EVCO S.p.A. | Codice 104RS200E214 | Page 1 of 8 | PT 24/13 | version 2.1
EVRS 200 range
Controllers in split execution for refrigerated display cases, ice-cream and sweet counters and plug ins.
EN ENGLISH
DIMENSIONS AND INSTALLATION
User interface dimensions and installation
The dimensions are expressed in mm (in); panel installation is envisioned, with elastic retainer wings (det. A).
For the dimensions and installation of the control module, see page 8.
dr il li ng t empl ate
To facilitate removal f the user interface, slightly smooth the internal longitudinal edges of the drilling template before
installation (det. B and C).
ELECTRIC CONNECTION
Electric connection
User interface
Third Input
Cabinet
Control module
Door micro switch/minutes f.2
TTI MODBUS port
In the EVRS205 model
Not available
Cabinet
Phase
Power supply neutral
Earth
Door micro switch/minutes f. 1
Door micro switch/minutes f. 2
IMPORTANT
Read this document thoroughly before installation and
before use of the device and follow all recommendations;
keep this document with the device for future consultation.
Only use the device in the way described in this document;
do not use the same as a safety device.
The device must be disposed of in compliance with
local Standards regarding the collection of electric
and electronic equipment.
1DIMENSIONS AND INSTALLATION
1.1Installation warnings
-the thickness of the panel on which the user interface is
to be installed must be between 0.8 and
2.0 mm (0.031 and 0.078 in)
-make sure that the device work conditions (temperature
of use, humidity, etc.) lie within the limits indicated;
see chapter 13
-do not install the device near to any heat sources (heating
elements, hot air ducts etc.), equipment containing
powerful magnets (large diffusers, etc.), areas affected
by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or shocks.
-any metal parts in proximity of the control module must
be at a distance such that they do not compromise the
safety distances.
-in compliance with Safety Standards, the device must
be installed correctly and in a way to protect against
any contact with electric parts; all parts that ensure
protection must be fixed in a way that they cannot be
removed without the use of tools.
2ELECTRIC CONNECTION
2.1Warnings for the electric connection
-do not use electric or pneumatic screwdrivers on the
device terminal board
-if the device has been taken from a cold to hot place,
humidity could condense inside; wait about 1 hour
before powering it
-make sure that the power supply voltage, the frequency
and the operational electric power of the device,
correspond with those of the local power supply; see
chapter 13
-disconnect the device power supply before proceeding
with any type of maintenance
-position the power cables as far away as possible from
the signal cables
-for repairs and information regarding the device, contact
the EVCO sales network.
3USER INTERFACE
3.1Preliminary notes
Operating Statuses:
-“on” state (the device is powered and is on: the regulators
can be switched on)
-“stand-by” status (the device is powered but is
switched off via software: the regulators are switched
off; the possibility to manually switch on/switch off
the cell light or auxiliary output depends on parameter u2)
-the “off” status (the device is not powered).
Hereafter, with the word “start-up” means the passage
from “stand-by” status to “on” status; the word “shutdown” means the passage from “on” status to “stand-by”
status.
When the power is switched back on, the device displays the status that it was in at the time it was disconnected.
3.2Device switch-on/off in manual mode
Operating Statuses:
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the key down for 2 s: the LED will switch off/on.
Using the digital inputs it is also possible to remotely switch
on/off the device.
3.3The display
If the device is switched on, during normal operation, the
display will show the cell temperature, except during
defrosting, when the device will show the temperature
established with parameter d6.
If the device is switched off, the display will be switched
off.
Evap. Fan
Defrosting
earth
Cabinet light
Alarm
(config.)
Equipment
(config.)
Page 2
EVCO S.p.A. | Codice 104RS200E214 | Page 2 of 8 | PT 24/13 | version 2.1
3.4Evaporator temperature display
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“Pb2”.
4. Press and release the key
.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
6.2 Press and release the
key.
If the evaporator probe is absent (parameter P3 = 0), the
label “Pb2” will not be displayed.
3.5Condenser temperature display
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
“Pb3”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
6.2 Press and release the
key.
If the third input function is that of the digital input (parameter
P4 = 0), the label “Pb3” will not be displayed.
3.6Activation/deactivation of “overcooling”
function
1. Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or
dripping is not in progress and that the evaporator fan
is off.
2. Hold the
key down for 4 s: the Overcooling LED will
light up.
During the “overcooling” function the working setpoint is
reduced by the temperature established with parameter r5;
the operation lasts for the amount of time established with
parameter r6.
During “overcooling” defrosting is never activated; if
the defrosting interval expires when the function is in
progress, defrosting will be activated at the end of the
function.
3.7Defrosting activation in manual mode
1. Make sure that the keyboard is not locked and that no
other operation is in progress; ensure that the
“overcooling” function is not in progress
2. Hold the
key down for 4 s.
If the evaporator probe function is that of the defrosting
probe (parameter P3=1) and upon activation of defrosting,
the temperature of the evaporator is higher than that
established with parameter d2, the defrosting function will
not be activated.
3.8Switch-on/off of the cell light in manual
mode (only if parameter u1
and/or parameter u11 is set at 0)
1. Make sure no procedures are in progress
2. Press and release the
key: the “AUX” LED will
switch on/off.
Using the door digital inputs it is also possible to switch on/
off the cell light by remote; see also parameter u2.
If parameter u1 is set at 0 (i.e. the utility managed by the
fourth output is the cabinet light) and parameter u11 is set
at 2 (i.e. the utility managed by the fifth output is the
auxiliary output), holding the
key down for 2 s will
cause the switch-on/off of the “AUX” LED and of the auxiliary output.
3.9Demister resistors switch-on (only if the
parameter u1 and/or parameter u11 is set at
1)
1. Ensure that the device is switched on and that no other
procedure is in progress.
2. Hold the
key down for 2 s: the “AUX” LED will
light up and the resistors will be switched on, both
for the amount of time established with parameter
u6.
Manually switching off the demisting resistors is not permitted
(that is, before the time established with parameter u6
expires).
3.10Switch-on/off of the auxiliary output in
manual mode (only if parameter u1 and/or
parameter u11 is set at 2)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
key: the “AUX” LED will
switch on/off.
Using the digital inputs it is also possible to remotely switch
on/off the auxiliary output.
If parameter u1 is set at 2 (i.e. the utility managed by the
fourth output is the auxiliary output) and parameter u11 is
set at 0 (i.e. the utility managed by the fifth output is the
cabinet light), holding the
key down for 2 s will cause
the switch-on/off of the “AUX” LED and of the cabinet
light.
