EVCO S.p.A. | Codice 104RS200E214 | Page 1 of 8 | PT 24/13 | version 2.1
EVRS 200 range
Controllers in split execution for refrigerated display cases, ice-cream and sweet counters and plug ins.
EN ENGLISH
DIMENSIONS AND INSTALLATION
User interface dimensions and installation
The dimensions are expressed in mm (in); panel installation is envisioned, with elastic retainer wings (det. A).
For the dimensions and installation of the control module, see page 8.
dr il li ng t empl ate
To facilitate removal f the user interface, slightly smooth the internal longitudinal edges of the drilling template before
installation (det. B and C).
ELECTRIC CONNECTION
Electric connection
User interface
Third Input
Cabinet
Control module
Door micro switch/minutes f.2
TTI MODBUS port
In the EVRS205 model
Not available
Cabinet
Phase
Power supply neutral
Earth
Door micro switch/minutes f. 1
Door micro switch/minutes f. 2
IMPORTANT
Read this document thoroughly before installation and
before use of the device and follow all recommendations;
keep this document with the device for future consultation.
Only use the device in the way described in this document;
do not use the same as a safety device.
The device must be disposed of in compliance with
local Standards regarding the collection of electric
and electronic equipment.
1DIMENSIONS AND INSTALLATION
1.1Installation warnings
-the thickness of the panel on which the user interface is
to be installed must be between 0.8 and
2.0 mm (0.031 and 0.078 in)
-make sure that the device work conditions (temperature
of use, humidity, etc.) lie within the limits indicated;
see chapter 13
-do not install the device near to any heat sources (heating
elements, hot air ducts etc.), equipment containing
powerful magnets (large diffusers, etc.), areas affected
by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or shocks.
-any metal parts in proximity of the control module must
be at a distance such that they do not compromise the
safety distances.
-in compliance with Safety Standards, the device must
be installed correctly and in a way to protect against
any contact with electric parts; all parts that ensure
protection must be fixed in a way that they cannot be
removed without the use of tools.
2ELECTRIC CONNECTION
2.1Warnings for the electric connection
-do not use electric or pneumatic screwdrivers on the
device terminal board
-if the device has been taken from a cold to hot place,
humidity could condense inside; wait about 1 hour
before powering it
-make sure that the power supply voltage, the frequency
and the operational electric power of the device,
correspond with those of the local power supply; see
chapter 13
-disconnect the device power supply before proceeding
with any type of maintenance
-position the power cables as far away as possible from
the signal cables
-for repairs and information regarding the device, contact
the EVCO sales network.
3USER INTERFACE
3.1Preliminary notes
Operating Statuses:
-“on” state (the device is powered and is on: the regulators
can be switched on)
-“stand-by” status (the device is powered but is
switched off via software: the regulators are switched
off; the possibility to manually switch on/switch off
the cell light or auxiliary output depends on parameter u2)
-the “off” status (the device is not powered).
Hereafter, with the word “start-up” means the passage
from “stand-by” status to “on” status; the word “shutdown” means the passage from “on” status to “stand-by”
status.
When the power is switched back on, the device displays the status that it was in at the time it was disconnected.
3.2Device switch-on/off in manual mode
Operating Statuses:
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the key down for 2 s: the LED will switch off/on.
Using the digital inputs it is also possible to remotely switch
on/off the device.
3.3The display
If the device is switched on, during normal operation, the
display will show the cell temperature, except during
defrosting, when the device will show the temperature
established with parameter d6.
If the device is switched off, the display will be switched
off.
Evap. Fan
Defrosting
earth
Cabinet light
Alarm
(config.)
Equipment
(config.)
EVCO S.p.A. | Codice 104RS200E214 | Page 2 of 8 | PT 24/13 | version 2.1
3.4Evaporator temperature display
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“Pb2”.
4. Press and release the key
.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
6.2 Press and release the
key.
If the evaporator probe is absent (parameter P3 = 0), the
label “Pb2” will not be displayed.
3.5Condenser temperature display
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“Pb3”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
6.2 Press and release the
key.
If the third input function is that of the digital input (parameter
P4 = 0), the label “Pb3” will not be displayed.
3.6Activation/deactivation of “overcooling”
function
1. Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or
dripping is not in progress and that the evaporator fan
is off.
2. Hold the
key down for 4 s: the Overcooling LED will
light up.
During the “overcooling” function the working setpoint is
reduced by the temperature established with parameter r5;
the operation lasts for the amount of time established with
parameter r6.
During “overcooling” defrosting is never activated; if
the defrosting interval expires when the function is in
progress, defrosting will be activated at the end of the
function.
3.7Defrosting activation in manual mode
1. Make sure that the keyboard is not locked and that no
other operation is in progress; ensure that the
“overcooling” function is not in progress
2. Hold the
key down for 4 s.
