INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE
FOR THE UNITED KINGDOM & EIRE
DOMIcompact F 24 D
IMPORTANT
Your "benchmark" Installation, Commissioning and Service Record Log Book is enclosed in the
last pages of this manual. “This record must be completed and left with the end user”.
Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme.
Benchmark has been introduced to improve the standards of installation and commissioning of central
heating systems in the UK and to encourage the regular servicing of all central heating systems to
ensure safety and efficiency.
Please see installation and servicing guidelines.
For EIRE (Southern Ireland) it is necessary to complete a “Declaration of Conformity” to indicate
compliance to I.S. 813. An example of this is given in the current edition of I.S. 813. In addition it is
necessary to complete the “Benchmark” logbook.
This symbol indicates “Caution” and is placed next to all safety information.
Strictly follow these instructions in order to avoid danger and damage to persons
or property.
This symbol calls attention to a note or important information, please read thourougly.
• Read the warnings given in this manual thoroughly.
They provide important information for safe installation, use and maintenance
• The instruction manual, by law must be left with the
end user.
• If the appliance is sold or transferred to another
owner or if the owner moves, leaving the appliance
behind, always ensure that the manual is kept with
the appliance for consultation by the new owner
and /or installer.
• Incorrect installation or poor maintenance absolves
the manufacturer from all liability for damage to
persons and property.
• Installation and maintenance must be carried out
in accordance with current legislation, according
to the manufacturer’s instructions and by qualified
corgi registered engineer.
• Before service or maintenance work is carried out
isolate the appliance from the mains electricity
supply.
• In the event of malfunction or faulty operation, isolate the appliance. Do not attempt to repair or carry
out any other operation on the appliance directly.
Contact Ferroli or a qualified engineer only.
Declaration of conformity
Manufacturer: FERROLI S.p.A.
Address: Via Ritonda 78/a 37047 San Bonifacio VR Italy
declares that this unit complies with the following EU directives:
Gas Appliance Directive 90/396
Efficiency Directive 92/42
Low Voltage Directive 73/23 (amended by 93/68)
Electromagnetic Compatibility Directive 89/336 (amended by 93/68)
• Repairs or the replacement of components must be
carried out exclusively by qualified personnel using
original spare parts only. Failure to adhere to the above
may compromise the safety of the appliance.
• To guarantee efficient operation, the appliance must
be serviced once a year by a Corgi registered engineer.
• The appliance may not be used for purposes other
than those for which it was explicitly designed.
• Incorrect installation and use or failure to follow the
instructions provided by the manufacturer absolve
the manufacturer from all liability for damage.
• After unpacking, check that the contents are correct
and undamaged.
• Keep packing out of reach of children as it could be
potentially hazardous.
• To clean external parts, use a damp cloth moistened
with soapy water if necessary. Avoid using abrasive
cleaning products and solvents.
Dear Customer,
Thank you for choosing DOMIcompact F 24 D, a FERROLI wall-mounting boiler featuring advanced
design and technology, high reliability and quality construction. Please read this manual carefully and
keep it for future reference.
DOMIcompact F 24 D is a high-efficiency appliance for heating and hot water production running on
natural or liquefied petroleum gas (configurable at the time of installation) and regulated by an advanced
microprocessor control system.
The boiler shell consists of a primary copper laminar heat exchanger and burner equipped with electronic
ignition and ionization flame control.
The boiler is totally room sealed from the installation room: the air required for combustion is drawn
from outside. The boiler also includes a fan, modulating gas valve, pump, expansion vessel, flow switch,
safety valve, temperature sensors, a safety thermostat and a low pressure switch .
Thanks to the microprocessor control and adjustment system with advanced self-diagnosis, unit operation is for the most part automatic. The power for heating is automatically governed by the control
system combined with the room thermostat (not supplied) The power for hot water is automatically and
continually governed to ensure a fast delivery and comfort under all operating conditions .
The user only has to set the temperature desired inside the home (by means of an optional room
thermostat or remote control, which is required under the building regulations 2002) or regulate the
temperature of the system, and set the desired outlet temperature for the hot water. The adjustment
and control system will provide optimum operation throughout the year.
The display continuously provides information on the unit’s operating status and it is possible to obtain
additional information on the sensor temperatures, set-points, etc , or configure them. Any operating
problems associated with the boiler are immediately signalled by the display and, if possible, corrected
automatically.
4
DOMIcompact F 24 D
1.2 Control panel
The control panel is composed of a multi-function button, two knobs and a display.
Key
1 Heating temperature adjustment and Summer/
Winter/ switch off control
2 Hot water temperature adjustment and switch
off control
3 Multi-function button (ECO/RESET/TEST)
4 Temperature display
During operation or standby in heating mode,
it displays the temperature of the heating
sensor. During hot water operation, it displays
the temperature of the hot water sensor.
5 Heating demand symbol
Appears during heating operation or when
adjusting the heating set-point temperature
6 Flame symbol
Appears when the burner is on
7 ECO symbol
ECO is displayed when the Economy function is on
8 Hot water demand symbol
Appears during hot water operation or when adjusting the hot water set-point temperature
Fig. 1
Information during operation
During normal operation, the boiler diagnostics display the running information or boiler status on the
control panel (Fig.1).see below.
Display
Type of operation
Boiler off
Boiler on stand-by
Boiler on stand-by / ECO
Heating operation
(burner on)
Hot tap water operation
(burner on)
Fault codes (See chap. 1.6 or 3.0)
(No demand from heating or Hot water)
(Displays heating flow temperature)
(Displays Hot water temperature)
(Frost protection active)
(Displays relevant fault code)
TEST mode operation
(burner on)
(For comissioning purposes only)
5
DOMIcompact F 24 D
1.3 Turning on and off
Ignition
• Open the gas isolation valve on the boiler.
• Purge the air from the pipe work to the gas valve.
• Turn on the 3amp electrical switch or insert the plug to the
boiler.
• Turn the heating and hot water control knobs onto their required
temperatures (see par. 1.4).
• The boiler is now ready to function automatically whenever hot
water is drawn or both the time clock and room thermostat call
for heating.
Turning off
Turn the knobs (ref. 1 and 2 Fig. 1) onto minimum.
If the boiler is turned off this way, then the P.C.B is still powe-
red.
Hot water and heating operation are disabled, the display shows
; but the frost protection function remains active
The frost protection will not work if the electricity and/or gas supply to the unit are cut off.
To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all
water from the boiler, the tap water and the system water; or drain off just the tap water and
add a suitable antifreeze to the heating system, as prescribed in chap. 2.3.
1.4 Adjustments
Summer/winter Switchover
Depending on the position of the control knobs “1” and “2” it is possible to switch off the boiler unit,
switch between summer and winter operation or turn off the domestic hot water .