If the auxiliary output has been switched on manually,
then it can also be switched off manually (similarly, if the
auxiliary output has been remotely switched on, then it
can only be switched off in the same manner); see also
parameter u2.
3.11Locking/unlocking the keyboard
To lock the keyboard:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 1 s:
the display will show “Loc”.
If the keyboard is locked, the following are not permitted:
-device switch-on/off in manual mode
-display of evaporator temperature (via the procedure
explained in paragraph 3.4)
-display of the condenser temperature (via the procedure
indicated in paragraph 3.5)
-activation/deactivation of “overcooling” function
-manual activation of defrosting
-manual switch on/off of the auxiliary output
-activation of operation for low of high percentage of
relative humidity and learning the kind of operation
-see information regarding the HACCP alarms
-cancellation of HACCP alarm list
-display of compressor operation hours
-cancellation of compressor operation hours
-changing the working setpoint (with the procedure
described in 9.1).
The operations cause the display of the label “Loc” per 1
sec.
To unlock the keyboard:
1. Hold the
key and thee key down for 1 s: the
display will show the message “UnL” for 1 sec.
3.12Silencing the buzzer
To lock the keyboard:
1. Make sure no procedures are in progress
2. Press a key (the first pressing of the key will not cause
the effect associated with that key).
If the parameter u1 and/or the parameter u11 is set at 3
(i.e. the utility managed by the fourth output and/or the
utility managed by the fifth output is the alarm output) and
parameter u4 is set at 1, pressing the key will also cause the
deactivation of the output.
If parameter u9 is set at 0, the buzzer will not be activated.
4OPERATION DUE TO LOW OR HIGH RELATIVE
HUMIDITY PERCENTAGE (ONLY IF PARAMETER
F0 IS ISET AT 5)
4.1Preliminary notes
During operation for low percentage of relative humidity, the
evaporator ventilator will be switched on if the compressor is
switched off (parameter F4 determines the amount of time
it is switched off while parameter F5 determines the amount
of time it is switched on).
During operation for a high percentage of relative humidity
the evaporator fan is always on.
4.2Activation of operation for low or high
percentage relative humidity in manual
mode.
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
and keys down for 4 s: the display will
show “rhL” (operation for low percentage of relative
humidity) or “rhH” (operation for high percentage of
relative humidity) for 10 sec.
To restore the normal display before the operation is
complete:
3. Press a key.
Activation of the operation for a low or high percentage of
relative humidity can be done using parameter F6.
If the parameter F0 is not set at 5, pressing the
and
keys will cause the display of the “- - -“ indication
for 1 s.
4.3Learning the type of operation in progress
1. Make sure no procedures are in progress
2. Press and release the and keys: the display
will show “rhL” (operation for low percentage of relative humidity) or “rhH” (operation for high percentage
of relative humidity) for 10 sec.
To restore the normal display before the operation is complete:
3. Press a key.
If parameter F0 is not set at 5, pressing the
and
keys will cause:
-the display of the message “- - - -“ for 1 sec if the
keyboard is not locked
-display of the label “Loc” for 1 sec if the keyboard is
locked..
5ENERGY SAVING
5.1Preliminary notes
Once the time you have set with parameter i10 has passed,
without activations of the door micro switch input (after the
cell temperature has reached the work set-point) the “energy saving” function is activated (until the input is activated
again).
During function “Energy Saving” the working setpoint is
increased of the temperature you have set with parameter
r4 and the evaporator fan is turned on cyclically, on condition
that parameter F0 has value 1 or 2 (parameter F13 sets the
time the fan remains turned off and parameter F14 the time
it remains turned on).
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor).
6“HACCP” FUNCTION
6.1Preliminary notes
The device can memorise the following HACCP alarms:
-minimum temperature alarm (code “AL”)
-maximum temperature alarm (code “AH”)
-door micro switch input alarm (code “id”)
The device supplies the following information for every
alarm:
-the critical value
-the duration of the alarm (from 1 min to 99 hours and
59 min, partial if the alarm is in progress).
Code Critical value
AL the minimum temperature of the cell during any
alarm of this type
AH the maximum temperature of the cell during any
alarm of this type
iD the maximum cell temperature during any alarm
of this type; see also parameter i4
The device stored the minimum temperature alarm on
condition that the temperature associated to the alarm is
that of the cell (parameter A0 = 0).
if the device is switched off, no alarms will be stored.
The device updates the information regarding the the alarms
provided the critical value of the new alarm is more critical
than that stored or provided the information has already
been displayed.
The “HACCP” LED provides information regarding the storage
status of the alarms; see paragraph 10.1.
6.2Display of HACCP alarm information
To begin the procedure:
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
4. Press and release the
or key to select “LS”.
key: the display will show
one of the codes included in the table in paragraph
6.1.
If the device does not have any alarms stored, the label
“LS” will not be displayed.
To select an alarm:
5. Press and release the
or key (to select, for
example, “AH”).
To see information regarding the alarm:
6. Press and release the
key: the HACCP LED will
stop flashing and remain on permanently and the display will show, for example, the following information
in succession (for example):
Inform. Part
8.0 the critical value is 8.0 °C/8 °F
dur the display is about to show the alarm duration
h01 the alarm lasted for 1 hour (other data continues)
n15 the alarm lasted 1 hour and 15 min
AH the alarm selected
the displays each piece of information for 1 s.
Page 3
EVCO S.p.A. | Codice 104RS200E214 | Page 3 of 8 | PT 24/13 | version 2.1
To exit the information sequence:
7. Press and release the
key: the display will show
the alarm selected (in the example “AH”).
To exit the procedure:
8. Exit the information sequence.
9.1 Press and release the
or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
9.2 Press and release the
key.
6.3Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
4. Press and release the
5. Press and release the
or key to select “rLS”.
key.
or key within
15 s to set “149”.
6. Press and release the
key or do not operate for
15 sec: the display will show a flashing “- - - -” for
4 sec and the “HACCP” LED switches off, after which
the device will exit the procedure.
If the device does not have any alarms stored, the label
“rLS” will not be displayed.
7COMPRESSOR OPERATING HOURS COUNT
7.1Preliminary notes
The device can memorise up to 9.990 compressor operating
hours.
The parameter C10 establishes the number of operating
hours is higher than the limit at which the need for
maintenance is signalled.
