay Module 11 CRF-300-6 module
address disabling 49 address setting 49 circuit board 48
wiring 49 CRF-300-6 module, wiring of 47 CRF-300-6 Relay Module 11
D
D350P Detector 11 D350RP Detector 11 DC resistance 14, 15 detector base, wiring of 50 Detector Bases 50 detector bases 50 detectors 50
listing 11 devices
addressable 21
auxiliary 11
supervised 54 document sources 9 drain wire 16 dry-contact 11 DTK-2LVLP-F 55
E
electrical interference 13 End-of-Line Resistor 41, 45
F
fault 12, 23 fault condition 21 Fault Isolator Module 21 Fire alarm service 29 foil 16 Form C relay 50 Form-C contacts 47 Form-C relays 11 four-wire configuration 42, 46
G
ground terminal 56, 57
H
H350 Detector 11, 50 H350R Detector 11 H355 11 H355HT 11 H355R 11 Heat Detector 50
I
I300 21
I300 Isolator Module 10 Initiating Device Circuits 25, 31, 33, 35 integral relay 21 Ionization Detector 50 Isolator Module 10
how it works 21 wiring of 21
isolator modules 23, 24
K
key-lock reset 52
L
LEDs 50 LiteSpeed 10 local building code 55 loop resistance 14, 15 loops 15
M
MDF-300 Dual module 10, 25, 35 MDF-300 module
wiring 35 metal conduit 16, 23 minimum resistance 53 MMF-300 module 10, 25, 31, 32 MMF-300-10 Module 10 MMF-300-10 module 27, 33, 34
wiring 33, 34 MMF-301 module 10, 25 MMF-302 module 10, 25, 36, 37
wiring 36 MMF-302-6 Interface Module 10 MMF-302-6 module 28, 38, 39
wiring 38 module circuits 25 modules
addressable 10
control 11
isolator 10
monitor 10
relay 11 Monitor Modules 10, 25 Multicriteria Detector 50 Multi-Point Module 30
N
NAC power 40 NAC wiring 40 NEC Article 800 55 NFPA Style 4
wiring of 19
with I300 22 NFPA Style 6
wiring of 20
with I300 23
The SLC Wiring Manual PN 51309:K 2/14/08 61
Page 62
Index
NFPA Style 7 21
with isolator modules 24
NFPA Style B
IDC wiring 31, 33, 35, 36, 38
NFPA Style D
IDC wiring 32, 34, 37, 39
NFPA Style Y 40
wiring of 41, 45
NFPA Style Z 40
wiring of 42, 46 Nonresettable power 17 normally closed contacts 54 Notification Appliance Circuit 11 notification appliances 54
O
older version and newer version mod­ules 8
P
performance 12 Photoelectric Detector 50 PLP-42N 55 Polling Protocols 10 power run 53, 54 power supervision relay 41, 42, 45, 46, 54 proper gauge wire 53 Pull Station 12 pull station 24
wiring of 52
R
RA400Z 50 rate of rise 11 ratings, relay contact 40, 47 relay contact ratings 40, 47 Relay Module 11 relays
Form-C 11 Remote LED Annunciator 50 Resettable power 17 resistance 14, 15 rotary switches 29, 34, 35, 36, 37, 38, 39, 50
SLC terminal block 16 SLC wiring 31, 32, 33, 34, 35, 36, 37, 38, 39 SLCP-030 55 Smoke Detectors 50 Sprinkler supervision 29 supervised
circuit 54
devices 54 supplying power 53 suppressors, surge 55 surge protector 10, 12, 55 switching 40
T
terminal blocks 17 termination of shield 16 Thermal Detector 50 thermistor sensing circuit 11 trouble conditions 12, 21 T-tapping 14, 19, 20, 23, 24 twisted-pair shielded wiring 13 two-wire configuration 41, 45
U
Unregulated power 17
V
verification cycle 50
W
Waterflow alarm service, automatic and manual 29 wire length 14, 15 wire size 13 wiring
NACs 40
of an isolator module 21 wiring pair 55 wiring requirements 13 wiring style requirements 12
S
SD350 Detector 11, 50 SD350T Detector 11 SD355 11 SD355T 11 sensing circuit, thermistor 11 short circuit 21 Signaling Line Circuit 10 Single Point Module 29 SLC address, setting of 29, 50 SLC connections 17
62
The SLC Wiring Manual PN 51309:K 2/14/08
Page 63
Limited Warranty
Honeywell International Inc. warrants products manufactured by it
to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufa cture. The sole and exclusive obligation of Honeywell International Inc. is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. Honeywell International Inc. does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than Honeywell
International Inc. or as expressly authorized by Honeywell International Inc. in writing, or is serviced by anyone other than Honeywell International Inc. or its authorized distributors. This
warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products. Honeywell International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Honeywell International Inc., is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PA RTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE F ACE HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE HONEYWELL
INTERNATIONAL INC.’S PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by Honeywell International Inc. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
Warn-HL-05-2007.fm
Page 64
World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.firelite.com
Loading...