Product information and specifications subject to change.
Part Number:
7183M2100
Released: 2014-07
Rev D
Page 2
ETC®, Unison Paradigm®, Echo™, and SmartLink® are either registered trademarks or trademarks of Electronic
Theatre Controls, Inc. in the United States and other countries. All other trademarks, both marked and not
marked, are the property of their respective owners.
ETC intends this document, whether printed or electronic, to be provided in its entirety.
Welcome to the installation manual for Unison® DRd enclosures. This manual contains the
procedures for safe and efficient installation of your DRd enclosure and related
terminations.
Use this manual in conjunction with the Unison Auxiliary Enclosure Installation Manual
when your DRd is to be installed with an adjoining auxiliary enclosure.
120/208 V AC
240/415 V AC
230/400 V AC CE Neutral Disconnect
277/480 V AC
120/208 V AC
240/415 V AC
230/400 V AC CE Neutral Disconnect
277/480 V AC
120/208 V AC
240/415 V AC
277/480 V AC
6 module enclosure for up to 12 circuits.
12 module enclosure for up to 24 circuits.
Two 12 module enclosures for up to 48 circuits.
DRd12-48 enclosures are cross-bussed using
the AX12X series main lug or main breaker
enclosure.
Introduction1
Page 6
Warnings and Notice Conventions
These symbols are used throughout this installation manual to alert you to danger or
important information:
Note:
CAUTION:
Notes are helpful hints or information that is supplemental to the main text.
A Caution statement indicates situations where there may be undefined or
unwanted consequences of an action, potential for data loss, or an equipment
problem.
WARNING:
A Warning statement indicates situations where damage may occur, people
may be harmed, or there are serious or dangerous consequences of an
action.
WARNING:
RISK OF ELECTRIC SHOCK! This warning statement indicates situations
where there is a risk of death by electric shock.
Contacting ETC
For questions about Unison system delivery, contact ETC Systems Group. For general
information, your most convenient resources are the references provided in this manual. To
search more widely try the ETC web site at www.etcconnect.com.
For technical questions about Unison systems, contact ETC Technical Services directly at
one of the offices listed below. Emergency service is available from all ETC offices outside
of normal business hours. When calling for assistance, please have the following
information handy:
•Your location and job name.
•A complete list of ETC equipment.
•A complete list of other installed products and components connected to the system
you are troubleshooting.
•DMX control source, if any.
Americas
ETC International
Technical Services Department
3031 Pleasant View Road
Middleton, WI 53562
800-775-4382 (USA, toll-free)
+1-608 831-4116
service@etcconnect.com
Asia
ETC Asia, Ltd.
Technical Services Department
Room 1801, 18/F, Tower 1, Phase 1
Enterprise Square
9 Sheung Yuet Road
Kowloon Bay, Kowloon, Hong Kong
+852 2799 1220
service@etcasia.com
United Kingdom
Electronic Theatre Controls, Ltd.
Technical Services Department
26 - 28 Victoria Industrial Estate
Victoria Road,
London W3 6UU, UK
+44 (0)20 8896 1000
service@etceurope.com
Please email comments about this manual to: TechComm@etcconnect.com
2DRd Enclosure Installation Manual
Page 7
Overview
DRd6
DRd12
Unison DRd enclosures are available in 6 or 12 module enclosures and are available for an
input voltage range of 85-300 V AC, 47-63 Hz. Enclosures are pre-wired and supplied with
three phase, 4 wire and ground, main lugs which are easily converted for split phase, 3 wire
and ground, operation without the need for additional materials.
Note:
DRd enclosures are available in 12, 24 and 48 circuit configurations.
In 48-circuit configurations, two DRd12-24 enclosures are cross-bussed to an
AX12X series main lug or main circuit breaker auxiliary enclosure. A single
Architectural Control Processor (Echo, Paradigm, or SmartLink ACP) provides
control for both enclosures.
DRd enclosures are supplied pre-wired for the specified voltage for your installation. All
enclosures operate at specified voltages within a frequency range of 47-63 Hz. Phases
within the enclosure may be bused together provided the maximum supplied current does
not exceed that of a three phase connection.
•100 / 200 V AC, 47-63 Hz, 1Ø
•100 / 173 V AC, 47-63 Hz, 3Ø
•120 / 208 V AC, 47-63 Hz, 3Ø
•120 / 240 V AC, 47-63 Hz, 1Ø
•127 / 220 V AC, 47-63 Hz, 3Ø
•230 / 400 V AC, 47-63 Hz, 3Ø CE with Neutral Disconnect
“Modules Specification” , page 57 for a complete list of compatible modules.
•The DRd is controlled from either the Echo
(E-ACP), SmartLink
Architectural Control Processor (P-ACP).
®
Architectural Control Processor (S-ACP) or the Paradigm™
®
Architectural Control Processor
Introduction3
Page 8
•The use of a station power module provides power and control for architectural control
stations.
•Use an Echo Station Power Module (E-SPM) to provide power for up to 16 Echo
control stations when used with the Echo ACP.
•Use a SmartLink Station Power Module (S-SPM) to provide power for up to 16
SmartLink control stations when used with the SmartLink ACP.
•Use a Paradigm Station Power Module (P-SPM) to provide power for up to 32
Paradigm control stations when used with the Paradigm ACP.
•The 0-10V control option (DRd-FLO) provides up to 24 outputs for control of 0-10V
(4-wire) LED drivers or fluorescent ballasts (up to 12 on a DRd6).
•The Digital Addressable Lighting Interface (DALI) option controls up to 24 loops of 64
DALI compatible ballasts or drivers in a broadcast mode (up to 12 on a DRd6).
•The Unison BatteryPack option provides power back-up to the Architectural Control
Processor in the DRd for a period up to 90 minutes.
•The Unison RideThru option provides power to the Architectural Control Processor in
the DRd for at least 10 seconds during brief power outages or drop outs.
•All empty module spaces in a DRd enclosure must be filled with airflow module or blank
modules (DRd-BM) for proper cooling.
•The DRd pedestal (DRd-PED) is a floor mounting stand for the DRd enclosure.
4DRd Enclosure Installation Manual
Page 9
Chapter 1
Prepare for Installation
Unpack and Inspect
Before you begin installation, check your shipment and confirm it arrived complete and
undamaged.
Step 1:Check the shipping container for physical damage.
Step 2:If you find damage, document it to help with a claim against your shipper.
Step 3:Unpack your order and check the contents against the packing list to be sure
your order is complete.
Step 4:If you discover a problem, call the ETC Systems Group the closest office of
purchase. See “Contacting ETC” on page 2.
Main Circuit Breaker Protection
Before you begin installing the DRd enclosure, make sure you have installed a main circuit
breaker cabinet or other readily accessible input power disconnect device. In certain
bussed and cross-bussed systems, this disconnect device may be the Unison AX series
auxiliary enclosure with a main circuit breaker.
WARNING:
DRd enclosures installed without an accessible power disconnect device
cannot be serviced or operated safely. Follow all local codes and
restrictions.
Before removing dimmer or control modules for service, de-energize main
feed to DRd and follow appropriate Lockout/Tagout procedures as
described in NFPA Standard 70E. It is important to note that electrical
equipment such as dimmer enclosures can present an arc flash safety
hazard if improperly serviced. This is due to available large short circuit
currents on the feeders of the equipment. Any work on energized equipment
must comply with OSHA Electrical Safe Working Practices.
Using 90° Copper Wire
To comply with UL requirements:
Use Copper Conductors Only, the torque rating for each Non-Class 2 field-wire
connector, and “Use 90°C conductors at the 75°C Ampacities”, where readily visible in
the field wiring compartment; Class 2 adjacent to each Class 2, field-wiring connector.
Use only 90°C-rated copper wiring installed in accordance with all applicable local electrical
codes.
CAUTION:
A two-wire circuit with separate hot and neutral conductors is required for every
branch circuit that will be connected to the DRd enclosure. Shared neutral (multiwire) branch circuit arrangements are not recommended for phase control
dimming systems due to harmonics and potentially elevated neutral currents in a
shared neutral arrangement.
For retrofit installations where shared neutral circuits are already installed, or
enclosure lighting installations where the enclosure has a shared neutral, consult
ETC Technical Services for installation guidelines.
1Prepare for Installation5
Page 10
Maximum Current Draw
TypePhase Type
DRd6
AX6
DRd12
AX12
AX12X
Note:
Single Phase (1Ø)120A150A
Three Phase (3Ø)80A100A
Single Phase (1Ø)
Three Phase (3Ø)
Single Phase (1Ø)240A300A
Three Phase (3Ø)160A200A
Single Phase (1Ø)
Three Phase (3Ø)
Single Phase (1Ø)
Three Phase (3Ø)
1
Connected to DRd enclosure with a full complement of 20A modules.
2
Connected to two DRd enclosures with a full complement of 20A modules.
3
Installed in a main circuit breaker model auxiliary enclosure.
4
Wire bending space limits the feed to the AX12X-MCB to 400A maximum. ETC
installs a 100% rated two pole breaker (or two poles from a three pole breaker) in
the AX12X-MCB, for a total deliverable current of 400A in a single phase (split
phase) configuration.
Maximum
Current Draw
1
120A
1
80A
1
240A
1
160A
2
480A
2
320A
Suggested
Breaker
Rating
3
150A
3
100A
3
300A
3
200A
4
400A
3
400A
Short Circuit Current Rating (SCCR)
SCCR at
Configuration
100-120v
Ac
DRd622,000A22,000A
DRd6 with AX6 (MCB)100,000A65,000A
DRd1222,000A22,000A
DRd12 with AX12 Main Lug22,000A22,000A
DRd12 with AX12X (cross-bussed) Main Lug22,000A22,000A
DRd12 with AX12 Main Circuit breaker100,000A65,000A
DRd12 with AX12X Main Circuit breaker100,000A65,000A
SCCR at
240 &
277v Ac
6DRd Enclosure Installation Manual
Page 11
Where to Install the Enclosure
Unison DRd enclosures are designed to be surface mounted on load bearing walls in an
electrical closet or a room with restricted public access. When required, an optional
semi-recessed installation kit is also available. It is recommended that you install the
enclosure at least 36” (915mm) above the finished floor to ensure clear view of the control
processor (E-ACP, S-ACP, or P-ACP) for programming and operation. Alternatively, DRd
enclosures may install to a floor standing pedestal (model DRd-Ped).
