Ferroli DOMIcompact F 24 B Instructions For Use, Installation And Maintenance

Page 1
wall-mounted gas fired, condensing combination boiler
DOMIcompact F 24 B
G C N° 47-267-37
INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE FOR THE UNITED KINGDOM & EIRE
cod. 3540B27/3 - 07/2006
Seasonal Effi ciency
(SEDBUK)
band B
Page 2
2
DOMIcompact F 24 B
IMPORTANT
Your "benchmark" Installation, Commissioning and Service Record Log Book is enclosed in the last pages of this manual. “This record must be completed and left with the end user”.
Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency. Please see installation and servicing guidelines. For EIRE (Southern Ireland) it is necessary to complete a “Declaration of Conformity” to indicate compliance to I.S. 813. An example of this is given in the current edition of I.S. 813. In addition it is necessary to complete the “Benchmark” logbook.
"Ferroli declare that no substances harmful to health are contained in the appliance or used
during the appliance manufacture”.
• Read the warnings given in this manual thoroughly. They provide important information for safe instal­lation, use and maintenance
• The instruction manual, by law must be left with the end user.
• If the appliance is sold or transferred to another owner or if the owner moves, leaving the appliance behind, always ensure that the manual is kept with the appliance for consultation by the new owner and /or installer.
• Incorrect installation or poor maintenance absolves the manufacturer from all liability for damage to persons and property.
• Installation and maintenance must be carried out in accordance with current legislation, according to the manufacturer’s instructions and by qualified corgi registered engineer.
• Before service or maintenance work is carried out isolate the appliance from the mains electricity supply.
• In the event of malfunction or faulty operation, iso­late the appliance. Do not attempt to repair or carry out any other operation on the appliance directly. Contact Ferroli or a qualified engineer only.
• Repairs or the replacement of components must be carried out exclusively by qualified personnel using original spare parts only. Failure to adhere to the above may compromise the safety of the appliance.
• To guarantee efficient operation, the appliance must be serviced once a year by a Corgi registered engi­neer.
• The appliance may not be used for purposes other than those for which it was explicitly designed.
• Incorrect installation and use or failure to follow the instructions provided by the manufacturer absolve the manufacturer from all liability for damage.
• After unpacking, check that the contents are correct and undamaged.
• Keep packing out of reach of children as it could be potentially hazardous.
• To clean external parts, use a damp cloth moistened with soapy water if necessary. Avoid using abrasive cleaning products and solvents.
This symbol indicates “Caution” and is placed next to all safety information. Strictly follow these instructions in order to avoid danger and damage to persons or property.
This symbol calls attention to a note or important information, please read thou­rougly.
President and Legal Representative
Cav. del Lavoro
Dante Ferroli
  
Declaration of conformity
Manufacturer: FERROLI S.p.A. Address: Via Ritonda 78/a 37047 San Bonifacio VR Italy declares that this unit complies with the following EU directives:
Gas Appliance Directive 90/396 Efficiency Directive 92/42 Low Voltage Directive 73/23 (amended by 93/68) Electromagnetic Compatibility Directive 89/336 (amended by 93/68)
Page 3
3
DOMIcompact F 24 B
1. Operating instructions ............................................................................4
1.1 Introduction ............................................................................................................4
1.2 Control panel ..........................................................................................................5
1.3 Turning on and off ..................................................................................................6
1.4 Adjustments ............................................................................................................6
1.5 Maintenance ............................................................................................................8
1.6 Faults .......................................................................................................................8
2. Installation ..............................................................................................9
2.1 General Instructions ................................................................................................9
2.2 Boiler location .......................................................................................................10
2.3 Boiler water connections ......................................................................................12
2.4 Connection to the gas system ..............................................................................14
2.5 Electrical Connections ..........................................................................................14
2.6 Flue system ...........................................................................................................15
2.7 Condensate outlet connection .............................................................................23
3. Service and maintenance ......................................................................25
3.1 Adjustments ..........................................................................................................25
3.2 Initial start-up ........................................................................................................27
3.3 Maintenance ..........................................................................................................28
3.4 Troubleshooting ....................................................................................................30
4 Technical characteristics and data .........................................................31
4.1 Dimensions and connections ................................................................................31
4.2 General view and main components ....................................................................32
4.3 Hydraulic diagram .................................................................................................33
4.4 Technical data table ..............................................................................................34
4.5 Diagrams ...............................................................................................................35
4.6 Time Clock ............................................................................................................36
4.7 Wiring diagram .....................................................................................................37
Benchmark ................................................................................................38
cod. 3540B27/3
Page 4
4
DOMIcompact F 24 B
1. OPERATING INSTRUCTIONS
1.1 Introduction
Dear Customer, Thank you for choosing DOMIcompact F 24 B, a FERROLI wall-mounting boiler featuring advanced
design and technology, high reliability and quality construction. Please read this manual carefully and keep it for future reference.
DOMIcompact F 24 B is a high-efficiency condensing appliance for heating and hot water production running on natural or liquefied petroleum gas (configurable at the time of installation) and regulated by an advanced microprocessor control system.
The boiler shell consists of a primary copper laminar heat exchanger, a secondary aluminium heat exchanger providing effective condensation of the water vapour contained in the flue gases, and burner equipped with electronic ignition and ionization flame control.
The boiler is totally room sealed from the installation room: the air required for combustion is drawn from outside. The boiler also includes a fan, modulating gas valve, pump, expansion vessel, flow switch, safety valve, temperature sensors, a safety thermostat and a low pressure switch .
Thanks to the microprocessor control and adjustment system with advanced self-diagnosis, unit ope­ration is for the most part automatic. The power for heating is automatically governed by the control system combined with the room thermostat (not supplied). The power for hot water is automatically and continually governed to ensure a fast delivery and comfort under all operating conditions .
The user only has to set the temperature desired inside the home (by means of an optional room thermostat or remote control, which is required under the building regulations 2002) or regulate the temperature of the system, and set the desired outlet temperature for the hot water. The adjustment and control system will provide optimum operation throughout the year.
The display continuously provides information on the unit’s operating status and it is possible to obtain additional information on the sensor temperatures, set-points, etc , or configure them. Any operating problems associated with the boiler are immediately signalled by the display and, if possible, corrected automatically.
Page 5
5
DOMIcompact F 24 B
1.2 Control panel
The control panel is composed of a multi-function button, two knobs and a display.
Key
1 Heating temperature adjustment and Summer/
Winter/ switch off control
2 Hot water temperature adjustment and switch
off control
3 Multi-function button (ECO/RESET/TEST) 4 Temperature display
During operation or standby in heating mode,
it displays the temperature of the heating sensor. During hot water operation, it displays
the temperature of the hot water sensor. 5 Heating demand symbol Appears during heating operation or when
adjusting the heating set-point temperature 6 Flame symbol Appears when the burner is on 7 ECO symbol ECO is displayed when the Economy function is on 8 Hot water demand symbol Appears during hot water operation or when adjusting the hot water set-point temperature
Fig. 1
Boiler on stand-by
Boiler on stand-by / ECO
Heating operation (burner on)
Hot tap water operation (burner on)
Fault codes (See chap. 1.6 or 3.0)
TEST mode operation (burner on)
Boiler off
Display
Type of operation
(Frost protection active)
(No demand from heating or Hot water)
(Displays heating flow temperature)
(Displays Hot water temperature)
(Displays relevant fault code)
(For comissioning purposes only)
Information during operation
During normal operation, the boiler diagnostics display the running information or boiler status on the
control panel (Fig.1).see below.