Boiler offBoiler in Summer operation
(only hot water production is active)
Boiler in Winter operation
(Display indicates hot water demand)
Boiler with only heating on and hot
water off
(Display indicates heating demand)
6
DOMIcompact F 24 D
Switching off the boiler. Switching between summer and winter operation has priority over the
heating only time control (optional) when this is connected to the boiler.
C.H. temperature setting
To set the system delivery temperature, turn the knob (ref. 1 - Fig. 1).
It can vary from a minimum of 30 °C to a maximum of 85°C; however, it is advisable not to operate the
boiler below 45 °C. When the knob is turned the display lights up, the radiator symbol flashes and the
temperature displayed will be the temperature actually set. On completing this operation, the display
will stay on for another 5 seconds and then go back to the actual operating temperature providing
there is a demand.
Domestic Hot water temperature adjustment
To set the tap water temperature, turn the knob (ref. 2 - Fig. 1).
It can vary from a minimum of 40 °C to a maximum of 55 °C. When the knob is turned the display lights
up, the tap symbol flashes and the temperature displayed will be the temperature actually set. On
completing this operation, the display will stay on for another 5 seconds to then go back to the actual
operating temperature providing there is a demand.
If the boiler is connected to the optional remote open therm control, the above adjustments
(system and hot water temperature) can only be made with the remote control.
ECO/COMFORT selection
The unit is equipped with a special internal device that ensures a high hot-water delivery speed and
excellent user comfort. When comfort mode is active the water in the boiler is maintained at a predetermined temperature, which means that hot water is available at the boiler outlet as soon as a tap
is opened, ie with no waiting.
The user can turn the device off (ECO mode) by pressing the multi-function button for 2 seconds with
the boiler on standby. In ECO mode the display shows the relevant symbol. To turn on COMFORT mode,
press the multi-function button again for 2 seconds, the ECO symbol will vanish from the display.
TEST MODE selection
Pressing the multi-function button 3 times in 3 seconds turns on TEST mode (the heating and hot
water symbols flash simultaneously - see par. 3.1). If TEST mode is turned on by accident, press
the button 3 times in 3 seconds again to exit (Test time 15 minutes unless cancelled early).
7
DOMIcompact F 24 D
1.5 Maintenance
It is strongly recommended to carry out annual maintenance on the boiler and the heating system. Please
refer to the “maintenance” section in this manual.
The casing, the control panel and the aesthetic parts of the boiler can be cleaned using a soft and damp
cloth.
Do not use abrasives or solvents.
1.6 Faults
The boiler is equipped with an advanced self-diagnosis system that signals any faults on the display.
Some faults (from F1 to F3) cause a boiler shutdown. In this case, operation must be reset manually by
pressing the multi-function button (RESET) for 1 second
Other faults (from F5 to F37) cause temporary shutdowns that are automatically reset as soon as the
value causing the fault comes back within the boiler’s normal working range.
Listed below are some anomalies that can be caused by simple, user-solvable problems.
If the problem remains after two attempts at resetting, contact the Ferroli Service Centre.
For other faults, refer to section 3.4 “Troubleshooting”.
FaultCureDisplay code
Make sure that the gas cocks ahead of the boiler and on the
meter are open.
Boiler shutdown
Low system pressure
Before calling a Ferroli service engineer, check that the problem is not due to there being no
gas or electricity, or low system pressure.
Press the multi-function button (for 1 second) (fig.1)
In case of repeated shutdowns, contact the nearest assistance
centre.
Fill the 'system to 1-1.5 bar cold by means of the 'specific
cock located near the boiler.
Close the cock after 'use.
8
DOMIcompact F 24 D
2. INSTALLATION
2.1 General Instructions
This device must only be used for the purpose for which it is specially designed. This unit is
designed to heat water to a temperature below boiling point and must be connected to a heating system and/or a water supply system for domestic use, compatible with its performance,
characteristics and its heating capacity. Any other use is considered improper.
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE
WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT
LAW, THE RECOMENDATION OF BS STANDARDS, ANY LOCAL REGULATIONS AND THE RULES OF
COMPETENT WORKMANSHIP.
In IE, the installation must be carried out by a Competent Person and installed in accordance with the
current edition of I.S. 813 “Domestic Gas Installations”, the current Building Regulations and reference
should be made to the current ETCI rules for electrical installation.
Incorrect installation can cause damage or physical injury for which the manufacturer declines any
responsibility.
This appliance must be installed strictly in accordance with these instructions and
regulations:
The Gas Safety Regulations (Installations & Use).
The Local Building Regulations.
The Building Regulations (Part L).
The Buildings Standards (Scotland - Consolidated) Regulations.
British Standards Codes of Practice:
B.S. 5440 Part 1 Flues
B.S. 5440 Part 2 Air supply
B.S. 5449 FORCED CIRCULATION HOT WATER SYSTEMS
B.S. 6798 INSTALLATION OF GAS FIRED HOT WATER BOILERS
B.S. 6891 GAS INSTALLATIONS
B.S. 7671 IEE WIRING REGULATIONS
B.S. 4814 SPECIFICATION FOR EXPANSION VESSELS
B.S. 5482 INSTALLATION OF LPG
B.S. 3632 RESIDENTIAL PARK HOMES
B.S. 7593 TREATMENT OF WATER IN DOMESTIC HOT WATER CENTRAL HEATING SYSTEMS
B.S. 5546 INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
I.S. 813 DOMESTIC GAS INSTALLATIONS (EIRE ONLY)
Local Water Bye Laws
B.S. 5955-8 PLASTIC PIPEWORK INSTALLATION
For Northern Ireland the rules in force apply
9
DOMIcompact F 24 D
2.2 Boiler location
The boilers combustion chamber is sealed off from the installation room. The installation room must be
sufficiently well ventilated to prevent any dangerous conditions from forming in the event of even slight
gas leakage. This safety standard is required by the EEC Directive no. 90/396 for all gas units, including
those with a so-called sealed chamber.
Therefore the place of installation must be free of dust, flammable materials or objects or corrosive
gases. The room must be dry and not subject to freezing.
The boiler is design to be installed on a solid wall. The wall fixing must ensure a stable and effective
support for the appliance, using the bracket and fixings supplied.
If the unit is enclosed in a cupboard or mounted alongside, there must be space for normal maintenance
work. Fig. 2 and tab. 1 give the minimum clearances to leave around the unit.
