ETC Unison DRd Dimming Rack Enclosure User Manual

Page 1
DRd Enclosure Installation Manual
Revision D
Copyright © 2014 Electronic Theatre Controls, Inc.
All Rights reserved.
Product information and specifications subject to change.
Part Number:
7183M2100
Released: 2014-07
Rev D
Page 2
ETC®, Unison Paradigm®, Echo™, and SmartLink® are either registered trademarks or trademarks of Electronic Theatre Controls, Inc. in the United States and other countries. All other trademarks, both marked and not marked, are the property of their respective owners.
ETC intends this document, whether printed or electronic, to be provided in its entirety.
Page 3
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Warnings and Notice Conventions . . . . . . . . . . . . . . . . . . . . . . .2
Contacting ETC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Chapter 1
Chapter 2
Prepare for Installation . . . . . . . . . . . . . . . . . 5
Unpack and Inspect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Main Circuit Breaker Protection . . . . . . . . . . . . . . . . . . . . . . . . . .5
Using 90° Copper Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Maximum Current Draw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Short Circuit Current Rating (SCCR) . . . . . . . . . . . . . . . . . . .6
Where to Install the Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Installation Environment Requirements . . . . . . . . . . . . . . . . . . . .8
Wire Routing and Specification . . . . . . . . . . . . . . . . . . . . . . . . . .8
Control Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Control Wire Specification . . . . . . . . . . . . . . . . . . . . . . . . . .10
Install Enclosures . . . . . . . . . . . . . . . . . . . . 12
Mounting Individual DRd Enclosures . . . . . . . . . . . . . . . . . . . . . . . .13
Mounting Individual Enclosures on a Wall . . . . . . . . . . . . . . . . .13
Mounting a DRd Enclosure on a Pedestal . . . . . . . . . . . . . . . . . . . .14
Mounting Auxiliary and DRd Enclosures Together. . . . . . . . . . . . . .15
Chapter 3
Chapter 4
Table of Contents i
Rough-in Conduit and Wiring . . . . . . . . . . . 17
Prepare the DRd Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Remove the DRd Power Supply/Dimming Engine Access Panel . 18
Modify Phase Bus for 120V AC Split Phase Operation . . . . . . .19
Rough-in Conduit to the DRd Enclosure . . . . . . . . . . . . . . . . . . . . .21
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Terminate Wiring. . . . . . . . . . . . . . . . . . . . . 24
Connect Line Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Connect Line Feed in an Individual DRd Installation . . . . . . . . .25
100, 120, 127 V AC, 3Ø DRd Enclosures. . . . . . . . . . . . . . .26
230V AC Neutral Disconnect DRd Enclosures . . . . . . . . . . .27
Page 4
240, 277V AC DRd Enclosures . . . . . . . . . . . . . . . . . . . . . .27
Connect Load Wires. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Fluorescent Load Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
3-wire Fluorescent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
2-wire Fluorescent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Connect Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
DRd Right I/O Data Terminations . . . . . . . . . . . . . . . . . . . . . . .34
Auxiliary Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
LinkConnect and EchoConnect Control Wiring . . . . . . . . . .35
UL 924 Listed Panic Input. . . . . . . . . . . . . . . . . . . . . . . . . . .35
DMX Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
AX12X Cross-bussed Interconnection . . . . . . . . . . . . . . . . .36
Terminate the Unison Options (URTO and UBPO) . . . . . . .37
Terminate DMX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
DRd Left I/O Data Termination . . . . . . . . . . . . . . . . . . . . . . . . .38
Connect to Serial RS-232 . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Connect to Ethernet RJ-45 . . . . . . . . . . . . . . . . . . . . . . . . . .38
Connect to Contact Inputs and Contact Outputs . . . . . . . . .39
Chapter 5
Chapter 6
Appendix A
Install Option Kits . . . . . . . . . . . . . . . . . . . . 40
Installation of Option Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
DALI Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Install the DALI Option kit . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Connect DALI Option Wiring. . . . . . . . . . . . . . . . . . . . . . . . .43
0-10V Control Option Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Connect 0-10V Control Option Wiring . . . . . . . . . . . . . . . . .45
RideThru Option Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Install the RideThru Option Kit . . . . . . . . . . . . . . . . . . . . . . .46
Connect RideThru Option Wiring . . . . . . . . . . . . . . . . . . . . .47
BatteryPack Option Kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Install the BatteryPack Option Kit . . . . . . . . . . . . . . . . . . . . .47
Final Installation and Power Up . . . . . . . . . 50
Checking the Installation before Installing Modules . . . . . . . . . . . . .51
Sealing Air Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Final Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Control Bypass (Test Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Reengage Module Retention Bar . . . . . . . . . . . . . . . . . . . . . . .55
Modules Specification. . . . . . . . . . . . . . . . . 57
Appendix B
ii DRd Enclosure Installation Manual
CE 230V Emergency Modules . . . . . . . . . . 61
About Emergency Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Wire Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Non Neutral Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
Neutral Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
Page 5

Introduction

DRd6
DRd12
Welcome to the installation manual for Unison® DRd enclosures. This manual contains the procedures for safe and efficient installation of your DRd enclosure and related terminations.
Use this manual in conjunction with the Unison Auxiliary Enclosure Installation Manual when your DRd is to be installed with an adjoining auxiliary enclosure.
DRd Series Enclosures
Series Voltage Notes
DRd6-12-120 DRd6-12-240 DRd6-12-230 DRd6-12-277
DRd12-24-120 DRd12-24-240 DRd12-24-230 DRd12-24-277
DRd12-48-120 DRd12-48-240 DRd12-48-277
120/208 V AC 240/415 V AC 230/400 V AC CE Neutral Disconnect 277/480 V AC
120/208 V AC 240/415 V AC 230/400 V AC CE Neutral Disconnect 277/480 V AC
120/208 V AC 240/415 V AC 277/480 V AC
6 module enclosure for up to 12 circuits.
12 module enclosure for up to 24 circuits.
Two 12 module enclosures for up to 48 circuits. DRd12-48 enclosures are cross-bussed using the AX12X series main lug or main breaker enclosure.
Introduction 1
Page 6

Warnings and Notice Conventions

These symbols are used throughout this installation manual to alert you to danger or important information:
Note:
CAUTION:
Notes are helpful hints or information that is supplemental to the main text.
A Caution statement indicates situations where there may be undefined or unwanted consequences of an action, potential for data loss, or an equipment problem.
WARNING:
A Warning statement indicates situations where damage may occur, people may be harmed, or there are serious or dangerous consequences of an action.
WARNING:
RISK OF ELECTRIC SHOCK! This warning statement indicates situations where there is a risk of death by electric shock.

Contacting ETC

For questions about Unison system delivery, contact ETC Systems Group. For general information, your most convenient resources are the references provided in this manual. To search more widely try the ETC web site at www.etcconnect.com.
For technical questions about Unison systems, contact ETC Technical Services directly at one of the offices listed below. Emergency service is available from all ETC offices outside of normal business hours. When calling for assistance, please have the following information handy:
Your location and job name.
A complete list of ETC equipment.
A complete list of other installed products and components connected to the system you are troubleshooting.
DMX control source, if any.
Americas
ETC International Technical Services Department 3031 Pleasant View Road Middleton, WI 53562 800-775-4382 (USA, toll-free) +1-608 831-4116 service@etcconnect.com
Asia
ETC Asia, Ltd. Technical Services Department Room 1801, 18/F, Tower 1, Phase 1 Enterprise Square 9 Sheung Yuet Road Kowloon Bay, Kowloon, Hong Kong +852 2799 1220 service@etcasia.com
United Kingdom
Electronic Theatre Controls, Ltd. Technical Services Department 26 - 28 Victoria Industrial Estate Victoria Road, London W3 6UU, UK +44 (0)20 8896 1000 service@etceurope.com
Germany
Electronic Theatre Controls, GmbH Technical Services Department Ohmstrasse 3 93607, Holzkirchen, Germany +49 (80 24) 47 00-0 techserv-hoki@etcconnect.com
Please email comments about this manual to: TechComm@etcconnect.com
2 DRd Enclosure Installation Manual
Page 7

