EVCO EVR274N9 User Manual

Page 1
EVCO S.p.A. | Code 104R200E114 | Page 1 of 10 | PT 14/13 | version 1.1
EVR 200 range
Controllers for cold rooms for bars, refrigerated display cabinets for ice cream/confectionery and small wine cellars
EN ENGLISH
DIMENSIONS AND INSTALLATION Dimensions and installation
The dimensions are expressed in mm (in); panel installation is envisioned, with elastic retainer wings (det. A).
Drill ing te mplate
To make easier a possible removal of the device, slightly bevel the longitudinal inside edges of the drilling template before the installation (det. B and C).
ELECTRIC CONNECTION Electric connection EVR203 / EVR233 / EVR263 / EVR273
Serial port
load
power supply
Door microswitch /multi f.
Electric connection EVR204 / EVR234 / EVR264 / EVR274
Serial port
Door microswitch /multi f.
power supply
Serial port
load 4
defrost
evap. fan
Fourth input
Door microswitch/multif. 1
cell
Door microswitch/multi f. 1
Electric connection EVR221 / EVR231 / EVR261 / EVR271 Electric connection EVR202 / EVR232
power supply
Page 2
EVCO S.p.A. | Code 104R200E114 | Page 2 of 10 | PT 14/13 | version 1.1
IMPORTANT
Read this document thoroughly before installation and be­fore use of the device and follow all recommendations; keep this document with the device for future consultation. Only use the device in the way described in this document; do not use the same as a safety device.
The device must be disposed of in compliance with local Standards regarding the collection of electric and electronic equipment.
1 DIMENSIONS AND INSTALLATION
1.1 Installation warnings
- the thickness of the panel must be between 0.8 and 2.0 mm (0.031 and 0.078 in)
- make sure that the device work conditions (tempera­ture of use, humidity, etc.) lie within the limits indi­cated; see chapter 12
- do not install the device near to any heat sources (heating elements, hot air ducts etc.), equipment containing powerful magnets (large diffusers, etc.), areas affected by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or shocks.
- in compliance with Safety Standards, the device must be installed correctly and in a way to protect against any contact with electric parts; all parts that ensure protection must be fixed in a way that they cannot be removed without the use of tools.
2 ELECTRIC CONNECTION
2.1 Warnings for the electric connection
- do not use electric or pneumatic screwdrivers on the device terminal board
- if the device has been taken from a cold to hot place, humidity could condense inside; wait about 1 hour before powering it
- make sure that the power supply voltage, the frequency and the operational electric power of the device, correspond with those of the local power supply; see chapter 12
- disconnect the device power supply before proceeding with any type of maintenance
- position the power cables as far away as possible from the signal cables
- for repairs and information regarding the device, contact the EVCO sales network.
3 USER INTERFACE
3.1 Preliminary notes
Operating Statuses:
- “on” state (the device is powered and is on: the regulators can be switched on)
- “stand-by” status (the device is powered but is switched off via software: the regulators are switched off; the possibility to manually switch on/switch off the cell light or auxiliary output depends on parameter u2)
- the “off” status (the device is not powered).
Hereafter, with the word “start-up” means the passage from “stand-by” status to “on” status; the word “shutdown” means the passage from “on” status to “stand-by” status. When the power is switched back on, the device displays the status that it was in at the time it was disconnected.
3.2 Device switch-on/off in manual mode
Operating Statuses:
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 2 s: the LED will switch
off/on.
Using the digital inputs it is also possible to remotely switch on/off the device.
3.3 The display
If the device is switched on, during normal operation, the display will show the cell temperature, except during defrosting, when the device will show the temperature established with parameter d6. If the device is switched off, the display will be switched off.
3.4 Display of the evaporator temperature (not
available in EVR221, EVR231, EVR261 and EVR271 models)
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
Pb2”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key. If the evaporator probe is absent (parameter P3 = 0), the label “Pb2” will not be displayed.
3.5 Condenser temperature display (in EVR204,
EVR234, EVR264 and EVR274 models only)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
Pb3”.
4. Press and release the
key. To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key. If the fourth input function is that of the digital input (parameter P4 = 0), the label “Pb3” will not be displayed.
3.6 Mains voltage display (in EVR263, EVR273,
EVR264 and EVR274 models only)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
Ui”.
4. Press and release the
key. To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
3.7 Activation/deactivation of “overcooling” function
1. Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or dripping is not in progress and that the evaporator fan is off.
2. Hold the
key down for 4 s: the Overcooling LED will
light up. During the “overcooling” function the working set-point is reduced by the temperature established with parameter r5; the operation lasts for the amount of time established with parameter r6. During “overcooling” defrosting is never activated; if the defrosting interval expires when the function is in progress, defrosting will be activated at the end of the function.
3.8 Defrosting activation in manual mode
1. Make sure that the keyboard is not locked and that no
other operation is in progress; ensure that the
“overcooling” function is not in progress
2. Hold the
key down for 4 s. If the evaporator probe function is that of the defrosting probe (parameter P3=1) and upon activation of defrosting, the temperature of the evaporator is higher than that established with parameter d2, the defrosting function will not be activated.
3.9 Switch-on/off of the cell light in manual
mode (not available in EVR221, EVR231, EVR261 and EVR271 models and only if parameter u0/u1 is set at 0)
1. Make sure no procedures are in progress
2. Press and release the
key: the “AUX” LED will
switch on/off. Using the door digital inputs it is also possible to switch on/ off the cell light by remote; see also parameter u2.
3.10 Switch-on of demister resistors (only in
EVR202, EVR232, EVR204, EVR234, EVR264 and EVR274 models and only if parameter u0/u1 is set at 1)
1. Ensure that the device is switched on and that no other
procedure is in progress.
2. Hold the
key down for 2 s: the “AUX” LED will light up and the resistors will be switched on, both for the amount of time established with parameter u6.
Manually switching off the demisting resistors is not permitted (that is, before the time established with parameter u6 expires).
3.11 Switch-on/off of auxiliary output in manual mode (only in EVR202, EVR232, EVR204, EVR234, EVR264 and EVR274 models and only if parameter u0/u1 is set at 2)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
key: the “AUX” LED will
switch on/off. Using the digital inputs it is also possible to remotely switch on/off the auxiliary output.
3.12 Locking/unlocking the keyboard
To lock the keyboard:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 1 s:
the display will show “Loc”. If the keyboard is locked, the following are not permitted:
- device switch-on/off in manual mode
- display of evaporator temperature (via the procedure
explained in paragraph 3.4)
- display of the condenser temperature (via the procedure
indicated in paragraph 3.5)
- display the mains voltage
- activation/deactivation of “overcooling” function
- manual activation of defrosting
- manual switch on/off of the auxiliary output
- activation of operation for low of high percentage of
relative humidity and learning the kind of operation
- see information regarding the HACCP alarms
- cancellation of HACCP alarm list
- display of compressor operation hours
- cancellation of compressor operation hours
- changing the working set-point (with the procedure
described in 8.1). The operations cause the display of the label “Loc” per 1 sec. To unlock the keyboard:
1. Hold the
key and thee key down for 1 s: the
display will show the message “UnL” for 1 sec.
