EVCO S.p.A. | Code 104RS235E104 | Page 1 of 10 | PT 07/14 | version 1.0
EVRS225 & EVRS235
Controllers in split version for refrigerated display cases, counters in butcher’s shop and sweet counters
EN ENGLISH
DIMENSIONS AND INSTALLATION
User interface dimensions and installation
The dimensions are expressed in mm (in); panel installation is envisioned, with elastic retainer wings (det. A).
For the dimensions and installation of the control module, see page 10.
38,0
(1,496)
28.0
(1.102)
1detail A
2
180,0 (7,086)
drilling templ ate
138,0 (5,433)
29,0 (1,141)
To facilitate removal f the user interface, slightly smooth the internal longitudinal edges of the drilling template before
installation (det. B and C).
detail B
detail C
detail C
detail B
ELECTRIC CONNECTION
Electric connection
EVRS225 & EVRS235
User interface
24232221
PWM output
gnd
third input
evap.
cabinet
port for
remote
+
indicator
(on request)
P4 = 1, 2 o 3P4 = 0
evap.
cabinet
(config.)
cond.
(config.)
port for
remote
indicator
(on request)
2525262627272828292930303131333332323435 36 3734
MODBUS TTL port
EVRS225 & EVRS235
Control module
21 22 23 24
K3
K4
max. 20 A
20
19
13
14
3
4
evap. fan
defrosting
17
15
789
6165
compressor
alarm
cabinet light
(config.)
(config.)
18
earth
equipment
phaseK1 K5K2
neutral
earth
power supply
IMPORTANT
Read this document thoroughly before installation and before use of the device and follow all recommendations;
keep this document with the device for future consultation.
Only use the device in the way described in this document;
do not use the same as a safety device.
The device must be disposed of in compliance with
local standards regarding the collection of electric
and electronic equipment.
1DIMENSIONS AND INSTALLATION
1.1Installation warnings
-the thickness of the panel on which the user interface is
to be installed must be between 0.8 and
2.0 mm (0.031 and 0.078 in)
-make sure that the device work conditions (temperature of use, humidity, etc.) lie within the limits indicated; see chapter 13
-do not install the device near to any heat sources (heating
elements, hot air ducts etc.), equipment containing
powerful magnets (large diffusers, etc.), areas affected
by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or shocks.
-any metal parts in proximity of the control module must
be at a distance such that they do not compromise the
safety distances.
-in compliance with Safety Standards, the device must
be installed correctly and in a way to protect against
any contact with electric parts; all parts that ensure
protection must be fixed in a way that they cannot be
removed without the use of tools.
2ELECTRIC CONNECTION
2.1Warnings for the electric connection
-do not use electric or pneumatic screwdrivers on the
device terminal board
-if the device has been taken from a cold to hot place,
humidity could condense inside; wait about 1 hour before powering it
-make sure that the power supply voltage, the frequency and the operational electric power of the device, correspond with those of the local power supply;
see chapter 13
-disconnect the device power supply before proceeding
with any type of maintenance
-position the power cables as far away as possible from
the signal cables
-for repairs and information regarding the device, contact the EVCO sales network.
3USER INTERFACE
3.1Preliminary notes
Operating Statuses:
-“on” state (the device is powered and is on: the regulators can be switched on)
-“stand-by” status (the device is powered but is switched
off via software: the regulators are switched off; the
possibility to manually switch on/switch off the cabinet
light or auxiliary output depends on parameter u2)
-the “off” status (the device is not powered).
Hereafter, with the word “start-up” means the passage from
“stand-by” status to “on” status; the word “shutdown” means
the passage from “on” status to “stand-by” status.
When the power is switched back on, the device displays the
status that it was in at the time it was disconnected.
3.2Device switch-on/off in manual mode
Operating Statuses:
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 2 s: the LED will switch
off/on.
Using the digital inputs it is also possible to remotely switch
on/off the device.
3.3The display
If the device is switched on, during normal operation, the
display will show the magnitude established with P5, except
during defrosting, when the device will show the temperature established with parameter d6.
