FAGOR FE-24EB, FE-24EN User Manual

N51J015F1-00
USER INSTRUCTIONS
AND
TECHNICAL INSTRUCTIONS
FE-24E // FE-27E
TTo Domestic Hot W
o Domestic Hot W
FE-24E
Minimum 7.6 kW (25,932.26 Btu/h) Maximum 23.7 kW (80,867.71 Btu/h)
FE-27E
Minimum 7.8 kW (26,614.69Btu/h) Maximum 27 kW (92,127.78Btu/h)
T
T
o Central Heating:
o Central Heating:
FE-24E
Minimum 7.6 kW (25,932.26 Btu/h) Maximum 23.7 kW (80,867.71 Btu/h)
FE-27E
Minimum 7.8 kW (26,614.69 Btu/h) Maximum 27 kW (92,127.78 Btu/h)
BOILER OUTPUT
BOILER OUTPUT
EC-TYPE EXAMINATION CERTIFICATE
PIN0099BN794 (FE-24E) PIN0099BO808 (FE-27E)
2
The compliance with a British Standard does not, of itself, confer immunity from legal obligations. In particu­lar the installation of this appliance must be in accordance with the relevant requirements of the Gas Safety(Installation and Use) Regulations 1984 as amended, current IEE Wiring Regulations, local Building Regulations, Building Standards (Scotland)(Consolidation) and byelaws of the local Water Company. Health and Safety Document No. 635 (Electricity at Work Regulation). It should in accordance with the relevant rec­ommendations of the following British Standards.
BS 6798:1987 Specifications for installation of gas fired hot water boilers of rated input not exceeding 60 kW BS 5449:1990 Central Heating for Domestic Premises. BS 5546:1990 Installation for gas hot water supplies for domestic purposes. BS 5440:1990 Flues and Ventilation for gas appliances of rated input not exceeding 60 kW: Flues. BS 5440:1990 Flues and Ventilation for gas appliances of rated input not exceeding 60 kW: Air Supply. BS 6891:1988 Installation of low pressure gas pipework installations up to 28 mm (R1)
To ensure that the installation will perform to the highest standards, the system and components should con­form to any other relevant British Standards in addition to those mentioned in the instructions.
The appliance is not suitable for external installation.
USER INDEX
Pág.
1.- CONTROL PANEL 4
2.- PREPARING THE BOILER FOR SERVICE 4
3.- USER INSTRUCTIONS 5
4.- MAINTENANCE 5
5.- PRECAUTION AGAINST FREEZING 6
6.- ANTI PUMP SEIZURE DEVICE 6
7.- FAULT CODES 6
INSTALLER INDEX
8.- HOMOLOGATION CERTIFICATE 7
9.- DESCRIPTION OF THE APPLIANCE 8 *Principal components 8
*Operation and safety controls 8
10.-TECHNICAL DATA 9
11.-FUNCTIONAL DIAGRAMS 10 *Gas and water system 10
*Electrical circuit diagrams 10
12.-DIMENSIONS AND CONNECTION DETAILS 11
13.-HYDRAULIC SYSTEM CHARACTERISTICS 11 *Domestic hot water 11
*Central heating 11
14.-INSTALLATION OF THE BOILER 12
15.-Ø 60-100 mm HORIZONTAL CONCENTRIC COMBUSTION PRODUCT EXTRACTION AND AIR INTAKE 13
16.-Ø 80-125 mm HORIZONTAL CONCENTRIC COMBUSTION PRODUCT EXTRACTION AND AIR INTAKE 14
17.-Ø 80 mmTWIN-PIPE COMBUSTION PRODUCT EXTRACTION AND AIR INTAKE 15
18.-80-125 mm VERTICAL CONCENTRIC COMBUSTION PRODUCT EXTRACTION AND AIR INTAKE. 16
19.-ELECTRICAL CONNECTIONS 17 *Connection of a room thermostat (optional) 17
20.-CONTROL PANEL 17
21.-PREPARING THE BOILER FOR SERVICE 18
22.- USER INSTRUCTIONS 18
23.-MAINTENANCE 19
24.-PRECAUTION AGAINST FREEZING 20
25.-ANTI PUMP SEIZURE DEVICE 20
26.-GAS CHANGE 21
27.-FAULT CODES 22
28.-FAULT FINDING 23
4
2.- COMMISSIONING THE BOILER
1.- CONTROL PANEL
USER
FE-24E
5
6
7
1
2
3
4
1.- Digital Display
2.- Heating temperature selector
3.- D.H.W temperature selector
4.- Main control switch and reset
5.- Boiler ON indicator light
6.- Burner on indicator light
7.- Reset indicator light
Connect the boiler to a 230V ~50 Hz mains supply. VERY IMPORTANT: before turning the boiler on
make sure that the installation has been filled.
Domestic hot water
Turn on the cold water stopcock beneath the boiler. Fill the unit by turning on the various hot water taps
in the installation.
Make sure that the assembly is completely airtight
and watertight.
The installation of a scale reducer/water softener is
recommended in hard water areas
To increase the hot water temperature, reduce the flow of water at the hot water tap. This may be nec­essary in winter months.
Central heating system
The correct installation is to be carried out as follows:
Open the radiator air vents.
