E (Festo AG & Co. KG, D73726 Esslingen, Federal Republic of Germany, 2007)
Internet: http://www.festo.com
E−Mail: service_international@festo.com
The copying, distribution and utilization of this document
as
well as the communication of its contents to others
without expressed authorization is prohibited. Violations
give rise to compensation. All rights are reserved, in particu
lar the right to carry out patent, utility model or ornamental
design registration.
Festo P.BE−CPX−EA−EN en 0705f
I
Contents and general instructions
CAGE CLAMP® is a registered trade mark of WAGO Kontakttechnik GmbH,
32385 Minden, Germany
TORX® is a registered trade mark of CAMCAR TEXTRON INC.,
Rockford, Ill., USA
HARAX® is a registered trade mark of HARTING Deutschland GmbH,
32381 Minden, Germany
SPEEDCON® is a registered trade mark of PHOENIX CONTACT
The CPX pneumatic interfaces, MPA pneumatic modules and
CPX I/O modules described in this manual have been de
signed exclusively for use in conjunction with CPX terminals
from Festo. The pneumatic interfaces and I/O modules are
only to be used as follows:
as specified in industrial applications
without any modifications by the user
In perfect technical condition.
If additional commercially−available components such as
sensors and actuators are connected, the specified limits for
pressures, temperatures, electrical data, torques, etc. must
not be exceeded.
Please observe the standards specified in the relevant
chapters and comply with
with national and local regulations.
the conversions or modifications described in the
Only
documentation supplied with pro duct are permitted.
technical regulations, as well as
Festo P.BE−CPX−EA−EN en 0705f
Warning
· In order to provide the electric power supply, use only
PELV circuits as per IEC/DIN EN 60204−1 (Protective
Extra−Low Voltage, PELV).
Take into account also the general requirements for
PELV circuits as per IEC/DIN EN 60204−1.
· Use only power packs which guarantee reliable electri
cal isolation of the operating voltage as per
IEC/DIN EN 60204−1.
By the use of PELV power units, protection against electric
shock (protection against direct and indirect contact) is guar
anteed in accordance with IEC/DIN EN 60204−1 (electrical
equipment of machines, general requirements).
VII
Contents and general instructions
Target group
This manual is intended exclusively for technicians trained in
control and automation technology, who have experience in
installing, commissioning, programming and diagnosing pro
grammable logic controllers (PLC) and field bus systems.
Service
Please consult your local Festo Service if you have any techni
cal problems.
VIII
Festo P.BE−CPX−EA−EN en 0705f
Contents and general instructions
Important user instructions
Danger categories
This manual contains instructions on the possible dangers
which can occur if the product is not used correctly. These
instructions are marked (Warning, Caution, etc), printed on
a shaded background and marked additionally with a picto
gram. A distinction is made between the following danger
warnings:
Warning
... means that failure to observe this instruction may result
in serious personal injury or damage to property.
Caution
... means that failure to observe this instruction may result
in personal injury or damage to property.
Festo P.BE−CPX−EA−EN en 0705f
Note
... means that failure to observe this instruction may result
in damage to property.
The following pictogram marks passages in the text which
describe activities with electrostatically sensitive compo
nents.
Electrostatically sensitive devices: Incorrect handling can
result in damage to components.
IX
Contents and general instructions
Identifying special information
The following pictograms mark passages in the text which
contain special information.
Pictograms
Information
Recommendations, tips and references to other sources of
information.
Accessories:
Information on necessary or useful accessories for the Festo
product.
Environment:
Information on the environment−friendly use of Festo prod
ucts.
Text markings
· The bullet indicates activities which may be carried out in
any order.
1. Figures denote activities which must be carried out in the
numerical order specified.
Hyphens indicate general activities.
X
Festo P.BE−CPX−EA−EN en 0705f
Contents and general instructions
Notes on the use of this manual
This manual contains general basic information on the
method of operation, on fitting and installing CPX pneumatic
interfaces, MPA pneumatic modules and CPX I/O modules.
General basic information on the method of operation, on
fitting, installing and commissioning CPX terminals can be
found in the CPX system manual.
Special information on commissioning, parametrizing and
diagnosing a CPX terminal with the field bus node you are
using can be found in the appropriate manual for the field
bus node.
Information on further CPX modules can be found in the
manual for the relevant module. An overview is provided in
table Tab.0/4.
Festo P.BE−CPX−EA−EN en 0705f
Conventions
The special parameters of the modules are
described in the
individual chapters. These appear in English on the Handheld
type CPX−MMI−1.
XI
Contents and general instructions
Structure of a CPX terminal
CPX terminals consist of electric function modules, individual
modules and components. The diagram below shows an
example:
1234
1 Field bus node
2 I/O modules
3 Pneumatic interface
4 Pneumatic modules
(example MPA)
Fig.0/1: Example of CPX terminal
XII
5
6
7
8
5 Manifold sub−base with additional power
supply
6 Manifold sub−base without supply
7 Manifold sub−base with system supply
8 End plate
Festo P.BE−CPX−EA−EN en 0705f
Contents and general instructions
CPX−AB−8−M8−4POL
CPX pneumatic interfaces and MPA pneumatic modules
An overview of the CPX pneumatic interfaces can be found in
Tab.1/1 and of the MPA pneumatic modules in Tab.2/1.
CPX I/O modules
I/O modulesType
ManualSub−bases and
designation
CPX−4DE
CPX−8DE
CPX−16DE
CPX−8DE−D
CPX−8NDE
CPX−4DA
CPX−8DA
CPX−8DA−H
CPX−8DE−8DAMulti I/O module
Input modules
with 4, 8 or 16 in
puts, PNP
Input module with
8 inputs and chan
nel diagnosis, PNP
Input module with
8 inputs, negative
logic, NPN
Output module
with 4 outputs,
PNP
Output module
with 8 outputs,
PNP
High−current out
put module with
8outputs, PNP
(input/output
module) with 8 in
puts and 8 out
puts, PNP
manifold sub−bases
The I/O modules each con
sist of the electronic mod
ule as well as a sub−base
and a manifold sub−base.
Sub−bases:
(Note the possible combina
tions in section 3.2.2).
CPX−AB−4−M12x2−5POL
CPX−AB−4−M12x2−5POL−R
CPX−AB−8−M8−3POL
The I/O modules each con
sist of the electronic mod
ule as well as a sub−base
and a manifold sub−base.
Sub−base:
CPX−M−8−M12x2−5POL
Manifold sub−bases:
CPX−GE−EV
CPX−GE−EV−...
XIV
Festo P.BE−CPX−EA−EN en 0705f
Contents and general instructions
Diagnosis via the field bus
Depending on the parametrization, CPX pneumatic interfaces
and CPX I/O modules register specific faults via the field bus.
These can be evaluated via the:
status bits (system status)
I/O diagnostic interface (system diagnosis)
module diagnosis
fault numbers
Further information on diagnosis can be found in the CPX
system manual or in the manual for the
field bus node.
Festo P.BE−CPX−EA−EN en 0705f
XV
Contents and general instructions
TypeTitleManual
Electronics
Manual
Electronics
Manual
Software
package
System manual"
Type P.BE−CPX−SYS−...
CPX field bus node"
Type P.BE−CPX−FB...
CPX I/O modules"
Type P.BE−CPX−EA−...
CPX analogue I/O
modules"
Type P.BE−CPX−AX−...
CPX−CP interface"
Type P.BE−CPX−CP−..
Handheld"
Type P.BE−CPX−MMI−1−..
CPX−FEC"
Type P.BE−CPX−FEC−...
FST"Programming in Statement List and Ladder
Overview of structure, components and
method of operation of CPX terminals;
installation and commissioning instructions
as well as basic principles of parametrizing
Instructions on fitting, installing, commission
ing and diagnosing the relevant field bus node
Notes on connection types and instructions on
fitting, installing and commissioning input and
output modules of type CPX−... , the MPA pneu
matic modules, as well as MPA, CPA and Midi/
Maxi pneumatic interfaces
Notes on connection types and instructions
on fitting, installing and commissioning
CPX analogue I/O modules
Instructions on fitting, installing, commission
ing and diagnosing CP systems with the
CP interface type CPX−CP−4−FB
Instructions on commissioning and diagnosing
CPX terminals with the Handheld type
CPX−MMI−1
Instructions on fitting, installing,
commissioning and diagnosing the CPX Front
End Controller.
Diagram for the FEC
Tab.0/3:Manuals on the CPX terminal − part 1
XVI
Festo P.BE−CPX−EA−EN en 0705f
Contents and general instructions
TypeTitleManual
Pneumatics
Manual
Valve terminals with
MPA pneumatics"
Type P.BE−MPA−...
Valve terminals with
CPA pneumatics"
Type P.BE−CPA−...
Valve terminals with
Midi/Maxi pneumatics"
type P.BE−MI DI/
MAXI−03−...
Valve terminal with
VTSA/ISO pneumatics"
type P.BE−VTSA−44−...