3.13 Silencing the buzzer
To lock the keyboard:
1. Make sure no procedures are in progress
2. Press a key (the first pressing of the key will not cause
the effect associated with that key). If parameter u0/u1 is set at 3 (i.e. the utility managed by the fourth output is the alarm output ) and parameter u4 is set at 1, pressing the key will also cause the deactivation of the output. If parameter u9 is set to 0, the buzzer will not be activated.
4 OPERATION DUE TO LOW OR HIGH
PERCENTAGE OF RELATIVE HUMIDITY (NOT AVAILABLE IN EVR221, EVR231, EVR261 AND EVR271 MODELS AND ONLY IF PARAMETER F0 IS SET AT 5)
4.1 Preliminary notes
During operation for low percentage of relative humidity, the evaporator ventilator will be switched on if the compressor is switched off (parameter F4 determines the amount of time it is switched off while parameter F5 determines the amount of time it is switched on). During operation for a high percentage of relative humidity the evaporator fan is always on.
4.2 Activation of operation for low or high
percentage relative humidity in manual mode.
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key and thee key down for 4 s: the display will show “rhL” (operation for low percentage of relative humidity) or “rhH” (operation for high per­centage of relative humidity) for 10 sec.
To restore the normal display before the operation is complete:
3. Press a key. Activation of the operation for a low or high percentage of relative humidity can be done using parameter F6. If the parameter F0 is not set at 5, pressing the and keys will cause the display of the “- - -“ indication for 1 s.
4.3 Learning the type of operation in progress
1. Make sure no procedures are in progress
2. Press and release the key and the.. key: the display will show “rhL” (operation for low percentage of relative humidity) or “rhH” (operation for high percentage of relative humidity) for 10 sec.
To restore the normal display before the operation is complete:
3. Press a key.
If parameter F0 is not set at 5, pressing the
and
keys will cause:
- the display of the message “- - - -“ for 1 sec if the keyboard is not locked
- display of the label “Loc” for 1 sec if the keyboard is locked.
Page 3
EVCO S.p.A. | Code 104R200E114 | Page 3 of 10 | PT 14/13 | version 1.1
5 ENERGY SAVING
5.1 Preliminary notes
Once the time you have set with parameter i10 has passed, without activations of the door microswitch input (after the cell temperature has reached the work set-point) the “en­ergy saving” function is activated (until the input is activated again). During function “Energy Saving” the working set-point is increased of the temperature you have set with parameter r4 and the evaporator fan is turned on cyclically, on condition that parameter F0 has value 1 or 2 (parameter F13 sets the time the fan remains turned off and parameter F14 the time it remains turned on). It is also possible to activate the “energy saving” function in remote mode through the digital inputs (with effect only on the compressor).
6 “HACCP” FUNCTION
6.1 Preliminary notes
The device can memorise the following HACCP alarms:
- minimum temperature alarm (code “AL”)
- maximum temperature alarm (code “AH”)
- door microswitch input alarm (code “id”) The device supplies the following information for every alarm:
- the critical value
- the duration of the alarm (from 1 min to 99 hours and 59 min, partial if the alarm is in progress).
Code Critical value
AL the minimum temperature of the cell during any
alarm of this type
AH the maximum temperature of the cell during any
alarm of this type
id the maximum cell temperature during any alarm
of this type; see also parameter i4
The device stored the minimum temperature alarm on con­dition that the temperature associated to the alarm is that of the cell (parameter A0 = 0). if the device is switched off, no alarms will be stored. The device updates the information regarding the alarms provided the critical value of the new alarm is more critical than that stored or provided the information has already been displayed. The “HACCP” LED provides information regarding the storage status of the alarms; see paragraph 9.1.
6.2 Display of HACCP alarm information
To begin the procedure:
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
LS”.
4. Press and release the
key: the display will show
one of the codes included in the table in paragraph 6.1.
If the device does not have any alarms stored, the label “LS” will not be displayed. To select an alarm:
5. Press and release the
or key (to select, for
example, “AH”).
To see information regarding the alarm:
6. Press and release the
key: the HACCP LED will stop flashing and remain on permanently and the dis­play will show, for example, the following information in succession (for example):
Inform. Part
8.0 the critical value is 8.0 °C/8 °F
dur the display is about to show the alarm duration h01 the alarm lasted for 1 hour (other data continues) n15 the alarm lasted 1 hour and 15 min
AH the alarm selected
the displays each piece of information for 1 s. To exit the information sequence:
7. Press and release the
key: the display will show
the alarm selected (in the example “AH”).
To exit the procedure:
8. Exit the information sequence.
9.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
9.2 Press and release the
key.
7.3 Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
rLS”.
4. Press and release the
key.
5. Press and release the
key or the key within
15 s to set “149”.
6. Press and release the
key or do not operate for 15 sec: the display will show a flashing “- - - -” for 4 sec and the “HACCP” LED switches off, after which the device will exit the procedure.
If the device does not have any alarms stored, the label “rLS” will not be displayed.
7 COMPRESSOR OPERATING HOURS COUNT
7.1 Preliminary notes
The device can memorise up to 9.990 compressor operating hours. The parameter C10 establishes the number of operating hours is higher than the limit at which the need for maintenance is signalled.
7.2 Display of Compressor Operation Hours
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the key down for 1 s: the display will show the first label available.
3. Press and release the
key or the key to select
CH”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
7.3 Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
rCH”.
4. Press and release the
5. Press and release the
key.
key or the key within
15 s to set “149”.
6. Press and release the
key or do not operate for 15 sec: the display will show “- - -” flashing for 4 sec, after which the device will exit the procedure.
8 SETTINGS
8.1 Setting the working set-point
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Press and release the
3. Press and release the
key: the LED will flash.
or key within
15 sec; see also parameters r1, r2 and r3
4. Press and release the 15 sec: the
LED will switch off and then the device
key or do not operate for
will exit the procedure.
To exit the procedure before the operation is complete:
5. Do not operate for 15 sec (any changes will be saved).
The working set-point can also be set via parameter SP.
8.2 Setting the configuration parameters
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
key or the key within
15 s to set “-19”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
key and the key down for 4 s:
the display will show “SP”.
To select a parameter:
7. Press and release the
key or the key.
To change a parameter:
8. Press and release the
9. Press and release the
key.
key or the key within
15 sec.
10. Press and release the
key or do not operate for
15 sec.
To exit the procedure:
11. Hold down the
and keys for 4 sec and do not
operate for 60 sec (any changes will be saved).
After changing the parameters, suspend power supply flow to the device.
8.3 Restoring the Manufacturer’s Settings
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
key or the key within
15 s to set “149”.
5. Press and release the key or do not operate for 15 sec.
6. Hold the
key and the key down for 4 s:
the display will show “dEF”.
7. Press and release the
8. Press and release the
key.
key or the key within
15 s to set “1”.
9. Press and release the
key or do not operate for 15 sec: the display will show “dEF” flashing for 4 sec, after which the device will exit the procedure.
10. Cut the device power supply off. To exit the procedure before the operation is complete:
11. Hold the
and key down for 4 s during the procedure (i.e. before setting “1”: Restore will not be performed).
Make sure that the manufacturer’s settings are appropriate (see chapter 13).