With the stopcock on and domestic cold water going through to the boiler, fill the central heating sys­tem by opening the filling tap provided by your installer.
Close the air vents off once water starts coming out of each of them.
Close the filling tap when the pressure gauge exceeds the pressure of 1.3 bar. Max = 1.5 bar.
By turning the main control switch to the winter set­ting . When the pump works the pressure in the dig­ital display increases.
Vent the central heating system once more. Then
let the pressure in the system settle at 1.3 bar. Max =
1.5 bar.. Make sure that there are no leaks in the installation. Make sure that the heating system is completely
full and vented. The pressure gauge should show between 1.3 and 1.5 bar with cold water in the heat­ing system.
Make sure that the boiler is wired to the correct volt-
age.
Make sure that the combustion flue outlet is not
restricted.
Gas circuit
Turn on the gas stopcock to the installation. Check that the whole gas circuit and gas connec-
tions to the boiler are airtight.
Settings
Before leaving the factory the boiler is pre-set in
accordance with the information on the adhesive data plate, and therefore needs no further adjustment. Should the type of gas need to be changed, check with the corresponding section.
5
3.- USERS INSTRUCTIONS
Domestic hot water service.
Turn the main control switch in the summer setting in order to turn the boiler on , see the figure below (the green light turns on). At that moment the boiler will be ready to supply domestic hot water whenever there is a demand for it.
When you turn on any of the hot taps the boiler will automatically come on with the pilot light switching on first of all followed by the burner. A water temperature of between 35° and 60° C can be selected by turning the domestic hot water temperature regulating knob.
When the D.H.W. temperature regulating knob is turned the digital display will show the values of the temperature.
Hot water and central heating service.
Turn the switch to the winter setting . The burner will automatically fire up if the clock and/or the room­thermostat are calling for heat. A temperature of between 60° and 85° C can be selected by turning the heating temperature regulating knob. This will stay on until it achieves the temperature selected either in the room thermostat or in the boiler itself.
Whenever domestic hot water is required when it is at the central heating setting, the boiler is designed to give priority to the supply of domestic hot water, with the central heating on hold, until the demand for domestic hot water ceases. When the D.H.W. tem­perature regulating knob is turned the digital display will show the values of the temperature.
Switching off the boiler.
Turn the main switch to the setting O.
Reset of the boiler.
This unit has a built-in reset indicator. Whenever
any fault is detected in the ignition process, the boil­er goes to lock out and the reset indicator switches on and the fault code is shown in the display.
To reset the boiler turn the main switch to position
O. The reset indicator should then turn off.
When the system pressure either falls down to 0.6 bar or goes over 2.8 bar, the display will shown F-3. It needs to fill it up to 1.3-1.5 bar (when system cold).
IMPORTANT: If the boiler has not been used for a length of time, or a new gas bottle is connected, the unit could lock out due to the presence of air in the pipes. Should this happen, the ignition procedure should be repeated until the gas circuit is cleared of all air in the gas supply.
USER
Check the gas connections and make sure that the gas is coming into the boiler (that the gas tap is open) Make sure that the heating system is completely full and vented. The pressure gauge should show between
1.3 and 1.5 bar with cold water in the heating system. Make sure that the electricity supply to the boiler is switched on.
6
4.- FROST PROTECTION
5.- ANTI PUM SEIZURE DEVICE
6.- FAULT CODES
Should a fault develop within the boiler (diagnostic), the P.C.B. will diagnose the possible cause via the reset indicator light (Red Neon) and the digital display. The fault will be shown in the display.
Each fault code begins with an “F” fol­lowed by a number. Ranging from 1 - 13. To reset the fault use the reset switch (4) (see Control Panel page 4)
The boiler has an frost protection security system.
IMPORTANT: the boiler must be electrically supplied and gas connected for this to operate.
Frost protection
When the heating thermistor detects a temperature of 6ºC, only the pump will switch and will continue to run until a temperature of 9ºC is obtained.
If the temperature drops to 3ºC, the boiler will start on minimum power until the temperature of 20ºC is obtained.
NOTE: If the boiler is not to be used for a long peri­od drain the heating installation using the valve (Z) beneath the boiler and the D.H.W. installation.
The D.H.W circuit must be drained down as follows:
Turn off the cold water supply. Open all the hot water outlet taps in the installation
(at least one tap should be found at a level lower than the boiler).
Release the tap to drain the flow switch to allow air
to come in and for the stored water in the boiler to be able to leave.(see figure)
When the operation is finished, close the hot water
outlet taps and the draining tap.
To put the boiler back into service, open the cold
water inlet tap.
When the boiler is not being used, the pump will auto­matically run for one minute every 24 hours to pre­vent seizure. TO ENSURE OPERATION OF THIS DEVICE ELECTRICAL SUPPLIES MUST BE ON.
If the pump jammed when the appliance is turned back on, consult your installer or service engineer.
USER
Z
NUMBER OF 1 SEC
‘FLASHES’
FAULT
1
Lack of gas or ignition problems; Flame supervision failure Burner on but flame Indicator Off; H L
2
Air Pressure Switch Failure
3
If the central heating pressure drops below 0.6 bar or gets above 2.8 bar , the boiler goes to lock out
4
The overheat thermostat blocks out the boiler
7.- CERTIFICATE
INSTALLER
Loading...
+ 16 hidden pages