Clearance Requirements
DRd enclosures require 12” (305mm) top clearance for proper airflow through the cabinet.
For sufficient door clearance, install the enclosure with at least 17” (432mm) of front
clearance and a 6” (152mm) clearance to the left of the door hinge from walls or other
equipment.
152 mm
(6”)
432 mm
(17”)
305 mm
(12”)
914.4 mm
(36”)
Note:
Additional Unison dimming and auxiliary enclosures of the same size are the
exception to the 6” (152mm) hinge side clearance rule. Unison enclosures are
designed for side by side installation.
Dimensions and Weights
Type
DRd621.8553174311025437.817.24219.0
DRd123178717431102545123.15525
Note:
HeightWidthDepth
inchesmminchesmminchesmmlbskgslbskgs
For module weight please reference “Modules Specification,” page 57.
Product
Weight
Shipping
Weight
1Prepare for Installation7
Page 12
Installation Environment Requirements
0°
10°
20°
30°
40°
50°
60°
70°
80°
90°
100°
-18°
-10°
0°
10°
20°
30°
40°
•For your own safety, install a main circuit breaker cabinet or other readily accessible
power disconnect in the same area as the DRd enclosure. For cross-bussed
installations, this device may be the auxiliary enclosure. Main breakers not in the same
room must have a physical means to be locked off. ETC recommends adopting lockout
/ tagout procedures for your facility and following appropriate Lockout/Tagout
procedures as described in NFPA Standard 70E.
•A clean (not dusty) temperature-controlled environment with an ambient temperature
of 32-104°F / 0-40°C and ambient humidity of 10-90%, non-condensing.
CAUTION:
HVAC systems must at all times maintain the specified ambient temperature at the
enclosure. Dimming systems operating within 10°F (5°C) of the upper or lower
temperature limits must strictly follow installation and operation guidelines to
operate reliably.
•Restricted public access to prevent tampering.
•Soundproofing or performance area separation to muffle ventilation fan noise is
recommended.
•All CE equipment is tested to EMC category B environment.
Wire Routing and Specification
When planning wire entry into the enclosure, notice that conduit knockouts are provided
only on the sides of the unit. These knockouts are primarily used for bussing to an auxiliary
enclosure but may also be used for load or control wiring. Signal and power wiring must be
run in separate conduit per local code.
Due to the bend radii of certain size line feed wires and the location of terminations, special
attention is required for line feed wire entry. Reference the wiring guidelines below for
recommendations.
CAUTION:
Do not route line (input feed) wires through the back panel. Doing so requires bend
radii that violate NEC code, UL standards and because of undue stress at the wire
joint is likely to create a poor connection.
Line and load wire used with Unison DRd enclosures must be copper. Load wires
may either be stranded (preferred) or solid core. The use of aluminum wire is not
allowed in DRd enclosures.
Aluminum feed wires are supported only in the auxiliary (AX Series) enclosures.
Wire Size
Wire Access
Location
DRd12 Feed
(max)
350 Kcmil
185mm
Top
Bottom
Left side
Right side
8DRd Enclosure Installation Manual
acceptableacceptableacceptableacceptable
acceptableacceptableacceptablepreferred
Do Not UseDo Not Useacceptableacceptable
Do Not UseDo Not Useacceptableacceptable
2
DRd6 Feed
(max)
2/0-3
2
70mm
Load Wires
12 - 6AWG
2.5 - 16mm
2
Control
Wires
Page 13
Note:
To a ddi t i ona l
DRd rack
enclosures
EchoConnect
& DMX
power
feed
power
feed
power
feed
To l o ad c i rc u i ts
DMX input
to DRd rack
ETC Console
(for optional stage lighting)
EchoConnect
Preset 4
Unison DRd12
rack enclosure
Echo
Relay Panel
Unison DRd12
rack enclosure
Echo Inspire Stations
Element
console
Split phase applications require a simple field adjustment to the phase bussing.
See “Modify Phase Bus for 120V AC Split Phase Operation” on page 19.
Wire Size
Wire Access
Location
Top
Bottom
Left side
Right side
Wire Access
Location
Top
Bottom
Left side
Right side
Feed (max)
350 Kcmil
185mm
2
acceptableacceptableacceptableacceptable
acceptableacceptableacceptablepreferred
Do Not UseDo Not Useacceptableacceptable
Do Not UseDo Not Useacceptableacceptable
DRd12 Feed
(max) 250 Kcmil
120mm
2
acceptableacceptableacceptableacceptable
acceptableacceptableacceptablepreferred
Do Not UseDo Not Useacceptableacceptable
Do Not UseDo Not Useacceptableacceptable
Control Specifications
The riser below is typical of a small Unison system utilizing Echo Architectural Control
Processors (E-ACP) for control and Unison Echo
activation. DMX input to the DRd enclosures provide an additional level of system control
and integrates the architectural and theatrical lighting control systems.
DRd6 Feed
(max)
250 KCmil
120mm
2
Wire Size
DRd6 Feed
(max)
2/0-3
2
70mm
Load Wires
12 - 6AWG
2.5 - 16mm
Control Wires
2
Load Wires
12 - 6AWG
2.5 - 16mm
®
Inspire™ control stations for control
Control Wires
2
1Prepare for Installation9
Note:
DRd enclosures are shipped with the lugs installed in a top feed orientation by
default. You can change the lug orientation to a bottom feed if required.
Page 14
The riser below is typical of a Unison system utilizing Paradigm Architectural Control
Processors (P-ACP) for control and Unison control stations for control activation. Paradigm
systems provide a DMX input into the system for larger system integration and control. A
Paradigm system also utilizes Net3 networking for an additional level of system-wide
control.
Preset 1
Preset 6
To a ddi t i ona l
DRd rack
enclosures
DMX
thru
Unison DRd12
rack enclosure
power
feed
To l o ad c i rc u i ts
Unison DRd12
rack enclosure
power
feed
Unison DRd12
rack enclosure
power
feed
Unison
LinkConnect
LinkConnect
Aux Power 24 vdc
DMX input
to DRd rack
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Gio
console
ETC Console
(for optional stage lighting)
Sequence
Macro Record
Heritage stations
Sequence
Macro Record
Preset 1
Preset 2
Preset 7
Preset 2
Preset 8
Preset 3
Preset 3
Preset 9
Preset 4
Preset 4
Preset 5
Preset 10
Preset 5
Preset 1
Preset 6
Preset 1
Preset 2
Preset 7
Preset 2
Preset 8
Preset 3
Preset 3
Preset 9
Preset 4
Preset 4
Preset 5
Preset 10
Preset 5
Paradigm Touchscreen
station
Note:
DRd enclosures are shipped with the lugs installed in a top feed orientation by
default. You may change the lug orientation to a bottom feed if required.
Control Wire Specification
The following tables lists the recommended control wire types used in a DRd installation
and the maximum length (aggregate) of wire runs allowed for each type.
Purpose
Total length of control wire
(without repeater module)
Maximum wire length
(station to station)
Maximum repeater distance
(P-SPM only)
Purpose
Total length of control wire
(without repeater module)
Maximum wire length
(station to station)
LinkConnect (P-SPM and S-SPM)
Aux 24 vDC
(Belden 8471)
(P-SPM only)
(2) #16 AWG
EchoConnect
(E-SPM)
Belden 8471 or
Belden 1583a
FeetMeterFeetMeterFeetMeter
164050015004571640500
131240013124001640500
16405001500457N/AN/A
DMX (Belden 9729)Category 5 /Belden 1583a
FeetMeterFeetMeter
1600487328100
1600487N/AN/A
10DRd Enclosure Installation Manual
Page 15
Data Types and Topologies
LinkConnect and EchoConnect Control Wiring
Control stations communicate with the control processor using the LinkConnect or
EchoConnect station communication bus.
Termination is available for up to six home runs of LinkConnect / EchoConnect data runs
utilizing Belden 8471 cable (or approved equal) plus one 14 AWG (2.5mm2) ESD drain
wire. This wiring is topology-free and can be installed in any combination of bus, star, loop,
and home run. The total combined length of all wire runs cannot exceed 1,640 feet (500m).
CAUTION:
Note:
Auxiliary 24 vDC
Auxiliary power is required when you are installing certain Unison control stations. ETC
recommends using two 16 AWG stranded wires for 24 vDC auxiliary power to the control
station(s). Auxiliary power is topology-free.
DMX (Digital Multiplex)
DMX can address up to 512 channels of control. DMX is installed in a daisy chain topology
and includes one pair of wires (data +, data -) plus an ISO ground. ETC recommends the
use of Belden 9729 (or approved equal) wire with a single end of line termination (90150). For best DMX performance, twist the wires together as close to the pluggable
connector as possible.
Note:
While the wiring terminations for LinkConnect, used in SmartLink and Paradigm
systems, and EchoConnect used in Echo systems, are similar, the communication
and control types are not interchangeable. Each product family requires a
dedicated station infrastructure that cannot be shared.
It is required that you terminate LinkConnect / EchoConnect station wiring and the
auxiliary power wiring in the same enclosure the station power module and
architectural control processor will be installed.
It is required that you terminate DMX control wiring in the same enclosure (rack 1)
where the architectural control processor will be installed.
1Prepare for Installation11
Page 16
Chapter 2
Install Enclosures
This chapter contains instructions for installation of the DRd enclosure.
Unison DRd enclosures are designed to be surface mounted on load bearing walls in an
electrical closet or a room with restricted public access. Alternatively the DRd enclosure
may be mounted on a pedestal (DRd-Ped). It is recommended that enclosures installed on
the pedestal floor stand also be secured to the wall for greater stability.