7.2Display of Compressor Operation Hours
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
key or the key to select
“CH”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
6.2 Press and release the
key.
7.3Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
4. Press and release the
5. Press and release the
or key to select “rCH”.
key.
or key within
15 s to set “149”.
6. Press and release the
key or do not operate for
15 sec: the display will show “- - -” flashing for
4 sec, after which the device will exit the procedure.
8SYNCHRONISATION OF DEFROSTING
PERIODS (ONLY IF PARAMETER i0 AND/OR
PARAMETER i5 IS SET AT 6)
8.1Preliminary notes
The activation of defrosting causes the activation of
the digital input (at maximum for the time established
with parameter d24 or until the conclusion of
predripping).
If the digital input is connected in parallel to the digital input
of other devices configured in the same way, the activation
of the input caused the activation of defrosting in the other
devices.
The devices start dripping simultaneously with the conclusion of the predripping of the last device to end the
same.
9SETTINGS
9.1Setting the working setpoint
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
key: the LED will
flash.
3. Press and release the
or key within
15 sec; see also parameters r1, r2 and r3
4. Press and release the
15 sec: the
LED will switch off and then the device
key or do not operate for
will exit the procedure.
To exit the procedure before the operation is complete:
5. Do not operate for 15 sec (any changes will be saved).
The working setpoint can also be set via parameter
SP.
9.2Setting the configuration parameters
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 4s:the display will
show “PA”.
3. Press and release the
4. Press and release the
key.
or key within
15 s to set “-19”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
and keys down for 4 s:
the display will show “SP”.
To select a parameter:
7. Press and release the
or key.
To change a parameter:
8. Press and release the
9. Press and release the
key.
or key within
15 sec.
10. Press and release the
key or do not operate for
15 sec.
To exit the procedure:
11. Hold down the
and keys for 4 sec and do not
operate for 60 sec (any changes will be saved).
After changing the parameters, suspend power supply flow
to the device.
9.3Restoring the Manufacturer’s Settings
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
or key within
15 s to set “149”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
and keys down for 4 s:
the display will show “dEF”.
7. Press and release the
8. Press and release the
key.
or key within
15 s to set “1”.
9. Press and release the
key or do not operate for
15 sec: the display will show “dEF” flashing for
4 sec, after which the device will exit the procedure.
10. Cut the device power supply off.
To exit the procedure before the operation is complete:
11. Hold the and key down for 4 s during the procedure (i.e. before setting “1”:
Restore will not be performed).
Make sure that the manufacturer’s settings are appropriate
(see chapter 14).
10WARNING LIGHTS AND DIRECTIONS
10.1Signals
LED Part
compressor LED light
if the LED is on, then the compressor is on
if the LED is flashing:
-the working setpoint is in the process of being
changed (via the procedure described in paragraph 9.1)
-a compressor protection will be in progress;
see parameters C0, C1, C2, C14, C15, C16
and i7
Defrost LED
If it is on:
-defrosting is in progress
-predripping will be in progress; see parameter
d16
if the LED is flashing:
-defrosting will be requested but a compressor
protection will be in progress; see the parameters C0, C1 and C2
-dripping will be in progress; see parameter
d7
-the refrigerant fluid heating will be in progress;
see parameter d15
Evaporator fan LED light
If it is on:
-the evaporator fan will be on
if the LED is flashing:
-evaporator fan standstill will be in progress;
see parameter F3
AUX Auxiliary LED
If it is on:
-the cell light will have been switched on in
manual mode (only if parameter u1 and/or
parameter u11 is set at 0)
-the demister resistors will be switched on (only
if the parameter u1 and/or parameter u11 is
set at 1)
-the auxiliary output will have been switched
on in manual mode (only if parameter u1
and/or parameter u11 is set at 2)
-the door resistors will be switched on (only
and provided parameter u1 and/or parameter
u11 is set at 4)
-the neutral area operating resistors will be
activated (only if parameter u1 and/or parameter u11 is set at 5)
-the condenser fan will be on (only if parameter
u1 and/or parameter u11 is set at 6)
if the LED is flashing:
-the cell light will have been switched on in
remote mode; see parameters i0 and i5 (only
if parameter u1 and/or parameter u11 is set
at 0)
-the auxiliary output will have been switched
on in remote mode; see parameters i0 and i5
(only if parameter u1 and/or parameter u11
is set at 1)
-condenser fan switch-off delay will be in
progress; see parameter F12 (only if
parameter u1 and/or parameter u11 is set at
6)
HACCP HACCP LED
if it is on, all information regarding HACCP alarms
has not been displayed
if it is flashing, the device has stored at least one
new HACCP alarm
if it is off, all information regarding the HACCP
alarms has been displayed or the list of alarms has
been cancelled
maintenance LED
if on, compressor maintenance will be requested;
see parameter C10
“overcooling” LED
if it is on, the “overcooling” function will be in
function; see parameters r5 and r6
°C degree Celsius LED
if on, the temperatures will be displayed using the
degree Celsius grade unit of measurement; see
parameter P2
if flashing, the “energy saving” function is in progress
(with effect only on the compressor)
°Fdegree Fahrenheit LED
if on, the temperatures will be displayed using the
degree Fahrenheit grade unit of measurement;
see parameter P2
if flashing, the “energy saving” function is in progress
(with effect only on the compressor)
On/stand-by LED
if it is on, the device will be off (
“stand-by” state)
if it is off, the device will be on (“on” state)
10.2Signal Descriptions/Explanations
Code Part
rhL operation for a low percentage of relative humidity
in progress
rhH operation for a high percentage of relative humidity
in progress
Loc the keyboard is blocked; see paragraph 3.11
the work setpoint is blocked; see parameter r3
- - - the operation requested is not available
11ALARMS
11.1Alarms
Code Part
AL Minimum alarm temperatures (HACCP alarms)
Solutions:
-check the temperature associated to the
alarm; see parameters A0, A1 and A2
Main consequences:
-if parameter A0 is set at 0, the device will
store the alarm
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
AH Maximum temperature alarm (HACCP alarms)
Solutions:
-check the cell temperature; see parameters
A4 and A5
Main consequences:
-the device will memorise the alarm
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
Page 4
EVCO S.p.A. | Codice 104RS200E214 | Page 4 of 8 | PT 24/13 | version 2.1
idDoor micro switch input alarm (HACCP alarms)
Solutions:
-check the causes of the activation of the input; see parameters i0, i1, i5 and i6
Main consequences:
-the effect established with the parameters i0
and i5
-if parameter is set at 1, the device will store
the alarm, provided parameter i2 is not set at
-1
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
iAMultifunction input alarm
Solutions:
-check the causes of the activation of the input; see parameters i0, i1, i5 and i6
Main consequences:
-the effect established with the parameters i0
and i5
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
iSd Pressure switch alarm
Solutions:
-check the causes of the activation of the
input; see parameters i0, i1, i5, i6, i7, i8
and i9
-switch off and re-start the device or suspend
the power supply
Main consequences:
-the regulators will switch off
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
COH Condenser overheated alarm.