Instructions on fitting, installing, commission
ing, maintaining and converting the MPA pneu
matics (type 32)
Instructions on fitting, installing, commission
ing, maintaining and converting the CPA pneu
matics (type 12)
Instructions on fitting, installing, commission
ing, maintaining and converting the Midi/Maxi
pneumatics (type 03)
Instructions on fitting, installing, commission
ing, maintaining and converting the VTSA/ISO
pneumatics (type 44)
Tab.0/4:Manuals on the CPX terminal − part 2
Festo P.BE−CPX−EA−EN en 0705f
XVII
Contents and general instructions
The following product−specific terms and abbreviations are
used in this manual:
Term/abbreviation
ADigital output
CPX modulesCommon term for the various modules which can be incorporated in a
CPX terminalModular, electric terminal type 50
Diagnosis D2Additional diagnostic functions of MPA input modules (see section 2.5)
DIL switchesDual−in−line switches consist of several switch elements with which set
EDigital input
Field bus nodeProvides the connection to specific field buses. Transmits control signals
I/O diagnostic interfaceThe I/O diagnostic interface is a bus−independent diagnostic interface at
I/O modulesCommon term for the CPX modules which provide digital inputs and out
I/OsDigital inputs and outputs
Input moduleCPX input module
Manifold sub−baseUpper part of the housing of a module or block for linking the module
MPA electronic moduleElectronic module which provides the electronic functionality including
Meaning
CPX terminal.
tings can be made.
to the connected modules and monitors their ability to function.
I/O level, permitting access to internal data of the CPX terminal.
puts (CPX input modules and CPX output modules).
electrically with the terminal.
the diagnostic functions for the valve solenoid coils of the MPA pneu
matics.
MPA pneumatic modulePneumatic module which provides digital outputs for the valves fitted
Output moduleCPX output module
PLC/IPCProgrammable logic controller/industrial PC
Pneumatic interfaceThe pneumatic interface is the interface between the modular electrical
XVIII
(valve solenoid coils).
periphery and the pneumatics.
Festo P.BE−CPX−EA−EN en 0705f
Contents and general instructions
Term/abbreviationMeaning
Status bitsInternal inputs which supply coded common diagnostic messages.
Sub−baseReplaceable upper part of housing of modules with connections.
The CPX pneumatic interfaces in a CPX valve terminal provide
the connection to the pneumatic modules.
The pneumatic modules enable pneumatic actuators to be
controlled by means of the valves fitted.
Pneumatic
interfaces
Type designationDescriptionConnection to
Pneumatics
VMPA−FB−EPL−...CPX pneumatic interface
VABA−10S6−X1CPX pneumatic interface
CPX−GP−03−4.0CPX pneumatic interface
CPX−GP−CPA−10
CPX−GP−CPA−14
to MPA
for VTSA pneumatics
(ISO, type 44)
to Midi/Maxi
CPX pneumatic interface
to CPA10
CPX pneumatic interface
to CPA14
Pneumatic interface for
connecting the modular
electrical peripherals of
type 50 (CPX) to valve
terminals type 32 (MPA).
Pneumatic interface for
connecting the modular
electrical peripherals of
type 50 (CPX) to VTSA/ISO
valves (type44)
Pneumatic interface for
connecting the modular
electrical periphery type50
(CPX) to valve terminals
type 03 (Midi/Maxi).
Pneumatic interface for
connecting the modular
electrical periphery type50
(CPX) to valve terminals
type 12 (CPA).
Tab.1/1:Overview of pneumatic interfaces
Festo P.BE−CPX−EA−EN en 0705f
1−3
1. Pneumatic interfaces
MPA pneumaticsFrom the technical point of view, the individual MPA pneu
matic modules each represent an electric module with e.g.
8digital outputs for controlling the valves fitted
(seechapter 2).
Please note
The pneumatic interface for MPA pneumatics provides the
mechanical and electrical connection to the MPA pneu
matic modules.
As regards the CPX terminal, this pneumatic interface does
not therefore count as an electric module.
Midi/Maxi pneumatics,
CPA pneumatics or VTSA
pneumatics
From the technical point of view, the pneumatic interfaces
for Midi/Maxi pneumatics, CPA
pneumatics or VTSA pneu
matics (ISO) each represent an electric module with a vari
able (configurable) number of digital outputs for controlling
the valves fitted (see following sections).
1−4
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
1.1.1Display and connecting elements
MPA pneumaticsThe pneumatic interface for MPA pneumatics (type 32)
possesses the following display and connecting elements:
1 Connecting plug to
the MPA pneumatic
modules
1
2 Inscription field
3
3 Connecting plug to
the CPX manifold
sub−bases
Fig.1/1: Display and connecting elements of the pneumatic interface for MPA
pneumatics
2
Festo P.BE−CPX−EA−EN en 0705f
1−5
1. Pneumatic interfaces
VTSA pneumatics (ISO)The pneumatic interface for VTSA pneumatics (ISO, type 44)
possesses the following display and connecting elements:
1 Connecting plug to
the VTSA pneumatic
modules
5
2 Fault LED (red)
1
2
3 Inscription field
4
4 DIL switch under a
transparent cover
5 Connecting plug to
the CPX manifold
sub−bases
Fig.1/2: Display and connecting elements of the pneumatic interface for ISO
pneumatics
3
1−6
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
Midi/Maxi or
CPA pneumatics
1 Pneumatic interface
for Midi/Maxi
pneumatics (type03)
The pneumatic interfaces for Midi/Maxi or CPA pneumatics
possess the following display and connecting elements:
12
2 Pneumatic interface
for CPA pneumatics
(type 12 here
size10)
3
4
3 Connecting plug for
the valves
5
4 Fault LED (red)
5 DIL switch under a
transparent cover
6 Identification fields
7 Connecting plug to
the CPX manifold
sub−bases
Fig.1/3: Display and connecting elements of the pneumatic interface for Midi/Maxi or
CPA pneumatics
77
6
3
4
5
Festo P.BE−CPX−EA−EN en 0705f
Use identification labels type IBS 6x10 for marking the
pneumatic interface for CPA pneumatics.
1−7
1. Pneumatic interfaces
1.2Fitting
Warning
Sudden unexpected movement of the connected actuators
and uncontrolled movements of loose tubing can cause
injury to human beings or damage to property.
Before carrying out installation and maintenance work,
switch off the following:
the compressed air supply
the operating and load voltage supplies.
The CPX terminal must first be dismantled before it can
be
extended or converted, or when a pneumatic interface must
be replaced. Instructions on this can be found in the CPX
system manual.
Instructions on extending or converting the pneumatic
modules can be found in the appropriate pneumatics manual.
For Midi/Maxi, CPA or ISO pneumatic interfaces:
The setting of the DIL switches for configuring
the pneumatics
(valves used) can be set on the CPX terminal without the need
to disamantle the terminal.
1−8
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
1.3Settings for configuring the pneumatics
Midi/Maxi, CPA or
VTSA pneumatics
Settings for configuring the pneumatics are only necessary
with the pneumatic interfaces for Midi/Maxi, CPA and VTSA
pneumatics (ISO).
No settings are required for MPA pneumatics.
Caution
After conversion or extension of the Midi/Maxi, CPA or
VTSA pneumatics, the number of output addresses occu
pied by the pneumatics must be set on a DIL switch on the
pneumatic interface.
CPX terminals can be fitted with various valves and electric
modules in accordance with the customer’s wishes.
The size of the
valve address range on Midi/Max, CPA or
VTSA pneumatics is not modified when the valves are ex
tended or converted, providing sufficient address space has
already been reserved for the extension. The valve address
range must be set with a DIL switch. The DIL switch is situ
ated under the transparent cover on
the pneumatic interface.
Festo P.BE−CPX−EA−EN en 0705f
Warning
Sudden unexpected movement of the connected actuators
and uncontrolled movements of loose tubing can cause
injury to human beings or damage to property.
Before carrying out installation and maintenance work,
switch off the following:
the compressed air supply
the operating and load voltage supplies.
1−9
1. Pneumatic interfaces
Caution
Modules may be damaged if they are not handled
correctly.
· Do not touch the electrical contacts of the modules.
· Observe the regulations for handling electrostatically
sensitive components.
· Discharge yourself electrostatically before fitting or re
moving components in order to protect the components
against discharges of static electricity.
Please note
Handle all modules and components of the CPX terminal
with great care. Please note especially the following:
· Screws must be fitted accurately (otherwise threads will
be damaged).
Screws must be fastened at first only by hand. Place the
screws so that the self−cutting threads are used.
· The specified torques must be observed.
· Screw connections must be fitted free of offset and
mechanical tension.
· Check the seals for damage (IP65).
· Connecting surfaces must be clean (to ensure sealing
effect, avoid leakage and contact faults).
The screw connection between the cover and the lower
part of the CPA pneumatic interface is designed for at least
10 fitting/removal cycles.
1−10
Removing the cover
1. Loosen the screws in the cover with a TORX screwdriver
size T10.
2. Lift the cover up carefully.
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
3. Set the DIL switch elements in accordance with the follow
ing table. Use a suitable tool, e.g. a small screwdriver, for
setting the DIL switches.
1 Printed circuit
board
2 Fault LED
3 DIL switches for
configuring the
pneumatics
Fig.1/4: DIL switches on the pneumatic interface (here for CPA pneumatics)
The DIL switch contains 8 switch elements. These switch
elements are numbered from 1...8. The positions OPEN (CPA,
VTSA/ISO) or ON (Midi/Maxi) are marked.