Mounting Individual Enclosures on a Wall
The wall must be strong enough to hold the enclosure fully populated with modules, conduit
and wire. See “Dimensions and Weights,” on page 7 and
“Modules Specification,” page 57.
Step 1:Determine where your enclosure will be installed using the weight and dimension
requirements detailed in “Where to Install the Enclosure,” page 7.
Step 2:Use the measured slot dimensions located in the graphic below to mark the hole
locations for the mounting hardware.
Step 3:Drill the holes and install the mounting hardware for each enclosure.
Step 4:Attach the enclosure to the wall.
Step 5:Check that the enclosure is level and plumb and tighten the mounting hardware.
432 mm
17”
184mm
7.25
194mm
7.64”
160mm
6.3”
113mm
4.45”
• Four 3/8” (M8-M10) bolts or screws 2-4” (50-100mm) long, and suitable
wall plugs are suggested mounting hardware (lag bolts recommended).
• Both the surface and the mounting hardware must support the weight of
the enclosure unit fully populated with modules.
• Expose at least 1” (25mm) of threads for mounting the enclosure.
2Install Enclosures13
Page 18
Mounting a DRd Enclosure on a Pedestal
The Unison DRd pedestal is designed with the same footprint as the DRd enclosure.
The acceptable conduit access in the bottom of the DRd overlaps the floor stand access
panel for contractor wiring and installation convenience. It is recommended to secure a
DRd enclosure installed on a pedestal to a wall for greater stability.
432mm
17”
186.7mm
7.35”
35.5mm
1.4”
35.5mm
1.4”
Step 1:Use the measured
dimensions in the
graphic (right) to mark
the hole locations for the
floor mounting hardware.
Step 2:Drill holes for floor
mounting hardware.
Step 3:Remove the eight screws and washers that secure the front panel to the unit.
Step 4:Position the floor stand on floor hardware previously placed for marking the
holes.
Step 5:Secure the pedestal base to the floor.
Step 6:Create conduit access in the bottom of the DRd enclosure. Notice the label inside
the bottom of the enclosure indicating the recommended locations for conduit
access. Do not create conduit access outside of the recommended locations.
Step 7:Position the DRd on the floor stand pedestal and align with the mounting holes
Step 8:Bolt the enclosure into place.
Step 9:Reinstall the front panel to the pedestal unit, replacing all hardware removed in
14DRd Enclosure Installation Manual
provided.
step 3.
Page 19
Mounting Auxiliary and DRd Enclosures Together
432mm
17”
451mm
17.75”
194mm
7.64”
113mm
4.45”
160mm
6.3”
432mm
17”
62mm
2.44”
787mm
31”
406mm
16”
406mm
16”
330mm
13”
559mm
22”
559mm
22”
DRd12-48 rear panel view
Unison DRd and AX auxiliary enclosures are designed to be surface mounted on load
bearing walls in an electrical closet or a room with restricted public access. One DRd
enclosure may be bussed to the AX series auxiliary enclosure, which may contain a main
circuit breaker or a main lug for power distribution to the adjacent DRd12 enclosure. Two
DRd12 enclosures may be cross-bussed to an AX12X auxiliary enclosure which is
designed to provide main lug or main breaker input feed termination to the adjacent DRd12
enclosures.
The wall must be strong enough to hold all enclosures fully populated with modules, conduit
and wire. Reference “Where to Install the Enclosure,” page 7 for weight, dimension and
clearance requirements.
Step 1:Determine where the enclosures will be installed using the weight and dimension
requirements detailed in “Where to Install the Enclosure,” page 7.
Step 2:Use the measured slot dimensions located in the graphics below to mark the hole
locations for the mounting hardware.
Step 3:Drill the holes and install the mounting hardware for each enclosure.
• Four 3/8” (M8-M10) bolts or screws 2-4” (50-100mm) long, and suitable
wall plugs are suggested mounting hardware per enclosure (lag bolts
recommended).
• Both the surface and the mounting hardware must support the weight of
Step 4:Remove the conduit knockouts from the mating side conduit plugs on the DRd
the enclosures fully populated with modules.
• Expose at least 1” (25mm) of threads for mounting the enclosure.
and auxiliary enclosures before installation. Only remove the knockouts that are
adjacent to another enclosure.
Step 5:Install one DRd enclosure first (follow instructions as outlined in “Mounting
Individual Enclosures on a Wall,” on page 13. Remember to install the DRd
enclosure to either side of the auxiliary enclosure in cross-bussed applications.
Step 6:Align the auxiliary enclosure against the DRd enclosure and mount it to the
previously installed hardware. Keyholes in the DRd and auxiliary enclosures are
aligned with each other for mounting to Unistrut or Kindorf. With conduit holes
mated, the bolt spacings are on 16” (406mm) centers (top left DRd and top left
2Install Enclosures15
Page 20
Ax) for installation convenience.
Step 7:Install the ETC supplied 2 1/2” (64mm) nylon insulated chase nipple and 2 1/2”
(64mm) locknut between the auxiliary and DRd enclosures.
Step 8:For cross-bussed DRd12-24 installations, install the second DRd12-24 by
following steps 4 through 7 above.
Step 9:Check that each enclosure is level and plumb then tighten the mounting
hardware for a secure installation.
Note:
Reference the related Auxiliary Enclosure Installation Manual to complete the
auxiliary enclosure installation and for DRd12-24 and DRd 12-48 enclosure input
power bus wiring termination.
Follow the instructions in this manual for all other DRd enclosure installation
procedures.
16DRd Enclosure Installation Manual
Page 21
Chapter 3
Rough-in Conduit and Wiring
This chapter contains instructions for conduit and wiring installation of the DRd enclosure.
The enclosure door
has been removed
from this graphic for
clarity of this
procedure.
All terminations are accessible from the front of the enclosure. Reference “Wire Routing
and Specification”, page 8 for conduit access specifications.
Prior to conduit installation you should remove the power supply access panel for clear
access to the top of the DRd enclosure. Reference “Remove the DRd Power Supply/
Dimming Engine Access Panel” below.
Take the opportunity before roughing in your conduit to change your DRd for split phase
operation (100/120V AC enclosures only) if required. Reference “Modify Phase Bus for
120V AC Split Phase Operation”, page 19.
Remove the DRd Power Supply/Dimming Engine Access Panel
Remove the power supply/dimming engine access panel to allow for better access in the
top of the DRd enclosure while roughing in conduit and cable.
18DRd Enclosure Installation Manual
Step 1:Loosen the two captive screws that secure the access panel.
Step 2:Gently pull the panel straight down until the top of the access panel is clear of the
enclosure.
Step 3:Tilt the supply access panel away from the enclosure.
Step 4:Disconnect the three cables that are attached to the unit.
a: For the cable bundle on the left side, squeeze the tabs on either side of the
connector and gently pull the cable until it is free from the unit.
Page 23
b: For the ribbon cable connected on the right rear side, release the tabs on
L1
L2
L3
N
L1
L2
L3
Step 1:
Step 2a:
Step 2b:
The enclosure door
has been removed
from this graphic for
clarity of this
procedure.
either side of the connector by sliding them opposite the connector then
gently pull the cable free. Temporarily secure this cable out of the way while
pulling conductors into the enclosure.
c: For the two-wire cable on the right side, gently pull the connector straight out.
Step 5:Remove the power supply access panel.
a: Align the panel perpendicular to the enclosure.
b: Slide the panel up approximately one inch to align the guide pins on the top
of the guided slots.
c: Then pull the panel straight out.
Note:
Store this access panel in a safe place until you are finished roughing in conduit
and terminations. You will need to reinstall this panel when then enclosure is
installed and all wires have been terminated.
Modify Phase Bus for 120V AC Split Phase Operation
The DRd can be simply field modified from a three phase operation to a split phase (3 wire
plus ground) operation.
3Rough-in Conduit and Wiring19
Step 1:Notice the two copper straps (stacked) on phase L2.
Step 2:Change the DRd operation from 3Ø to split phase by moving the copper straps,
strapping the phase bars together, (reference the graphic above to follow along).
a: Move one of the copper straps to connect between phase 1 (L1) and phase
2 (L2). The screws required are installed to the phase bars in the location the
copper strap will be mounted.
Page 24
b: Remove the red sense wire from phase 2 (L2) and reroute it to the neutral
L1
L2
L3
N
N
L1
L2 L3
L1 L2 L3
L1
L2
L3
N
The enclosure
doors have
been removed
from this
graphic for
clarity of this
procedure.
bar.
c: Move the second copper strap to connect between phase 2 (L2) and phase
3 (L3).
Step 3:For cross-bussed DRd12-48 installations, complete step 2 for both enclosures.
20DRd Enclosure Installation Manual
Page 25
Rough-in Conduit to the DRd Enclosure
L1
L2
L3
N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Top Feed DRdBottom Feed DRd
Line feed wires terminate on the main lugs provided.
The DRd12 enclosure is shipped from the factory with the main lugs in a top feed
orientation. The lugs can be changed to a bottom feed orientation by removing the lug
mounting bolt, rotating the lug 180°, and re-mounting the lug in the opposite lug mounting
PEM. This is true for all DRd12 models.
The DRd6 enclosure phase lugs are both top and bottom feed by default and don’t require
any change, but the neutral and ground lugs will require re-orientation for bottom feed.
1
2
3
4
5
6
L1
L2
L3
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
When utilizing an auxiliary enclosure with the DRd enclosure, line feed wires from the
auxiliary enclosure enter the DRd enclosure through the top side conduit knockout. For
cross-bussed installations the line feed wires will be fed to the DRd through the conduit
knockout on the adjoining side of the auxiliary enclosure.
Load circuits terminate to the right side the enclosure.
L1
L2
L3
N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Load Hot / Live
Load Neutral
Load Ground /
Earth
The enclosure door
has been removed
from this graphic for
clarity of this
procedure.
Load wires terminate to the load lugs on the
right side of the enclosure.
Load neutral and load ground wires terminate
on the neutral and ground bus bars located on
the back panel of the enclosure. An exception
to this is made for the DRd with CE neutral
disconnect. Neutrals are terminated to the
neutral disconnect on the left side of the
enclosure. See “230V AC Neutral Disconnect
DRd Enclosures” on page 27.
