FEC AFC1500 User Manual

0 (0)

Chapter 5: Control Interfaces

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.1 I/O Interface Board

The Multi-2 unit interface board provides the interface between real world control signals and the AFC1500 Fastening system I/O. Since there are many different I/O control structures in the industry today, the Multi-2 unit has the ability to adapt to these through use of the I/O interface board. The interface is available in many Fieldbus or “open architecture” configurations as well as standard hardwired discrete I/O.

The Multi-2 unit I/O assumes control of the individual SAN unit I/O, thus eliminating the need to wire to each individual spindle.

All I/O interface motherboards have a DIP Switch SW1 (located at position 7D) which has to be configured so the Multi-2 Unit can identify the type of interface installed. The table below identifies the switch set-up for configurable interface boards.

Interface Type

SW1

SW1

SW1

SW1

1

2

3

4

 

Discrete I/O (Sink Type – active true low )

ON

OFF

OFF

OFF

Discrete I/O (Source Type – active true high)

OFF

ON

OFF

OFF

DeviceNet-S® (for Toolsnet®)

ON

ON

OFF

OFF

Profinet IO

OFF

OFF

ON

OFF

Interbus-S® (for Toolsnet®)

ON

OFF

ON

OFF

Allen Bradley Remote I/O

OFF

ON

ON

OFF

Profibus® (for Toolsnet®)

ON

ON

ON

OFF

Modbus Plus®

OFF

OFF

OFF

ON

DeviceNet-S®

ON

OFF

OFF

ON

Ethernet I/P

OFF

ON

OFF

ON

Interbus-S®

ON

ON

OFF

ON

Mitsubishi CC-Link® Version 2 (I/O & Messaging)

OFF

OFF

ON

ON

Profibus®

ON

OFF

ON

ON

Mitsubishi CC-Link® Version 1 (I/O only)

OFF

ON

ON

ON

M-Net

ON

ON

ON

ON

(Other interfaces available, contact FEC)

5.2 Interface Board DIP Switch Setup

Throughout this chapter, SW1 settings will be represented as follows:

- Represents switch position

 

CN3

 

 

12

34

 

 

 

 

22

 

1

 

 

 

23

 

 

13

34

12

 

 

 

 

22

 

23

1

 

 

 

 

CN4 13

 

Side View I/O Interface Circuit Board

PAGE 5 - 2

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.3 Discrete I/O Interface

The Discrete I/O Interface is commonly used for hardwire direct connect PLC applications. Two types of Discrete I/O interfaces are available: 24VDC Sinking Type and 24VDC Sourcing Type. The standard discrete I/O interface is the Sinking Type interface.

5.3.1 Sinking Type (NPN)

The Sinking Type I/O interface is standard with discrete I/O Multi Units. It connects to 24VDC True Low type (NPN) PLC cards.

 

CN3

 

 

12

34

 

 

 

 

22

 

1

 

 

 

23

 

 

13

34

12

 

 

 

 

22

 

23

1

 

 

 

 

CN4 13

 

- Represents switch position

 

CN3

 

 

12

34

 

 

 

 

22

 

1

 

 

 

23

 

 

13

34

12

 

 

 

 

22

 

23

1

 

 

 

 

CN4 13

 

Discrete I/O (Sinking Type) Board Specifications

Operating Voltage

24 VDC

 

 

 

 

Maximum current (outputs)

200 ma

 

 

 

 

Logic

True Low (Sinking)

 

 

 

 

 

PLC-IN

Connector: Honda #MR-34F

Mating Connectors

(Cable #FEB-1271)

Housing: Honda #MR-34L

 

 

PLC-OUT

Connector: Honda #MR-34M

 

 

(Cable #FEB-1272)

Housing: Honda #MR-34L

 

 

 

PAGE 5 - 3

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.3.1.1 Discrete Signal Connection (Sinking Type)

AFC1500 MULTI-2 Unit

Device PLC

Output

Output

PAGE 5 - 4

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.3.2 Sourcing Type (PNP)

The Sourcing Type I/O interface is optional with discrete I/O Multi Units. It connects to 24VDC True High type (PNP) PLC cards. (This interface must be specified during ordering)

 

CN3

 

 

12

34

 

 

 

 

22

 

1

 

 

 

23

 

 

13

34

12

 

 

 

 

22

 

23

1

 

 

 

 

CN4 13

 

 

CN3

 

 

12

34

 

 

 

 

22

 

1

 

 

 

23

 

 

13

34

12

 

 

 

 

22

 

23

1

 

 

 

 

CN4 13

 

- Represents switch position

Discrete I/O (Sourcing Type) Board Specifications

Operating Voltage

24 VDC

 

 

 

 

Maximum current (outputs)

200 ma

 

 

 

 

Logic

True High (Sourcing)

 

 

 

 

 

PLC-IN

Connector: Honda #MR-34F

Mating Connectors

(Cable #FEB-1271)

Housing: Honda #MR-34L

 

 

PLC-OUT

Connector: Honda #MR-34M

 

 

(Cable #FEB-1272)

Housing: Honda #MR-34L

 

 

 

PAGE 5 - 5

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.3.2.1 Discrete Signal Connection (Sourcing Type)

AFC1500 MULTI Unit

Device PLC

Output signal

Input signal

PAGE 5 - 6

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.3.3 Input Signals (PLC-IN) Connector

The Input Signals are provided on the PLC IN connector. Inputs are assigned in the order as shown in the table below and cannot be changed. Pins designated as “Not Used” have no input assigned to them.

NOTE: When using Discrete I/O, “Bypass Spindle” input signals assigned to the PLC IN connector can only be used for up to 10 individual Spindles (from the Multi-2 Unit). When using Discrete I/O and you desire to connect this signal from additional spindles, the signal must be wired from the individual SAN Controllers using the SAN Unit’s PLC connector. (An alternative to this is to use a fieldbus interface which has control of all spindle bypass signals from the interface.)

Pin#

Signal

Contac

Description

 

t

 

 

 

 

 

 

1

Emergency Stop

N.C.

Emergency Stop Input

 

 

2

Reset

N.O.

Reset Input

 

 

3

Reverse

N.O.

Reverse Spindle Rotation Input

 

 

4

Start

N.O.

Start Cycle Input

 

 

5

Sequence Select 0

N.O.

 

 

 

6

Sequence Select 1

N.O.

Sequence Select Input

 

 

7

Sequence Select 2

N.O.

 

 

 

 

 

8

Sequence Select 3

N.O.

 

 

 

9

Cycle Count Up

N.O.

Cycle Count Input

 

 

10

Cycle Count Clear

N.O.

 

 

 

11

Self Check Disable

N.O.

Disables automatic self check

 

 

12

Not Used

 

 

 

 

13

IN PORT 1

N.O.

 

 

 

14

IN PORT 2

N.O.

External Sequence interface Input

 

15

IN PORT 3

N.O.

 

 

 

 

16

IN PORT 4

N.O.

 

 

 

17

BYPASS Spindle No.1

N.O.

