Fantech PLATINUM STAGE, ERV-WI 500, HRV-XI 450, ERV-XI 450 User Manual

1
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Your ventilation system should be installed in conformance with the appropriate provincial or state requirements or in the absence of such requirements with the current edition of the National Building Code, and / or ASHRAE’s “ good Engineering Practice”.
IMPORTANT -
PLEASE READ THIS
MANUAL BEFORE INSTALLING UNIT
to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, oper­ating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflow’s of the Heat / Energy Recovery Ventilators. It is always important to assess how the operation of any HRV/ERV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
NEVER - install a ventilator in a situation where its normal opera-
tion, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment!!!
Light Commercial
Heat/Energy Recovery Ventilator
C
HRV-XI 450 or ERV-XI 450ERV-WI 500
R
C
R
US
C
2
TABLE OF CONTENTS
TECHNICAL DATA
HRV-XI 450 ............................................................................................. 3
ERV-XI 450 ............................................................................................. 5
ERV-WI 500 ............................................................................................. 7
OPERATION
Modes Of Operation ......................................................................................9
Optional Remote Controls............................................................................. 9
INSTALLATION.................................................................................................. 10
Mounting the Unit ....................................................................................... 10
Location & Ducting....................................................................................... 11
Examples .......................................................................................... 14
Air Flow Balancing ...................................................................................... 16
MAINTENANCE ............................................................................................17
ELECTRICAL CONNECTIONS ........................................................................ 18
Limited Warranty
• The HRV-XI 450 heat recovery polypropylene core has a limited lifetime warranty.
• The ERV-XI 450 energy recovery enthalpy core has a limited 5 year warranty.
• The ERV-WI 500 energy recovery enthalpy wheel has a limited 1 year warranty.
• The HRV-XI 450 & ERV-XI 450 has a warranty that is limited to 5 years on parts and 7 years on the motor & the ERV-WI 500 has a warranty that is limited to 1 year on parts and 7 years on the motors each from the date of purchase, including parts replaced during this time period. If there is no proof of purchase available, the date associated with the serial number will be used for the beginning of the warranty period.
• The motors found in all Fantech HRV/ERV’s require no lubrication, and are factory balanced to prevent vibration and promote silent operation.
• The limited warranty covers normal use. It does not apply to any defects, malfunctions or failures as a result of improper installation, abuse, mishandling, misapplication, fortuitous occurrence or any other circumstances outside Fantech’s control.
• Inappropriate installation or maintenance may result in the cancellation of the warranty.
• Any unauthorized work will result in the cancellation of the warranty.
• Fantech is not responsible for any incidental or consequential damages incurred in the use of the ventilation system.
• Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area.
• Fantech reserves the right to supply refurbished parts as replacements.
• Transportation, removal and installation fees are the responsibility of the purchaser.
• The purchaser is responsible to adhering to all codes in effect in his area.
* This warranty is the exclusive and
only warranty in effect relative to the ventilation system and all other warranties either expressed or implied are invalid.
ASHRAE Standard 62-2001 defines acceptable ventilation rates for various applications.
Outdoor Air Requirements Examples
Application CFM per Person L/s per Person Coin-operated laundry 15 8 Cafeteria, Fast Food 20 10 Bars 30 15 Conference Room 20 10 Reception Area 15 8 Beauty Shop 25 13 Classroom 15 8 Libraries 15 8 Medical 15 8 Photo Studios 15 8 Living Areas
(residential) .35 air changes per hour but
not less than 15 cfm (7.5 L/s)
per person Autopsy Rooms – (0.5 cfm/Ft2 or 2.5 L/s m2) Locker Rooms – (0.5 cfm/Ft2 or 2.5 L/s m2) * Swimming Pools – (0.5 cfm/Ft2 or 2.5 L/s m2) Public Restrooms (cfm/wc or cfm/urimac) 50 25
* Call factory for details 1.800.565.548
3
POWER & WEIGHT
• Volts 115V Total
• Amperage 7.7 Amps Total
• Weight 140 Lbs
• Shipping Weight 180 Lbs
• Blowers 115V, 60 Hz, 3.85 Amps
• Phase Single Phase
HRV-XI 450
Light Commercial HRV
The HRV-XI 450 Heat Recovery Ventilation system (HRV) complements the energy efficiency of the modern building by filtering incoming fresh outdoor air before it enters the heat­recovery core where it is preheated by the outgoing, stale contaminated air. The HRV then distributes the preheated fresh filtered air throughout the building by direct ductwork installed specifically for the HRV or through the ductwork of a forced-air system.