Page 6
6
DOMIcompact F 24 B
1.4 Adjustments
Boiler off Boiler in Summer operation
(only hot water production is active)
Boiler with only heating on and hot
water off
(Display indicates heating demand)
Boiler in Winter operation
(Display indicates hot water demand)
1.3 Turning on and off
Ignition
• Open the gas isolation valve on the boiler.
• Purge the air from the pipe work to the gas valve.
• Turn on the 3amp electrical switch or insert the plug to the boiler.
• Turn the heating and hot water control knobs onto their required temperatures (see par. 1.4).
• The boiler is now ready to function automatically whenever hot water is drawn or both the time clock and room thermostat call for heating.
Turning off
Turn the knobs (ref. 1 and 2 Fig. 1) onto minimum. If the boiler is turned off this way, then the P.C.B is still powe-
red. Hot water and heating operation are disabled, the display shows
; but the frost protection function remains active
The frost protection will not work if the electricity and/or gas supply to the unit are cut off. To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from the boiler, the tap water and the system water; or drain off just the tap water and add a suitable antifreeze to the heating system, as prescribed in chap. 2.3.
Summer/winter Switchover
Depending on the position of the control knobs “1” and “2” it is possible to switch off the boiler unit, switch between summer and winter operation or turn off the domestic hot water .
Page 7
7
DOMIcompact F 24 B
Switching off the boiler. Switching between summer and winter operation has priority over the heating only time control (optional) when this is connected to the boiler.
C.H. temperature setting
To set the system delivery temperature, turn the knob (ref. 1 - Fig. 1). It can vary from a minimum of 30 °C to a maximum of 85°C; however, it is advisable not to operate the
boiler below 45 °C. When the knob is turned the display lights up, the radiator symbol flashes and the temperature displayed will be the temperature actually set. On completing this operation, the display will stay on for another 5 seconds and then go back to the actual operating temperature providing there is a demand.
Domestic Hot water temperature adjustment
To set the tap water temperature, turn the knob (ref. 2 - Fig. 1). It can vary from a minimum of 40 °C to a maximum of 55 °C. When the knob is turned the display lights
up, the tap symbol flashes and the temperature displayed will be the temperature actually set. On completing this operation, the display will stay on for another 5 seconds to then go back to the actual operating temperature providing there is a demand.
If the boiler is connected to the optional remote open therm control, the above adjustments (system and hot water temperature) can only be made with the remote control.
ECO/COMFORT selection
The unit is equipped with a special internal device that ensures a high hot-water delivery speed and excellent user comfort. When comfort mode is active the water in the boiler is maintained at a pre­determined temperature, which means that hot water is available at the boiler outlet as soon as a tap is opened, ie with no waiting.
The user can turn the device off (ECO mode) by pressing the multi-function button for 2 seconds with the boiler on standby. In ECO mode the display shows the relevant symbol. To turn on COMFORT mode, press the multi-function button again for 2 seconds, the ECO symbol will vanish from the display.
TEST MODE selection
Pressing the multi-function button 3 times in 3 seconds turns on TEST mode (the heating and hot water symbols flash simultaneously - see par. 3.1). If TEST mode is turned on by accident, press the button 3 times in 3 seconds again to exit (Test time 15 minutes unless cancelled early).
Page 8
8
DOMIcompact F 24 B
1.5 Maintenance
It is strongly recommended to carry out annual maintenance on the boiler and the heating system. Please refer to the “maintenance” section in this manual.
The casing, the control panel and the aesthetic parts of the boiler can be cleaned using a soft and damp cloth.
Do not use abrasives or solvents.
1.6 Faults
The boiler is equipped with an advanced self-diagnosis system that signals any faults on the display. Some faults (from F1 to F3) cause a boiler shutdown. In this case, operation must be reset manually by pressing the multi-function button (RESET) for 1 second
Other faults (from F5 to F37) cause temporary shutdowns that are automatically reset as soon as the value causing the fault comes back within the boiler’s normal working range.
Listed below are some anomalies that can be caused by simple, user-solvable problems. If the problem remains after two attempts at resetting, contact the Ferroli Service Centre. For other faults, refer to section 3.4 “Troubleshooting”.
Boiler shutdown
Low system pressure
Make sure that the gas cocks ahead of the boiler and on the meter are open. Check condensate discharge, make sure it is clean and not obstructed. Press the multi-function button (for 1 second) (fig.1) In case of repeated shutdowns, contact the nearest assistance centre.
Fill the 'system to 1-1.5 bar cold by means of the 'filling point C.h. (see page 11)
Fault CureDisplay code
Before calling a Ferroli service engineer, check that the problem is not due to there being no gas or electricity, or low system pressure.
Page 9
9
DOMIcompact F 24 B
2. INSTALLATION
2.1 General Instructions
This device must only be used for the purpose for which it is specially designed. This unit is designed to heat water to a temperature below boiling point and must be connected to a heating system and/or a water supply system for domestic use, compatible with its performance, characteristics
and its heating capacity. Any other use is considered improper. BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE RECOMENDATION OF BS STANDARDS, ANY LOCAL REGULATIONS AND THE RULES OF COMPETENT WORKMANSHIP.
In IE, the installation must be carried out by a Competent Person and installed in accordance with the current edition of I.S. 813 “Domestic Gas Installations”, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
Incorrect installation can cause damage or physical injury for which the manufacturer declines any responsibility.
This appliance must be installed strictly in accordance with these instructions and regulations:
The Gas Safety Regulations (Installations & Use). The Local Building Regulations. The Building Regulations (Part L). The Buildings Standards (Scotland - Consolidated) Regulations. British Standards Codes of Practice: B.S. 5440 Part 1 Flues B.S. 5440 Part 2 Air supply B.S. 5449 FORCED CIRCULATION HOT WATER SYSTEMS B.S. 6798 INSTALLATION OF GAS FIRED HOT WATER BOILERS B.S. 6891 GAS INSTALLATIONS B.S. 7671 IEE WIRING REGULATIONS B.S. 4814 SPECIFICATION FOR EXPANSION VESSELS B.S. 5482 INSTALLATION OF LPG B.S. 3632 RESIDENTIAL PARK HOMES B.S. 7593 TREATMENT OF WATER IN DOMESTIC HOT WATER CENTRAL HEATING SYSTEMS B.S. 5546 INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES I.S. 813 DOMESTIC GAS INSTALLATIONS (EIRE ONLY)
Local Water Bye Laws B.S. 5955-8 PLASTIC PIPEWORK INSTALLATION
For Northern Ireland the rules in force apply
Page 10
10
DOMIcompact F 24 B
Minimum
A
B
D
5 cm
20 cm
60 cm (via an openable panel)
C 20 cm
Table 1
fig. 2
fig. 3
D
A A
B
C
2.2 Boiler location
The boilers combustion chamber is sealed off from the installation room. The installation room must be sufficiently well ventilated to prevent any dangerous conditions from forming in the event of even slight gas leakage. This safety standard is required by the EEC Directive no. 90/396 for all gas units, including those with a so-called sealed chamber.