This appliance does not require compartment ventilation for combustion purposes
C
AA
Table 1
Minimum
5 cm
A
20 cm
B
B
D
fig. 2
C20 cm
D
60 cm
(via an openable panel)
Drilling Template
Select suitable mounting position for boiler, using the template mark flue outlet and boiler mounting
points. Drill two 10mm holes 70mm deep to accept the wall plugs. Fit the supplied wall plugs on the
left and right side drill and fit the special wall plug in the middle (fig. 3). Fix the wall bracket to the wall
using standard lock nuts (M8) on both sides. Using a Core drill cut a 118mm diameter hole for the flue
as detailed on page 17. Mount the boiler on the wall bracket and secure using the special antitheft nut
(M8) as described in the fig. 3.
10
fig. 3
DOMIcompact F 24 D
Make Up Water
Provision must be made for replacing water lost from the sealed system. Reference should be made
to BS6798, for methods of filling and making up sealed systems. There must be no direct connection
between the boiler's central heating system and the mains water supply. The use of mains water to
charge and pressurise the system directly, is conditional upon the Local Water Byelaws. Again any such
connection must be disconnected after use. The temporary filling loop (Not supplied) is shown in fig. 5.
Ensure the filling point is on the return pipe to the boiler.
Attention - is drawn to the Local Water Byelaws.
Fittings manufactured from duplex (alpha-beta) brass are not acceptable for underground use and certain
water undertakings will not accept their use above ground.
Ensure all pipework is adequately supported
Hot water
Gas
NOTE: An automatic bypass capable of
passing 6 ltrs per minute must be fitted as
far as possible from the boiler if thermostatic radiator valves are fitted thoughout.
As per the building regulations part ‘L’
Cold water inlet
Automatic
Bypass
4
3
Filling
point C.H.
2
Additional expansion
vessel C.H. (if required)
1
fig. 4
Key
1 Filling point C.H 15mm
isolation valve.
2 Temporary flexible connection
3 Cold water supply 15mm
isolation valve
4 Double check valve
fig. 5
11
DOMIcompact F 24 D
2.3 Boiler water connections
The heating capacity of the unit should be previously established by calculating the building’s heat
requirement according to current regulations. For efficient operation and long life of the boiler, the
plumbing system must be well designed and always complete with all those accessories that guarantee
regular operation and running, ie room thermostat, trv’s and automatic bypass etc .
If the flow and return pipes follow a path where air pockets could form in certain places, it is esential
to install air vent valves at these points. Also, install a type “A” drain cocks at the lowest point s in the
system to allow its complete draining. when required The temperature differential between the flow
manifold and the return to the boiler should not exceed 20° C.
A minimum flow of 6 litres/min is requied through the heat exchanger, it is therefore essential to fit an
automatic by-pass a min of 3 metres away from the appliance, This should be calibrated on site.
Do not use the water system pipes to
earth electrical appliances.
Before installation, carefully flush all the pipes
of the heating system to remove residues or
impurities that could affect the unit’s efficient
operation (BS 7593 Building regs Doc L).
Make the connections to the appliance as
shown in fig. 6.
3595606095113
12345
Key
1 Heating system flow Ø 3/4”
2 Hot water outlet Ø 1/2”
3 Gas inlet 1/2”
4 Tap water inlet Ø 1/2”
5 Heating system return Ø 3/4”
3695114956060
460
fig. 6
It is essential to install the isolation valves supplied between the boiler and heating system, allowing the
boiler to be isolated from the system if necessary.
The safety valve outlet must be connected to a 15 mm pipe to allow safe discharge to the outside
ground in the event of over-pressure in the heating circuit. If this is not done, and the drain valve
opens and floods the room, the boiler manufacturer is not to be held responsible. The pipework
must have a continuous fall from the boiler, The outlet should face back against the outer brickwork or building face to prevent harm or injury from hot water discharging in the evet of an
over-pressuried system.
Make the boiler connection in such a way that its internal pipework is free of stress.
If a check valve is installed on the tap water circuit (where applicable), it is necessary to mount a safety
valve between the boiler and this circuit (check valve minimum 3 meters from boiler).
12
DOMIcompact F 24 D
The connecting kits shown in fig. 7 are supplied as standard.
Key
A = Nut
B = Compression olive
D = 3/4 seal (green)
E = 1/2 seal (green)
F = 1/2 gas seal (blue)
G = Filter
H = Cap
D
A
B
Ø22
A
B
Ø15
A
B
Ø22
Flow isolation valve
E
Hot water connection
F
Gas isolation valve
E
A
Ø22
B
Ø15
D
A
B
Return isolation valve
Cold water isolation valve
fig. 7
Water treatment
When treatment is used ferroli limited only recommend the use of proprietary Brand s , such as Fernox or
Sentinel water treatment products, which must be used in accordance with the manufacturers instructions,
Note - When the boiler is installed with an existing or new system any unsuitable additives or system
debris must be removed by thorough chemical cleansing. All systems should be cleansed according to
B.S. 7593.
Note - It is important that the correct concentration of the water treatment product is maintained in
accordance with the manufacturers instructions.
Note - In hard water areas it may be necessary to install a scale reducer prior to the boiler on the cold
water inlet .
13
DOMIcompact F 24 D
2.4 Connection to the gas system
If necessary the local Gas supplier should be consulted, at the installation planning stage, in order to
establish the availability of an adequate supply of gas.
An existing service pipe must not be used whitout prior consultation with the local Gas supplier.
A gas meter can only be connected by the Local Gas supplier, or by a Local Gas suppliers Contractor.
Installation pipes should be fitted in accordance with BS6891.
Appliance inlet working pressure must be 20 mbar MINIMUM, for NG and 37 mbar minimum for pro-
pane.
Do not use pipes of a smaller diameter than the combination boiler inlet gas isolation valve (22 mm).
The complete installation must be tested for gas soundness and purged as described in BS6891.
All pipework must be adquately supported. An isolating gas valve is provided and must be fitted
on the boiler gas inlet. Please wait 10 minutes when lighting from cold before checking the gas
rate, this will ensure thermal equilibrium.
2.5 Electrical Connections
The unit must be installed in conformity with current national and local regulations inc 16th Edition &
B.S 7671 .
Connection to the electrical supply.
The boiler must be connected to a single-phase, 230 Volt-50 Hz electrical supply.
The unit’s electrical safety is only guaranteed when correctly connected to an efficient earthing
system installed according to current safety standards and checked by a professionally qualified
person . The manufacturer is not responsible for any damage caused by failure to earth the system.
Also make sure that the electrical system is adequate for the maximum power absorbed by the
unit, as specified on the boiler dataplate, in particular ensuring that the crossectional area of the
electrical cables are suitable for the power absorbed by the unit .
The boiler is prewired and provided with a cable for connection to the electrical supply The prewired
cable must be connected to the supply with a permanent connection and equipped with a double pole
switch which contacts have a minimum opening of at least 3 mm, and fused at max. 3A between the
boiler and the line. It is important to check the polarities (LIVE: brown wire / NEUTRAL: blue wire /
EARTH: yellow-green wire) and ensure they are correctly connected to the corresponding terminals on
the electrical supply .