If the evaporator probe function is that of the defrosting
probe (parameter P3=1) and upon activation of defrosting,
the temperature of the evaporator is higher than that
established with parameter d2, the defrosting function will
not be activated.
3.8Switch-on/off of the cell light in manual
mode (only if parameter u1
and/or parameter u11 is set at 0)
1. Make sure no procedures are in progress
2. Press and release the
key: the “AUX” LED will
switch on/off.
Using the door digital inputs it is also possible to switch on/
off the cell light by remote; see also parameter u2.
If parameter u1 is set at 0 (i.e. the utility managed by the
fourth output is the cabinet light) and parameter u11 is set
at 2 (i.e. the utility managed by the fifth output is the
auxiliary output), holding the
key down for 2 s will
cause the switch-on/off of the “AUX” LED and of the auxiliary output.
3.9Demister resistors switch-on (only if the
parameter u1 and/or parameter u11 is set at
1)
1. Ensure that the device is switched on and that no other
procedure is in progress.
2. Hold the
key down for 2 s: the “AUX” LED will
light up and the resistors will be switched on, both
for the amount of time established with parameter
u6.
Manually switching off the demisting resistors is not permitted
(that is, before the time established with parameter u6
expires).
3.10Switch-on/off of the auxiliary output in
manual mode (only if parameter u1 and/or
parameter u11 is set at 2)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
key: the “AUX” LED will
switch on/off.
Using the digital inputs it is also possible to remotely switch
on/off the auxiliary output.
If parameter u1 is set at 2 (i.e. the utility managed by the
fourth output is the auxiliary output) and parameter u11 is
set at 0 (i.e. the utility managed by the fifth output is the
cabinet light), holding the
key down for 2 s will cause
the switch-on/off of the “AUX” LED and of the cabinet
light.
If the auxiliary output has been switched on manually,
then it can also be switched off manually (similarly, if the
auxiliary output has been remotely switched on, then it
can only be switched off in the same manner); see also
parameter u2.
3.11Locking/unlocking the keyboard
To lock the keyboard:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 1 s:
the display will show “Loc”.
If the keyboard is locked, the following are not permitted:
-device switch-on/off in manual mode
-display of evaporator temperature (via the procedure
explained in paragraph 3.4)
-display of the condenser temperature (via the procedure
indicated in paragraph 3.5)
-activation/deactivation of “overcooling” function
-manual activation of defrosting
-manual switch on/off of the auxiliary output
-activation of operation for low of high percentage of
relative humidity and learning the kind of operation
-see information regarding the HACCP alarms
-cancellation of HACCP alarm list
-display of compressor operation hours
-cancellation of compressor operation hours
-changing the working setpoint (with the procedure
described in 9.1).
The operations cause the display of the label “Loc” per 1
sec.
To unlock the keyboard:
1. Hold the
key and thee key down for 1 s: the
display will show the message “UnL” for 1 sec.
3.12Silencing the buzzer
To lock the keyboard:
1. Make sure no procedures are in progress
2. Press a key (the first pressing of the key will not cause
the effect associated with that key).
If the parameter u1 and/or the parameter u11 is set at 3
(i.e. the utility managed by the fourth output and/or the
utility managed by the fifth output is the alarm output) and
parameter u4 is set at 1, pressing the key will also cause the
deactivation of the output.
If parameter u9 is set at 0, the buzzer will not be activated.
4OPERATION DUE TO LOW OR HIGH RELATIVE
HUMIDITY PERCENTAGE (ONLY IF PARAMETER
F0 IS ISET AT 5)
4.1Preliminary notes
During operation for low percentage of relative humidity, the
evaporator ventilator will be switched on if the compressor is
switched off (parameter F4 determines the amount of time
it is switched off while parameter F5 determines the amount
of time it is switched on).
During operation for a high percentage of relative humidity
the evaporator fan is always on.
4.2Activation of operation for low or high
percentage relative humidity in manual
mode.
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
and keys down for 4 s: the display will
show “rhL” (operation for low percentage of relative
humidity) or “rhH” (operation for high percentage of
relative humidity) for 10 sec.
To restore the normal display before the operation is
complete:
3. Press a key.
Activation of the operation for a low or high percentage of
relative humidity can be done using parameter F6.
If the parameter F0 is not set at 5, pressing the
and
keys will cause the display of the “- - -“ indication
for 1 s.
4.3Learning the type of operation in progress
1. Make sure no procedures are in progress
2. Press and release the and keys: the display
will show “rhL” (operation for low percentage of relative humidity) or “rhH” (operation for high percentage
of relative humidity) for 10 sec.
To restore the normal display before the operation is complete:
3. Press a key.
If parameter F0 is not set at 5, pressing the
and
keys will cause:
-the display of the message “- - - -“ for 1 sec if the
keyboard is not locked
-display of the label “Loc” for 1 sec if the keyboard is
locked..