Bypass’s spindle #1

 

 

18

BYPASS Spindle No.2

N.O.

Bypass’s spindle #2

 

 

19

BYPASS Spindle No.3

N.O.

Bypass’s spindle #3

 

 

20

BYPASS Spindle No.4

N.O.

Bypass’s spindle #4

 

 

21

BYPASS Spindle No.5

N.O.

Bypass’s spindle #5

 

 

22

BYPASS Spindle No.6

N.O.

Bypass’s spindle #6

 

 

23

BYPASS Spindle No.7

N.O.

Bypass’s spindle #7

 

 

24

BYPASS Spindle No.8

N.O.

Bypass’s spindle #8

 

 

25

BYPASS Spindle No.9

N.O.

Bypass’s spindle #9

 

 

26

BYPASS Spindle No.10

N.O.

Bypass’s spindle #10

 

 

27

Not Used

 

 

 

 

28

Not Used

 

 

 

 

29

Not Used

 

 

 

 

30

Data Select 0

 

 

 

 

31

Data Select 1

N.O.

Output Data Bank Select inputs

 

 

32

Data Select 2

 

 

 

 

33

Input Signal Power

 

Common for input signal.

Sink Type

+24V

34

Input Signal Power

 

Source Type

+0V

 

 

Note) NC: Normal Closed, NO: Normal Open

 

 

 

For Input Signal definition see Section 4.7.2.

PAGE 5 - 7

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.3.4 Ouput Signals (PLC-OUT) Connector

The Multi-2 Unit is capable of providing over 570 Output signals to indicate the status of the Multi-2 Unit and of all the AFC1500 SAN Controllers connected to it (up to 31 controllers). These signals are user configurable using the AFC User Console Software and may be programmed on any designated pin. Up to 8 separate output data “Banks” can be set up, each with 32 different output signals. The Output “Bank” is then selected using the Data Select inputs (Data Select 0, Data Select 1, Data Select 2).

FEC Standard* Output Layout

 

NO

 

 

Signal

 

 

Type**

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Total Reject

 

 

NO

 

Output when the fastening result is a REJECT.

 

 

 

 

 

 

 

 

 

2

 

 

Total Accept

 

 

NO

 

Output when the fastening result is a ACCEPT.

 

 

3

 

 

Abnormal

 

 

NO

 

Output when an Abnormal condition occurs.

 

 

 

4

 

 

Ready

 

 

NO

 

Output when the system is in the READY condition.

 

 

5

 

 

Busy

 

 

NO

 

System is in cycle

 

 

 

 

6

 

 

End

 

 

NO

 

Output when a fastening cycle is complete.

 

 

 

7

 

 

Sequence Output 0

 

 

NO

 

 

 

 

 

 

8

 

 

Sequence Output 1

 

 

NO

 

Output confirmation of SEQUENCE SELECT 0~4 input

 

 

9

 

 

Sequence Output 2

 

 

NO

 

selections.

 

 

 

 

10

 

 

Sequence Output 3

 

 

NO

 

 

 

 

 

 

11

 

 

Out Port 1

 

 

NO

 

 

 

 

 

 

12

 

 

Out Port 2

 

 

NO

 

 

 

 

 

 

13

 

 

Out Port 3

 

 

NO

 

These signals will output when the fastening sequence

 

 

14

 

 

Out Port 4

 

 

NO

 

 

 

 

 

 

 

 

reaches a step that has a [PLC OUTPUT] instruction

 

 

15

 

 

Out Port 5

 

 

NO

 

 

 

 

 

 

 

 

inserted.

 

 

 

 

16

 

 

Out Port 6

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

 

 

Out Port 7

 

 

NO

 

 

 

 

 

 

18

 

 

Out Port 8

 

 

NO

 

 

 

 

 

 

19

 

 

Spindle in Bypass

 

 

NO

 

Output when any connected spindle is in Bypass

 

 

20

 

 

Current Limit Warning

 

 

NO

 

Active when the high current limit has been exceeded.

 

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

 

As Configured

 

 

NO

 

 

 

 

 

 

29

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

Always ON / Always OFF

 

 

NO

 

See “Output Data Banks” on following page

 

 

 

31

 

 

Always ON / Always OFF

 

 

NO

 

See “Output Data Banks” on following page

 

 

 

32

 

 

Always ON / Always OFF

 

 

NO

 

See “Output Data Banks” on following page

 

 

 

33

 

 

Output Signal Power

 

 

 

 

 

Common for output signal.

Sink Type

+0V

 

 

34

 

 

Output Signal Power

 

 

 

 

 

Source Type

+24V

 

 

 

 

 

 

 

 

 

 

 

*This “Standard” layout is only provided as a guide. Any signal may be programmed on any pin using the AFC Software.

The layout above is programmed standard from FEC. It contains only “Multi” or system signals as shown, however, individual spindle signals are available and may be programmed (Ex. Individual spindle accept or reject

– See 4.7.3 for complete list of signals that may be programmed on these pins) ** Type: NO = (Normally Open)

For Output Signal definition see Section 4.7.3.

PAGE 5 - 8

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.3.4.1 Ouput Data Banks

When working with the Discrete I/O interface, the output signals are programmed into

“Banks” of 32 output signals in up to 8 output “Banks” (Max. 256 outputs). If the required output signals from the Multi-2 Unit exceed 32 signals, then Bank 2 can be programmed with additional signals. If over 64 signals are required, Bank 3 can be programmed and so on. These Output “Banks” can then be selected by the Data Select input signals. The Data

Select input signals 0, 1 & 2 together form a binary code to select up to eight (8) different Data Banks. (See Table 3 below)

Note: Bank Select inputs do not function with any interface except the Discrete I/O interface. When using Bank selects, it is recommended that the bank number be monitored to confirm actual output status of shared discrete output points. This can be performed by using the “Always On / Always Off” bits set-up in specific discrete output points when programming the output points with the AFC User Console Software. For this function, program the

“Always On / Always Off” bits to mimic the Data Select input bits. “Always On” bits will turn on the output in that particular Bank as soon as the bank is selected. “Always Off” bits will turn off the output in the particular Bank which is selected. Using different combinations of these bits programmed in an output in each Bank will allow monitoring of which Bank is selected.

The number of discrete outputs used for this monitoring function depends on how many Banks are required as shown below:

Number of Banks Required

Number of Discrete Outputs Required

for Monitoring Output Bank Status

 

1 (32 outputs)

0 or 1

2-4 (64 – 128 outputs)

2

5-8 (160 – 256 outputs)

3

Typically these “Always On / Always Off” bits are programmed in the last output points (Pins

30 -32 as shown on the previous page).

