EVCO EVRS205N9 User Manual

EVCO S.p.A. | Codice 104RS200E214 | Page 1 of 8 | PT 24/13 | version 2.1
EVRS 200 range
Controllers in split execution for refrigerated display cases, ice-cream and sweet counters and plug ins.
EN ENGLISH
DIMENSIONS AND INSTALLATION User interface dimensions and installation
The dimensions are expressed in mm (in); panel installation is envisioned, with elastic retainer wings (det. A). For the dimensions and installation of the control module, see page 8.
dr il li ng t empl ate
ELECTRIC CONNECTION Electric connection
User interface
Third Input
Cabinet
Control module
Door micro switch/minutes f.2
TTI MODBUS port
In the EVRS205 model
Not available
Cabinet
Phase
Power supply neutral
Earth
Door micro switch/minutes f. 1
Door micro switch/minutes f. 2
IMPORTANT
Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this document with the device for future consulta­tion. Only use the device in the way described in this document; do not use the same as a safety device.
The device must be disposed of in compliance with local Standards regarding the collection of electric and electronic equipment.
1 DIMENSIONS AND INSTALLATION
1.1 Installation warnings
- the thickness of the panel on which the user interface is to be installed must be between 0.8 and
2.0 mm (0.031 and 0.078 in)
- make sure that the device work conditions (temperature of use, humidity, etc.) lie within the limits indicated; see chapter 13
- do not install the device near to any heat sources (heating elements, hot air ducts etc.), equipment containing powerful magnets (large diffusers, etc.), areas affected by direct sunlight, rain, humidity, excessive dust, me­chanical vibrations or shocks.
- any metal parts in proximity of the control module must be at a distance such that they do not compromise the safety distances.
- in compliance with Safety Standards, the device must be installed correctly and in a way to protect against any contact with electric parts; all parts that ensure protection must be fixed in a way that they cannot be removed without the use of tools.
2 ELECTRIC CONNECTION
2.1 Warnings for the electric connection
- do not use electric or pneumatic screwdrivers on the device terminal board
- if the device has been taken from a cold to hot place, humidity could condense inside; wait about 1 hour before powering it
- make sure that the power supply voltage, the frequency and the operational electric power of the device, correspond with those of the local power supply; see chapter 13
- disconnect the device power supply before proceeding with any type of maintenance
- position the power cables as far away as possible from the signal cables
- for repairs and information regarding the device, contact the EVCO sales network.
3 USER INTERFACE
3.1 Preliminary notes
Operating Statuses:
- “on” state (the device is powered and is on: the regulators can be switched on)
- “stand-by” status (the device is powered but is switched off via software: the regulators are switched off; the possibility to manually switch on/switch off the cell light or auxiliary output depends on param­eter u2)
- the “off” status (the device is not powered).
Hereafter, with the word “start-up” means the passage from “stand-by” status to “on” status; the word “shut­down” means the passage from “on” status to “stand-by” status. When the power is switched back on, the device dis­plays the status that it was in at the time it was discon­nected.
3.2 Device switch-on/off in manual mode
Operating Statuses:
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the key down for 2 s: the LED will switch off/on.
Using the digital inputs it is also possible to remotely switch on/off the device.
3.3 The display
If the device is switched on, during normal operation, the display will show the cell temperature, except during defrosting, when the device will show the temperature established with parameter d6. If the device is switched off, the display will be switched off.
Evap. Fan
Defrosting
earth
Cabinet light
Alarm
(config.)
Equipment
(config.)
EVCO S.p.A. | Codice 104RS200E214 | Page 2 of 8 | PT 24/13 | version 2.1
3.4 Evaporator temperature display
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
Pb2”.
4. Press and release the key
.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key. If the evaporator probe is absent (parameter P3 = 0), the label “Pb2” will not be displayed.
3.5 Condenser temperature display
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
Pb3”.
4. Press and release the
key. To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key. If the third input function is that of the digital input (parameter P4 = 0), the label “Pb3” will not be displayed.
3.6 Activation/deactivation of “overcooling”
function
1. Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or dripping is not in progress and that the evaporator fan is off.
2. Hold the
key down for 4 s: the Overcooling LED will
light up. During the “overcooling” function the working setpoint is reduced by the temperature established with parameter r5; the operation lasts for the amount of time established with parameter r6. During “overcooling” defrosting is never activated; if the defrosting interval expires when the function is in progress, defrosting will be activated at the end of the function.
3.7 Defrosting activation in manual mode
1. Make sure that the keyboard is not locked and that no
other operation is in progress; ensure that the
“overcooling” function is not in progress
2. Hold the
key down for 4 s. If the evaporator probe function is that of the defrosting probe (parameter P3=1) and upon activation of defrosting, the temperature of the evaporator is higher than that established with parameter d2, the defrosting function will not be activated.
