EVCO EVR274N9 User Manual

EVCO S.p.A. | Code 104R200E114 | Page 1 of 10 | PT 14/13 | version 1.1
EVR 200 range
Controllers for cold rooms for bars, refrigerated display cabinets for ice cream/confectionery and small wine cellars
EN ENGLISH
DIMENSIONS AND INSTALLATION Dimensions and installation
The dimensions are expressed in mm (in); panel installation is envisioned, with elastic retainer wings (det. A).
Drill ing te mplate
To make easier a possible removal of the device, slightly bevel the longitudinal inside edges of the drilling template before the installation (det. B and C).
ELECTRIC CONNECTION Electric connection EVR203 / EVR233 / EVR263 / EVR273
Serial port
load
power supply
Door microswitch /multi f.
Electric connection EVR204 / EVR234 / EVR264 / EVR274
Serial port
Door microswitch /multi f.
power supply
Serial port
load 4
defrost
evap. fan
Fourth input
Door microswitch/multif. 1
cell
Door microswitch/multi f. 1
Electric connection EVR221 / EVR231 / EVR261 / EVR271 Electric connection EVR202 / EVR232
power supply
EVCO S.p.A. | Code 104R200E114 | Page 2 of 10 | PT 14/13 | version 1.1
IMPORTANT
Read this document thoroughly before installation and be­fore use of the device and follow all recommendations; keep this document with the device for future consultation. Only use the device in the way described in this document; do not use the same as a safety device.
The device must be disposed of in compliance with local Standards regarding the collection of electric and electronic equipment.
1 DIMENSIONS AND INSTALLATION
1.1 Installation warnings
- the thickness of the panel must be between 0.8 and 2.0 mm (0.031 and 0.078 in)
- make sure that the device work conditions (tempera­ture of use, humidity, etc.) lie within the limits indi­cated; see chapter 12
- do not install the device near to any heat sources (heating elements, hot air ducts etc.), equipment containing powerful magnets (large diffusers, etc.), areas affected by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or shocks.
- in compliance with Safety Standards, the device must be installed correctly and in a way to protect against any contact with electric parts; all parts that ensure protection must be fixed in a way that they cannot be removed without the use of tools.
2 ELECTRIC CONNECTION
2.1 Warnings for the electric connection
- do not use electric or pneumatic screwdrivers on the device terminal board
- if the device has been taken from a cold to hot place, humidity could condense inside; wait about 1 hour before powering it
- make sure that the power supply voltage, the frequency and the operational electric power of the device, correspond with those of the local power supply; see chapter 12
- disconnect the device power supply before proceeding with any type of maintenance
- position the power cables as far away as possible from the signal cables
- for repairs and information regarding the device, contact the EVCO sales network.
3 USER INTERFACE
3.1 Preliminary notes
Operating Statuses:
- “on” state (the device is powered and is on: the regulators can be switched on)
- “stand-by” status (the device is powered but is switched off via software: the regulators are switched off; the possibility to manually switch on/switch off the cell light or auxiliary output depends on parameter u2)
- the “off” status (the device is not powered).
Hereafter, with the word “start-up” means the passage from “stand-by” status to “on” status; the word “shutdown” means the passage from “on” status to “stand-by” status. When the power is switched back on, the device displays the status that it was in at the time it was disconnected.
3.2 Device switch-on/off in manual mode
Operating Statuses:
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 2 s: the LED will switch
off/on.
Using the digital inputs it is also possible to remotely switch on/off the device.
3.3 The display
If the device is switched on, during normal operation, the display will show the cell temperature, except during defrosting, when the device will show the temperature established with parameter d6. If the device is switched off, the display will be switched off.
3.4 Display of the evaporator temperature (not
available in EVR221, EVR231, EVR261 and EVR271 models)
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
Pb2”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key. If the evaporator probe is absent (parameter P3 = 0), the label “Pb2” will not be displayed.
3.5 Condenser temperature display (in EVR204,
EVR234, EVR264 and EVR274 models only)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
Pb3”.
4. Press and release the
key. To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key. If the fourth input function is that of the digital input (parameter P4 = 0), the label “Pb3” will not be displayed.
3.6 Mains voltage display (in EVR263, EVR273,
EVR264 and EVR274 models only)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
Ui”.
