The reproduction, distribution and utilization of this docu−
ment as
well as the comunication of its contents to others
without express authorization is prohibited. Offenders will
be held liable for the payment of damages. All rights re−
served in the event of the grant of a patent, utility module
or design.
Festo P.BE−CPX−FB14−EN en 0810b
I
Page 4
Contents and general instructions
®
TORX
is a registered trade mark
of Acument Intellectual Properties, LLC
(Manufacturer: Acument Global Technologies
NorthAmerica, Sterling Heights, Michigan, USA)
The field bus node type CPX−FB14 described in this manual
has been designed exclusively for use as a slave on the
CANopen field bus.
The CPX terminal must only be used as follows:
as intended
in original condition
without unauthorised modifications
In faultless technical condition.
The limit values specified for pressures, temperatures,
Please comply with the regulations of the workers’
compensation insurance association, the German Technical
Control Board (TÜV) and the electrical requirements of the
VDE or the corresponding national and local safety
regulations.
electrical data, torques
etc. should be observed.
Target group
Service
Festo P.BE−CPX−FB14−EN en 0810b
This manual is intended exclusively for technicians trained in
control and automation technology who have experience in
installing, commissioning, programming and diagnosing
slaves on the CANopen field bus.
Please consult your local Festo repair service if you have any
technical problems.
VII
Page 10
Contents and general instructions
Notes onthismanual
This manual contains specific information on installing,
configuring, parameterizing, commissioning, programming
and diagnosing with the CPX field bus node for CANopen.
This manual refers to the following versions:
Versions
Rev 24 (19 Nov. 08)
Rev 20 (10 Oct. 07)
Rev 14 (12 Jul. 05) CPX−FEC
EDS file from 1 Sep. 08
1)
1)
Software status (SW) or revision no. (R) see type plate
Support of
Virtual modules via the Function
Assignment Object (see section 2.4.13)
CPX−CP interface
Tab.0/1:Revisions of the CPX−FB14 until December 2008
An overview of thestructure of theCPXterminal user
documentationiscontained intheCPXsystem
description.
General basic information about the method of operation,
fitting,
installing and commissioning CPX terminals can be
found in the CPX system description.
Information about further CPX modules can be found in the
manual for the respective module.
VIII
Festo P.BE−CPX−FB14−EN en 0810b
Page 11
Contents and general instructions
Importantuser instructions
Danger categories
This manual contains instructions on the possible dangers
which may occur if the product is not used correctly. These
instructions are marked (Warning, Caution, etc.), printed on a
shaded background and marked additionally with a picto
gram. A distinction is made between the following danger
warnings:
Warning
This means that failure to observe this instruction may
result in serious personal injury or damage to property.
Caution
This means that failure to observe this instruction may
result in personal injury or damage to property.
Festo P.BE−CPX−FB14−EN en 0810b
Note
This means that failure to observe this instruction may
result in damage to property.
The following pictogram marks passages in the text which
describe activities with electrostatically sensitive compo
nents.
Electrostatically sensitive components may be damaged if
they are not handled correctly.
IX
Page 12
Contents and general instructions
Marking special information
The following pictograms mark passages in the text
containing special information.
Pictograms
Information:
Recommendations, tips and references to other sources of
information.
Accessories:
Information on necessary or sensible accessories for the
Festo product.
Environment:
Information on environment−friendly use of Festo products.
Textmarkings
·The bullet indicates activities which may be carried out in
any order.
1. Figures denote activities which must be carried out in the
numerical order specified.
Hyphens indicate general activities.
X
Festo P.BE−CPX−FB14−EN en 0810b
Page 13
Contents and general instructions
The following product−specific terms and abbreviations are
used in this manual:
Term / abbreviation
AO, AIAnalogue output, analogue input
COBCommunication object identifier
CPX terminalComplete system consisting of CPX modules with or without pneumatics
DIL switchDual−in−line switches consist of several switch elements with which
F0
h
Field bus nodeProvides the connection to specific fieldbuses. They transmit control
HandheldHandheld programmer for commissioning and service purposes (CPX−MMI)
I/OsDigital inputs and outputs
I/O diagnostic interface The I/O diagnostic interface is a bus−independent diagnostic interface at
I/O modulesCollective term for the CPX modules which provide digital inputs and
IW / OWInput Word / Output Word
O, IDigital output, digital input
OBOutput byte
PLC/IPCProgrammable logic controller/industrial PC
Meaning
settings can be made
Hexadecimal numbers are marked by a low−set h"
signals to the connected modules and monitor their functioning
I/O level, permitting access to internal data of the CPX terminal
outputs
Pneumatic interfaceThe pneumatic interface is the interface between the modular electrical
SC/O
SCS, SCO, SCV
Status bitsInternal inputs which supply coded common diagnostic messages.
periphery and the pneumatics
Short circuit/overload
Short circuit/overload sensor supply, outputs, valves
Before carrying out installation andmaintenance work,
switch off the following:
compressed air supply
the operating voltage supply for the electronics/sensors
the load voltage supply fo
In this way, you can avoid:
uncontrolled movements of loose tubing.
unexpected movements of the connected actuators
r the outputs/valves.
Festo P.BE−CPX−FB14−EN en 0810b
non−defined switching states
of the electronic
components.
Caution
The CPX field bus node contains electrostatically sensitive
components.
· Therefore, do not touch any components.
· Observe the handling specifications for electrostatically
sensitive components.
They will help you avoid damage to the electronics.
Information about fitting the CPX terminal can be
found in the
CPX systemmanual (P.BE−CPX−SYS−...).
1−3
Page 18
1. Installation
Electrical connection and display elements
The following connecting and display elements can be found
on the CPX field bus node for CANopen:
MS PS
PL
NS
SF
IO
4
M
3
1 Bus−status−specific and CPX−specific
LEDs
3 Transparent cover for the DIL switches
4 Service interface for handheld
2 Field bus connection
(9−pin Sub−D plug)
Fig.1/1:Connecting and display elements on the CPX field bus node
Note
Use protective caps or blanking plugs to seal unused
connections. You will then comply with protection class
IP65/IP67.
1
2
1−4
Festo P.BE−CPX−FB14−EN en 0810b
Page 19
1. Installation
Dismantling and fitting
The field bus node is fitted in an interlinking block of the CPX
terminal (see Fig.1/2).
DismantlingDismantle the field bus node as follows:
1. Loosen the 4 screws in the field busscrewdriver size T10.
2. Pull the field bus node carefully and without tilting away
from the contact rails of the manifold base.
1 Fieldbus node
CPX−FB14
4
2 Interlocking block
3 Contact rails
4 TORX T10 screws
3
Fig.1/2: Dismantling/fitting the fieldbus node
node with a TO RX
1
2
Festo P.BE−CPX−FB14−EN en 0810b
1−5
Page 20
1. Installation
Note
Always use the correct screws for the interlocking block,
which depend on whether the block is made of metal or
plastic.
For plastic interlocking blocks: thread−cutting s
For metal interlocking blocks: screws with metric thread.
Both types of screws are enclosed respectively when orderingthe bus node as a single part.
FittingFit the field bus node as follows:
1. Check seal and seal surfaces
2. Place the field bus node in the interlocking block.
Make sure that the grooves with the power contact
terminals on the bottomo
f the fieldbus node lie above
the contact rails.
crews
1−6
3. Press the field bus node carefully and without tilting as
far as possible into the interlocking block.
