Fantech AEV 1000 Nstallation, Operation And Maintenance Manual

C
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
IMPORTANT - PLEASE READ THIS
AEV Series
Air Exchange Ventilator
MANUAL BEFORE INSTALLING UNIT
CAUTION -
tem will operate if connected to any other piece of mechanical equipement,i.e. a forced air furnace or air handler,operating at a higher static.After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflow’s of the Air Exchange Ventilator by using the balancing procedure found in this manual. It is always important to assess how the operation of any AEV may interact with vented combustion equipment (i.e. Gas Furnaces,Oil Furnaces,Wood Stoves,etc.).
NEVER - install a ventilator in a situation where its normal operation,lack of operation
or partial failure may result in the backdrafting or improper functioning of vented combus­tion equipment!!!
Before installation,careful consideration must be given to how this sys-
C
C
R
Your ventilation system should be installed in conformance with the appropriate provincial or state require­ments or in the absence of such requirements with the current edition of the National Building Code, and / or ASHRAE’ s “ good Engineering Pratice”.
AEV Models
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
AEV 1000
Fan Tech at
kitchen
U N L I M I T E D
::
accessories
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
The Best Limited W arranty in the Business
• The motors found in all Fantech AEV’s require no lubrication,and are factory balanced to prevent vibration and promote silent operation.
• The limited warranty covers normal use. It does not apply to any defects, malfunctions or failures as a result of improper installation,abuse, mishandling, misapplication,fortuitous occurrence or any other circumstances outside Fantech’s control.
• Inappropriate installation or maintenance may result in the cancellation of the warranty.
• Any unauthorized work will result in the cancellation of the warranty.
• Fantech is not responsible for any incidental or consequential damages incurred in the use of the ventilation system.
• Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area.
TABLE OF CONTENTS
TECHNICAL DATA
AEV Series ......................................................................................................................1
OPERATION ................................................................................................................................. 2
Modes Of Operation ................................................................................................................2
Optional Remote Controls..................................................................................................... 3
INSTALLATION............................................................................................................................ 4
Mounting the Unit ................................................................................................................... 4
Location & Ducting................................................................................................................... 5
Examples ..................................................................................................................... 7
Air Flow Balancing ................................................................................................................... 8
MAINTENANCE .....................................................................................................................11
TROUBLESHOOTING.............................................................................................................13
• Fantech reserves the right to supply refurbished parts as replacements.
• Transportation,removal and installation fees are the responsibility of the purchaser.
• The purchaser is responsible to adhering to all codes in effect in his area.
• The warranty is limited to 5 y parts and 7 years on the motor from the date of purchase,including par ts replaced during this time period.If there is no proof of purchase available, the date associated with the serial number will be used for the beginning of the warranty period.
* This warranty is the exclusive and only
warranty in effect relative to the ventilation system and all other warranties either expressed or implied are invalid.Please fill out the warranty registration and return it within two weeks of purchase or the warranty will be voided.
ears on
Sizining (Example) for maximum airflow normally required.
AEV’s are typicaly sized to be able to ventilate the whole house at a maximum of 1/3 of an air change per hour.To calculate this simply take the square footage of the home (including basement) multiply by the height of the ceiling to get cubic volume,and then multiply that by .005.
Example: SQFT of House 1100
Basement 1100
Total SQFT 2200
Height of ceiling x 8
Cubic volume 17600
x .005
Maximum airflow required (CFM) 88
* Always consult your local code for sizing requirements in your area.
Room classification Number of rooms CFM (L/s) CFM Required
Master bedroom x 20 cfm (10 l/s) = Basement yes or no = Bedrooms x 10 cfm (5 l/s) = Living room x 10 cfm (5 l/s) =
if yes add 20 cfm / 10 l/s if no = 0
Others x 10 cfm (5 l/s) = Kitchen x 10 cfm (5 l/s) =
Bathroom x 10 cfm (5 l/s) = Laundry room x 10 cfm (5 l/s) =
1 cfm = 0.47189 l/s 1 l/s = 3.6 m
3
/hr
Utility room
Fan Tech at
x 10 cfm (5 l/s) =
Total ventilation Requirements
kitchen
U N L I M I T E D
::
accessories
(add last column )
=
TECHNICAL DATA
C
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
Components
CASE - 22 gauge galvanized steel with powder coat paint, lined with strong top
quality insulation.