4. Press and release the
key. To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
3.7 Activation/deactivation of “overcooling” function
1. Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or dripping is not in progress and that the evaporator fan is off.
2. Hold the
key down for 4 s: the Overcooling LED will
light up. During the “overcooling” function the working set-point is reduced by the temperature established with parameter r5; the operation lasts for the amount of time established with parameter r6. During “overcooling” defrosting is never activated; if the defrosting interval expires when the function is in progress, defrosting will be activated at the end of the function.
3.8 Defrosting activation in manual mode
1. Make sure that the keyboard is not locked and that no
other operation is in progress; ensure that the
“overcooling” function is not in progress
2. Hold the
key down for 4 s. If the evaporator probe function is that of the defrosting probe (parameter P3=1) and upon activation of defrosting, the temperature of the evaporator is higher than that established with parameter d2, the defrosting function will not be activated.
3.9 Switch-on/off of the cell light in manual
mode (not available in EVR221, EVR231, EVR261 and EVR271 models and only if parameter u0/u1 is set at 0)
1. Make sure no procedures are in progress
2. Press and release the
key: the “AUX” LED will
switch on/off. Using the door digital inputs it is also possible to switch on/ off the cell light by remote; see also parameter u2.
3.10 Switch-on of demister resistors (only in
EVR202, EVR232, EVR204, EVR234, EVR264 and EVR274 models and only if parameter u0/u1 is set at 1)
1. Ensure that the device is switched on and that no other
procedure is in progress.
2. Hold the
key down for 2 s: the “AUX” LED will light up and the resistors will be switched on, both for the amount of time established with parameter u6.
Manually switching off the demisting resistors is not permitted (that is, before the time established with parameter u6 expires).
3.11 Switch-on/off of auxiliary output in manual mode (only in EVR202, EVR232, EVR204, EVR234, EVR264 and EVR274 models and only if parameter u0/u1 is set at 2)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Press and release the
key: the “AUX” LED will
switch on/off. Using the digital inputs it is also possible to remotely switch on/off the auxiliary output.
3.12 Locking/unlocking the keyboard
To lock the keyboard:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 1 s:
the display will show “Loc”. If the keyboard is locked, the following are not permitted:
- device switch-on/off in manual mode
- display of evaporator temperature (via the procedure
explained in paragraph 3.4)
- display of the condenser temperature (via the procedure
indicated in paragraph 3.5)
- display the mains voltage
- activation/deactivation of “overcooling” function
- manual activation of defrosting
- manual switch on/off of the auxiliary output
- activation of operation for low of high percentage of
relative humidity and learning the kind of operation
- see information regarding the HACCP alarms
- cancellation of HACCP alarm list
- display of compressor operation hours
- cancellation of compressor operation hours
- changing the working set-point (with the procedure
described in 8.1). The operations cause the display of the label “Loc” per 1 sec. To unlock the keyboard:
1. Hold the
key and thee key down for 1 s: the
display will show the message “UnL” for 1 sec.
3.13 Silencing the buzzer
To lock the keyboard:
1. Make sure no procedures are in progress
2. Press a key (the first pressing of the key will not cause
the effect associated with that key). If parameter u0/u1 is set at 3 (i.e. the utility managed by the fourth output is the alarm output ) and parameter u4 is set at 1, pressing the key will also cause the deactivation of the output. If parameter u9 is set to 0, the buzzer will not be activated.
4 OPERATION DUE TO LOW OR HIGH
PERCENTAGE OF RELATIVE HUMIDITY (NOT AVAILABLE IN EVR221, EVR231, EVR261 AND EVR271 MODELS AND ONLY IF PARAMETER F0 IS SET AT 5)
4.1 Preliminary notes
During operation for low percentage of relative humidity, the evaporator ventilator will be switched on if the compressor is switched off (parameter F4 determines the amount of time it is switched off while parameter F5 determines the amount of time it is switched on). During operation for a high percentage of relative humidity the evaporator fan is always on.
4.2 Activation of operation for low or high
percentage relative humidity in manual mode.
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Hold the
key and thee key down for 4 s: the display will show “rhL” (operation for low percentage of relative humidity) or “rhH” (operation for high per­centage of relative humidity) for 10 sec.
To restore the normal display before the operation is complete:
3. Press a key. Activation of the operation for a low or high percentage of relative humidity can be done using parameter F6. If the parameter F0 is not set at 5, pressing the and keys will cause the display of the “- - -“ indication for 1 s.
