AEV Series
Air Exchange Ventilator
MANUAL BEFORE INSTALLING UNIT
CAUTION -
tem will operate if connected to any other piece of mechanical equipement,i.e. a forced air
furnace or air handler,operating at a higher static.After installation, the compatibility of the
two pieces of equipment must be confirmed by measuring the airflow’s of the Air Exchange
Ventilator by using the balancing procedure found in this manual.
It is always important to assess how the operation of any AEV may interact with vented
combustion equipment (i.e. Gas Furnaces,Oil Furnaces,Wood Stoves,etc.).
NEVER - install a ventilator in a situation where its normal operation,lack of operation
or partial failure may result in the backdrafting or improper functioning of vented combustion equipment!!!
Before installation,careful consideration must be given to how this sys-
C
C
R
US
Your ventilation system should be installed in conformance with the appropriate provincial or state requirements or in the absence of such requirements with the current edition of the National Building Code, and /
or ASHRAE’ s “ good Engineering Pratice”.
AEV Models
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
AEV 1000
Fan Tech at
kitchen
U N L I M I T E D
::
accessories
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
The Best
Limited W arranty
in the Business
• The motors found in all Fantech AEV’s
require no lubrication,and are factory
balanced to prevent vibration and
promote silent operation.
• The limited warranty covers normal use.
It does not apply to any defects,
malfunctions or failures as a result of
improper installation,abuse, mishandling,
misapplication,fortuitous occurrence or
any other circumstances outside
Fantech’s control.
• Inappropriate installation or
maintenance may result in the
cancellation of the warranty.
• Any unauthorized work will result in
the cancellation of the warranty.
• Fantech is not responsible for any
incidental or consequential damages
incurred in the use of the ventilation
system.
• Fantech is not responsible for providing
an authorized service centre near the
purchaser or in the general area.
• Fantech reserves the right to supply
refurbished parts as replacements.
• Transportation,removal and installation
fees are the responsibility of the purchaser.
• The purchaser is responsible to adhering
to all codes in effect in his area.
• The warranty is limited to 5 y
parts and 7 years on the motor from the
date of purchase,including par ts replaced
during this time period.If there is no
proof of purchase available, the date
associated with the serial number will be
used for the beginning of the warranty
period.
* This warranty is the exclusive and only
warranty in effect relative to the ventilation
system and all other warranties either
expressed or implied are invalid.Please fill
out the warranty registration and return it
within two weeks of purchase or the
warranty will be voided.
ears on
Sizining (Example) for maximum airflow normally required.
AEV’s are typicaly sized to be able to ventilate the whole house at a maximum of 1/3 of an
air change per hour.To calculate this simply take the square footage of the home (including
basement)
multiply by the height of the ceiling to get cubic volume,and then multiply that by .005.
Example:SQFT of House1100
Basement1100
Total SQFT2200
Height of ceilingx 8
Cubic volume17600
x .005
Maximum airflow required (CFM)88
* Always consult your local code for sizing requirements in your area.
Room classificationNumber of roomsCFM (L/s)CFM Required
Master bedroomx 20 cfm (10 l/s)=
Basementyes or no=
Bedroomsx 10 cfm (5 l/s)=
Living roomx 10 cfm (5 l/s)=
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
Components
CASE- 22 gauge galvanized steel with powder coat paint, lined with strong top
quality insulation.
FILTER- Synthetic high quality filter for better indoor air quality and clean air .
UNIT CONTROLS - Case mounted rocker switches provide the following functions.
ON/OFF switch is to engage the operations of the ventilation system.
At OFF position,the system can still achieve high speed from the
remote dehumidistat or optional timer switch.LOW/MED switch is to
control the continuous ventilation mode. At LOW speed, the system
will be operating at its lowest ventilation requirement.At MED speed,
the system will operate to meet building codes requirements according
to sizing and design conditions.
