EVF204 Digital controller for refrigerated cabinets, made up from user interface with capacitive touch keys
(integrated into the unit) and a control moduleversion 1.00
EN
ENGLISH
1IMPORTANT
1.1Important
Read these instructions carefully before installation and before use and follow all installation recommendations regarding installation and the electric connections. Keep the instructions with the instrument for future
consultation.
The instrument must be disposed of in compliance with the local Standards regarding the collection of electrical and electronic appliances.
2INTRODUCTION
2.1Introduction
EVF204 is a digital controller developed for the management of normal
or low temperature refrigerated cabinets. whose design and easy
cleaning cover an important role.
The instrument has:
• alarm buzzer
•3 measurement inputs (cabinet probe, evaporator probe and
condenser probe) for NTC probes
• 2 digital inputs (door micro switch and multipurpose)
•4 digital outputs (relays) for compressor management
(30 A @ 250 VAC), defrost and evaporator fan management and a
block of work set-point modification (with the procedure indicated in paragraph 5.1)
1 = YES
r40.099.0 °C/°F (1)0 .0
r50.099.0 °C/°F (1)0 .0
r60240 min30
r70.099.0 °C/°F (1)10.0
temperature increases during Energy Saving function; see also i5 and i10
temperature decrease during Overcooling function; see also r6
duration of the Overcooling function; see also r5
minimum “cabinet temperature - work set-point” difference (on instrument switch-on) such to cause the exclusion of the consequent evaporator temperature value from those
used for the calculation of the relative average (for the activation of defrosting; only if d8 = 3); see also d17 (3)
compressor switch-on delay from instrument switch-on (3)
minimum time between two consecutive switch-ons of the compressor; also pressure switch-on delay from the conclusion of the cabinet probe error (“Pr1”code) (4) (5)
minimum duration of compressor switch-off (4)
minimum duration of compressor switch-on
compressor switch-off duration during cabinet probe error (“Pr1” code); see also C5
compressor switch-on duration during cabinet probe error (“Pr1” code); see also C4
condenser temperature over which the overheated condenser alarm is activated (“COH” code) (6)
condenser temperature over which the compressor blocked alarm is activated (“CSd” code)
compressor blocked alarm delay (“CSd” code) (7)
number of compressor functioning hours above which a maintenance request is signalled
0 = no function
DEF.MIN. MAX. U. M.PAR.
d0099h8
DEFROSTING
if d8 = 0, 1 or 2, defrosting interval (8)
0 = defrosting at intervals will never be activated
if d8 = 3, maximum defrosting interval
d102- - - -0
type of defrosting
0=
ELECTRIC - during defrosting the compressor will remain off and the defrosting output will be activated; the evaporator fan activity will depend on parameter F2
1=
WITH HOT GAS - during defrosting the compressor will be switched-on and the defrosting output will be activated; the evaporator fan activity will depend on parameter
F2
2=
DUE TO COMPRESSOR STOPPING - during defrosting the compressor will remain off and the defrosting output will be deactivated; the evaporator fan activity will depend
on parameter F2
d2-99.0 99.0 °C/°F (1)2. 0
d3099min30
temperature of defrosting end (only if P3 = 1); see also d3
if P3 = 0 or 2, duration of defrosting
if P3 = 1, maximum duration of defrosting; see also d2
0 = defrosting will never be activated
d401- - - -0
defrosting on instrument switch-on (only if d8 = 0, 1, 2 or 3) (3)
1 = YES
d5099min0
if d4 = 0, minimum time between switch-on of the instrument and the activation of defrosting; see also i5 (3)
if d4 = 1, defrosting activation delay from instrument switch-on; see also i5 (3)
d601- - - -1
temperature displayed during defrosting
0 = cabinet temperature
1 = if, on activation of defrosting, the cabinet temperature is below “work set-point + r0”, at maximum “work set-point + r0”; if, on activation of defrosting, the cabinet
temperature is above “work set-point + r0”, at maximum the temperature of the cabinet on activation of defrosting (9)
d7015min2