9 WARNING LIGHTS AND DIRECTIONS
9.1 Signals LED Part
compressor LED light if the LED is on, then the compressor is on if the LED is flashing:
- the working set-point is in the process of being changed (via the procedure described in paragraph 8.1)
- a compressor protection will be in progress; see parameters C0, C1, C2, C14, C15, C16 and i7
Defrost LED If it is on:
- defrosting is in progress
- predripping will be in progress; see parameter d16
If the LED is flashing:
- defrosting will be requested but a compres sor protection will be in progress; see the parameters C0, C1 and C2
- dripping will be in progress; see parameter d7
- the refrigerant fluid heating will be in progress; see parameter d15
Evaporator fan LED light if it is on:
- the evaporator fan will be on
If the LED is flashing:
- evaporator fan standstill will be in progress; see parameter F3
AUX Auxiliary LED
If it is on:
- the cell light will have been switched on in manual mode (only if parameter u0/u1 is set at 0)
- the demister resistors will be switched on (only if the parameter u0/u1 is set at 1)
- the auxiliary output will have been switched on in manual mode (only if parameter u0/u1
is set at 2)
- the door resistors will be switched on (only if the parameter u0/u1 is set at 4)
- the evaporator valve will be activated (only if parameter u0/u1 is set at 5)
- the condenser fan will be on (only if param­eter u0/u1 is set at 6)
if the LED is flashing:
- the cell light will have been switched on in remote mode; see parameters i0 and i5 (only if parameter u0/u1 is set at 0)
- the auxiliary output will have been switched on in remote mode; see parameters i0 and i5 (only if parameter u0/u1 is set at 1)
HACCP HACCP LED
if it is on, all information regarding HACCP alarms has not been displayed if it is flashing, the device has stored at least one new HACCP alarm if it is off, all information regarding the HACCP alarms has been displayed or the list of alarms has been cancelled maintenance LED if on, compressor maintenance will be requested; see parameter C10 “overcooling” LED if it is on, the “overcooling” function will be in function; see parameters r5 and r6
°C degree Celsius LED
if on, the temperatures will be displayed using the degree Celsius grade unit of measurement; see parameter P2 if flashing, the “energy saving” function is in progress (with effect only on the compressor)
Page 4
EVCO S.p.A. | Code 104R200E114 | Page 4 of 10 | PT 14/13 | version 1.1
°F degree Fahrenheit LED
if on, the temperatures will be displayed using the degree Fahrenheit grade unit of measurement; see parameter P2 if flashing, the “energy saving” function is in progress (with effect only on the compressor) On/stand-by LED if it is on, the device will be off ( “stand-by” state) if it is off, the device will be on (“on” state)
9.2 Signal Descriptions/Explanations Code Part
rhL operation for a low percentage of relative humidity
in progress
rhH operation for a high percentage of relative humidity
in progress
Loc the keyboard is blocked; see paragraph 3.12
the work set-point is blocked; see parameter r3
- - - the operation requested is not available
10 ALARMS
10.1 Alarms Code Part
AL Minimum alarm temperatures (HACCP alarms)
Solutions:
- check the temperature associated to the alarm; see parameters A0, A1 and A2
Main consequences:
- if parameter A0 is set to 0, the device will store the alarm
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
AH Maximum temperature alarm (HACCP alarms)
Solutions:
- check the cell temperature; see parameters A4 and A5
Main consequences:
- the device will memorise the alarm
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
id Door microswitch input alarm (HACCP alarms)
Solutions:
- check the causes of the activation of the in­put; see parameters i0, i1, i5 and i6
Main consequences:
- the effect established with the parameters i0 and i5
- if parameter is set to 1, the device will store the alarm, provided parameter i2 is not set to -1
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
iA Multifunction input alarm
Solutions:
- check the causes of the activation of the in­put; see parameters i0, i1, i5 and i6
Main consequences:
- the effect established with the parameters i0 and i5
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
iSd Pressure switch alarm
Solutions:
- check the causes of the activation of the in­put; see parameters i0, i1, i5, i6, i7, i8 and i9
- switch off and re-start the device or suspend the power supply
Main consequences:
- the regulators will switch off
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
UA Mains voltage alarm
Solutions:
- check the mains voltage; see parameters C14, C15 and C16
Main consequences:
- the compressor will be switched off and will not be switched on
CF Compressor forced switch-on alarm
Solutions:
- check the mains voltage; see parameter C18
Main consequences:
- the device will perform forced compressor switch-on; the device restores normal display when the temperature of the cell reaches the work set-point.
COH Condenser overheated alarm.
Solutions:
- check the condenser temperature; see pa­rameter C6
Main consequences:
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
- the condenser fan will be on (only if param­eter u0/u1 is set at 6)
CSd Condenser overheated alarm.
Solutions:
- check the condenser temperature; see pa­rameter C7
- switch the device off and back on again: if when the device is switched back on, the temperature of the condenser is still higher than that established in parameter C7, dis­connect the power supply and clean the con­denser
Main consequences:
- the compressor and the evaporator fan will be switched off
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
- the condenser fan will be on (only if param­eter u0/u1 is set at 6)
dFd Defrosting alarm switched off because maximum
time has been reached Solutions:
- heck the integrity of the evaporator probe; see parameters d2, d3 and d11
- press a key to restore normal display
Main consequences:
- the device will continue to operate normally.
When the cause of the alarm disappears, the device restores normal operation, except for the following alarms:
- pressure switch alarm (code “iSd”) which requires the switching off of the device or the temporary suspension of the power supply
- compressor blocked by condenser temperature alarm (code “CSd”) which requires the switching off of the device or the temporary suspension of the power supply
- the compressor forced switch-on alarm (code “CF”) that requires the cell temperature to have reached the work set-point
- Defrosting alarm switched off because maximum time has been reached (code “dFd”) which requires the pressing of a key.
11 ERRORS
11.1 Errors
Code Part
Pr1 Cell probe error
Solutions:
- check that the probe is the PTC or NTC type; see parameter P0
- - check the device-probe connection
- check the cell temperature
Main consequences:
- compressor activity will depend on param­eters C4 and C5
- the defroster will not be activated
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
- the door resistors will be switched off (only if the parameter u0/u1 is set at 4)
- the evaporator valve will be deactivated (only if parameter u0/u1 is set at 5)
Pr2 Evaporator probe error
Solutions:
- the same as the preceding case but with re­spect to the evaporator probe
Main consequences:
- if parameter P3 is set to 1, the defrosting period will last for the amount of time set with parameter 3
- if parameter P3 is set to 1 and parameter d8 is set to 2 or to 3, the device will operate as if parameter d8 were set to 0
- if parameter F0 is set to 3 or 4, the device will operate as if the parameter were set to 2
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
Pr3 Condenser probe error.
Solutions:
- the same as the preceding case but with re­spect to the condenser probe
Main consequences:
- condenser overheated alarm (code “COH”) will not be activated
- the compressor blocked alarm (“CSd” code) will never be activated
- the alarm output will be activated (only if parameter u0/u1 is set at 3)
- the condenser fan will operate parallel tot the compressor (only if parameter u0/u1 is set at
6)
When the problem that caused the alarm disappears, the device is restored to normal operation.
12 TECHNICAL DATA
12.1 Technical data Purpose of the command device: operating command
device. Construction of the command device: built-in electronic device.
Case: grey self-extinguishing. Dimensions: 180.0 x 38.0 x 44.0 mm (7.086 x 1.496 x
1.732 in; L x H x D). Method of mounting the command device: panel, with elastic retaining wings.