Control wires terminate to the right and left I/O boards in
the DRd enclosure.
Control wires can enter the enclosure from the top, bottom, or
either side, although ETC recommends that you pull control
wires into the enclosure from the bottom since all control
AUX POWER
LON LINK / ECHO BUS
SIGNAL DISTRO
LPS
terminations are located near the bottom.
RIDE THRU/BATT
A+ A- COM
B+ B- COMA+ A- COM
B+ B- COM
COMPANIC
SRCOFFEND
CDI
J9
DUAL RACKS
APM
DMXB DMXA
The right I/O board is shipped standard with all DRd
enclosures and includes terminations for:
•24 vDC Auxiliary Power output connector.
•LinkConnect/EchoConnect connector.
•UL 924 emergency contact input for control bypass.
A Left I/O card is available for use with Echo
ACP and is required for use with Paradigm ACP
systems.
Optional Echo Left I/O
The Echo Left I/O board is available as an option
for use with the Echo Architectural Control
Processor and includes Ethernet connection.
Required Paradigm Left I/O
The Paradigm left I/O board is included with the
Paradigm ACP system and include terminations
for:
•Ethernet
•RS232 bi-directional serial
•4 dry contact inputs
•4 relay contact outputs
Procedure
Step 1:Plan wire entry to the enclosure. See “Wire Routing and Specification” on page 8.
Step 2:Make the desired conduit access (top, bottom, left or right) from the enclosure.
Read and comply with the label inside the enclosure which details the
recommended access locations for conduit entry.
Note:
Step 3:Punch holes and install conduit fittings or insert lining materials in conduit
Step 4:Be sure there are minimal air gaps. See “Sealing Air Leaks” on page 52.
CAUTION:
Do not run power and control cable in the same conduit.
opening.
Wire openings must have fittings, bushings, grommets or fiche paper lining
material to protect the wire and cable insulation from damage by sharp metal
edges, and to prevent air leaks.
All terminations must be done with the power off. DRd enclosures installed
without an accessible power disconnect device cannot be serviced or
operated safely. In some instances, this device may be an auxiliary
enclosure with a main circuit breaker. Follow all local codes and
restrictions.
Before servicing, de-energize main feed to DRd and follow appropriate
Lockout/Tagout procedures as described in NFPA Standard 70E. It is
important to note that electrical equipment such as dimmer enclosures can
present an arc flash safety hazard if improperly serviced. This is due to
available large short circuit currents on the feeders of the equipment. Any
work on energized equipment must comply with OSHA Electrical Safe
Working Practices.
Line and load wires used with the Unison DRd must be copper. Do not use
aluminum wire.
Connect Line Feed in an Individual DRd Installation
Line feed cables are terminated on the main phase lugs. It is best to route line (feeder)
cables first, load neutral and ground/earth wires next, load phase and control wires last. In
multiple enclosure installations, load neutral and ground/earth wires must terminate in the
same enclosure as the matching load phase wires.
Note:
For DRd6 and DRd12 main lug, main breaker, and cross-bussed applications,
reference the Unison Auxiliary Series Enclosure Installation Manual.
The bus bars are different for each enclosure type (DRd6 or DRd12) and each voltage (120,
230 or 240-277). Graphics are provided on the following page for reference.
Step 1:Pull the line phase, neutral and ground cables to the enclosure through the
openings (conduit or other fittings) previously prepared.
Step 2:Strip the insulation from the end of each cable and terminate them to the lugs.
Reference the table below for wire stripping lengths.
Model
DRd6 120, 240, 277V AC
DRd6 230V AC
DRd12 240, 277V AC
DRd12 120, 230V AC
• Line and neutral connections are labeled L1, L2, L3 and N. The equipment
grounding/earthing lug is labeled with the universal grounding symbol for
easy identification.
Hex Key Size / Wire Strip Length
Phase
3/16” /
5mm
5/16” /
8mm
5/16” /
8mm
3/8” /
10mm
Strip
Length
5/8” /
16mm
1” / 25mm
1” / 25mm
1” / 25mm
Neutral
3/16” /
5mm
5/16” /
8mm
3/8” /
10mm
3/8” /
10mm
Strip
Length
5/8” /
16mm
1” / 25mm
1” / 25mm
1” / 25mm
Ground/
Earth
3/16” /
5mm
3/16” /
5mm
3/16” /
5mm
3/16” /
5mm
Strip
Length
5/8” /
16mm
5/8” /
16mm
5/8” /
16mm
5/8” /
16mm
4Terminate Wiring25
Page 30
Note:
CE enclosures are supplied with ANSI hex wrenches for line feed terminations.
Step 3:Tighten the lugs to the correct torque based on cable size. Torque ratings are
also labeled in the DRd enclosure for your convenience.
Dress wires neatly and avoid leaving extra wire inside the enclosure. Too much
clutter can restrict airflow and cause overtemp errors.
100, 120, 127 V AC, 3Ø DRd Enclosures
1
2
3
4
5
6
L1
L2
L3
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
N
23
24
DRd12
240 and 277V AC
250kcmil -
1 AWG
120mm2 -
50mm
2-6 AWG2/0-3 AWG4-6 AWG
35mm2 -
2
16mm
DRd6
(all models)
2
25mm
L1
2
L2
L3
N
70mm2 -
1
2
3
4
5
6
7
8
9
10
11
12
25mm2 -
2
16mm
Note:
For 120V AC single phase installation you must modify the phase bus before
connecting wiring. See “Modify Phase Bus for 120V AC Split Phase Operation” on
page 19.
26DRd Enclosure Installation Manual
Page 31
230V AC Neutral Disconnect DRd Enclosures
L1
L2
L3
N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
L1
L2
L3
N
1
2
3
4
5
6
7
8
9
10
11
12
L1
L2
L3
N
1
2
3
4
5
6
7
8
9
10
11
12
240, 277V AC DRd Enclosures
1
2
3
4
5
L1
L2
L3
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
N
4Terminate Wiring27
Page 32
Connect Load Wires
Load wire phase
Load wire
ground bus
Load wire
neutral bus
120, 240, and 277V AC DRd
enclosures share similar load
lugs.
L1
L2
L3
N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Load wire phase
Load wire
ground bus
Load wire
neutral bus
230V AC DRd enclosures have a
neutral disconnect bus structure.
This design places neutral lugs
on the same side of the enclosure
as the main feeds. Neutral output
lugs are numbered on the filter
PCB. It is important to wire hot
and neutral from each load to the
corresponding numbered
outputs.
Load wires are terminated to the load lugs on the right side of the enclosure. In 120V AC
and 240/277V AC DRd enclosures, load neutral and load ground wires are terminated to
the terminal strips on the back panel. In 230V AC enclosure types, load neutrals are
connected to the left side of the enclosure, stacked on top of the input feeds to maintain a
true neutral disconnect.
Phase balancing of the loads is set from within the Architectural Control Processor “Dimmer
Setup” menu. Reference the related Architectural Control Processor configuration manual
for details.
1
2
3
4
5
6
L1
L3
7
8
9
10
11
12
13
L2
14
15
16
17
18
19
20
21
22
N
23
24
WARNING:
Use of emergency modules (ED15AFE or ER15AFE) in CE 230V DRd
enclosures require the neutral (N) lug in place of the neutral jumper per
module.
CAUTION:
A two-wire circuit with separate hot/live and neutral conductors is required for
every branch circuit that will be connected to the DRd. Shared neutral (multi wire)
branch circuit arrangements are not recommended for phase-control dimming
systems due to harmonics and potentially elevated neutral currents in a shared
28DRd Enclosure Installation Manual
neutral arrangement.
For retrofit installations where shared neutral circuits are already installed, or
enclosure lighting installations where the enclosure has a shared neutral, consult
ETC Technical Services for installation guidelines.
Page 33
Note:
a: Insert the wire on the back side of the lugs.
b: Torque the lug screw to the recommended
value indicated in the table below.
Plan load wiring appropriately to avoid splicing wiring. Only one load wire per load
terminal.
Step 1:Route the load wires to the DRd enclosure(s) through the conduit previously
installed.
Step 2:Prepare the load wires for termination:
a: Label each wire in the set with circuit designation.
b: Separate load circuit wires into ground, neutral and hot/live wire bundles.
CAUTION:
Step 3:Strip 5/8” (16mm) of insulation from the end of each load wire.
Step 4:Route each load hot/live wire to its individual load output connection.
Connection
15 - 20 amp
Ground bus
Neutral bus
(excluding
Dress and terminate wires neatly and avoid leaving extra wire inside the
enclosure. Too much clutter (especially along the right side of the enclosure) can
restrict air circulation and reduce cooling efficiency. If cabling interferes with
airflow during operation, the DRd may be forced to shut down due to overheating.
Load wires should not cross between DRd enclosures. Instead, they should enter
the enclosure in which they will be terminated. Hot/Live and neutral load wiring
must follow the same conduit/path for each circuit.
load lugs
230V AC)
Cable SizeTorque
AWG
14 - 102.5 - 6352.94.0
6 - 416453.85.1
14 - 82.5 - 6756.38.5
6 - 4161109.212.4
14 - 82.5 - 6756.38.5
6 - 4161109.212.4
mm
2
lbf-inlbf-ftN - m
Wire Strip
Length
5/8” - 16mm810403.34.5
5/16” - 8mm
5/16” - 8mm
Neutral
Disconnect
(230V AC only)
4Terminate Wiring29
14 - 102.5 - 6352.94.0
5/8” - 16mm810403.34.5
6 - 416453.85.1
Page 34
Step 5:Strip the neutral wire to the length indicated in the table above and terminate to
the neutral terminal assembly. Torque to the recommended value also indicated
in the table above. For 230V AC DRd enclosures, the neutral bus is located on
the line input feed side of the enclosure.
Step 6:Strip the ground/earth wires to the length indicated in the table above and
terminate to the ground bus terminal. Torque to the recommended value also
indicated in the table above.