4. Tighten the screws at first only b
y hand.Place the screws
so that the self−cutting threads can be used.
5. Tighten the screws with a TORX screwdriver size T10
with 0.9 Ū 1.1 Nm.
Festo P.BE−CPX−FB14−EN en 0810b
Page 21
1. Installation
1.2Settings of the DIL switches on the field bus node
In order to set the CPX fieldbus node, youmust first remove
the cover over the DI L switches.
Caution
The CPX field bus node contains electrostatically sensitive
components.
· Do not therefore touch any contacts.
· Observe the handling specifications for electrostatically
sensitive components.
Youwill then prevent the electronics in the node frombeing
damaged.
1.2.1Removing and fitting the cover over the DIL switches
In order to set the CPX field bus node, you must first remove
the cover over the DI L switches.
Removing1. Switch off the power supply.
2. Unscrew the two fastening screws in
3. Remove the cover.
Fitting1. Place the cover carefully on the node.
Note
· Make sure that the seal is seated correctly.
2. Tighten the two fastening screws at first by hand and then
with torque 0.4Nm.
Festo P.BE−CPX−FB14−EN en 0810b
the switch cover.
1−7
Page 22
1. Installation
1.2.2Setting the DIL switches
When the cover over the DIL switches is removed, you will see
5DIL switches in the field bus node (see Fig.1/3).
You can set the following parameters with the DIL swit
ches:
operating mode
fault mode
station number
baud rate
CPX diagnostic mode.
Procedure:
1. Switch off the power supply.
2. Remove the cover over the DIL switches (section1.2.1).
the desired operating mode (DIL switch1, factory
3. Set setting: remoteI/O).
4. Set the error mode (DI L switch2).
5. Assign an unused station number to the CPX terminal.
Set the desired station
number (8−position DIL switch3,
switch elements 1Ū7).
6. Set the baud rate (DIL switch4).
1−8
7. Operating mode RemoteI/O:
Set the CPX diagnosticmode (DIL switch5).
operating mode Remote Controller:
With
Set the required number of logical I/Os of the CPX−FB14
(DIL switch 5).
8. Fit the cover again (section1.2.1).
Festo P.BE−CPX−FB14−EN en 0810b
Page 23
1. Installation
1 DIL switch 1:
Operation mode
2 DIL switch 2:
1
2
Undervoltage
error message
3
mode
3 DIL switch 3:
Station number
4 DIL switch 4:
Baud rate
4
5
5 DIL switch 5:
CPX diagnosis
mode or number
of logical I/Os
with RemoteController"
Fig.1/3: DIL switch in the field bus node
(further information on
1Ū5 in the following)
Setting theoperating mode with DIL switch
Youcan set the operating mode of the fieldbus node with
switch element 1of DIL switch 1:
ONON
12 12
ON
ONON
12 12
8
12 34 56 7
1
Operating mode
Remote I/O operating mode
All functions of the CPX terminal are controlled directly by
the CANopen Master. An FEC built into the CPX terminal
functions like a passive function module without a controller.
Remotecontrolleroperating mode
An FEC integrated in the CPX terminal takes control of the
I/Os. This operating mode is only useful if an FEC isintegrated in the CPX terminal.
Tab.1/1:DIL switch 1 (operating mode)
Festo P.BE−CPX−FB14−EN en 0810b
Setting DIL switch1
DIL 1.1: OFF
DIL 1.2: OFF
(factory setting)
DIL 1.1: ON
DIL 1.2: OFF
1−9
Page 24
1. Installation
Setting theerrormode with DIL switch2
You set the error mode with switch element 1 of the
2−element DIL switch 2:
Errormode
Registering undervoltageerror2.1: OFF
Filtering undervoltageerror
Errors during monitoring of the
operating and load voltagesupplies are ignored
With the setting Filter undervoltage", voltage errors which
occur will not be reproted as errors. In this way, you can,
for
example, suppress unnecessary error messages during the
commissioning phase.
The setting of the DIL switch has precedence over the para
meterizing of defined settings. No emergency message is
transmitted with error filtering.
1−10
Festo P.BE−CPX−FB14−EN en 0810b
Page 25
1. Installation
1 Setting of station
numbers (switch
elements 1Ū7)
Setting thestationnumber with DIL switch3
You can set the station number of the CPX terminal binary
coded with the 8−element DIL switch 3.
1
Fig.1/4: DIL switch 3 (station number)
The following station numbers are permitted:
Protocol
CANopenStation number1; ...; 127
Tab.1/2:Permissible station numbers
Recommendation:
Assign the station numbers in ascending order. Assign the
station numbers in accordance with the machine structure of
your system.
1234 5678
Address designation Permissible
station numbers
Festo P.BE−CPX−FB14−EN en 0810b
1−11
Page 26
1. Installation
Example: Station number
set: 05
20 + 22 =
1234 5678
1 + 4 =
5
Example: Station number
set: 38
21 + 22 + 25 =
2 + 4 + 32 =
1234 5678
38
Tab.1/3:Examples of set station numbers
(binary coded)
On the following pages you will find an overview of the station
number settings.
1−12
Festo P.BE−CPX−FB14−EN en 0810b
Page 27
1. Installation
Station
no.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
12345678
Not permitted
ON
OFF OFF OF F OFF OFF OFF
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON
OFF OFF OF F
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON ON
OFF OFF OF F OFF OFF
OFF OFF OF F OFF OFF
ON
OFF OFF OF F OFF
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON
OFF OFF OF F OFF
OFF OFF OF F OFF
OFF OFF OF F OFF
ON
OFF OFF OF F
ON
OFF OFF OF F
ON
OFF
OFF
ON ON
ON ON
OFF OFF OF F
ON
OFF OFF OF F
OFF OFF OF F
OFF OFF OF F
OFF OFF OF F
OFF OFF OF F
Station
no.
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
12345678
OFF
OFF
OFF
OFF
ON ON
ON ON
ON ON
ON ON
ON
OFF OFF
ON
OFF OFF
ON
OFF OFF
ON
OFF OFF
ON
OFF OFF
ON
OFF OFF
ON
OFF OFF
ON
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OF F OFF OFF
ON
OFF OFF OF F
ON
OFF
ON ON
OFF OF F
ON
OFF
ON ONON
OFF OF F OFF
ON
OFF
ON ON
OFF OF F
ON
OFF
ON ONON ONON
OFF OFF
OFF OFF
ON
ON
OFF
ON ON
OFF OFF
ON
OFF
OFF
ON ONON
ON ONON
OFF
ON ONON ON
Tab.1/4:Setting of station numbers 1 Ū 31: Position of the DIL switch elements
Festo P.BE−CPX−FB14−EN en 0810b
1−13
Page 28
1. Installation
Station
no.
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
12345678
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF OFF OF F OFF OFF
ON
OFF OFF OF F OFF
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON
OFF OFF OF F
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON ON
OFF OFF OF F
OFF OFF OF F
ON
ON
OFF
ON ON
OFF OFF
ON
OFF
OFF
ON ON
ON ON
OFF
ON ONON
OFF OFF
OFF OFF
OFF OFF
OFF OFF
ON
ON
ON
ON
Station
no.