during dripping (during dripping the compressor will remain off and the defrosting output will remain deactivated. If d16 = 0, the evaporator fan activity will depend on
parameter F2; if d16 ≠ 0, the evaporator fan will remain off)
d803- - - -0
defrosting activation method
0=
AT INTERVALS - defrosting will be activated when the instrument has remained on completely for time d0
1=
AT INTERVALS - defrosting will be activated when the compressor has been left on completely for time d0
2=
AT INTERVALS - defrosting will be activated when the evaporator temperature as remained below temperature d9 completely for time d0 (10)
3=
ADAPTIVE - defrosting will be activated when one of the following conditions occurs; see also d0: (10)
- condition 1: the evaporator temperature will be below temperature d22 and the compressor will have remained on totally for time d18
- condition 2: the evaporator temperature will drop below temperature d19
d9-99.0 99.0 °C/°F (1)0. 0
d1 1 01- - - -0
temperature of the evaporator over which the defrosting interval count is suspended (only if d8 = 2)
enabling of the defrosting alarm concluded due to maximum duration (“dFd” code; only if P3 = 1 and without evaporator probe error (“Pr2” code))
1 = YES
d15 099min0
d16 099min0
d1 7 11 0- - - -1
d18 03,000 min4 0
minimum duration of the compressor switch-on on activation of defrosting so that this can be activated (only if d1 = 1) (11)
duration of pre-dripping (during pre-dripping the compressor will remain off, the defrosting output will be activated and the evaporator fan will remain off)
number of evaporator temperature values used to calculate the relative average (for the activation of defrosting; only if d8 = 3); see also r7, i11 and i12
defrosting interval (only if d8 = 3 and for condition 1)
0 = defrosting due to condition 1 will never be activated
d19 0.040.0 °C/°F (1)3 .0
temperature of the evaporator below which defrosting is activated (relative to the average temperatures of the evaporator, i.e. “average of the evaporator temperatures +
d19) (only if d8 = 3 and due to condition 2); see also d17
d20 0500 min180
minimum consecutive duration of the compressor, such to cause activation of defrosting
0 = defrosting will never be activated due to the effect of compressor switch-on
minimum consecutive duration of compressor switch-on from instrument switch-on (on condition that the “cabinet temperature - work set-point” difference is over
temperature r7) and from the activation of the Overcooling function, such to cause activation of defrosting
0 = defrosting will never be activated due to the effect of compressor switch-on
temperature of the evaporator above which the defrosting interval count will be suspended (relative to the average temperatures of the evaporator, i.e. “average of the
evaporator temperatures + d22”) (only if d8 = 3 and due to condition 1); see also d17
increase of the average evaporator temperatures during the Energy Saving function (for activation of defrosting; only if d8 = 3); see also d17
TEMPERATURE ALARMS
temperature associated to the minimum temperature alarm (“AL” code)
0 = cabinet temperature
1 = evaporator temperature (12)
temperature below which the minimum temperature alarm is activated (“AL” code); see also A0, A2 and A11
type of minimum temperature alarm (“AL” code)
0 = no alarm
1 = relative to the work set-point (i.e. ”work set-point - A1”; consider A1 without sign)
2 = absolute (i.e. A1)
temperature above which the maximum temperature alarm is activated (“AH” code); see also A5 and A11
type of maximum temperature alarm (“AH” code)
0 = no alarm
1 = relative to the work set-point (i.e. “work set-point + A4”; consider A4 without sign)
2 = absolute (i.e. A4)
maximum temperature alarm delay (“AH” code) from instrument switch-on (3)
temperature alarm delay (“AL” code and “AH” code)
maximum temperature alarm delay (“AH” code) from conclusion of the evaporator fan standstill (13)
maximum temperature alarm delay (“AH” code) from deactivation of the door micro switch input (14)
differential of parameters A1 and A4
enabling of the HACCP LED
1 = YES
EVAPORATOR FAN
evaporator fan activity during normal functioning