1
2
3
Festo P.BE−CPX−EA−EN en 0705f
Rules for setting
If the number of valve solenoid coils fitted is less than the
number of output addresses set with the DIL switch, the
superfluous addresses will be reserved for later exten
sions (if the maximum number of valves is fitted, output
addresses will then remain unused).
Modifications to the configuration will not become
effective until
8 further output addresses per switch element will be
assigned for valves in the address range.
The setting of the highest−value DIL switch in the ON
(closed) position is decisive for the assigned address
range.
In the case of field bus protocols with which, due to the
limiting of the address range, the setting 32 outputs"
(VTSA/ISO or Midi/Maxi) or 24 outputs" (CPA) together
with the CPX equipment fittings would lead to an error, the
DIL switches have been set at the factory according to the
actual
number of valve solenoid coils.
Please note
DIL switch settings which are not represented are not
permitted.
Fitting the cover
1. Check the seal and the surface opposite it for damage or
dirt. If necessary, the seal must be replaced (only with
type CPX−GP−03−4.0) or the surfaces must be cleaned.
Festo P.BE−CPX−EA−EN en 0705f
2. Place the cover carefully into position so that the seal is
not damaged.
With type CPX−GP−CPA−...: Tighten the screws at first only
by hand. Place
the screws so that the self−cutting threads
can be used.
3. Tighten the screws in diagonally opposite sequence with
a TORX screwdriver size T10. Observe the tightening
torques listed in the table below.
Pneumatic interface
Midi/Maxi (type CPX−GP−03−4.0)1.0 ... 1.3 Nm
CPA (type CPX−GP−CPA−...)0.9 ... 1.1 Nm
VTSA (type VABA−10S6−X1)1.2 ... 1.8 Nm
Tightening torque
Tab.1/3:Tightening torques for the pneumatic interfaces
1−13
1. Pneumatic interfaces
1.4Installation
Instructions on installing the pneumatic components can be
found in the relevant pneumatics manual.
Instructions on installing the electric components can be
found in the CPX system manual.
Instructions on addressing the valve solenoid coils as well as
further instructions on installing the electric components can
be found in the relevant field bus
node manual.
Power supply
The 24 V supply for the valves is provided via the load voltage
for the valves of the CPX terminal (V
The power supply for the electronics of the pneumatic inter
faces is provided via the operating voltage supply for the
electronics/sensors (V
EL/SEN
).
VAL
).
1−14
Address assignment within the pneumatic modules
Instructions on assigning the addresses to the individual
valve solenoid coils with Midi/Maxi or CPA pneumatics can be
found in the appropriate pneumatics manual.
Instructions on assigning the addresses to the individual
valve solenoid coils with MPA pneumatic modules can be
found in chapter 2.
Protection class
When completely fitted, the pneumatic interfaces with the
valve terminal pneumatics comply with protection class IP65
(see appendix A.1).
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
1.5Instructions on commissioning
Midi/Maxi, CPA or
VTSA pneumatics
The reaction of the pneumatic interface for Midi/Maxi, CPA
or VTSA pneumatics can be parametrized. The table below
gives an overview of the parameters for the pneumatic
interfaces.
With the MPA pneumatics, parametrizing takes place via the
individual MPA pneumatic modules (module−orientated, see
chapter 2).
Further information on parametrizing can
be found in the
system manual or in the manual for the field bus node.
Please note
Activate the wire−fracture monitoring only for outputs
which also have a valve solenoid coil.
If the wire−fracture monitoring is activated for an output
which does not have a valve solenoid coil, the CPX terminal
will register the fault Wire fracture" when it is switched
on, due to the valve solenoid coil being
incorrectly regis
tered as defective.
Festo P.BE−CPX−EA−EN en 0705f
1−15
1. Pneumatic interfaces
Parameters of pneumatic interfaces types
CPX−GP−03−4.0, CPX−GP−CPA−... and VABA−10S6−X1
Module parameters: Monitoring the CPX module
Function no.4828 + m * 64 + 0m = module number (0...47)
DescriptionMonitoring of the possible faults can be activated or deactivated (suppressed)
Values1 = active
RemarkMonitoring can also be set for the complete CPX terminal
[...] = display in the Handheld
for each module separately. Active monitoring causes the following: The fault is:
sent to the CPX field bus node
displayed by the common module fault LED.
Monitoring
Bit
Description
2
Undervoltage of valves (V
3
Short circuit at the valve (SCV)
0 = inactive
Presetting: bit 2: active;
(see CPX system manual).
bit 3: inactive
VAL
)
[Monitor]
[Monitor Vval]
[Monitor SCV]
[Active]
[Inactive]
Tab.1/4:Monitoring the CPX module
1−16
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
Module parameters:Monitoring wire fracture channel x
fault between the pneumatic interface and the valve coil) is recognized.
[Monitor open circuit Out Ch ...]
[Inactive]
[Active]
Tab.1/5:Monitoring wire fracture channel x (channel−specific)
Module parameters: Fail safe channel x
Function no.Access to these module parameters is made via protocol−specific functions
DescriptionFault mode channel x:Hold last state
RemarkWith the aid of the so−called Fail safe parametrizing, you can specify the signal
(see the manual for the field bus node).
Fault state (presetting)
Fault state channel x:Set output
Reset output (presetting)
status which the outputs are to assume in the event of field bus communication
faults (see also CPX system manual).
Tab.1/6:Fail safe channel x (channel−specific)
Festo P.BE−CPX−EA−EN en 0705f
1−17
1. Pneumatic interfaces
Module parameters: Idle mode channel x
Function no.Access to these module parameters is made via protocol−specific functions
DescriptionOnly relevant for certain field bus protocols.
RemarkWith the aid of the so−called Idle mode parametrizing, you can determine the
(see the manual for the field bus node).
Idle mode channel x:Hold last state
Idle state (presetting)
Idle state channel x:Set output
Reset output (presetting)
signal status which the outputs are to assume when switching is made to the
Idle state (see also CPX system manual).
This parameter is not available with all field bus protocols.
Tab.1/7:Idle mode channel x (channel−specific)
Module parameters: Force channel x
Function no.Access to these module parameters is made via protocol−specific functions
DescriptionForce mode of outputs channel x:Blocked (presetting)
RemarkThe Force function enables the manipulation of signal states detached from
(see the manual for the field bus node).
Force state
Force state of outputs channel x:Set signal
Reset signal (presetting)
actual operating states (see also CPX system manual).
Tab.1/8:Force channel x (channel−specific)
1−18
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
1.6Diagnosis
Midi/Maxi, CPA or
VTSA pneumatics
Specific faults of the pneumatic interfaces are registered or
suppressed depending on the module parametrizing.
The faults are shown on−the−spot by means of the Fault LED
and, if necessary, can be evaluated with the Handheld (MMI).
Depending on the module parametrizing, the faults are sent
to the field bus
node, where they can be evaluated according
to the field bus protocol used.
With the MPA pneumatics, parametrizing takes place via the
individual MPA pneumatic modules (module−orientated, see
chapter 2).
Festo P.BE−CPX−EA−EN en 0705f
1−19
1. Pneumatic interfaces
1.6.1Fault messages of the pneumatic interfaces
Midi/Maxi, CPA or
VTSA pneumatics
Fault number
5Fault in load voltage for valves
11Fault short circuit at valve
DescriptionFault treatment
Load voltage for the valves (V
missing or too low.
Short circuit/overload at the valve
A pneumatic interface can register the following standard
faults:
)
1)
VAL
2)
· Check the load voltage
· Check that the valves are fitted
correctly and check the electrical
connections,
· If necessary, replace the valve
13Fault wire fracture
Monitoring the residual current of the
valve solenoid coils (open load, only
active with 0−signal).
Only relevant for CPA or VTSA pneu
matics.
2)
· Check that the valves are fitted
correctly and check the electrical
connections,
· If necessary, replace the valve
· Correct any faulty parametrizing (e.g.
with reserved valve locations/blank
ing plates, see section 1.3)
1)
Tolerance range of the load voltage supply V
2)
Number of the faulty channel: see module diagnostic data.
see Technical specifications" in the appendix.
VAL
Tab.1/9:Fault messages of the pneumatic interface for Midi/Maxi, CPA or VTSA
pneumatics
1−20
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
1.6.2LED display
Midi/Maxi, CPA or
VTSA pneumatics
CPX−GP−03−4.0CPX−GP−CPA−...VABA−10S6−X1
There is an LED under the transparent cover for diagnosing
these pneumatic interfaces.
111
1 Fault LED (red)
Fig.1/5: LED display of the pneumatic interfaces
Festo P.BE−CPX−EA−EN en 0705f
1−21
1. Pneumatic interfaces
LED lights up
Fault LED
Midi/Maxi, CPA or
VTSA pneumatics
The red fault LED of these pneumatic interfaces indicates
the faults of the pneumatic interface depending on the
parametrization.
Fault LED
(red)
LED is out
LED lights up
SequenceStatusFault
number
ON
OFF
ON
OFF
Faultless operationNone
Fault in load voltage for valves
Load voltage for the valves (V
missing or too low.
Fault short circuit at valve
Short circuit/overload at valve
Wire fracture fault
Monitoring the residual current of
the valve solenoid coils (open load,
only active with 0−signal).
Only relevant for CPA or VTSA pneu
matics.
VAL
5See section
)
11
13
Fault
treatment
1.6.1, Tab.1/9.
