ETC Unison Fluorescent Option Kit User Manual

ETC® Setup Guide
Step 2:
Step 3:
Step 4:
Unison® Fluorescent Option Kit Installation
.
Note:
A single Unison DRd rack supports the use of either the DALI option kit or the FLO option kit, but not both in the same rack.
It is best to install rack options after conduit rough-in and the line, load and control terminations are complete to reduce the likelihood of damage to the option board.
Fluorescent Option Kit

Install the Fluorescent Option Kit

The fluorescent option (DRd-FLO) kit provides 24 outputs for control of 4-wire (0-10 Vdc) fluorescent ballasts. Each channel output is linked one - to - one with a rack circuit for power control. The FLO board is comprised of 24 individual 0 - 10 Vdc connections, each rated to control a maximum of 400mA per channel (typically 50 or more ballasts).
Each output connection is clearly labeled on the removable screw terminal bus connectors. The removable connectors accept 12 - 24 AWG (4 - .25mm
2
) Class 1 wire.
Step 1: Align the FLO option board to the mounting studs in the bottom of the DRd rack.
• Notice the mounting holes on the FLO option board. One is a slotted keyhole, another is an open ended slot and the remaining two on the other end of the board are standard mounting holes used to secure the board in place.
Step 2: Set the rear stud through the slotted keyhole and align the open ended slot with the
back right side mounting stud.
Step 3: Gently slide the FLO board toward the right I/O board aligning the five prong
connector to the receptacle on the right I/O board.
Step 4: Secure the remaining two mounting holes to the pems with the screws provided.
Corporate Headquarters London, UK Rome, IT  Holzkirchen, DE Hong Kong  Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong  Tel +852 2799 1220  Fax +852 2799 9325 Service: Web: 7183M2220
Unison Fluorescent Option Kit Setup Guide Page 1 of 2 Electronic Theatre Controls, Inc.
 Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK  Tel +44 (0)20 8896 1000  Fax +44 (0)20 8896 2000
Via Pieve Torina, 48, 00156 Rome, Italy  Tel +39 (06) 32 111 683  Fax +44 (0) 20 8752 8486
(Americas) service@etcconnect.com
www.etcconnect.com
 Rev C  Released 2012-02 ETC intends this document to be provided in its entirety.
 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA  Tel +608 831 4116  Fax +608 836 1736
 Ohmstrasse 3, 83607 Holzkirchen, Germany  Tel +49 (80 24) 47 00-0  Fax +49 (80 24) 47 00-3 00
Copyright © 2012 ETC. All Rights Reserved.  Product information and specifications subject to change.
(UK) service@etceurope.com  (DE) techserv-hoki@etcconnect.com
(Asia) service@etcasia.com
ETC Setup Guide
Each of the four bus connectors on the option board provide termination for six fluorescent outputs. Each bus connector is labeled for ease of identification and is pluggable for ease of wiring termination. Terminals accept 12-24 AWG (4 - .25mm
2
)
Class 1 wire.

Connect Fluorescent Option Wiring

Unison® Fluorescent Option Kit
Note:
Note:
Fluorescent control wiring must be routed in separate conduit from the line voltage wiring for 0-10V ballast.
To control 4-wire fluorescent ballasts, the power circuit in the rack must be a dimmer module and assigned to 4-wire fluorescent dimmer mode. Reference the related architectural control processor configuration manual for instruction to change dimmer mode.
It is important to label the 4-wire fluorescent load and control wiring sets with the circuit designation. Control wires terminate on the associated FLO option board output terminal.
The associated output loop terminal number should always match the straight power circuit numbering label inside the rack, regardless of straight or balanced rack dimmer configuration.
Example: If circuit 1 is configured as a dimmer with a 4-wire fluorescent dimmer mode, ballast control wiring would terminate to the FLO option board output terminals labeled “1”.
Label
-6+ -5+ -4+ -3+ -2+ -1+
2008
-12+ -11+ -10+ -9+ -8+ -7+
-18+ -17+ -16+ -15+ -14+ -13+
-24+ -23+ -22+ -21+ -20+ -19+
FLUOR 1 - 6
FLUOR 7 - 12
FLUOR 13 - 18
FLUOR 19 -24
Step 1: Pull fluorescent ballast control wiring pairs into the DRd rack enclosure per the wire
entry plan.
Step 2: Strip each wire pair back 1/4 inch (6mm).
Step 3: Remove the bus connector for fluorescent outputs 1-6. The pluggable connector is
seated tight in the receptacle. You may need to gently pry the connector free from the board using a small jewelers screwdriver.
Step 4: Notice the connector is labeled for your reference during wire termination. Using a
jewelers screwdriver, loosen the terminals and insert each of the data “+” and data “-” wires in the wire set into the appropriate terminal.
a: Terminate the violet (typical) control wire of the first pair into the “+” terminal
associated to the power circuit.
b: Terminate the gray (typical) control wire of the first pair into the “-” terminal
associated to the power circuit.
c: Tighten each screw terminal until the wire is held snug.
Step 5: Repeat steps 1 through 4 for the remaining fluorescent outputs through output 6.
Step 6: Replace the first bus connector to the FLO option board and repeat for the remaining
fluorescent outputs in the system (up to 24 outputs).
Unison Fluorescent Option Kit Setup Guide Page 2 of 2 Electronic Theatre Controls, Inc.
Loading...