Note:
Ground connections must use all metal nuts and lock washers.
30DRd Enclosure Installation Manual
Page 35
Fluorescent Load Wiring
a: Insert the wire on the back side of the lugs.
b: Torque the lug screw to the recommended
value indicated in the table below.
Note:
When using D20FB modules, connected to dimmable fluorescent 2-wire ballasts
with integral battery backup, use the same terminations as listed in the 3-wire
Fluorescent instructions.
3-wire Fluorescent
To control 3-wire fluorescent ballasts, the power circuit in the enclosure must be configured
as a fluorescent module type (D15F, D20F, AD15F, AD20F,HD25F), which is a single
density module, with a 2/3 wire fluorescent dimmer mode assignment. Reference the
related Architectural Control Processor Configuration Manual for instructions on changing
the dimmer mode.
Note:
Step 1:Pull the three wire fluorescent ballast wiring into the DRd enclosure per the wire
Step 2:Strip 5/8” (16mm) of insulation from the end of each load wire.
Step 3:Terminate the black switched hot/live wire to the top terminal in its assigned
Even though two lugs are used, the configuration (as found in the Dimmer Setup
menu of the ACP) refers only to the top (odd) number lug.
entry plan.
dimmer lug pair. Insert the wire between the back of the lug and the pressure
plate as shown.
Cable SizeTorque
Connection
AWG
14 - 102.5 - 6352.94.0
mm
2
lbf-inlbf-ftN - m
15 - 20 amp
load lugs
6 - 416453.85.1
Ground bus
Neutral bus
(excluding
230V AC)
Neutral
14 - 82.5 -6756.38.5
6 - 4101109.212.4
14 - 82.5 -6756.38.5
6 - 4101109.212.4
14 - 102.5 - 6352.94.0
Disconnect
(230V AC only)
Step 4:Terminate the dimmed hot/live wire to the bottom terminal in its assigned dimmer
lug pair. Insert the wire between the back of the lug and the pressure plate as
4Terminate Wiring31
6 - 416453.85.1
Wire Strip
Length
5/8” - 16mm810403.34.5
5/16” - 8mm
5/16” - 8mm
5/8” - 16mm810403.34.5
Page 36
shown in the graphic above. Torque the wire to the recommended value in the
torque table above.
Step 5:Strip the neutral wire to the length indicated in the table above and terminate to
the neutral terminal assembly. Torque to the recommended value also indicated
in the table above.
Step 6:Strip the ground/earth wires to the length indicated in the table above and
terminate to the ground bus terminal. Torque to the recommended value also
indicated in the table above.
Note:
Ground connections must use all metal nuts and lock washers.
2-wire Fluorescent
To control 2-wire fluorescent ballasts, the power circuit in the enclosure must be configured
as a standard module type (D15, D20, AD15, AD20, ED15, ED25, HD15, HD25) with a 2/
3 wire fluorescent dimmer mode assignment. Reference the related Architectural Control
Processor Configuration Guide for instruction to change dimmer mode.
Step 1:Pull fluorescent ballast power wiring into the DRd enclosure per the wire entry
plan.
Step 2:Strip 5/8” (16mm) of insulation from the end of each load wire.
Step 3:Terminate the load wire (typically black) to the assigned dimmer lug by inserting
wire between the back of the lug and the pressure plate.
a: Insert the wire on the back side of the lugs.
b: Torque the lug screw to the recommended value indicated in the table below.
Connection
15 - 20 amp
load lugs
Ground bus
Neutral bus
(excluding
230V AC)
Cable SizeTorque
AWG
14 - 102.5 - 6352.94.0
6 - 416453.85.1
14 - 82.5 -6756.38.5
6 - 4101109.212.4
14 - 82.5 -6756.38.5
6 - 4101109.212.4
mm
2
lbf-inlbf-ftN - m
Wire Strip
Length
5/8” - 16mm810403.34.5
5/16” - 8mm
5/16” - 8mm
Neutral
Disconnect
(230V AC only)
Step 4:Strip the neutral wire to the length indicated in the table above and terminate to
the neutral terminal assembly. Torque to the recommended value also indicated
in the table above.
Step 5:Strip the ground/earth wires to the length indicated in the table above and
terminate to the ground bus terminal. Torque to the recommended value also
indicated in the table above.
Note:
32DRd Enclosure Installation Manual
Ground connections must use all metal nuts and lock washers.
14 - 102.5 - 6352.94.0
5/8” - 16mm810403.34.5
6 - 416453.85.1
Page 37
Connect Control Wiring
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
3
Right I/O board ships standard with
each DRd enclosure.
Left I/O board is
available as part of the
Paradigm Termination
Kit which ships with
the Paradigm ACP.
An optional Left I/O kit
is available for use
with Echo ACP when
DRd is being used in a
networked system.
The enclosure door has
been removed from these
graphics for clarity of the
procedure.
Note:
Overview
All low voltage data and option wiring connects to pluggable connectors on the left and right
I/O boards near the bottom of the DRd enclosure.
The DRd ships with a right side I/O board for low voltage control connections. Left side I/O
board is available in the optional Paradigm and Echo Termination Kits.
•The Paradigm Left I/O Kit supports contact inputs and outputs, serial RS232 and
•The Echo Network Kit supports an Ethernet connection for the Echo ACP. The Echo
All low voltage control cables must run in separate conduit from power wires.
Ethernet control. This Left I/O board is not compatible with the SmartLink or Echo
Architectural Control Processors.
Network Kit is not compatible with the SmartLink or Paradigm ACPs.
4Terminate Wiring33
Note:
•The right side I/O board is shipped installed with each DRd and provides termination
for SmartLink / LinkConnect / EchoConnect, auxiliary power, DMX, and a UL 924
emergency contact input. The DRd enclosure supports option kits which install in the
bottom of the DRd for extended control and operation and terminate to the right I/O
board. Option modules include:
•0-10V Control Option (DRd-FLO) which provides 24 outputs for control of 0-10V
(4-wire) control for LED drivers and fluorescent ballasts. Each channel output is
linked one-to-one with a circuit for power control.
•Digital Addressable Lighting Interface (DRd-DALI) which provides 24 outputs for
control of DALI-compatible fluorescent ballasts. Each channel output of DALI
control is linked one-to-one with a circuit for power control (DALI Broadcast Mode).
A DRd enclosure supports the use of either a DALI option board (DRd-DALI) or
the FLO option board (DRd-FLO), but not both.
•Unison RideThru kit provides power to the ACP during brief power outages or drop
outs. The URTO sustains power to the ACP for at least 12 seconds.
•Unison BatteryPack kit sustains power to the ACP for up to 90 minutes during
power outages.
Page 38
.
Note:
A DRd enclosure supports the use of either the Unison RideThru option or the
Unison BatteryPack option, but not both.
RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all power to
the enclosure before working inside the DRd could result in serious injury
or death.
De-energize main feed to DRd enclosure and follow appropriate Lockout/
Tagout procedures as described in NFPA Standard 70E. It is important to
note that electrical equipment such as dimmer enclosures can present an
arc flash safety hazard if improperly serviced. This is due to available large
short circuit currents on the feeders of the equipment. Any work on
energized equipment must comply with OSHA Electrical Safe Working
Practices.
AUX POWER
SIGNAL DISTRO
Note:
Auxiliary Power
The auxiliary power connector (labeled Aux Power) provides termination for up to 16 wires
in the eight position pluggable connector. Each terminal allows up to two 16 AWG (1.5mm
wires and provides 24vDC power to control stations when used with the Paradigm Station
Power Module. Auxiliary power is not compatible with the Echo or SmartLink Station Power
Module.
Note:
Step 1:Pull control auxiliary power wiring (typically 16 AWG (1.5mm
Step 2:Strip 3/16” (5mm) of insulation from the ends of each wire pair.
Step 3:Remove the auxiliary power connector from the right I/O board.
Step 4:Loosen the terminal screws for as many auxiliary wire pairs as you are
Step 5:Insert the black auxiliary power wire from the pair into a “-” terminal on the
Step 6:Insert the red auxiliary power wire from the pair into a “+” terminal on the
Step 7:Repeat steps 5 and 6 for each auxiliary power wire pair.
Step 8:Replace the connector on the right I/O board.
All low voltage control cables must run in separate conduit from power wires.
2
It is required that you terminate LinkConnect / EchoConnect station wiring and the
auxiliary power wiring in the same enclosure (rack 1) where the station power
module and architectural control processor will be installed.
2
) red / black wire
pair) into the enclosure through the conduit opening previously prepared.
terminating.
connector and tighten the screw to secure the wire into the connector.
connector and tighten the screw to secure the wire into the connector.
)
34DRd Enclosure Installation Manual
Page 39
LinkConnect and EchoConnect Control Wiring
Control stations communicate with the Architectural Control Processor using the
LinkConnect or EchoConnect station communication bus from the Architectural Control
Processor to the stations.
Note:
Note:
Termination is available for up to six home runs of LinkConnect / EchoConnect data runs
utilizing Belden 8471 cable (or approved equal) plus one 14 AWG (2.5mm
2
) ESD drain
wire. This wiring is topology-free and can be installed in any combination of bus, star, loop,
and home run. The total combined length of all wire runs cannot exceed 1,640 feet (500m).
While the wiring for LinkConnect in SmartLink and Paradigm and EchoConnect for
Echo systems are similar, the communication and control types are not
interchangeable. Each product family requires a dedicated station infrastructure
that cannot be shared.
Step 1:Pull Belden 8471 (approved equal) control wiring and a 14 AWG ground into the
enclosure through the conduit opening previously prepared.
Step 2:Strip 3/16” (5mm) of insulation from the ends of each wire pair.
Step 3:Remove the EchoConnect/ LinkConnect (LON) connector from the right I/O
board.
Step 4:Loosen the terminal screws for as many wire pairs you are terminating.
Step 5:Insert each white wire (typical) from the pairs into a “B” terminal on the connector
and tighten the screws firmly to secure the wire into the connector.