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
12345678
OFF OF F OFF OFF
ON
OFF OFF OF F
ON
OFF
ON ON
OFF OF F
ON
OFF
ON ONON
OFF OF F OFF
ON
OFF
ON ON
OFF OF F
ON
OFF
ON ONON ONON ON
OFF OFF
OFF OFF
ON
ON
OFF
ON ON
OFF OFF
ON
OFF
OFF
ON ONON ON
ON ONON ON
OFF
ON ONON ONON
ON ON
ON ON
ON ON
ON ON
ON ON
OFF
ON ON
OFF
ON ON
OFF
ON ON
OFF
ON ONON
ON ONON
ON ONON
ON ONON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Tab.1/5:Setting of station numbers 32 Ū 63: Position of the DIL switch elements
1−14
Festo P.BE−CPX−FB14−EN en 0810b
Page 29
1. Installation
Station
no.
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
12345678
OFF OFF OF F OFF OFF OFF
ON
OFF OFF OF F OFF OFF
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON
OFF OFF OF F
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON ON
OFF OFF OF F OFF
OFF OFF OF F OFF
ON
OFF OFF OF F
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON
OFF OFF OF F
OFF OFF OF F
OFF OFF OF F
ON
ON
ON
OFF
ON
OFF
ON ON
ON ON
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Station
no.
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
12345678
OFF OF F OFF OFF
ON
OFF OFF OF F
ON
OFF
ON ON
OFF OF F
ON
OFF
ON ONON
OFF OF F OFF
ON
OFF
ON ON
OFF OF F
ON
OFF
ON ONON ONON
OFF OFF
OFF OFF
ON
OFF
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON ON
OFF
OFF
OFF
ON ON
ON ON
ON ON
OFF
ON ON
OFF
ON ONON
ON ONON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Tab.1/6:Setting of station numbers 64 Ū 95: Position of the DIL switch elements
Festo P.BE−CPX−FB14−EN en 0810b
1−15
Page 30
1. Installation
Station
no.
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
12345678
OFF OFF OF F OFF OFF
ON
OFF OFF OF F OFF
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON
OFF OFF OF F
ON
OFF
ON ON
OFF OFF
ON
OFF
ON ONON ON
OFF OFF OF F
OFF OFF OF F
ON
ON
OFF
ON ON
OFF OFF
ON
OFF
OFF
ON ON
ON ON
OFF
ON ONON
OFF OFF
OFF OFF
OFF OFF
OFF OFF
ON
ON
ON
ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
OFF
ON ON
OFF
ON ON
OFF
ON ON
OFF
ON ON
OFF
ON ON
OFF
ON ON
OFF
ON ON
OFF
Station
no.
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
12345678
OFF
OFF OFF OF F
ON
OFF OFF OF F
ON
OFF
ON ON
OFF OF F
ON
OFF
ON ONON
OFF OF F OFF
ON
OFF
ON ON
OFF OF F
ON
OFF
ON ONON ONON ONON
OFF OFF
OFF OFF
ON
ON
OFF
ON ON
OFF OFF
ON
OFF
OFF
ON ONON ONON
ON ONON ONON
OFF
ON ONON ONON ON
ON ONON
ON ONON
ON ONON
ON ONON
ON ONON
OFF
ON ONON
OFF
ON ONON
OFF
ON ONON
OFF
ON ONON ON
ON ONON ON
ON ONON ON
ON ONON ON
Tab.1/7:Setting of station numbers 96 Ū 127: Position of the DIL switch elements
1−16
Festo P.BE−CPX−FB14−EN en 0810b
Page 31
1. Installation
Setting thebaud rate with DIL switch4
Youcan set the baud rate with 2−element DIL switch 4:
Baud rate
125 kBaud4.1: OFF
250 kBaud4.1: ON
500 kBaud4.1: OFF
1000 kBaud4.1: ON
Setting DIL switch 4
4.2: OFF
(factory setting)
4.2: OFF
4.2: ON
4.2: ON
Tab.1/8:DIL switch 4 (baud rate)
The following table shows the settings of the DIL switch.
Festo P.BE−CPX−FB14−EN en 0810b
1−17
Page 32
1. Installation
Setting the diagnosticmodeornumberof logical I/Os with
DIL switch
5
The function of DIL switch 5 depends on the set operating
mode of the CPX terminal (see Tab.1/1):
Operating mode Remote I/O:
Setting the CPX diagnostic mode
The status
bits occupy 8 bits and the I/O diagnostic inter
face 16 bits in PDO 4 (bit 0 Ū 7 or 0 Ū 15, see Fig.2/1).
Remote controller operating mode:
64 I/Os are provided for
communication of the fieldbus
node with the FEC in PDO 1 (see Fig.2/2).
Remote I/O operating mode
DiagnosticmodeNumberof I/O bytes
The I/O diagnosticinterfaceand
thestatusbitsareswitched off
(+ 0 I/O bits)
Thestatusbitsareswitched on
(+ 8 (16) I bits)
The I/O diagnostic interface is
switched on
(+ 16 I/O bits)
Reserved for future extensions8 bytes I/8 bytes O
1)
The diagnosis mode (status bits or I/O diagnosis interface) occupies 2 bytes or 4 bytes of address
space (16 I bits or 16 I/O bits; 8I bits remain unused in the status bits mode)
1)
Remote controller
operating mode
Setting not permitted3.1: OFF
1)
for communication between
the fieldbus node and the
CPX−FEC
Setting
DIL switch5
3.2: OFF
(factory setting)
3.1: OFF
3.2: ON
3.1: ON
3.2: OFF
3.1: ON
3.2: ON
Tab.1/9:DIL switch 5 (diagnosis mode or number of I/O bytes with remote controller)
1−18
Festo P.BE−CPX−FB14−EN en 0810b
Page 33
1. Installation
Note
(1) An activateddiagnosis mode reduces the available
address space in the PDO4.
Use of the diagnosticmode (status bits or I/Odiagnostic
interface) occupies 16 Ior 16I/O
bits in the PDO 4. In
combination with technology modules, the number of I/O
bits available for module communication is thus reduced.
In this way, the number of addressable modules is
reduced
in favour of additional status or diagnostic information.
Take account of this fact for the planning of your
CPXterminal.
(2) Later activation of the diagnosis mod
e requires
reconfiguration.
During later activation of the diagnosis module (status bits
or I/O diagnosis interface), the CPX−internal I/O image can
be displaced. Restart the CPX terminal with Power
OFF/ON.
Festo P.BE−CPX−FB14−EN en 0810b
1−19
Page 34
1. Installation
1.3Connecting the field bus
1.3.1Field bus cable
Note
Faulty installations or high transmission rates may cause
data transmission errors as a result of signal reflectionsand attenuations.
Transmission errors can be caused by:
missing or
incorrect screened connection.
branches
transmission over long distances
unsuitable cables.
Observe the cable specifications. Refer to the manual
your control system for information on the type of cable to
be used.
incorrect terminating resistor.
for
1−20
Use a twisted, screened 4−wire cable as field bus line. The
CANopen bus interface
power via the field bus cable.
If the Festo field bus plug is used, a cable diameter of 5Ū8
or 7Ū10 mm is
Note
If the CPX terminal is fitted onto the moving part of a
machine, the field bus cable on the moving part must be
provided with strain relief. Please also observe the relevant
regulatio
ns in EN60204part 1.
of the CPX terminal is suppliedwith
permitted.