Solutions:
-check the condenser temperature; see parameter C6
Main consequences:
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
-the condenser fan will be on (only if parameter
u1 and/or parameter u11 is set at 6)
CSd Condenser overheated alarm.
Solutions:
-check the condenser temperature; see parameter C7
-switch the device off and back on again: if
when the device is switched back on, the
temperature of the condenser is still higher
than that established in parameter C7, disconnect the power supply and clean the condenser
Main consequences:
-the compressor and the evaporator fan will be
switched off
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
-the condenser fan will be on (only if parameter
u1 and/or parameter u11 is set at 6)
dFd Defrosting alarm switched off because maximum
time has been reached
Solutions:
-heck the integrity of the evaporator probe;
see parameters d2, d3 and d11
-press a key to restore normal display
Main consequences:
-the device will continue to operate normally.
When the cause of the alarm disappears, the device restores
normal operation, except for the following alarms:
-pressure switch alarm (code “iSd”) which requires the
switching off of the device or the temporary suspension
of the power supply
-compressor blocked by condenser temperature alarm
(code “CSd”) which requires the switching off of the
device or the temporary suspension of the power supply
-Defrosting alarm switched off because maximum time
has been reached (code “dFd”) which requires the
pressing of a key.
12ERRORS
12.1Errors
Code Part
Pr1 Cell probe error
Solutions:
-check that the probe is the PTC or NTC type;
see parameter P0
--check the device-probe connection
-check the cell temperature
Main consequences:
-compressor activity will depend on parameters C4 and C5
-the defroster will not be activated
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
-the door resistors will be switched off (only
and provided parameter u1 and/or parameter
u11 is set at 4)
-the neutral area operating resistors will be
deactivated (only if parameter u1 and/or parameter u11 is set at 5)
Pr2 Evaporator probe error
Solutions:
-the same as the preceding case but with respect to the evaporator probe
Main consequences:
-if parameter P3 is set at 1, the defrosting
period will last for the amount of time set with
parameter 3
-if parameter P3 is set at 1and parameter d8 is
set at 2 or to 3, the device will operate as if
parameter d8 were set at 0
-if parameter F0 is set at 3 or 4, the device will
operate as if the parameter were set at 2
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
Pr3 Condenser probe error.
Solutions:
-the same as the preceding case but with respect to the condenser probe
Main consequences:
-condenser overheated alarm (code “COH”)
will not be activated
-the compressor blocked alarm (“CSd” code)
will never be activated
-the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
-the condenser fan will operate parallel to the
compressor (only if parameter u1 and/or
parameter u11 is set at 6)
ErC User interface-control module compatibility error.
Solutions:
-check the compatibility of the user interface
with the control module (check the data stated
on the labels)
Main consequences:
-the control module will continue to operate
regularly.
ErL User interface-control module communication er-
ror.
Solutions:
-check user interface-control module control
module
Main consequences:
-the control module will continue to operate
regularly.
When the problem that caused the alarm disappears, the
device is restored to normal operation.
13TECHNICAL DATA
13.1Technical data
Purpose of the command device: operating command
device.
Construction of the command device: built-in electronic
device.
User interface container:
-user interface: grey self-extinguishing
-control module: without cover.
User interface dimensions:
-user interface: 180.0 x 38.0 x 28.0 mm (7.086 x 1.496
x 1.102 in; L x H x D)
-control module: 134,0 x 108.0 x 24.0 mm (5.275 x
4.251 x 0.944 in; L x H x D).
Method of mounting the command device:
-user interface: panel, with elastic retaining wings
6.3 m faston (0.248 in, power supply, equipment earth
and outputs), removable screw terminal board (user
interface) 6 pole connector (serial port).
The maximum length of the analogue inputs and digital
outputs connection cables must be less than 10 m
(32,808 ft).
The maximum length of the user interface-control module
connection cables must be less than 20 m (65,616 ft).
Operating temperature: from 0 to 55 °C (from 32 to
131 °F).
Storage temperature:from -25 to 70 °C (from -13 to
158 F).
Humidity for use: from 10% to 90% relative humidity
without condensate.
Rated impulse voltage: 4K V.
Overvoltage category: II.
Class and structure of software: A.
Analogue inputs: 2 inputs (cabinet probe and evaporator
probe), can be set via configuration parameter for PTC/NTC
probes
PTC type analogue inputs (990 Ω @ 25°C, 77°F)
Type of sensor:KTY 81-121.
Measurement field:from -50 to 150 °C
(from -58 to 302°F).
Resolution:0.1 ° (1 °F).
Protection:none.
PTC type analogue inputs NTC (10K Ω @ 25°C, 77°F)
Type of sensor:ß3435.
Measurement field:from -50 to 105 ° (from -40 to
220 °).
Resolution:0.1 ° (1 °F).
Protection:none.
Digital inputs: 1 input (door micro/multi-function 2 switch),
which can be set via configuration parameter due to normally
open contact/normally closed contact (free of voltage contact,
5 VDC, 2 mA)
Digital inputs
Power:none.
Protection:none.
Other inputs: 1 input that can be set via configuration
parameter for analogue input (condenser probe)/digital input
(door micro switch/multifunction 1), with the same technical
features illustrated previously.
Displays: custom 3 digit display with function icon.
Digital outputs:
4 outputs (electro-mechanical relays) in the EVRS204 model,
5 outputs (electro-mechanical relays) in the EVRS205 model
-1 x 30 A res. output @ 250 VAC SPST type (K2) for
compressor management
-1 x 16 A res. output @ 250 VAC type SPST (K4) for
defrosting management
-1 x 8 A res. output @ 250 VAC type SPST (K5) for
management of the evaporator fan
-1 x 16 A res. output @ 250 VAC type SPST (K3) for
management of the cell light, demisting resistors, aux.
output, alarm output, door resistors, neutral area
operation resistors, condenser fan of compressor 2 fan.