Tab.1/10: Fault LED for pneumatic interfaces Midi/Maxi, CPA or VTSA pneumatics
The fault indicated by the red fault LED is transmitted by the
pneumatic interface to the field bus node (unless parame
trized otherwise).
1−22
Status LEDs of the valve solenoid coils
The yellow status LEDs on the valve solenoid coils indicate
the status of the relevant output (see appropriate pneumatics
manual).
Festo P.BE−CPX−EA−EN en 0705f
1. Pneumatic interfaces
1.6.3Fault treatment and parametrizing
Midi/Maxi, CPA or
VTSA pneumatics
The following diagram shows the fault treatment of the pneu
matic interface for Midi/Maxi, CPA or VTSA pneumatics.
Further registering and display of the faults can be sup
pressed as desired with the appropriate module parameters,
represented in the diagram as switches. The parameters are
described in section 1.5.
Fault message to
field bus node
Monitoring
01010101
V
VAL
Fault no. 5
Fault in load
voltage for
valves
Fault no. 11
Fault short
circuit at valve,
channel 0
Module
fault LED
Monitoring
SCV
Fault no. 11
...
Fault short
circuit at valve,
channel x
Monitoring
Wire fracture
Channel 0
Fault no. 13
Fault wire
fracture,
channel 0
...
...
Fault no. 13
Fault wire
fracture,
channel x
1
Monitoring
Wire fracture
channel x
2
3
1 Module parameters (switch position represented = default setting)
2 Module−specific fault
3 Channel−specific faults (fault no. 13 only with CPA or VTSA pneumatics)
Fig.1/6: Principle of fault treatment and parametrizing of the pneumatic interface for
In the CPX terminal the MPA pneumatic modules provide
digital outputs for controlling the valves and thus enable
pneumatic actuators to be controlled.
From a technical point of view, the individual pneumatic
modules each represent a separate electric module with
digital outputs.
Without intermediate electrical supply (see section 2.3)
maximum 8 MPA pneumatic modules
terminal. Up to 64 valve solenoid coils (exclusively MPA1) or
32valve solenoid coils (exclusively MPA2) are therefore
possible.
With intermediate electrical supply (see section 2.3) maxi
mum 16 MPA pneumatic modules are permitted per CPX
terminal. Up to 128 valve solenoid coils (exclusively MPA1)
or 64valve solenoid coils (exclusively MPA2)
possible.
are permitted per CPX
are therefore
1 Valve plates or
blanking plates
2 Electronic module
3 Sub−base
Fig.2/1: Components of an MPA pneumatic module (example MPA1)
Festo P.BE−CPX−EA−EN en 0705f
1
2
3
2−3
2. MPA pneumatic modules
TypeDescription of the MPA pneumatic module
MPA1 pneumatic module: Output module with MPA
VMPA1−FB−EM...
VMPA1−FB−AP−4−1
VMPA1−M1H−...
VMPA1−RP
pneumatics, consisting of:
Electronic module with 8 outputs
Variants and description see Tab.2/2
Sub−base for 4 valve plates
Valve plates (or corresponding pneumatic
components) or
Cover plates for reserve locations.
MPA1
MPA2 pneumatic module: Output module with MPA
VMPA2−FB−EM...
VMPA2−FB−AP−2−1
VMPA2−M1H−...
VMPA2−RP
pneumatics, consisting of:
Electronic module with 4 outputs
Variants and description see Tab.2/2
Sub−base for 2 valve plates,
Valve plates (or corresponding pneumatic
components) or
Cover plates for reserve locations.
MPA2
Outputs correspond to valve solenoid coils
Tab.2/1:Overview of MPA pneumatic modules
2−4
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
The electrical function of an MPA pneumatic module is deter
mined by the electronic module used. The following table
provides an overview of the MPA electronic modules:
Type
VMPA1−FB−EMG−88 outputs
VMPA1−FB−EMS−88 outputs
VMPA1−...
VMPA2−FB−EMG−44 outputs
VMPA2−FB−EMS−44 outputs
VMPA2−...
Outputs correspond to valve solenoid coils
Description of the electronic module
with electrical isolation
without electrical isolation
with electrical isolation
without electrical isolation
Tab.2/2:Overview of the MPA electronic modules
Festo P.BE−CPX−EA−EN en 0705f
2−5
2. MPA pneumatic modules
2.1.1Display and connecting elements
The MPA pneumatic modules possess the following display
and connecting elements:
1 LEDs: see sections
2.5.1 and 2.5.2
12
2 Connecting plug to
further MPA pneu
matic modules
3 Manual override
5
1357
0246
4 Label supports with
inscription field
5 Connecting plug to
the CPX pneumatic
interface or to further
MPA pneumatic
modules
Fig.2/2: Display and connecting elements (example: MPA1)
Use sign supports type VMPA1−ST−1−4 for identification of the
MPA pneumatic modules.
3
4
2−6
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
2.2Fitting
Warning
Sudden unexpected movement of the connected actuators
and uncontrolled movements of loose tubing can cause
injury to human beings or damage to property.
Before carrying out installation and maintenance work,
switch off the following:
the compressed air supply
the operating and load voltage supplies.
The CPX terminal must first be dismantled before it can
be
extended or converted, or when a pneumatic interface must
be replaced. Instructions on this can be found in the CPX sys
tem manual.
Instructions on extending or converting the MPA pneumatic
modules can be found in the appropriate pneumatics manual.
Electronic modules or valve plates can be replaced on the
fitted CPX terminal.
Caution
Modules may be damaged if they are not handled
correctly.
· Do not touch the electrical contacts of the modules.
· Observe the regulations for handling electrostatically
sensitive components.
· Discharge yourself electrostatically before fitting or re
moving components in order to protect the components
against discharges of static electricity.
Festo P.BE−CPX−EA−EN en 0705f
2−7
2. MPA pneumatic modules
Please note
Handle all modules and components of the CPX terminal
with great care. Please note especially the following:
· Screws must be fitted accurately (otherwise threads will
be damaged).
Screws must be fastened at first only by hand. Place the
screws so that the self−cutting threads are used.
· The specified torques must be observed.
· Screw connections must be fitted free of offset and
mechanical tension.
· Check the seals for damage (IP65).
· Connecting surfaces must be clean (to ensure sealing
effect, avoid leakage and contact faults).
Dismantling the electronic module
1. Use a screwdriver with a narrow blade to loosen the
fastening screws of all valve or blanking plates and
remove the plates from the sub−bases.
2−8
2. Loosen the screws with which the electronic module is
fastened to the sub−base.
3. Pull the electronic module upwards out of the body of the
sub−base.
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
1 Fastening screws of
the valve plate or
blanking plate
1
2 Valve plates or
blanking plates
3 Flat seals
9
8
4 Electronic module
5 Sub−base
6 Inscription label
holder
7
7 Sealing lip of the
electronic module
8 Fastening screws of
the electronic module
9 2 conical ring seals
per valve plate or
blanking plate
Fig.2/3: Dismantling and fitting the electronic module (example MPA1)
2
3
4
5
6
Festo P.BE−CPX−EA−EN en 0705f
2−9
2. MPA pneumatic modules
Fitting the electronic module
Caution
Replace an electronic module only by an electronic module
of the same type (see section 2.3).
Please note
Before fitting, check the condition and position of the
following seals:
the sealing lip of the electronic module
the ring seal of the electrical contacts
the flat seal of the valve plates or blanking plates.
1. Place the electronic module in the sub−base.
2. Tighten the screws of the electronic module with
0.2...0.25Nm.
2−10
3. Then fit
the valve plates or blanking plates. Check the
seals of the valve or blanking plates for damage. Replace
seals if they are damaged.
4. Make sure that the seals are seated correctly.
The flat seal between the sub−base and the component
must be seated in the recess in the component. The ring
seals between
the electronic module and the component
are conical. The ring seals must be fitted on the guide
pins of the components so that the cone slides easily into
the appropriate recess in the electronic module
(seeFig.2/3).
5. Place the components on the sub−base.
6. Screw the components at first only slightly and then
tighten with 0.2
... 0.25 Nm.
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
2.3Installation
Instructions on installing the pneumatic components can be
found in the Pneumatics Manual type P.BE−MPA−...
Instructions on installing the electric components can be
found in the CPX System Manual.
Instructions on addressing the valve solenoid coils as well as
further instructions on installing the electric components can
be found in the relevant field
bus node manual.
Power supply
The 24 V supply for the valves is provided via the load voltage
for the valves of the CPX terminal (V
The power supply for the electronic modules is provided via
the operating voltage supply for the electronics/sensors
EL/SEN
).
(V
VAL
).
Festo P.BE−CPX−EA−EN en 0705f
Caution
Damage to components and functional damage!
It is not permitted to supply voltage to MPA pneumatic
modules with electronic modules without electrical isola
tion via a manifold sub−base type CPX−GE−EV−V... (valve
supply) or CPX−GE−EV−S−7/8−5POL (5−pin system supply).
· If your MPA pneumatics are fitted with electronic mod
ules of type VMPA1−FB−EMS−... or VMPA2−FB−EMS−...,
you must supply the MPA pneumatics exclusively via a
4−pin system supply module type CPX−GE−EV−S or CPX−
GE−EV−S−7/8−4POL.