If the device is switched off, the display will be switched off.
3.4Cabinet temperature display (if parameter P4
is set at 0, 1 or 2) or the temperature detected by the inlet air probe (if parameter P4
is set at 3)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“Pb1”.
EVCO S.p.A. | Code 104RS235E104 | Page 2 of 10 | PT 07/14 | version 1.0
4. Press and release the key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the magnitude established with parameter P5 or
do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
3.5Evaporator temperature display
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“Pb2”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the magnitude established with parameter P5 or
do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
If the evaporator probe is absent (parameter P3 = 0), the
label “Pb2” will not be displayed.
3.6Display of the condenser temperature (if
parameter P4 is set at1), of the temperature
detected by the display probe (if parameter
P4 is set at 2) or of the temperature detected by the outlet air probe (if the parameter P4 is set at 3)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“Pb3”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the magnitude established with parameter P5 or
do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
If the third input function is that of the digital input (parameter P4 = 0), the label “Pb3” will not be displayed.
3.7Display of CPT temperature
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“Pb4”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the magnitude established with parameter P5 or
do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
If the “multideck” function is not active (parameter P4 = 0,
1 or 2), la label “Pb4” will not be displayed.
3.8Activation/deactivation of “overcooling”
function
1. Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or
dripping is not in progress and that the evap. fan is off.
2. Hold the
key down for 4 s: the Overcooling LED will
light up.
During the “overcooling” function the working set point is
reduced by the temperature established with parameter r5;
the operation lasts for the amount of time established with
parameter r6.
During “overcooling” defrosting is never activated; if the
defrosting interval expires when the function is in progress,
defrosting will be activated at the end of the function.
3.9Defrosting activation in manual mode
1. Make sure that the keyboard is not locked and that no
other operation is in progress; ensure that the
“overcooling” function is not in progress
2. Hold the
key down for 4 s.
If the evaporator probe function is that of the defrosting
probe (parameter P3=1) and upon activation of defrosting,
the temperature of the evaporator is higher than that established with parameter d2, the defrosting function will not be
activated.
3.10Switch-on/off of the cabinet light in manual
mode (only if parameter u1 and/or parameter u11 is set at 0)
1. Make sure no procedures are in progress
2. Press and release the
key: the “AUX” LED will
switch on/off.
Using the door digital inputs it is also possible to switch on/
off the cabinet light by remote; see also parameter u2.
If parameter u1 is set at 0 (i.e. the utility managed by the
fourth output is the cabinet light) and parameter u11 is set at
2 (i.e. the utility managed by the fifth output is the auxiliary
output), holding the
key down for 2 s will cause the
switch-on/off of the “AUX” LED and of the auxiliary output.
3.11Demister heating elements switch-on (only
if the parameter u1 and/or parameter u11 is
set at 1)
1. Ensure that the device is switched on and that no other
procedure is in progress.
2. Hold the
key down for 2 s: the “AUX” LED will light
up and the heating elements will be switched on, both
for the amount of time established with parameter u6.
Manually switching off the demisting heating elements is not
permitted (that is, before the time established with parameter u6 expires).
3.12Switch-on/off of the auxiliary output in
manual mode (only if parameter u1 and/or
parameter u11 is set at 2)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
key: the “AUX” LED will
switch on/off.
Using the digital inputs it is also possible to remotely switch
on/off the auxiliary output.
If parameter u1 is set at 2 (i.e. the utility managed by the
fourth output is the auxiliary output) and parameter u11 is
set at 0 (i.e. the utility managed by the fifth output is the
cabinet light), holding the
key down for 2 s will cause
the switch-on/off of the “AUX” LED and of the cabinet light.
If the auxiliary output has been switched on manually, then
it can also be switched off manually (similarly, if the auxiliary output has been remotely switched on, then it can only
be switched off in the same manner); see also parameter
u2.
3.13Locking/unlocking the keyboard
To lock the keyboard:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 1 s:
the display will show “Loc”.