-1 x 30 A res. output @ 250 VAC type SPST (K1) for
management of the cell light, demisting resistors, aux.
output, alarm output, door resistors, neutral area
operation resistors, condenser fan of compressor 2 fan.
The maximum load current allowed is 20 A.
Type 1 or Type 2 actions: Type 1.
Complementary features of Type 1 or Type 2 actions: C.
Communication port: 1 x TTL serial port with MODBUS
communication protocol (for EVKEY programming key and
other EVCO products).
Signal buzzer and alarm:on request.
Page 5
EVCO S.p.A. | Codice 104RS200E214 | Page 5 of 8 | PT 24/13 | version 2.1
14WORKING SETPOINT AND CONFIGURATION PARAMETERS
14.1Working set-point
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 WORKING SETPOINT
r1r2 °C/°F (1) -18,0-18,0 working set-point; see also r0
14.2Configuration parameters
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 WORKING SETPOINT
SPr1r2°C/°F (1) -18,0-18,0 working set-point; see also r0
P802500.1 s55delay displaying temperature variation detected by the probes
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 MAIN REGULATOR
r00,1 (3)15,0 °C/°F (1) 2,02,0working set-point differential
r1-99r2°C/°F (1) -50-50minimum working set-point
r2r199,0 °C/°F (1) 50,050,0 maximum working set-point
r301- - -00locking of working set-point calibration (using the procedure described in paragraph 10.1)
1= YES
r40,099,0 °C/°F (1) 0,00,0increase in temperature during “energy saving” function; see also i0, i5 and i10
r50,099,0 °C/°F (1) 0,00,0decrease in temperature during “overcooling” function; see also r6
r60240min3030duration of “overcooling” function; see also r5
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 COMPRESSROR PROTECTION SYSTEM
C00240min00delay in switching on of compressor after the device switches on (4)
C10240min55minimum time between two consecutive compressor start-ups; also delay in compressor start-up after conclusion of cell probe error
(code “Pr1”) (5) (6)
C20240min33minimum compressor switch-off duration; see also C18 (5) (7)
C30240s00minimum duration of compressor switch on time
C40240min1010duration of compressor switch off during cell probe error (code “Pr1”); see also C5
C50240min1010duration of compressor switch on during cell probe error (code “Pr1”); see also C4
C60,0199 °C/°F (1) 80,080,0 condenser temperature is higher than that at which the condenser overheating alarm is activated (code “COH”) (8)
C70,0199 °C/°F (1) 90,090,0 condenser temperature above which the blocked compressor alarm is activated (“CSd” code)
C8015min11blocked compressor alarm delay (“CSd” code) (9)
C10099910 h00number of operating hours is higher than the limit at which the need for maintenance is signalled.
0 = function absent
C110240s33compressor 2 switch-on delay from compressor 1 switch-on (only if u1 and/or u11 = 7) (10)
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 DEFROSTING
d0099h88if d8 = 0, 1 or 2, defrosting interval (11)
0 = interval defrosting will never be activated
if d8 = 3, maximum defrost interval
d102- - -00type of defrosting
0=
ELECTRIC - during defrosting the compressor will remain off and the defrosting output will be activated; evaporator fan
activity will depend on parameter F2
1=
BY HOT GAS - during defrosting the compressor will be switched on and the defrosting output will be activated; evaporator
fan activity will depend on parameter F2
2=
VIA STOPPING OF COMPRESSOR - during defrosting the compressor will remain switched off and the defrosting output will
remain deactivated; evaporator fan activity will depend on parameter F2
d2-9999,0 °C/°F (1) 2,02,0temperature at end of defrosting (only if P3 = 1); see also d3
d3099min3030se P3 = 0 or 2, defrosting duration
se P3 = 1, maximum defrosting duration; see also d2
0 = defrosting will not be activated
d401- - -00defrosting on device switch-on (4)
1= YES
d5099min00if d4 = 0, minimum time between switching on of device and activation of defrosting; see also i0 and i5 (4)
if d4 = 1, delay in activation of defrosting after device is switched on ; see also i0 and i5 (4)
d601- - -11temperature displayed during defrosting
0 = cell temperature
1 = if at the time of defrosting activation, the cell temperature is lower than the “working set-point + r0”, at most “working
set- point + r0”; if at the time of defrosting activation, the cell temperature is higher than the “working set-point + r0”,
at most the cell temperature when defrosting is activated (12)
d7015min22dripping duration (during dripping the compressor will remain switched off and the defrosting output will remain deactivated; if d16
= 0, evaporator fan activity will depend on parameter F2; if d16 ≠ 0, the evaporator fan will remain switched off)
d803- - -00defrosting activation methods
0=
AT INTERVALS - defrosting will be activated once the device has altogether been running for time d0
1=
AT INTERVALS - FOR COMPRESSOR SWITCH-ON - defrosting will be activated once the compressor has altogether been
switched on for time d0
2=
AT INTERVALS - FOR EVAPORATOR TEMPERATUREE - defrosting will be activated when the evaporator temperature has
remained below the temperature d9 for a total time of d0 (13)
3=
ADAPTABLE - defrosting will be activated at intervals, whose duration will each time depend on the duration of compressor
switch-ons and the evaporator temperature; see also d18, d19 and d22 (13)
d9-9999,0 °C/°F (1) 0,00,0evaporator temperature is higher than that at which the defrost interval counter is suspended (only if d8 = 2)
d1101- - -00defrosting alarm switches off once maximum time limit has been reached (code “dFd”; only if P3 = 1 and in absence of an
evaporator probe (code “Pr2”)
1= YES
d15099min00minimum time that the compressor must be switched on before defrosting can be activated (only if
d1 = 1) (14)
Page 6
EVCO S.p.A. | Codice 104RS200E214 | Page 6 of 8 | PT 24/13 | version 2.1
d16099min00predripping duration (during predripping the compressor will remain switched off, the defrosting output will be activated and the
evaporator fan will remain switched off)
d180999min4040defrosting interval (only if d8 = 3; defrosting will be activated when the compressor has been on totally, with the evaporator
temperature below that of d22, for time d18)
0 = defrosting will never be activated due to the effect of this condition