Protection rating: IP55. Connections: 6.3 mm faston (0.248 in, power supply and
outputs), removable screw terminal board (inputs), 6 pole connector (serial port). The maximum length of the analogue input and digital input connection cables must be less than 10 m (32.808 ft).
Operating temperature: from 0 to 55 °C (from 32 to 131 °F). Storage temperature:from -25 to 70 °C (from -13 to
158 °F). Humidity for use: from 10% to 90% relative humidity without condensate.
Command device pollution situation: 2. Power supply (according to the model):
- 115... 230 VAC (+10% -15%), 50/60 Hz, 5.5 VA max
- 230 VAC (+10% -15%), 50/60 Hz, 3 VA max.
Rated impulse voltage: 4K V. Overvoltage category:
- II in models with power supply of 115... 230 VAC
- III in models with power supply of 230 VAC.
Class and structure of software: A. Analogue inputs:
- 1 input (cell probe) in EVR221, EVR231, EVR261 and EVR271 models, can be set via configuration parameter for PTC/NTC probes
- 2 inputs (cell probe and evaporator probe) in EVR202, EVR232, EVR203, EVR233, EVR263, EVR273, EVR204, EVR234, EVR264 and EVR274 models, can be set via configuration parameter for PTC/NTC probes.
PTC type analogue inputs (990 @ 25°C, 77°F) Type of sensor: KTY 81-121. Measurement field: from -50 to 150 °C
(from -58 to 302°F). Resolution: 0.1 °C (1 °F). Protection: none. PTC type analogue inputs NTC (10K @ 25°C, 77°F) Type of sensor: ß3435. Measurement field: from -50 to 105 °C (from -40
to
220 °C). Resolution: 0.1 °C (1 °F). Protection: none. Digital inputs: 1 input (door micro/multi-function 1 switch), which can be set via configuration parameter due to normally open contact/normally closed contact (free of voltage contact, 5 VDC, 2 mA) Digital inputs Power: none. Protection: none.
Other inputs (in EVR204, EVR234, EVR264 and EVR274 models only): 1 input that can be set via
configuration parameter for analogue input (condenser probe)/digital input (door microswitch/multifunction 2), with the same technical features illustrated previously.
Displays: custom 3 digit display with function icon. Digital outputs:
1 output (electromechanical relay) in EVR221, EVR231, EVR261 and EVR271 models
- 1 x 30 A res. output @ 250 VAC type SPST (K1) for
compressor management in models with power supply of 115... 230 VAC, 1 x 16 A in-rush res. output @ 250 VAC type SPST (K1) for compressor management in
models with power supply of 230 VAC. 2 outputs (electromechanical relays) in EVR202 and EVR232 models
- 1 x 30 A res. output @ 250 VAC type SPST (K1) for
compressor management in models with power supply
of 115... 230 VAC, 1 x 16 A in-rush res. output @ 250
VAC type SPST (K1) for compressor management in
models with power supply of 230 VAC
- 1 x 8 A res. output @ 250 VAC type SPDT (K2) for
management of the cell light, demisting resistors, aux.
output, alarm output, door resistors, evaporator valve,
evaporator fan or defrost.
Page 5
EVCO S.p.A. | Code 104R200E114 | Page 5 of 10 | PT 14/13 | version 1.1
3 outputs (electromechanical relays) in EVR203, EVR233, EVR263 and EVR273 models
- 1 x 30 A res. output @ 250 VAC type SPST (K1) for compressor management in models with power supply of 115... 230 VAC, 1 x 16 A in-rush res. output @ 250 VAC type SPST (K1) for compressor management in models with power supply of 230 VAC
- 1 x 8 A res. output @ 250 VAC type SPDT (K2) for cell light or defrosting management
- 1 x 5 A res. output @ 250 VAC type SPST (K3) for management of the evaporator fan.
4 outputs (electromechanical relays) in EVR204, EVR234, EVR264 and EVR274 models
- 1 x 30 A res. output @ 250 VAC type SPST (K1) for compressor management in models with power supply of 115... 230 VAC, 1 x 16 A in-rush res. output @ 250 VAC type SPST (K1) for compressor management in
- 1 x 8 A res. output @ 250 VAC type SPDT (K2) for defrosting management
- 1 x 5 A res. output @ 250 VAC type SPST (K3) for management of the evaporator fan
- 1 x 8 A res. output @ 250 VAC type SPST (K4) for management of the cell light, demisting resistors, aux. output, alarm output, door resistors, evaporator valve or condenser fan.
The maximum load current allowed is 10 A.
Type 1 or Type 2 actions: Type 1. Complementary features of Type 1 or Type 2 actions: C. Communication port: 1 x TTL serial port with MODBUS
communication protocol (for EVKEY programming key and other EVCO products). Operation with EVT100 remote indicator is only allowed in models with power supply of 115... 230 VAC. Signal buzzer and alarm: on request.
models with power supply of 230 VAC
13 WORKING SET-POINT AND CONFIGURATION PARAMETERS
13.1 Working set-point
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 WORKING SET-POINT
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
r1 r2 °C/°F (1) -18,0 -18,0 0,0 -18,0 -18,0 -18,0 -18,0 working set-point; see also r0
13.2 Configuration parameters
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 WORKING SET-POINT
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
SP r1 r2 °C/°F (1) -18,0 -18,0 0,0 -18,0 -18,0 -18,0 -18,0 working set-point; see also r0
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 MEASUREMENT INPUTS
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274 CA1 -25 25,0 °C/°F (1) 0,0 0,0 0,0 0,0 0,0 0,0 0,0 offset cell probe CA2 -25 25,0 °C/°F (1)not avail.not avail. 0,0 0,0 0,0 0,0 0,0 offset evaporator probe CA3 -25 25,0 °C/°F (1)not avail.not avail.not avail. not avail.not avail. 0,0 0,0 offset condenser probe
P001- - -1111111probe type
0 = PTC 1 = NTC
P101- - -1111111degree Celsius decimal point (during normal operation)
1 = YES
P201- - -0000000temperature unit of measurement (2)
0=°C 1=°F
P3 0 2 - - - not avail.not avail. 11111evaporator probe function
0 = probe absent 1 = defrosting probe and probe for evaporator fan thermostating 2 = probe for evaporator fan thermosatating
P4 0 1 - - - not avail.not avail.not avail.not avail.not avail. 1 1 fourth input function
0 = digital input (multi-function input 2) 1 = analogue input (condenser probe)
P6 0 4 - - - 0 0 reserved 0000value displayed by the remote indicator (not significant in models with 230 VAC
power supply) 0 = cell temperature 1 = work set-point 2 = evaporator temperature 3 = “cell temperature - evaporator temperature” 4 = condenser temperature (only if P4 = 1)
P8 0 250 0.1 s 5555555delay displaying temperature variation detected by the probes
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 MAIN REGULATOR
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
r0 0,1 (3) 15,0 °C/°F (1) 2,0 2,0 2,0 2,0 2,0 2,0 2,0 working set-point differential r1 -99 r2 °C/°F (1) -50 -50 -50 -50 -50 -50 -50 minimum working set-point r2 r1 99,0 °C/°F (1) 50,0 50,0 50,0 50,0 50,0 50,0 50,0 maximum working set-point r301- - -0000000locking of working set-point calibration (using the procedure described in paragraph
9.1)
1 = YES r4 0,0 99,0 °C/°F (1) 0,0 0,0 0,0 0,0 0,0 0,0 0,0 increase in temperature during “energy saving” function; see also i0, i5 and i10 r5 0,0 99,0 °C/°F (1) 0,0 0,0 0,0 0,0 0,0 0,0 0,0 decrease in temperature during “overcooling” function; see also r6 r6 0 240 min 30 30 30 30 30 30 30 duration of “overcooling” function; see also r5 r8 0 1 - - - 0 0 0 not avail.not avail. not avail.not avail. operation in cooling or heating (4)
0 = for cooling
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 COMPRESSROR PROTECTION SYSTEM