0 = off
1 = on; se also F13, F14 and i10
2 = parallel to the compressor; se also F9, F13, F14 and i10
3 = depending on F1 (15)
4 = off if the compressor is off, depending on F1 if the compressor is on; see also F9 (15)
5 = depending on F6; see also F9
evaporator temperature over which the evaporator fan is switched off (sonly if F0 = 3 or 4); see also F8
activity of the evaporator fan during defrosting and dripping
0 = off
1 = on (it is recommended to set parameter d7 at 0)
2 = depending on F0
maximum duration of the evaporator fan standstill; see also F7 (during evaporator fan standstill, the compressor may be on, the defrosting output will remain deactivated
and the evaporator fan will remain off)
duration of evaporator fan switch-off during functioning due to low relative humidity percentage when the compressor is off; see also F5 (only if F0 = 5)
duration of evaporator fan switch-on during functioning due to low relative humidity percentage when the compressor is off; see also F4 (only if F0 = 5)
functioning due to low or high relative humidity percentage (only if F0 = 5) (16)
0=
LOW RELATIVE HUMIDITY - the evaporator fan will function in parallel to the compressor; see also F4 and F5
1=
HIGH RELATIVE HUMIDITY - the evaporator fan will always be on
evaporator temperature below which the evaporator fan standstill is concluded (relative to the work set-point, i.e. “work set-point + F7”); see also F3
parameter F1 differential
evaporator fan switch-off delay from switch-off of the compressor (only if F0 = 2, 4 and 5)
condenser temperature over which the condenser fan will be switched-on (“F11 + 2,0 °C/4 °F, only if u1 = 6 and on condition that the compressor is on); see also F12 (17)
condenser fan switch-off delay from switch-off of the compressor (only if u1 = 6); see also F11
duration of evaporator fan switch-off during the Energy Saving function; see also F14 and i10 (only if F0 = 1 or 2)
duration of evaporator fan switch-on during the Energy Saving function; see also F13 and i10 (only if F0 = 1 or 2)
DIGITAL INPUTS
effect caused by the activation of the door micro switch input; see also i4
0 = no effect
1 = the compressor and the evaporator fan will be switched-off (at maximum for time i3 or until when the input is deactivated) (18)
2 = the evaporator fan will be switched-off (at maximum for time i3 or until when the input is deactivated)
3 = the cabinet light will be switched on (only if u1 = 0, until the input is deactivated)
4 = the compressor and the evaporator fan will be switched-off (at maximum for time i3 or until the input is deactivated) and the cabinet light will be switched on (only
if u1 = 0, until the input is deactivated) (18)
5 = the evaporator fan will be switched-off (at maximum for time i3 or until the input is deactivated) and the cabinet light will be switched on (only if u1 = 0, until the input
is deactivated)
type of door micro switch input contact
0 = normally open (active input with closed contact)
1 = normally closed (input open with contact open)
door micro switch input alarm signalling delay (“id” code)
-1 = the alarm will not be signalled
maximum duration of the effect caused by activation of the door micro switch input on the compressor and on the evaporator fan
-1 = the effect will last until the input is deactivated
door micro switch input alarm memorisation (“id” code) (19)
1 = YES
effect caused by the activation of the multipurpose input
0 = no effect
1=
SYNCHRONISATION OF DEFROSTING - on expiry of time d5 defrosting will be activated
2=
ACTIVATION OF THE ENERGY SAVING FUNCTION - the Energy Saving function will be activated (until the input is deactivated), on condition that the Overcooling function
is not in progress; see also r4
3=
ACTIVATION OF THE MUTIPURPOSE INPUT ALARM - when time i7 has expired, the display will show “iA” flashing and the buzzer will be activated (up to when the input
is deactivated)
4=
ACTIVATION OF THE PRESSURE SWITCH ALARM - the compressor will be off, if u1 = 6 the condenser fan will be on, the display will show the flashing “iA” code and