3.8 Switch-on/off of the cell light in manual
mode (only if parameter u1 and/or parameter u11 is set at 0)
1. Make sure no procedures are in progress
2. Press and release the
key: the “AUX” LED will
switch on/off. Using the door digital inputs it is also possible to switch on/ off the cell light by remote; see also parameter u2. If parameter u1 is set at 0 (i.e. the utility managed by the fourth output is the cabinet light) and parameter u11 is set at 2 (i.e. the utility managed by the fifth output is the auxiliary output), holding the
key down for 2 s will cause the switch-on/off of the “AUX” LED and of the auxil­iary output.
3.9 Demister resistors switch-on (only if the
parameter u1 and/or parameter u11 is set at
1)
1. Ensure that the device is switched on and that no other
procedure is in progress.
2. Hold the
key down for 2 s: the “AUX” LED will light up and the resistors will be switched on, both for the amount of time established with parameter u6.
Manually switching off the demisting resistors is not permitted (that is, before the time established with parameter u6 expires).
3.10 Switch-on/off of the auxiliary output in manual mode (only if parameter u1 and/or parameter u11 is set at 2)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
key: the “AUX” LED will
switch on/off. Using the digital inputs it is also possible to remotely switch on/off the auxiliary output. If parameter u1 is set at 2 (i.e. the utility managed by the fourth output is the auxiliary output) and parameter u11 is set at 0 (i.e. the utility managed by the fifth output is the cabinet light), holding the
key down for 2 s will cause the switch-on/off of the “AUX” LED and of the cabinet light. If the auxiliary output has been switched on manually, then it can also be switched off manually (similarly, if the auxiliary output has been remotely switched on, then it can only be switched off in the same manner); see also parameter u2.
3.11 Locking/unlocking the keyboard
To lock the keyboard:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 1 s:
the display will show “Loc”.
If the keyboard is locked, the following are not permitted:
- device switch-on/off in manual mode
- display of evaporator temperature (via the procedure
explained in paragraph 3.4)
- display of the condenser temperature (via the procedure
indicated in paragraph 3.5)
- activation/deactivation of “overcooling” function
- manual activation of defrosting
- manual switch on/off of the auxiliary output
- activation of operation for low of high percentage of
relative humidity and learning the kind of operation
- see information regarding the HACCP alarms
- cancellation of HACCP alarm list
- display of compressor operation hours
- cancellation of compressor operation hours
- changing the working setpoint (with the procedure
described in 9.1). The operations cause the display of the label “Loc” per 1 sec. To unlock the keyboard:
1. Hold the
key and thee key down for 1 s: the
display will show the message “UnL” for 1 sec.
3.12 Silencing the buzzer
To lock the keyboard:
1. Make sure no procedures are in progress
2. Press a key (the first pressing of the key will not cause
the effect associated with that key). If the parameter u1 and/or the parameter u11 is set at 3 (i.e. the utility managed by the fourth output and/or the utility managed by the fifth output is the alarm output) and parameter u4 is set at 1, pressing the key will also cause the deactivation of the output. If parameter u9 is set at 0, the buzzer will not be acti­vated.
4 OPERATION DUE TO LOW OR HIGH RELATIVE
HUMIDITY PERCENTAGE (ONLY IF PARAMETER F0 IS ISET AT 5)
4.1 Preliminary notes
During operation for low percentage of relative humidity, the evaporator ventilator will be switched on if the compressor is switched off (parameter F4 determines the amount of time it is switched off while parameter F5 determines the amount of time it is switched on). During operation for a high percentage of relative humidity the evaporator fan is always on.
4.2 Activation of operation for low or high
percentage relative humidity in manual mode.
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
and keys down for 4 s: the display will show “rhL” (operation for low percentage of relative humidity) or “rhH” (operation for high percentage of relative humidity) for 10 sec.
To restore the normal display before the operation is complete:
3. Press a key. Activation of the operation for a low or high percentage of relative humidity can be done using parameter F6. If the parameter F0 is not set at 5, pressing the
and
keys will cause the display of the “- - -“ indication
for 1 s.
4.3 Learning the type of operation in progress
1. Make sure no procedures are in progress
2. Press and release the and keys: the display will show “rhL” (operation for low percentage of rela­tive humidity) or “rhH” (operation for high percentage of relative humidity) for 10 sec.
To restore the normal display before the operation is com­plete:
3. Press a key.
If parameter F0 is not set at 5, pressing the
and
keys will cause:
- the display of the message “- - - -“ for 1 sec if the keyboard is not locked
- display of the label “Loc” for 1 sec if the keyboard is locked..