[Table 3] Output Data (BANK) Selection

 

Data Select 2

 

 

Data Select 1

 

 

Data Select 0

 

 

Output Data Bank

 

 

 

 

 

 

 

 

 

 

OFF

 

 

OFF

 

 

OFF

 

 

0

 

 

OFF

 

 

OFF

 

 

ON

 

 

1

 

 

OFF

 

 

ON

 

 

OFF

 

 

2

 

 

OFF

 

 

ON

 

 

ON

 

 

3

 

 

ON

 

 

OFF

 

 

OFF

 

 

4

 

 

ON

 

 

OFF

 

 

ON

 

 

5

 

 

ON

 

 

ON

 

 

OFF

 

 

6

 

 

ON

 

 

ON

 

 

ON

 

 

7

 

PAGE 5 - 9

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.3.5 Standard I/O Cable Wire Color Code

The table below shows the color code of the standard FEC Discrete I/O cable used for I/O connectors PLC IN and PLC OUT.

(FEC Cable Assemblies #FEB -1271 (PLC IN Cable), #FEB-1272 (PLC OUT Cable))

Pin No.

Wire Color

 

 

1

Black

2

Brown

3

Red

4

Orange

5

Yellow

6

Green

7

Blue

8

Violet

9

Gray

10

White

11

White/Black

12

White/Brown

13

White/Red

14

White/Orange

15

White/Yellow

16

White/Green

17

White/Blue

18

White/Violet

19

White/Gray

20

White/Black/Brown

21

White/Black/Red

22

White/Black/Orange

23

White/Black/Yellow

24

White/Black/Green

25

White/Black/Blue

26

White/Black/Violet

27

White/Black/Gray

28

White/Brown/Red

29

White/Brown/Orange

30

White/Brown/Yellow

31

White/Brown/Green

32

White/Brown/Blue

33

White/Brown/Violet

34

White/Brown/Gray

PAGE 5 - 10

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.4 Interbus S® Interface

InterBus S from Phoenix Contact is an open-ring based, distributed device I/O network. I/O data is transmitted in frames that provide simultaneous and predictable updates to all devices in the network. This interface board (S - version) has up to 512 bytes of assigned input data and 512 bytes of assigned output data* (64bytes default). The 64 bytes of assigned I/O data allow a maximum of 512 inputs and 512 outputs per node. FEC I/O is assigned to the I/O points in these data areas (some I/O will be designated spare). FEC Inputs match the discrete input layout. FEC Output locations are programmed using the AFC User Console Software.

* When using Master boards where the PCP channel is NOT supported, the maximum number of I/O will be 20 input bytes and 20 output bytes.

FEC integrates the Interbus S board manufactured by HMS Fieldbus Systems AB into the Multi-2 Unit modular I/O board. For further technical information on the Interbus S interface go to the HMS website. (www.hms.se)

6

1

 

9

5

 

9

5

 

6

1

3

1

4

2

 

DB9 Connector (male)

6

1

 

9

5

 

RBC

 

BA

 

 

9

5

RBDA/ERR

 

 

 

6

1

 

 

DB9 Connector

 

(female)

- Represents switch position

Daughter board

 

1

2

 

3

 

 

7

4

6

 

5

 

Item

 

 

Description

1

Application Connector

2

BUS-IN Connector

 

3

BUS-OUT Connector

4

Baud Rate Jumper

 

5

Status LEDs (4)

 

6

UL LED - Green if voltage is OK at Bus

 

 

 

Red - (flashing @ 2Hz) - ASIC and FLASH ROM check fault.

7

Watchdog LED

 

Green (flashing @ 2Hz) - module not initialized.

 

Green (flashing @ 1Hz) - module initialized and running OK.

 

 

 

 

 

 

Red (flashing @ 1Hz) - RAM check fault.

 

 

 

PAGE 5 - 11

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

Red (flashing @ 4Hz) - DPRAM check fault.

InterBus Specifications

Baud Rate

500K or 2M bits/sec.

 

 

Nodes

256

 

 

Distance

400 m

 

 

Cable

Point to point twisted pair

 

 

Packet Size

1-256 words

 

 

Communication Type

Master/Slave

 

 

Interface Specifications

Input data bytes (including free data)

512

(Default: 64 input data*)

 

 

 

Output data bytes (including free data)

512

(Default: 64 output data*)

 

 

Interface type

Remote bus interface

 

 

Operating Voltage

+5VDC / 200 ma

 

 

Data Width

4 words (1 word PCP, 3 words data)

 

 

ID Code

F3 Hex

 

 

Output objects

6000H through 603FH

 

 

Input objects

6040H through 607FH

 

 

 

* Actual Input/Output data length is configurable using the AFC Software package.

PAGE 5 - 12

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.4.1 Component Descriptions

Fieldbus Interface Connectors

 

Bus IN

Pin No.

Signal

Description

 

 

Housing

PE

Protective Earth Ground

 

 

1

DO1

Data Output

6

1

2

DI1

Data Input

 

 

3

GND

Signal Ground

9

5

4

NC

-

 

5

NC

-

 

 

 

 

6

/DO1

Inverted Data Output

 

 

7

/DI1

Inverted Data Input

 

 

8

NC

-

(9 pin male D-sub)

9

NC

-

 

Bus OUT

Pin No.

Signal

Description

 

 

Housing

PE

Protective Earth Ground

 

 

1

DO2

Data Output

 

 

2

DI2

Data Input

 

5

3

GND

Signal Ground

9

4

NC

-

 

 

 

5

GND

Signal Ground

6

1

6

/DO2

Inverted Data Output

 

 

7

/DI2

Inverted Data Input

 

 

8

NC

-

(9 pin female D-sub)

9

RBST

*

*Always terminate RBST to ground if it is not the last module on the bus. If the RBST is not connected to ground, the interface will automatically terminate the bus.

Baud Rate Switch

The module supports 2Mbit/s and 500Kbit/s operation. To select the desired baud rate, just move the jumper cap to the corresponding location.

selected before power is on and cannot be changed during operation.

Status LEDs

 

 

 

No.

LED

Color

Description

 

 

 

 

 

 

1

CC/RC

Green

Cable connection is good & master not in reset

 

 

 

 

 

 

 

 

 

 

2

BA

Green

Bus Active

 

 

 

 

 

 

 

 

 

 

3

RD

Yellow

Remote Bus Disabled

 

 

 

 

 

 

 

 

 

 

4

TR

Green

PCP - Communication active.

 

 

 

Hold Time = 500ms

 

 

 

 

 

 

 

 

 

 

 

PAGE 5 - 13

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.4.2 AFC User Console Software Settings

The Anybus board is set up by sending a Fieldbus Configuration File (*.fcf) containing initialization messages from the Multi-2 Unit to the board during power up. This string of data initializes different characteristics required for the board to communicate over the Interbus S network. In this string are messages which set the length of I/O data as well as other messages. Since the board is only initialized during power-up, the Multi-2 Unit MUST have the power cycled OFF/ON after the

“fcf” file is downloaded.

To download the fcf file, select “Field Bus Setup” from the “Multi” pull down menu. Select the appropriate “Bus Type” and click “Browse” to locate the correct fcf file. After the file has been selected, click “download” to send the file data to the Anybus board.

If no file exists (or if the settings need to be changed), after the Bus Type has been selected click on the Setup Tab.