Note the overview in Tab.2/3.
2−11
2. MPA pneumatic modules
Note that MPA electronic modules may only be supplied with
power via the following supply modules:
MPA electronic
Permitted supply modules (type)
module
VMPA1−FB−EMS−...
VMPA2−FB−EMS−...
(in each case without
electrical isolation)
VMPA1−FB−EMG−...
VMPA2−FB−EMG−...
(in each case with
electrical isolation)
1)
If a 4−pin system supply module is used, the electrical isolation
will no longer be effective.
System supply module
CPX−GE−EV−S (M18 4−pin) or
System supply module
CPX−GE−EV−S−7/8−4POL (7/8" 4−pin)
Valve supply modules
CPX−GE−EV−V... (M18 or 7/8") or
System supply modules
CPX−GE−EV−S... (M18 or 7/8")
Intermediate electrical ssupply module
(supply plate (electric) type
VMPA−FB−SP−...−V−...)
1)
Tab.2/3:Permitted supply modules modules for MPA
electronic modules
In the case of MPA electronic modules with electrical isolation
type VMPA1−FB−EMG−... or VMPA2−FB−EMG−..., V
V
are completely electrically isolated. In conjunction with
VAL
EL/SEN
and
the following voltage supply modules, it is therefore possible
to switch off the valve supply voltage at all poles:
Manifold sub−base with valve supply type CPX−GE−EV−V...
(M18 or 7/8")
2−12
7/8" manifold sub−base with 5−pin system supply module
type CPX−GE−EV−S−7/8−5POL
Intermediate electrical supply module (supply
plate
(electric) type VMPA−FB−SP−...−V−...)
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
12345
0Vval
6
7
8
24Vval
0Vout
24Vout
0Vel/sen
24Vel/sen
FE
9
0V
24V
24V
1
Manifold sub−base with system supply
FE
n.c.
24V
2 Manifold sub−base without supply
3 Manifold sub−base with electrical
valvesupply
4 MPA pneumatic interface
5 MPA pneumatic modules with
electrical isolation (necessary due to
separate electrical valve supply 3.
Because of this supply, modules
without electrical isolation are not
permitted here.)
0Vval
24Vval
(Pin assignments see CPX System Manual)
0V
FE
6 Load voltage for valves (V
7 Load voltage for digital outputs (V
8 Operating voltage for electronics and
sensors (V
EL/SEN
)
9 5 further rails
VAL
)
)
OUT
Fig.2/4: Circuit diagram of the voltage supply for MPA pneumatic modules with
separate electrical valve supply (see also Tab.2/3)
Festo P.BE−CPX−EA−EN en 0705f
2−13
2. MPA pneumatic modules
123456
0Vval
7
8
9
24Vval
0Vout
24Vout
0Vel/sen
24Vel/sen
FE
aJ
24V0V
24V
(Pin assignments see CPX System Manual)
FE
1 Manifold sub−base with system supply
2 Manifold sub−base without supply
3 MPA pneumatic interface
4 MPA pneumatic module without
electrical isolation.
Not permitted if the load supply V
is provided via a sub−base with
electrical valve supply or 5−pin system
supply (7/8").
VAL
0Vval
24Vval
24V
n.c.
0V FE
6 MPA pneumatic module with electrical
isolation (necessary due to intermedi
ate electrical supply 5)
7 Load voltage for valves (V
8 Load voltage for digital outputs (V
VAL
)
OUT
9 Operating voltage for electronics and
sensors (V
EL/SEN
)
aJ 5 further rails
)
5 Intermediate electrical supply module
(type VMPA−FB−SP−...−V−...)
Fig.2/5: Circuit diagram of the voltage supply for MPA pneumatic modules with
intermediate electrical supply on the pneumatic side (see also Tab.2/3)
Protection class
When completely fitted, the MPA pneumatic modules comply
with protection class IP65 (see appendix A.1).
2−14
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
Address assignment within the pneumatic modules
An MPA1 pneumatic module always occupies 8 output
addresses; an MPA2 pneumatic module always occupies
4output addresses.
Each valve location occupies 2 addresses, irrespective of
whether a valve plate or blanking plate is fitted.
The following assignment applies:
solenoid coil 14 occupies the lower−value address,
solenoid coil 12 occupies the higher−value address.
12
12 14 12 141412141214
12
14
Ox+1
Ox+0
Ox+3
Ox+2
Ox+5
Ox+4
Ox+7
Ox+6
Oy+1
Oy+0
Oy+3
Oy+2
3
4
3
4
7
6
5
5 Valve plates with two solenoid coils
6 Valve plates with one solenoid coil
(addresses Ox+5 unused)
MPA1 pneumatic module
1
2 MPA2 pneumatic module
534
3 Addresses of coil 14 (channel 0, 2, 4, 6)
7 Blanking plate
4 Addresses of coil 12 (channel 1, 3, 5, 7)
Fig.2/6: Example: Address assignment of MPA pneumatic modules (viewed from above)
Festo P.BE−CPX−EA−EN en 0705f
2−15
2. MPA pneumatic modules
2.4Instructions on commissioning
The reaction of the MPA pneumatic modules can be parame
trized. The tables below give an overview of the parameters
for the MPA pneumatic modules.
Further information on parametrizing can be found in the
system manual or in the manual for the field bus node.
2.4.1Parameters of the MPA pneumatic modules
The following parameters apply in general to all electronic
modules of the MPA pneumatic modules.
Module parameters: Monitoring the CPX module
Function no.4828 + m * 64 + 0m = module number (0...47)
DescriptionMonitoring of the possible faults can be activated or deactivated (suppressed) for
Values1 = active (presetting)
RemarkMonitoring can also be set for the complete CPX terminal (see CPX system manual).
each module separately. Active monitoring causes the following: The fault is:
displayed via the fault LEDs.
sent to the CPX field bus node
Monitoring
Bit
Description
2
Undervoltage of valves (V
0 = inactive
VAL
)
[Parameters]
[Monitor Vout/val]
[Active]
[Inactive]
Tab.2/4:Monitoring the CPX module
2−16
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
Module parameters: Fail safe channel x
Function no.Access to these module parameters is made via protocol−specific functions
DescriptionFault mode channel x:Hold last state
RemarkWith the aid of the so−called Fail safe parametrizing, you can specify the signal
(see the manual for the field bus node).
Fault state (presetting)
Fault state channel x:Set output
Reset output (presetting)
status which the outputs are to assume in the event of field bus communication
faults (see also CPX system manual).
Tab.2/5:Fail safe channel x (channel−specific)
Module parameters: Idle mode channel x
Function no.Access to these module parameters is made via protocol−specific functions
DescriptionOnly relevant for certain field bus protocols.
RemarkWith the aid of the so−called Idle mode parametrizing, you can determine the signal
(see the manual for the field bus node).
Idle mode channel x:Hold last state
Idle state (presetting)
Idle state channel x:Set output
Reset output (presetting)
status which the outputs are to assume when switching is made to the Idle state
(see also CPX system manual).
This parameter is not available with all field bus protocols.
Tab.2/6:Idle mode channel x (channel−specific)
Module parameters: Force channel x
Function no.Access to these module parameters is made via protocol−specific functions
(see the manual for the field bus node).
DescriptionForce mode of outputs channel x:Blocked (presetting)
Force state
Force state of outputs channel x:Set signal
Reset signal (presetting)
RemarkThe Force function enables the manipulation of signal states detached from actual
operating states (see also CPX system manual).
Tab.2/7:Force channel x (channel−specific)
Festo P.BE−CPX−EA−EN en 0705f
2−17
2. MPA pneumatic modules
2.5Diagnosis
Specific faults of the MPA pneumatic modules are registered
or suppressed depending on the module parametrizing.
The faults are shown on−the−spot via the fault LEDs and, if
necessary, can be evaluated with the handheld.
VMPA1−..., VMPA2−...MPA pneumatic modules with electronic modules of types
VMPA1−...−8 and VMPA2−...−4 can register the following stan
dard faults:
Fault:Load
voltage for valves (V
VAL
)
2−18
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
2.5.1Composition of the LED display on MPA1
For diagnosing the MPA1 pneumatic modules there is a two−
colour LED for each channel on the electronic modules.
1 LED of the valve
solenoid coils 12
123
(here channel 1)
2 LED of the valve
solenoid coils 14
(here channel 0)
3 Addresses and LED
assignment of the
valve solenoid
coils12
4 Addresses and LED
assignment of the
valve solenoid
coils14
Fig.2/7: LED display of the MPA1 pneumatic modules
1357
0246
12 14 12 14 12 14 12 14
1357
0246
4
3
4
Festo P.BE−CPX−EA−EN en 0705f
2−19
2. MPA pneumatic modules
2.5.2Composition of the LED display on MPA2
For diagnosing the MPA2 pneumatic modules up to software
status SW31.03.06, there is a two−colour LED for each chan
nel on the electronic modules:
1 LED of the valve
solenoid coils 12
(here channel 1)
123
13
02
4
2 LED of the valve
solenoid coils 14
(here channel 0)
12141214
1032
3
3 Addresses and LED
assignment of the
valve solenoid
coils12
4 Addresses and LED
assignment of the
valve solenoid
coils14
Fig.2/8: LED display of the MPA2 pneumatic modules up to software status SW31.03.06
Rev. 4 (type ...−EMS−4) or SW31.03.06 Rev. 3 (type ...−EMG−4)
4
3
4
2−20
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
For diagnosing the MPA2 pneumatic modules up to software
status SW12.04.06, there are separate LEDs for switching
status (yellow) and diagnosis (red) for each channel on the
electronic modules:
1 LEDs of the valve
solenoid coils
1
2
3
(example of channel
assignment)
LEDs channel 1
LEDs channel 0
LEDs channel 3
LEDs channel 2
2 Yellow LED of the
valve solenoid coils12
(channel x+1)
12141214
1032
3 Red LED of the valve
solenoid coils 12
(channel x+1)
4 Yellow LED of the
valve solenoid coils14
(channel x+0)
5 Red LED of the valve
solenoid coils 14
(channel x+0)
Fig.2/9: Separate display with yellow and red LEDs on MPA2 pneumatic modules up to
software status SW12.04.06 Rev. 5 (type ...−EMS−4) or
SW12.04.06 Rev. 4 (type ...−EMG−4).