The user must never change the boilers power cable. If the cable gets damaged, switch off the unit
and have it changed only by professionally qualified personnel. If changing the electric power cable,
use only “HAR H05 VV-F” 3x0.75 mm2 cable with a maximum outside diameter of 8 mm.
5 Core cable must not be used to replace the existing 3 core!
14
DOMIcompact F 24 D
Access to the electrical terminal block
To access the terminal block where the room thermostat (Low voltage) or the remote timer control is
to be connected, carry out the following operations:
1 Unscrew the two screws “A” (Fig. 8a)
2 Lower the instrument panel (Fig. 8b)
3 Turn the instrument panel (Fig. 8c)
You can now access the terminal block “B”
(Fig. 8c)
Low voltage time
clock or
1
Room
thermostat
2
Fig. 8a
Fig. 8b
A
A
Or
1
2
Remote
timer
control
(Opentherm)
B
Fig. 8c
15
DOMIcompact F 24 D
2.6 Flue system
The unit is “type C” with an airtight chamber and forced draught, the air inlet and fume outlet must be
connected to one of the following extraction/suction systems. With the aid of the tables and methods of
calculation indicated, before commencing installation, it is first necessary to check that the fume ducts
do not exceed the maximum permissible lengths. The current standards and local regulations must be
observed.
This C-type unit must be installed using the fume exhaust and suction ducts supplied by FERROLI
S.p.A. in accordance with UNI-CIG 7129/92. Failure to use them automatically forfeits all warranty
and liability of FERROLI S.p.A.
Restrictors
Boiler operation requires fitting the restrictors supplied with the unit as instructed in the following
tables.
Choosing the restrictor using
concentric pipes
TypeLength up to:Restrictor to use
Concentric
60/100
Concentric
80/125
1 bend + 1 metre 43 mm
1 bend + 4 metres No restrictor
1 bend + 3 metres 43 mm
1 bend + 4 metres 47 mm
1 bend + 5 metres No restrictor
1
2
Diaphragm
Choosing the restrictor using
two pipe system
Pipe length calculated
in linear metres
MinMax
0 m15 m43 mm
15 m38 m47 mm
38 m48 m
3
2
Restrictor to use
No restrictor
3
4
16
1
5
Restrictor
6
The restrictor Ø43 is fitted as standard on all boilers.
Before inserting the flue outlet pipe, it is therefore necessary to check there is the right restrictor
(when it is to be used) and that it is correctly positioned.
DOMIcompact F 24 D
70 min.
70 min.
Connection with concentric flue
The unit can be connected to a coaxial air/fume duct with a wall or rooftop outlet as shown on the
following drawings. Numerous accessories are available on request to meet the various installation
requirements. Please refer to the fume accessory catalogue or the price list.
Rear Outlet
Side view
P
S
Bend 60/100
010007X0
80
30
95
P = S + 93 mm
View from above
50*43
125
*= between
10 and 60 mm
70
Cut the internal pipe
70 mm longer than “P”
Side Outlet
Front view
L
Bend 60/100
010007X0
80
30
95
194266
Ø60 Ø80
DS
50*
125
*= between
70
10 and 60 mm
Cut the internal pipe
70 mm longer than “L”
L = S + D + 251 mm with rh outlet
S + D + 179 mm with lh outlet
80
-3 mm/m
266194
View from above
108
30
95
43
Drill the wall 10-20 mm
more than the pipe diameter
70
Tilt downwards
by 3 mm/m
S 50* 125
P
Fig. 9a
108
30
95
194266
DS50* 125
L
Fig. 9b
Drill the wall 10-20 mm
more than the pipe diameter
70
Tilt downwards
by 3 mm/m
17
DOMIcompact F 24 D
The total length in linear metres of the coaxial
duct must not exceed the maximum lengths
stated in the following table, considering that
each bend gives rise to the stated reduction.
For example, a duct D= 60/100 composed of 1
bend of 90° +1 horizontal metre + 2 bends of
45° + 1 horizontal metre has a total equivalent
length of 4 metres.
Ø mm
60/100
Maximum permissible
flue length
Reduction factors for bends
Concentric bend at 90° - Ø 60/100 mm1 m
Concentric bend at 45° - Ø 60/100 mm0,5 m
Concentric bend at 90° - Ø 80/125 mm0,5 m
Concentric bend at 45° - Ø 80/125 mm0,25 m
5 m5 m
Ø mm
80/125
Roof end piece
Terminale tetto
1KWMA83U
1KWMA83U
Tegola inclinata
Angled roof tile
1KWMA82U
1KWMA82U
Prolunga 60/100
Extension 60/100
1KWMA56U
1KWMA56U
Vertical Outlet
10
1000125
50
950
50
For the installation:
1. Define the position for installing the unit
2. Drill the wall for the air/fume pipe outlet according to the references stated in the figures,
considering that the horizontal sections of
piping must have a gradient of approximately 3 mm per metre of length downwards
to prevent any rainwater getting into the
boiler.
3. Make a hole of diameter 10 - 20 mm greater
than the nominal diameter of the coaxial pipe
used to facilitate insertion.
4. If necessary, cut the end pipe to size, considering that the external pipe must protrude
from the wall by between 10 and 60 mm (Fig.
9a and 9b). Eliminate the cutting burrs.
5. Connect the ducts to the boiler, positioning
the gaskets correctly and seal the wall coupling points with special sleeves.
Adattatore
Concentric
concentrico 60/100
adapter 60/100
1KWMA33K
010006X0
50950
95050
68
194266
Fig. 9c
18
DOMIcompact F 24 D
Connection with two pipe system
The unit can be connected to a system of separate air/fume ducts for a wall or rooftop outlet
as shown on the drawings 10 - 11 alongside.
Numerous accessories are available on request
to meet the various installation requirements.
The components used most frequently are
stated in the tables.
Please refer to the fume accessory catalogue or
the price list for additional components.
To check you do not exceed the maximum permissible duct length, it is necessary to make a
simple calculation before installation:
1. For each component, the tables provide an
“equivalent load loss in linear metres”, depending on the position of installation of the component (with air suction or fume extraction,
vertical or horizontal).
The loss is called “equivalent in linear metres”
since it is compared to the loss of one metre of
duct in air suction (defined as equal to 1). For
example, a bend at 90° of Ø80 in fume extraction
has an equivalent loss of 2.5 linear metres, i.e.
it has a loss equal to that of 2.5 linear metres
of duct in air suction.