d190,040,0 °C/°F (1) 3,03,0evaporator temperature above which the defrost is activated (relative to the evaporator temperatures average, or “evaporator
temperatures average - d19”) (only if d8 = 3)
d200500min180180 minimum consecutive time the compressor must be switched on such as to provoke the defrost activation
0 = defrosting will never be activated due to the effect of this condition
d220,010,0 °C/°F (1) 2,02,0evaporator temperature above which the defrosting interval is suspended (relative to the evaporator temperatures average, or
“evaporator temperatures average + d22”) (only if d8 = 3); also look at d18
d240999min3030maximum duration of activation of the defrosting synchronisation input due to activation of defrosting (only if i0 and/or i5 = 6)
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 TEMPERATURE ALARMS
A001- - -00temperature associated with the minimum temperature alarm (code “AL”)
0 = cell temperature
1 = evaporator temperature (15)
A1-9999,0 °C/°F (1) -10,0-10,0 temperature below that at which the minimum temperature alarm is activated (code “AL”); see also A0, A2 and A11
A202- - -11type of minimum temperature alarm (code “AL”)
0 = alarm absent
1 = relative to working set-point (that is “working set-point - A1”; consider A1 without sign)
2 = absolute (that is A1)
A4-9999,0 °C/°F (1) 10,010,0 temperature higher than that at which the maximum temperature alarm is activated (code “AH”); see also A5 and A11
A502- - -11type of maximum temperature alarm (code “AH”)
0 = alarm absent
1 = relative to working set-point (that is “working set-point + A4”; consider A1 without sign))
2 = absolute (that is A4)
A60240min120120 delay in maximum temperature alarm (code “AH”) after the device is switched on (4)
A70240min1515temperature alarm delay(“AL” code and “AH” code)
A80240min1515delay in maximum temperature alarm (code “AH”) from the conclusion of evaporator fan standstill (16)
A90240min1515delay in maximum temperature alarm (code “AH”) following the deactivation of the door micro switch input (17)
A110,1 (3)15,0 °C/°F (1) 2,02,0differential of parameters A1and A4
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 EVAPORATOR FAN AND CONDENSER FAN
F005- - -11evaporator fan activity during normal operation
0 = switched off
1 = switched on; see also F13, F14 and i10 (18)
2 = in parallel with the compressor; see also F9, F13, F14 and i10 (19)
3 = depending on F1; see also F9, F13 and F14 (20) (21)
4 = switched off if the compressor is switched off, dependent on F1 if the compressor is switched on; see also F9, F13 and F14
(20) (22)
5 = dependent on F6; see also F9
F1-9999,0 °C/°F (1) -1,0-1,0 evaporator temperature above the limit at which the evaporator fan is switched off (only if F0 = 3 or 4); see also F8
F202- - -00evaporator fan activity during defrosting and dripping
0 = switched off
1 = switched on (setting parameter d7 to 0 is recommended)
2 = dependent on F0
F3015min22maximum duration of evaporator fan deactivation; see also F7 (during evaporator fan deactivation the compressor can be switched
on, the defrosting output will remain deactivated and the evaporator fan will remain switched off)
F40240s6060time duration that evaporator fan is switched off during operation for a low percentage of relative humidity when the compressor
is switched off; see also F5 (only if F0 = 5)
F50240s1010time duration that evaporator fan is switched on during operation for a low percentage of relative humidity when the compressor
is switched off; see also F4 (only if F0 = 5)
F601- - -00operation for low or high percentage of relative humidity (only if F0 = 5) (23)
0=
LOW RELATIVE HUMIDITY - the evaporator fan will operate in parallel with the compressor; see also F4 and F5
1=HIGH RELATIVE HUMIDITY - the evaporator fan will always be switched on
F7-9999,0 °C/°F (1) 5,05,0evaporator temperature below limit at which the evaporator fan is deactivated (relative to working setpoint, that is “working
setpoint + F7”); see also F3
F80,1 (3)15,0 °C/°F (1) 2,02,0parameter F1differential
F90240s00delay in the switching off of evaporator fan following the switching off of the compressor (only if F0 = 2, 3, 4 and 5)
F110,099,0 °C/°F (1) 15,015,0 temperature of the condenser above which the condenser fan is switched on (“F11 + 2,0 °C/4 °F, only if
u1 and/or u11 = 6) (24) (25)
F120240s3030delay in the switching off of condenser fan following the switching off of the compressor (only if P4 = 0 and u1 and/or u11= 6)
F13024010 s3030time the evaporator fan remains turned off during function “energy saving”; see also F14 and i10 (only if F0 = 1, 2, 3 or 4)
F14024010 s3030time the evaporator fan remains turned on during function “energy saving”; see also F13 and i10 (only if
F0 = 1, 2, 3 or 4)
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 DIGITAL INPUTS
i0011- - -77effect caused by the activation of the door micro switch/multifunction 1 input; see also i4 (26)
0 = no effect
1=
DOOR MICROSWITCH - COMPRESSOR AND EVAPORATOR FAN SWITCH-OFF - the compressor and the evaporator fan will
be switched off (at maximum for time i3 or until the input is deactivated) (27)
2=
DOOR MICROSWITCH - EVAPORATOR FAN SWITCH-OFF - the evaporator fan will be switched off (at maximum for time
i3 or until the input is deactivated)
3=
DOOR MICROSWITCH - CELL LIGHT SWITCH-ON - the cell light will be switched on (only if u1 and/or u11 = 0, until the input
will be deactivated)
4=
DOOR MICROSWITCH - SWITCH-OFF OF THE COMPRESSOR, EVAPORATOR FAN, SWITCH-ON OF CELL LIGHT - the
compressor and the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) and the
cell light will be switched on (only if u1 = 0, until the input is deactivated) (27)
5=
DOOR MICROSWITCH - SWITCH-OFF OF THE EVAPORATOR FAN, SWITCH-ON OF CELL LIGHT - the evaporator fan will be
switched off (at maximum for time i3 or until the input is deactivated) and the cell light will be switched on (only if u1 and/
or u11 = 0, until the input is deactivated)
6=
MULTIFUNCTION - SYNCHRONISATION OF DEFROSTING PERIODS - the activation of defrosting will cause activation of the
input (at maximum for time d24 or until the conclusion of predripping): if the input is connected in parallel to the input of
other devices configured in the same way, the activation of the input will cause activation of defrosting in the other devices.