Therefore the place of installation must be free of dust, flammable materials or objects or corrosive gases. The room must be dry and not subject to freezing.
The boiler is design to be installed on a solid wall. The wall fixing must ensure a stable and effective support for the appliance, using the bracket and fixings supplied.
If the unit is enclosed in a cupboard or mounted alongside, there must be space for normal maintenance work. Fig. 2 and tab. 1 give the minimum clearances to leave around the unit.
This appliance does not require compartment ventilation for combustion purposes
Drilling Template
Select suitable mounting position for boiler, using the template mark flue outlet and boiler mounting points. Drill two 10mm holes 70mm deep to accept the wall plugs. Fit the supplied wall plugs on the left and right side drill and fit the special wall plug in the middle (fig. 3). Fix the wall bracket to the wall using standard lock nuts (M8) on both sides. Using a Core drill cut a 118mm diameter hole for the flue as detailed on page 17. Mount the boiler on the wall bracket and secure using the special antitheft nut (M8) as described in the fig. 3.
Page 11
11
DOMIcompact F 24 B
fig. 4
Gas
Hot water
Additional expansion vessel C.H. (if required)
Filling point C.H.
Automatic Bypass
fig. 5
3
2
1
4
Cold water mains
Make Up Water
Provision must be made for replacing water lost from the sealed system. Reference should be made to BS6798, for methods of filling and making up sealed systems. There must be no direct connection between the boiler's central heating system and the mains water supply. The use of mains water to charge and pressurise the system directly, is conditional upon the Local Water Byelaws. Again any such connection must be disconnected after use. The temporary filling loop (Not supplied) is shown in fig. 5. Ensure the filling point is on the return pipe to the boiler.
Attention - is drawn to the Local Water Byelaws.
Fittings manufactured from duplex (alpha-beta) brass are not acceptable for underground use and certain water undertakings will not accept their use above ground.
Ensure all pipework is adequately supported
NOTE: An automatic bypass capable of passing 6 ltrs per minute must be fitted as far as possible from the boiler if thermosta­tic radiator valves are fitted thoughout. As per the building regulations part ‘L’
Key
1 Filling point C.H 15mm
isolation valve.
2 Temporary flexible connection
3 Cold water supply 15mm
isolation valve
4 Double check valve
Page 12
12
DOMIcompact F 24 B
Key
1 System flow (22 mm with isolation valve fitted) 2 DHW outlet (15 mm with isolation valve fitted) 3 Gas inlet (22 mm with isolation valve fitted) 4 Cold main inlet (15 mm with isolation valve fitted) 5 System return - (22 mm with isolation valve fitted c/w filter) 6 Condense outlet
It is essential to install the isolation valves supplied between the boiler and heating system, allowing the boiler to be isolated from the system if necessary.
The safety valve outlet must be connected to a 15 mm pipe to allow safe discharge to the outside ground in the event of over-pressure in the heating circuit. If this is not done, and the drain valve opens and floods the room, the boiler manufacturer is not to be held responsible. The pipework must have a continuous fall from the boiler, The outlet should face back against the outer bri­ckwork or building face to prevent harm or injury from hot water discharging in the evet of an over-pressuried system. Make the boiler connection in such a way that its internal pipework is free of stress.
If a check valve is installed on the tap water circuit (where applicable), it is necessary to mount a safety valve between the boiler and this circuit (check valve minimum 3 meters from boiler).
fig. 6
2.3 Boiler water connections
The heating capacity of the unit should be previously established by calculating the building’s heat requirement according to current regulations. For efficient operation and long life of the boiler, the plumbing system must be well designed and always complete with all those accessories that guarantee regular operation and running, ie room thermostat, trv’s and automatic bypass etc .
If the flow and return pipes follow a path where air pockets could form in certain places, it is esential to install air vent valves at these points. Also, install a type “A” drain cocks at the lowest point s in the system to allow its complete draining. when required The temperature differential between the flow manifold and the return to the boiler should not exceed 20° C.
A minimum flow of 6 litres/min is requied through the heat exchanger, it is therefore essential to fit an automatic by-pass a min of 3 metres away from the appliance, This should be calibrated on site.
Do not use the water system pipes to earth electrical appliances.
Before installation, carefully flush all the pipes of the heating system to remove residues or impurities that could affect the unit’s efficient operation (BS 7593 Building regs Doc L).
Make the connections to the appliance as shown in fig. 6.
36 95 60 60 95 114
149
97
1 2 3 5
46
Page 13
13
DOMIcompact F 24 B
The connecting kits shown in fig. 7 are supplied as standard.
fig. 7
Water treatment
When treatment is used ferroli limited only recommend the use of proprietary Brand s , such as Fernox or Sentinel water treatment products, which must be used in accordance with the manufacturers instruc­tions,
For further information contact:
Fernox Manufacturing Co. LTD. Cookson Electronics, Forsyth Road Sheerwater,Woking,Surrey GU21 5RZ Tel: 0870 8700362
Sentinel Division Betz Dearborn LTD Widnes, Cheshire WA8 8ND Tel: 0151 424 5351
Note - When the boiler is installed with an existing or new system any unsuitable additives or system debris must be removed by thorough chemical cleansing. All systems should be cleansed according to B.S. 7593.
Note - It is important that the correct concentration of the water treatment product is maintained in accordance with the manufacturers instructions.
Note - In hard water areas it may be necessary to install a scale reducer prior to the boiler on the cold water inlet .
Key
A = Nut B = Compression olive D = 3/4 seal (green) E = 1/2 seal (green) F = 1/2 gas seal (blue) G = Filter H = Cap
Flow isolation valve
Hot water connection
Return isolation valve
Ø22
Ø22
Ø15
A
A
A
B
B
B
D
D
E
Cold water isolation valve
Ø15
AB
E
Gas isolation valve
Ø22
AB
F
Page 14
14
DOMIcompact F 24 B
2.4 Connection to the gas system
If necessary the local Gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas.
An existing service pipe must not be used whitout prior consultation with the local Gas supplier. A gas meter can only be connected by the Local Gas supplier, or by a Local Gas suppliers Contractor. Installation pipes should be fitted in accordance with BS6891. Appliance inlet working pressure must be 20 mbar MINIMUM, for NG and 37 mbar minimum for pro-
pane. Do not use pipes of a smaller diameter than the combination boiler inlet gas isolation valve (22 mm).
The complete installation must be tested for gas soundness and purged as described in BS6891. All pipework must be adquately supported. An isolating gas valve is provided and must be fitted on the boiler gas inlet. Please wait 10 minutes when lighting from cold before checking the gas rate, this will ensure thermal equilibrium.
2.5 Electrical Connections
The unit must be installed in conformity with current national and local regulations inc 16th Edition & B.S 7671 .
Connection to the electrical supply.
The boiler must be connected to a single-phase, 230 Volt-50 Hz electrical supply.