Select the desired settings from the pull downs. When finished, go back to the General Tab and click “download” to send the file data to the Anybus board.

PAGE 5 - 14

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.4.3 Input Signals Mapping (CH1 ~ CH16)

Inputs are assigned in the order as shown in the table below and cannot be changed. Bits designated as “Unused” have no input assigned to them.

NOTE: If Interbus S TOOLSNET version is used – Input/Output Signal layout is different than shown. See 5.12 for TOOLSNET I/O Layout

 

CH. No.

 

 

Bit

 

 

 

Signal

 

 

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

 

Emergency Stop

1

 

 

 

 

 

 

1bit

 

Reset

2

 

 

 

 

 

 

2bit

 

Reverse

3

 

 

 

 

 

 

3bit

 

Start

4

 

 

 

 

 

 

4bit

 

Sequence Select 0

5

 

 

 

 

 

 

5bit

 

Sequence Select 1

6

 

 

 

Input CH.

 

6bit

 

Sequence Select 2

7

 

 

 

 

7bit

 

Sequence Select 3

8

 

 

 

 

 

 

 

 

 

 

No.01

 

8bit

 

Cycle Count Up

9

 

 

 

 

9bit

 

Cycle Count Clear

10

 

 

 

 

 

 

 

 

 

 

 

 

 

10bit

 

Self Check Disable

11

 

 

 

 

 

 

11bit

 

Unused

12

 

 

 

 

 

 

12bit

 

INPORT 1

13

 

 

 

 

 

 

13bit

 

INPORT 2

14

 

 

 

 

 

 

14bit

 

INPORT 3

15

 

 

 

 

 

 

15bit

 

INPORT 4

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH. No.

 

 

Bit

 

 

Signal

 

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

 

 

BYPASS SP#11

33

 

 

 

 

 

 

1bit

 

 

BYPASS SP#12

34

 

 

 

 

 

 

2bit

 

 

BYPASS SP#13

35

 

 

 

 

 

 

3bit

 

 

BYPASS SP#14

36

 

 

 

 

 

 

4bit

 

 

BYPASS SP#15

37

 

 

 

 

 

 

5bit

 

 

BYPASS SP#16

38

 

 

 

Input CH.

 

6bit

 

 

BYPASS SP#17

39

 

 

 

 

7bit

 

 

BYPASS SP#18

40

 

 

 

 

 

 

 

 

 

 

 

No.03

 

8bit

 

 

BYPASS SP#19

41

 

 

 

 

9bit

 

 

BYPASS SP#20

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10bit

 

 

BYPASS SP#21

43

 

 

 

 

 

 

11bit

 

 

BYPASS SP#22

44

 

 

 

 

 

 

12bit

 

 

BYPASS SP#23

45

 

 

 

 

 

 

13bit

 

 

BYPASS SP#24

46

 

 

 

 

 

 

14bit

 

 

BYPASS SP#25

47

 

 

 

 

 

 

15bit

 

 

BYPASS SP#26

48

 

 

 

CH. No.

 

 

Bit

 

 

Signal

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

BYPASS SP#1

17

 

 

 

 

 

1bit

BYPASS SP#2

18

 

 

 

 

 

2bit

BYPASS SP#3

19

 

 

 

 

 

3bit

BYPASS SP#4

20

 

 

 

 

 

4bit

BYPASS SP#5

21

 

 

 

 

 

5bit

BYPASS SP#6

22

 

 

Input CH.

 

6bit

BYPASS SP#7

23

 

 

 

7bit

BYPASS SP#8

24

 

 

 

 

 

 

 

No.02

 

8bit

BYPASS SP#9

25

 

 

 

9bit

BYPASS SP#10

26

 

 

 

 

 

 

 

 

 

 

10bit

Unused

27

 

 

 

 

 

11bit

Unused

28

 

 

 

 

 

12bit

Unused

29

 

 

 

 

 

13bit

Unused

30

 

 

 

 

 

14bit

Unused

31

 

 

 

 

 

15bit

Unused

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH. No.

 

 

Bit

 

Signal

 

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

 

BYPASS SP#27

49

 

 

 

 

 

1bit

 

BYPASS SP#28

50

 

 

 

 

 

2bit

 

BYPASS SP#29

51

 

 

 

 

 

3bit

 

BYPASS SP#30

52

 

 

 

 

 

4bit

 

BYPASS SP#31

53

 

 

 

 

 

5bit

 

 

 

 

54

 

 

Input CH.

 

6bit

 

 

 

 

55

 

 

 

7bit

 

 

 

 

56

 

 

 

 

 

 

 

 

 

 

 

No.04

 

8bit

 

 

 

 

57

 

 

 

9bit

 

 

 

 

58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10bit

 

 

 

 

59

 

 

 

 

 

11bit

 

 

 

 

60

 

 

 

 

 

12bit

 

 

 

 

61

 

 

 

 

 

13bit

 

 

 

 

62

 

 

 

 

 

14bit

 

 

 

 

63

 

 

 

 

 

15bit

 

 

 

 

64

 

The Channel Number at the Master Unit output side differs according to node address settings. Please check before operating the unit.

Note: For signal definitions see Section 4.7.2

PAGE 5 - 15

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.4.4 Ouput Signals (CH1 ~ CH16)

The Multi-2 Unit is capable of providing over 570 Output signals to indicate the status of the Multi-2 Unit and of all the AFC1500 SAN Controllers connected to it (up to 31 controllers).

 

CH. No.

 

 

Bit

 

 

Signal

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

 

Total Reject

1

 

1

 

 

 

 

 

1bit

 

Total Accept

1

 

2

 

 

 

 

 

2bit

 

Abnormal

1

 

3

 

 

 

 

 

3bit

 

Ready

1

 

4

 

 

 

 

 

4bit

 

Busy

1

 

5

 

 

 

 

 

5bit

 

End

1

 

6

 

 

Output CH.

 

6bit

 

Sequence Output 0

1

 

7

 

 

 

7bit

 

Sequence Output 1

1

 

8

 

 

No.01

 

 

 

 

 

 

8bit

 

Sequence Output 2

1

 

9

 

 

 

 

 

 

 

 

 

 

 

 

9bit

 

Sequence Output 3

1

 

10

 

 

 

 

 

10bit

 

Spindle in Bypass

1

 

11

 

 

 

 

 

11bit

 

Current Warning

1

 

12

 

 

 

 

 

12bit

 

Spindle No.1 Accept

1

 

13

 

 

 

 

 

13bit

 

Spindle No.1 Reject

1

 

14

 

 

 

 

 

14bit

 

Spindle No.1 ABN.

1

 

15

 

 

 

 

 

15bit

 

Spindle No.1 BYP

1

 

16

 

 

 

 

 

0bit

 

Spindle No.2 Accept

1

 

17

 

 

 

 

 

1bit

 

Spindle No.2 Reject

1

 

18

 

 

 

 

 

2bit

 

Spindle No.2 ABN

1

 

19

 

 

 

 

 

3bit

 

Spindle No.2 BYP

1

 

20

 

 

 

 

 

4bit

 

Spindle No.3 Accept

1

 

21

 

 

 

 

 

5bit

 

Spindle No.3 Reject

1

 

22

 

 

Output CH.