Festo P.BE−CPX−FB14−EN en 0810b
Page 35
1. Installation
1.3.2Field bus baud rate and field bus length
The maximum permissible field bus length and length of the
branch lines depends on the baud rate used. Detailed specifi
cations can be found in the manuals for the
system or bus interface.
Note
· Refer to the manuals for your control systemor bus
interface in order to ascertain which T−adapter and
maximum branch line length are permitted for your
controller.
· Also take into account the sum of the branch line lengths
when calculating the maximum permitted length of the
fieldbus cable.
your control
Festo P.BE−CPX−FB14−EN en 0810b
1−21
Page 36
1. Installation
1.3.3Information on connecting the field bus
Bus power supplyAvoid long distances between the bus interface supply and
the CPX terminal.
Caution
· Make sure the polarity is correct when you connect the
fieldbus interface and the power supply for the bus
interface/internal logics.
· Protect the power supply for the bus interface with an
external fuse, in accordance with the number of bus
slaves.
· Connect the screen.
Note
Power supply is needed over the field bus cable (pin3and
pin 9 on the Sub−D plug).
Bus slaves have different tolerances in respect of the
interface power supply, depend
Observe this when planning the bus length and placing the
power supply unit.
ing on the manufacturer.
1−22
The following tolerance in the bus interface power supply
(pin3/pin 9 on the sub−D
V
= 30.0 V
max
V
= 11.0 V
min
plug) applies to the CPX terminal:
Recommendation:
Place the power supply unit approximately at the centre ofthe bus.
Festo P.BE−CPX−FB14−EN en 0810b
Page 37
1. Installation
6
You can implement a T−adapter with the Festo field bus plug
(see fig.).
231
5
1 Field bus
2 Power supply
3 Screening
Fig.1/5: Layout of the bus interface and example of connection
Festo P.BE−CPX−FB14−EN en 0810b
4 Branch line
5 T−adapter (T−Tap)
6 Field bus plug with T−adapter function
4
1−23
Page 38
1. Installation
1.3.4Field bus interface
There is 9−pin sub−D plug on the field bus node for connecting
the CPX terminal to the fieldbus. This connection is used for
the incoming andcontinuing fieldconnect the CPX terminal with the fieldbus plug fromFesto
type FBS−SUB−9−BU−2x5POL−B.
bus cables. Youcan
Note
Note that only the Festo field bus plug guarantees
compliance with protection class IP65.
Before using field bus plugs from other manufacturers:
· Replace the two flat screws with bolts
(typeUNC4−40/M3x6).
Plug on
the CPX
PinInternal
contacts
CANopenDesignation
terminal
1
2
3
4
96
5
51
6
7
8
9
Housing
(plug)
FE
n.c.
CAN_L
CAN_GND
n.c.
CAN_SHLD
GND
CAN_H
n.c.
CAN_V+
Not connected
CAN Bus Low
Power supply to bus (0 V)
Not connected
Connection to functional earth
(screening/shield)
Optional GND
CAN Bus High
Not connected
Power supply to bus (24 V)
Tab.1/10: Pin assignment of the field bus interfaceof the CPX field bus node
1−24
Festo P.BE−CPX−FB14−EN en 0810b
Page 39
1. Installation
1.3.5Connecting with the field bus plug from Festo
Note
Use protective caps or blanking plugs to seal unused
connections. You will then comply with protection class
IP65.
·Observe the fitting instructions for the field bus plug.
Tighten the two fastening screws at first by hand and then
with max. 0.4 Nm.
You can connect the CPX valve terminal easily to the fiel
d bus
with the field bus plug from Festo (FBS−SUB−9−BU−2x5POL−B).
Youcan disconnect the plug from the node without inter
rupting the bus cable (T−Tap functio
n).
Note
The clamp strap in the Festo field bus plug is connected
only capacitively internally with the metal housing of the
sub−Dplug. This prevents equalizing currents from flowing
via the
screening of the field bus cable (Fig.1/6).
·Clamp the screen of the field bus cable under the clamp
strap in the field bus plug.
Festo P.BE−CPX−FB14−EN en 0810b
1−25
Page 40
1. Installation
1 Folding cover
with inspection
window
2 Clamp strap for
screen
connection
3 Protective cap if
connection is not
used
4 Field bus
continuing (OUT)
5 Fieldbus
incoming (IN)
6 Only capacitively
connected
Fig.1/6: Festo field bus plug type FBS−SUB−9−BU−2x5−POL−B
21
Bus IN
GND
V+
H
L
56
SLD
Bus OUT
GND
SLD
V+
H
L
3
4
1−26
Festo P.BE−CPX−FB14−EN en 0810b
Page 41
1. Installation
1.3.6Further connection possibilities for the field bus with adapters
Caution
· When connecting the fieldbus interface and the power
supply for the bus interface pay attention to the polarity.
· Connect the screen.
There are further possibilities of connecting the CPX terminal
with adapters which can be ordered separately from Festo.
M12 adapter 5−pin
(protectio
Type FBA−2−M12−5POL
Screw terminal adapter 5−pin
(protection class IP20)
Type FBA−1−SL−5POL
n class IP65)
Festo P.BE−CPX−FB14−EN en 0810b
1−27
Page 42
1. Installation
M12 adapter (IP65)
With this adapter the bus is connected via a 5−pin M12 socket
with PG9 screw connector. Use the second connection socket
for the continuation of the field bus.
Note
· Use protective caps or blanking plugs to seal unused
connections.
You will then comply with protection class IP65.
Order this connection at Festo (FBA−2−M12−5POL).
M12
adapterPin no.
2
3
Bus IN
151
5
4
2
4
Bus OUT
1. Screening
2. 24 V DC bus (max. 4A)
3
Protective cap or plug with bus terminationresistor if connection is not used.
3. 0 V bus
4. CAN_H
5. CAN_L
Fig.1/7: Pin assignment of field bus interface (adapter for 5−pin M12 connection)
With the two M12 connections you can implement a T−adapter
(see Fig.1/5).
1−28
Festo P.BE−CPX−FB14−EN en 0810b
Page 43
1. Installation
Screw terminal adapter (IP20)
With this adapter the bus is connected to a 2x5−pin terminal
strip.Use the second rowof connections for the continuing
fieldbus.
The maximum permitted current at the
Use cables with a cross sectional area of min. 0.34mm
Order this connection from Festo (FBA−1−SL−5POL) together
with the terminal strip type FBSD−KL−2x5POL.
terminals is 4A.
2
.
Screw terminal
Pin no.
adapter
1. 0 V bus
2. CAN_L
12 345
3. Screening
4. CAN_H
5. 24 V DC bus (max. 4 A)
2x5−pin terminal strip
Fig.1/8: Pin allocation for field bus interface
(5−pin screw terminal adapter)
If you connect the field bus via the terminal strip
FBSD−KL−2x5POL from Festo, you can imp
lement a T−adapter
function.
Festo P.BE−CPX−FB14−EN en 0810b
1−29
Page 44
1. Installation
1.4Bus terminal with terminating resistors
Note
Always use a bus termination at both ends of the fieldbus.
This also applies if the CPX terminal is at the endof the
fieldbus.
If you are using T−adapters, install
the terminating resistor at
the unusedoutput of the T−adapter.