If the keyboard is locked, the following are not permitted:
-device switch-on/off in manual mode
-displays the cabinet temperature of the temperature
detected by the inlet air probe (with the procedure
indicated in paragraph 3.4)
-display of evaporator temperature (via the procedure
explained in paragraph 3.5)
-to display the condenser temperature, the temperature
detected by the display probe or the temperature detected by the outlet air probe (with the procedure indicated in paragraph 3.6)
-display of the CPT temperature (via the procedure indi-
cated in paragraph 3.7)
-activation/deactivation of “overcooling” function
-manual activation of defrosting
-manual switch on/off of the auxiliary output
-see information regarding the HACCP alarms
-cancellation of HACCP alarm list
-display of compressor operation hours
-cancellation of compressor operation hours
-set the working set point (with the procedure described
in 9.2).
-set the evaporator fan speed (via the procedure ex-
plained in paragraph 9.3)
The operations cause the display of the label “Loc” per 1 sec.
To unlock the keyboard:
1. Hold the
key and thee key down for 1 s: the
display will show the message “UnL” for 1 sec.
3.14Silencing the buzzer
To lock the keyboard:
1. Make sure no procedures are in progress
2. Press a key (the first pressing of the key will not cause
the effect associated with that key).
If the parameter u1 and/or the parameter u11 is set at 3
(i.e. the utility managed by the fourth output and/or the
utility managed by the fifth output is the alarm output) and
parameter u4 is set at 1, pressing the key will also cause
the deactivation of the output.
If parameter u9 is set at 0, the buzzer will not be activated.
4MULTIDECK
4.1Preliminary notes
If parameter P4 is set at 3, the temperature associated to
the regulation will mainly depend on the temperature detected by the inlet air probe and that detected by the air
outlet probe, herein called CPT temperature (Calculated
Product Temperature).
The formula for the calculation of the CPT temperature is:
CPT temperature= {[(value established with parameter P7)
x (temperature detected by the inlet air probe)] + [(100 value established with parameter P7) x (temperature detected by the outlet air probe)] : 100}.
5ENERGY SAVING
5.1Preliminary notes
Once the time you have set with parameter i10 has passed,
without activations of the door micro switch input (after the
cabinet temperature or CPT temperature has reached the
work set-point) the “energy saving” function is activated
(until the input is activated again).
During the “energy saving” function, the work set point is
increased by the temperature established with parameter
r4.
In case of analogue management, the evaporator fan is
switched on (if required) at the speed established with parameter F21; in case of digital management, the evaporator
fan is switched on in cyclic mode (parameter F13 establishes
the duration of fan switch off and parameter F14 that of
switch on.
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor), through parameters H01... H14 it is finally
possible to activate the “energy saving” function in real time
(EVRS235 model only).
6“HACCP” FUNCTION
6.1Preliminary notes
The device can memorise the following HACCP alarms:
-minimum temperature alarm (code “AL”)
-maximum temperature alarm (code “AH”)
-door micro switch input alarm (code “id”)
-power supply cut-off alarm (“PF code”; in EVRS235
model only).
EVRS225 can memorise up to 3 alarms (one per type);
EVRS235 can memorise up to 9 alarms, after which the
oldest alarm is overwritten.
The device supplies the following information for every alarm:
-the critical value
-the date and time at which the alarm occurs (EVRS235
model only)
-the duration of the alarm (from 1 min to 99 hours and
59 min, partial if the alarm is in progress).
Code Critical value
AL the minimum cabinet temperature or the minimum
CPT temperature during the alarm
AH the maximum cabinet temperature or the
maximum CPT temperature during the alarm
iD the maximum cabinet temperature or maximum
CPT temperature during any alarm of this type;
see also parameter i4
PF the cabinet temperature or the CPT temperature
when power supply is restored; see also parameters A10 and A12
EVRS225 updates the information regarding the the alarms
provided the critical value of the new alarm is more critical
than that stored or provided the information has already
been displayed.
The device stored the minimum temperature alarm on condition that the temperature associated to the alarm is that of
the cabinet or CPT (parameter A0 = 0).
if the device is switched off, no alarms will be stored.