Overview

DRd6
DRd12
Unison DRd enclosures are available in 6 or 12 module enclosures and are available for an input voltage range of 85-300 V AC, 47-63 Hz. Enclosures are pre-wired and supplied with three phase, 4 wire and ground, main lugs which are easily converted for split phase, 3 wire and ground, operation without the need for additional materials.
Note:
DRd enclosures are available in 12, 24 and 48 circuit configurations.
In 48-circuit configurations, two DRd12-24 enclosures are cross-bussed to an AX12X series main lug or main circuit breaker auxiliary enclosure. A single Architectural Control Processor (Echo, Paradigm, or SmartLink ACP) provides control for both enclosures.
DRd enclosures are supplied pre-wired for the specified voltage for your installation. All enclosures operate at specified voltages within a frequency range of 47-63 Hz. Phases within the enclosure may be bused together provided the maximum supplied current does not exceed that of a three phase connection.
100 / 200 V AC, 47-63 Hz, 1Ø
100 / 173 V AC, 47-63 Hz, 3Ø
120 / 208 V AC, 47-63 Hz, 3Ø
120 / 240 V AC, 47-63 Hz, 1Ø
127 / 220 V AC, 47-63 Hz, 3Ø
230 / 400 V AC, 47-63 Hz, 3Ø CE with Neutral Disconnect
240 / 415 V AC, 47-63 Hz, 3Ø
277 / 480 V AC, 47-63 Hz, 3Ø
Supports universal dimmer modules, fluorescent dimmer modules, constant circuit breaker modules, relay modules, and reverse phase dimmer modules. Reference
“Modules Specification” , page 57 for a complete list of compatible modules.
The DRd is controlled from either the Echo (E-ACP), SmartLink
Architectural Control Processor (P-ACP).
®
Architectural Control Processor (S-ACP) or the Paradigm™
®
Architectural Control Processor
Introduction 3
Page 8
The use of a station power module provides power and control for architectural control stations.
Use an Echo Station Power Module (E-SPM) to provide power for up to 16 Echo
control stations when used with the Echo ACP.
Use a SmartLink Station Power Module (S-SPM) to provide power for up to 16
SmartLink control stations when used with the SmartLink ACP.
Use a Paradigm Station Power Module (P-SPM) to provide power for up to 32
Paradigm control stations when used with the Paradigm ACP.
The 0-10V control option (DRd-FLO) provides up to 24 outputs for control of 0-10V (4-wire) LED drivers or fluorescent ballasts (up to 12 on a DRd6).
The Digital Addressable Lighting Interface (DALI) option controls up to 24 loops of 64 DALI compatible ballasts or drivers in a broadcast mode (up to 12 on a DRd6).
The Unison BatteryPack option provides power back-up to the Architectural Control Processor in the DRd for a period up to 90 minutes.
The Unison RideThru option provides power to the Architectural Control Processor in the DRd for at least 10 seconds during brief power outages or drop outs.
All empty module spaces in a DRd enclosure must be filled with airflow module or blank modules (DRd-BM) for proper cooling.
The DRd pedestal (DRd-PED) is a floor mounting stand for the DRd enclosure.
4 DRd Enclosure Installation Manual
Page 9
Chapter 1

Prepare for Installation

Unpack and Inspect

Before you begin installation, check your shipment and confirm it arrived complete and undamaged.
Step 1: Check the shipping container for physical damage.
Step 2: If you find damage, document it to help with a claim against your shipper.
Step 3: Unpack your order and check the contents against the packing list to be sure
your order is complete.
Step 4: If you discover a problem, call the ETC Systems Group the closest office of
purchase. See “Contacting ETC” on page 2.

Main Circuit Breaker Protection

Before you begin installing the DRd enclosure, make sure you have installed a main circuit breaker cabinet or other readily accessible input power disconnect device. In certain bussed and cross-bussed systems, this disconnect device may be the Unison AX series auxiliary enclosure with a main circuit breaker.
WARNING:
DRd enclosures installed without an accessible power disconnect device cannot be serviced or operated safely. Follow all local codes and restrictions.
Before removing dimmer or control modules for service, de-energize main feed to DRd and follow appropriate Lockout/Tagout procedures as described in NFPA Standard 70E. It is important to note that electrical equipment such as dimmer enclosures can present an arc flash safety hazard if improperly serviced. This is due to available large short circuit currents on the feeders of the equipment. Any work on energized equipment must comply with OSHA Electrical Safe Working Practices.

Using 90° Copper Wire

To comply with UL requirements:
Use Copper Conductors Only, the torque rating for each Non-Class 2 field-wire connector, and “Use 90°C conductors at the 75°C Ampacities”, where readily visible in the field wiring compartment; Class 2 adjacent to each Class 2, field-wiring connector.
Use only 90°C-rated copper wiring installed in accordance with all applicable local electrical codes.
CAUTION:
A two-wire circuit with separate hot and neutral conductors is required for every branch circuit that will be connected to the DRd enclosure. Shared neutral (multi­wire) branch circuit arrangements are not recommended for phase control dimming systems due to harmonics and potentially elevated neutral currents in a shared neutral arrangement.
For retrofit installations where shared neutral circuits are already installed, or enclosure lighting installations where the enclosure has a shared neutral, consult ETC Technical Services for installation guidelines.
1 Prepare for Installation 5
Page 10

Maximum Current Draw

Type Phase Type
DRd6
AX6
DRd12
AX12
AX12X
Note:
Single Phase (1Ø) 120A 150A
Three Phase (3Ø) 80A 100A
Single Phase (1Ø)
Three Phase (3Ø)
Single Phase (1Ø) 240A 300A
Three Phase (3Ø) 160A 200A
Single Phase (1Ø)
Three Phase (3Ø)
Single Phase (1Ø)
Three Phase (3Ø)
1
Connected to DRd enclosure with a full complement of 20A modules.
2
Connected to two DRd enclosures with a full complement of 20A modules.
3
Installed in a main circuit breaker model auxiliary enclosure.
4
Wire bending space limits the feed to the AX12X-MCB to 400A maximum. ETC installs a 100% rated two pole breaker (or two poles from a three pole breaker) in the AX12X-MCB, for a total deliverable current of 400A in a single phase (split phase) configuration.
Maximum Current Draw
1
120A
1
80A
1
240A
1
160A
2
480A
2
320A
Suggested Breaker Rating
3
150A
3
100A
3
300A
3
200A
4
400A
3
400A

Short Circuit Current Rating (SCCR)

SCCR at
Configuration
100-120v
Ac
DRd6 22,000A 22,000A
DRd6 with AX6 (MCB) 100,000A 65,000A
DRd12 22,000A 22,000A
DRd12 with AX12 Main Lug 22,000A 22,000A
DRd12 with AX12X (cross-bussed) Main Lug 22,000A 22,000A
DRd12 with AX12 Main Circuit breaker 100,000A 65,000A
DRd12 with AX12X Main Circuit breaker 100,000A 65,000A
SCCR at
240 &
277v Ac
6 DRd Enclosure Installation Manual
Page 11

Where to Install the Enclosure

Unison DRd enclosures are designed to be surface mounted on load bearing walls in an electrical closet or a room with restricted public access. When required, an optional semi-recessed installation kit is also available. It is recommended that you install the enclosure at least 36” (915mm) above the finished floor to ensure clear view of the control processor (E-ACP, S-ACP, or P-ACP) for programming and operation. Alternatively, DRd enclosures may install to a floor standing pedestal (model DRd-Ped).

Clearance Requirements

DRd enclosures require 12” (305mm) top clearance for proper airflow through the cabinet. For sufficient door clearance, install the enclosure with at least 17” (432mm) of front clearance and a 6” (152mm) clearance to the left of the door hinge from walls or other equipment.
152 mm
(6”)
432 mm
(17”)
305 mm
(12”)
914.4 mm (36”)
Note:
Additional Unison dimming and auxiliary enclosures of the same size are the exception to the 6” (152mm) hinge side clearance rule. Unison enclosures are designed for side by side installation.

Dimensions and Weights

Type
DRd6 21.8 553 17 431 10 254 37.8 17.2 42 19.0
DRd12 31 787 17 431 10 254 51 23.1 55 25
Note:
Height Width Depth
inches mm inches mm inches mm lbs kgs lbs kgs
For module weight please reference “Modules Specification,” page 57.
Product
Weight
Shipping
Weight
1 Prepare for Installation 7
Page 12

Installation Environment Requirements

10°
20°
30°
40°
50°
60°
70°
80°
90°
100°
-18°
-10°
10°
20°
30°
40°
For your own safety, install a main circuit breaker cabinet or other readily accessible power disconnect in the same area as the DRd enclosure. For cross-bussed installations, this device may be the auxiliary enclosure. Main breakers not in the same room must have a physical means to be locked off. ETC recommends adopting lockout / tagout procedures for your facility and following appropriate Lockout/Tagout procedures as described in NFPA Standard 70E.
A clean (not dusty) temperature-controlled environment with an ambient temperature of 32-104°F / 0-40°C and ambient humidity of 10-90%, non-condensing.
CAUTION:
HVAC systems must at all times maintain the specified ambient temperature at the enclosure. Dimming systems operating within 10°F (5°C) of the upper or lower temperature limits must strictly follow installation and operation guidelines to operate reliably.
Restricted public access to prevent tampering.
Soundproofing or performance area separation to muffle ventilation fan noise is recommended.
All CE equipment is tested to EMC category B environment.