5 ENERGY SAVING
5.1 Preliminary notes
Once the time you have set with parameter i10 has passed, without activations of the door micro switch input (after the cell temperature has reached the work set-point) the “en­ergy saving” function is activated (until the input is activated again). During function “Energy Saving” the working setpoint is increased of the temperature you have set with parameter r4 and the evaporator fan is turned on cyclically, on condition that parameter F0 has value 1 or 2 (parameter F13 sets the time the fan remains turned off and parameter F14 the time it remains turned on). It is also possible to activate the “energy saving” function in remote mode through the digital inputs (with effect only on the compressor).
6 “HACCP” FUNCTION
6.1 Preliminary notes
The device can memorise the following HACCP alarms:
- minimum temperature alarm (code “AL”)
- maximum temperature alarm (code “AH”)
- door micro switch input alarm (code “id”)
The device supplies the following information for every alarm:
- the critical value
- the duration of the alarm (from 1 min to 99 hours and 59 min, partial if the alarm is in progress).
Code Critical value
AL the minimum temperature of the cell during any
alarm of this type
AH the maximum temperature of the cell during any
alarm of this type
iD the maximum cell temperature during any alarm
of this type; see also parameter i4
The device stored the minimum temperature alarm on condition that the temperature associated to the alarm is that of the cell (parameter A0 = 0). if the device is switched off, no alarms will be stored. The device updates the information regarding the the alarms provided the critical value of the new alarm is more critical than that stored or provided the information has already been displayed. The “HACCP” LED provides information regarding the storage status of the alarms; see paragraph 10.1.
6.2 Display of HACCP alarm information
To begin the procedure:
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
4. Press and release the
or key to select “LS”.
key: the display will show
one of the codes included in the table in paragraph
6.1.
If the device does not have any alarms stored, the label “LS” will not be displayed. To select an alarm:
5. Press and release the
or key (to select, for
example, “AH”).
To see information regarding the alarm:
6. Press and release the
key: the HACCP LED will stop flashing and remain on permanently and the dis­play will show, for example, the following information in succession (for example):
Inform. Part
8.0 the critical value is 8.0 °C/8 °F
dur the display is about to show the alarm duration h01 the alarm lasted for 1 hour (other data continues) n15 the alarm lasted 1 hour and 15 min
AH the alarm selected
the displays each piece of information for 1 s.
EVCO S.p.A. | Codice 104RS200E214 | Page 3 of 8 | PT 24/13 | version 2.1
To exit the information sequence:
7. Press and release the
key: the display will show
the alarm selected (in the example “AH”).
To exit the procedure:
8. Exit the information sequence.
9.1 Press and release the
or key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
9.2 Press and release the
key.
6.3 Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
4. Press and release the
5. Press and release the
or key to select “rLS”. key.
or key within
15 s to set “149”.
6. Press and release the
key or do not operate for 15 sec: the display will show a flashing “- - - -” for 4 sec and the “HACCP” LED switches off, after which the device will exit the procedure.
If the device does not have any alarms stored, the label “rLS” will not be displayed.
7 COMPRESSOR OPERATING HOURS COUNT
7.1 Preliminary notes
The device can memorise up to 9.990 compressor operating hours. The parameter C10 establishes the number of operating hours is higher than the limit at which the need for maintenance is signalled.
7.2 Display of Compressor Operation Hours
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
key or the key to select
CH”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
7.3 Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key for 1 s: the display will show the first
label available.
3. Press and release the
4. Press and release the
5. Press and release the
or key to select “rCH”. key.
or key within
15 s to set “149”.
6. Press and release the
key or do not operate for 15 sec: the display will show “- - -” flashing for 4 sec, after which the device will exit the procedure.
8 SYNCHRONISATION OF DEFROSTING
PERIODS (ONLY IF PARAMETER i0 AND/OR PARAMETER i5 IS SET AT 6)
8.1 Preliminary notes
The activation of defrosting causes the activation of the digital input (at maximum for the time established with parameter d24 or until the conclusion of predripping). If the digital input is connected in parallel to the digital input of other devices configured in the same way, the activation of the input caused the activation of defrosting in the other devices. The devices start dripping simultaneously with the con­clusion of the predripping of the last device to end the same.
9 SETTINGS
9.1 Setting the working setpoint
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Press and release the
key: the LED will
flash.
3. Press and release the
or key within
15 sec; see also parameters r1, r2 and r3
4. Press and release the 15 sec: the
LED will switch off and then the device
key or do not operate for
will exit the procedure.
To exit the procedure before the operation is complete:
5. Do not operate for 15 sec (any changes will be saved).
The working setpoint can also be set via parameter SP.
9.2 Setting the configuration parameters
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 4s:the display will
show “PA”.