2. After completely defining the layout of the
system of split flues, add up the losses in equivalent metres, depending on the installation
position, of all the components and accessories
in the system.
Flue
Air
Fig. 10
6
3. Check that the total calculated loss is less than
or equal to 48 equivalent metres, i.e. the maxi-
mum permissible for this model of boiler.
If the chosen flue system exceeds the
maximum permissible limit, it is recommended to use ducts with a larger diameter for some sections.
Ref.N° Pieces Description
11Air bend Ø801.5 m
21Horizontal air pipe Ø801.0 m
31Windproof end piece2.0 m
41Condensate collection cup coupling3.0 m
536Vertical fume pipe Ø8036.0 m
61Outlet flue + coupling4.0 m
Total47.5
Equivalent
loss
5
4
123
Fig. 11
19
Table of pipe and accessory losses
DOMIcompact F 24 D
A
c
c
e
s
s
o
r
e
s
Ø
8
0
i
Description
Pipe Ø 80
male-female
Bend 45° Ø 80 mm
female-female
Bend 90° Ø 80 mm
male-female
Bend 90° Ø 80 mm
cap+trap to
T-coupling /M/F
drain condensate
80 mm with inspection
Equivalent losses
in metres (linear)
AirFlue
Vertical
Vertical
Horizontal
Horizontal
A
c
c
e
s
s
o
r
e
s
Ø
8
0
Equivalent losses
in metres (linear)
AirFlue
Description
products of
Windproof end piece
combustion Ø 80 mm
Ø 80 mm
air end piece
Suction protection
air suction
Fume exhaust flue
for coaxial connection
Vertical
Vertical
Horizontal
Horizontal
i
Coupling for flue
fume exhaust Ø 80 mm
20
air suction
Fume exhaust flue
for split connection Ø 80 mm
cup coupling
Condensate collection
Ø 80/100 mm
Cup reduction
The stated loss values refer to genuine Ferroli ducts and accessories.
DOMIcompact F 24 D
F
l
e
x
i
b
l
e
p
i
p
e
Description
AISI 316L
int. Ø 72 mm,
ext. Ø 79 mm.
Roll of flexible pipe
30 m, smooth inside,
AISI 316L
End sleeve
flexible pipe
Ø 72/79 mm to 80 mm
AISI 316L
End sleeve
flexible pipe
Ø 79/72 mm to 80 mm
Equivalent losses
in metres (linear)
AirFlue
Vertical
Horizontal
Curved 90°
Vertical
Horizontal
Curved 90°
A
c
c
e
s
s
o
r
i
e
s
Description
Pipe Ø 100
male-female
male-female
Bend 45° Ø 100 mm
male-female
Bend 90° Ø 100 mm
Windproof
end pieces
products of
combustion
Ø 100Ø 100
Equivalent losses
in metres (linear)
Air
261.rtf
263.rtf
Flue
262.rtf
264.rtf
The stated loss values refer to genuine
Ferroli ducts and accessories.
Ø
Cup
1
reduction
Ø 100/80 mm
0
0
Cup
reduction
Ø 100/80 mm
21
DOMIcompact F 24 D
Terminal Position
P
Q
l
F
J
L
B
G
Q
D, E
C
A
H
H
MM
N
Fig. 12
Minimum Dimensions of Flue Terminal Positions
Q
N
K
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
NOTE
N/A = Not applicable
Directly below an opening, air brick,
opening windows, etc.
Above an opening, air brick,
opening windows, etc.
Horizontally to an opening, air brick,
opening windows, etc.
Below gutters, soil pipes or drain pipes
Below eaves
Below balconies or car port roof
From a vertical drain pipe or soil pipe
From an internal or external corner
Above ground roof or balcony level
From a surface facing the terminal
From a terminal facing the terminal
From an opening in the car port (e.g. door,
window) into the dwelling
Vertically from a terminal on the same wall
Horizontally from a terminal on the same wall
From the wall on which the terminal is mounted
From a vertical structure on the roof
Above intersection with roof
300mm
300mm
300mm
75mm
200mm
200mm
150mm
100mm
300mm
600mm
1200mm
1200mm
1500mm
300mm
N/A
150mm
300mm
22
In addition, the terminal must not be nearer than 300mm to an opening in the
building fabric formed for the purpose of accommodating a built-in element
such as a window frame.
DOMIcompact F 24 D
Connection to collective flues or single flues with natural draught
The UNI 10641 standard prescribes the design criteria and checking the internal dimensions of the
collective flues and single flues with natural draught for units with a sealed chamber equipped with a
fan in the combustion circuit.
If you are then going to connect the Domicompact F 24 Boiler to a collective flue or a single flue with
natural draught, the flue must be expressly designed by professionally qualified technical personnel in
conformity with the UNI 10641 standard.
In particular, flues must have the following characteristics:
• Be sized according to the method of calculation stated in the standard
• Be airtight to the products of combustion, resistant to the fumes and heat and waterproof for the condensate
• Have a circular or quadrangular cross-section (some hydraulically equivalent sections are permissible),
with a vertical progression and with no constrictions
• Have the ducts conveying the hot fumes adequately distanced or isolated from combustible materials
• Be connected to just one unit per floor, for at most 6 units in all (8 if there is a compensation duct or
opening)
• Have no mechanical suction devices in the main ducts
• Be at a lower pressure, all along their length, under conditions of stationary operation
• Have at their base a collection chamber for solid materials or condensation of at least 0.5 m, equipped
with a metal door with an airtight closure.
23
DOMIcompact F 24 D
3. SERVICE AND MAINTENANCE
3.1 Adjustments
All adjustment and conversion operations must be carried out by a Qualified and trained engineer such
as a Ferroli Service.engineer
FERROLI S.p.A. declines any responsibility for damage or physical injury caused by unqualified and
unauthorised persons tampering with the device.
Gas supply conversion
The unit can function with either Natural Gas or LPG and is factory-set for use with one of the two gases,
as clearly shown on the packing and on the unit’s dataplate. Whenever a different gas to that for which
the unit is preset has to be used, a conversion kit will be required, proceeding as follows:
1. Replace the injectors at the main burner, by inserting those specified in the technical data table in chart.
4, according to the type of gas used
2. Adjust the burner minimum and maximum pressures (ref.to page 33), setting the values given in the
technical data chart for the type of gas used.
3. How to Adjust the parameter for the specific type of gas to be used:
- turn the boiler onto standby
- press the RESET button for 10 seconds
- P1 will appear on the display
- press the RESET button for 5 seconds
- turn the hot water knob (ref. 2 - fig 1) onto “0” (for Natural Gas operation) or onto “1” (for LPG
operation)
- press the RESET button for 5 seconds
- P2 will appear on the display
- turn the heating knob (ref. 1 - fig 1) onto minimum and then onto maximum
- the boiler will go back onto standby
- turn the heating & hot water knobs onto the set temperatures.