Wire Routing and Specification

When planning wire entry into the enclosure, notice that conduit knockouts are provided only on the sides of the unit. These knockouts are primarily used for bussing to an auxiliary enclosure but may also be used for load or control wiring. Signal and power wiring must be run in separate conduit per local code.
Due to the bend radii of certain size line feed wires and the location of terminations, special attention is required for line feed wire entry. Reference the wiring guidelines below for recommendations.
CAUTION:
Do not route line (input feed) wires through the back panel. Doing so requires bend radii that violate NEC code, UL standards and because of undue stress at the wire joint is likely to create a poor connection.
Line and load wire used with Unison DRd enclosures must be copper. Load wires may either be stranded (preferred) or solid core. The use of aluminum wire is not allowed in DRd enclosures.
Aluminum feed wires are supported only in the auxiliary (AX Series) enclosures.
Wire Size
Wire Access
Location
DRd12 Feed
(max)
350 Kcmil
185mm
Top
Bottom
Left side
Right side
8 DRd Enclosure Installation Manual
acceptable acceptable acceptable acceptable
acceptable acceptable acceptable preferred
Do Not Use Do Not Use acceptable acceptable
Do Not Use Do Not Use acceptable acceptable
2
DRd6 Feed
(max)
2/0-3
2
70mm
Load Wires
12 - 6AWG
2.5 - 16mm
2
Control
Wires
Page 13
Note:
To a ddi t i ona l
DRd rack
enclosures
EchoConnect
& DMX
power
feed
power
feed
power
feed
To l o ad c i rc u i ts
DMX input to DRd rack
ETC Console
(for optional stage lighting)
EchoConnect
Preset 4
Unison DRd12 rack enclosure
Echo
Relay Panel
Unison DRd12 rack enclosure
Echo Inspire Stations
Element console
Split phase applications require a simple field adjustment to the phase bussing.
See “Modify Phase Bus for 120V AC Split Phase Operation” on page 19.
Wire Size
Wire Access
Location
Top
Bottom
Left side
Right side
Wire Access
Location
Top
Bottom
Left side
Right side
Feed (max)
350 Kcmil
185mm
2
acceptable acceptable acceptable acceptable
acceptable acceptable acceptable preferred
Do Not Use Do Not Use acceptable acceptable
Do Not Use Do Not Use acceptable acceptable
DRd12 Feed
(max) 250 Kcmil
120mm
2
acceptable acceptable acceptable acceptable
acceptable acceptable acceptable preferred
Do Not Use Do Not Use acceptable acceptable
Do Not Use Do Not Use acceptable acceptable

Control Specifications

The riser below is typical of a small Unison system utilizing Echo Architectural Control Processors (E-ACP) for control and Unison Echo activation. DMX input to the DRd enclosures provide an additional level of system control and integrates the architectural and theatrical lighting control systems.
DRd6 Feed
(max)
250 KCmil
120mm
2
Wire Size
DRd6 Feed
(max)
2/0-3
2
70mm
Load Wires
12 - 6AWG
2.5 - 16mm
Control Wires
2
Load Wires
12 - 6AWG
2.5 - 16mm
®
Inspire™ control stations for control
Control Wires
2
1 Prepare for Installation 9
Note:
DRd enclosures are shipped with the lugs installed in a top feed orientation by default. You can change the lug orientation to a bottom feed if required.
Page 14
The riser below is typical of a Unison system utilizing Paradigm Architectural Control Processors (P-ACP) for control and Unison control stations for control activation. Paradigm systems provide a DMX input into the system for larger system integration and control. A Paradigm system also utilizes Net3 networking for an additional level of system-wide control.
Preset 1
Preset 6
To a ddi t i ona l
DRd rack
enclosures
DMX
thru
Unison DRd12 rack enclosure
power
feed
To l o ad c i rc u i ts
Unison DRd12 rack enclosure
power
feed
Unison DRd12 rack enclosure
power
feed
Unison
LinkConnect
LinkConnect
Aux Power 24 vdc
DMX input to DRd rack
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Gio console
ETC Console
(for optional stage lighting)
Sequence
Macro Record
Heritage stations
Sequence
Macro Record
Preset 1
Preset 2
Preset 7
Preset 2
Preset 8
Preset 3
Preset 3
Preset 9
Preset 4
Preset 4
Preset 5
Preset 10
Preset 5
Preset 1
Preset 6
Preset 1
Preset 2
Preset 7
Preset 2
Preset 8
Preset 3
Preset 3
Preset 9
Preset 4
Preset 4
Preset 5
Preset 10
Preset 5
Paradigm Touchscreen
station
Note:
DRd enclosures are shipped with the lugs installed in a top feed orientation by default. You may change the lug orientation to a bottom feed if required.
Control Wire Specification
The following tables lists the recommended control wire types used in a DRd installation and the maximum length (aggregate) of wire runs allowed for each type.
Purpose
Total length of control wire (without repeater module)
Maximum wire length (station to station)
Maximum repeater distance (P-SPM only)
Purpose
Total length of control wire (without repeater module)
Maximum wire length (station to station)
LinkConnect (P-SPM and S-SPM)
Aux 24 vDC
(Belden 8471)
(P-SPM only)
(2) #16 AWG
EchoConnect
(E-SPM)
Belden 8471 or
Belden 1583a
Feet Meter Feet Meter Feet Meter
1640 500 1500 457 1640 500
1312 400 1312 400 1640 500
1640 500 1500 457 N/A N/A
DMX (Belden 9729) Category 5 /Belden 1583a
Feet Meter Feet Meter
1600 487 328 100
1600 487 N/A N/A
10 DRd Enclosure Installation Manual
Page 15
Data Types and Topologies
LinkConnect and EchoConnect Control Wiring
Control stations communicate with the control processor using the LinkConnect or EchoConnect station communication bus.
Termination is available for up to six home runs of LinkConnect / EchoConnect data runs utilizing Belden 8471 cable (or approved equal) plus one 14 AWG (2.5mm2) ESD drain wire. This wiring is topology-free and can be installed in any combination of bus, star, loop, and home run. The total combined length of all wire runs cannot exceed 1,640 feet (500m).
CAUTION:
Note:
Auxiliary 24 vDC
Auxiliary power is required when you are installing certain Unison control stations. ETC recommends using two 16 AWG stranded wires for 24 vDC auxiliary power to the control station(s). Auxiliary power is topology-free.
DMX (Digital Multiplex)
DMX can address up to 512 channels of control. DMX is installed in a daisy chain topology and includes one pair of wires (data +, data -) plus an ISO ground. ETC recommends the use of Belden 9729 (or approved equal) wire with a single end of line termination (90­150). For best DMX performance, twist the wires together as close to the pluggable connector as possible.
Note:
While the wiring terminations for LinkConnect, used in SmartLink and Paradigm systems, and EchoConnect used in Echo systems, are similar, the communication and control types are not interchangeable. Each product family requires a dedicated station infrastructure that cannot be shared.
It is required that you terminate LinkConnect / EchoConnect station wiring and the auxiliary power wiring in the same enclosure the station power module and architectural control processor will be installed.
It is required that you terminate DMX control wiring in the same enclosure (rack 1) where the architectural control processor will be installed.
1 Prepare for Installation 11
Page 16
Chapter 2

Install Enclosures

This chapter contains instructions for installation of the DRd enclosure.
This chapter contains the following sections:
Mounting Individual DRd Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Mounting a DRd Enclosure on a Pedestal. . . . . . . . . . . . . . . . . . . . . . . . 14
Mounting Auxiliary and DRd Enclosures Together . . . . . . . . . . . . . . . . 15
12 DRd Enclosure Installation Manual
Page 17

Mounting Individual DRd Enclosures

432 mm
17”
451 mm
17.75”
194mm
7.64”
113mm
4.45”
160mm
6.3”
DRd12 rear panel
DRd6 rear panel
Unison DRd enclosures are designed to be surface mounted on load bearing walls in an electrical closet or a room with restricted public access. Alternatively the DRd enclosure may be mounted on a pedestal (DRd-Ped). It is recommended that enclosures installed on the pedestal floor stand also be secured to the wall for greater stability.

Mounting Individual Enclosures on a Wall

The wall must be strong enough to hold the enclosure fully populated with modules, conduit and wire. See “Dimensions and Weights,” on page 7 and
“Modules Specification,” page 57.
Step 1: Determine where your enclosure will be installed using the weight and dimension
requirements detailed in “Where to Install the Enclosure,” page 7.
Step 2: Use the measured slot dimensions located in the graphic below to mark the hole
locations for the mounting hardware.
Step 3: Drill the holes and install the mounting hardware for each enclosure.
Step 4: Attach the enclosure to the wall.
Step 5: Check that the enclosure is level and plumb and tighten the mounting hardware.
432 mm
17”
184mm
7.25
194mm
7.64”
160mm
6.3”
113mm
4.45”
• Four 3/8” (M8-M10) bolts or screws 2-4” (50-100mm) long, and suitable wall plugs are suggested mounting hardware (lag bolts recommended).
• Both the surface and the mounting hardware must support the weight of the enclosure unit fully populated with modules.
• Expose at least 1” (25mm) of threads for mounting the enclosure.
2 Install Enclosures 13
Page 18

Mounting a DRd Enclosure on a Pedestal

The Unison DRd pedestal is designed with the same footprint as the DRd enclosure. The acceptable conduit access in the bottom of the DRd overlaps the floor stand access panel for contractor wiring and installation convenience. It is recommended to secure a DRd enclosure installed on a pedestal to a wall for greater stability.
432mm
17”
186.7mm
7.35”
35.5mm
1.4”
35.5mm
1.4”
Step 1: Use the measured
dimensions in the graphic (right) to mark the hole locations for the floor mounting hardware.
Step 2: Drill holes for floor
mounting hardware.
Step 3: Remove the eight screws and washers that secure the front panel to the unit.
Step 4: Position the floor stand on floor hardware previously placed for marking the
holes.
Step 5: Secure the pedestal base to the floor.
Step 6: Create conduit access in the bottom of the DRd enclosure. Notice the label inside
the bottom of the enclosure indicating the recommended locations for conduit access. Do not create conduit access outside of the recommended locations.
Step 7: Position the DRd on the floor stand pedestal and align with the mounting holes
Step 8: Bolt the enclosure into place.
Step 9: Reinstall the front panel to the pedestal unit, replacing all hardware removed in
14 DRd Enclosure Installation Manual
provided.
step 3.
Page 19