The devices will start dripping simultaneously on conclusion of predripping of the last device to conclude the same
7=
MULTIFUNCTION - ACTIVATION OF “ENERGY SAVING” FUNCTION - the “energy saving” function will be activated (just with
effect on the compressor, until the input is deactivated), provided the “overcooling” function is not running; see also r4
8=
MULTIFUNCTION - ACTIVATION OF MULTIFUNCTION INPUT ALARM - once time i7 has passed the display will show the
flashing code “iA” and the buzzer will be activated (until the input is deactivated)
Page 7
EVCO S.p.A. | Codice 104RS200E214 | Page 7 of 8 | PT 24/13 | version 2.1
9=MULTIFUNCTION- ACTIVATION OF THE PRESSURE SWITCH ALARM - the compressor will be switched off, if u1 and/or u11
= 6 the condenser fan will be switched on, the display will show the flashing code iA” and the buzzer will be activated (until
the input is deactivated): when the input has been activated the number of times established with parameter i8 the
regulators will be switched off, if u1 and/or u11 = 6 the condenser fan will be switched on, the display will show the flashing
code “iSd” and the buzzer will be activated (until the input is deactivated and the device is switched off and re-started or
until the power supply is interrupted); see also i7 and i9
10 =
MULTIFUNCTION - SWTICHING ON THE AUXILIARY OUTPUT - the auxiliary output will be switched on (only if u1 and/or u11
= 2, until the input is deactivated)
11 = MULTIFUNCTION - SWITCHING OFF THE DEVICE - the device will be switched off (until the input is deactivated)
i101- - -00type of door micro switch/multifunction 1 input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
i2-1120min3030delay in signalling of door micro switch input alarm (code “id”)
-1 = the alarm will not be signalled
i3-1120min1515maximum duration of the effect caused by the activation of the door micro switch input on the compressor and the evaporator
-1 = the effect will last until the input is deactivated
i401- - -00storage of door micro switch input alarm (code “id”) (28)
1= YES
i5011- - -55effect caused by the activation of the door micro switch/multifunction 2 input; see also i4 (26)
0 = no effect
1=
DOOR MICROSWITCH - COMPRESSOR AND EVAPORATOR FAN SWITCH-OFF - the compressor and the evaporator fan will
be switched off (at maximum for time i3 or until the input is deactivated) (27)
2=
DOOR MICROSWITCH - EVAPORATOR FAN SWITCH-OFF - the evaporator fan will be switched off (at maximum for time
i3 or until the input is deactivated)
3=
DOOR MICROSWITCH - CELL LIGHT SWITCH-ON - the cell light will be switched on (only if u1 and/or u11 = 0, until the input
will be deactivated)
4=
DOOR MICROSWITCH - SWITCH-OFF OF THE COMPRESSOR, EVAPORATOR FAN, SWITCH-ON OF CELL LIGHT - the
compressor and the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) and the
cell light will be switched on (only if u1 = 0, until the input is deactivated) (27)
5=
DOOR MICROSWITCH - SWITCH-OFF OF THE EVAPORATOR FAN, SWITCH-ON OF CELL LIGHT - the evaporator fan will be
switched off (at maximum for time i3 or until the input is deactivated) and the cell light will be switched on (only if u1 and/
or u11 = 0, until the input is deactivated)
6=
MULTIFUNCTION - SYNCHRONISATION OF DEFROSTING PERIODS - the activation of defrosting will cause activation of the
input (at maximum for time d24 or until the conclusion of predripping): if the input is connected in parallel to the input of
other devices configured in the same way, the activation of the input will cause activation of defrosting in the other devices.
The devices will start dripping simultaneously on conclusion of predripping of the last device to conclude the same
7=
MULTIFUNCTION - ACTIVATION OF “ENERGY SAVING” FUNCTION - the “energy saving” function will be activated (just with
effect on the compressor, until the input is deactivated), provided the “overcooling” function is not running; see also r4
8=
MULTIFUNCTION - ACTIVATION OF MULTIFUNCTION INPUT ALARM - once time i7 has passed the display will show the
flashing code “iA” and the buzzer will be activated (until the input is deactivated)
9=
MULTIFUNCTION- ACTIVATION OF THE PRESSURE SWITCH ALARM - the compressor will be switched off, if u1 and/or u11
= 6 the condenser fan will be switched on, the display will show the flashing code iA” and the buzzer will be activated (until
the input is deactivated): when the input has been activated the number of times established with parameter i8 the
regulators will be switched off, if u1 and/or u11 = 6 the condenser fan will be switched on, the display will show the flashing
code “iSd” and the buzzer will be activated (until the input is deactivated and the device is switched off and re-started or
until the power supply is interrupted); see also i7 and i9
10 =
MULTIFUNCTION - SWTICHING ON THE AUXILIARY OUTPUT - the auxiliary output will be switched on (only if u1 and/or u11
= 2, until the input is deactivated)
11 = MULTIFUNCTION - SWITCHING OFF THE DEVICE - the device will be switched off (until the input is deactivated)
i601- - -00type of door micro switch/multifunction 2 input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
if i0 and/or i5 = 9, delay in compressor switching on after the deactivation of the multifunction input (29)
i8015- - -00number of multifunction input alarms (code “iA”) such to cause a pressure switch alarm (code “iSd”) (only if i0 and/or i5 = 9)
0 = alarm absent
i91999min240240 time that must pass in absence of multifunction output alarms (code “iA”) so that the alarm counter is reset (only if i0 and/or i5 =
9)
i100999min00time without activations of the door switch input (on condition that the cabinet temperature has reached the working setpoint) in
order that function “energy saving” is activated (it has effect on the evaporator fan only if F0 = 1, 2, 3 or 4)
0 = the function will never be activated due to the effect of this condition
i130240- - -180180 number of door switch input activations such as to provoke the defrost activation
0 = defrosting will never be activated due to the effect of this condition
i140240min3232minimum duration of the door switch input activation such as to provoke the defrost activation
0 = defrosting for this condition will never be activated
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 DIGITAL OUTPUTS
u107- - -00operation controlled by fourth output (30)
0=
CELL LIGHT - in this case the key and parameters i0, i5 AND u2 will be activated
1=
DEMISTER RESISTORS - in this case the key and parameter u6 will be activated
2=
AUXILIARY OUTPUT - in this case the key and parameters i5 and u2 will be activated
3=
ALARM OUTPUTS - in this case parameter u4 will be activated
4=
DOOR RESISTORS - in this case parameter u5 will be activated
5=
RESISTORS FOR NEUTRAL AREA OPERATION - in this case parameter u7 will be activated
6=
CONDENSER FAN - in this case parameters P4, F11 and F12 will be activated