 

6bit

 

Spindle No.3 ABN

1

 

23

 

 

 

7bit

 

Spindle No.3 BYP

1

 

24

 

 

No.02

 

 

 

 

 

 

8bit

 

Spindle No.4 Accept

1

 

25

 

 

 

 

 

 

 

 

 

 

 

 

9bit

 

Spindle No.4 Reject

1

 

26

 

 

 

 

 

10bit

 

Spindle No.4 ABN.

1

 

27

 

 

 

 

 

11bit

 

Spindle No.4 BYP

1

 

28

 

 

 

 

 

12bit

 

Spindle No.5 Accept

1

 

29

 

 

 

 

 

13bit

 

Spindle No.5 Reject

1

 

30

 

 

 

 

 

14bit

 

Spindle No.5 ABN.

1

 

31

 

 

 

 

 

15bit

 

Spindle No.5 BYP

1

 

32

 

 

 

 

 

0bit

 

Spindle No.6 Accept

2

 

1

 

 

 

 

 

1bit

 

Spindle No.6 Reject

2

 

2

 

 

 

 

 

2bit

 

Spindle No.6 ABN

2

 

3

 

 

 

 

 

3bit

 

Spindle No.6 BYP

2

 

4

 

 

 

 

 

4bit

 

Spindle No.7 Accept

2

 

5

 

 

 

 

 

5bit

 

Spindle No.7 Reject

2

 

6

 

 

 

 

 

6bit

 

Spindle No.7 ABN

2

 

7

 

 

Output CH.

 

7bit

 

Spindle No.7 BYP

2

 

8

 

 

 

8bit

 

Spindle No.8 Accept

2

 

9

 

 

No.03

 

 

 

 

 

 

 

 

9bit

 

Spindle No.8 Reject

2

 

10

 

 

 

 

 

10bit

 

Spindle No.8 ABN.

2

 

11

 

 

 

 

 

11bit

 

Spindle No.8 BYP

2

 

12

 

 

 

 

 

12bit

 

Spindle No.9 Accept

2

 

13

 

 

 

 

 

13bit

 

Spindle No.9 Reject

2

 

14

 

 

 

 

 

14bit

 

Spindle No.9 ABN.

2

 

15

 

 

 

 

 

15bit

 

Spindle No.9 BYP

2

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH. No.

 

 

Bit

 

 

Signal

 

 

 

 

 

 

 

 

 

Output CH.

 

0bit

 

 

 

 

8

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.16

 

 

 

 

 

 

 

 

 

 

 

 

 

15bit

 

 

 

 

8

 

32

 

 

 

 

 

 

 

 

 

 

 

See Section 4.7.3 for available output signals.

These Output signals are user configurable using the AFC User Console Software and may be programmed on any designated bit.

The Output signal mapping shown is only an EXAMPLE. The signals may be programmed for placement in ANY bit position.

The CH. No. at the Master input side differs according to node address settings. Please check before operating the unit.

PAGE 5 - 16

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.5 DeviceNet® Interface

The DeviceNet communication interface allows slave connection to an industrial DeviceNet network. DeviceNet allows industrial devices to be controlled over an open network architecture enabling device connection at various locations in the field. This “fieldbus” technology reduces hard wiring/cabling & provides ease of installation. It uses a broadcast-oriented protocol -the CAN (Controller Area Network)- that can interface to many devices such as limit switches, sensors, directional valves, motor starters, bar code readers, process sensors, frequency drives, etc. The network can have up to 64 nodes. Maximum I/O data is 512 input bytes & 512 output bytes. FEC Inputs match the discrete input layout. FEC Output location is programmed using the AFC User Console Software.

Note: The DeviceNet interface is implemented according to the ODVA specification for a communications adapter (profile no.12). It is acting as a “group two only server” on the DeviceNet network.

FEC integrates the DeviceNet board manufactured by HMS Fieldbus Systems AB into the Multi-Unit modular I/O board. For further technical information on the DeviceNet interface go to the HMS website. (www.hms.se)

Further DeviceNet information can be found through the Open DeviceNet Vendors Association (ODVA). (www.ODVA.org)

DEVICENET CONNECTOR

BAUD/MAC ID SETTING

LED INDICATORS

DEVICENET

DEVICENET

CONNECTOR

CONNECTOR

BAUD/MAC ID

BAUD/MAC ID

SETTING

SETTING

LED

LED

INDICATORS

INDICATORS

- Represents switch position

1

2

3

5

4

Item

Description

1Application Connector

2DeviceNet Connector

3Configuration Switches

4Status LEDs (4)

Red - (flashing @ 2Hz) - ASIC and FLASH ROM check fault.

Green (flashing @ 2Hz) - module not initialized.

5 Watchdog LED Green (flashing @ 1Hz) - module initialized and running OK. Red (flashing @ 1Hz) - RAM check fault.

Red (flashing @ 4Hz) - DPRAM check fault.

PAGE 5 - 17

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

DeviceNet Specifications

Speed

125K, 250K and 500K baud

Nodes

64

 

500 meters at 125K baud

Maximum Distance

250 meters at 250K baud

 

100 meters at 500K baud

 

Twisted pair for signal and power

Cable

Allen Bradley or equivalent ;

Thin Cable #1485C-P1-C

 

 

Thick Cable # 1485C-P1-A

Communications Type

Master/Slave

Interface Board Specifications

Operating Voltage

+5V, 200 ma

Output data bytes

512 max.*

Input data bytes

512 max.*

Servers per group

2 Maximum

Interface type

Dual Port RAM or Serial Interface

* Typical configuration is 32 Bytes (256 I/O points) but can be altered using the AFC Software package. (See AnyBus-S Reference at the end of this chapter for I/O Setting example.)

EDS File

Each device on a DeviceNet network is associated with an EDS file containing all necessary information about the device to be connected. The network configuration program uses this file during configuration of the network.

The EDS file associated with the FEC device can be downloaded from the FEC website. www.fecusa.com (file: abs.eds)

Direct link:www.fec-usa.com/fecusacomnew/support/index.htm (the file can also be downloaded directly from HMS - www.hms.se)

Note: The FEC system will appear in the network Vendor list as “HMS Fieldbus Systems” and in the network as “Anybus-S DeviceNet” adapter. This is the manufacturer of the interface board which is integrated into the Multi-2 Unit.

NOTE: COMPATIBILITY ISSUE

There is a known compatibility issue using with OMRON C200HW-DRM21-V1

PLC’s and the Devicenet interface. This is an OMRON problem.

Omron suggests using CS1-DRM21-V1 PLC in its place.

PAGE 5 - 18

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.5.1 Component Descriptions

Fieldbus Interface Connections

Pin No.