The unit’s electrical safety is only guaranteed when correctly connected to an efficient earthing system installed according to current safety standards and checked by a professionally qualified person . The manufacturer is not responsible for any damage caused by failure to earth the system. Also make sure that the electrical system is adequate for the maximum power absorbed by the unit, as specified on the boiler dataplate, in particular ensuring that the crossectional area of the
electrical cables are suitable for the power absorbed by the unit . The boiler is prewired and provided with a cable for connection to the electrical supply The prewired cable must be connected to the supply with a permanent connection and equipped with a double pole switch which contacts have a minimum opening of at least 3 mm, and fused at max. 3A between the boiler and the line. It is important to check the polarities (LIVE: brown wire / NEUTRAL: blue wire / EARTH: yellow-green wire) and ensure they are correctly connected to the corresponding terminals on the electrical supply .
The user must never change the boilers power cable. If the cable gets damaged, switch off the unit
and have it changed only by professionally qualified personnel. If changing the electric power cable,
use only “HAR H05 VV-F” 3x0.75 mm2 cable with a maximum outside diameter of 8 mm.
5 Core cable must not be used to replace the existing 3 core!
Page 15
15
DOMIcompact F 24 B
B
Fig. 8c
Fig. 8b
A
A
Fig. 8a
1
2
Room thermostat
1
2
Remote timer control (Opentherm)
Or
Access to the electrical terminal block
To access the terminal block where the room thermostat (Low voltage) or the remote timer control is to be connected, carry out the following operations:
1 Unscrew the two screws “A” (Fig. 8a) 2 Lower the instrument panel (Fig. 8b) 3 Turn the instrument panel (Fig. 8c)
You can now access the terminal block “B” (Fig. 8c)
2.6 Flue system
The unit is “type C” with a sealed chamber and forced draught, the air inlet and flue outlet must be connected to one of the following flue systems. With the aid of the tables and methods of calculation indi­cated, before commencing installation, it is first necessary to check that the flue system does not exceed the maximum permissible length. The current standards and local regulations must be observed.
It should be noted that only Ferroli flue system and accessories should be used on this appliance, as per BS 5440 2000 and C.E. test certification.
Low voltage time clock or
Page 16
16
DOMIcompact F 24 B
1
fig. 9
Choice of restrictor:
• With the 2 pipe system:
- Calculate the total flow resistance of the combined air and flue pipes in metres.
- utilise the table shown below to choose the most suitable restrictor for the flow resistance calculated (see page 19)
• With concentric systems:
- Choose correct restrictor from table below. (see page 17 & 18)
N.B.: the diameter of the hole is
stamped on the restrictor
RESTRICTOR FOR TWO PIPE SYSTEM
Total flow resistance
of flue system
Use
restrictor
size
minimum maximum mm
0 m 20 m 43
20 m 55 m No restrictor
RESTRICTOR FOR CONCENTRIC SYSTEM
Flue lenght up to:
Use
restrictor
size
Concentric
60 / 100
1 bend + 1 metre 43 mm
1 bend + 3 metres No restrictor
Concentric
80 / 125
1 bend + 5 metres 43 mm
1 bend + 12 metres No restrictor
Restrictor
This appliance is factory fitted with the correct restrictor for use with a standard 100mm concentric flue terminal of less than 1mtr.For different flueing applications choose the correct size restrictor from the tables below. To change the restrictor please follow the instructions below, shown in figure 9.
Determine the correct size of flue restrictor required, before installing the standard concentric flue kit onto the boiler, check that the restrictor fitted is 50mm diameter and that it is correctly positioned (see fig. 9).
Page 17
17
DOMIcompact F 24 B
* = between 10 and 60 mm
Drill the wall 10÷20 mm more than the pipe diameter
010008X0
* = between 10 and 60 mm
Drill the wall 10÷20 mm more than the pipe diameter
95
125S 50* 12550*
12550*SD
L
30
95
254206
L
P
50*S
98
98
95
30
254206
30
Fall back to boiler 3mm/metre
Fall back to boiler 3mm/metre
1KWMA56W
Fall back to boiler 3mm/metre
Fall back to boiler 3mm/metre
D S
95
30
P
Side view
View from above
fig. 10a
Side Outlet
fig. 10b
Front view
View from above
P = S + 83 mm
Rear Outlet
L = S + D + 239 mm
Horizontal flue installation
1. Define the Suitable position for installing the boiler(See 2.2 Boiler location) .
2. When installing a horizontal flue kit, please ensure a 3 mm per metre fall back to the appliance is incor­porated .
3. Make a hole of diameter 10 - 20 mm greater than the nominal diameter of the concentric pipe used.
4. If necessary, cut the end pipe to size, ensuring that the external pipe protrudes from the wall by between 10 and 60 mm (Fig. 10a and 10b). Remove all cutting burrs and lubricate the seals with a suitable silicone based grease .
Connection with concentric flue system
The unit can be connected to a concentric air/flue duct with a horizontal or vertical outlet as shown in the following drawings. Numerous accessories are available on request to meet the various installation requirements. Please refer to our “flue manual” or the price list for details .
Horizontal concentric flue installation
Page 18
18
DOMIcompact F 24 B
Vertical Outlet
fig. 10c
The total length in equivalent metres of the concentric flue must not exceed the maximum lengths stated in the following table, note that each bend gives an increase to the stated reduc­tion. For example, a duct = 60/100 composed of 1 bend of 90° +1 horizontal metre + 2 bends of 45° + 1 horizontal metre has a total equivalent length of 4 metres.
Angled roof tile
1KWMA82U
1KWMA56U
950
50
010009X0
max. 4 metres 60/100
max. 12 metres 80/125
Roof end piece
1KWMA83U
68
95050
50 950
50
1000 125
10
Reduction factors for bends
Concentric bend at 90° - Ø 60/100 mm
Concentric bend at 45° - Ø 60/100 mm
Concentric bend at 90° - Ø 80/125 mm
Concentric bend at 45° - Ø 80/125 mm
1m
0.5 m
0.5 m
0.25 m
Table 2b
Maximum permissible duct length (Horizontal)
Ø mm
60/100
3 m 12 m
Ø mm
80/125
Table 2a
Maximum permissible duct length (vertical)
4 m 12 m
5. Connect the flue to the boiler, positioning the seals correctly. Seal the flue into the wall with silicone or sand & cement and cover with wall seals provided.
Flue seals should be lubricated with a silicone type grease to prevent damage (grease not sup­plied)
Page 19
19
DOMIcompact F 24 B
1
3
4
2
1KWMA84U
1KWMA82U
1KWMA83W
Ref.
1 2 3 4
N° Pieces
16 16
1 1
Vertical flue pipe Ø80
Vertical air pipe Ø80
Vertical flue terminal
Two pipe adaption kit (1KWMR54A)
Description
Equivalent
loss
25,6 m
16,0 m
12,0 m
0,0 m
53,6 m
Total
Table 3
fig. 11
fig. 12
2
Ø80
AIR
Ø80
FUMES
Remove the closing cap
1
Two pipe adaption kit cod. 1KWMR54A
Connection with 80 mm pipe system
The unit can be connected to a system of sepa­rate air/flue pipes for a horizontal or vertical outlet as shown on the fig. 11- 12. Numerous accessories are available on request to meet the various installation requirements.
Please refer to the flue manual catalogue or the price list for additional components.
To check you do not exceed the maximum per­missible flue length, it is necessary to make a simple calculation prior to installation:
1. For each component, tables 4 - 5 (page
20) provide an “equivalent loss in metres”, depending on the position of installation of the component (with air intake or flue extraction, vertical or horizontal).