Mounting Auxiliary and DRd Enclosures Together

432mm
17”
451mm
17.75”
194mm
7.64”
113mm
4.45”
160mm
6.3”
432mm
17”
62mm
2.44”
787mm
31”
406mm
16”
406mm
16”
330mm
13”
559mm
22”
559mm
22”
DRd12-48 rear panel view
Unison DRd and AX auxiliary enclosures are designed to be surface mounted on load bearing walls in an electrical closet or a room with restricted public access. One DRd enclosure may be bussed to the AX series auxiliary enclosure, which may contain a main circuit breaker or a main lug for power distribution to the adjacent DRd12 enclosure. Two DRd12 enclosures may be cross-bussed to an AX12X auxiliary enclosure which is designed to provide main lug or main breaker input feed termination to the adjacent DRd12 enclosures.
The wall must be strong enough to hold all enclosures fully populated with modules, conduit and wire. Reference “Where to Install the Enclosure,” page 7 for weight, dimension and clearance requirements.
Step 1: Determine where the enclosures will be installed using the weight and dimension
requirements detailed in “Where to Install the Enclosure,” page 7.
Step 2: Use the measured slot dimensions located in the graphics below to mark the hole
locations for the mounting hardware.
Step 3: Drill the holes and install the mounting hardware for each enclosure.
• Four 3/8” (M8-M10) bolts or screws 2-4” (50-100mm) long, and suitable wall plugs are suggested mounting hardware per enclosure (lag bolts recommended).
• Both the surface and the mounting hardware must support the weight of
Step 4: Remove the conduit knockouts from the mating side conduit plugs on the DRd
the enclosures fully populated with modules.
• Expose at least 1” (25mm) of threads for mounting the enclosure.
and auxiliary enclosures before installation. Only remove the knockouts that are adjacent to another enclosure.
Step 5: Install one DRd enclosure first (follow instructions as outlined in “Mounting
Individual Enclosures on a Wall,” on page 13. Remember to install the DRd
enclosure to either side of the auxiliary enclosure in cross-bussed applications.
Step 6: Align the auxiliary enclosure against the DRd enclosure and mount it to the
previously installed hardware. Keyholes in the DRd and auxiliary enclosures are aligned with each other for mounting to Unistrut or Kindorf. With conduit holes mated, the bolt spacings are on 16” (406mm) centers (top left DRd and top left
2 Install Enclosures 15
Page 20
Ax) for installation convenience.
Step 7: Install the ETC supplied 2 1/2” (64mm) nylon insulated chase nipple and 2 1/2”
(64mm) locknut between the auxiliary and DRd enclosures.
Step 8: For cross-bussed DRd12-24 installations, install the second DRd12-24 by
following steps 4 through 7 above.
Step 9: Check that each enclosure is level and plumb then tighten the mounting
hardware for a secure installation.
Note:
Reference the related Auxiliary Enclosure Installation Manual to complete the auxiliary enclosure installation and for DRd12-24 and DRd 12-48 enclosure input power bus wiring termination.
Follow the instructions in this manual for all other DRd enclosure installation procedures.
16 DRd Enclosure Installation Manual
Page 21
Chapter 3

Rough-in Conduit and Wiring

This chapter contains instructions for conduit and wiring installation of the DRd enclosure.
This chapter contains the following sections:
Prepare the DRd Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Remove the DRd Power Supply/Dimming Engine Access Panel . . . . . 18
Modify Phase Bus for 120V AC Split Phase Operation . . . . . . . . . . . . . 19
Rough-in Conduit to the DRd Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . 21
3 Rough-in Conduit and Wiring 17
Page 22

Prepare the DRd Enclosure

Step 1
Step 4.a
Step 4.b
Step 4.c
The enclosure door has been removed from this graphic for clarity of this procedure.
All terminations are accessible from the front of the enclosure. Reference “Wire Routing
and Specification”, page 8 for conduit access specifications.
Prior to conduit installation you should remove the power supply access panel for clear access to the top of the DRd enclosure. Reference “Remove the DRd Power Supply/
Dimming Engine Access Panel” below.
Take the opportunity before roughing in your conduit to change your DRd for split phase operation (100/120V AC enclosures only) if required. Reference “Modify Phase Bus for
120V AC Split Phase Operation”, page 19.

Remove the DRd Power Supply/Dimming Engine Access Panel

Remove the power supply/dimming engine access panel to allow for better access in the top of the DRd enclosure while roughing in conduit and cable.
18 DRd Enclosure Installation Manual
Step 1: Loosen the two captive screws that secure the access panel.
Step 2: Gently pull the panel straight down until the top of the access panel is clear of the
enclosure.
Step 3: Tilt the supply access panel away from the enclosure.
Step 4: Disconnect the three cables that are attached to the unit.
a: For the cable bundle on the left side, squeeze the tabs on either side of the
connector and gently pull the cable until it is free from the unit.
Page 23
b: For the ribbon cable connected on the right rear side, release the tabs on
L1
L2
L3
N
L1
L2
L3
Step 1:
Step 2a:
Step 2b:
The enclosure door has been removed from this graphic for clarity of this procedure.
either side of the connector by sliding them opposite the connector then gently pull the cable free. Temporarily secure this cable out of the way while pulling conductors into the enclosure.
c: For the two-wire cable on the right side, gently pull the connector straight out.
Step 5: Remove the power supply access panel.
a: Align the panel perpendicular to the enclosure.
b: Slide the panel up approximately one inch to align the guide pins on the top
of the guided slots.
c: Then pull the panel straight out.
Note:
Store this access panel in a safe place until you are finished roughing in conduit and terminations. You will need to reinstall this panel when then enclosure is installed and all wires have been terminated.

Modify Phase Bus for 120V AC Split Phase Operation

The DRd can be simply field modified from a three phase operation to a split phase (3 wire plus ground) operation.
3 Rough-in Conduit and Wiring 19
Step 1: Notice the two copper straps (stacked) on phase L2.
Step 2: Change the DRd operation from 3Ø to split phase by moving the copper straps,
strapping the phase bars together, (reference the graphic above to follow along).
a: Move one of the copper straps to connect between phase 1 (L1) and phase
2 (L2). The screws required are installed to the phase bars in the location the copper strap will be mounted.
Page 24
b: Remove the red sense wire from phase 2 (L2) and reroute it to the neutral
L1
L2
L3
N
N
L1
L2 L3
L1 L2 L3
L1
L2
L3
N
The enclosure doors have been removed from this graphic for clarity of this procedure.
bar.
c: Move the second copper strap to connect between phase 2 (L2) and phase
3 (L3).
Step 3: For cross-bussed DRd12-48 installations, complete step 2 for both enclosures.
20 DRd Enclosure Installation Manual
Page 25

Rough-in Conduit to the DRd Enclosure

L1
L2
L3
N
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
Top Feed DRd Bottom Feed DRd
Line feed wires terminate on the main lugs provided.
The DRd12 enclosure is shipped from the factory with the main lugs in a top feed orientation. The lugs can be changed to a bottom feed orientation by removing the lug mounting bolt, rotating the lug 180°, and re-mounting the lug in the opposite lug mounting PEM. This is true for all DRd12 models.
The DRd6 enclosure phase lugs are both top and bottom feed by default and don’t require any change, but the neutral and ground lugs will require re-orientation for bottom feed.
1 2
3 4
5 6
L1
L2
L3
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
When utilizing an auxiliary enclosure with the DRd enclosure, line feed wires from the auxiliary enclosure enter the DRd enclosure through the top side conduit knockout. For cross-bussed installations the line feed wires will be fed to the DRd through the conduit knockout on the adjoining side of the auxiliary enclosure.
Enclosure
Type
Lug Mounting
Bolt Torque
Wire Range
Lug Wire
Tightening
Torque
350kcmil -
185mm
375 in-lbs 200 in-lbs 375 in-lbs 275 in-lbs 50 in-lbs 45 in-lbs
DRd12
120 and 230V AC
DRd12
240 and 277V AC
6 Ft-lbs 8 Nm 11 Ft-lbs 15 Nm 6 Ft-lbs 8 Nm
2
250kcmil -
1 AWG
120mm2 -
2
50mm
2-6 AWG 2/0-3 AWG 4-6 AWG
35mm2 -
2
16mm
1 AWG
50mm
2-6 AWG
2
-
35mm2 -
2
16mm
42.4 Nm 22.6 Nm 42.4 Nm 31 Nm 5.65 Nm 5.1 Nm
N
(all models)
70mm2 -
2
25mm
DRd6
25mm2 -
2
16mm
3 Rough-in Conduit and Wiring 21
Page 26
Load circuits terminate to the right side the enclosure.
L1
L2
L3
N
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
Load Hot / Live
Load Neutral
Load Ground / Earth
The enclosure door has been removed from this graphic for clarity of this procedure.
Load wires terminate to the load lugs on the right side of the enclosure.
Load neutral and load ground wires terminate on the neutral and ground bus bars located on the back panel of the enclosure. An exception to this is made for the DRd with CE neutral disconnect. Neutrals are terminated to the neutral disconnect on the left side of the enclosure. See “230V AC Neutral Disconnect
DRd Enclosures” on page 27.
Control wires terminate to the right and left I/O boards in the DRd enclosure.
Control wires can enter the enclosure from the top, bottom, or either side, although ETC recommends that you pull control wires into the enclosure from the bottom since all control
AUX POWER
LON LINK / ECHO BUS
SIGNAL DISTRO
LPS
terminations are located near the bottom.
RIDE THRU/BATT
A+ A- COM
B+ B- COM A+ A- COM
B+ B- COM
COM PANIC
SRC OFF END
CDI
J9 DUAL RACKS
APM
DMXB DMXA
The right I/O board is shipped standard with all DRd enclosures and includes terminations for:
24 vDC Auxiliary Power output connector.
LinkConnect/EchoConnect connector.
UL 924 emergency contact input for control bypass.
Auxiliary enclosure (Dual Enclosure) cross-bussed interconnection.
(2) DMX connections and a DMX pass-through connection.
DMXA
DMX PASS-THRU
7183B4606 REV F © 2013 ETC, INC. MADE IN THE U.S.A.
DMXB
All option kit connections including DALI, 0-10V, Unison RideThru option / Unison BatteryPack option.
22 DRd Enclosure Installation Manual
Page 27
A Left I/O card is available for use with Echo ACP and is required for use with Paradigm ACP systems.
Optional Echo Left I/O
The Echo Left I/O board is available as an option for use with the Echo Architectural Control Processor and includes Ethernet connection.
Required Paradigm Left I/O
The Paradigm left I/O board is included with the Paradigm ACP system and include terminations for:
Ethernet
RS232 bi-directional serial
4 dry contact inputs
4 relay contact outputs