Signal

Wire Color

 

 

 

1

V-

Black

 

 

 

2

CAN_L

Blue

 

 

See “Termination”

 

 

3

Drain/Shield

 

 

 

 

 

 

 

4

CAN_H

White

 

 

 

 

 

 

5

V+

Red

 

 

 

Termination

Termination of the fieldbus requires a terminating resistor at each end of the fieldbus. These resistors should have a value of 121 ohms.

Configuration Switches

On a DeviceNet network, each node must be assigned its own unique Mac ID. The Mac ID is a value between 0 and 63 used to identify each node. The Mac ID and Baud Rate are set using the DIP switches on the front of the module.

These switches must be set before power is on and cannot be changed during operation.

Baud Rate Settings

 

Baud Rate

SW-1

SW-2

 

 

 

 

125K

OFF

OFF

 

 

 

ON1

250K

OFF

 

ON

 

 

 

500K

ON

OFF

 

 

 

 

 

 

 

2

Reserved

ON

 

ON

 

 

 

 

 

 

 

 

3

Mac ID Settings

 

 

 

 

 

 

4

Mac ID

SW-3 (MSB)

SW-4

SW-5

SW-6

SW-7

SW-8 (LSB)

5

Address 0

OFF

OFF

 

OFF

OFF

OFF

OFF

6

Address 1

OFF

OFF

 

OFF

OFF

OFF

ON

7

Address 2

OFF

OFF

 

OFF

OFF

ON

OFF

8

Address 3

OFF

OFF

 

OFF

OFF

ON

ON

 

 

 

 

Address 61

ON

ON

 

ON

ON

OFF

ON

 

Address 62

ON

ON

 

ON

ON

ON

OFF

 

Address 63

ON

ON

 

ON

ON

ON

ON

Status LEDs

 

 

 

 

 

LED

State

Description

 

 

 

 

1

- Reserved

-

Reserved for future use.

 

 

 

 

 

 

Off

Not Powered / Not Online

 

 

 

 

 

 

 

 

 

 

 

 

Green solid

Link OK, Online, Connected

 

 

 

 

2

- Network Status

Green flashing

Online, Not connected

 

 

 

 

 

 

Red solid

Critical Link Failure

 

 

 

 

 

 

Red flashing

Connection Timeout

 

 

4

1

 

 

Off

No power to device

 

 

 

 

 

 

 

 

3

2

 

 

Green solid

Device operational

 

 

 

 

3

- Module Status

Green flashing

Data size bigger than configured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red solid

Unrecoverable fault

 

 

 

 

 

 

Red flashing

Minor fault

 

 

 

 

4

- Reserved

-

Reserved for future use.

PAGE 5 - 19

FEC AFC1500 User Manual

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.5.2 User Console Software Settings

The Anybus board is set up by sending a Fieldbus Configuration File (*.fcf) containing initialization messages from the Multi-2 Unit to the board during power up. This string of data initializes different characteristics required for the board to communicate over the DeviceNet network. In this string are messages which set the length of I/O data as well as other messages. Since the board is only initialized during power-up, the Multi-2 Unit MUST have the power cycled OFF/ON after the

“fcf” file is downloaded.

To download the fcf file, select “Field Bus Setup” from the “Multi” pull down menu. Select the appropriate “Bus Type” and click “Browse” to locate the correct fcf file. After the file has been selected, click “download” to send the file data to the Anybus board.

If no file exists (or if the settings need to be changed), after the Bus Type has been selected click on the Setup Tab.

Select the desired settings from the pull downs. In I/O SETUP, select the “Input Data Length” and “Output Data Length” as required by you application. (INPUT & OUTPUT in this screen refer to PLC side I/O, INPUT = FEC Output size, OUTPUT = FEC Input size) When finished, go back to the

General Tab and click “download” to send the file data to the Anybus board.

The DeviceNet interface also has the ability to transfer fastening results data (message data). Refer to the AFC1500 User Console Manual for message setup information.

See section 5.11.5 for message set-up example (reference only)

PAGE 5 - 20

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.5.3 Input Signals (CH1 ~ CH16)

Inputs are assigned in the order as shown in the table below and cannot be changed. Bits designated as “Not Used” have no input assigned to them.

Operation Note: The first 16 bits of I/O are used by DeviceNet communication. The first input must be set “ON” to enable communication.

NOTE: If Devicenet TOOLSNET version is used – Input/Output Signal layout is different than shown. See 5.12 for TOOLSNET I/O Layout

 

CH. No.

 

 

Bit

 

 

 

Signal

 

 

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

 

Emergency Stop

1

 

 

 

 

 

 

1bit

 

Reset

2

 

 

 

 

 

 

2bit

 

Reverse

3

 

 

 

 

 

 

3bit

 

Start

4

 

 

 

 

 

 

4bit

 

Sequence Select 0

5

 

 

 

 

 

 

5bit

 

Sequence Select 1

6

 

 

 

Input CH.

 

6bit

 

Sequence Select 2

7

 

 

 

 

7bit

 

Sequence Select 3

8

 

 

 

 

 

 

 

 

 

 

No.01

 

8bit

 

Cycle Count Up

9

 

 

 

 

9bit

 

Cycle Count Clear

10

 

 

 

 

 

 

 

 

 

 

 

 

 

10bit

 

Self Check Disable

11

 

 

 

 

 

 

11bit

 

Unused

12

 

 

 

 

 

 

12bit

 

INPORT 1

13

 

 

 

 

 

 

13bit

 

INPORT 2

14

 

 

 

 

 

 

14bit

 

INPORT 3

15

 

 

 

 

 

 

15bit

 

INPORT 4

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH. No.

 

 

Bit

 

 

Signal

 

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

 

 

BYPASS SP#11

33

 

 

 

 

 

 

1bit

 

 

BYPASS SP#12

34

 

 

 

 

 

 

2bit

 

 

BYPASS SP#13

35

 

 

 

 

 

 

3bit

 

 

BYPASS SP#14

36

 

 

 

 

 

 

4bit

 

 

BYPASS SP#15

37

 

 

 

 

 

 

5bit

 

 

BYPASS SP#16

38

 

 

 

Input CH.

 

6bit

 

 

BYPASS SP#17

39

 

 

 

 

7bit

 

 

BYPASS SP#18

40

 

 

 

 

 

 

 

 

 

 

 

No.03

 

8bit

 

 

BYPASS SP#19

41

 

 

 

 

9bit

 

 

BYPASS SP#20

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10bit

 

 

BYPASS SP#21

43

 

 

 

 

 

 

11bit

 

 

BYPASS SP#22

44

 

 

 

 

 

 

12bit

 

 

BYPASS SP#23

45

 

 

 

 

 

 

13bit

 

 

BYPASS SP#24

46

 

 

 

 

 

 

14bit

 

 

BYPASS SP#25

47

 

 

 

 

 

 

15bit

 

 

BYPASS SP#26

48

 

 

 

CH. No.