4. Attach the sticker contained in the conversion kit, near the dataplate, as proof of the conversion.
Turning on TEST mode
To turn on TEST mode, press the multi-function button 3 times
in 3 seconds.
The display will show the radiator and hot water symbols flashing,
the current heating power, the ECO symbol (if ECONOMY mode
is on) and the flame symbol.
To exit TEST mode, press the multi-function button 3 times in 3
seconds.
TEST mode turns off automatically after 15 minutes.
X3
24
DOMIcompact F 24 D
Adjusting burner pressure
Since this unit has flame modulation, there are two fixed pressure settings: the minimum and maximum,
which must be as stated in the technical data chart according to the type of gas.
• Connect a suitable pressure gauge to pressure point “B” downstream from the gas valve.,having loosened it first
• Disconnect the pressure compensation tube “H”.
• Take off the protective cap “D”.
• Run the boiler in TEST mode (press the multi-function button 3 times in 3 seconds):
- TEST mode on: turn the heating knob (ref. 1 - fig 1) onto maximum.
• Adjust the maximum pressure with the screw “G”, clockwise to increase it and anticlockwise to decrease
it.
• Disconnect one of the two electrical connectors from the modureg “C” on the gas valve.
• Adjust the minimum pressure with the screw “E”, clockwise to decrease it and anticlockwise to increase it.
• Reconnect the electrical connector disconnected from the modureg on the gas valve.
• Check that the maximum pressure has not changed.
• Reconnect the pressure compensation tube “H”.
• Put the protective cap “D” back on.
• To end TEST mode, repeat the sequence for turning it on or wait 15 minutes
• Shut down the boiler
• Remove the pressure gauge
• Re-seal test point ‘B’
• Re-light the boiler and check for gas leaks using a suitable “Leak detection fluid”
Key
B Pressure point
CModureg electrical connection
D Protective cap
EMinimum pressure adjustment
GMaximum pressure adjustment
fig. 13
Having disturbed test point ‘B’ when
checking or adjusting the gas pressures, it
is considered mandatory to check for gas
leaks using a suitable leak detection fluid
or sniffer.at that connection
25
DOMIcompact F 24 D
Adjusting the maximum heating output
To adjust the heating power, set the boiler on TEST operation (see par. 3.1). Turn the heating temperature control knob (ref. 1 - Fig. 1) clockwise to increase the power or anticlockwise to decrease it
(see pressure/power diagram Fig. 20). The display shows the power setting from 0 to 99%. Exit TEST
operation (see par. 3.1). The maximum heating power will remain as set during the TEST mode. (100%
output shown as 99% due to the display only being 2 digits ).
Ignition power adjustment
To adjust the ignition power, set the boiler on TEST operation (see par. 3.1).
Turn the hot water temperature control knob (ref. 3 - Fig. 1) clockwise to increase the power or anti-
clockwise to decrease it (see pressure/power diagram Fig. 20). The display shows the power setting
from 0 to 60%. Exit TEST operation (see par. 3.1). The ignition power will remain as set during the TEST
mode.
NOTE Recomended ignition pressure for standard 100mm concentric horizontal flueing is 30%
3.2 Initial start-up
Commissioning must be performed by Qualified Personnel only!.
Checks to be made at initial start up, and after all maintenance operations that involved disconnecting from the system or an intervention of a safety device.
Before lighting the boiler:
• Open any isolation valves between the boiler and the systems.
• Check the soundness of the gas system, proceeding with caution and using a suitable leak detection
fluid to detect any leaks in connections.after completing a tightness test
• Fill the water system and make sure that all air contained in the boiler and the system has been vented
by opening the air vent valve on the boiler and any vent valves on the system.
• Make sure there are no water leaks in the system, hot water circuits, connections or boiler.
• Make sure the electrical supply is correctly connected.
• Make sure that the unit is connected to a good earthing system.
• Make sure that there is sufficient gas available to produce safe combustion. (min inlet working pressure
= 20mbar).
• Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler.
Lighting the boiler
• Open the gas isolation valve on the boiler.
• Purge the air from the gas pipe work to the boiler.
• Switch on the electrical supply to the boiler.
• Turn control knob “1” (Fig. 1) onto Winter in correspondence with a value greater than 50 °C and ensure
the room thermostat is calling, At this point, the burner will light and the boiler begins to function
automatically, controlled by its software and safety devices.
If, after following the lighting procedure, the burners do not light and fault F1 is generated, press
the RESET button for 1 second and release it. The software will repeat the ignition cycle in the
next 30 seconds. If the burners do not light after the second attempt, consult the “Troubleshooting” paragraph.
26
In case of an electrical power failure while the boiler is working, the burners will go out and reignite automatically when power is restored.
DOMIcompact F 24 D
Checks during operation
• Check the soundness of the gas circuit and water systems.
• Check the efficiency of the flue and air-flue ducts while the boiler is working.
• Check that the water is circulating properly between the boiler and the systems.
• Make sure that the gas valve modulates correctly in both the heating and hot water production
modes.
• Check for correct ignition of the boiler by performing various tests, turning it on and off with the room
thermostat or remote control.
• Make sure that the gas consumption indicated on the meter corresponds to that given in the technical
data table in chap. 4.(Input rating)
• Check there is the correct flow rate of hot water with the Δt stated in the technical data chart: The
measurement should be made with specific instruments and as close as possible to the boiler, also considering the heat lost from the pipe work.
• Make sure that with no call for heating the burner ignites correctly upon opening a hot water tap. Check
that during heating operation, on opening a hot water tap, the heating pump stops and there is a constant production of hot water.
Turning off
Turn the knobs (ref. 1 and 2 Fig. 1) onto minimum.
When the boiler is turned off, the printed circuit board is still powered.
Hot water and heating operations are disabled, the display shows ; but the frost protection mode
remains active..
The frost protection system will not work if the electricity and/or gas supply to the boiler are
cut off.
To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all
water from the boiler, both tap and the system water; or drain off just the tap water and add a
suitable antifreeze to the heating system, as prescribed in chap. 2.3.
3.3 Maintenance
The following operations must only be carried out by suitably trained and Qualified Personnel,
such as Ferroli service engineers.
Seasonal inspection of the boiler and flue
It is advisable to carry out the following checks at least once a year:
• The control and safety devices (gas valve, flow switch, thermostats, etc.) must function correctly.
• The air-flue terminal and ducts must be free of obstructions and leaks.
• The gas and water systems must be sound.
• The burner and exchanger must be clean. Follow the instructions in the next paragraph.
• The electrode must be free of debris and correctly positioned.