7=COMPRESSOR 2 - in this case, parameter C11 will assume significance of
u201- - -00enabling of manual switch on/switch off of the cell light or the auxiliary output when the device is switched off(only if u1 and/or u11=
0 or 2) (31)
1= YES
u401- - -11enabling of alarm output deactivation with the silencing of the buzzer (only if u1 and/or u11 = 3)
1= YES
u5-9999,0 °C/°F (1) -1,0-1,0 temperature of the cell below which the door resistors are switched on (“u5 - 2,0 °C/4 °F, only if u1 and/or u11 = 4) (8)
u61120min55operating time of demister resistors (only if u1 and/or u11 = 1)
u7-9999,0 °C/°F (1) -5,0-5,0 neutral area value (relative to the work set-point, i.e. “work set-point + u7) (only if u1 and/or u11 = 5) (32)
u8- - -- - -- - -- - -- - - reserved
u901- - -11enabling the buzzer
1= YES
u1107- - - not avail.3operation controlled by fifth output (30)
0=
CELL LIGHT - in this case the key and parameters i0 and u2 will be activated
1=
DEMISTER RESISTORS - in this case the key and parameter u6 will be activated
2=
AUXILIARY OUTPUT - in this case the key and parameters i0 and u2 will be activated
3=
ALARM OUTPUTS - in this case parameter u4 will be activated
4=
DOOR RESISTORS - in this case parameter u5 will be activated
Page 8
EVCO S.p.A. | Codice 104RS200E214 | Page 8 of 8 | PT 24/13 | version 2.1
5=RESISTORS FOR NEUTRAL AREA OPERATION - in this case parameter u7 will be activated
6=
CONDENSER FAN - in this case parameters P4, F11 and F12 will be activated
7=COMPRESSOR 2 - in this case, parameter C11 will assume significance of
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 ENERGY SAVING
HE20999min00maximum duration of the “energy saving” function activated due to the effect of absence of door micro switch input activation
0 = the function will last until the input is activated
PARAM. MIN.MAX.U.M. EVRS204 EVRS205 SERIAL NETWORK
(1)the unit of measurement depends on P2
(2)Properly set the parameters corresponding to the
regulators after modifying parameter P2
(3)the value depends on parameter P2 (0.1 °C or 1
°F)
(4)the parameter has effect even after an interrup-
tion in the power supply that occurs while the
device is switched on
(5)the time established with the parameter is counted
even when the device is switched off
(6)if parameter C1 is set at 0, the delay after the end
of the cell probe error will be 2 min
(7)if parameter C2 is set at 0, the device will function
as if parameter C18 were set at 0
(8)The parameter differential is 2.0 °/4 °F
(9)if when the device is switched on, the condenser
temperature is already above that established in
parameter C7, then parameter C8 will not have
effect
(10)compressor 2 is switched off when compressor 1 is
switched off
(11)the device memorises the defrosting interval count
every 30 minutes; the modification of parameter
d0 has effect from the conclusion of the previous
defrosting interval (or the activation of defrosting
in manual mode)
(12)the display restores normal operation when, on
conclusion of evaporator fan standstill, the cell tem-
perature drops below that which has blocked the
display (or if a temperature alarm occurs)
(13)if parameter P3 is set at 0 or 2, the device will
function as if parameter d8 were set at 0
(14)if when defrosting is activated, the operating dura-
tion of the compressor is less than the time estab-
lished with parameter d5, the compressor will re-
main on for the amount of time necessary to com-
tablished with parameter F11 on condition that the
compressor is off
(26)if the parameter i0 and parameter i5 are set at the
same value, the effect will be caused by the activation of at least one of the inputs (until both
inputs are deactivated)
(27)the compressor is switched off 10 sec after the
activation of the input; if the input is activated
during defrosting or when the evaporator fan is
deactivated, the activation will not have any effect
on the compressor
(28)the device stores the alarm once the time estab-
lished in parameter i2 has expired; if parameter i2
is set at -1, the device will not store the alarm
(29)make sure that the time established with param-
eter i7 is less than that established with parameter
i9
(30)to avoid damaging the unit connected to the
instrument, change the parameter setting when
the device is switched off
(31)if parameter u2 is set at 0, switching off the device
may cause the cell light and/or the auxiliary output
to switch off (the next time the instrument is
switched on the unit connected will remain switched
off); if parameter u2 is set at 1, switching off the
device will not cause the cell light or the auxiliary
output to switch off (the next time the instrument
is switched on the unit connected will remain
switched on).
(32)the resistors are switched on when the tempera-
ture of the cell drops below the “work set-point +
u7” and are switched off when the temperature
rises above the “work set-point + u7 + 2 °C/°F”.
DIMENSIONS AND INSTALLATION
Control module dimensions and installation
The dimensions are expressed in mm (in); installation is envisioned on a flat surface, with shims.
plete defrosting.
(15)if parameter P3 is set at 0, the device will function
as if parameter A0 were set at 0 but it will not store
the alarm
(16)during defrosting and dripping and when the evapo-
rator fan is stopped, the temperature alarms are
absent, provided that these were signalled after
the activation of defrosting
(17)during activation of the door micro switch input,
the maximum temperature alarm is absent,
provided the alarm was signalled after the activation
of the input
(18)parameters F13 and F14 have effect when the
compressor is off
(19)parameters F13 and F14 have effect when the
compressor is on
(20)if parameter P3 is set at 0, the device will function
as if parameter F0 were set at 2
(21)parameters F13 and F14 have effect when the
evaporator temperature is below the temperature
established with parameter F1
(22)parameters F13 and F14 have effect when the
compressor is on and the temperature of the
evaporator is below the temperature established
with parameter F1
(23)the parameter can also be modified using the
procedure described in paragraph 4.2
(24)if parameter P4 is set at 0, the condenser fan will
function in parallel with the compressor
(25)the condenser fan is off when the temperature of
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
phone +39 0437 8422 | fax +39 0437 83648
email info@evco.it | web www.evco.it
This document is exclusive property of EVCO. EVCO does not assume any liability regarding possible errors stated.
The customer (manufacturer, installer or final user) assumes all liability regarding configuration of the device.
EVCO does not take any responsibility about damages coming by the non-observance of additional information.
EVCO reserves the right to make any change without prejudice the basic safety and operating features.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.