Step 6:Insert each black wire (typical) from the pairs into an “A” terminal, next to the
previously installed “B” terminal on the connector and tighten the screws firmly to
secure the wire into the connector.
It is required that you terminate LinkConnect / EchoConnect station wiring and the
auxiliary power wiring in the same enclosure (rack 1) where the station power
module and architectural control processor will be installed.
Step 7:Terminate the 14 AWG (2.5mm
2
) ground wire to the DRd ground bus bar in the
rear of the enclosure.
Step 8:Replace the connector to the right I/O board.
UL 924 Listed Panic Input
Termination is available for a UL 924 Listed dry contact input for
control bypass. The two pin panic connector, labeled “PANIC”,
accepts 16 AWG (1.5mm
2
) wire. Reference the related
Architectural Control Processor Configuration Manual for panic
look setup.
Step 1:Pull panic wiring into the enclosure through the conduit
opening previously prepared.
Step 2:Strip 3/16” (5mm) of insulation from the ends of each
wire.
Step 3:Remove the 2 pin Panic connector from the right I/O board.
Step 4:Loosen the terminal screws.
Step 5:Insert each wire into the terminals on the connector and tighten the screws firmly
to secure the wires into the connector.
Step 6:Replace the connector to the right I/O board.
ER /
RU/BATT
COM PANI C
J9
DUAL RACKS
CDI
4Terminate Wiring35
Page 40
DMX Control Wiring
12345678
n/c
n/c
COM
Data +
Data - ORG
W/ORG
W/BRN
COM
Data +
Data - ORG
W/ORG
W/BRN
Use the DMX Pass-Thru
connector
If daisy-chaining to
another rack or
DMX device...
DMX A
Thru
DMX B
Thru
1234567812345678
COM
Data +
Data +
Data -
Data - ORG
W/ORG
BRN
GRN
W/GRN
BLU
W/BLU
W/BRN
ORG
W/ORG
BRN
GRN
W/GRN
BLU
W/BLU
W/BRN
COM
From source
DMX A
From source
DMX B
Note:
It is required that you terminate DMX wiring in the same enclosure (rack 1) where
the architectural control processor will be installed.
DMX wire preparation and termination will vary with the type of wire and termination kit
being used. Please refer to the instructions supplied with the DMX termination kit for
specific wire preparation.
DMX Input Wire Termination using the Screw Terminals
Connector
The graphic to the left illustrates DMX termination layout for the
screw-terminal connectors that are intended for use with Belden
9729 cable (or approved equal) cable type.
Screw terminal connectors are supplied as standard in the DMX
Preparation Kit w/ Screw Connector, part number 4100A1012.
Be aware that cable other than Belden 9729 may have a different
color code for its wire pairs.
DMX Input Wire Termination using the Insulation
Displacement Connector (IDC)
The graphic below illustrates DMX termination layout for an insulation displacement
connector. This connector type is intended for use with Belden 1583A (or approved equal,
such as Category 5, 5E, or 6) cable type. Be aware that cable other than Category 5 may
have a different color code for its wire pairs.
If daisy-chaining to
From source
another rack or
DMX A
DMX device...
COM
Data + (Red)
Data - (Black)
n/c
n/c
n/c
n/c
n/c
12345678
Reference and follow the DMX Cable Preparation for IDC Termination instruction sheet that
is shipped with the insulation displacement pluggable connector kit (part number
4100A1013).
AX12X Cross-bussed Interconnection
Termination is provided for connection of a second DRd enclosure when installed in a
cross-bussed application. This termination point is labeled “Dual Enclosures” on the right
I/O board.
An interconnect cable is provided which connects enclosure 1, which is the DRd with the
ACP installed, to enclosure 2, which is the secondary enclosure in the cross-bussed
system. This cable is labeled at both ends, one end indicating enclosure 1 and the other
end indicating enclosure 2. You must have installed this cable to the correct enclosure for
proper operation.
This interconnection of enclosures allows full control of both DRd enclosures from only one
Architectural Control Processor installed in rack 1. This may only be used in a cross-bussed
applications.
Reference the Unison Auxiliary Enclosure Installation Manual for instructions to accomplish
this termination.
36DRd Enclosure Installation Manual
Page 41
Terminate the Unison Options (URTO and UBPO)
LO
Termination is available on the right I/O for the either the Unison
Ride Through Option or the Unison BatteryPack Option. You may
use only one of these option kits per enclosure.
Step 1:Notice the two pin connector labeled “RideThru / Batt” on
the right I/O board.
Step 2:Follow the instructions provided in the Setup Guide,
provided with the option kit, for appropriate termination.
APM
-THRU
B
+ B- COM
DMXBDMXA
SRCOFFEND
Note:
Terminate DMX
DMX requires 120 termination at the last DMX
device in the control run. Since a DRd with a
Paradigm module installed can utilize up to two DMX
inputs (2 DMX runs) the right I/O board provides
convenient termination switches for use.
Notice the two termination switches labeled DMXA
and DMXB. Each switch has three termination
positions:
•Source - reserved for RDM termination (future
A single DRd enclosure supports the use of either the Unison RideThru Option
board or the Unison BatteryPack Option, but not both in one enclosure.
RideThru/Batt
development).
J9
DUAL RACK
Half
•Off - no termination, DMX will pass through this device on to the next DMX device in
the data run.
•End - termination is on. Used for the last DMX device (DRd) that is physically
connected in the daisy-chained DMX data run.
When a Paradigm ACP is used in an Unison DRd enclosure, port B will be configured as
an output and cannot be changed. Port A is configured as either a DMX input or output.
When used as an output the DMX termination should always be set to “Off”.
When an Echo or SmartLink ACP is utilized in the Unison DRd enclosure, port A is
automatically configured to be a DMX input and cannot be changed, port B is not used.
The Left I/O board is not included with the DRd enclosure when shipped from the factory.
Instead, the appropriate board is provided in the Paradigm DRd Termination kit or Echo
ACP Network Option kit when ordered separately. The Left I/O board should be installed
by the installing contractor or field technician. Follow the instructions provided with the Left
I/O board for installation and wire termination.
Note:
Data terminations to the left I/O board are specific to the processor used.
SmartLink does not support a left I/O option.
The left I/O board supports the Echo Architectural Control Processor and Paradigm
Architectural Control Processor data terminations including:
•Ethernet on a RJ-45 female connector.
•RS-232 on a male 9 pin (D style) connector (P-ACP only).
•Contact closure input terminations on a 8 pin pluggable connector (P-ACP only).
•Terminations available for 4 inputs and 4 common wires.
•Contact closure output terminations on a 8 pin pluggable connector (P-ACP only).
•Terminations available for 4 normally open relay outputs and 4 common wires.
Connect to Serial RS-232
Integrators or users of advanced systems can interface with the Unison system through the
RS-232 connector on the left I/O board. This connection provides an interface with external
devices capable of sending or receiving RS-232. This connection can also receive serial
commands from a transmitter and provide DRd and system status when queried.
Note:
The RS-232 cable (not supplied) should follow common RS-232 pinout for a DB9
receptacle (pin 2 is RS-232 Rx, pin 3 is RS-232 Tx, and pin 5 is ground).
Connect to Ethernet RJ-45
Network interface to the DRd is made through the RJ-45 connector (labeled Ethernet)
located on the left I/O board.
38DRd Enclosure Installation Manual
Note:
All Ethernet terminations must follow IEEE 802.3 and be terminated to the T568B
standard.
Page 43
Connect to Contact Inputs and Contact Outputs
The left I/O provides a convenient interface (inputs and outputs) to external devices via
contact closure on removable pluggable connectors. Up to four contact inputs are available
and can be configured for either maintained or momentary operation by the technician
creating the Paradigm architectural configuration. Up to four contact outputs are available
and are preset for normally open operation.
Note:
Terminate Contact Inputs
Step 1:Remove the contact inputs removable screw terminal connector located on the
Step 2:Loosen the desired number of contact input screw terminals and related ground
Step 3:Insert contact closure 1 into the terminal labeled “IN1” on the connector and
Step 4:Insert the related common wire for contact closure 1 into the terminal labeled
Step 5:Repeat for each contact input and ground wire pair (up to four total).
Terminate Contact Outputs
Step 1:Remove the contact outputs removable screw terminal connector located on the
Step 2:Loosen the desired number of contact output (normal open) screw terminals and
Step 3:Insert contact output 1 into the terminal labeled “NO1” on the connector and
Step 4:Insert the related common wire for contact output 1 into the terminal labeled
Step 5:Repeat for each contact output and common wire (up to four total).
Typical contact I/O wiring is color coded as follows: contact 1 - brown, contact 2 orange, contact 3 - yellow, contact 4 - green. All commons and ground voltages
are typically black or red.
left I/O board. Each connector is labeled for installation convenience.
screw terminals on the connector.
tighten the screw terminal.
“GND” on the connector and tighten the screw terminal.
left I/O board. Each connector is labeled for installation convenience.
related ground screw terminals on the connector.
tighten the screw terminal.
“COM1” on the connector and tighten the screw terminal.
Unison DRd enclosure options include the 0-10V control option kit, the Digital Addressable
Lighting Interface Option kit, the RideThru option kit, and the BatteryPack option kit.
Note:
It is best to install option kits after conduit rough-in and the line, load and control
terminations are complete to reduce the likelihood of damage to the option boards.
A single DRd enclosure supports the use of either the DALI Option kit or the 0-10V
Option kit, but not both in the same enclosure.
In addition, a single DRd enclosure supports the use of either the Unison RideThru
Option or the Unison BatteryPack Option, but not both in the same enclosure.
DALI Option
Install the DALI Option kit
The Digital Addressable Lighting Interface option controls 24 loops of 64 DALI compatible
ballasts and drivers in a broadcast mode. Each of the 24 DALI loops are linked one to one
with a circuit for power control. For example, DALI loop 1 is controlled by dimmer 1, DALI
loop 2 is controlled by dimmer 2, etc.
To control DALI ballasts or drivers, the circuit must be populated with a module and
assigned to DALI dimmer mode within the ACP software. Reference the related
Architectural Control Processor programming guide for instruction to change dimmer mode.