The loss is called “equivalent length” since it
is compared to the loss of one metre of flue (defined as equal to 1). For example, a bend at 90° of Ø80 in flue run has an equivalent loss of 2.5 linear metres, i.e. it has a loss equal to that of 2.5 metres of flue length.
2. After designing the layout of the system, add up the losses in equivalent metres, depending on the installation position, of all the compo­nents and accessories in the system.
3. Check that the total calculated loss is less than or equal to 55 equivalent metres, i.e. the maximum permissible for this model of boiler.
For further flue options please contact FERROLI or check our comprensive flue manual.
Page 20
20
DOMIcompact F 24 B
Table of flue and accessories
KWMA86A
KWMA85A
KWMA84U
Air Flue
Vertical
Horizontal
Vertical
Horizontal
KWMA65W
KWMA01W
KWMA83W  1,00 m
Description
Pipe Ø 80
male-female
Bend 45° Ø 80 mm
male - female
Bend 90° Ø 80 mm
male - female
Description
Horozontial
flue terminal
Horozontial air terminal
Vertical flue
terminal
1 1 1.6 2
1.2 1.8
1.5 2.0
Equivalent losses in
metres (linear)
5
2
Air Flue
Vertical
Horizontal
Vertical
Horizontal
Equivalent losses in
metres (linear)
12
Accessories Ø 80 Accessories Ø 80
Table 4 Table 5
The stated loss values refer to genuine Ferroli flue accessories.
Terminal Position
P
D, E
Q
Q
l
B
C
A
G
F
L
J
H
H
K
N
N
MM
Q
Page 21
21
DOMIcompact F 24 B
The plume should not cross:
• a frequently used access route;
• any frequently used area (such as a patio or car parking space);
• a neighbouring dwelling.
Nor should it be directed towards a window or door, or be sited close to a facing wali or other surface.
There are also other aspects to consider when planning the flue terminal position.
• A free passage of air is needed at all times to aid plume dispersal - which may be difficult in sheltered locations.
• In cold weather, the condensate could cause a safety hazard if it freezes on pathways, or if it results in frost damage to surfaces.
• The plume could trigger infra-red security lighting if sited in the wrong place.
• Ensure terminals do not obscure security camera field of vision.
• The terminal guards must be able to resist corrosive properties of the condensate.
Statutory mininum distances for terminai siting
A - minimum distance 600mm - may be a nuisance if it ‘wets’opposite boundary, crosses
main pathway or condensate can drip on pathway. B - minimum distance 600mm - may be a nuisance as plume could obscure window. C - minimum distance 600mm - may be a nuisance if plumecrosses door.
A
B
C
Opposite boundary
Pathway
Page 22
22
DOMIcompact F 24 B
Minimum Dimensions of Flue Terminal Positions
Directly below an opening, air brick, opening windows, etc.
Above an opening, air brick,
opening windows, etc.
Horizontally to an opening, air brick,
opening windows, etc.
Below gutters, soil pipes or drain pipes
Below balconies or car port roof
Below eaves
From a vertical drain pipe or soil pipe
From an internal or external corner
From a surface facing the terminal
From a terminal facing the terminal
From the wall on which the terminal is mounted
From a vertical structure on the roof
Above intersection with roof
Horizontally from a terminal on the same wall
Vertically from a terminal on the same wall
From an opening in the car port (e.g. door, window) into the dwelling
Above ground roof or balcony level
300mm
300mm
300mm
200mm
75mm
200mm
150mm
100mm
300mm
600mm
300mm
300mm
150mm
1200mm
1200mm
1500mm
N/A
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
NOTE
N/A = Not applicable
In addition, the terminal must not be nearer than 300mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window frame.
Condensing Terminal Positions: If the flue is to be terminated at low level, then the potential effect of the plume must be considered.
The plume should not be directed:
across a frequently used access route
across a neighbouring property
towards a window or door
Page 23
23
DOMIcompact F 24 B
fig. 13
2.7 Condensate outlet connection
Connection to collective flues or single flues with natural draught
If you are then going to connect the DOMIcompact F 24 B boiler to a collective flue or a single flue with natural draught, the flue must be expressly designed by professionally qualified technical personnel in conformity with the standards and rules in force.
In particular, flues must have the following characteristics:
• Be sized according to the method of calculation stated in the standard
• Be airtight to the products of combustion, resistant to the fumes and heat and waterproof for the con­densate
• Have a circular or square cross-section (some hydraulically equivalent sections are permissible), with a vertical progression and with no restrictions
• Have the ducts conveying the hot fumes adequately distanced or isolated from combustible materials
• Be connected to just one unit per floor, for at most 6 units in all (8 if there is a compensation duct or opening)
• Have no mechanical suction devices in the main ducts
• Be at a lower pressure, all along their length, under conditions of stationary operation
• Have at their base a collection chamber for solid materials or condensation of at least 0.5 m, equipped with a metal door with an airtight closure.
The boiler is equipped with an internal siphon -trap to drain off the condensate. Screw on the inspection bowl A and the push in the flexible hose B (approximately 3 cm), then tighten the compression collar on the trap .
Fill the siphon-trap with approximately 0.5 ltrs. of water and connect the hose to the waste system or soakaway
0,5 l.
Page 24
24
DOMIcompact F 24 B
fig. 14
Condensate discharge
Where possible the condensate should discharge into an internal soil pipe or waste system. The minimum pipe diameter required is 22 mm, a trap has already been fitted to the appliance with a flexible hose to facilitate the connection to the condensate discharge pipe.
The pipe should be a solvent weld plastic, not copper, as the condensate has a ph value of 4 (slightly acidic).
Where it is not possible to terminate internally, the condensate discharge pipe may be run outside (see below drawing).
Any external run is subject to freezing, in severe weather conditions. To avoid this the pipework should be installed to dispose of the condensate quickly, with as much as possible run internally, before passing through the wall.
Pipework external to the building should be increased in diameter to 32 or 40 mm solvent weld. It should be run to a external drain or soakaway, with a maximum length of 3 metres.
If a soakaway (condensate absorption point) is used, it should be constructed as shown below.
External legth of pipe 3m max.
32/40Ø min.
500
Ground (either/or)
25 min.
300 min.
Hole depth 400 min.
Two rows of three 12 mm holes at 25 mm centres 50 mm from bottom of tube and facing away from house
The gradient of the discarge pipe should be 2.5° (45 mm/m) minimum.
Limestone
cladding
Bottom of
tube sealed
Ø 100
plastic tube
Page 25
25
DOMIcompact F 24 B
X3
3. SERVICE AND MAINTENANCE
3.1 Adjustments
All adjustment and conversion operations must be carried out by a Qualified and trained engineer such as a Ferroli Service.engineer
FERROLI S.p.A. declines any responsibility for damage or physical injury caused by unqualified and unauthorised persons tampering with the device.
Gas supply conversion
The unit can function with either Natural Gas or LPG and is factory-set for use with one of the two gases, as clearly shown on the packing and on the unit’s dataplate. Whenever a different gas to that for which the unit is preset has to be used, a conversion kit will be required, proceeding as follows:
1. Replace the injectors at the main burner, by inserting those specified in the technical data table in chap. 4, according to the type of gas used
2. Adjust the burner minimum and maximum pressures (ref.to page 33), setting the values given in the technical data chart for the type of gas used.