Recommendation:
For bus termination, fit a resistor (120 , 0.25 W, see following diagram) in the Festo field bus
1 Protective cover
12
2 Resistor for bus
termination
(120 , 0.25 W)
GND
GND
SLD
SLD
V+
V+
H
L
H
L
Fig.1/9: Bus termination with resistor in Festo field bus plug
1.4.1Install a terminating resistor using the adapters
If the CPX terminal to be connected is at the end of the field
bus, a terminating resistor (120 , 0.25 W) must be fitted in
the field bus socket.
plug.
V+
GND
SLD
H
L
1−30
·Connect the terminating resistor between the cores for
CAN_H and CAN_L.
Festo P.BE−CPX−FB14−EN en 0810b
Page 45
1. Installation
1.5Pinassignment of power supply
Warning
· For the power supply, use only PELV circuits as per
IEC/DIN EN60204−1 (Protective Extra−Low Voltage,
PELV).
Take into account also the general requirements for
PELV circuits as per IEC/DINEN60204−1.
· Use only power sourcesthat guarantee reliable
electrical isolation of the operating voltage as per
IEC/DINEN60204−1.
Through the use of PELV circuits, protection against electric
shock (protection against direct and indirect contact) is
ensured in accordance with IEC/DINEN60204−1 (electrical
equipment of machines, general requirements).
Festo P.BE−CPX−FB14−EN en 0810b
The current consumption of a CPX
terminal depends on the
number and type of integrated modules and components.
Read the information on power supply as well as on the
earthing measures to be carried out in the CPX system
manual.
1−31
Page 46
1. Installation
1)
)
System power supply,
additional power supply
and valve power supply
Plugs
(top view of device)
7/8"−4POL
C
B
7/8"−5POL
2
3
4
M18
1
4
Push−pull
1
5
2
Interlinking block with
Systemsupply
Type CPX−(M−)GE−EV−S...
A: 24V
B: 24V
D
C: FE
D:0V
A
1: 0V
2: 0V
3: FE
4: 24V
5: 24V
1: 24V
2: 24V
3: 0V
2
3
4: FE
1: 24V
2: 0V
3: 24V
4: 0V
5: FE
The CPX terminal is supplied with operating and load power
via the interlinking block with system, additional and valve
power supply. Further interlinking blocks are in preparation.
0V
0V
el/sen
val
el/sen
/ 0V
val
/ 0V
val
el/sen
el/sen
val
el/sen
val
el/sen
/ 0V
val
el/sen
el/sen
val
/ 0V
val
/ 24V
/
out
out
/ 24V
/ 24V
/
out
/ 24V
out
out
out
out
out
Additional power supply
Type CPX−(M−)GE−EV−Z...
A: not connected
B: 24V
out
C: FE
D:0V
out
1: 0V
out
2: not connected
3: FE
4: not connected
5: 24V
out
1: not connected
2: 24V
out
3: 0V
out
4: FE
1: not connected
2: not connected
3: 24V
out
4: 0V
out
5: FE
Valvesupply
Type CPX−GE−EV−V...
A: not connected
B: 24V
val
C: FE
D:0V
val
1: not connected
2: 24V
val
3: 0V
val
4: FE
V
:Operating voltage for electronics/sensors
el/sen
V
:Load voltage for outputs
out
V
:Load voltage for valves
val
FE:Functional earth
1)
Note the specifications on the plug.
2) Interlinking blocks with forwarding function and interlinking blocks with system supply are
identically constructed.
Tab.1/11: Pin assignment for system supply, additional supply and valve supply
This section describes the configuration and addressing of a
CPX valve terminal on a CANopen interface or CANopen
master.
The following specifications have been taken into account:
CANopenspecifications
DS201
DS207
DS301, V4.01The Draft Standard 301 is based on the CAL
DS401, V2.0The Draft Standard 401 defines the device
CAN Application Layer CAL
communication profile
profiles for input and output modules within
CANopen
Tab.2/1:CANopen specifications taken into account with
the CPX terminal
In order to understand this chapter, you should be familiar
with C ANopen and the specifications DS301 and DS401.
Festo P.BE−CPX−FB14−EN en 0810b
2−3
Page 50
2. Commissioning
2.1.1General information on CANopen
CANopen devices have an object directory which makes all
important slave parameters accessible in a standardized
manner. A CANopen system is configured mainly by access to
the object directory of the individual slaves. The access
mechanism is provided by Service Data Objects (SDOs).
There are two different communication mechanisms in a
CANopen system.
Process DataObjects (PDOs) provide fast transfer of
The
processing data and are transmitted by simple CAN
messages without protocol overhead. Process Data Objects
can be transmitted event−controlled, synchronous to a system
pulse sequence or on demand.
ervice Data Objects (SDO) form a point−to−point
The S
connection and permit access to every entry in the object
directory of a node.
2−4
Festo P.BE−CPX−FB14−EN en 0810b
Page 51
2. Commissioning
2.2Configuration
2.2.1Addressing the CPX terminal
Before configuring, ascertain the exact number of available
inputs/outputs. Depending on what you have ordered, a CPX
terminal comprises a different number of I/Os.
The I/Os will be assigned automatically within the CPX
terminal (standard setting). The following applies to inputs
and outputs:
The address assignment of the inputs does not depend on
outputs.
the
The counting method does not depend on the position of
the field bus node. The field bus node counts as a module
with 0 or 8 inputs or 16 inputs and outputs, depending on
the setting of DIL switch 5 (see section 1.2.2).
Festo P.BE−CPX−FB14−EN en 0810b
Counting is from left to right, in ascending order
gaps.
Note
Note that a CPX terminal provides status bits or an
I/Odiagnostic interface, depending on the setting.
The status bits must be treated like inputs and occupy
8bits in the Transmit PDO 4 (standard setting).
The 16 bits of the I/O diagnostic interface must be
treated like inputs and outputs. They each occupy
16bits
in the Transmit and Receive PDO 4 (standard
setting).
without
2−5
Page 52
2. Commissioning
The following diagram shows the standard distribution of
I/Os in the operating mode Remote I/O. If you use more than
8 I/O bytes, you must map these into the PDOs by mapping".
In this case, the use of analogue channels will be limited.
The same applies in the reverse case if more
Depending on configuration:
with status bits: I0 Ū I7, with I/O diagnostic interface: I0 Ū I15
The input words of the technology modules shift correspondingly.
2)
Depending on configuration:
With activated I/O diagnosin interface O0 Ū O15 (see section 1.2.2)
The output words of the technology modules shift correspondingly.
Fig.2/1: Overview of PDO 1 Ū 4 and position of the status bits and I/O diagnostic
interface
Note
For the Receive PDO 1 Ū 4:
The necessary telegram length depends on the
equipment fitted on the CPX and is 1 Ū 8 byte.
If the telegram received is shorter than the necessary
telegram length, a fault message will be output.
If the telegram received is longer, the part
corresponding to the
necessary length will be
processed.
2−6
Festo P.BE−CPX−FB14−EN en 0810b
Page 53
2. Commissioning
Remote controller operating mode
In the Remote Controller operating mode (DIL switch1)
onlythe PDOs 1 are assigned. They contain 64 logical I/Os
for data exchange with the Remote Controller.
Manual mapping:
The CPX−CP interface occupies in the configuration 16 byte outputs (128O). Since the PDO 4 can
only address the first 8 bytes (64O), manual mapping is required for configuration of this CPX
terminal. As a result, the remaining output bytes can be made available over other PDOs.
(OW4ŪOW7 are not depicted in Fig.2/5).