The “HACCP” LED provides information regarding the storage status of the alarms; see paragraph 10.1.
6.2Display of HACCP alarm information
To begin the procedure:
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“LS”.
4. Press and release the
key:
-in the EVRS225 model, the display will show one
of the codes included in the table in paragraph 6.1.
-in the EVRS235 model, the display will show one of the
codes stated in the table in paragraph 6.1 followed by
a number the higher the number the older the alarm.
If the device does not have any alarms stored, the label
“LS” will not be displayed.
EVCO S.p.A. | Code 104RS235E104 | Page 3 of 10 | PT 07/14 | version 1.0
To select an alarm:
5. Press and release the
key or the key.
To see information regarding the alarm:
6. Press and release the
key: the HACCP LED will stop
flashing and remain on permanently and the display will
show, for example, the following information in succession:
Inform. Part
8.0 the critical value is 8.0 °C/8 °F
StA the display is about to show the date and time at
which the alarm occurs (EVRS235 model only)
y14 the alarm occurred in 2014 (continue...)
n03 the alarm occurred in the month of March (conti-
nue...)
d26 the alarm occurred on 26 March 2014 (continue...)
h16 the alarm occurred at 16:00 (continue...)
n30 the alarm occurred at 16:30
dur the display is about to show the alarm duration
h01 the alarm lasted for 1 hour (other data continues)
n15 the alarm lasted 1 hour and 15 min
code the alarm selected
the displays each piece of information for 1 s.
To exit the information sequence:
7. Press and release the
key: the display will show
the alarm selected.
To exit the procedure:
8. Exit the information sequence.
9.1 Press and release the
or key until the display
shows the magnitude established with parameter P5 or
do not operate for 60 sec.
Alternatively:
9.2 Press and release the
key.
6.3Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“rLS”.
4. Press and release the
5. Press and release the
key.
key or the key within
15 s to set “149”.
6. Press and release the
key or do not operate for
15 sec: the display will show a flashing “- - - -” for
4 sec and the “HACCP” LED switches off, after which
the device will exit the procedure.
If the device does not have any alarms stored, the label
“rLS” will not be displayed.
7COMPRESSOR OPERATING HOURS COUNT
7.1Preliminary notes
The device can memorise up to 999 comp. operating hours.
The parameter C10 establishes the number of operating
hours is higher than the limit at which the need for maintenance is signalled.
7.2Display of Compressor Operation Hours
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“CH”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the magnitude established with parameter P5 or
do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
7.3Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“rCH”.
4. Press and release the
5. Press and release the
key.
key or the key within
15 s to set “149”.
6. Press and release the
key or do not operate for
15 sec: the display will show “- - -” flashing for
4 sec, after which the device will exit the procedure.
8SYNCHRONISATION OF DEFROSTING PERI-
ODS (ONLY IF PARAMETER i0 IS SET AT 6)
8.1Preliminary notes
The activation of defrosting causes the activation of the
digital input (at maximum for the time established with
parameter d24 or until the conclusion of predripping).
If the digital input is connected in parallel to the digital input of
other devices configured in the same way, the activation of the
input caused the activation of defrosting in the other devices.
The devices start dripping simultaneously with the conclusion of the predripping of the last device to end the same.
9SETTINGS
9.1Setting the date, time and day of the week
(EVRS235 model only)
The date can be set in the day-month-year format; the
time in the hours-minutes format (24 h).
To access the procedure:
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“rtc”.
To set the year:
4. Press and release the
key: the display will show
“y” followed by the last two numbers of the year.
5. Press and release the
key or the key within
15 sec.
To set the month:
6. Press and release the
key when setting the year:
the display will show “n” followed by the number of the
month
7. Press and release the
key or the key within
15 sec.
To set the day:
8. Press and release the
key when setting the month:
the display will show “d” followed by the number of the
day.
9. Press and release the
key or the key within
15 sec.
To set the hour:
10. Press and release the
key when setting the day:
the display will show “h” followed by the number of the
hour.
11. Press and release the
key or the key within
15 sec.