Note:
The DALI device is powered by an external DALI power supply (supplied by
others). Each DALI loop requires its own power supply and possibly more than
one power supply depending on the load.
5Install Option Kits41
Page 46
The DALI option supports 64 DALI compatible devices per DALI loop. All DALI devices
Step 2:
Step 3:
Step 4:
connected to that loop will respond at the same time and to the same level as sent by the
broadcast command.
Step 1:Align the DALI option board to the mounting studs in the bottom right side of the
enclosure.
•Notice the mounting holes on the DALI option board. One is a slotted
keyhole, another is an open ended slot and the remaining two on the other
end of the board are standard mounting holes used to secure the board in
place.
Step 2:Set the rear left stud through the slotted keyhole and align the open ended slot
with the back right side mounting stud.
Step 3:Gently slide the DALI board toward the right I/O board aligning the five prong
connector to the receptacle on the I/O board.
Step 4:Secure the bottom two mounting studs with the screws provided.
42DRd Enclosure Installation Manual
Page 47
Connect DALI Option Wiring
2008
Label
Each of the four bus connectors on the option board provide
termination for six DALI loops. Each bus connector is labeled
for ease of loop identification and is pluggable for ease of
wiring termination. Terminals accept 12-24 (4 - .25mm
2
) AWG
Class 1 wire.
*Maximum Run Lengths for Class 1 wiring
18 AWG
2
1mm
16 AWG
1.3 mm
14 AWG
2
1.6 mm
2
12 AWG
2
2 mm
**Max.
aggregate run
length
feetmeterfeetmeterfeetmeterfeetmeterfeetmeter
5701759002751,4304352,2807003000900
*Maximum Run Length - the longest distance between any device and any power supply on
the DALI bus.
**Maximum Aggregate Run Length - the longest total length of all total wiring connected to
the DALI bus.
It is important to label the DALI fluorescent ballast load and control wiring sets with the
circuit designation. Control wires terminate on the associated DALI board output loop
terminal.
For example: If circuit 1 is configured as a D20 in DALI dimmer mode, DALI fluorescent
ballast control wiring should terminate to the DALI board loop output terminals labeled “1”.
Note:
Step 1:Remove the DALI bus connector for loop outputs 1-6.
Step 2:Strip each wire in the pair back 1/4 inch (6mm).
Step 3:Using a small 3,35mm or 1/8” flat blade screwdriver, loosen the terminals and
Step 4:Tighten the terminal screw until the wire is held snugly.
Step 5:Repeat steps 1 through 4 for the remaining DALI loops through loop 6.
Step 6:Replace the DALI bus connector on the DALI board and repeat for the remaining
The lug number inside the enclosure should match the control line number
designation regardless of whether the DRd is configured for straight or balanced
numbering.
insert each wire into the data “+” or data “–” terminals for the specific circuit loop.
Data wires in the wire set are polarity independent.
DALI loops in the system (up to 24 loops).
5Install Option Kits43
Page 48
0-10V Control Option Kit
Step 2
Step 3
Step 4
Install the 0-10V Option Kit
The 0-10V Control option (DRd-FLO) provides 24 outputs for control of 0-10V (4-wire)
ballasts and drivers. Each channel output is linked one-to-one with a circuit for power
control. The FLO board is comprised of 24 individual 0-10 vDC connections, each rated to
control a maximum of 400mA per channel.
Each output connection is clearly labeled on the removable screw terminal bus connectors.
The removable connectors accept 12 - 24 AWG (4 - .25mm
Step 1:Align the 0-10V option board to the mounting studs in the bottom of the
enclosure.
•Notice the mounting holes on the 0-10V option board. One is a slotted
keyhole, another is an open ended slot, and the remaining two on the other
end of the board are standard mounting holes used to secure the board in
place.
Step 2:Set the rear left stud through the slotted keyhole and align the open ended slot
with the back right side mounting stud.
Step 3:Gently slide the option board toward the right I/O board aligning the five prong
connector to the receptacle on the I/O board.
Step 4:Secure the remaining two mounting holes to the pems with the screws provided.
2
) Class 1 wire.
44DRd Enclosure Installation Manual
Page 49
Connect 0-10V Control Option Wiring
2008
Label
-6+ -5+ -4+ -3+ -2+ -1+
-12+ -11+ -10+ -9+ -8+ -7+
-18+ -17+ -16+ -15+ -14+ -13+
-24+ -23+ -22+ -21+ -20+ -19+
FLUOR 1 - 6
FLUOR 7 - 12
FLUOR 13 - 18
FLUOR 19 -24
Each of the four bus connectors on the option board
provide termination for six fluorescent outputs. Each
bus connector is labeled for ease of identification and is
pluggable for ease of wiring termination. Terminals
accept 12-24 (4 - .25mm
2
) AWG Class 1 wire.
Note:
Note:
0-10V control wiring must be routed in separate conduit from the line voltage
wiring.
To control 0-10V devices, the power circuit in the DRd must be a dimmer or relay module
and assigned to 4-wire fluorescent dimmer mode. Reference the related Architectural
Control Processor configuration manual for instruction to change dimmer mode.
It is important to label the 0-10V load and control wiring sets with the circuit designation.
Control wires terminate on the associated 0-10V option board output terminal. Example: If
circuit 1 is configured as a dimmer with a 4-wire fluorescent dimmer mode, ballast control
wiring would terminate to the 0-10V option board output terminals labeled “1”.
The lug number inside the enclosure should match the control line number
designation regardless of whether the DRd is configured for straight or balanced
numbering.
Step 1:Pull 0-10V control wiring pairs into the DRd enclosure per the wire entry plan.
Step 2:Strip each wire pair back 1/4 inch (6mm).
Step 3:Remove the bus connector for outputs 1-6. The pluggable connector is seated
tight in the receptacle. You may need to gently pry the connector free from the
board using a small 3,35mm or 1/8” flat blade screwdriver.
Step 4:Notice the connector is labeled for your reference during wire termination. Using
a small 3,35mm or 1/8” flat blade screwdriver, loosen the terminals and insert
each of the data “+” and data “–” wires in the wire set into the appropriate
terminal.
a: Terminate the violet (typical) control wire of the first pair into the “+” terminal
associated to the power circuit.
b: Terminate the gray (typical) control wire of the first pair into the “–” terminal
associated to the power circuit.
c: Tighten each screw terminal until the wire is held snug.
Step 5:Repeat for the remaining outputs through output 6.
Step 6:Replace the first bus connector to the option board and repeat for the remaining
fluorescent outputs in the system (up to 24 outputs).
5Install Option Kits45
Page 50
RideThru Option Kit
Note:
A single DRd supports the use of either the Unison RideThru Option or the Unison
BatteryPack Option, but not both in the same enclosure.
Install the RideThru Option Kit
WARNING:
The RideThru Option kit provides power for the Architectural Control Processor for a
minimum of 12 seconds during brief power outages or power drop outs. The RideThru
Option board fully charges and is ready for operation within ten minutes of the DRd being
powered.
Risk of Electric Shock! The Unison RideThru option board retains an
electrical charge even when power to the DRd is off.
2008
Step 1:Align the RideThru Option board to the mounting studs in the bottom of the
enclosure.
•Notice the mounting holes on the option board. Two are open ended slots
used to place the board, and the remaining two standard mounting holes
used to secure the board in place.
•Align the open ended slots to the studs and rest the other end of the board
on the mounting studs.
Step 2:Secure the board to the two mounting studs with the screws provided.
46DRd Enclosure Installation Manual
Page 51
Connect RideThru Option Wiring
2008
Step 1:
The BatteryPack Option kit provides sustained battery power to
the Architectural Control Processor for up to 90 minutes during
power outages. The self-contained battery installs on the bottom
of the host DRd enclosure.
The Unison RideThru Option board is provided with a wiring harness for connection
between the option board and the right I/O board.
Step 1:Connect one end of the wiring harness to the two pin receptacle on the option
board.
Step 2:Connect the other end of the wiring harness to the two pin receptacle labeled
“RideThru/Batt” on the right I/O board. See “DRd Right I/O Data Terminations”
on page 34.
•Secure the wiring harness to the DRd enclosure using the cable tie and cable
tie mounts supplied with the RideThru Option board.
BatteryPack Option Kit
Note:
A single DRd supports the use of either the Unison RideThru Option or the Unison
BatteryPack Option, but not both in the same enclosure.
Install the BatteryPack Option Kit
Step 1:The BatteryPack Option board is provided with a wiring harness for connection
between the BatteryPack and the right I/O board. Install the wiring harness and
connector into the enclosure (the connector is keyed for proper orientation).
5Install Option Kits47
Page 52
a: Insert the connector end through the opening in the bottom of the enclosure.
DRd enclosure before UBPO cable and
connector installation
DRd enclosure after UBPO cable and
connector installation
The connector is designed to snap into place without additional hardware,
therefore slight force may be required to ensure the connector installs
properly.
Step 2:Connect the two pin receptacle labeled “RideThru/Batt” on the DRd right I/O
board. See “DRd Right I/O Data Terminations” on page 34.
Step 3:Secure the wiring harness to the enclosure using the cable tie and cable tie
mount supplied with the BatteryPack Option kit. A loose or poorly routed wiring
harness could interfere with option module (DRd-FLO or DRd-DALI) installation.
48DRd Enclosure Installation Manual
Page 53
Step 4:Install the BatteryPack on to the bottom of the enclosure.
see Note:
Step 4a:
Step 4b:
Note:
a: Insert the tabs from the BatteryPack into the slots in the DRd enclosure.
As the battery is mated to the enclosure, the connector on the BatteryPack and
the connector receptacle installed in step 1 also mate.
b: Secure the BatteryPack to the enclosure using the captive screw provided.
5Install Option Kits49
Page 54
Chapter 6
Final Installation and Power Up
This chapter contains the following sections:
•Checking the Installation before Installing Modules . . . . . .51
Checking the Installation before Installing Modules
It’s a good idea to look over the entire installation before installing modules or applying
power to the enclosure.