3. How to Adjust the parameter for the specific type of gas to be used:
- turn the boiler onto standby
- press the RESET button for 10 seconds
- P1 will appear on the display
- press the RESET button for 5 seconds
- turn the hot water knob (ref. 2 - fig 1) onto “0” (for Natural Gas operation) or onto “1” (for LPG operation)
- press the RESET button for 5 seconds
- P2 will appear on the display
- turn the heating knob (ref. 1 - fig 1) onto minimum and then onto maximum
- the boiler will go back onto standby
- turn the heating & hot water knobs onto the set temperatures.
4. Attach the sticker contained in the conversion kit, near the dataplate, as proof of the conversion.
Turning on TEST mode
To turn on TEST mode, press the multi-function button 3 times in 3 seconds.
The display will show the radiator and hot water symbols flashing, the current heating power, the ECO symbol (if ECONOMY mode is on) and the flame symbol.
To exit TEST mode, press the multi-function button 3 times in 3 seconds.
TEST mode turns off automatically after 15 minutes.
Page 26
26
DOMIcompact F 24 B
fig. 15
Adjusting burner pressure
Since this unit has flame modulation, there are two fixed pressure settings: the minimum and maximum, which must be as stated in the technical data chart according to the type of gas.
• Connect a suitable pressure gauge to pressure point “B” downstream from the gas valve.,having loo­sened it first
• Disconnect the pressure compensation tube “H”.
• Take off the protective cap “D”.
• Run the boiler in TEST mode (press the multi-function button 3 times in 3 seconds):
- TEST mode on: turn the heating knob (ref. 1 - fig 1) onto maximum.
• Adjust the maximum pressure with the screw “G”, clockwise to increase it and anticlockwise to decrease it.
• Disconnect one of the two electrical connectors from the modureg “C” on the gas valve.
• Adjust the minimum pressure with the screw “E”, clockwise to decrease it and anticlockwise to increase it.
• Reconnect the electrical connector disconnected from the modureg on the gas valve.
• Check that the maximum pressure has not changed.
• Reconnect the pressure compensation tube “H”.
• Put the protective cap “D” back on.
• To end TEST mode, repeat the sequence for turning it on or wait 15 minutes
• Shut down the boiler
• Remove the pressure gauge
• Re-seal test point ‘B’
• Re-light the boiler and check for gas leaks using a suitable “Leak detection fluid”
Key
B Pressure point C Modureg electrical connection D Protective cap E Minimum pressure adjustment G Maximum pressure adjustment
Having disturbed test point ‘B’ when checking or adjusting the gas pressures, it is considered mandatory to check for gas leaks using a suitable leak detection fluid or sniffer.at that connection
Page 27
27
DOMIcompact F 24 B
Adjusting the maximum heating output
To adjust the heating power, set the boiler on TEST operation (see par. 3.1). Turn the heating tem­perature control knob (ref. 1 - Fig. 1) clockwise to increase the power or anticlockwise to decrease it (see pressure/power diagram Fig. 21). The display shows the power setting from 0 to 99%. Exit TEST operation (see par. 3.1). The maximum heating power will remain as set during the TEST mode. (100% output shown as 99% due to the display only being 2 digits ).
Ignition power adjustment
To adjust the ignition power, set the boiler on TEST operation (see par. 3.1). Turn the hot water temperature control knob (ref. 3 - Fig. 1) clockwise to increase the power or anti-
clockwise to decrease it (see pressure/power diagram Fig. 21). The display shows the power setting from 0 to 60%. Exit TEST operation (see par. 3.1). The ignition power will remain as set during the TEST mode.
NOTE Recomended ignition pressure for standard 100mm concentric horizontal flueing is 30%
3.2 Initial start-up
Commissioning must be performed by Qualified Personnel only!. Checks to be made at initial start up, and after all maintenance operations that involved discon­necting from the system or an intervention of a safety device.
Before lighting the boiler:
• Open any isolation valves between the boiler and the systems.
• Check the soundness of the gas system, proceeding with caution and using a suitable leak detection fluid to detect any leaks in connections.after completing a tightness test
• Fill the water system and make sure that all air contained in the boiler and the system has been vented by opening the air vent valve on the boiler and any vent valves on the system.
• Make sure there are no water leaks in the system, hot water circuits, connections or boiler.
• Make sure the electrical supply is correctly connected.
• Make sure that the unit is connected to a good earthing system.
• Make sure that there is sufficient gas available to produce safe combustion. (min inlet working pressure = 20mbar).
• Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler.
Lighting the boiler
• Open the gas isolation valve on the boiler.
• Purge the air from the gas pipe work to the boiler.
• Switch on the electrical supply to the boiler.
• Turn control knob “1” (Fig. 1) onto Winter in correspondence with a value greater than 50 °C and ensure the room thermostat is calling, At this point, the burner will light and the boiler begins to function automatically, controlled by its software and safety devices.
If, after following the lighting procedure, the burners do not light and fault F1 is generated, press the RESET button for 1 second and release it. The software will repeat the ignition cycle in the next 30 seconds. If the burners do not light after the second attempt, consult the “Troubleshoo­ting” paragraph.
In case of an electrical power failure while the boiler is working, the burners will go out and re­ignite automatically when power is restored.
Page 28
28
DOMIcompact F 24 B
Checks during operation
• Check the soundness of the gas circuit and water systems.
• Check the efficiency of the flue and air-flue ducts while the boiler is working.
• Check that the water is circulating properly between the boiler and the systems.
• Make sure that the gas valve modulates correctly in both the heating and hot water production modes.
• Check for correct ignition of the boiler by performing various tests, turning it on and off with the room thermostat or remote control.
• Make sure that the gas consumption indicated on the meter corresponds to that given in the technical data table in chap. 4.(Input rating)
• Check there is the correct flow rate of hot water with the Δt stated in the technical data chart: The measurement should be made with specific instruments and as close as possible to the boiler, also con­sidering the heat lost from the pipe work.
• Make sure that with no call for heating the burner ignites correctly upon opening a hot water tap. Check that during heating operation, on opening a hot water tap, the heating pump stops and there is a con­stant production of hot water.
Turning off
Turn the knobs (ref. 1 and 2 Fig. 1) onto minimum. When the boiler is turned off, the printed circuit board is still powered.
Hot water and heating operations are disabled, the display shows ; but the frost protection mode
remains active..
The frost protection system will not work if the electricity and/or gas supply to the boiler are cut off. To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from the boiler, both tap and the system water; or drain off just the tap water and add a suitable antifreeze to the heating system, as prescribed in chap. 2.3.
3.3 Maintenance
The following operations must only be carried out by suitably trained and Qualified Personnel, such as Ferroli service engineers.
Seasonal inspection of the boiler and flue
It is advisable to carry out the following checks at least once a year:
• The control and safety devices (gas valve, flow switch, thermostats, etc.) must function correctly.
• The air-flue terminal and ducts must be free of obstructions and leaks.
• The gas and water systems must be sound.
• The burner and exchanger must be clean. Follow the instructions in the next paragraph.
• The electrode must be free of debris and correctly positioned.
• The water pressure in the cold water system must be approximately 1 bar; otherwise, bring it to that value.