MPA1S: VMPA1−FB−EMS−8
MPA pneumatic module
R−PDO 1: O20 Ū O27
Obj. 6200,3
Obj. 6200,4
Tab.2/4:Configuration for example terminal 3 in Fig.2/5
Festo P.BE−CPX−FB14−EN en 0810b
2−13
Page 60
2. Commissioning
2.3Overview
2.3.1Brief overview of the scope of functions
Module states and boot−up as per Communication Profile
DS301
1 service data object for read and write access to the
object directory Send and receive SDO
4 process data objects for access to digital and analogue
inputs: Transmit PDO 1 Ū 4
4 process data objects for access to digital and analogue
outputs:
Emergency telegram for fault message to the master
Node guarding and heart beat
Receive PDO 1 Ū 4
2−14
Default setting of all identifiers as per DS301 and the
station number (predefined connection set)
Variable mapping
Function assignment and virtual modules
Festo P.BE−CPX−FB14−EN en 0810b
Page 61
2. Commissioning
2.3.2Overview Object directory
Index (hex)ObjectsSeesection
1000Ū1200Communication part of the object directories2.4.1
1400Ū1403Communication parameters for receive PDO 1Ū42.4.4
1800Ū1803Communication parameters for Transmit PDO 1Ū42.4.3
1600Ū1603Mapping parameters for Receive PDO 1Ū42.4.4
1A00Ū1A03Mapping parameters for Transmit PDO 1Ū42.4.3
Resetting the communication functions:
Outputs are reset
Communication parameters are reset
(objects 1000Ū1FFF)
1)
5Reset_Node_
Indication
81
h
Module reset including application:
Outputs are reset
Maskings of the outputs are reset to default
Communication parameters are reset
(objects 1000Ū1FFF)
Stored parameters (2000Ū5FFF) are not
reloaded.
1)
The objects 6000Ū are always loaded with the default settings after power−on
2)
Only after the transition from operational mode to stopped or pre−operational mode
Tab.2/6:Status transitions
Festo P.BE−CPX−FB14−EN en 0810b
2−17
Page 64
2. Commissioning
2.3.4Default identifier distribution
The following table shows the identifier distribution:
Broadcast objects
Object name
SYNC080
Object designationValue range of the COB identifier on the CPX
Tab.2/7:Broadcast objects
terminal
h
128
d
2−18
Festo P.BE−CPX−FB14−EN en 0810b
Page 65
2. Commissioning
Peer−to−peer objects
Object
EMERGENCYFor procedures with high
Object designationValue range of the COB identifier
priority, e.g. undervoltage
081
129dŪ 255
Transmit PDO 1PDO 1 (tx)181
385dŪ 511
Receive PDO 1PDO 1 (rx)201
513dŪ 639
Transmit PDO 2PDO 2 (tx)281
641dŪ 767
Receive PDO 2PDO 2 (rx)301
769dŪ 895
Transmit PDO 3PDO 3 (tx)381
897dŪ 1023
Receive PDO 3PDO 3 (rx)401
1025dŪ 1151
Transmit PDO 4PDO 4 (tx)481
1153dŪ 1279
Receive PDO 4PDO 4 (rx)501
1281dŪ 1407
Transmit SDOSDO 1 (tx)581
1409dŪ 1535
Receive SDOSDO 1 (rx)601
1537dŪ 1663
Node guarding /
Heart beat
Guarding701h 77F
1793dŪ 1919
0FF
h
h
h
h
h
h
h
h
h
h
h
h
d
1FF
h
d
27F
h
d
2FF
h
d
37F
h
d
3FF
h
d
47F
h
d
4FF
h
d
57F
h
d
5FF
h
d
67F
h
d
h
d
Tab.2/8:Peer to Peer objects of the CPX−FB14
Festo P.BE−CPX−FB14−EN en 0810b
2−19
Page 66
2. Commissioning
2.4Object directories
2.4.1Communication profile
The following tables show the objects of the communication
part (values and examples: module ID = 1).
In the following:U= unsigned
Note
For mapping the rules as per CiA DS301 apply: Mapping
entries are only possible if the number of parameters has
previously been set to zero.
(Example: index 1A00, subindex 3 Ū 8:
After entering the mapping values, set the number of
parameters to the appropriate value again.
ro= read only
rw= read/write
Map. = mapping possible
Attr. = attribute
Set subindex 0 to 0").
2−20
Festo P.BE−CPX−FB14−EN en 0810b
Page 67
2. Commissioning
Index
(hex)
10000Device type U32ro00 0F 91 01As from software status
10010Error
10010Error
10020Manufac
Sub
index
Designa
tion
register
turer status
register
Type Attr. Map. Values
Explanation
(hex)
V1.10:
OF = maximum amount of
equipment on the CPX
terminal
00 0x 91 01Prior to software status
Example:
00 03 91 01
U8roYes00no error
U8roYesxxGeneric/manufacturer error
U32roYes00 00 00 00Module number and fault
V1.10:
91 01 = device profile
x = depends on equipment
fitted on the CPX terminal:
Bit 16: digital inputs
Bit 17: digital outputs
Bit 18: analogue inputs
Bit 19: analogue outputs
CPX terminal with digital
inputs and outputs
(see section 3.5.1)
number
(see section 3.5.1)
Festo P.BE−CPX−FB14−EN en 0810b
2−21
Page 68
2. Commissioning
Index
(hex)
10030Pre−defined
10050COB−ID
10080Manufact.
10090Manufact.
Sub
tion
index
error field
1Standard
error field
2xx xx xx xxError (n+1)
3xx xx xx xxError (n+2)
.........
A
h
SYNC
message
device name
hardware
version
Map.Attr.TypeDesigna
ExplanationValues
(hex)
U8rw00 Ū 0ANumber of current errors
U32roxx xx xx xxMost recent error (n)
xx xx xx xxOldest error n+9
U32rw80Default SYNC message
Str.roFB14"Node designation
Str.ro0810"
(example)
(Write 00 deletes all errors)
(see section 3.5.1)
Byte 0 Ū 1 = error code
(see section 3.5.1)
Byte 2 = byte 0 of
index 1002
Byte 3 = byte 1 of
index 1002
COB−ID 80
Current hardware status
h
100A0Manufact.
software
version
100C0Guard timeU16rw00 00Timeout monitoring [ms]
100D0Life time
factor
10140COB−ID
emergency
object
2−22
Str.roV2.0"
(example)
U8rw00Timeout monitoring
U32rw80 + node IDDefault emergency object
Current software status
(Guard time x life time
factor = complete node
guard time)
COB−ID 80h + node ID
Festo P.BE−CPX−FB14−EN en 0810b
Page 69
2. Commissioning
p
Index
(hex)
10150Inhibit time
10160Consumer
10170Producer
10180Identity
10181Vendor IDU32ro00 00 00 1DVendor ID (from CiA)
Sub
tion
index
emergency
message
heart beat
time
1C.H. time 1U32rw00 00 00 00Heart beat ID und heart
2C.−H. time 200 00 00 00
.........
6C.−H. time 600 00 00 00
heart beat
time
object
2Product
code
U16rw00 00Transmit blocking time
U8ro6Number of entries
U16rw00 00Heart beat time [ms]
U8ro4Number of entries
Map.Attr.TypeDesigna
(hex)
00 00 00 CDProduct code
ExplanationValues
emergency message
[100s]
beat time [ms]
COB−ID = Node guard ID
Status (pre−operational,
operational, stopped)
3Revision
number
4Serial
number
10270Module listU8ro1 ŪNumber of connected CPX
1Module 0U16See CPX−
2Module 1
3Module 2
.........