WARNING:
Step 1:Clean out dust, metal scraps or other debris from the interior of the enclosure.
Step 2:Check for loose connections, bare wires and damaged insulation.
Step 3:Manually spin the top cooling fan in both directions to be sure it is not obstructed.
Step 4:Correct air leaks caused by misaligned or removed conduit panel openings or
Step 5:Check resistance between phases, Neutral and Earth for short circuits. With the
Step 6:Check Load Wiring. Check resistance between the load terminals and the
Power must be turned OFF when you perform this procedure.
Before service, de-energize main feed to DRd and follow appropriate
Lockout/Tagout procedures as described in NFPA Standard 70E. It is
important to note that electrical equipment such as dimmer enclosures can
present an arc flash safety hazard if improperly serviced. This is due to
available large short circuit currents on the feeders of the equipment. Any
work on energized equipment must comply with OSHA Electrical Safe
Working Practices.
•ETC recommends vacuuming the interior before installing modules.
empty screw holes. For complete instructions for this procedure reference
Sealing Air Leaks, page 52.
power connector to the Power Supply/Dimming Engine still removed (this was
accomplished prior to installing conduit and terminating any wires, see Remove
the DRd Power Supply/Dimming Engine Access Panel, page 18), and the all
modules removed from the enclosure, including the Station Power Module,
check resistance between phases, neutral and ground busses with a digital
voltmeter (DVM).
a: Phase to Phase; resistance should be 10M ohm or higher.
b: Phase to Earth (ground); resistance should be 10M ohm or higher.
c: Neutral to Earth (ground); resistance should be less than 1 ohm.
d: Phase to Neutral; resistance should be 10M ohm or higher.
Neutral buss.
a: Above 1M ohm is normal when no load is connected.
b: Between 6-300 ohm is a reasonable reading when loads are connected.
c: Below 1M ohm indicates a dead short in the load wiring and an infinite
reading indicates no load or an open circuit
.
CAUTION:
A dead short can cause module damage.
6Final Installation and Power Up51
Page 56
Sealing Air Leaks
After you have attached all the conduit to the enclosure and connected all wiring, you must
seal any air leaks in the enclosure that was created during the installation process. ETC
recommends use of urethane aerosol foam to fill air gaps in conduit fittings.
•Seal all conduit access holes.
•Completely cover all conduit openings with fiche paper and/or urethane aerosol foam
or duct seal.
•Seal any air gaps caused by bent access panels.
•Fill in any gaps inside partially filled wiring conduit.
•Fill in other gaps or holes in the cabinet created during installation.
•Any enclosures that are installed side - by - side (bolted together) should only have
minimal airflow between them.
CAUTION:
Air leaks can cause the DRd to overheat during operation and shut down. Air leaks
can also cause a DRd to shut down via an overtemp error, meaning that too little
air is flowing through the front of the enclosure where it is needed to cool the
dimmers.
52DRd Enclosure Installation Manual
Page 57
Final Installation
Step 3
Step 2a
Step 2.b
Step 2.c
The enclosure
door has been
removed from
this graphic for
clarity of this
procedure.
Step 1:Reinstall the Power Supply / Dimming
Engine Access Panel that was
removed prior to conduit installation
and wire termination.
a: Align the guide pins located on the
access panel to the guided slots
on the enclosure.
b: Glide the access panel down, so
that it rests fully into the guided
slots.
c: Tilt the supply access panel away
from the enclosure.
Note:
All DRd enclosures are shipped with a dimmer module retention bar installed. The
dimmer module retention bar prohibits installed modules from being removed from
the enclosure without the use of a tool.
Before installing modules into the DRd, loosen the screws retaining this bar in
place, then slide the bar to the left side of the enclosure (door hinge side).
Complete the final installation procedure outlined below, then reengage the
module retention bar (see page 55). This bar is required to be installed in all
enclosures in order to maintain proper CE rating and NFPA70 compliance.
.
6Final Installation and Power Up53
Step 2:Reconnect the three cable assemblies to the unit.
a: For the cable bundle on the left side, insert the connector into receptacle until
you hear a click.
b: For the ribbon cable on the right rear side; insert the connector into the
receptacle. Press gently on both sides until it clips into place.
c: For the two-wire cable on the right side, gently press the connector straight
into the receptacle. This connection is also keyed and can only install one
way.
Step 3:Rotate the access panel closed, then slide the panel up approximately one inch
to align the panel to the captured screws.
Step 4:Tighten the two captive screws, securing the access panel in place.
Step 5:Install modules into the DRd.
a: Align each dimmer module with the correct module slot and firmly press into
place. The face of the dimmer module should be flush with the DRd
enclosure.
b: Install the Station Power Module and Architectural Control Processor into
their respective slots. The Architectural Control Processor installs into the
lowest module slot. The Station Power Module installs into the slot directly
above the ACP.
Page 58
WARNING:
Control Bypass switch
Step 6:Power up the enclosure. Before installing or removing dimmer or control
Step 7:Switch all module circuit breakers to the “On” position.
Step 8:Reference the related Architectural Control Processor Configuration Manual for
Never power up or operate the DRd enclosure without all modules installed.
Failure to comply exposes you to dangerously high voltages that may result
in death by electrical shock.
modules for service, de-energize main feed to DRd and follow appropriate
Lockout/ Tagout procedures as described in NFPA Standard 70E. It is important
to note that electrical equipment such as dimmer enclosures can present an arc
flash safety hazard if improperly serviced. This is due to available large short
circuit currents on the feeders of the equipment. Any work on energized
equipment must comply with OSHA Electrical Safe Working Practices.
DRd configuration setup and operation.
Control Bypass (Test Mode)
Test load circuits connected to the DRd enclosure by switching the “Control Bypass” switch
to the “Test” position. The Control Bypass switch allows testing of lighting loads and
provides temporary lighting before complete system commissioning. Return the switch to
its “Normal” setting after the test is complete.
CAUTION:
54DRd Enclosure Installation Manual
Turning the Control Bypass switch to the “Test” position with all module circuit
breakers “On” will bring all lighting loads to full. To select only certain lighting loads
for test, switch “Off” undesired module circuit breakers in the DRd enclosure.
Page 59
Reengage Module Retention Bar
Enclosure door removed
from graphic only for
clarity of the dimmer
module retention
installation.
Dimmer module
retention bar
Step 1:Check that all required modules have been installed into the DRd enclosure including
dimmer modules, air flow modules, Station Power Module, and Architectural Control
Processor. All module slots should be populated.
Step 2:Loosen the screws on the retention bar.
Step 3:Slide the retention bar to the right. Notice the retention bar has two tabs that insert into
the ACP and Station Power Module slots for retention.
Step 4:Secure the retention bar in place using the screws provided.
AELV5Dual 5A at 277V AC Reverse Phase Dimmer Module7183A10282.6 lbs / 1.2 kgs
AR15Dual 15A at 277V AC Relay Module7083A10822.6 lbs / 1.2 kgs
AR20Dual 20A at 277V AC Relay Module7083A10832.6 lbs / 1.2 kgs
Single, 3 wire, 5A at 277V AC Reverse Phase Dimmer
Module
7083A10762.4 lbs / 1.1 kgs
AModules Specification59
Page 64
60DRd Enclosure Installation Manual
Page 65
Appendix B
Figure 1: Emergency Module Circuit
Module Circuit Breaker
Dimming Circuit
Dimmed Output
Constant Output
CE 230V Emergency Modules
230V CE Emergency modules are non-standard for DRd 230V enclosures. On the
occasion that your installation requires use of these modules, refer to the information
outlined below for installation.
Note:
When configuring the dimmer modules at the Architectural Control Processor,
configure as either the ED15 or the ER15 module type.
About Emergency Modules
The 230V CE Emergency modules provide two live outputs, one of which is dimmed or
switched, and one of which is live whenever the breaker is turned “On”. This setup allows
the modules to control battery-backed lighting, which requires both a constant and a
switched or dimmed feed.
ETC offers two varieties of Emergency Modules - ED15AFE (15A Dimmer), and
ER15AFE(15A Relay), painted red for easy identification.
Wire Termination
The constant output from the module is connected to the Neutral lugs at the left of the
enclosure. Therefore, unlike Neutral Disconnect modules, Emergency modules provide a
live output at these lugs, not a neutral connection.
Note:
BCE 230V Emergency Modules61
ETC does not offer a Neutral Disconnect or RCD version of the emergency
modules.
Step 1:Locate the module slot in the enclosure where the Emergency module is to be
fitted.
Step 2:Terminate the outgoing dimmed line to the terminals at the right hand side of the
enclosure.
Step 3:Terminate the outgoing (constant feed) line to the terminals at the left side of the
enclosure.
Step 4:Terminate the outgoing (Earth) line to the earth bar terminals.
Page 66
Step 5:Terminate the Neutral as described in the following section, dependant on your
Figure 2: Emergency Module Connections
Constant live
line is landed
on the Neutral
lugs
Dimmed or
switched line is
landed on live
lugs
DRd enclosure model.
Non Neutral Disconnect
For enclosures which have neutral jumpers fitted, the Neutral of the load, fed by the
Emergency module, must be connected to the Neutral terminal of an adjacent module.
Neutral Disconnect
In enclosures without neutral jumpers (Neutral Disconnect enclosures), the Neutral of the
load should not be connected to another load’s Neutral terminal. This can cause unwanted
tripping of RCD modules.
Instead, an auxiliary neutral terminal must be fitted to the neutral plate and the loads should
be connected to the terminal. If your enclosure was ordered with Emergency modules from
the factory, the auxiliary neutral terminal will be factory fitted. If you require an auxiliary
neutral terminal for field installation, please contact ETC as shown using the details in
Contacting ETC, page 2.
62DRd Enclosure Installation Manual
Page 67
BCE 230V Emergency Modules63
Page 68
Corporate Headquarters
London, UK
Rome, IT
Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK Tel +44 (0)20 8896 1000 Fax +44 (0)20 8896 2000