the buzzer will be activated (until the input is deactivated): when the input has been activated the number of times established by parameter i8 the regulators will be
switched off, if u1 = 6 the condenser fan will be switched on, the display will show the flashing “iSd” code and the buzzer will be activated (until the input is deactivated
and the instrument is switched off and back on again or the power supply is cut-off); see also i7 and i9
5=
AUXILIARY OUTPUT SWITCH-ON - the auxiliary output will be switched-on (only if u1 = 2, until the input is deactivated)
6=
INSTRUMENT SWITCH-OFF - the instrument will be switched off (until the input is deactivated)
type of multipurpose input contact
0 = normally open (active input with closed contact)
1 = normally closed (input open with contact open)
if i5 = 3, multipurpose input alarm signal delay (“iA” code)
if i5 = 4, compressor switch-on delay from the activation of the multipurpose input (20)
number of multipurpose input alarms (“iA” code) such to cause the pressure switch alarm (“iSd” code) (only if i5 = 4)
0 = no alarm
Evco S.p.A. • Code 104F204E00 • page 7/8
i91999 min240
i100999 min0
time that must pass in absence of multipurpose input alarms (“iA” code) so that the alarms contactor is reset (only if i5 = 4)
time that must pass without activation of the door micro switch input (after the cabinet temperature has reached the work set-point) so that the Energy Saving function is
activated automatically (it affects the evaporator fan only if F0 = 1 or 2)
0 = the function will never be activated automatically
i110240 s15
minimum duration of door micro switch activation such to cause the exclusion of the consequent evaporator temperature value from those used for the calculation of the
relative average (for the activation of defrosting; only if d8 = 3); see also d17
i120240 s60
minimum total duration of door micro switch activation such to cause the exclusion of the consequent evaporator temperature value from those used for the calculation
of the relative average (for the activation of defrosting; only if d8 = 3); see also d17
i1 302 40 - - - -180
number of door micro switch input activations such to cause the activation of defrosting
0 = defrosting will never be activated due to the effect of door micro switch input activation
i140240 min32
minimum duration of door micro switch input activations such to cause the activation of defrosting
0 = defrosting will never be activated due to the effect of door micro switch input activation
DEF.MIN. MAX. U. M.PAR.
u106- - - -0
u201- - - -0
DIGITAL OUTPUTS
utility managed by the fourth output (21)
0=
CABINET LIGHT - in this case the key, parameters i0 and u2 will have meaning
1=
DEMISTING HEATERS - in this case the key and parameter u6 will have meaning
2=
AUXILIARY OUTPUT - in this case the key, parameters i5 and u2 will have meaning
3=
ALARM OUTPUT - in this case, parameter u4 will have meaning
4=
DOOR HEATERS - in this case, parameter u5 will have meaning
5=
EVAPORATOR VALVE - in this case, parameters u7 and u8 will have meaning
6=
CONDENSER FAN - in this case, parameters P4, F11 and F12 will have meaning
enabling of cabinet light or auxiliary output switch-on/off in manual mode when the instrument is off (only if u1 = 0 or 2) (22)
1 = YES
u401- - - -1
enabling deactivation of the alarm output with silencing of the buzzer (only if u1 = 3)
1 = YES
u5-99.0 99.0 °C/°F (1)-1 .0
u61120 min5
u70.099.0 °C/°F (1)2. 0
u801- - - -0
cabinet temperature below which the door heaters are switched-on (“u5 - 2.0 °C/4 °F, only if u1 = 4) (6)
duration of demisting heaters switch-on (only if u1 = 1)
cabinet temperature below which the evaporator valve is disabled (relative to the work set-point, i.e. “work set-point + u7”) (only if u1 = 5) (6)
type of evaporator valve contact (only if u1 = 5)
0 = normally open (active valve with closed contact)
1 = normally closed (active valve with open contact)
u901- - - -1
enabling of the buzzer
1 = YES
DEF.MIN. MAX. U. M.PAR.
LA12 47- - - -24 7
Lb03- - - -2
SERIAL NETWORK (MODBUS)
instrument address
baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
LP02- - - -2
parity
0 = none (no parity)
1 = odd
2 = even
PARAM. MIN. MAX. U.O.M.DEF.