1)
Sequence as in CPX terminal from left to right
Festo P.BE−CPX−FB14−EN en 0810b
xx xx.xx xxVersion (like object 100A)
xx xx xx xxSerial number (individual
system
description
for each module)
modules
Module code module 0
Module code module 1
Module code module 2
1)
1)
1)
2−23
Page 70
2. Commissioning
Index
(hex)
10290Error
Sub
tion
index
behaviour,
number
oferror
classes
1Communi
cation error
2Output error01With short circuit/overload
3Input error01With short circuit/overload
Map.Attr.TypeDesigna
ExplanationValues
(hex)
U8ro3Number of error classes
rw00With communication errors
(timeout/heart beat)
0 = pre−operational
1 = no state change
2 = stopped
Error code: 8130, 8140
As from V1.10: 8100, 8130,
8140
at output module
0 = pre−operational
1 = no state change
2 = stopped
Error codes: 23xx, 33xx
at input module or failure
in sensor supply
0 = pre−operational
1 = no state change
2 = stopped
Error codes: 21xx, 31xx
PDO 4Technology modules, status bits, I/O diagnostic interface
If necessary, the default PDO structure can be changed via
SDO (see PDO communication mapping parameter" in the
following sections, index1A00hŪ1A03h, 1600hŪ1603h)
Festo P.BE−CPX−FB14−EN en 0810b
2−25
Page 72
2. Commissioning
ppg
2.4.3Digital inputs (transmit PDO 1)
Index
(hex)
181 Ū
1FF
18000PDO com
1A000PDO com
Sub
Designa
index
tion
Transmit
PDO 1
munication
parameter
record
1PDO COB−ID U32rw180 + node IDDefault COB−ID of the
U = unsignedMap. = mapping possible
ro = read onlyAttr. = attribute
rw = read/write
1)
During the transition from pre−operational to operational, the current SDO values will be frozen"
(e.g. analogue inputs). These values will be transmitted with each remote transmission request
(RTR), irrespective of further settings (e.g. interrupt enable for analogue inputs).
Festo P.BE−CPX−FB14−EN en 0810b
2−27
Page 74
2. Commissioning
ppg
2.4.4Digital outputs (receive PDO 1)
Index
(hex)
201 Ū
27F
14000PDO com
16000PDO com
Sub
Designa
index
tion
Receive
PDO 1
munication
parameter
record
1PDO COB−ID U32rw200 + node IDDefault COB−ID of the
U = unsignedMap. = mapping possible
ro = read onlyAttr. = attribute
rw = read/write
1)
See remark in section 2.2.1.
2−28
Festo P.BE−CPX−FB14−EN en 0810b
Page 75
2. Commissioning
Index
(hex)
Sub
index
tion
62000Write
output 8bit
1
2xx... Outputs 8 Ū 15
3xx... Outputs 16 Ū 23
4xx... Outputs 24 Ū 31
5xx... Outputs 32 Ū 39
6xx... Outputs 40 Ū 47
7xx... Outputs 48 Ū 55
8xx... Outputs 56 Ū 63
9xx... Outputs 64 Ū 71
A
h
B
h
C
h
D
h
E
h
F
h
10
h
Map.Attr.TypeDesigna
ExplanationValues
(hex)
U8ro0 Ū 10Number of 8−output groups
rwYesxxStatus of outputs 0 Ū 7
xx... Outputs 72 Ū 79
xx... Outputs 80 Ū 87
xx... Outputs 88 Ū 95
xx... Outputs 96 − 103
xx... Outputs 104 Ū 111
xx... Outputs 112 Ū 119
xx... Outputs 120 Ū 127
Festo P.BE−CPX−FB14−EN en 0810b
2−29
Page 76
2. Commissioning
Index
(hex)
Sub
index
tion
62060Fault mode
output 8bit
1
2FF... Outputs 8 Ū 15
3FF... Outputs 16 Ū 23
4FF... Outputs 24 Ū 31
5FF... Outputs 32 Ū 39
6FF... Outputs 40 Ū 47
7FF... Outputs 48 Ū 55
8FF... Outputs 56 Ū 63
9FF... Outputs 64 Ū 71
A
h
B
h
C
h
D
h
E
h
F
h
10
h
Map.Attr.TypeDesigna
ExplanationValues
(hex)
U8ro0 Ū 10Number of 8−output groups
rwFFFault mode outputs 0 Ū 7
FF... Outputs 72 Ū 79
FF... Outputs 80 Ū 87
FF... Outputs 88 Ū 95
FF... Outputs 96 Ū 103
FF... Outputs 104 Ū 111
FF... Outputs 112 Ū 119
FF... Outputs 120 Ū 127
2−30
Festo P.BE−CPX−FB14−EN en 0810b
Page 77
2. Commissioning
Index
(hex)
Sub
index
tion
62070Error state
output 8bit
1
U8ro0 Ū 10Number of 8−output groups
Map.Attr.TypeDesigna
(hex)
rw00Error state outputs 0 Ū 7
200... Outputs 8 Ū 15
300... Outputs 16 Ū 23
400... Outputs 24 Ū 31
500... Outputs 32 Ū 39
600... Outputs 40 Ū 48
700... Outputs 48 Ū 55
800... Outputs 56 Ū 63
900... Outputs 64 Ū 71
A
B
C
D
E
F
10
h
h
h
h
h
h
h
00... Outputs 72 Ū 79
00... Outputs 80 Ū 87
00... Outputs 88 Ū 95
00... Outputs 96 Ū 103
00... Outputs 104 Ū 111
00... Outputs 112 Ū 119
00... Outputs 120 Ū 127
U = unsignedMap. = mapping possible
ro = read onlyAttr. = attribute
rw = read/write
ExplanationValues
Festo P.BE−CPX−FB14−EN en 0810b
2−31
Page 78
2. Commissioning
The states of the valves and outputs of the CPX valve terminal
can be defined in case there should be a fault.
Note
With Index 6206 you can define the outputs which are to
assume a defined status in the event of a fault.
With Index 6207 you can define the status which the fixed
outputs are to assume in the event of a fault.
The settings do not become active until the CPX valve
terminal is put into the operational mode.
After each switching on or after each reset (hardware
initialization), the default values will automatically be
accepted, any maskings will be overwritten.
The following applies:
Index (hex)
6206
Subindex 1 Ū 10
Bit 0 Ū 7
6207
Subindex 1 Ū 10
Bit 0 Ū 7
2−32
Definition
0 = status of the output is retained
h
h
1 = output assumes the status defined in index 6207
CANopen represents the 16−bit analogue values with the
following objects left justified in a 32−bit value:
6422, 6424, 6425, 6426, 6444, 5444, 5434
Values of an analogue input are loaded into the PDO only if
the following conditions are fulfilled:
Globale interrupt enable must be set to enable
(index6423).
With the interrupt trigger (index
6421), you can define
how the analogue value in the following step is to be
checked (minimum/maximum value, value modifica
tion, index 6424, 6425, 6426).