5ENERGY SAVING
5.1Preliminary notes
Once the time you have set with parameter i10 has passed,
without activations of the door micro switch input (after the
cell temperature has reached the work set-point) the “energy saving” function is activated (until the input is activated
again).
During function “Energy Saving” the working setpoint is
increased of the temperature you have set with parameter
r4 and the evaporator fan is turned on cyclically, on condition
that parameter F0 has value 1 or 2 (parameter F13 sets the
time the fan remains turned off and parameter F14 the time
it remains turned on).
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor).
6“HACCP” FUNCTION
6.1Preliminary notes
The device can memorise the following HACCP alarms:
-minimum temperature alarm (code “AL”)
-maximum temperature alarm (code “AH”)
-door micro switch input alarm (code “id”)
The device supplies the following information for every
alarm:
-the critical value
-the duration of the alarm (from 1 min to 99 hours and
59 min, partial if the alarm is in progress).
Code Critical value
AL the minimum temperature of the cell during any
alarm of this type
AH the maximum temperature of the cell during any
alarm of this type
iD the maximum cell temperature during any alarm
of this type; see also parameter i4
The device stored the minimum temperature alarm on
condition that the temperature associated to the alarm is
that of the cell (parameter A0 = 0).
if the device is switched off, no alarms will be stored.
The device updates the information regarding the the alarms
provided the critical value of the new alarm is more critical
than that stored or provided the information has already
been displayed.
The “HACCP” LED provides information regarding the storage
status of the alarms; see paragraph 10.1.
6.2Display of HACCP alarm information
To begin the procedure:
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
4. Press and release the
or key to select “LS”.
key: the display will show
one of the codes included in the table in paragraph
6.1.
If the device does not have any alarms stored, the label
“LS” will not be displayed.
To select an alarm:
5. Press and release the
or key (to select, for
example, “AH”).
To see information regarding the alarm:
6. Press and release the
key: the HACCP LED will
stop flashing and remain on permanently and the display will show, for example, the following information
in succession (for example):
Inform. Part
8.0 the critical value is 8.0 °C/8 °F
dur the display is about to show the alarm duration
h01 the alarm lasted for 1 hour (other data continues)
n15 the alarm lasted 1 hour and 15 min
AH the alarm selected
the displays each piece of information for 1 s.
EVCO S.p.A. | Codice 104RS200E214 | Page 3 of 8 | PT 24/13 | version 2.1
To exit the information sequence:
7. Press and release the
key: the display will show
the alarm selected (in the example “AH”).
To exit the procedure:
8. Exit the information sequence.
9.1 Press and release the
or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
9.2 Press and release the
key.
6.3Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
4. Press and release the
5. Press and release the
or key to select “rLS”.
key.
or key within
15 s to set “149”.
6. Press and release the
key or do not operate for
15 sec: the display will show a flashing “- - - -” for
4 sec and the “HACCP” LED switches off, after which
the device will exit the procedure.
If the device does not have any alarms stored, the label
“rLS” will not be displayed.
7COMPRESSOR OPERATING HOURS COUNT
7.1Preliminary notes
The device can memorise up to 9.990 compressor operating
hours.
The parameter C10 establishes the number of operating
hours is higher than the limit at which the need for
maintenance is signalled.
7.2Display of Compressor Operation Hours
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
key or the key to select
“CH”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
6.2 Press and release the
key.
7.3Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
4. Press and release the
5. Press and release the
or key to select “rCH”.
key.
or key within
15 s to set “149”.
6. Press and release the
key or do not operate for
15 sec: the display will show “- - -” flashing for
4 sec, after which the device will exit the procedure.
8SYNCHRONISATION OF DEFROSTING
PERIODS (ONLY IF PARAMETER i0 AND/OR
PARAMETER i5 IS SET AT 6)
8.1Preliminary notes
The activation of defrosting causes the activation of
the digital input (at maximum for the time established
with parameter d24 or until the conclusion of
predripping).
If the digital input is connected in parallel to the digital input
of other devices configured in the same way, the activation
of the input caused the activation of defrosting in the other
devices.
The devices start dripping simultaneously with the conclusion of the predripping of the last device to end the
same.
9SETTINGS
9.1Setting the working setpoint
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
key: the LED will
flash.
3. Press and release the
or key within
15 sec; see also parameters r1, r2 and r3
4. Press and release the
15 sec: the
LED will switch off and then the device
key or do not operate for
will exit the procedure.
To exit the procedure before the operation is complete:
5. Do not operate for 15 sec (any changes will be saved).
The working setpoint can also be set via parameter
SP.
9.2Setting the configuration parameters
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 4s:the display will
show “PA”.