• The expansion tank must be filled with air @ 1bar.
• The gas flow and pressure must correspond to that given in the respective tables.
• The circulation pump must be manually spun, vented and not be restricted.
• The condensate discharge must be clean, free of obstructions, leaks and clean out the sediment inspec­tion bowl.
Opening the casing
To open the boiler casing:
1 Unscrew the two screws A 2 Lower the instrument panel 3 Drop down the instrument panel 4 Fully unscrew the two screws B 5 Raise and remove the casing C
Page 29
29
DOMIcompact F 24 B
Before carrying out any operation inside the boiler, disconnect the electrical power and isolate the gas supply.
Fig. 16b
A
A
Fig. 16a
B
B
C
Fig. 16c
Fig. 16d
Cleaning the boiler and burner
The body and burner must not be cleaned with chemical products or wire brushes. Special care must be taken over all the seals pertaining to the sealed chamber (gaskets, cable clamps, etc.).
After performing all these operations, check and carry out all the phases of ignition and thermostat operation, the gas valve and circulation pump.
After these checks, make sure there are no gas leaks.
Combustion analyser testing
It is possible to analyse the combustion through the air and flue sampling points shown in fig. 17. To make the measurement, it is necessary to:
1) Open the flue sampling point
2) Insert the probe;
3) Turn on the hot water tap;
4) Turn the domestic hot water stat
to maximum;
5) Allow the boiler to reach thermal equilibrium (10 - 15 min.);
6) Wait 10 minutes for the boiler to stabilise
7) Take the measurement.(see the data table)
Flue
Flue
Air
Air
fig. 17
Page 30
30
DOMIcompact F 24 B
 No gas
 Detection or ignition
electrode fault
 Defective gas valve
 Ignition power too low
 Condensate discharge
full or dirty
Safety thermostat trips  Heating sensor damaged
 No water circulation in
the system
 Air in the system
Air pressure switch
(fails to close the contacts
within 60 sec. of turning
on the fan)
 Air pressure switch
contact open
 Incorrect wiring to the
air pressure switch
 Incorrect restrictor ring
fitted
 Flue not correctly sized
or obstructed
Fault
No burner ignition
Possible cause
Low system pressure  System empty
 Low Water pressure switch
not connected or damaged
Cure
Flame present with
burner off signal
 Electrode fault
 PCB fault
Delivery sensor fault  Sensor damaged
 Wiring shorted
 Wiring broken
Tap water sensor fault  Sensor damaged
 Wiring shorted
 Wiring broken
 Check the regular gas flow to the
boiler and the air has been purged
from the pipes.
 Check the wiring of the electrode
and that it is correctly positioned and
free of any deposits
 Check and change the gas valve
 Adjust the ignition power
 Check and clean condensate discharge
 Check the correct positioning and
operation of the heating sensor
 Check the circulator
 Vent the system
 Check the system bypass is sufficient
 Check the wiring to the fan  Check the pressure switch  Change the restrictor ring  Check the fan venturi
 Check the wiring or change
the sensor
 Fill the system to 1 - 1,5 bar
 Check the low water pressure switch
 Check the wiring or change
the sensor
Display code
F1
F3
F2
F5
F37
F7
F9
 Check the ionizing electrode wiring
 Check the card
3.4 Troubleshooting
Fault Diagnosis
The boiler is equipped with an advanced self-diagnosis system. In the event of a fault within the boiler, the display will show the relevant code.
There are faults that cause shutdown (faults from F1 to F3): in order to restore operation it requires the operator to press RESET for 1 second (ref. 2 - Fig. 1) if the boiler fails to start, it will be necessary to resolve the fault indicated on the display.
Other faults (from F5 to F37) cause temporary shutdowns that are automatically reset as soon as the value comes back within the boiler’s normal working range.
Page 31
31
DOMIcompact F 24 B
4 TECHNICAL CHARACTERISTICS AND DATA
4.1 Dimensions and connections
Fig. 18
Top view
Bottom view
Key
1 Heating system Flow Ø 3/4” (22mm with isolation valve fitted) 2 Hot water outlet Ø 1/2” (15mm with isolation valve fitted) 3 Gas inlet 1/2” (22mm with isolation valve fitted) 4 Tap water inlet Ø 1/2” (15mm with isolation valve fitted) 5 Heating system return Ø 3/4” (22mm with isolation valve fitted) 6 Condense outlet Ø 3/4” (flexible connection supplied)
149
460
706
681
266
97
36 95 60 60 95 114
1 2 3 5
86
120
254
266
98
6 4
Page 32
32
DOMIcompact F 24 B
4.2 General view and main components
fig. 19
Key
5 Combustion chamber 7 Gas inlet 8 DHW outlet 9 Cold water inlet 10 CH flow 11 CH return 14 Safety valve 16 Fan 19 Combustion chamber 21 Gas injector manifold 22 Burner assembly
26 Combustion chamber
insulation
27 Copper heat exchanger for
c.h. + d.h.w.
32 Heating pump 34 Heating flow sensor 36 Automatic air vent
42 D.h.w. temperature sensor 43 Air pressure switch
44 Gas valve 49 Safety thermostat 56 Expansion vessel
81 Spark ele c trode 114 Low Water pressure switch 126 Flue gas safety thermostat 132 Flue gas deflector
136 Flow switch 154 Condense outlet 193 Condensate Siphon 277 Secondary heat exchanger
32
56
132
27
19
26
81
16
43
5
49
34
10 8 7 9 11
22
21
42
14
114
44 136
277
193 154
126
36
Page 33
33
DOMIcompact F 24 B
4.3 Hydraulic diagram
Fig. 20
Key 5 Combustion chamber 7 Gas inlet 8 DHW outlet 9 Cold main inlet 10 CH flow 11 CH return 14 Heating safety valve 16 Fan 27 Heat exchanger 32 Heating pump 34 Flow temperature sensor
38 Flow switch 42 D.h.w. temperature sensor 43 Air pressure switch 44 Gas valve 49 Safety thermostat 56 Expansion vessel
81 Spark electrode 114 Low Water pressure switch 126 Flue gas safety thermostat 277 Secondary heat exchanger
117
9
27
10
8
56
81
32
49
5
38
42
34
43
16
P1
P2
44
277
126
114
14
Page 34
34
DOMIcompact F 24 B
4.4 Technical data table
Heating
Heating temperature adjustment range °C Maximum working temperature in heating °C
Heating circuit PMS safety valve (preset) bar Minimum working pressure in heating bar Expansion vessel capacity litres
Expansion vessel pre-filling pressure bar Total boiler water content litres
Hot water
Hot tap water supply Dt 25° C l/min
Hot tap water supply Dt 30° C l/min Hot tap water supply Dt 35° C l/min Tap water temperature adjustment range °C Maximum working pressure in hot water production bar Minimum working pressure in hot water production bar
Dimensions, weights connections
Height mm Width mm Depth mm Weight with packing kg Gas system connection mm Heating system connections mm Hot water circuit connections mm
Maximum length of separate flues D=80*
m
eq
(*Measurement given in equivalent linear metres  cfr FERROLI calculation system)
Electrical power supply
Max electrical power absorbed W
30 - 85
90
3
0.8 8
1
2,0
13,8
11,5
9,8
40 - 55
9
0.25
681 460 266
38 1/2 3/4 1/2
55
135
Powers
Hi Heating power
Pmax Pmin
kW 25,5 10,3
Useful Heating Power 80° C - 60° C Useful Heating Power 50° C - 30° C
kW 25,0 10,8
kW 24,1 9,9
Table 10
Protection level
IP X5D
Gas supply
Natural Gas delivery (G20)
Natural Gas main injectors (G20)
Pressure at Natural Gas burner (G20)
Natural Gas supply pressure (G20)
LPG delivery (G31)
LPG main injectors (G31)
Pressure at LPG burner (G31)
LPG supply pressure (G31)
mm 12 x 1,30 mbar 20,0 mbar 11,8 2,5
nm
3
/h 2,65 1,14
mm 12 x 0,77 mbar 37,0 mbar 35,0 7,5
kg/h 1,96 0,84
Efficiency
Seasonal Efficiency (SEDBUK)
87,7 % 88,7 %
Natural gas
LPG
Page 35
35
DOMIcompact F 24 B
4.5 Diagrams
Head available for the system
Fig. 21
0
0
1
2
3
4
5
6
7
500 1.000 1.500 2.000
Q [l/h]
H [m H
2
O]
3
2
1
A
= Pump speed
321
A
= Pressure loss through boiler
Page 36
36
DOMIcompact F 24 B
4.6 Time Clock
A 24 hour time clock is fitted to the boiler to control the central heating, this will come into operation when the selector switch “F“ is turned to the position marked “AUTO”.