REMOTE OVERRIDE -24 volts (low voltage) remote switching circuit for high speed
operation to reduce the humidity level in the dwelling.This is archieved
by a dehumidistat,an optional timer switch or any indoor air quality
(IAQ) remote sensor
BLOWERS- The motors are factory-balanced to prevent vibrations,providing
greater comfort without noise pollution.
-Fans equipped with motors of insulation class “B”
- The motors are completely sealed , keeping out moisture, dust and
lint.
- The motors feature maintance-free bearings and are the most
dependable and efficient on the market.
- Built-in thermocontact prevents overheating
- Increased corrision protection
AEV Series Performance Data
Airflow Cap.L/s (cfm)
Model
AEV 100049 (104) 38 (60) 20 (42)
High
MedLow
AEV Series Electrical Data
ModelVoltsAmp Rating
AEV 1000115 V0.6 A
All of the AEV models are 120V unless specified otherwise.
C
C
R
US
Dimensions
Fan Tech at
kitchen
U N L I M I T E D
::
accessories
1
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
OPERATION
An Air Exchanger Ventilator (AEV) is designed to provide fresh air into a building while exhausting an equal amount of stale air.
During the winter months,the incoming cold fresh air is warmed by mixing it with return air before it is supplied to the home.
During summer months when the indoor space is air conditioned,the AEV will help in cooling the incoming fresh air with the
stale air that is being exhausted.
Fantech AEV’s are designed to run continuous or on intermittent,giving the homeowner complete control over their air quality.
Continuous low speed ventilation is recommended,which will help eliminate carbon dioxide, voc’s and other gases as well as
freshen up the home.Intermittent high speed ventilation can be obtained through a variety of optional remote controls found in
this manual (page 3 ).Below are some examples of seasonal operation of an AEV.
Winter:
Humidity control is very important during the winter months. This is when problems will be most apparent since
condensation on the windows will often occur. The colder the outside temperature,the greater the risk of condensation in the home.The average relative humidity should be maintained between (30-60) to avoid condensation.Low speed continuous ventilation with high speed override is recommended.
Spring:
Temperatures are more moderate and become warmer each day. To keep the humidity and temperature uniform,
set the dehumidistat higher and the switch on the AEV to standby.
Summer:
The air is sometimes hot and humid. To stop the warm humid air from entering,set the dehumidistat at its highest level and the switch on the AEV to standby.
Fall:
Rain and rapid temperature changes make it difficult to control the internal humidity level and may result in condensation on the windows.A remote dehumidistat may help give greater control over the inside environment.
NOTE:Some products may not be exactly as illustrated in the Installation,Operation and Maintenance Manual.
Fantech Inc. reserves the right to modify,at any time and without notice, any or all of its products’ features,designs, components
and specifications,to maintain their technological leadership position.
2
Fan Tech at
kitchen
U N L I M I T E D
::
accessories
OPERATION (CON’T)
OPTIONAL REMOTE CONTROLS
Call 1-800-667-8721 anywhere in the US and Canada - www.kitchensource.com
PRACTICAL
TIPS
To avoid window
condensation:
• It is not necessary to change
the humidity control every
day.Monitor the average
weekly temperature or
experiment with various
settings until you find a level
that is comfortable for you.
Adjust the control when
needed.
Dehumidistat I
The wall mount dehumidistat monitors the humidity level in
the area it is installed.When the humidity level rises above the
desired set-point, the AEV will activate to high speed/override
mode. Once the humidity level returns to desired condition,
the unit will return to the normal mode.
2 low voltage wires required for operation.
Air Quality Sensor
The wall mount Air Quality Sensor (AQS) monitors indoor
air quality and activates the override mode when carbon
monoxide,formaldehyde,benzene, volatile organic
compounds and other pollutants are detected. The unit will
then return to normal mode once the air pollutants are
reduced to a pre-determined lower level.
Three low voltage wires are required for operation with
transformer
* This control is not a warning device.
* All controls are low voltage. 18 to 24 gauge wire is recommended.