 

 

Bit

 

 

Signal

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

BYPASS SP#1

17

 

 

 

 

 

1bit

BYPASS SP#2

18

 

 

 

 

 

2bit

BYPASS SP#3

19

 

 

 

 

 

3bit

BYPASS SP#4

20

 

 

 

 

 

4bit

BYPASS SP#5

21

 

 

 

 

 

5bit

BYPASS SP#6

22

 

 

Input CH.

 

6bit

BYPASS SP#7

23

 

 

 

7bit

BYPASS SP#8

24

 

 

 

 

 

 

 

No.02

 

8bit

BYPASS SP#9

25

 

 

 

9bit

BYPASS SP#10

26

 

 

 

 

 

 

 

 

 

 

10bit

Unused

27

 

 

 

 

 

11bit

Unused

28

 

 

 

 

 

12bit

Unused

29

 

 

 

 

 

13bit

Unused

30

 

 

 

 

 

14bit

Unused

31

 

 

 

 

 

15bit

Unused

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH. No.

 

 

Bit

 

Signal

 

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

 

BYPASS SP#27

49

 

 

 

 

 

1bit

 

BYPASS SP#28

50

 

 

 

 

 

2bit

 

BYPASS SP#29

51

 

 

 

 

 

3bit

 

BYPASS SP#30

52

 

 

 

 

 

4bit

 

BYPASS SP#31

53

 

 

 

 

 

5bit

 

 

 

 

54

 

 

Input CH.

 

6bit

 

 

 

 

55

 

 

 

7bit

 

 

 

 

56

 

 

 

 

 

 

 

 

 

 

 

No.04

 

8bit

 

 

 

 

57

 

 

 

9bit

 

 

 

 

58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10bit

 

 

 

 

59

 

 

 

 

 

11bit

 

 

 

 

60

 

 

 

 

 

12bit

 

 

 

 

61

 

 

 

 

 

13bit

 

 

 

 

62

 

 

 

 

 

14bit

 

 

 

 

63

 

 

 

 

 

15bit

 

 

 

 

64

 

The Channel Number at the Master Unit output side differs according to node address settings. Please check before operating the unit.

Note: For signal definitions see Section 4.7.2

PAGE 5 - 21

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.5.4 Ouput Signals (CH1 ~ CH16)

The Multi-2 Unit is capable of providing over 570 Output signals to indicate the status of the Multi-2 Unit and of all the AFC1500 SAN Controllers connected to it (up to 31 controllers).

 

CH. No.

 

 

Bit

 

 

Signal

 

 

FEC Multi-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank

 

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0bit

 

Total Reject

1

 

1

 

 

 

 

 

1bit

 

Total Accept

1

 

2

 

 

 

 

 

2bit

 

Abnormal

1

 

3

 

 

 

 

 

3bit

 

Ready

1

 

4

 

 

 

 

 

4bit

 

Busy

1

 

5

 

 

 

 

 

5bit

 

End

1

 

6

 

 

Output CH.

 

6bit

 

Sequence Output 0

1

 

7

 

 

 

7bit

 

Sequence Output 1

1

 

8

 

 

No.01

 

 

 

 

 

 

8bit

 

Sequence Output 2

1

 

9

 

 

 

 

 

 

 

 

 

 

 

 

9bit

 

Sequence Output 3

1

 

10

 

 

 

 

 

10bit

 

Spindle in Bypass

1

 

11

 

 

 

 

 

11bit

 

Current Warning

1

 

12

 

 

 

 

 

12bit

 

Spindle No.1 Accept

1

 

13

 

 

 

 

 

13bit

 

Spindle No.1 Reject

1

 

14

 

 

 

 

 

14bit

 

Spindle No.1 ABN.

1

 

15

 

 

 

 

 

15bit

 

Spindle No.1 BYP

1

 

16

 

 

 

 

 

0bit

 

Spindle No.2 Accept

1

 

17

 

 

 

 

 

1bit

 

Spindle No.2 Reject

1

 

18

 

 

 

 

 

2bit

 

Spindle No.2 ABN

1

 

19

 

 

 

 

 

3bit

 

Spindle No.2 BYP

1

 

20

 

 

 

 

 

4bit

 

Spindle No.3 Accept

1

 

21

 

 

 

 

 

5bit

 

Spindle No.3 Reject

1

 

22

 

 

Output CH.

 

6bit

 

Spindle No.3 ABN

1

 

23

 

 

 

7bit

 

Spindle No.3 BYP

1

 

24

 

 

No.02

 

 

 

 

 

 

8bit

 

Spindle No.4 Accept

1

 

25

 

 

 

 

 

 

 

 

 

 

 

 

9bit

 

Spindle No.4 Reject

1

 

26

 

 

 

 

 

10bit

 

Spindle No.4 ABN.

1

 

27

 

 

 

 

 

11bit

 

Spindle No.4 BYP

1

 

28

 

 

 

 

 

12bit

 

Spindle No.5 Accept

1

 

29

 

 

 

 

 

13bit

 

Spindle No.5 Reject

1

 

30

 

 

 

 

 

14bit

 

Spindle No.5 ABN.

1

 

31

 

 

 

 

 

15bit

 

Spindle No.5 BYP

1

 

32

 

 

 

 

 

0bit

 

Spindle No.6 Accept

2

 

1

 

 

 

 

 

1bit

 

Spindle No.6 Reject

2

 

2

 

 

 

 

 

2bit

 

Spindle No.6 ABN

2

 

3

 

 

 

 

 

3bit

 

Spindle No.6 BYP

2

 

4

 

 

 

 

 

4bit

 

Spindle No.7 Accept

2

 

5

 

 

 

 

 

5bit

 

Spindle No.7 Reject

2

 

6

 

 

 

 

 

6bit

 

Spindle No.7 ABN

2

 

7

 

 

Output CH.

 

7bit

 

Spindle No.7 BYP

2

 

8

 

 

 

8bit

 

Spindle No.8 Accept

2

 

9

 

 

No.03

 

 

 

 

 

 

 

 

9bit

 

Spindle No.8 Reject

2

 

10

 

 

 

 

 

10bit

 

Spindle No.8 ABN.

2

 

11

 

 

 

 

 

11bit

 

Spindle No.8 BYP

2

 

12

 

 

 

 

 

12bit

 

Spindle No.9 Accept

2

 

13

 

 

 

 

 

13bit

 

Spindle No.9 Reject

2

 

14

 

 

 

 

 

14bit

 

Spindle No.9 ABN.

2

 

15

 

 

 

 

 

15bit

 

Spindle No.9 BYP

2

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH. No.

 

 

Bit

 

 

Signal

 

 

 

 

 

 

 

 

 

Output CH.

 

0bit

 

 

 

 

8

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.16

 

 

 

 

 

 

 

 

 

 

 

 

 

15bit

 

 

 

 

8

 

32

 

 

 

 

 

 

 

 

 

 

 

See Section 4.7.3 for available output signals.

These Output signals are user configurable using the AFC User Console Software and may be programmed on any designated bit.

The Output signal mapping shown is only an EXAMPLE. The signals may be programmed for placement in ANY bit position.