The channel number of the interrupt−triggering analogue
input is entered in Object 6422. The PDO is then transmitted
according to the transmission code in Object 1801
(FF
, FDh, FCh or 0 Ū F0h).
h
Festo P.BE−CPX−FB14−EN en 0810b
2−33
Page 80
2. Commissioning
Index
(hex)
281 Ū
2FF
18010PDO commu
U = unsignedMap. = mapping possible
ro = read onlyAttr. = attribute
rw = read/write
2.4.9Technology modules, status bits, I/O diagnostic interface (PDO 4)
Note
In order to use the status bits or the I/O diagnostic
interface, you must activate them with the DIL switches on
the field bus node (see section 1.2.2).
Further information on the status bits and on the I/O
diagnostic interface can be found in section 3.3 and 3.4.
Transmit PDO 4
Index
(hex)
481 Ū
4FF
18030PDO commu−
1)
Sub
Designation Type Attr.Map. Values
index
Transmit
PDO4
nication
parameter
record
1PDO COB−IDU32rw480 + nodeIDDefault COB−ID of the inputs
2Transmission
type
3Inhibit timeU1600 00Transmit blocking time
4not used
5Event timer00 00Time−controlled trans
See remark on page 2−27
Explanation
(hex)
xxTelegram length 2, 4, 6 or
U8ro05Number of entries
U8FFDefault: acyclic
8bytes
Byte 0, 1: Status bits or I/O
diagnostic interface (de
pending on configuration)
Byte 2, 3: reserved
Byte 4, 5: reserved
Byte 6, 7: reserved
1)
inputs [100s]
mission of the inputs [ms]
Festo P.BE−CPX−FB14−EN en 0810b
2−45
Page 92
2. Commissioning
ppg
Index
(hex)
1A030PDO commu−
61000Read input
index
nication
1
mapping
parameters
2
361 00 03 10 ... at IW2
461 00 04 10 ... at IW3
500 00 00 00 ... at mapping object5
600 00 00 00 ... at mapping object6
700 00 00 00 ... at mapping object7
800 00 00 00 ... at mapping object8
16bit
1
2xxIW1: depending on
Map.Attr.TypeDesignationSub
ExplanationValues
(hex)
U8rw0 Ū 8Number of entries
U3261 00 01 10 Pointer at IW0
61 00 02 10 ... at IW1
U8roYes0 Ū 20Number of IW groups
U16xxIW0, depending on
configuration1):
status bits or
I/O diagnostic interface
1. input word technology
module
configuration: 1. or 2. input
word technology module
1)
3xxIW2 technology module
.........
20
h
1)
Depending on diagnostic setting
2−46
xxIW31 technology module
Festo P.BE−CPX−FB14−EN en 0810b
Page 93
2. Commissioning
ppg
Sub
Index
(hex)
Designation Type Attr.Map. Values
index
Receive PDO 4
A description of the method of operation of the I/O diagnostic
interface can be found in the Diagnosis chapter of the CPX
System Description.
With Index 6306 you can define the outputs which are to
assume a defined status in the event of an error.
With Index 6307 you can define the status which the fixed
outputs are to assume in the event of an error.
The settings do not become active until the CPX valve
terminal is put into the operational mode.
After each switching on or after each reset (hardware
initialization), the default values will automatically be
accepted, any maskings will be overwritten.
2.4.10 Manufacturer specific profile
Further information can be found in the following tables and
in the CPX System Description (P.BE−CPX−SYS−...).
Index
DesignationMap. Explanation
(hex)
2000System data Operating mode, details see Tab.2/10
2010Module dataDetails see Tab.2/11
2200System diagnostic dataYesDetails see Tab.2/12
2210Module diagnostic dataDetails see Tab.2/13
(global system configuration)
Tab.2/9:Overview of the indices of the manufacturer specific profile area
Festo P.BE−CPX−FB14−EN en 0810b
2−49
Page 96
2. Commissioning
System data
Index
(hex)
20000System data U8ro3Number of parameters
Sub
index
Designa
tion
Type Attr.Values
(hex)
ExplanationFunc
tion no.
1Operating
mode1
2Fail safexxSee index 6206, 6207, 6306,
3Monitoring
the CPX
terminal
Tab.2/10: System data
xxCPX operating mode
Bit 0 Ū 3: CPX operating
mode
Bit 4:CPX expansion
Bit 5:Handheld
Bit 6:Force mode
Bit 7:System start
Tab.2/12: System diagnostic data (PDO mapping is possible)
Module diagnostic data
Index
(hex)
22100Module
Sub
Designa
index
tion
diagnostics
1Diagnostic
module 0
2Diagnostic
module 1
Type Attr.Values
ExplanationFunc
(hex)
U8ro1 ŪNumber of entries
U32ro00 Ū FF
00 Ū FF
00
00
00 Ū FF
00 Ū FF
00
00
I/O channel/channel number
Fault number
Ū
reserved
reserved
I/O channel/channel number
Fault number
reserved
reserved
1937
1943
tion no.
2008 +
1)
xx
............
1)
All details: See appendix in CPX system manual
Tab.2/13: Module diagnostic data
2−52
Festo P.BE−CPX−FB14−EN en 0810b
Page 99
2. Commissioning
g
00
3B
3
Numb
00
63
Number of 10 ms
1stmessage after power−on)
00
2F
Moduleposition
Diagnosticmemory parametersand data
Index
(hex)
Sub
index
Designa
tion
Type Attr.Values
(hex)
ExplanationFunc
tion no.
23000Status/
23100Diagnosis
mode
1
diagnostic
memory
2
3rw00Number of entries in the
4ro00Current status / overrun3483
5rw00Trigger conditions
600Module number (MN)3485
700Channel number (CN)3486
800Fault number (FN)3487
memory
11. Entry
(latest error)
22. entry
33. entry
......
28
40. entry
h
(oldest
saved error)
U8ro8Number of entries
rwxxDiagnostic memory mode3480
diagnostic memory
(writing 0" will delete all
entries)
(Run/stop filter 2, error
end filter, fault number filter,
module/channel filter)
U8ro0 Ū 28Number of entries
Oct.
string
00 Ū FF
00 Ū 17
Ū
00 Ū 3B
00 Ū 6
Ū
(+ 80)
00 Ū FF
00 Ū 2F
Ū
00 Ū FF
00 Ū FF
00 Ū FF
Number of days
Number of hours
er of minutes
Number of seconds
Number of 10 ms
(and designation for
1stmessage after power−on)
Module code
Module position
Channel number
Fault number
Following channels
3482
3484
3488,
Ū
Tab.2/14: Diagnostic memory data
Festo P.BE−CPX−FB14−EN en 0810b
2−53
Page 100
2. Commissioning
System parameters
Index
(hex)
Sub
index
Designa
tion
Type Attr.Values
(hex)
ExplanationFunc
tion no.
24000System
1)
At system start with saved parameterization, only the objects 2000Ū5FFF are loaded.
The objects 6000Ū are always loaded with the default settings after power−on.
parameters
1Parameter
byte 0
2Parameter
byte 1
3Parameter
byte 2
4 Ū 8reservedreserved
U8ro8Number of entries
rw0 Ū FFreserved4400
0 Ū FFMonitoring (active/inactive)4401
0 Ū FFBit 0, 1: not implemented
Bit 2, 3: Force mode
Bit 4, 5: not implemented
Bit 6, 7: System start
Tab.2/15: System parameters
Detailed information on parameters and data can be found in
the CPX system manual.
4402
1)
2−54
Festo P.BE−CPX−FB14−EN en 0810b
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.