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274 C00240min0000000delay in switching on of compressor after the device switches on (5) C10240min5555555minimum time between two consecutive compressor start-ups; also delay in com-
pressor start-up after conclusion of cell probe error (code “Pr1”) (6) (7) C20240min3333333minimum compressor switch-off duration; see also C18 (6) (8) C30240s0000000minimum duration of compressor switch on time C4 0 240 min 10 10 10 10 10 10 10 duration of compressor switch off during cell probe error (code “Pr1”); see also C5 C5 0 240 min 10 10 10 10 10 10 10 duration of compressor switch on during cell probe error (code “Pr1”); see also C4 C6 0,0 199 °C/°F (1)not avail.not avail.not avail.not avail.not avail. 80,0 80,0 condenser temperature is higher than that at which the condenser overheating alarm
is activated (code “COH”) (9) C7 0,0 199 °C/°F (1)not avail.not avail.not avail.not avail.not avail. 90,0 90,0 condenser temperature is higher than the limit at which the compressor blocked
alarm is activated (code “CSd”) C8 0 15 min not avail.not avail.not avail.not avail.not avail. 1 1 blocked compressor alarm delay (“CSd” code) (10)
C10099910 h0000000number of operating hours is higher than the limit at which the need for maintenance
is signalled
0 = function absent
C14 0 300 V not avail. 200 not avail.not avail. 200 not avail. 200 mains voltage, below which the compressor is not switched on C15 0 C14 V not avail. 190 not avail.not avail. 190 not avail. 190 mains voltage below which the compressor is switched off; see also C17 C16 C14 300 V not avail. 255 not avail.not avail. 255 not avail. 255 mains voltage above which the compressor is switched off or is not switched on; see
also C17
Page 6
EVCO S.p.A. | Code 104R200E114 | Page 6 of 10 | PT 14/13 | version 1.1
C17 0 60 s not avail. 5 not avail.not avail. 5 not avail. 5 consecutive minimum duration of mains voltage permanence below C15 or above
C16, such to cause switch-off of the compressor
C18 0 60 - - - not avail. 5 not avail.not avail. 5 not avail. 5 consecutive number of compressor switch ons aborted due to mains voltage outside
of C14, C15 or C16, such to cause forced compressor switch-on (11)
0 = C4, C5 and C6 will not have effect
oo = the device will never perform forced compressor switch on
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 DEFROSTING
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
d0099h8888888if d8 = 0, 1 or 2, defrosting interval (12)
0 = interval defrosting will never be activated
if d8 = 3, maximum defrost interval
d1 0 2 - - - not avail.not avail. 00000type of defrosting
0=
ELECTRIC - during defrosting the compressor will remain off and the defrosting output will be activated; evaporator fan activity will depend on parameter F2
1=
BY HOT GAS - during defrosting the compressor will be switched on and the defrosting output will be activated; evaporator fan activity will depend on parameter F2
2=
VIA STOPPING OF COMPRESSOR - during defrosting the compressor will remain switched off and the defrosting output will remain deactivated;
evaporator fan activity will depend on parameter F2 d2 -99 99,0 °C/°F (1)not avail.not avail. 2,0 2,0 2,0 2,0 2,0 temperature at end of defrosting (only if P3 = 1); see also d3 d3 0 99 min 30 30 30 30 30 30 30 se P3 = 0 or 2, defrosting duration
se P3 = 1, maximum defrosting duration; see also d2 0 = defrosting will not be activated
d401- - -0000000defrosting on device switch-on (5)
1 = YES
d5099min0000000if d4 = 0, minimum time between switching on of device and activation of defrost-
ing; see also i0 and i5 (5) if d4 = 1, delay in activation of defrosting after device is switched on ; see also i0 and i5 (5)
d601- - -1111111temperature displayed during defrosting
0 = cell temperature 1 = if at the time of defrosting activation, the cell temperature is lower than the
“working set-point + r0”, at most “working set- point + r0”; if at the time
of defrosting activation, the cell temperature is higher than the “working
set-point + r0”, at most the cell temperature when defrosting is activated d7 0 15 min not avail.not avail. 22222dripping duration (during dripping the compressor will remain switched off and the
defrosting output will remain deactivated; if d16 = 0, evaporator fan activity will depend on parameter F2; if d16 0, the evaporator fan will remain switched off)
d803 (14)- - -0000000defrosting activation methods
0=
AT INTERVALS - defrosting will be activated once the device has altogether
been running for time d0
1=
AT INTERVALS - FOR COMPRESSOR SWITCH-ON - defrosting will be acti-
vated once the compressor has altogether been switched on for time d0
2=
AT INTERVALS - FOR EVAPORATOR TEMPERATURE - defrosting will be
activated when the evaporator temperature has remained below the tem-
perature d9 for a total time of d0 (15)
3=
ADAPTABLE - defrosting will be activated at intervals, whose duration will
each time depend on the duration of compressor switch-ons and the
evaporator temperature; see also d18, d19 and d22 (15) d9 -99 99,0 °C/°F (1)not avail.not avail. 0,0 0,0 0,0 0,0 0,0 evaporator temperature is higher than that at which the defrost interval counter is
suspended (only if d8 = 2)
d11 0 1 - - - not avail.not avail. 00000enabling of defrosting alarm concluded for maximum duration (code “dFd”; only if
P3 = 1 and in absence of an evaporator probe error (code “Pr2”) 1 = YES
d15 0 99 min not avail.not avail. 00000minimum time that the compressor must be switched on before defrosting can be
activated (only if d1 = 1) (16)
d16 0 99 min not avail.not avail. 00000predripping duration (during predripping the compressor will remain switched off, the
defrosting output will be activated and the evaporator fan will remain switched off)
d18 0 999 min not avail.not avail. 40 40 40 40 40 defrosting interval (only if d8 = 3; defrosting will be activated when the compressor
has been on totally, with the evaporator temperature below that of d22, for time d18) 0 = defrosting will never be activated due to the effect of this condition
d19 0,0 40,0 °C/°F (1)not avail.not avail. 3,0 3,0 3,0 3,0 3,0 evaporator temperature above which the defrost is activated (relative to the evapo-
rator temperatures average, or “evaporator temperatures average - d19”) (only if d8 = 3)
d20 0 500 min not avail.not avail. 180 180 180 180 180 minimum consecutive time the compressor must be switched on such as to provoke
the defrost activation 0 = defrosting will never be activated due to the effect of this condition
d22 0,0 10,0 °C/°F (1)not avail.not avail. 2,0 2,0 2,0 2,0 2,0 evaporator temperature above which the defrosting interval is suspended (relative
to the evaporator temperatures average, or “evaporator temperatures average + d22”) (only if d8 = 3); also look at d18
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 TEMPERATURE ALARMS
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
A0 0 1 - - - not avail.not avail. 00000temperature associated with the minimum temperature alarm (code “AL”)
0 = cell temperature 1 = evaporator temperature (17)
A1 -99 99,0 °C/°F (1) -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 temperature below that at which the minimum temperature alarm is activated (code
AL”); see also A0, A2 and A11
A202- - -1111111type of minimum temperature alarm (code “AL”)