• The water pressure in the cold water system must be approximately 1 bar; otherwise, bring it to that
value.
• The expansion tank must be filled with air @ 1bar.
• The gas flow and pressure must correspond to that given in the respective tables.
• The circulation pump must be manually spun, vented and not be restricted.
Opening the casing
To open the boiler casing:
1 Unscrew the two screws A
2 Lower the instrument panel
3 Drop down the instrument panel
27
4 Fully unscrew the two screws B
5 Raise and remove the casing C
Before carrying out any operation inside the boiler, disconnect the electrical power and isolate
the gas supply.
DOMIcompact F 24 D
A
fig. 14a
A
fig. 14b
C
B
fig. 14c
B
fig. 14d
Cleaning the boiler and burner
The body and burner must not be cleaned with chemical products or wire brushes. Special care must be
taken over all the seals pertaining to the sealed chamber (gaskets, cable clamps, etc.).
After performing all these operations, check and carry out all the phases of ignition and thermostat
operation, the gas valve and circulation pump.
After these checks, make sure there are no gas leaks.
Combustion analyser testing
It is possible to analyse the combustion through the
air and flue sampling points shown in fig. 15.
To make the measurement, it is necessary to:
1) Insert the probes as far as the stop;
2) Open a hot water tap;
3) Adjust the hot water temperature to maxi-
mum.
4) Wait 10-15 minutes for the boiler to stabilize*
5) Take the measurement.
Analyses made with an unstabilized boiler
can cause measurement errors.
28
Fumes
Air
Fig. 15
DOMIcompact F 24 D
3.4 Troubleshooting
Fault Diagnosis
The boiler is equipped with an advanced self-diagnosis system. In the event of a fault within the boiler,
the display will show the relevant code.
There are faults that cause shutdown (faults from F1 to F3): in order to restore operation it requires the
operator to press RESET for 1 second (ref. 2 - Fig. 1) if the boiler fails to start, it will be necessary to
resolve the fault indicated on the display.
Other faults (from F5 to F37) cause temporary shutdowns that are automatically reset as soon as the
value comes back within the boiler’s normal working range.
Fault
No burner ignition
Display code
F1
Flame present with
burner off signal
Safety thermostat trips Heating sensor damaged
F2
F3
Air pressure switch
(fails to close the contacts
within 60 sec. of turning
on the fan)
F5
Possible cause
No gas
Detection or ignition
electrode fault
Defective gas valve
Ignition power too low
Electrode fault
Card trouble
No water circulation in
the system
Air in the system
Air pressure switch
contact open
Incorrect wiring to the
air pressure switch
Wrong diaphragm
Flue not correctly sized
or obstructed
Cure
Check the regular gas flow to the
boiler and the air has been eliminated
from the pipes.
Check the wiring of the electrode
and that it is correctly positioned and
free of any deposits
Check and change the gas valve
Adjust the ignition power
Check the ionizing electrode wiring
Check the card
Check the correct positioning and
operation of the heating sensor
Check the circulator
Vent the system
Check the wiringoCheck the fan
Check the pressure switch
Change the restrictor
Delivery sensor fault Sensor damaged
F7
Tap water sensor fault Sensor damaged
F9
Low system pressure System empty
F37
Wiring shorted
Wiring broken
Wiring shorted
Wiring broken
Water pressure switch
not connected or damaged
Check the wiring or change
the sensor
Check the wiring or change
the sensor
Fill the system
Check the sensor
29
DOMIcompact F 24 D
4 TECHNICAL CHARACTERISTICS AND
DATA
4.1 Dimensions and connections
Top view
74120120146
108158
680
Key
1Heating system delivery Ø 3/4”
2Hot water outlet Ø 1/2”
3Gas inlet 1/2”
4Tap water inlet Ø 1/2”
5Heating system return Ø 3/4”
12345
3660956095
460
681
114
30
Fig. 16
Bottom view
DOMIcompact F 24 D
4.2 General view and main components
91
16
132
34
49
81
20
21
42
47
90
5
2943187
Key
5 Airtight chamber
7 Gas inlet
8 Hot water outlet
9 Cold water inlet
56
10 System flow
11 System return
14 Safety valve
16 Fan
28
19 Combustion chamber
27
20 Burner assembly
21 Main nozzle
22 Burner
26 Combustion chamber insulation
27 Copper exchanger for heating
and hot water
28 Flue manifold
29 Flue outlet manifold
19
32 Heating circulator
26
34 Heating temp. sensor
36 Automatic air vent
22
38 Flow switch
42 Tap water temperature sensor
43 Air pressure switch
44 Gas valve
47 Modureg
49 Safety thermostat
14
56 Expansion tank
36
81 Ignition and detection electrode
90 Flue detection point
91 Air detection point
114
114 Water pressure switch
132 Flue deflector
187 Flue restrictor
1087
44
38
91132
Fig. 17
31
4.3 Hydraulic diagram
29
DOMIcompact F 24 D
187
16
49
34
27
20
42
-
+
5
43
56
81
44
114
14
Key
5 Airtight chamber
7 Gas inlet
8 Hot water outlet
9 Cold water inlet
10 System delivery
11 System return
14 Safety valve
16 Fan
20 Burner assembly
27 Heat exchanger
29 Flueoutlet manifold
32 Heating circulator
34 Heating temperature sensor
78
9
Fig. 18
32
38
1110
38 Flow switch
42 Tap water temperature sensor
43 Air pressure switch
44 Gas valve
49 Safety thermostat
56 Expansion tank
81Ignition and detection electrode114 Water pressure switch187 Flue restrictor
32
DOMIcompact F 24 D
4.4 Technical data table
PowersPmaxPmin
Heating Power (Net Heat Value - Hi)kW25,88,3
Available Thermal Power 80°C - 60°CkW24,07,2
Hot Water Heating PowerkW24,07,2
Energy marking (92/42 EEC directive)
NOx emission class3
Gas supplyPmaxPmin
Natural Gas main nozzles (G20)mm12x1,30
Natural Gas supply pressure (G20)mbar20,0
Pressure at Natural Gas burner (G20)mbar12,01,5
Natural Gas delivery (G20)nm3/h2,730,88
LPG main nozzles (G31)mm12x0,77
LPG supply pressure (G31)mbar37,0
Pressure at LPG burner (G31)mbar35,05,0
LPG burner (G31)kg/h2,000,65
Heating
Maximum working temperature in heating°C90
Maximum working pressure in heatingbar3
Safety valvebar3
Minimum working pressure in heatingbar0,8
Expansion tank capacitylitri8
Expansion tank pre-filling pressurebar1
Boiler water contentlitres1,5
Hot water
Maximum hot water production Δt 25 °Cl/min13,7
Maximum hot water production Δt 30 °Cl/min11,4
Maximum working pressure in hot water productionbar9
Minimum working pressure in hot water productionbar0,25
Hot water contentlitres0,5
Dimensions, weights connections
Heightmm680
Widthmm460
Depthmm266
Weightkg34
Gas system connectioninches1/2”
Heating system connectionsinches3/4”
Hot water circuit connectionsinches1/2”
Electrical power supply
Max electrical power absorbedW110
Hot water max electrical power absorbedW40
Power voltage/frequencyV/Hz230/50
Electrical protection ratingIPX5D
ÌÌÌ
33
4.5 Diagrams
Pressure - power diagrams
mbar
DOMIcompact F 24 D
G31
LPG
G20
Natural
gas
H [m H
Circulator losses of head
7
O]
2
6
3
5
2
4
3
1
2
1
kW
Fig. 19
A
34
0
05001.0001.5002.000
321
= Circulator speed
A
= Boiler losses of head
Fig. 20
Q [l/h]
DOMIcompact F 24 D
4.6 Time Clock (optional)
A 24 hour time clock can be optionally fitted to the boiler to control the central heating, this will come
into operation when the selector switch “F“ is turned to the position marked “AUTO”.