Procedure

Step 1: Plan wire entry to the enclosure. See “Wire Routing and Specification” on page 8.
Step 2: Make the desired conduit access (top, bottom, left or right) from the enclosure.
Read and comply with the label inside the enclosure which details the recommended access locations for conduit entry.
Note:
Step 3: Punch holes and install conduit fittings or insert lining materials in conduit
Step 4: Be sure there are minimal air gaps. See “Sealing Air Leaks” on page 52.
CAUTION:
Do not run power and control cable in the same conduit.
opening.
Wire openings must have fittings, bushings, grommets or fiche paper lining material to protect the wire and cable insulation from damage by sharp metal edges, and to prevent air leaks.
3 Rough-in Conduit and Wiring 23
Page 28
Chapter 4

Terminate Wiring

This chapter contains the following sections:
Connect Line Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Connect Load Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Fluorescent Load Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Connect Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
24 DRd Enclosure Installation Manual
Page 29

Connect Line Power Wiring

WARNING:
CAUTION:
All terminations must be done with the power off. DRd enclosures installed without an accessible power disconnect device cannot be serviced or operated safely. In some instances, this device may be an auxiliary enclosure with a main circuit breaker. Follow all local codes and restrictions.
Before servicing, de-energize main feed to DRd and follow appropriate Lockout/Tagout procedures as described in NFPA Standard 70E. It is important to note that electrical equipment such as dimmer enclosures can present an arc flash safety hazard if improperly serviced. This is due to available large short circuit currents on the feeders of the equipment. Any work on energized equipment must comply with OSHA Electrical Safe Working Practices.
Line and load wires used with the Unison DRd must be copper. Do not use aluminum wire.

Connect Line Feed in an Individual DRd Installation

Line feed cables are terminated on the main phase lugs. It is best to route line (feeder) cables first, load neutral and ground/earth wires next, load phase and control wires last. In multiple enclosure installations, load neutral and ground/earth wires must terminate in the same enclosure as the matching load phase wires.
Note:
For DRd6 and DRd12 main lug, main breaker, and cross-bussed applications, reference the Unison Auxiliary Series Enclosure Installation Manual.
The bus bars are different for each enclosure type (DRd6 or DRd12) and each voltage (120, 230 or 240-277). Graphics are provided on the following page for reference.
Step 1: Pull the line phase, neutral and ground cables to the enclosure through the
openings (conduit or other fittings) previously prepared.
Step 2: Strip the insulation from the end of each cable and terminate them to the lugs.
Reference the table below for wire stripping lengths.
Model
DRd6 120, 240, 277V AC
DRd6 230V AC
DRd12 240, 277V AC
DRd12 120, 230V AC
• Line and neutral connections are labeled L1, L2, L3 and N. The equipment grounding/earthing lug is labeled with the universal grounding symbol for easy identification.
Hex Key Size / Wire Strip Length
Phase
3/16” /
5mm
5/16” /
8mm
5/16” /
8mm
3/8” /
10mm
Strip
Length
5/8” /
16mm
1” / 25mm
1” / 25mm
1” / 25mm
Neutral
3/16” /
5mm
5/16” /
8mm
3/8” /
10mm
3/8” /
10mm
Strip
Length
5/8” /
16mm
1” / 25mm
1” / 25mm
1” / 25mm
Ground/
Earth
3/16” /
5mm
3/16” /
5mm
3/16” /
5mm
3/16” /
5mm
Strip
Length
5/8” /
16mm
5/8” /
16mm
5/8” /
16mm
5/8” /
16mm
4 Terminate Wiring 25
Page 30
Note:
CE enclosures are supplied with ANSI hex wrenches for line feed terminations.
Step 3: Tighten the lugs to the correct torque based on cable size. Torque ratings are
also labeled in the DRd enclosure for your convenience.
Type
Lug Mounting
Bolt Torque
Wire Range
Lug Wire
Tightening
Torque
CAUTION:
350kcmil -
185mm2 -
375 in-lbs 200 in-lbs 375 in-lbs 275 in-lbs 50 in-lbs 45 in-lbs
DRd12
120 and 230V AC
6 Ft-lbs 8 Nm 11 Ft-lbs 15 Nm 6 Ft-lbs 8 Nm
2
2-6 AWG
35mm2 -
2
16mm
1 AWG
50mm
42.4 Nm 22.6 Nm 42.4 Nm 31 Nm 5.65 Nm 5.1 Nm
Dress wires neatly and avoid leaving extra wire inside the enclosure. Too much clutter can restrict airflow and cause overtemp errors.
100, 120, 127 V AC, 3Ø DRd Enclosures
1 2
3 4
5 6
L1
L2
L3
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
N
23 24
DRd12
240 and 277V AC
250kcmil -
1 AWG
120mm2 -
50mm
2-6 AWG 2/0-3 AWG 4-6 AWG
35mm2 -
2
16mm
DRd6
(all models)
2
25mm
L1
2
L2
L3
N
70mm2 -
1 2
3 4
5 6
7 8
9
10
11 12
25mm2 -
2
16mm
Note:
For 120V AC single phase installation you must modify the phase bus before connecting wiring. See “Modify Phase Bus for 120V AC Split Phase Operation” on
page 19.
26 DRd Enclosure Installation Manual
Page 31
230V AC Neutral Disconnect DRd Enclosures
L1
L2
L3
N
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
L1
L2
L3
N
1 2
3 4
5 6
7 8
9
10
11 12
L1
L2
L3
N
1 2
3 4
5 6
7 8
9
10
11 12
240, 277V AC DRd Enclosures
1 2
3 4
5
L1
L2
L3
6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
N
4 Terminate Wiring 27
Page 32

Connect Load Wires

Load wire phase
Load wire ground bus
Load wire neutral bus
120, 240, and 277V AC DRd enclosures share similar load lugs.
L1
L2
L3
N
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
Load wire phase
Load wire ground bus
Load wire neutral bus
230V AC DRd enclosures have a neutral disconnect bus structure. This design places neutral lugs on the same side of the enclosure as the main feeds. Neutral output lugs are numbered on the filter PCB. It is important to wire hot and neutral from each load to the corresponding numbered outputs.
Load wires are terminated to the load lugs on the right side of the enclosure. In 120V AC and 240/277V AC DRd enclosures, load neutral and load ground wires are terminated to the terminal strips on the back panel. In 230V AC enclosure types, load neutrals are connected to the left side of the enclosure, stacked on top of the input feeds to maintain a true neutral disconnect.
Phase balancing of the loads is set from within the Architectural Control Processor “Dimmer Setup” menu. Reference the related Architectural Control Processor configuration manual for details.
1 2
3 4
5 6
L1
L3
7 8
9 10
11 12
13
L2
14
15 16
17 18
19 20
21 22
N
23 24
WARNING:
Use of emergency modules (ED15AFE or ER15AFE) in CE 230V DRd enclosures require the neutral (N) lug in place of the neutral jumper per module.
CAUTION:
A two-wire circuit with separate hot/live and neutral conductors is required for every branch circuit that will be connected to the DRd. Shared neutral (multi wire) branch circuit arrangements are not recommended for phase-control dimming systems due to harmonics and potentially elevated neutral currents in a shared
28 DRd Enclosure Installation Manual
neutral arrangement.
For retrofit installations where shared neutral circuits are already installed, or enclosure lighting installations where the enclosure has a shared neutral, consult ETC Technical Services for installation guidelines.
Page 33
Note:
a: Insert the wire on the back side of the lugs. b: Torque the lug screw to the recommended
value indicated in the table below.
Plan load wiring appropriately to avoid splicing wiring. Only one load wire per load terminal.
Step 1: Route the load wires to the DRd enclosure(s) through the conduit previously
installed.
Step 2: Prepare the load wires for termination:
a: Label each wire in the set with circuit designation.
b: Separate load circuit wires into ground, neutral and hot/live wire bundles.
CAUTION:
Step 3: Strip 5/8” (16mm) of insulation from the end of each load wire.
Step 4: Route each load hot/live wire to its individual load output connection.
Connection
15 - 20 amp
Ground bus
Neutral bus
(excluding
Dress and terminate wires neatly and avoid leaving extra wire inside the enclosure. Too much clutter (especially along the right side of the enclosure) can restrict air circulation and reduce cooling efficiency. If cabling interferes with airflow during operation, the DRd may be forced to shut down due to overheating.
Load wires should not cross between DRd enclosures. Instead, they should enter the enclosure in which they will be terminated. Hot/Live and neutral load wiring must follow the same conduit/path for each circuit.
load lugs
230V AC)
Cable Size Torque
AWG
14 - 10 2.5 - 6 35 2.9 4.0
6 - 4 16 45 3.8 5.1
14 - 8 2.5 - 6 75 6.3 8.5
6 - 4 16 110 9.2 12.4
14 - 8 2.5 - 6 75 6.3 8.5
6 - 4 16 110 9.2 12.4
mm
2
lbf-in lbf-ft N - m
Wire Strip
Length
5/8” - 16mm8 10 40 3.3 4.5
5/16” - 8mm
5/16” - 8mm
Neutral
Disconnect
(230V AC only)
4 Terminate Wiring 29
14 - 10 2.5 - 6 35 2.9 4.0
5/8” - 16mm8 10 40 3.3 4.5
6 - 4 16 45 3.8 5.1
Page 34
Step 5: Strip the neutral wire to the length indicated in the table above and terminate to
the neutral terminal assembly. Torque to the recommended value also indicated in the table above. For 230V AC DRd enclosures, the neutral bus is located on the line input feed side of the enclosure.
Step 6: Strip the ground/earth wires to the length indicated in the table above and
terminate to the ground bus terminal. Torque to the recommended value also indicated in the table above.
Note:
Ground connections must use all metal nuts and lock washers.
30 DRd Enclosure Installation Manual
Page 35