3. Press and release the
4. Press and release the
key.
or key within
15 s to set “-19”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
and keys down for 4 s:
the display will show “SP”.
To select a parameter:
7. Press and release the
or key.
To change a parameter:
8. Press and release the
9. Press and release the
key.
or key within
15 sec.
10. Press and release the
key or do not operate for
15 sec.
To exit the procedure:
11. Hold down the
and keys for 4 sec and do not
operate for 60 sec (any changes will be saved).
After changing the parameters, suspend power supply flow
to the device.
9.3Restoring the Manufacturer’s Settings
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
or key within
15 s to set “149”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
and keys down for 4 s:
the display will show “dEF”.
7. Press and release the
8. Press and release the
key.
or key within
15 s to set “1”.
9. Press and release the
key or do not operate for
15 sec: the display will show “dEF” flashing for
4 sec, after which the device will exit the procedure.
10. Cut the device power supply off.
To exit the procedure before the operation is complete:
11. Hold the and key down for 4 s during the procedure (i.e. before setting “1”:
Restore will not be performed).
Make sure that the manufacturer’s settings are appropriate
(see chapter 14).
10WARNING LIGHTS AND DIRECTIONS
10.1Signals
LED Part
compressor LED light
if the LED is on, then the compressor is on
if the LED is flashing:
-the working setpoint is in the process of being
changed (via the procedure described in paragraph 9.1)
-a compressor protection will be in progress;
see parameters C0, C1, C2, C14, C15, C16
and i7
Defrost LED
If it is on:
-defrosting is in progress
-predripping will be in progress; see parameter
d16
if the LED is flashing:
-defrosting will be requested but a compressor
protection will be in progress; see the parameters C0, C1 and C2
-dripping will be in progress; see parameter
d7
-the refrigerant fluid heating will be in progress;
see parameter d15
Evaporator fan LED light
If it is on:
-the evaporator fan will be on
if the LED is flashing:
-evaporator fan standstill will be in progress;
see parameter F3
AUX Auxiliary LED
If it is on:
-the cell light will have been switched on in
manual mode (only if parameter u1 and/or
parameter u11 is set at 0)
-the demister resistors will be switched on (only
if the parameter u1 and/or parameter u11 is
set at 1)
-the auxiliary output will have been switched
on in manual mode (only if parameter u1
and/or parameter u11 is set at 2)
-the door resistors will be switched on (only
and provided parameter u1 and/or parameter
u11 is set at 4)
-the neutral area operating resistors will be
activated (only if parameter u1 and/or parameter u11 is set at 5)
-the condenser fan will be on (only if parameter
u1 and/or parameter u11 is set at 6)
if the LED is flashing:
-the cell light will have been switched on in
remote mode; see parameters i0 and i5 (only
if parameter u1 and/or parameter u11 is set
at 0)
-the auxiliary output will have been switched
on in remote mode; see parameters i0 and i5
(only if parameter u1 and/or parameter u11
is set at 1)
-condenser fan switch-off delay will be in
progress; see parameter F12 (only if
parameter u1 and/or parameter u11 is set at
6)
HACCP HACCP LED
if it is on, all information regarding HACCP alarms
has not been displayed
if it is flashing, the device has stored at least one
new HACCP alarm
if it is off, all information regarding the HACCP
alarms has been displayed or the list of alarms has
been cancelled
maintenance LED
if on, compressor maintenance will be requested;
see parameter C10
“overcooling” LED
if it is on, the “overcooling” function will be in
function; see parameters r5 and r6
°C degree Celsius LED
if on, the temperatures will be displayed using the
degree Celsius grade unit of measurement; see
parameter P2
if flashing, the “energy saving” function is in progress
(with effect only on the compressor)
°Fdegree Fahrenheit LED
if on, the temperatures will be displayed using the
degree Fahrenheit grade unit of measurement;
see parameter P2
if flashing, the “energy saving” function is in progress
(with effect only on the compressor)
On/stand-by LED
if it is on, the device will be off (
“stand-by” state)
if it is off, the device will be on (“on” state)
10.2Signal Descriptions/Explanations
Code Part
rhL operation for a low percentage of relative humidity
in progress
rhH operation for a high percentage of relative humidity
in progress
Loc the keyboard is blocked; see paragraph 3.11
the work setpoint is blocked; see parameter r3
- - - the operation requested is not available
11ALARMS
11.1Alarms
Code Part
AL Minimum alarm temperatures (HACCP alarms)
Solutions:
-check the temperature associated to the
alarm; see parameters A0, A1 and A2
Main consequences:
-if parameter A0 is set at 0, the device will
store the alarm
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
AH Maximum temperature alarm (HACCP alarms)
Solutions:
-check the cell temperature; see parameters
A4 and A5
Main consequences:
-the device will memorise the alarm
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.