To set the minute:
12. Press and release the
key when setting the hour:
the display will show “n” followed by the number of the
minute.
13. Press and release the
key or the key within
15 sec.
To set the day of the week:
14. Press and release the
key when setting the minute:
the display will show the first label available.
15. Press and release the
key or the key within
15 sec to set:
-“Mon” (Monday)
-“tuE” (Tuesday)
-“UEd” (Wednesday)
-“thu” (Thursday)
-“Fri” (Friday)
-“SAt” (Saturday)
-“Sun” (Sunday).
16. Press and release the
key: the device will exit the
procedure.
To exit the procedure before the operation is complete:
17. Do not operate for 60 sec (any changes will be saved).
9.2Setting the working set point
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
3. Press and release the
key: the LED will flash.
or key within
15 sec; see also parameters r1, r2 and r3
4. Press and release the
15 sec: the
LED will switch off after which:
key or do not operate for
-if the parameter F0 is set at 0, 1, 2, 3 or 4, the device
will exit the procedure
-if parameter F0 is set at 5, the device will access the
procedure to set the evaporator fan speed; see paragraph 9.3
To exit the procedure before the operation is complete:
5. Do not operate for 15 sec (any changes will be saved).
The working set point can also be set via parameter SP.
9.3Setting evaporator fan speed (intended as
percentage of max. speed and in case of analogue management)
1. Press and release the
set point: the
2. Press and release the
key while setting the work
LED will flash.
or key within
15 sec; see also parameters F15 and F16.
3. Press and release the
15 sec: the
LED will switch off and then the device
key or do not operate for
will exit the procedure.
To exit the procedure before the operation is complete:
5. Do not operate for 15 sec (any changes will be saved).
The evaporator fan speed can also be set through parameter F17.
9.4Setting the configuration parameters
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
key or the key within
15 s to set “-19”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
key and the key down for 4 s:
the display will show “SP”.
To select a parameter:
7. Press and release the
key or the key.
To set a parameter:
8. Press and release the
9. Press and release the
key.
key or the key within
15 sec.
10. Press and release the
key or do not operate for
15 sec.
To exit the procedure:
11. Hold down the
and keys for 4 sec and do not
operate for 60 sec (any changes will be saved).
After setting the parameters, suspend power supply flow to
the device.
9.5Restoring the Manufacturer’s Settings
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
key or the key within
15 s to set “149”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
key and the key down for 4 s:
the display will show “dEF”.
7. Press and release the
8. Press and release the
key.
key or the key within
15 s to set “1”.
9. Press and release the
key or do not operate for
15 sec: the display will show “dEF” flashing for
4 sec, after which the device will exit the procedure.
10. Cut the device power supply off.
To exit the procedure in advance:
11. Hold the and key down for 4 s during the procedure
(i.e. before setting “1”: Restore will not be performed).
Make sure that the manufacturer’s settings are appropriate
(see chapter 14).
10WARNING LIGHTS AND DIRECTIONS
10.1Signals
LED Part
compressor LED light
if the LED is on, then the compressor is on
if the LED is flashing:
-the working set point is in the process of being
set (via the procedure described in paragraph
9.2)
-a compressor protection will be in progress;
see parameters C0, C1, C2, C14, C15, C16
and i7
Defrost LED
If it is on:
-defrosting is in progress
-predripping will be in progress; see parameter
d16
if the LED is flashing:
-defrosting will be requested but a compressor
protection will be in progress; see the parameters C0, C1 and C2
-dripping will be in progress; see parameter d7
-the refrigerant fluid heating will be in progress;
see parameter d15
Evaporator fan LED light
If it is on:
-setting the evaporator fan speed will be in
progress (via the procedure explained in paragraph 9.3)
-the evaporator fan will be on
if the LED is flashing:
-evaporator fan standstill will be in progress;
see parameter F3
AUX auxiliary LED
If it is on:
-the cabinet light will have been switched on in
manual mode (only if parameter u1 and/or
parameter u11 is set at 0)
-the demister heating elements will be switched
on (only if the parameter u1 and/or parameter u11 is set at 1)
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.