Fluorescent Load Wiring

a: Insert the wire on the back side of the lugs. b: Torque the lug screw to the recommended
value indicated in the table below.
Note:
When using D20FB modules, connected to dimmable fluorescent 2-wire ballasts with integral battery backup, use the same terminations as listed in the 3-wire Fluorescent instructions.

3-wire Fluorescent

To control 3-wire fluorescent ballasts, the power circuit in the enclosure must be configured as a fluorescent module type (D15F, D20F, AD15F, AD20F,HD25F), which is a single density module, with a 2/3 wire fluorescent dimmer mode assignment. Reference the related Architectural Control Processor Configuration Manual for instructions on changing the dimmer mode.
Note:
Step 1: Pull the three wire fluorescent ballast wiring into the DRd enclosure per the wire
Step 2: Strip 5/8” (16mm) of insulation from the end of each load wire.
Step 3: Terminate the black switched hot/live wire to the top terminal in its assigned
Even though two lugs are used, the configuration (as found in the Dimmer Setup menu of the ACP) refers only to the top (odd) number lug.
entry plan.
dimmer lug pair. Insert the wire between the back of the lug and the pressure plate as shown.
Cable Size Torque
Connection
AWG
14 - 10 2.5 - 6 35 2.9 4.0
mm
2
lbf-in lbf-ft N - m
15 - 20 amp
load lugs
6 - 4 16 45 3.8 5.1
Ground bus
Neutral bus
(excluding
230V AC)
Neutral
14 - 8 2.5 -6 75 6.3 8.5
6 - 4 10 110 9.2 12.4
14 - 8 2.5 -6 75 6.3 8.5
6 - 4 10 110 9.2 12.4
14 - 10 2.5 - 6 35 2.9 4.0
Disconnect
(230V AC only)
Step 4: Terminate the dimmed hot/live wire to the bottom terminal in its assigned dimmer
lug pair. Insert the wire between the back of the lug and the pressure plate as
4 Terminate Wiring 31
6 - 4 16 45 3.8 5.1
Wire Strip
Length
5/8” - 16mm8 10 40 3.3 4.5
5/16” - 8mm
5/16” - 8mm
5/8” - 16mm8 10 40 3.3 4.5
Page 36
shown in the graphic above. Torque the wire to the recommended value in the torque table above.
Step 5: Strip the neutral wire to the length indicated in the table above and terminate to
the neutral terminal assembly. Torque to the recommended value also indicated in the table above.
Step 6: Strip the ground/earth wires to the length indicated in the table above and
terminate to the ground bus terminal. Torque to the recommended value also indicated in the table above.
Note:
Ground connections must use all metal nuts and lock washers.

2-wire Fluorescent

To control 2-wire fluorescent ballasts, the power circuit in the enclosure must be configured as a standard module type (D15, D20, AD15, AD20, ED15, ED25, HD15, HD25) with a 2/ 3 wire fluorescent dimmer mode assignment. Reference the related Architectural Control Processor Configuration Guide for instruction to change dimmer mode.
Step 1: Pull fluorescent ballast power wiring into the DRd enclosure per the wire entry
plan.
Step 2: Strip 5/8” (16mm) of insulation from the end of each load wire.
Step 3: Terminate the load wire (typically black) to the assigned dimmer lug by inserting
wire between the back of the lug and the pressure plate. a: Insert the wire on the back side of the lugs. b: Torque the lug screw to the recommended value indicated in the table below.
Connection
15 - 20 amp
load lugs
Ground bus
Neutral bus
(excluding
230V AC)
Cable Size Torque
AWG
14 - 10 2.5 - 6 35 2.9 4.0
6 - 4 16 45 3.8 5.1
14 - 8 2.5 -6 75 6.3 8.5
6 - 4 10 110 9.2 12.4
14 - 8 2.5 -6 75 6.3 8.5
6 - 4 10 110 9.2 12.4
mm
2
lbf-in lbf-ft N - m
Wire Strip
Length
5/8” - 16mm8 10 40 3.3 4.5
5/16” - 8mm
5/16” - 8mm
Neutral
Disconnect
(230V AC only)
Step 4: Strip the neutral wire to the length indicated in the table above and terminate to
the neutral terminal assembly. Torque to the recommended value also indicated in the table above.
Step 5: Strip the ground/earth wires to the length indicated in the table above and
terminate to the ground bus terminal. Torque to the recommended value also indicated in the table above.
Note:
32 DRd Enclosure Installation Manual
Ground connections must use all metal nuts and lock washers.
14 - 10 2.5 - 6 35 2.9 4.0
5/8” - 16mm8 10 40 3.3 4.5
6 - 4 16 45 3.8 5.1
Page 37

Connect Control Wiring

1 2
3 4
5 6
7 8
9
10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
3
Right I/O board ­ships standard with each DRd enclosure.
Left I/O board is available as part of the Paradigm Termination Kit which ships with the Paradigm ACP.
An optional Left I/O kit is available for use with Echo ACP when DRd is being used in a networked system.
The enclosure door has been removed from these graphics for clarity of the procedure.
Note:

Overview

All low voltage data and option wiring connects to pluggable connectors on the left and right I/O boards near the bottom of the DRd enclosure.
The DRd ships with a right side I/O board for low voltage control connections. Left side I/O board is available in the optional Paradigm and Echo Termination Kits.
The Paradigm Left I/O Kit supports contact inputs and outputs, serial RS232 and
The Echo Network Kit supports an Ethernet connection for the Echo ACP. The Echo
All low voltage control cables must run in separate conduit from power wires.
Ethernet control. This Left I/O board is not compatible with the SmartLink or Echo Architectural Control Processors.
Network Kit is not compatible with the SmartLink or Paradigm ACPs.
4 Terminate Wiring 33
Note:
The right side I/O board is shipped installed with each DRd and provides termination for SmartLink / LinkConnect / EchoConnect, auxiliary power, DMX, and a UL 924 emergency contact input. The DRd enclosure supports option kits which install in the bottom of the DRd for extended control and operation and terminate to the right I/O board. Option modules include:
0-10V Control Option (DRd-FLO) which provides 24 outputs for control of 0-10V
(4-wire) control for LED drivers and fluorescent ballasts. Each channel output is linked one-to-one with a circuit for power control.
Digital Addressable Lighting Interface (DRd-DALI) which provides 24 outputs for
control of DALI-compatible fluorescent ballasts. Each channel output of DALI control is linked one-to-one with a circuit for power control (DALI Broadcast Mode).
A DRd enclosure supports the use of either a DALI option board (DRd-DALI) or the FLO option board (DRd-FLO), but not both.
Unison RideThru kit provides power to the ACP during brief power outages or drop
outs. The URTO sustains power to the ACP for at least 12 seconds.
Unison BatteryPack kit sustains power to the ACP for up to 90 minutes during
power outages.
Page 38
.
Note:
A DRd enclosure supports the use of either the Unison RideThru option or the Unison BatteryPack option, but not both.