4
5
Festo P.BE−CPX−EA−EN en 0705f
2−21
2. MPA pneumatic modules
2.5.3LED messages for MPA electronic modules with standard diagnosis
The yellow LEDs indicate the status of the relevant output
(see also appropriate pneumatics manual).
The red LEDs indicate the faults of the MPA pneumatic mod
ule depending on the parametrizing. If the module fault Load
voltage for valves" occurs, all red LEDs will light up.
MPA electronic modules VMPA1−...−8 and VMPA2−...−4
LED
(yellow/red)
LED is out
SequenceStatusFault
number
ON
OFF
Faultless operation
Status of assigned channel logical 0
None
Fault
treatment
(output supplies 0−signal)
ON
OFF
lights up
yellow
ON
OFF
lights up red
1)
Tolerance range of the load voltage supply V
Field marked grey: Note the instruction for MPA1 below.
Faultless operation
Status of assigned channel logical 1
(output supplies 1−signal)
Fault in load voltage for valves
Load voltage for valves (V
VAL
)
missing or too low.
see Technical specifications" in the appendix.
VAL
None
5· Check the
load voltage
Tab.2/8:LED messages of the MPA electronic modules VMPA1−...−8 and VMPA2−...−4
2−22
Festo P.BE−CPX−EA−EN en 0705f
2. MPA pneumatic modules
Please note
In Tab.2/8 the grey−marked fault message of the red LED
there appears orange when the message is displayed
together with the yellow status LED (applies only to MPA1
pneumatics as from SW12.04.06 Rev. 7 (type ...−EMG) or
SW12.04.06 Rev. 8 (type ...−EMS)).
Check by means of the fault number to ascertain which
fault has occurred (diagnostic message to the field bus or
with the Handheld).
The fault Load voltage for valves" is sent to the field bus
node by the MPA electronic module (if not parametrized
differently, see section 2.4.1).
Please note
With MPA electronic modules the fault Load voltage for
valves" will be displayed depending on the hardware and
software status or channel−by−channel.
The following table provides an overview:
Fault in load voltage for valves
Fault is registered for the complete
module (Module fault, channel no. 1)
Tab.2/9:Message of the fault Load voltage for valves" with different software states
(SW)
The fault Load voltage for valves" is sent to the field bus
node by the MPA electronic module (if not parametrized
differently, see section 2.4.1).
Festo P.BE−CPX−EA−EN en 0705f
2−23
2. MPA pneumatic modules
2.5.4Fault treatment and parametrizing
Depending on the module parametrizing, the faults are sent
to the field bus node, where they can be evaluated according
to the field bus protocol used.
The following diagram show the fault treatment in the MPA
pneumatic modules. Further registering and display of the
faults can be suppressed as desired with the appropriate
module
parameters, represented here as switches.
The parameter is described in section 2.4.
Fault message to
field bus node
01
Fault no. 5
Fault in load
voltage for
valves
Fault LEDs
Monitoring
V
VAL
1 Module parameters
(switch position represented = default setting)
2 Module−specific faults
Fig.2/10: Principle of fault treatment and parametrizing
(MPA pneumatic modules VMPA1−...−8 and
VMPA2−...−4)
The sub−base provides the electrical connections in the
form of different sockets or terminal strips.
The electronic module contains the printed circuit board
with the electronics and the LED display of the I/O mod
ule. The electronic module is fitted into the sub−base and
is connected to
means of electric plug connectors.
The manifold sub−base as the lower part of the housing
provides the mechanical and electrical link between the
module and the valve terminal.
this and to the manifold sub−base by
1 Sub−base with
specific
connections
2 Electronic
module
1
3 Manifold
sub−base
Fig.3/1: Components of an I/O module (representation)
Festo P.BE−CPX−EA−EN en 0705f
2
3
3−3
3. Overview and connecting technology I/O modules
3.2Connections
Individual connection requirements can be fulfilled with
different sub−bases. These sub−bases provide the required
sockets or terminal strips for connecting the sensors and
actuators, irrespective of the I/O module used.
Sub−base
TypeDescription
CPX−AB−4−M12x2−5POL4 M12 sockets, 5−pin
Protection class IP 65/IP 67
One functional earth connection per
socket
Screening/shielding possibility via
screening/shield plate (see
Accessories," AppendixA.10)
CPX−AB−4−M12x2−5POL−R4 M12 sockets with metal thread, 5−pin
Protection class IP 65/IP 67
One functional earth connection per
socket
Screening/shielding possibility via
metal thread
enables M12 connectors and
SPEEDCON plug connectors to be
used.
CPX−AB−8−M8−3POL8 M8 sockets, 3−pin
Protection class IP 65/IP 67
Tab.3/1:Connection designs − part 1
3−4
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
Sub−baseTypeDescription
CPX−AB−8−M8−4POL8 M8 sockets, 4−pin
CPX−AB−8−KL−4POL2 terminal strips, 16−pin (4 x 4−pin)
CPX−AB−1−SUB−BU−25POL1 SUB−D socket, 25−pin
Protection class IP 65/IP 67
Protection class IP 20
Protection class IP65/IP67 with
cover AK−8KL and screw connector
set VG−K−M9
All cores can be laid individually in
spring−clip terminals
Connections are in groups of 4, one
functional earth connection per
group
Protection class IP 20
With plug type SD−SUB−D−ST25:
IP65/IP 67 (see Accessories,"
AppendixA.10)
Tab.3/2:Connection designs − part 2
Festo P.BE−CPX−EA−EN en 0705f
3−5
3. Overview and connecting technology I/O modules
Sub−baseTypeDescription
CPX−AB−4−HARX2−4POL4 HARAX connections, 4−pin
CPX−AB−4−M12−8POL4 M12 sockets, 8−pin
Tab.3/3:Connection designs − part 3
Protection class IP 65/IP 67 with the
plugs intended for this purpose (see
Accessories," AppendixA.10)
Insulation−piercing connection
Protection class IP 65/IP 67
Intended for connecting cylinder−
valve combination type DNCV
Connections are arranged in groups,
one functional−earth connection per
group
Screening/shielding possibility via
screening/shield plate (see
Accessories," AppendixA.10)
3−6
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
Sub−base,
TypeDescription
Metal design
CPX−M−4−M12x2−5POL4 M12 sockets with metal thread, 5−pin
CPX−M−8−M12x2−5POL8 M12 sockets with metal thread, 5−pin
Protection class IP 65/IP 67
One functional earth connection per
socket
Screening/shielding possibility via
metal thread
enables M12 connectors and
SPEEDCON plug connectors to be
used.
Protection class IP 65/IP 67
One functional earth connection per
socket
Screening/shielding possibility via
metal thread
enables M12 connectors and
SPEEDCON plug connectors to be
used.
Tab.3/1:Connection designs − part 4 Sub−bases in metal design
Festo P.BE−CPX−EA−EN en 0705f
3−7
3. Overview and connecting technology I/O modules
3.2.1Display and connecting elements
On most input and output modules the LEDs and the module
identification are visible through the transparent cover of the
sub−base (see Fig.3/2). The input module type CPX−
M−16DE−D is an exception (see Fig.3/3).
1 Type plate
2 Module identification
(here 8DI for an input
module type
CPX−8DE)
3 Electrical connections
(example)
5
0
4
1
5
8
DI
2
6
3
7
4 Inscription fields for
addresses
5 LEDs:
Inputs (green)
Outputs (yellow),
Faults (red)
4
Fig.3/2: Display and connecting elements on modules with transparent cover
Use identity labels type IBS 6x10 for marking the addresses.
1
2
3
3−8
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
1 Type plate
2 Electrical
connections
(example)
3
3 LEDs:
Inputs (green)
Outputs (yellow),
Faults (red)
4 Holes for fastening
identity labels
4
Fig.3/3: Display and connecting elements on metal designs
(here CPX−M−8−M12x2−5POL)
Use screws type CPX−M−M2,5X6−12X for fastening the identity
labels.