E901- - - -1
RESERVED
reserved
(1) the unit of measurement depends on parameter P2
(2) appropriately set the parameters relative to the regulators after modification of parameter P2
(3) the parameter only has effect after a power cut that occurs when the instrument is on
(4) the time established with the parameter is counted also when the instrument is off
(5) if parameter C1 is set at 0, the delay from the conclusion of the cabinet probe error will be 2 min
(6) the parameter differential is 2.0 °C/4 °F
(7) on instrument switch-on, the temperature of the condenser is already above that established with parameter C7, parameter C8 will have no effect
(8) the instrument memorises the defrosting interval count every 30 min. The modification of parameter d0 has effect from the conclusion of the previous defrosting interval or from the activation of defrosting in manual
mode
(9) the display restores normal functioning when, on conclusion of evaporator fan standstill, the cabinet temperature drops below that which has blocked the display (or if a temperature alarm occurs)
(10) if parameter P3 is set at 0 or 2, the instrument will function as if parameter d8 is set at 0
(11) if, on activation of defrosting, the switch-on duration of the compressor is less than the time established with parameter d15, the compressor will remain on for the fraction of time required to complete it
(12) if parameter P3 is set at 0, the instrument will function as if parameter A0 is set at 0 but will not memorise the alarm
(13) during defrosting, dripping and evaporator fan standstill, the temperature alarms are not present as long as these have occurred after activation of defrosting
(14) during the activation of the door micro switch input, the maximum temperature alarm is absent on the condition that these occur after activation of the input
(15) if parameter P3 is set at 0, the instrument will function as if parameter F0 is set at 2
(16) the parameter is also modified by operating with the procedure given in paragraph 4.8.1
(17) if parameter P4 is set at 0, the condenser fan will function in parallel to the compressor
(18) the compressor is switched-off after 10 s from activation of the input. If the input is activated during defrosting or standstill of the evaporator fan, the activation will not have any effect on the compressor
(19) the instrument memorises the alarm on expiry of the time established with parameter i2. If parameter i2 is set at -1, the instrument does not memorise the alarm
(20) make sure that the time established with parameter i7 is lower than that established with parameter i9
(21) to prevent damage to the utility connected, modify the parameter when the instrument is off
(22) if parameter u2 is set at 0, instrument switch-off will cause the cabinet light or auxiliary output to switch off (on successive switch-on of the instrument, the utility will remain off); if the parameter u2 is set at 1, instrument
switch-off will not cause the cabinet light or auxiliary output to switch off (on successive switch-on of the instrument, the utility will remain on).
Evco S.p.A. • Code 104F204E00 • page 8/8
13ELECTRIC CONNECTION
13.1Preliminary considerations
With reference to the wiring diagram:
• the utility managed by the fourth output will depend on parameter u1
• the serial is the port for communication with the Parameters Manager set-up software system or to the monitoring and supervision system of RICS plants (through a serial interface, via TTL, with MODBUS communication
protocol) or with the EVKEY programming key.
The port must not be used simultaneously for three purposes.
13.2Electric connection
13.3Rec ommendations for the electric connection
• do not operate on the terminal boards using electric or pneumatic screwdrivers
• if the instrument has been taken from a old place to a hot one, the humidity could condense inside. Wait about one hour before applying power
• make sure that the power supply voltage, frequency and operational electric power correspond to those of the local power supply
• disconnect the power supply before performing any type of maintenance
• do not use the instrument as a safety device
• for repairs and information regarding the instrument, contact the Evco sales network.
EVCO S.p.A.This document belongs to Evco; unless you are authorized by Evco, you cannot publish this document.
Via Mezzaterra 6, 32036 Sedico Belluno ITALYEvco does not take any responsibility about features, technical data and possible mistakes related in this document.
Phone +39-0437-852468 • Fax +39-0437-83648Evco does not take any responsibility about damages coming by the non-observance of additional information.
info@evco.it • www.evco.itEvco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.