DRd Right I/O Data Terminations

7183B4606 REV F © 2013 ETC, INC. MADE IN THE U.S.A.
DMXB
WARNING:
B+ B- COM
DMX PASS-THRU
DMXB DMXA
DMXA
B+ B- COM A+ A- COM
SRC OFF END
APM
RIDE THRU/BATT
A+ A- COM
J9
DUAL RACKS
CDI
LON LINK / ECHO BUS
COM PANIC
LPS
RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all power to the enclosure before working inside the DRd could result in serious injury or death.
De-energize main feed to DRd enclosure and follow appropriate Lockout/ Tagout procedures as described in NFPA Standard 70E. It is important to note that electrical equipment such as dimmer enclosures can present an arc flash safety hazard if improperly serviced. This is due to available large short circuit currents on the feeders of the equipment. Any work on energized equipment must comply with OSHA Electrical Safe Working Practices.
AUX POWER
SIGNAL DISTRO
Note:
Auxiliary Power
The auxiliary power connector (labeled Aux Power) provides termination for up to 16 wires in the eight position pluggable connector. Each terminal allows up to two 16 AWG (1.5mm wires and provides 24vDC power to control stations when used with the Paradigm Station Power Module. Auxiliary power is not compatible with the Echo or SmartLink Station Power Module.
Note:
Step 1: Pull control auxiliary power wiring (typically 16 AWG (1.5mm
Step 2: Strip 3/16” (5mm) of insulation from the ends of each wire pair.
Step 3: Remove the auxiliary power connector from the right I/O board.
Step 4: Loosen the terminal screws for as many auxiliary wire pairs as you are
Step 5: Insert the black auxiliary power wire from the pair into a “-” terminal on the
Step 6: Insert the red auxiliary power wire from the pair into a “+” terminal on the
Step 7: Repeat steps 5 and 6 for each auxiliary power wire pair.
Step 8: Replace the connector on the right I/O board.
All low voltage control cables must run in separate conduit from power wires.
2
It is required that you terminate LinkConnect / EchoConnect station wiring and the auxiliary power wiring in the same enclosure (rack 1) where the station power module and architectural control processor will be installed.
2
) red / black wire
pair) into the enclosure through the conduit opening previously prepared.
terminating.
connector and tighten the screw to secure the wire into the connector.
connector and tighten the screw to secure the wire into the connector.
)
34 DRd Enclosure Installation Manual
Page 39
LinkConnect and EchoConnect Control Wiring
Control stations communicate with the Architectural Control Processor using the LinkConnect or EchoConnect station communication bus from the Architectural Control Processor to the stations.
Note:
Note:
Termination is available for up to six home runs of LinkConnect / EchoConnect data runs utilizing Belden 8471 cable (or approved equal) plus one 14 AWG (2.5mm
2
) ESD drain wire. This wiring is topology-free and can be installed in any combination of bus, star, loop, and home run. The total combined length of all wire runs cannot exceed 1,640 feet (500m).
While the wiring for LinkConnect in SmartLink and Paradigm and EchoConnect for Echo systems are similar, the communication and control types are not interchangeable. Each product family requires a dedicated station infrastructure that cannot be shared.
Step 1: Pull Belden 8471 (approved equal) control wiring and a 14 AWG ground into the
enclosure through the conduit opening previously prepared.
Step 2: Strip 3/16” (5mm) of insulation from the ends of each wire pair.
Step 3: Remove the EchoConnect/ LinkConnect (LON) connector from the right I/O
board.
Step 4: Loosen the terminal screws for as many wire pairs you are terminating.
Step 5: Insert each white wire (typical) from the pairs into a “B” terminal on the connector
and tighten the screws firmly to secure the wire into the connector.
Step 6: Insert each black wire (typical) from the pairs into an “A” terminal, next to the
previously installed “B” terminal on the connector and tighten the screws firmly to secure the wire into the connector.
It is required that you terminate LinkConnect / EchoConnect station wiring and the auxiliary power wiring in the same enclosure (rack 1) where the station power module and architectural control processor will be installed.
Step 7: Terminate the 14 AWG (2.5mm
2
) ground wire to the DRd ground bus bar in the
rear of the enclosure.
Step 8: Replace the connector to the right I/O board.
UL 924 Listed Panic Input
Termination is available for a UL 924 Listed dry contact input for control bypass. The two pin panic connector, labeled “PANIC”, accepts 16 AWG (1.5mm
2
) wire. Reference the related Architectural Control Processor Configuration Manual for panic look setup.
Step 1: Pull panic wiring into the enclosure through the conduit
opening previously prepared.
Step 2: Strip 3/16” (5mm) of insulation from the ends of each
wire.
Step 3: Remove the 2 pin Panic connector from the right I/O board.
Step 4: Loosen the terminal screws.
Step 5: Insert each wire into the terminals on the connector and tighten the screws firmly
to secure the wires into the connector.
Step 6: Replace the connector to the right I/O board.
ER /
RU/BATT
COM PANI C
J9 DUAL RACKS
CDI
4 Terminate Wiring 35
Page 40
DMX Control Wiring
12345678
n/c
n/c
COM
Data +
Data - ORG
W/ORG
W/BRN
COM
Data +
Data - ORG
W/ORG
W/BRN
Use the DMX Pass-Thru
connector
If daisy-chaining to
another rack or
DMX device...
DMX A
Thru
DMX B
Thru
1234567812345678
COM
Data +
Data +
Data -
Data - ORG
W/ORG
BRN
GRN
W/GRN
BLU
W/BLU
W/BRN
ORG
W/ORG
BRN
GRN
W/GRN
BLU
W/BLU
W/BRN
COM
From source
DMX A
From source
DMX B
Note:
It is required that you terminate DMX wiring in the same enclosure (rack 1) where the architectural control processor will be installed.
DMX wire preparation and termination will vary with the type of wire and termination kit being used. Please refer to the instructions supplied with the DMX termination kit for specific wire preparation.
DMX Input Wire Termination using the Screw Terminals Connector
The graphic to the left illustrates DMX termination layout for the screw-terminal connectors that are intended for use with Belden 9729 cable (or approved equal) cable type.
Screw terminal connectors are supplied as standard in the DMX Preparation Kit w/ Screw Connector, part number 4100A1012.
Be aware that cable other than Belden 9729 may have a different color code for its wire pairs.
DMX Input Wire Termination using the Insulation Displacement Connector (IDC)
The graphic below illustrates DMX termination layout for an insulation displacement connector. This connector type is intended for use with Belden 1583A (or approved equal, such as Category 5, 5E, or 6) cable type. Be aware that cable other than Category 5 may have a different color code for its wire pairs.
If daisy-chaining to
From source
another rack or
DMX A
DMX device...
COM
Data + (Red)
Data - (Black)
n/c
n/c
n/c
n/c
n/c
12345678
Reference and follow the DMX Cable Preparation for IDC Termination instruction sheet that is shipped with the insulation displacement pluggable connector kit (part number 4100A1013).
AX12X Cross-bussed Interconnection
Termination is provided for connection of a second DRd enclosure when installed in a cross-bussed application. This termination point is labeled “Dual Enclosures” on the right I/O board.
An interconnect cable is provided which connects enclosure 1, which is the DRd with the ACP installed, to enclosure 2, which is the secondary enclosure in the cross-bussed system. This cable is labeled at both ends, one end indicating enclosure 1 and the other end indicating enclosure 2. You must have installed this cable to the correct enclosure for proper operation.
This interconnection of enclosures allows full control of both DRd enclosures from only one Architectural Control Processor installed in rack 1. This may only be used in a cross-bussed applications.
Reference the Unison Auxiliary Enclosure Installation Manual for instructions to accomplish this termination.
36 DRd Enclosure Installation Manual
Page 41
Terminate the Unison Options (URTO and UBPO)
LO
Termination is available on the right I/O for the either the Unison Ride Through Option or the Unison BatteryPack Option. You may use only one of these option kits per enclosure.
Step 1: Notice the two pin connector labeled “RideThru / Batt” on
the right I/O board.
Step 2: Follow the instructions provided in the Setup Guide,
provided with the option kit, for appropriate termination.
APM
-THRU
B
+ B- COM
DMXB DMXA
SRC OFF END
Note:
Terminate DMX
DMX requires 120 termination at the last DMX device in the control run. Since a DRd with a Paradigm module installed can utilize up to two DMX inputs (2 DMX runs) the right I/O board provides convenient termination switches for use.
Notice the two termination switches labeled DMXA and DMXB. Each switch has three termination positions:
Source - reserved for RDM termination (future
A single DRd enclosure supports the use of either the Unison RideThru Option board or the Unison BatteryPack Option, but not both in one enclosure.
RideThru/Batt
development).
J9 DUAL RACK
Half
Off - no termination, DMX will pass through this device on to the next DMX device in
the data run.
End - termination is on. Used for the last DMX device (DRd) that is physically
connected in the daisy-chained DMX data run.
When a Paradigm ACP is used in an Unison DRd enclosure, port B will be configured as an output and cannot be changed. Port A is configured as either a DMX input or output. When used as an output the DMX termination should always be set to “Off”.
When an Echo or SmartLink ACP is utilized in the Unison DRd enclosure, port A is automatically configured to be a DMX input and cannot be changed, port B is not used.
4 Terminate Wiring 37
Page 42