4.3 Learning the type of operation in progress
1. Make sure no procedures are in progress
2. Press and release the key and the.. key: the display will show “rhL” (operation for low percentage of relative humidity) or “rhH” (operation for high percentage of relative humidity) for 10 sec.
To restore the normal display before the operation is complete:
3. Press a key.
If parameter F0 is not set at 5, pressing the
and
keys will cause:
- the display of the message “- - - -“ for 1 sec if the keyboard is not locked
- display of the label “Loc” for 1 sec if the keyboard is locked.
EVCO S.p.A. | Code 104R200E114 | Page 3 of 10 | PT 14/13 | version 1.1
5 ENERGY SAVING
5.1 Preliminary notes
Once the time you have set with parameter i10 has passed, without activations of the door microswitch input (after the cell temperature has reached the work set-point) the “en­ergy saving” function is activated (until the input is activated again). During function “Energy Saving” the working set-point is increased of the temperature you have set with parameter r4 and the evaporator fan is turned on cyclically, on condition that parameter F0 has value 1 or 2 (parameter F13 sets the time the fan remains turned off and parameter F14 the time it remains turned on). It is also possible to activate the “energy saving” function in remote mode through the digital inputs (with effect only on the compressor).
6 “HACCP” FUNCTION
6.1 Preliminary notes
The device can memorise the following HACCP alarms:
- minimum temperature alarm (code “AL”)
- maximum temperature alarm (code “AH”)
- door microswitch input alarm (code “id”) The device supplies the following information for every alarm:
- the critical value
- the duration of the alarm (from 1 min to 99 hours and 59 min, partial if the alarm is in progress).
Code Critical value
AL the minimum temperature of the cell during any
alarm of this type
AH the maximum temperature of the cell during any
alarm of this type
id the maximum cell temperature during any alarm
of this type; see also parameter i4
The device stored the minimum temperature alarm on con­dition that the temperature associated to the alarm is that of the cell (parameter A0 = 0). if the device is switched off, no alarms will be stored. The device updates the information regarding the alarms provided the critical value of the new alarm is more critical than that stored or provided the information has already been displayed. The “HACCP” LED provides information regarding the storage status of the alarms; see paragraph 9.1.
6.2 Display of HACCP alarm information
To begin the procedure:
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
LS”.
4. Press and release the
key: the display will show
one of the codes included in the table in paragraph 6.1.
If the device does not have any alarms stored, the label “LS” will not be displayed. To select an alarm:
5. Press and release the
or key (to select, for
example, “AH”).
To see information regarding the alarm:
6. Press and release the
key: the HACCP LED will stop flashing and remain on permanently and the dis­play will show, for example, the following information in succession (for example):
Inform. Part
8.0 the critical value is 8.0 °C/8 °F
dur the display is about to show the alarm duration h01 the alarm lasted for 1 hour (other data continues) n15 the alarm lasted 1 hour and 15 min
AH the alarm selected
the displays each piece of information for 1 s. To exit the information sequence:
7. Press and release the
key: the display will show
the alarm selected (in the example “AH”).
To exit the procedure:
8. Exit the information sequence.
9.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
9.2 Press and release the
key.
7.3 Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
rLS”.
4. Press and release the
key.
5. Press and release the
key or the key within
15 s to set “149”.
6. Press and release the
key or do not operate for 15 sec: the display will show a flashing “- - - -” for 4 sec and the “HACCP” LED switches off, after which the device will exit the procedure.
If the device does not have any alarms stored, the label “rLS” will not be displayed.
7 COMPRESSOR OPERATING HOURS COUNT
7.1 Preliminary notes
The device can memorise up to 9.990 compressor operating hours. The parameter C10 establishes the number of operating hours is higher than the limit at which the need for maintenance is signalled.
7.2 Display of Compressor Operation Hours
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the key down for 1 s: the display will show the first label available.
3. Press and release the
key or the key to select
CH”.
4. Press and release the
key.
To exit the procedure:
5. Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or down key until the display shows the cell temperature or do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
7.3 Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Hold the
key down for 1 s: the display will show the
first label available.
3. Press and release the
key or the key to select
rCH”.
4. Press and release the
5. Press and release the
key.
key or the key within
15 s to set “149”.