APPLICATIONS INCLUDE:
• Class Rooms • Offices
• Retail Shops • Clinics
• Hair Salons • Animal Shelters
• Bars & Restaurants • Large Homes
SPECIFICATIONS
CASE 20 gauge galvanized steel. Baked powder coated paint,
grey. Insulated with 1" (25 mm) foil-face fiberglass insulation to prevent condensation. Two (2) drain connections 1/2" NPT.
BLOWERS Two ebm™ direct drive external rotor blowers with forward curved blades. Blowers come with permanently lubricated sleeves for smooth and quiet operation. Blowers come pre-wired with 4 speeds, three of which are available to the installer as standard. Blowers are electrically connected with a quick connect for quick and easy inspection of blowers.
CORES Two (2) modular polyproplene heat recovery cores configured for an efficient cross-flow ventilation. Each core is 12" x 12" (305 x 305 mm) with a 15" (380 mm) depth. Cores are manufactured using silicone to withstand extreme temperature variations. (Aluminum cores are optional.)
FILTERS Four (4) Washable Electrostatic Panel Type Air Filters, 11.75" (298mm) x 15" (380mm) x 0.25" (6mm)
MOUNTING Unit can be installed using the four (4) mounting brackets included. Brackets fasten to HRV (bolts provided) and to floor joists using wood screws, not provided. Unit may also be suspended by using the supplied brackets and threaded rod, not supplied, or placed on a platform.
CONTROLS Low voltage (24VAC) external dry contacts to activate high speed. External three (3) position switch for LOW/STAND BY/ MED continuous ventilation speeds.
DEFROST A preset 5 minute defrost sequence is activated at an outdoor air temperature of 23˚F (-5˚C) and lower. During the defrost sequence, the supply blower shuts down & the exhaust blower switches into high speed to maximize the effectiveness of the defrost strategy. The unit then returns to normal operation for 25 minutes, and continues cycle.
SERVICEABILITY Cores, filters and drain pans can be accessed easily from both sides of the HRV from hinged access panels. Cores conveniently slide out with only 15
"
(380mm) clearance. Blowers can be accessed from both sides of the HRV from fastened access panels. Blowers are easily removed by removing the access panel and sliding the motor plates out of the HRV. A quick connect allows for fast inspection of blowers.
C
C
US
R
OPTIONAL CONTROLS (WHITE ONLY)
• MDEH 1 – Mechanical Low Voltage Dehumidistat
• FD 15M – 15 Minutes Crank Timer
• AQS 1 – Air Quality Sensor
* External dry contacts (provided)
Heat Recovery Ventilator
FOR MORE INFORMATION CONTACT:
4
Unit: Date: Contractor: Project:
Dimensions
Airflow
HRV-XI 450 Light Commercial HRV
2.3"
(58mm)
0 35 71 106 142 177 212 248 283
2
1.8
1.6
1.4
1.2
14.0"
(355mm)
32.0"
(816mm)
Airflow (L/s)
High
* Med-High
MOUNTING HOLES(1/4-20UNC BOLT)
8.0"
(202mm)
8.0"
(202mm)
DRAIN CONNECTION 1/2 NPT
1.9"
(47mm)
497.6
447.8
398.1
348.3
298.6
0.75
0.7
0.65
ELECTRICAL BOX
to either the front or the back of the cabinet depending on port direction installer chooses)
(can be relocated in the field
22.0"
(556mm)
32.4"
(822mm)
1
0.8
0.6
0.4
Static Pressure (in WC)
0.2
0
0 50 100 150 200 250 300 350 400 450 500
Med
Low
Airflow (cfm)
* Med-High - Contact Factory for wiring info
248.8
199.0
149.3
Static Pressure (Pa)
99.5
49.8
0.0
0.6
Efficiency (%)
0.55
0.5
0.45 150 200 250 300 350 400 450 500
Airflow (cfm)
FOR MORE INFORMATION CONTACT:
POWER & WEIGHT
• Volts 115V Total
• Amperage 7.7 Amps Total
• Weight 140 Lbs
• Shipping Weight 180 Lbs
• Blowers 115V, 60 Hz, 3.85 Amps
• Phase Single Phase
ERV-XI 450
Light Commercial ERV
The ERV-XI 450 lowers demand on air conditioning systems. Air supplied from outdoors enters through the Energy Recovery Core where it transfers the heat and humidity to the exhaust air . The air supplied by the ERV-XI 450 is now cooler, dryer and more comfortable. The ERV-XI 450 distributes the pre-conditioned fresh filtered air throughout the building by direct ductwork installed specifically for the ERV or through the ductwork of a forced-air system.