AUTO
+
-
R
OVER RIDE
x
x
A
B
E
RDP
AUTO
P
OI
F
P
A Slide switch: set clock - auto - set programme B Display. Symbol in Display = Timer ON
P Select programme ON/OFF 1.....8
D Push buttons Time + Time
-
E Override: Boiler will switch ON if it is OFF; and OFF if it is ON F I=Heating continuous - AUTO=Heating timed - O=Heating disabled R Reset (with pencil) only with switch A in set clock position
1.1 Use buttons + and - to set 1st ON time eg. 6:00
Display
2.1 Use buttons + and - to set OFF time, eg. 9:00
Display
3.1 Use button + and - to set 2nd ON time, eg. 12:30
Display
4.1 Use button + and - to set 2nd OFF time eg. 14:00
Display
5.1 Use button + and - to set 3rd ON time, eg. 16:00
Display
6.1 Use button + and - to set 3rd OFF time eg. 23:30
Display
8. On completion of programming slide switch (A) to Auto position, the time of day will be displayed and the central heating will switch ON and OFF according to the programme set.
1. Slide switch (A) to right position (P)
Display
2. Press button (P)
Display
3. Press button (P)
Display
4. Press button (P)
Display
5. Press button (P)
Display
6. Press button (P)
Display
7. The timer can be programmed with up to 8 ON and 8 OFF times by repeating the above procedure.
6:30
1
8:30
2
12:00
3
12:00
4
6:00
1
9:00
2
12:30
3
14:00
4
16:30
5
22:30
6
16:00
5
23:30
6
Over ride
By pressing the over ride button (E) the timer programme is over ridden ie, if programme is in OFF time it will come ON and if in ON time will go OFF. The timer will revert back to it set programme on reaching the next ON or OFF time. When the programme is on over ride the sign will be shown in the display window (B).
Reset Button
By the use of a pencil the reset button can be pushed (R). This will clear all programmes apart from those factory pre set.
Reset is only possible with switch (A) in set Clock position!
To set time of day
1. Slide switch (A) to left position
2. Using button + and
-
adjust until the correct time is shown on display (B).
Pre Set Programmes. The timer is pre programmed with 3 ON and 3 OFF times.
6:30 - 8:30 12:00 - 12:00 16:30 - 22:30
If these are suitable no programming is required and the slide switch (A) can be moved to the Auto position and the central heating will be ON for these periods. (12:00 - 12:00 will not switch on the boiler)
To Set Own ON and OFF times. Symbol in Display = ON time
Page 37
37
DOMIcompact F 24 B
4.7 Wiring diagram
Fig. 22
Key
16 Fan
32 Heating circulator
34 Heating temp. sensor
38 Flow switch
42 Tap water temperature sensor
43 Air pressure switch
44 Gas valve
47 Modureg
49 Safety thermostat
72 Room thermostat
81 Ignition/detection electrode
114 Water pressure switch
126 Flue gas safety thermostat
139 Remote timer control (opentherm)
34
43
49
MF08FA.1
TRANSFORMER
42
114
441632
230V 50Hz
X5 X3 X7
X6 X4
1 2 123 1 23 4 123456712345678910 11
FUSE
FUSE
X1
N L
81
47
38
F 3.15A
F 3.15A
72
139
126
Condensate
discharge
full
CAUTION
Before connecting the voltage free room thermostat
or remote timer control, remove the jumper on the
terminal block.
Page 38
BENCHMARK
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROLTO HEATING ROOM T/STAT & PROGRAMMER/TIMER PROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATER CYLINDER T/STAT & PROGRAMMER/TIMER
COMBI BOILER
HEATING ZONE VALVES FITTED NOT REQUIRED
HOT WATER ZONE VALVES FITTED NOT REQUIRED
THERMOSTATIC RADIATOR VALVES FITTED
AUTOMATIC BYPASS TO SYSTEM FITTED NOT REQUIRED
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATE ft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE) mbar
CENTRAL HEATING FLOW TEMPERATURE °C
CENTRAL HEATING RETURN TEMPERATURE °C
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED? YES NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATE ft3/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE) mbar
COLD WATER INLET TEMPERATURE °C
HOT WATER OUTLET TEMPERATURE °C
WATER FLOW RATE
lts/min
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS? YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT WATER SYSTEM COMPLIES WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING? N/A YES CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
m3/hr
m
3
/hr
COMMISSIONING ENG’S NAME PRINT CORGI ID No.
SIGN DATE
BOILER SERIAL No. NOTIFICATION No.
BENCHMARK No.
GAS BOILER COMMISSIONING CHECKLIST
COLLECTIVE MARK
N/A
N/A
267
Please add the first 4 digits of the Boiler serial No to complete the BENCHMARK No.
Page 39
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SERVICE 1
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 2
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 3
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 4
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 5
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 6
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 7
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 8
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNA
TURE
SERVICE 9
DATE
ENGINEER NAME
COMP
ANY NAME
TEL
No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 10
DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
FERROLI TECHNICAL HELPLINE - 08707 282 885
Page 40
Phone numbers:
Installer
Service Engineer
BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.
ALL SPECIFICATIONS SUBJECT TO CHANGE
Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check
this is not caused by lack of electricity supply, gas supply or low water pressure before calling our
Customer Service Helpline.
Lichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE14 3HD
Tel. 08707 282 885 - Fax 08707 282 886
EIRE only:
HEATOVENT Greenhills Industrial Estate,
Greenhills Road, Walkinstown, Dublin 12, IRELAND
Tel 014508166 - Fax 014508501
Should you require any assistance during the installation
call our Technical Service Helpline on
08707 282 885 option 1
Should you require a service engineer to visit
call our service centre on
08707 282 885 option 2
(For U.K. and Northern Ireland)
For EIRE only call HEATOVENT on
014508166