AUTO
AUTO
P
F
To set time of day
1. Slide switch (A) to left position
2. Using button + and
Pre Set Programmes. The timer is pre programmed with 3 ON and 3 OFF times.
6:30 - 8:30
12:00 - 12:00
16:30 - 22:30
To Set Own ON and OFF times. Symbol in Display = ON time
1. Slide switch (A) to right position (P)
Display
2. Press button (P)
OI
x
OVER RIDE
-
+
P
R
RDP
A
B
x
E
-
adjust until the correct time is shown on display (B).
If these are suitable no programming is required and the slide switch (A) can be moved to the
Auto position and the central heating will be ON for these periods.
(12:00 - 12:00 will not switch on the boiler)
6:30
1
A Slide switch: set clock - auto - set programme
B Display. Symbol in Display = Timer ON
P Select programme ON/OFF 1.....8
D Push buttons Time + Time
E Override: Boiler will switch ON if it is OFF; and OFF if it is ON
F I=Heating continuous - AUTO=Heating timed - O=Heating disabled
R Reset (with pencil) only with switch A in set clock position
1.1 Use buttons + and - to set 1st ON time eg. 6:00
Display
2.1 Use buttons + and - to set OFF time, eg. 9:00
-
6:00
1
Display
3. Press button (P)
Display
4. Press button (P)
Display
5. Press button (P)
Display
6. Press button (P)
Display
7. The timer can be programmed with up to 8 ON and
8 OFF times by repeating the above procedure.
Over ride
By pressing the over ride button (E) the timer programme is over ridden ie, if programme is in OFF time it will
come ON and if in ON time will go OFF.
The timer will revert back to it set programme on reaching the next ON or OFF time.
When the programme is on over ride the sign will be shown in the display window (B).
Reset Button
By the use of a pencil the reset button can be pushed (R). This will clear all programmes apart from those factory
pre set.
Reset is only possible with switch (A) in set Clock position!
8:30
12:00
12:00
16:30
22:30
2
3
4
5
6
Display
3.1 Use button + and - to set 2nd ON time, eg. 12:30
Display
4.1 Use button + and - to set 2nd OFF time eg. 14:00
Display
5.1 Use button + and - to set 3rd ON time, eg. 16:00
Display
6.1 Use button + and - to set 3rd OFF time eg. 23:30
Display
8. On completion of programming slide switch (A) to Auto position,
the time of day will be displayed and the central heating will switch
ON and OFF according to the programme set.
9:00
12:30
14:00
16:00
23:30
2
3
4
5
6
35
4.7 Wiring diagram
DOMIcompact F 24 D
34
43
49
114
42
47
38
72
139
X6X4
47 Modureg
49 Safety thermostat
72 Room thermostat
81 Ignition/detection electrode
114 Water pressure switch
139 Remote timer control (opentherm)
MF08FA.1
TRANSFORMER
F 3.15A
FUSE
F 3.15A
FUSE
1 21 2 31 2 3 4123456712345678910 11
N L
X5X3X7
X1
81
441632
230V 50Hz
36
Key
16 Fan
32 Heating circulator
34 Heating temp. sensor
38 Flow switch
42 Tap water temperature sensor
43 Air pressure switch
44 Gas valve
Fig. 21
CAUTION
Before connecting the room thermostat or the
remote timer control, remove the jumper on the
terminal block.
BENCHMARK
BENCHMARK No.
Please add the first 4 digits of the Boiler serial No to complete the BENCHMARK No.
267
COLLECTIVE MARK
GAS BOILER COMMISSIONING CHECKLIST
BOILER SERIAL No.NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATINGROOM T/STAT & PROGRAMMER/TIMERPROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATERCYLINDER T/STAT & PROGRAMMER/TIMER
HEATING ZONE VALVESFITTEDNOT REQUIRED
HOT WATER ZONE VALVESFITTEDNOT REQUIRED
THERMOSTATIC RADIATOR VALVESFITTED
AUTOMATIC BYPASS TO SYSTEMFITTEDNOT REQUIRED
COMBI BOILER
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATEft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE)mbar
CENTRAL HEATING FLOW TEMPERATURE°C
CENTRAL HEATING RETURN TEMPERATURE°C
m3/hr
N/A
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED? YES NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATEft3/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)mbar
COLD WATER INLET TEMPERA
HOT WATER OUTLET TEMPERATURE°C
WATER FLOW RATE
TURE°C
m
N/A
3
/hr
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER’S INSTRUCTIONS?YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT WATER SYSTEM COMPLIES
WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING?N/AYESCO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
lts/min
COMMISSIONING ENG’S NAME PRINTCORGI ID No.
SIGNDATE
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SERVICE 1
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 3
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 5
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SERVICE 2
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 4
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 6
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SIGNATURE
SERVICE 7
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 9
ENGINEER NAME
ANY NAME
COMP
No.
TEL
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
SIGNATURE
SERVICE 8
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
TURE
SIGNA
SERVICE 10
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
FERROLI TECHNICAL HELPLINE - 08707 282 885
Should you require any assistance during the installation
Phone numbers:
Installer
Service Engineer
call our Technical Service Helpline on
08707 282 885 option 1
Should you require a service engineer to visit
call our service centre on
08707 282 885 option 2
(For U.K. and Northern Ireland)
For EIRE only call HEATOVENT on
014508166
BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS
MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.
ALL SPECIFICATIONS SUBJECT TO CHANGE
Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check
this is not caused by lack of electricity supply, gas supply or low water pressure before calling our