APPLICATIONS INCLUDE:
• Class Rooms • Offices
• Retail Shops • Clinics
• Hair Salons • Animal Shelters
• Bars & Restaurants • Larger Homes
SPECIFICATIONS
CASE 20 gauge galvanized steel. Baked powder coated paint,
grey. Insulated with 1" (25 mm) foil-face fiberglass insulation to prevent condensation.
BLOWERS Two ebm™ direct drive external rotor blowers with forward curved blades. Blowers come with permanently lubricated sleeves for smooth, quiet operation. Blowers come pre-wired with 4 speeds, three of which are available to the installer as standard. Blowers are electrically connected with a quick connect for fast and easy inspection of blowers.
CORES Two (2) modular enthalpic energy recovery cores configured for an efficient cross-flow ventilation. Each core is 12" x 12" (305 x 305 mm) with a 15" (380 mm) depth.
FILTERS Four (4) Washable Electrostatic Panel Type Air Filters, 11.75" (298mm) x 15" (380mm) x 0.25" (6mm)
MOUNTING Unit can be installed using the four (4) mounting brackets included. Brackets fasten to ERV (bolts provided) and to floor joists using wood screws, not provided. Unit may also be suspended by using the supplied brackets and threaded rod, not supplied, or placed on a platform.
CONTROLS Low voltage (24VAC) external dry contacts to activate high speed. External three (3) position switch for LOW/STAND BY/ MED continuous ventilation speeds.
SERVICEABILITY Cores and filters can be accessed easily from both sides of the ERV from hinged access panels. Cores conveniently slide out with only 15"(380mm) clearance. Blowers can be accessed from both sides of the ERV from fastened access panels. Blowers are easily removed by removing the access panel and sliding the motor plates out of the ERV. A quick connect allows for fast inspection of blowers.
C
C
US
R
OPTIONAL CONTROLS (WHITE ONLY)
• FD 15M – 15 Minute Crank Timer
• AQS 1 – Air Quality Sensor
• MDEH – Dehumidistat
(read full description of control found under "optional remote control" in this manual)
Energy Recovery Ventilator
5
6
Dimensions
Airflow
ERV-XI 450 Light Commercial ERV
Unit: Date: Contractor: Project:
Airflow (L/s)
24 59 94 130 165 201 236 271
1.6
398.1
0.85
1.4
1.2
1
0.8
0.6
0.4
Static Pressure (in W.C.)
0.2
0
50 100 150 200 250 300 350 400 450 500
Low
High
* Med-High
Med
Airflow (cfm)
* Med-High - Contact Factory for wiring info
348.3
298.6
248.8
199.0
149.3
99.5
Static Pressure (Pa)
49.8
0.0
0.83
0.81
0.79
0.77
0.75
Efficiency (%)
0.73
0.71
0.69
0.67 150 200 250 300 350 400 450
Airflow (cfm)
Loading...