Fantech DB10 User Manual

fantech
Installation and Operation Manual
DB10 Kit
Pressure Sensing Switch
DB10 Kit Includes:
DB10 Pressure Sensing Switch, 1 pc 3’ Section of Tubing, 1 pc Grommet for Tubing, 1 pc Wire Nuts for Electrical Connection, 4 pcs
Item #: 412811
Rev Date: 040314
United States
10048 Industrial Blvd., Lenexa, KS, 66215 Tel.: 800.747.1762 • Fax: 800.487.9915
50 Kanalflakt Way, Bouctouche, NB, E4S 3M5 Tel.: 800.565.3548 • Fax: 877.747.8116
2
Note Warning /
Important
Information Technical
information
Practical tip
note
Read and Save these instructions for future reference.
Pressure Sensor Switch Operation
The DB10 is a positive pressure sensing switch that is used with a dryer exhaust booster fan. A booster fan is recommended where dryer output alone is insufficient to maintain adequate airflow in a long dryer exhaust duct run. The DB10 senses dryer operation and activates the booster fan from an independent electrical circuit (120VAC).
The electrical supply to the booster fan is connected in series through the DB10 switch. One end of a pressure tube is connected to a nipple on the switch, the other end of the tube is tapped into the dryer duct through a grommet. Within ten seconds of the dryer beginning operation, positive pressure in the duct causes the switch diaphragm to close, activating the electronic timer circuit. The timer directs power to the fan in consecutive five minute cycles, effectively providing continuous boost as long as the dryer is on. When the dryer finishes its operation, the fan will complete the five minute cycle that it had started before the dryer stopped and then it will begin one final clearing cycle of five minutes. This means that the fan will continue to run for between five and ten minutes after the dryer has stopped.
Installation Instructions
Step 1. Selecting Switch Location
The DB10 switch can be located anywhere along the dryer duct between the dryer and the fan. The switch is not intended for outside use. Locating the switch close to the booster fan is recommended as this will allow a short wiring connection between the switch and the fan.
The DB10 should be connected to an electrical wiring box (not included) as shown. The electrical box should be permanently attached to a wall or other building structure.
PRESSURE TUBE INSERTED 1/4" INTO DRILLED HOLE IN DRYER DUCT BEFORE ELBOW. TUBE MUST BE SEALED WITH GROMMET TO PREVENT LEAKAGE.
DB10
ELECTRICAL BOX
(NOT INCLUDED)
PRESSURE TUBE
RVF4XL EXTERIOR FAN
fantech
Step 2. Mount Switch
Switch must be positioned so that diaphragm is maintained in vertical plane.
Pressure Switch Diaphragm Positioning
Insert the DB10 conduit connector through a knock-out in the electrical box and secure with the nut as shown.
3
PRESSURE
TUBE
Step 3. Installing Grommet and Tubing
Note
Grommet should be mounted no more than 30 inches from the pressure switch in order to allow the tubing to reach from the switch to the duct.
GROMMET
DRYER EXHAUST DUCT WALL
PRESSURE TUBE INSERTED
1/4" INTO DRYER DUCT
First, drill a 3/8 inch diameter hole in the duct wall. Carefully insert the grommet into the hole. (Drilling a metal duct may produce burrs. Be careful not to be cut or pricked by the burrs or the duct.) Next, force one end of the tubing over the nipple on the switch. It may be necessary to use a lubricant in order to slide the tubing over the entire nipple.
Make a mark a distance of 1/2 inch from the other end of the tubing. Slide this end of the tubing through the center of the grommet up to the mark. Do not use a lubricant on this end of the tubing.
fantech
Loading...
+ 5 hidden pages