The CH. No. at the Master input side differs according to node address settings. Please check before operating the unit.

PAGE 5 - 22

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.6 Profibus® Interface

The Profibus-DP communication interface allows slave connection to an industrial Profibus network. Profibus-DP allows industrial devices to be controlled over an open network architecture enabling device connection at various locations in the field. This “Fieldbus” technology reduces hardwiring/cabling & provides ease of installation. It can interface to many devices such as limit switches, sensors, directional valves, motor starters, bar code readers, process sensors, frequency drives, etc. The network can have up to 126 nodes. Its maximum communication baud rate is 12M baud and its minimum baud rate is 9.6K baud.

Node addressing is selectable using the address selection switches. Baud rate is auto detected from the master and no user setup is required. Module & Network status LED’s provide network diagnostics.

Maximum I/O data is 244 input bytes & 244 output bytes. FEC Inputs match the discrete input layout. FEC Output location is programmed using the AFC User Console Software.

Note: The Profibus interface is implemented according to the Profibus-DP EN 50 170 (DIN 19245 Part 1) specification.

FEC integrates the Profibus-DP board manufactured by HMS Fieldbus Systems AB into the Multi-Unit modular I/O board. For further technical information on the Profibus interface go to the HMS website. (www.hms.se)

Further Profibus information can be found on the Profibus website at www.profibus.com.

PROFIBUS CONNECTOR

TERMINATION SWITCH

ADDRESS

SETTING

LED INDICATORS

PROFIBUS

PROFIBUS

CONNECTOR

CONNECTOR

TERMINATION

TERMINATION

SWITCH

SWITCH

ADDRESS

ADDRESS

SETTING

SETTING

LED

LED

INDICATORS

INDICATORS

- Represents switch position

1

2

3

4

6

5

Item

 

Description

1

Application Connector

2

Profibus Connector

3

Terminator Switch

4

Address Switches

5

Status LEDs (4)

 

 

Red - (flashing @ 2Hz) - ASIC and FLASH ROM check fault.

 

 

Green (flashing @ 2Hz) - module not initialized.

6

Watchdog LED

Green (flashing @ 1Hz) - module initialized and running OK.

 

 

Red (flashing @ 1Hz) - RAM check fault.

 

 

Red (flashing @ 4Hz) - DPRAM check fault.

 

 

PAGE 5 - 23

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

 

 

 

 

Profibus Specifications

 

 

 

 

 

 

 

 

 

 

Speed

 

9.6K - 12M baud - auto selected

 

 

 

Nodes

 

126 Note: Node 126 is reserved for commissioning purposes only

 

 

Distance

 

200m max. at 1.5Mbit/s extendable with repeaters.

 

 

Cable

 

Shielded Copper Twisted Pair or fiber optic

 

 

Communications Type

 

Master/Slave - EIA RS485

 

 

 

Protocol Version

 

Ver. 1.10

 

 

 

Maximum Cyclic I/O Size

 

244bytes In, 244 bytes out max.

416 total bytes max.

 

 

Data transmission

 

The module only supports cyclic I/O data transmission.

 

Configuration

FEC Profibus I/O configuration is programmable using the AFC User Console software. I/O can be set as required by the application according to parameter limits set forth by the GSD (Profibus) configuration file. The AFC Software allows configuration of the number of I/O in the Multi Unit. Configuration of the Profibus Master MUST match the configuration of the FEC Profibus slave. In the Profibus Master setup, input size and output size is set as “byte” ordering. (Do not use “word” ordering. This will inverse the I/O location) When setting the Profibus Master configuration, PLC input size refers to FEC output size (ie. Accept, Reject, Busy, etc.) and PLC output size refers to FEC inputs (ie. Start, Stop, Reset, etc.). FEC will show up as 2 modules. Module 1 is inputs, module 2 is outputs. (See AnyBus-S Reference at the end of this chapter for I/O Setting example.)

GSD File

Each device on a Profibus network is associated with a GSD file containing all necessary information about the device to be connected. The network configuration program uses this file during configuration of the network.

The GSD file associated with the FEC device can be downloaded from the FEC website. www.fecusa.com (File : hms_1003.gsd)

Direct link:www.fec-usa.com/fecusacomnew/support/index.htm (The file can also be downloaded directly from HMS - www.hms.se)

PAGE 5 - 24

Chapter 5: Control Interfaces

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

5.6.1 Component Descriptions

Fieldbus Interface Connection

 

 

Pin No.

Signal

Description

 

 

1

N.C.

 

 

5

2

N.C.

 

9

3

B- Line

Positive RxD/TxD according to RS485 Spec.

 

 

 

 

 

4

RTS

Request to send

6

1

5

GND Bus

Isolated GND from RS 485 side

 

6

+5V Bus

Isolated +5V from RS 485 side

 

 

 

 

7

N.C.

 

 

 

8

A- Line

Negative RxD/TxD according to RS485 Spec.

 

 

9

N.C.

 

(9 pin female D-sub)

Housing

Shield

Connected to PE

Termination

Termination of the fieldbus requires a terminating resistor at each end of the fieldbus. A termination switch is provided on the Profibus-DP interface board. Set the switch to “ON”, if termination is required. If external terminators are used, the switch must be in the off position.

Node Address

Before configuring the Profibus-DP module, the node address has to be set. This is done with two rotary switches on the module which can set the node address 1-99 in decimal format. The Upper rotary switch (closest to the D-sub) sets the “tens” digit (10x), and the bottom rotary switch sets the “ones” digit (1x). Example: To set node 37, place the “tens” digit switch on 3 and the “ones” digit switch on 7.

This switch must be set before power is on, and cannot be changed during operation.

Status LEDs

 

 

 

 

LED

Status

Description

 

 

 

 

1

-

Not Used

 

 

 

 

2

Off

Module not on-line

 

 

 

 

Green

Module is on-line and data exchange is possible.

 

 

 

 

 

 

 

 

 

3

Off

Module is not off-line

 

 

 

 

Red

Module is off-line and data exchange is not

 

 

 

 

 

possible.

 

 

 

 

 

 

 

 

 

 

 

Off

No diagnostics present.

 

 

 

 

 

 

Error in configuration: IN and/or OUT length set

 

 

4

1

 

Red flashing at 1

during initialization of the module is not equal to

 

 

 

second intervals

the length set during configuration of the

 

 

 

 

 

 

 

3

2

4

 

network.

 

 

 

 

 

 

 

 

 

Fieldbus

 

Error in user parameter data: The

 

 

 

 

 

 

 

 

 

Red flashing at 1/2

length/contents of the User Parameter data set

 

 

 

 

Diagnostics

during initialization of the module is not equal to

 

 

 

 

second intervals

 

 

 

 

 

the length/contents set during configuration of

 

 

 

 

 

 

 

 

 

 

 

 

the network.

 

 

 

 

 

Red flashing at 1/4

Error in initialization of the PROFIBUS

 

 

 

 

 

second intervals

communication ASIC.

PAGE 5 - 25

Loading...
+ 58 hidden pages