FILTER - Synthetic high quality filter for better indoor air quality and clean air .
UNIT CONTROLS - Case mounted rocker switches provide the following functions.
ON/OFF switch is to engage the operations of the ventilation system. At OFF position,the system can still achieve high speed from the remote dehumidistat or optional timer switch.LOW/MED switch is to control the continuous ventilation mode. At LOW speed, the system will be operating at its lowest ventilation requirement.At MED speed, the system will operate to meet building codes requirements according to sizing and design conditions.
REMOTE OVERRIDE -24 volts (low voltage) remote switching circuit for high speed
operation to reduce the humidity level in the dwelling.This is archieved by a dehumidistat,an optional timer switch or any indoor air quality (IAQ) remote sensor
BLOWERS - The motors are factory-balanced to prevent vibrations,providing
greater comfort without noise pollution.
-Fans equipped with motors of insulation class “B”
- The motors are completely sealed , keeping out moisture, dust and lint.
- The motors feature maintance-free bearings and are the most dependable and efficient on the market.
- Built-in thermocontact prevents overheating
- Increased corrision protection
AEV Series Performance Data
Airflow Cap.L/s (cfm)
Model
AEV 1000 49 (104) 38 (60) 20 (42)
High
Med Low
AEV Series Electrical Data
Model Volts Amp Rating
AEV 1000 115 V 0.6 A
All of the AEV models are 120V unless specified otherwise.
C
C
R
US
Dimensions
Fan Tech at
kitchen
U N L I M I T E D
::
accessories
1
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
OPERATION
An Air Exchanger Ventilator (AEV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. During the winter months,the incoming cold fresh air is warmed by mixing it with return air before it is supplied to the home. During summer months when the indoor space is air conditioned,the AEV will help in cooling the incoming fresh air with the stale air that is being exhausted.
Fantech AEV’s are designed to run continuous or on intermittent,giving the homeowner complete control over their air quality. Continuous low speed ventilation is recommended,which will help eliminate carbon dioxide, voc’s and other gases as well as freshen up the home.Intermittent high speed ventilation can be obtained through a variety of optional remote controls found in this manual (page 3 ).Below are some examples of seasonal operation of an AEV.
Winter:
Humidity control is very important during the winter months. This is when problems will be most apparent since condensation on the windows will often occur. The colder the outside temperature,the greater the risk of con­densation in the home.The average relative humidity should be maintained between (30-60) to avoid condensa­tion.Low speed continuous ventilation with high speed override is recommended.
Spring:
Temperatures are more moderate and become warmer each day. To keep the humidity and temperature uniform, set the dehumidistat higher and the switch on the AEV to standby.
Summer:
The air is sometimes hot and humid. To stop the warm humid air from entering,set the dehumidistat at its high­est level and the switch on the AEV to standby.
Fall:
Rain and rapid temperature changes make it difficult to control the internal humidity level and may result in con­densation on the windows.A remote dehumidistat may help give greater control over the inside environment.
NOTE:Some products may not be exactly as illustrated in the Installation,Operation and Maintenance Manual. Fantech Inc. reserves the right to modify,at any time and without notice, any or all of its products’ features,designs, components
and specifications,to maintain their technological leadership position.
2
Fan Tech at
kitchen
U N L I M I T E D
::
accessories
OPERATION (CON’T)
OPTIONAL REMOTE CONTROLS
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
PRACTICAL TIPS
To avoid window condensation:
It is not necessary to change the humidity control every day.Monitor the average weekly temperature or experiment with various settings until you find a level that is comfortable for you. Adjust the control when needed.
Dehumidistat I
The wall mount dehumidistat monitors the humidity level in the area it is installed.When the humidity level rises above the desired set-point, the AEV will activate to high speed/override mode. Once the humidity level returns to desired condition, the unit will return to the normal mode. 2 low voltage wires required for operation.
Air Quality Sensor
The wall mount Air Quality Sensor (AQS) monitors indoor air quality and activates the override mode when carbon monoxide,formaldehyde,benzene, volatile organic compounds and other pollutants are detected. The unit will then return to normal mode once the air pollutants are reduced to a pre-determined lower level. Three low voltage wires are required for operation with transformer
* This control is not a warning device.
* All controls are low voltage. 18 to 24 gauge wire is recommended.
Fan Tech at
kitchen
U N L I M I T E D
::
accessories
3
Loading...
+ 10 hidden pages