0 = alarm absent 1 = relative to working set-point (that is “working set-point - A1”; consider A1
without sign)
2 = absolute (that is A1)
A4 -99 99,0 °C/°F (1) 10,0 10,0 10,0 10,0 10,0 10,0 10,0 temperature higher than that at which the maximum temperature alarm is activated
(code “AH”); see also A5 and A11
A502- - -1111111type of maximum temperature alarm (code “AH”)
0 = alarm absent 1 = relative to working set-point (that is “working set-point + A4”; consider A1
without sign))
2 = absolute (that is A4)
Page 7
EVCO S.p.A. | Code 104R200E114 | Page 7 of 10 | PT 14/13 | version 1.1
A6 0 240 min 120 120 120 120 120 120 120 delay in maximum temperature alarm (code “AH”) after the device is switched on
(5) A7 0 240 min 15 15 15 15 15 15 15 temperature alarm delay (code “AL” and code “AH”) A8 0 240 min 15 15 15 15 15 15 15 delay in maximum temperature alarm (code “AH”) from the conclusion of evapora-
tor fan standstill (18) A9 0 240 min 15 15 15 15 15 15 15 delay in maximum temperature alarm (code “AH”) following the deactivation of the
door microswitch input (19)
A11 0,1 (3) 15,0 °C/°F (1) 2,0 2,0 2,0 2,0 2,0 2,0 2,0 differential of parameters A1and A4
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 EVAPORATOR FAN AND CONDENSER FAN
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
F0 0 5 - - - not avail.not avail. 11111evaporator fan activity during normal operation
0 = switched off
1 = switched on; see also F13, F14 and i10 (20)
2 = in parallel with the compressor; see also F9, F13, F14 and i10 (21)
3 = depending on F1; see also F9, F13 and F14 (22) (23)
4 = switched off if the compressor is switched off, dependent on F1 if the
compressor is switched on; see also F9 (22)
5 = dependent on F6; see also F9 F1 -99 99,0 °C/°F (1)not avail.not avail. -1,0 -1,0 -1,0 -1,0 -1,0 evaporator temperature above the limit at which the evaporator fan is switched off
(only if F0 = 3 or 4); see also F8 F2 0 2 - - - not avail.not avail. 00000evaporator fan activity during defrosting and dripping
0 = switched off
1 = switched on (setting parameter d7 to 0 is recommended)
2 = dependent on F0 F3 0 15 min not avail. not avail.not avail. 2222maximum duration of evaporator fan deactivation; see also F7 (during evaporator
fan deactivation the compressor can be switched on, the defrosting output will
remain deactivated and the evaporator fan will remain switched off) F4 0 240 s not avail.not avail. 60 60 60 60 60 time duration that evaporator fan is switched off during operation for a low percent-
age of relative humidity when the compressor is switched off; see also F5 (only if
F0 = 5) F5 0 240 s not avail.not avail. 10 10 10 10 10 time duration that evaporator fan is switched on during operation for a low percent-
age of relative humidity when the compressor is switched off; see also F4 (only if
F0 = 5) F6 0 1 - - - not avail.not avail. 00000operation for low or high percentage of relative humidity (only if F0 = 5) (25)
0=
LOW RELATIVE HUMIDITY - the evaporator fan will operate in parallel with the compressor; see also F4 and F5
1=HIGH RELATIVE HUMIDITY - the evaporator fan will always be switched on F7 -99 99,0 °C/°F (1)not avail.not avail.not avail. 5,0 5,0 5,0 5,0 evaporator temperature below limit at which the evaporator fan is deactivated
(relative to working set-point, that is “working set-point + F7”); see also F3 F8 0,1 (3) 15,0 °C/°F (1)not avail.not avail. 2,0 2,0 2,0 2,0 2,0 parameter F1differential F9 0 240 s not avail.not avail. 00000delay in the switching off of evaporator fan following the switching off of the
compressor (only if F0 = 2, 3, 4 and 5)
F11 0,0 99,0 °C/°F (1)not avail.not avail.not avail.not avail.not avail. 15,0 15,0 temperature of the condenser above which the condenser fan is switched on (“F11
+ 2.0 °C/4 °F, only if u0/u1 = 6) (26) (27)
F12 0 240 s not avail. not avail.not avail.not avail.not avail. 30 30 delay in the switching off of condenser fan following the switching off of the
compressor (only if P4 = 0 and u0/u1 = 6)
F13 0 240 10 s not avail.not avail. 30 30 30 30 30 time the evaporator fan remains turned off during function “energy saving”; see also
F14 and i10 (only if F0 = 1, 2, 3 or 4)
F14 0 240 10 s not avail.not avail. 30 30 30 30 30 time the evaporator fan remains turned on during function “energy saving”; see also
F13 and i10 (only if F0 = 1, 2, 3 or 4)
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 DIGITAL INPUTS
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
i0 0 7 - - - 4 4 not avail.not avail.not avail.not avail.not avail. effect caused by the activation of the door microswitch/multifunction 1 input; see
also i4 (28)
0 = no effect
1=
DOOR MICROSWITCH - COMPRESSOR SWITCH-OFF - the compressor will be switched off (at maximum for time i3 or until the input is deactivated) (29)
2=
DOOR MICROSWITCH - ACTIVATION OF DOOR MICROSWITCH INPUT ALARM
- once time i2 has passed the display will show the flashing code “id” and the buzzer will be activated (until the input is deactivated)
3=
MULTIFUNCTION - SYNCHRONISATION OF DEFROSTING PERIODS - once time d5 has passed defrosting will be activated
4=
MULTIFUNCTION - ACTIVATION OF ENERGY SAVING FUNCTION - the “en­ergy saving” function will be activated (until the input is deactivated), provided the “overcooling” function is running; see also r4
5=
MULTIFUNCTION - ACTIVATION OF MULTIFUNCTION INPUT ALARM - once time i7 has passed the display will show the flashing code “iA” and the buzzer will be activated (until the input is deactivated)
6=
MULTIFUNCTION - ACTIVATION OF PRESSURE SWITCH ALARM - the com­pressor will be switched off, the display will show the flashing code “iA” and the buzzer will be activated (until the input is deactivated) when the input has been activated the number of times established with parameter i8 the regulators will be switched off, the display will show the flashing code “iSd” and the buzzer will be activated (until the input is deactivated and the device is switched off and re-started or until the power supply is interrupted); see also i7 and i9
7=
MULTIFUNCTION - SWITCHING OFF THE DEVICE - the device will be switched off (until the input is deactivated)
i0 0 11 - - - not avail.not avail. 33333effect caused by the activation of the door microswitch/multifunction 1 input; see
also i4 (28)
0 = no effect
1=
DOOR MICROSWITCH - COMPRESSOR AND EVAPORATOR FAN SWITCH­OFF - the compressor and the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) (29)
2=
DOOR MICROSWITCH - EVAPORATOR FAN SWITCH-OFF - the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated)
3=
DOOR MICROSWITCH - CELL LIGHT SWITCH-ON - the cell light will be switched on (only if u0/u1 = 0, until the input will be deactivated)
Page 8
EVCO S.p.A. | Code 104R200E114 | Page 8 of 10 | PT 14/13 | version 1.1
4=DOOR MICROSWITCH - SWITCH-OFF OF THE COMPRESSOR, EVAPORA-
TOR FAN, SWITCH-ON OF CELL LIGHT - the compressor and the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) and the cell light will be switched on (only if u0/u1 = 0, until the input is deactivated) (29)
5=
DOOR MICROSWITCH - SWITCH-OFF OF THE EVAPORATOR FAN, SWITCH­ON OF CELL LIGHT - the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) and the cell light will be switched on (only if u0/u1 = 0, until the input is deactivated)
6=
MULTIFUNCTION - SYNCHRONISATION OF DEFROSTING PERIODS - once time d5 has passed defrosting will be activated
7=