6. Press and release the
key or do not operate for 15 sec: the display will show “- - -” flashing for 4 sec, after which the device will exit the procedure.
8 SETTINGS
8.1 Setting the working set-point
1. Make sure that the keyboard is not locked and that no procedure is in progress.
2. Press and release the
3. Press and release the
key: the LED will flash.
or key within
15 sec; see also parameters r1, r2 and r3
4. Press and release the 15 sec: the
LED will switch off and then the device
key or do not operate for
will exit the procedure.
To exit the procedure before the operation is complete:
5. Do not operate for 15 sec (any changes will be saved).
The working set-point can also be set via parameter SP.
8.2 Setting the configuration parameters
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
key or the key within
15 s to set “-19”.
5. Press and release the
key or do not operate for
15 sec.
6. Hold the
key and the key down for 4 s:
the display will show “SP”.
To select a parameter:
7. Press and release the
key or the key.
To change a parameter:
8. Press and release the
9. Press and release the
key.
key or the key within
15 sec.
10. Press and release the
key or do not operate for
15 sec.
To exit the procedure:
11. Hold down the
and keys for 4 sec and do not
operate for 60 sec (any changes will be saved).
After changing the parameters, suspend power supply flow to the device.
8.3 Restoring the Manufacturer’s Settings
To begin the procedure:
1. Make sure no procedures are in progress
2. Hold the
key and the key down for 4 s:
the display will show “PA”.
3. Press and release the
4. Press and release the
key.
key or the key within
15 s to set “149”.
5. Press and release the key or do not operate for 15 sec.
6. Hold the
key and the key down for 4 s:
the display will show “dEF”.
7. Press and release the
8. Press and release the
key.
key or the key within
15 s to set “1”.
9. Press and release the
key or do not operate for 15 sec: the display will show “dEF” flashing for 4 sec, after which the device will exit the procedure.
10. Cut the device power supply off. To exit the procedure before the operation is complete:
11. Hold the
and key down for 4 s during the procedure (i.e. before setting “1”: Restore will not be performed).
Make sure that the manufacturer’s settings are appropriate (see chapter 13).
9 WARNING LIGHTS AND DIRECTIONS
9.1 Signals LED Part
compressor LED light if the LED is on, then the compressor is on if the LED is flashing:
- the working set-point is in the process of being changed (via the procedure described in paragraph 8.1)
- a compressor protection will be in progress; see parameters C0, C1, C2, C14, C15, C16 and i7
Defrost LED If it is on:
- defrosting is in progress
- predripping will be in progress; see parameter d16
If the LED is flashing:
- defrosting will be requested but a compres sor protection will be in progress; see the parameters C0, C1 and C2
- dripping will be in progress; see parameter d7
- the refrigerant fluid heating will be in progress; see parameter d15
Evaporator fan LED light if it is on:
- the evaporator fan will be on
If the LED is flashing:
- evaporator fan standstill will be in progress; see parameter F3
AUX Auxiliary LED
If it is on:
- the cell light will have been switched on in manual mode (only if parameter u0/u1 is set at 0)
- the demister resistors will be switched on (only if the parameter u0/u1 is set at 1)
- the auxiliary output will have been switched on in manual mode (only if parameter u0/u1
is set at 2)
- the door resistors will be switched on (only if the parameter u0/u1 is set at 4)
- the evaporator valve will be activated (only if parameter u0/u1 is set at 5)
- the condenser fan will be on (only if param­eter u0/u1 is set at 6)
if the LED is flashing:
- the cell light will have been switched on in remote mode; see parameters i0 and i5 (only if parameter u0/u1 is set at 0)
- the auxiliary output will have been switched on in remote mode; see parameters i0 and i5 (only if parameter u0/u1 is set at 1)
HACCP HACCP LED
if it is on, all information regarding HACCP alarms has not been displayed if it is flashing, the device has stored at least one new HACCP alarm if it is off, all information regarding the HACCP alarms has been displayed or the list of alarms has been cancelled maintenance LED if on, compressor maintenance will be requested; see parameter C10 “overcooling” LED if it is on, the “overcooling” function will be in function; see parameters r5 and r6
°C degree Celsius LED
if on, the temperatures will be displayed using the degree Celsius grade unit of measurement; see parameter P2 if flashing, the “energy saving” function is in progress (with effect only on the compressor)
Loading...
+ 7 hidden pages