1
2
Festo P.BE−CPX−EA−EN en 0705f
3−9
3. Overview and connecting technology I/O modules
3.2.2Combinations of I/O modules and sub−bases
The following tables show the permitted combinations of I/O
modules with plastic and metal sub−bases:
Sub−base type
CPX−AB−4−M12x2−5POL
(4 M12 sockets, 5−pin)
CPX−AB−4−M12x2−5POL−R
(4 M12 sockets with
metal thread, 5−pin)
CPX−AB−8−M8−3POL
(8 M8 sockets, 3−pin)
CPX−AB−8−M8−4POL
(8 M8 sockets, 4−pin)
CPX−AB−8−KL−4POL
(2 terminal strips, 16−pin)
CPX−AB−1−SUB−BU−25POL
(1 SUB−D socket, 25−pin)
CPX−AB−4−HARX2−4POL
(4 M12 sockets with in
sulation piercing, 4−pin)
CPX−AB−4−M12−8POL
(4 M12 sockets, 8−pin)
Digital input modules
CPX−4DE
(4 inputs)
CPX−8DE
CPX−8DE−D
CPX−8NDE
(8 inputs)
··
··
··
···
···
··
CPX−16DE
(16 inputs)
·
Can be combined
·
Cannot be combined
Tab.3/2:Permitted combinations of digital input modules with plastic sub−bases
3−10
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
Sub−base typeDigital output modules and multi I/O module
CPX−4DA
(4 outputs)
CPX−8DA
(8 outputs)
CPX−8DA−H
(8 high current
outputs)
CPX−8DE/8DA
(8 inputs and
outputs)
CPX−AB−4−M12x2−5POL
(4 M12 sockets, 5−pin)
CPX−AB−4−M12x2−5POL−R
(4 M12 sockets with
metal thread, 5−pin)
CPX−AB−8−M8−3POL
(8 M8 sockets, 3−pin)
CPX−AB−8−M8−4POL
(8 M8 sockets, 4−pin)
CPX−AB−8−KL−4POL
(2 terminal strips, 16−pin)
CPX−AB−1−SUB−BU−25POL
(1 SUB−D socket, 25−pin)
CPX−AB−4−HARX2−4POL
(4 M12 sockets with in
sulation piercing, 4−pin)
CPX−AB−4−M12−8POL
(4 M12 sockets, 8−pin)
Can be combined
·
Cannot be combined
··
···
··
···
····
····
··
·
Tab.3/3:Permitted combinations of digital output modules and multi I/O modules
with plastic sub−bases
Festo P.BE−CPX−EA−EN en 0705f
3−11
3. Overview and connecting technology I/O modules
Sub−base,
Digital input modules
Metal design
Type
CPX−M−4−M12x2−5POL
(4 M12 sockets with
metal thread, 5−pin)
CPX−M−8−M12x2−5POL
(8 M12 sockets with
metal thread, 5−pin)
Can be combined
·
Cannot be combined
CPX−4DE
(4 inputs)
··
CPX−8DE
CPX−8DE−D
CPX−8NDE
(8 inputs)
CPX−16DE
(16 inputs)
CPX−16DE−D
(16 inputs)
·
Tab.3/4:Permitted combinations of digital input modules with metal sub−bases
Sub−base,
Digital output modules and multi I/O module
Metal design
Type
CPX−M−4−M12x2−5POL
(4 M12 sockets with
metal thread, 5−pin)
CPX−4DA
(4 outputs)
···
CPX−8DA
(8 outputs)
CPX−8DA−H
(8 high current
outputs)
CPX−8DE/8DA
(8 inputs and
outputs)
CPX−M−8−M12x2−5POL
(8 M12 sockets with
metal thread, 5−pin)
Can be combined
·
Cannot be combined
Tab.3/5:Permitted combinations of digital output modules and multi I/O modules
with sub−bases in metal design
3−12
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
3.2.3Connecting the cables and plugs to the sub−bases
Sensors and actuators must be connected to the CPX I/O
modules only at the sub−bases. In this way, e.g. when an elec
tronic module is replaced, the plugs and cables remain fitted
in the sub−base.
Warning
Sudden unexpected movement of the connected actuators
and uncontrolled movements of loose tubing can cause
injury to human beings or damage to property.
Before carrying out installation and maintenance work,
switch off the following:
the compressed air supply
the operating and load voltage supplies.
Festo P.BE−CPX−EA−EN en 0705f
The protection class of the I/O modules depends on the
sub−
base used as well as on the plugs and protective caps used.
Instructions can be found on the following pages and in the
Appendix A.6.
Use plugs and cables from the Festo range for connecting
sensors and actuators (see Appendix A.10).
3−13
3. Overview and connecting technology I/O modules
Sub−basesCPX−AB−4−M12x2−5POL (−R)
CPX−M−4−M12x2−5POL,
CPX−M−8−M12x2−5POL
Note
In order that completely fitted modules with sub−base
CPX−AB−4−M12x2−5POL (−R) or CPX−M−...−M12x2−5POL
comply with protection class IP65/IP 67:
· use plugs and cables from the Festo range for connect
ing the sensors and actuators (see Appendix A.10).
· Tighten the union nuts of the plugs at first by hand.
· Seal unused sockets with protective caps type IS K−M12
(see Appendix A.10: Accessories).
The sub−bases with metal thread (type CPX−AB−4−
M12x2−5POL−R and CPX−M−...−M12x2−5POL) enable fast lock
ing systems to be used, e.g. SPEEDCON from Phoenix Con
tact.
3−14
· When using fast locking systems follow the manufac
turer’s instructions in order to comply with protection
class IP 65/IP 67.
Screening/shield
On plugs without metal housing:
· Connect the cable screening to pin5 (functional
earth FE).
On plugs with metal housing:
· Use the sub−base with metal thread (type CPX−
AB−4−M12x2−5POL−R and CPX−M−...−M12x2−5POL).
The metal thread of this sub−base is connected inter
nally with pin5 (functional earth FE).
or
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
· Connect the cable screening via the plug housing and
the screening plate to FE.
Screening plate type CPX−AB−S−4−12
Sub−base CPX−AB−4−M12x2−5POL (without metal thread) can
be combined with a screening/shield plate. Depending on
what you have ordered, this may already be fitted on the sub−
base.
Instructions on subsequent fitting of the screening/shield
plate can be
found in section 3.3.2.
The electromagnetic compatibility can be improved with
screening/shield plates, e.g. in environments heavily sub
jected to interference or for analogue signals. For this pur
pose the screening/shield plates must be earthed at the flat
contact intended for this purpose as per DIN 46 244 B2,8−1
(2.8 x 1 mm).
Festo P.BE−CPX−EA−EN en 0705f
· Connect the earth cable of the screening/shield plate
with low impedance to the functional earth connection
(FE) as per Fig.3/4.
Screening/shield plates lying next to each other are con
nected together by spring clips and must not be con
nected individually to FE.
If the intended plugs are used (see Accessories," Appendix
A.10), the
plug housing will be connected to functional earth
via the spring contacts on the screening/shield plate.
· Before fitting the plugs screw the spring contacts as far as
possible onto the thread of the plug.
3−15
3. Overview and connecting technology I/O modules
1 Plug
2 Spring contact
3 Screening/shield
plate
4 Functional earth
connection (FE)
with blade
connector as per
DIN46245
B2,8−1
Fig.3/4: Connecting the screening/shield plate
Note
In order to comply with protection class IP 65/IP 67:
· Do not use the spring contacts if you have sealed un
used sockets with protective caps.
1
2
3
4
3−16
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
Sub−bases CPX−AB−8−M8−3POL and −4POL
Note
In order that the completely fitted modules with sub−bases
CPX−AB−8−M8−3POL and −4POL comply with protection
class IP 65/IP 67:
· use plugs and cables from the Festo range for connect
ing the sensors and actuators (see Appendix A.10).
· Tighten the union nuts of the plugs at first by hand.
· Seal unused sockets with protective caps type IS K−M8
(Accessories).
Sub−base CPX−AB−8−KL−4POL
The completely fitted sub−base CPX−AB−8−KL−4POL complies
with protection class IP 20.
Festo P.BE−CPX−EA−EN en 0705f
Specifications of the cable terminals:
Cable cross−sectional area: 0.08 ... 1.5 mm
2
Max. current:see chapter A.6
Insulation removed:5 ... 6 mm
Permitted copper conductors:
single wire, multi−wire, fine wire, also with tin−plated indi
vidual cores
Fine wire strands compressed
Fine wire with core end sleeves (sealed against gas,
crimped on)*)
Fine wire with pin cable socket (sealed against gas,
crimped on)*)
*) If necessary, use next smaller cross−sectional
area
3−17
3. Overview and connecting technology I/O modules
1 Screwdriver, blade
2.5 x 0.4 mm
1
2 Unlocking opening
(inside)
3
3 Cable
4 Terminal opening
for inserting the
conductors (outside)
5 Terminal strips
45
Fig.3/5: Fitting and removing the cables
Fitting and removing the cables
Note
· To ensure reliable contact, connect only one conductor
per spring terminal.
· Insert only cables into the terminal opening. The ter
minal will be damaged if a screwdriver is inserted into
the opening.
1
2
3
4
5
2
3−18
When connecting and disconnecting the cables:
1. Press the screwdriver with a light rotary movement to
wards the centre of the unlocking opening (see Fig.3/5).
The cable terminal will then be unlocked.
2. When the
the ends of the cable through the opening.
terminal is unlocked you can insert or pull out
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
3. Remove the screwdriver from the unlocking opening.
The cable will then be securely locked.