MULTIFUNCTION - ACTIVATION OF “ENERGY SAVING” FUNCTION - the “energy saving” function will be activated (just with effect on the compres­sor, until the input is deactivated), provided the “overcooling” function is not running; see also r4
8=
MULTIFUNCTION - ACTIVATION OF MULTIFUNCTION INPUT ALARM - once time i7 has passed the display will show the flashing code “iA” and the buzzer will be activated (until the input is deactivated)
9=
MULTIFUNCTION- ACTIVATION OF THE PRESSURE SWITCH ALARM - the compressor will be switched off, if u0/u1 = 6 the condenser fan will be switched on, the display will show the flashing code iA” and the buzzer will be activated (until the input is deactivated): when the input has been activated the number of times established with parameter i8 the regulators will be switched off, if u0/u1 = 6 the condenser fan will be switched on, the display will show the flashing code “iSd” and the buzzer will be activated (until the input is deactivated and the device is switched off and re-started or until the power supply is interrupted); see also i7 and i9
10 =
MULTIFUNCTION - SWITICHING ON THE AUXILIARY OUTPUT - the auxiliary output will be switched on (only if u0/u1 = 2, until the input is deactivated)
11 =
MULTIFUNCTION - SWITCHING OFF THE DEVICE - the device will be switched off (until the input is deactivated)
i101- - -0000000type of door microswitch/multifunction 1 input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
i2 -1 120 min 30 30 30 30 30 30 30 delay in signalling of door microswitch input alarm (code “id”)
-1 = the alarm will not be signalled
i3 -1 120 min 15 15 15 15 15 15 15 maximum duration of the effect caused by the activation of the door microswitch
input on the compressor and the evaporator
-1 = the effect will last until the input is deactivated
i401- - -0000000storage of door microswitch input alarm (codeid”) (30)
1 = YES
i5 0 11 - - - not avail.not avail.not avail.not avail.not avail. 7 7 effect caused by the activation of the door microswitch/multifunction 2 input; see
also i4 (28)
0 = no effect
1=
DOOR MICROSWITCH - COMPRESSOR AND EVAPORATOR FAN SWITCH­OFF - the compressor and the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) (29)
2=
DOOR MICROSWITCH - EVAPORATOR FAN SWITCH-OFF - the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated)
3=
DOOR MICROSWITCH - CELL LIGHT SWITCH-ON - the cell light will be switched on (only if u0/u1 = 0, until the input will be deactivated)
4=
DOOR MICROSWITCH - SWITCH-OFF OF THE COMPRESSOR, EVAPORA­TOR FAN, SWITCH-ON OF CELL LIGHT - the compressor and the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) and the cell light will be switched on (only if u0/u1 = 0, until the input is deactivated) (29)
5=
DOOR MICROSWITCH - SWITCH-OFF OF THE EVAPORATOR FAN, SWITCH­ON OF CELL LIGHT - the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) and the cell light will be switched on (only if u0/u1 = 0, until the input is deactivated)
6=
MULTIFUNCTION - SYNCHRONISATION OF DEFROSTING PERIODS - once time d5 has passed defrosting will be activated
7=
MULTIFUNCTION - ACTIVATION OF “ENERGY SAVING” FUNCTION - the “energy saving” function will be activated (just with effect on the compres­sor, until the input is deactivated), provided the “overcooling” function is not running; see also r4
8=
MULTIFUNCTION - ACTIVATION OF MULTIFUNCTION INPUT ALARM - once time i7 has passed the display will show the flashing code “iA” and the buzzer will be activated (until the input is deactivated)
9=
MULTIFUNCTION- ACTIVATION OF THE PRESSURE SWITCH ALARM - the compressor will be switched off, if u0/u1 = 6 the condenser fan will be switched on, the display will show the flashing code iA” and the buzzer will be activated (until the input is deactivated): when the input has been activated the number of times established with parameter i8 the regulators will be switched off, if u0/u1 = 6 the condenser fan will be switched on, the display will show the flashing code “iSd” and the buzzer will be activated (until the input is deactivated and the device is switched off and re-started or until the power supply is interrupted); see also i7 and i9
10 =
MULTIFUNCTION- SWTICHING ON THE AUXILIARY OUTPUT - the auxiliary output will be switched on (only if u0/u1 = 2, until the input is deactivated)
11 =
MULTIFUNCTION - SWITCHING OFF THE DEVICE - the device will be switched off (until the input is deactivated)
i6 0 1 - - - not avail.not avail.not avail.not avail.not avail. 0 0 type of door microswitch/multifunction 2 input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
i70120min0000000if i1 and/or i5 = 8, multifunction input alarm delay (code “iA”)
if i1 and/or i5 = 9, delay in compressor switching on after the deactivation of the
multifunction input (31)
i8015- - -0000000number of multifunction input alarms (code “iA”) such to cause a pressure switch
alarm (code “iSd”) (only if i0 and/or i5 = 9)
0 = alarm absent
Page 9
EVCO S.p.A. | Code 104R200E114 | Page 9 of 10 | PT 14/13 | version 1.1
i9 1 999 min 240 240 240 240 240 240 240 time that must pass in absence of multifunction output alarms (code “iA”) so that
the alarm counter is reset (only if i0 and/or i5 = 9)
i100999min0000000time without activations of the door switch input (on condition that the cabinet
temperature has reached the working set-point) in order that function “energy
saving” is activated (it has effect on the evaporator fan only if F0 = 1, 2, 3 or 4)
0 = the function will never be activated due to the effect of this condition
i13 0 240 - - - 180 180 180 180 180 180 180 number of door switch input activations such as to provoke the defrost activation
0 = defrosting will never be activated due to the effect of this condition
i14 0 240 min 32 32 32 32 32 32 32 minimum duration of the door switch input activation such as to provoke the defrost
activation
0 = defrosting for this condition will never be activated
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 DIGITAL OUTPUTS
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
u0 0 7 - - - not avail.not avail. 7 not avail.not avail.not avail.not avail. operation controlled by second output (32)
0=
CELL LIGHT - in this case the key and parameters i0, i5 AND u2 will be activated
1=
DEMISTER RESISTORS - in this case the key and parameter u6 will be activated
2=
AUXILIARY OUTPUT - in this case the key and parameters i5 and u2 will be activated
3=
ALARM OUTPUTS - in this case parameter u4 will be activated
4=
DOOR RESISTORS - in this case parameter u5 will be activated
5=
RESISTORS FOR NEUTRAL AREA OPERATION - in this case parameter u7 will be activated
6=
EVAPORATOR FAN - in this case parameters d7, d16, F, i0 and i10 will be activated
7=DEFROST - in this case parameters d1, d7 and d16 will be activated u0 0 1 - - - not avail.not avail.not avail. 1 1 not avail.not avail. utility managed by the second output (32)
0=
CELL LIGHT - in this case the key and parameters i0 and u2 will be activated
1=DEFROSTING - in this case, the d0... d22 parameters will be activated u1 0 6 - - - not avail.not avail.not avail.not avail.not avail. 0 0 operation controlled by fourth output (32)
0=
CELL LIGHT - in this case the key and parameters i0, i5 AND u2 will be activated
1=
DEMISTER RESISTORS - in this case the key and parameter u6 will be activated
2=
AUXILIARY OUTPUT - in this case the key and parameters i5 and u2 will be activated
