BG12LOBface.wmf
Dual Action BG-12LOB
BG-12LO/-12LOB Manual Pull Station
(Listed for Outdoor Applications)
Document 51378 Revision A ECN 00-215 06/16/2000
Description
The BG-12LOB Pull Station is a non-coded manual pull station
which provides a Fire Alarm Control Panel (FACP) with a single
alarm initiating input signal. The pull station is a dual action
model equipped with a key lock reset, an approved outdoor
gasket, and an accompanying outdoor backbox. It is UL listed
and meets the ADA requirement of a 5-lb. maximum pull down
force to activate. Operating instructions are molded into the
handle. Molded terminal numbers can also be found adjacent
to the wiring terminals.
BG-12LOB
The features of the pull station include Dual-Action operation,
Key-Lock Reset function, Screw Terminal Wire connections,
outdoor use gasket, a WBB outdoor approved 4-inch backbox,
and a sealed switch with gold-plated switch contacts.
Note: The BG-12LOB is applicable with the WP-10 backbox
in retrofit applications. To meet UL requirements for outdoor
use, the BG-12LO Pull Station must be mounted to the WBB or
WP-10 Backbox to create the BG-12LOB model.
Switch Contact Rating
FACP Circuit (Terminals 1 & 2):
Rated to .25 Amp at 30 Volts (AC or DC).
Door ‘keys’ into
backplate at this point
Pos t
UL
Product ID
Label
Hole
Post
Hole
Post
Door mated to Backplate
at this stage.
Door Attachment
If the door becomes detached, complete the following steps to
reattach the door to the backplate. The door cannot be connected
to the pull station if the unit is mounted to a backbox.
With the door and backplate
aligned and ‘keyed’ together,
slide the holes down onto the
posts.
UL
Product ID
Label
Closing the door slightly
locks the door and
backplate together.
1. Position the door and backplate side
by side in the full open position. (i.e.
180-degrees with respect to each
other.)
2. With the backplate position fixed,
move the door behind the backplate,
as shown in the illustration, part A.
3. Align the hinge posts and holes by
bringing the door up to meet the
backplate, paying particular attention
to the ‘keying’ that occurs when the
door’s post hole is aligned to the
backplate’s hinge post. Refer to the
illustration, part B.
4. With the two pieces aligned and
12LAdoormount.wmf
‘keyed’ together, slide the holes
down onto the posts. Refer to the
illustration, part C.
5. Holding the backplate, close the door
slightly to lock the door and backplate
together.
Wiring Instructions
1) Surface mount the supplied Outdoor Backbox (WBB) using
the side flanges incorporate into the backbox design. The
box can be positioned to allow conduit connection from
any side. The pull station will mount in any position desired.
2) Before mounting the pull station, pull all necessary wiring
through the backbox.
3) Remove the correct amount of wire insulation. The pull
station’s backplate is molded with a strip gauge to measure
the amount of insulation to be removed.
4) Connect the wiring from the fire alarm control panel’s
Initiating Device Circuit (IDC), or any previous device on
the IDC to terminals 1 and 2 located on the pull station’s
terminal strip. Connect the next device on the IDC or Endof-Line Resistor (ELR) to terminals 1 and 2.
Note: Maintain consistent polarity with all connections
throughout the IDC.
Outdoor Stations
Install the BG-12LO with a listed, outdoor-approved backbox
(WBB or WP-10) to meet UL requirements for outdoor use.
Without one of these backboxes, the BG-12LO is not listed for
outdoor applications. Use the four supplied 8-32 x .375"
mounting screws to attach the Pull Station to the outdoorapproved backbox.
BG-12LO + WBB
= BG-12LOB
12LOBmount.wmf
From FACP
IDC
23
23
23
23
23
23
23
23
23
23
23456
To Next Device
IDC
Operation
To activate the dual-action station, first push in the handle, and
then pull the handle down. The handle locks into the activated
position. The word ‘ACTIVATED’ appears after the handle is
pulled down. The pull station remains in the activated position
until reset with the key lock.
1) Reset the BG-12LOB by
inserting the key into the
lock and turning it ¼ turn
(counter-clockwise).
2) Open the door until the
handle returns to the
‘NORMAL’ position.
3) Close and lock the door.
Closing the door auto-
12lobwiring.wmf
Outdoor-Use Gasket
(Does not cover any
user-serviced connections)
matically resets the switch
to the ‘NORMAL’ position. Note: Opening the
pull station door will not
activate or deactivate the
FACP alarm switch.
BG12LOBact.wmf
BG-12LOB
Pull Station
(Shown Activated)
CAUTION
Install the pull station in accordance with the supplied instructions, applicable NFPA standards, national and local Fire and Electrical
codes and the requirements of the Authority Having Jurisdiction (AHJ). Conduct regular testing of the devices using appropriate
NFPA standards. Fire•Lite is not responsible for devices that have not been properly installed, tested or maintained. For ADA
compliance, if the clear floor space only allows forward approach to an object, the maximum forward reach height allowed is 48 inches
(121.92cm). If the clear floor space allows parallel approach by a person in a wheelchair, the maximum side reach height allowed is
54 inches (137.16cm).
Document 51378 Revision A ECN 00-215 06/16/2000