3. Press and release the
4. Press and release the
key.
or key within
15 s to set “-19”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
and keys down for 4 s:
the display will show “SP”.
To select a parameter:
7. Press and release the
or key.
To change a parameter:
8. Press and release the
9. Press and release the
key.
or key within
15 sec.
10. Press and release the
key or do not operate for
15 sec.
To exit the procedure:
11. Hold down the
and keys for 4 sec and do not
operate for 60 sec (any changes will be saved). After changing the parameters, suspend power supply flow to the device.
9.3 Restoring the Manufacturer’s Settings
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
and keys down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
or key within
15 s to set “149”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
and keys down for 4 s:
the display will show “dEF”.
7. Press and release the
8. Press and release the
key.
or key within
15 s to set “1”.
9. Press and release the
key or do not operate for 15 sec: the display will show “dEF” flashing for 4 sec, after which the device will exit the proce­dure.
10. Cut the device power supply off. To exit the procedure before the operation is complete:
11. Hold the and key down for 4 s during the proce­dure (i.e. before setting “1”: Restore will not be performed).
Make sure that the manufacturer’s settings are appropriate (see chapter 14).
10 WARNING LIGHTS AND DIRECTIONS
10.1 Signals
LED Part
compressor LED light if the LED is on, then the compressor is on if the LED is flashing:
- the working setpoint is in the process of being changed (via the procedure described in para­graph 9.1)
- a compressor protection will be in progress; see parameters C0, C1, C2, C14, C15, C16 and i7
Defrost LED If it is on:
- defrosting is in progress
- predripping will be in progress; see parameter d16
if the LED is flashing:
- defrosting will be requested but a compressor protection will be in progress; see the param­eters C0, C1 and C2
- dripping will be in progress; see parameter d7
- the refrigerant fluid heating will be in progress; see parameter d15
Evaporator fan LED light If it is on:
- the evaporator fan will be on
if the LED is flashing:
- evaporator fan standstill will be in progress; see parameter F3
AUX Auxiliary LED
If it is on:
- the cell light will have been switched on in manual mode (only if parameter u1 and/or parameter u11 is set at 0)
- the demister resistors will be switched on (only if the parameter u1 and/or parameter u11 is set at 1)
- the auxiliary output will have been switched on in manual mode (only if parameter u1 and/or parameter u11 is set at 2)
- the door resistors will be switched on (only and provided parameter u1 and/or parameter u11 is set at 4)
- the neutral area operating resistors will be activated (only if parameter u1 and/or pa­rameter u11 is set at 5)
- the condenser fan will be on (only if parameter u1 and/or parameter u11 is set at 6)
if the LED is flashing:
- the cell light will have been switched on in remote mode; see parameters i0 and i5 (only if parameter u1 and/or parameter u11 is set at 0)
- the auxiliary output will have been switched on in remote mode; see parameters i0 and i5 (only if parameter u1 and/or parameter u11 is set at 1)
- condenser fan switch-off delay will be in progress; see parameter F12 (only if parameter u1 and/or parameter u11 is set at
6)
HACCP HACCP LED
if it is on, all information regarding HACCP alarms has not been displayed if it is flashing, the device has stored at least one new HACCP alarm if it is off, all information regarding the HACCP alarms has been displayed or the list of alarms has been cancelled maintenance LED if on, compressor maintenance will be requested; see parameter C10 “overcooling” LED if it is on, the “overcooling” function will be in function; see parameters r5 and r6
°C degree Celsius LED
if on, the temperatures will be displayed using the degree Celsius grade unit of measurement; see parameter P2 if flashing, the “energy saving” function is in progress (with effect only on the compressor)
°F degree Fahrenheit LED
if on, the temperatures will be displayed using the degree Fahrenheit grade unit of measurement; see parameter P2 if flashing, the “energy saving” function is in progress (with effect only on the compressor) On/stand-by LED if it is on, the device will be off ( “stand-by” state) if it is off, the device will be on (“on” state)
10.2 Signal Descriptions/Explanations Code Part
rhL operation for a low percentage of relative humidity
in progress
rhH operation for a high percentage of relative humidity
in progress
Loc the keyboard is blocked; see paragraph 3.11
the work setpoint is blocked; see parameter r3
- - - the operation requested is not available
11 ALARMS
11.1 Alarms Code Part
AL Minimum alarm temperatures (HACCP alarms)
Solutions:
- check the temperature associated to the alarm; see parameters A0, A1 and A2
Main consequences:
- if parameter A0 is set at 0, the device will store the alarm
- the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
AH Maximum temperature alarm (HACCP alarms)
Solutions:
- check the cell temperature; see parameters A4 and A5
Main consequences:
- the device will memorise the alarm
- the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
Loading...
+ 5 hidden pages