You will then comply with protection class IP65/IP67.
In order that sub−base CPX−AB−8−KL−4POL complies with
protection class IP 65/IP 67, use cover type AK−8KL and
the screw connector set type VG−K−M9 from Festo. Note the
relevant fitting instructions.
1 Cover AK−8KL
2 Screw connector
set VG−K−M9
1
2
Fig.3/6: Cover and screw connector set for sub−base CPX−AB−8−KL−4POL (for complying
with protection class IP65/67)
Sub−base CPX−AB−1−SUB−BU−25POL
The completely fitted sub−base CPX−AB−1−SUB−BU−25POL
complies with protection class IP 20.
In order that sub−base CPX−AB−1−S UB−BU−25POL complies
with protection class IP 65/IP 67, use plug type SD−SUB−
D−ST25 from Festo.
When fitting the plug onto the sub−base, observe the maxi
mum tightening torque of 0.5 Nm.
Festo P.BE−CPX−EA−EN en 0705f
3−19
3. Overview and connecting technology I/O modules
Sub−base CPX−AB−4−HARX2−4POL
Note
In order that completely fitted modules with sub−base
CPX−AB−4−HARX2−4POL comply with protection class
IP 65/IP 67:
· use plugs type SEA−GS−HAR−4POL from the Festo range
(consisting of union nut, strain relief and splicing ring)
for connecting sensors and actuators.
· Tighten the union nuts of the plugs at first by hand.
· Seal the unused connecting sockets with protective
caps from Harting (see Accessories, AppendixA.10).
Specifications of the cables for the sub−base
CPX−AB−4−HARX2−4POL:
Cable cross−sectional area:0.25 ... 0.5 mm
2
3−20
Strand cross−section:up to 0.1 mm
Insulation material:PVC/PUR/PE
Insulation thickness:max. 1.6 mm
Core diameter:1.2 mm ... 1.6 mm
Cable outer diameter:4.0 ... 5.1 mm
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
Mounting
1 Cut the cable to
length and remove
the coating. Push the
union nut and the
seal insert onto the
end of the cable.
2 Insert the ends of
the core into the
appropriate slots
of the splicing ring.
4
3 Place the seal and
the splicing ring to
gether and cut off the
projecting core ends
flush with the splicing
ring.
1
3
2
1
2
3
4 Insert the pre−fitted
splicing seal element
into the contact sup
port in the sub−base.
Screw in the union
nut as far as possible.
Fig.3/7: Connecting the cables to sub−base CPX−AB
Dismantling
· Loosen the screw connector and remove the cores by
pulling them out of the contacts.
The cores can be connected up to 10 times if the contact
ends are cut away each time (if the same core diameter is
used). Cut off the used cable ends and repeat steps 2 to 4.
Festo P.BE−CPX−EA−EN en 0705f
4
3−21
3. Overview and connecting technology I/O modules
Sub−base CPX−AB−4−M12−8POL
Note
In order that completely fitted modules with sub−base
CPX−AB−4−M12−8POL comply with protection class
IP 65/IP 67:
· use cable type KM12−8GD8GS−2−PU from Festo for con
necting the cylinder−valve combination type DNCV or
other sensors and actuators (see AppendixA.10)
· Tighten the union nuts of the plugs at first by hand.
· Seal unused sockets with protective caps type IS K−M12
(Accessories).
Screening plate type CPX−AB−S−4−12
Sub−base CPX−AB−4−M12−8POL can be combined with a
screening plate. This can be ordered separately as an acces
sory.
3−22
Instructions on subsequent fitting of the screening/shield
plate can be found in section 3.3.2.
Instructions on using the screening plates can be found with
sub−base CPX−AB−4−M12x2−5POL.
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
3.3Mounting
Warning
Sudden unexpected movement of the connected actuators
and uncontrolled movements of loose tubing can cause
injury to human beings or damage to property.
Before carrying out installation and maintenance work,
switch off the following:
the compressed air supply
the operating and load voltage supplies.
Caution
Inappropriate handling can result in damage to the
modules.
· Do not touch the electrical contacts of the modules.
· Observe the handling specifications for electrostatically
sensitive devices.
· Discharge yourself before installing or removing sub−
assemblies to protect the sub−assemblies from static
discharges.
Festo P.BE−CPX−EA−EN en 0705f
Before the CPX terminal can be extended or converted, it
must first be unscrewed and dismantled. Instructions on this
can be found in the CPX system manual.
The CPX terminal does not need to be dismantled when sub−
or electronic modules are fitted or removed. This also
bases
applies to the plugs and cables on the sub−base.
3−23
3. Overview and connecting technology I/O modules
3.3.1Fitting the sub−bases
Note
Handle all modules and components of the CPX terminal
with great care. Note especially the following:
· Screws must be fitted accurately (otherwise threads will
be damaged).
Screws must be fastened at first only by hand. Screws
must be placed so that the self−cutting threads can be
used.
· The specified torques must be observed.
· Screw connections must be fitted free of offset and
mechanical tension.
· Check the seals for damage (IP 65/IP 67).
· Connecting surfaces must be clean (to ensure sealing
effect, avoid leakage and contact faults).
The screw connection between the sub−base and the mani
fold sub−base is designed to withstand at least 10 fitting/
removal cycles under observance of the instructions.
Observe also the installation instructions supplied with
modules and components ordered at a later
stage.
3−24
CPX terminals are supplied from the factory completely fitted.
It may be necessary to fit or remove the sub−bases for the
following reasons:
for replacing the connections
to simplify fitting the sensor plugs or cables.
It may be necessary to fit or remove the electronic modules
for the following reasons:
for changing the
function of the I/O module (e.g. CPX−8DE
instead of CPX−4DE)
for replacing defective electronic modules.
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
DismantlingDismantle the sub−base as follows (see Fig.3/8):
1. Loosen the 4 screws in the relevant sub−base with
a Torx screwdriver size T10.
2. Pull the sub−base carefully and without tilting away from
the electrical plug connection of the electronic module.
Only in cases where the electronic module is to be removed:
· Pull the electronic module carefully and without tilting
away from the contact rails of the manifold sub−base.
1 Sub−base
2 Screws
1
3 Electrical plug
connector
4 Electronic
module
5 Contact rails
3
6 Manifold
sub−base
Fig.3/8: Fitting/removing the I/O module (representation)
2
4
5
6
Festo P.BE−CPX−EA−EN en 0705f
3−25
3. Overview and connecting technology I/O modules
FittingFit the modules as follows (see Fig.3/8):
Note
· Please observe the instructions on combining I/O mod
ules and sub−bases in section 3.2.2.
· Please observe the instructions on combining and ar
ranging modules on the CPX terminal in the CPX system
manual.
Note
With a combination of sub−bases and manifold sub−bases
with metal on plastic or plastic on metal, always use the
appropriate screws for the manifold sub−base (see Appen
dix A.10: Accessories):
with plastic manifold sub−bases: thread−cutting screws
with metal manifold sub−bases: screws with metric
thread
3−26
Only in cases where the electronic module has been re
moved:
· Place the electronic module in the manifold sub−base.
Make sure that the grooves with the contact terminals on
the bottom of the electronic module lie above the contact
rails. Then push the electronic module carefully and with
out tilting as far as possible into the manifold sub−base.
Fitting the sub−bases:
1. Only CPX−M−8−M12x2−5POL:
Observe the
following asymmetrically arranged features
for the correct alignment of the components:
the centre electrical plug connector and
the optical wave guide for the error LED
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
2. Align the sub−base over the manifold sub−base with the
electronic module. Make sure that the plug connectors of
the sub−base are aligned exactly with the connectors of
the electronic module. Then push the sub−base carefully
and without tilting onto the manifold sub−base.
3. Tighten the screws at first only by hand. Place the screws
that the self−cutting threads can be used.
so
Tighten the screws with a Torx screwdriver size T10 with
torque 0.9 ... 1.1Nm.
Festo P.BE−CPX−EA−EN en 0705f
3−27
3. Overview and connecting technology I/O modules
3.3.2Fitting the screening/shield plates
A screening plate type CPX−AB−S−4−12 can be fitted on sub−
bases CPX−AB−4−M12x5−5POL and CPX−AB−4−M12−8POL.
The sub−base must be removed before the terminal is fitted
or dismantled.
FittingFit the screening plate as follows (see Fig.3/9):
1. Dismantle the sub−base (see section 3.3.1).
2. Snap the spring clips of the screening/shield plate from
above into the appropriate recesses
sub−base.
3. Fit the sub−base.
Instructions on earthing the screening/shield plate can be
found in section 3.2.3.
DismantlingThe screening/shield plate must be removed in the opposite
sequence to the fitting procedure.
on the dismantled
3−28
Festo P.BE−CPX−EA−EN en 0705f
3. Overview and connecting technology I/O modules
1 Spring contact
2 Screening/shield
plate
3 Spring clip
4 Sub−base type
CPX−AB−4−
M12x2−5POL or
CPX−AB−4−
M12−8POL
5 CPX terminal
1
2
3
4
5
Fig.3/9: Fitting screening/shield plate type CPX−AB−S−4−12
Festo P.BE−CPX−EA−EN en 0705f
3−29
3. Overview and connecting technology I/O modules
3−30
Festo P.BE−CPX−EA−EN en 0705f
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.