3=
ALARM OUTPUTS - in this case parameter u4 will be activated
4=
DOOR RESISTORS - in this case parameter u5 will be activated
5=
RESISTORS FOR NEUTRAL AREA OPERATION - in this case parameter u7 will be activated
6=
CONDENSER FAN - in this case parameters P4, F11 and F12 will be activated
u2 0 1 - - - not avail.not avail. 00000enabling of manual switch on/switch off of the cell light or the auxiliary output when
the device is switched off(only if u0/u1 = 0 or 2) (33)
1 = YES u4 0 1 - - - not avail.not avail. 1 not avail.not avail. 1 1 enabling of alarm output deactivation with the silencing of the buzzer (only if
u0/u1 = 3)
1 = YES u5 -99 99,0 °C/°F (1)not avail.not avail. -1,0 not avail.not avail. -1,0 -1,0 temperature of the cell below which the door resistors are switched on
(“u5 - 2,0 °C/4 °F, only if u0/u1 = 4) (9) u6 1 120 min not avail.not avail. 5 not avail.not avail. 5 5 operating time of demister resistors (only if u0/u1 = 1) u7 -99 99,0 °C/°F (1)not avail.not avail. -5,0 not avail.not avail. -5,0 -5,0 neutral area value (relative to the work set-point, i.e. “work set-point + u7) (only
if u0/u1 = 5) (34) u8 - - - - - - - - - not avail.not avail. - - - not avail.not avail. - - - - - - reserved u901- - -1111111enabling the buzzer
1 = YES
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 ENERGY SAVING
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
HE20999min0000000maximum duration of the “energy saving” function activated due to the effect of
absence of door microswitch input activation
0 = the function will last until the input is activated
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 SERIAL NETWORK
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274 LA 1 247 - - - 247 247 247 247 247 247 247 device address Lb03- - -2222222baud rate
0 = 2.400 baud 1 = 4.800 baud 2 = 9.600 baud 3 = 19.200 baud
LP02- - -2222222parity
0 = none (no parity) 1 = odd 2 = even
Notes:
(1) the unit of measurement depends on P2 (2) Properly set the parameters corresponding to the regulators after modifying parameter P2 (3) the value depends on parameter P2 (0.1 °C or 1 °F) (4) if parameter r8 is set at 1, the “energy saving” function and the defrosting functions will not be enabled (5) the parameter has effect even after an interruption in the power supply that occurs while the device is switched on (5) the parameter has effect even after an interruption in
the power supply that occurs while the device is switched on (6) the time established with the parameter is counted even when the device is switched off (7) if parameter C1 is set to 0, the delay after the end of the cell probe error will be 2 min (8) if parameter C2 is set to 0, the device will function as if parameter C18 were set to 0 (9) The parameter differential is 2.0 °C/4 °F (10) if when the device is switched on, the condenser temperature is already above that established in parameter C7, then parameter C8 will not have effect (11) the device verifies the mains voltage at established intervals with parameter C2; if there is a power cut, the count of the number of switch-ons aborted will be reset. (12) the device memorises the defrosting interval count every 30 minutes; the modification of parameter d0 has effect from the conclusion of the previous defrosting interval (or the
activation of defrosting in manual mode)
Page 10
EVCO S.p.A. | Code 104R200E114 | Page of 10 | PT 14/13 | version 1.1
(13) the display restores normal operation when, on conclusion of evaporator fan standstill, the cell temperature drops below that which has blocked the display (or if a temperature
alarm occurs) (14) in the EVR221, EVR231, EVR261 and EVR271 models, the maximum value of parameter d8 is 1 (15) if parameter P3 is set to 0 or 2, the device will function as if parameter d8 were set to 0 (16) if when defrosting is activated, the operating duration of the compressor is less than the time established with parameter d5, the compressor will remain on for the amount of time
necessary to complete defrosting. (17) if parameter P3 is set to 0, the device will function as if parameter A0 were set to 0 but it will not store the alarm (18) during defrosting and dripping and when the evaporator fan is stopped, the temperature alarms are absent, provided that these were signalled after the activation of defrosting (19) during activation of the door microswitch input, the maximum temperature alarm is absent, provided the alarm was signalled after the activation of the input (20) parameters F13 and F14 have effect when the compressor is off (21) parameters F13 and F14 have effect when the compressor is on (22) if parameter P3 is set to 0, the device will function as if parameter F0 were set to 2 (23) parameters F13 and F14 have effect when the evaporator temperature is below the temperature established with parameter F1 (24) parameters F13 and F14 have effect when the compressor is on and the temperature of the evaporator is below the temperature established with parameter F1 (25) the parameter can also be modified using the procedure described in paragraph 4.2 (26) if parameter P4 is set to 0, the condenser fan will function in parallel with the compressor (27) the condenser fan is off when the temperature of the condenser drops below the temperature established with parameter F11 on condition that the compressor is off (28) if the parameter i0 and parameter i5 are set at the same value, the effect will be caused by the activation of at least one of the inputs (until both inputs are deactivated) (29) the compressor is switched off 10 sec after the activation of the input; if the input is activated during defrosting or when the evaporator fan is deactivated, the activation will not
have any effect on the compressor (30) the device stores the alarm once the time established in parameter i2 has expired; if parameter i2 is set to -1, the device will not store the alarm (31) make sure that the time established with parameter i7 is less than that established with parameter i9 (32) to avoid damaging the unit connected to the instrument, change the parameter setting when the device is switched off (33) if parameter u2 is set to 0, switching off the device may cause the cell light and/or the auxiliary output to switch off (the next time the instrument is switched on the unit connected
will remain switched off); if parameter u2 is set to 1, switching off the device will not cause the cell light or the auxiliary output to switch off (the next time the instrument is switched
on the unit connected will remain switched on). (34) the resistors are switched on when the temperature of the cell drops below the “work set-point + u7” and are switched off when the temperature rises above the “work set-point
+ u7 + 2 °C/°F”.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALIA
telephone 0437 8422 | fax 0437 83648
email info@evco.it | web www.evco.it
This document is exclusive property of EVCO. EVCO does not assume any liability regarding possible errors stated.
The customer (manufacturer, installer or final user) assumes all liability regarding configuration of the device.
EVCO does not take any responsibility about damages coming by the non-observance of additional information.
EVCO reserves the right to make any change without prejudice the basic safety and operating features.
Loading...