DRd Left I/O Data Termination

1
6
NO4
COM4
NO3
COM3
NO2
COM2
NO1
COM1
IN4
GND
IN3
GND
IN2
GND
IN1
GND
OUTPUTSINPUTS J4 J5
7183B4605 REV © 2008 ETC, INC. MADE IN THE U.S.A.
RS-232
J3
J2 E THERNET
Paradigm Network Termination board
Echo Network Termination board
The Left I/O board is not included with the DRd enclosure when shipped from the factory. Instead, the appropriate board is provided in the Paradigm DRd Termination kit or Echo ACP Network Option kit when ordered separately. The Left I/O board should be installed by the installing contractor or field technician. Follow the instructions provided with the Left I/O board for installation and wire termination.
Note:
Data terminations to the left I/O board are specific to the processor used. SmartLink does not support a left I/O option.
The left I/O board supports the Echo Architectural Control Processor and Paradigm
Architectural Control Processor data terminations including:
Ethernet on a RJ-45 female connector.
RS-232 on a male 9 pin (D style) connector (P-ACP only).
Contact closure input terminations on a 8 pin pluggable connector (P-ACP only).
Terminations available for 4 inputs and 4 common wires.
Contact closure output terminations on a 8 pin pluggable connector (P-ACP only).
Terminations available for 4 normally open relay outputs and 4 common wires.
Connect to Serial RS-232
Integrators or users of advanced systems can interface with the Unison system through the RS-232 connector on the left I/O board. This connection provides an interface with external devices capable of sending or receiving RS-232. This connection can also receive serial commands from a transmitter and provide DRd and system status when queried.
Note:
The RS-232 cable (not supplied) should follow common RS-232 pinout for a DB9 receptacle (pin 2 is RS-232 Rx, pin 3 is RS-232 Tx, and pin 5 is ground).
Connect to Ethernet RJ-45
Network interface to the DRd is made through the RJ-45 connector (labeled Ethernet) located on the left I/O board.
38 DRd Enclosure Installation Manual
Note:
All Ethernet terminations must follow IEEE 802.3 and be terminated to the T568B standard.
Page 43
Connect to Contact Inputs and Contact Outputs
The left I/O provides a convenient interface (inputs and outputs) to external devices via contact closure on removable pluggable connectors. Up to four contact inputs are available and can be configured for either maintained or momentary operation by the technician creating the Paradigm architectural configuration. Up to four contact outputs are available and are preset for normally open operation.
Note:
Terminate Contact Inputs
Step 1: Remove the contact inputs removable screw terminal connector located on the
Step 2: Loosen the desired number of contact input screw terminals and related ground
Step 3: Insert contact closure 1 into the terminal labeled “IN1” on the connector and
Step 4: Insert the related common wire for contact closure 1 into the terminal labeled
Step 5: Repeat for each contact input and ground wire pair (up to four total).
Terminate Contact Outputs
Step 1: Remove the contact outputs removable screw terminal connector located on the
Step 2: Loosen the desired number of contact output (normal open) screw terminals and
Step 3: Insert contact output 1 into the terminal labeled “NO1” on the connector and
Step 4: Insert the related common wire for contact output 1 into the terminal labeled
Step 5: Repeat for each contact output and common wire (up to four total).
Typical contact I/O wiring is color coded as follows: contact 1 - brown, contact 2 ­orange, contact 3 - yellow, contact 4 - green. All commons and ground voltages are typically black or red.
left I/O board. Each connector is labeled for installation convenience.
screw terminals on the connector.
tighten the screw terminal.
“GND” on the connector and tighten the screw terminal.
left I/O board. Each connector is labeled for installation convenience.
related ground screw terminals on the connector.
tighten the screw terminal.
“COM1” on the connector and tighten the screw terminal.
4 Terminate Wiring 39
Page 44
Chapter 5

Install Option Kits

DALI Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
0-10V Control Option Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
RideThru Option Kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
BatteryPack Option Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
40 DRd Enclosure Installation Manual
Page 45

Installation of Option Kits

Unison DRd enclosure options include the 0-10V control option kit, the Digital Addressable Lighting Interface Option kit, the RideThru option kit, and the BatteryPack option kit.
Note:
It is best to install option kits after conduit rough-in and the line, load and control terminations are complete to reduce the likelihood of damage to the option boards.
A single DRd enclosure supports the use of either the DALI Option kit or the 0-10V Option kit, but not both in the same enclosure.
In addition, a single DRd enclosure supports the use of either the Unison RideThru Option or the Unison BatteryPack Option, but not both in the same enclosure.

DALI Option

Install the DALI Option kit
The Digital Addressable Lighting Interface option controls 24 loops of 64 DALI compatible ballasts and drivers in a broadcast mode. Each of the 24 DALI loops are linked one to one with a circuit for power control. For example, DALI loop 1 is controlled by dimmer 1, DALI loop 2 is controlled by dimmer 2, etc.
To control DALI ballasts or drivers, the circuit must be populated with a module and assigned to DALI dimmer mode within the ACP software. Reference the related Architectural Control Processor programming guide for instruction to change dimmer mode.
Note:
The DALI device is powered by an external DALI power supply (supplied by others). Each DALI loop requires its own power supply and possibly more than one power supply depending on the load.
5 Install Option Kits 41
Page 46
The DALI option supports 64 DALI compatible devices per DALI loop. All DALI devices
Step 2:
Step 3:
Step 4:
connected to that loop will respond at the same time and to the same level as sent by the broadcast command.
Step 1: Align the DALI option board to the mounting studs in the bottom right side of the
enclosure.
Notice the mounting holes on the DALI option board. One is a slotted keyhole, another is an open ended slot and the remaining two on the other end of the board are standard mounting holes used to secure the board in place.
Step 2: Set the rear left stud through the slotted keyhole and align the open ended slot
with the back right side mounting stud.
Step 3: Gently slide the DALI board toward the right I/O board aligning the five prong
connector to the receptacle on the I/O board.
Step 4: Secure the bottom two mounting studs with the screws provided.
42 DRd Enclosure Installation Manual
Page 47
Connect DALI Option Wiring
2008
Label
Each of the four bus connectors on the option board provide termination for six DALI loops. Each bus connector is labeled for ease of loop identification and is pluggable for ease of wiring termination. Terminals accept 12-24 (4 - .25mm
2
) AWG
Class 1 wire.
*Maximum Run Lengths for Class 1 wiring
18 AWG
2
1mm
16 AWG
1.3 mm
14 AWG
2
1.6 mm
2
12 AWG
2
2 mm
**Max.
aggregate run
length
feet meter feet meter feet meter feet meter feet meter
570 175 900 275 1,430 435 2,280 700 3000 900 *Maximum Run Length - the longest distance between any device and any power supply on
the DALI bus. **Maximum Aggregate Run Length - the longest total length of all total wiring connected to the DALI bus.
It is important to label the DALI fluorescent ballast load and control wiring sets with the circuit designation. Control wires terminate on the associated DALI board output loop terminal.
For example: If circuit 1 is configured as a D20 in DALI dimmer mode, DALI fluorescent ballast control wiring should terminate to the DALI board loop output terminals labeled “1”.
Note:
Step 1: Remove the DALI bus connector for loop outputs 1-6.
Step 2: Strip each wire in the pair back 1/4 inch (6mm).
Step 3: Using a small 3,35mm or 1/8” flat blade screwdriver, loosen the terminals and
Step 4: Tighten the terminal screw until the wire is held snugly.
Step 5: Repeat steps 1 through 4 for the remaining DALI loops through loop 6.
Step 6: Replace the DALI bus connector on the DALI board and repeat for the remaining
The lug number inside the enclosure should match the control line number designation regardless of whether the DRd is configured for straight or balanced numbering.
insert each wire into the data “+” or data “–” terminals for the specific circuit loop. Data wires in the wire set are polarity independent.
DALI loops in the system (up to 24 loops).
5 Install Option Kits 43
Page 48

0-10V Control Option Kit

Step 2
Step 3
Step 4
Install the 0-10V Option Kit
The 0-10V Control option (DRd-FLO) provides 24 outputs for control of 0-10V (4-wire) ballasts and drivers. Each channel output is linked one-to-one with a circuit for power control. The FLO board is comprised of 24 individual 0-10 vDC connections, each rated to control a maximum of 400mA per channel.
Each output connection is clearly labeled on the removable screw terminal bus connectors. The removable connectors accept 12 - 24 AWG (4 - .25mm
Step 1: Align the 0-10V option board to the mounting studs in the bottom of the
enclosure.
Notice the mounting holes on the 0-10V option board. One is a slotted keyhole, another is an open ended slot, and the remaining two on the other end of the board are standard mounting holes used to secure the board in place.
Step 2: Set the rear left stud through the slotted keyhole and align the open ended slot
with the back right side mounting stud.
Step 3: Gently slide the option board toward the right I/O board aligning the five prong
connector to the receptacle on the I/O board.
Step 4: Secure the remaining two mounting holes to the pems with the screws provided.
2
) Class 1 wire.
44 DRd Enclosure Installation Manual
Page 49
Connect 0-10V Control Option Wiring
2008
Label
-6+ -5+ -4+ -3+ -2+ -1+
-12+ -11+ -10+ -9+ -8+ -7+
-18+ -17+ -16+ -15+ -14+ -13+
-24+ -23+ -22+ -21+ -20+ -19+
FLUOR 1 - 6
FLUOR 7 - 12
FLUOR 13 - 18
FLUOR 19 -24
Each of the four bus connectors on the option board provide termination for six fluorescent outputs. Each bus connector is labeled for ease of identification and is pluggable for ease of wiring termination. Terminals accept 12-24 (4 - .25mm
2
) AWG Class 1 wire.
Note:
Note:
0-10V control wiring must be routed in separate conduit from the line voltage wiring.
To control 0-10V devices, the power circuit in the DRd must be a dimmer or relay module and assigned to 4-wire fluorescent dimmer mode. Reference the related Architectural Control Processor configuration manual for instruction to change dimmer mode.
It is important to label the 0-10V load and control wiring sets with the circuit designation. Control wires terminate on the associated 0-10V option board output terminal. Example: If circuit 1 is configured as a dimmer with a 4-wire fluorescent dimmer mode, ballast control wiring would terminate to the 0-10V option board output terminals labeled “1”.
The lug number inside the enclosure should match the control line number designation regardless of whether the DRd is configured for straight or balanced numbering.
Step 1: Pull 0-10V control wiring pairs into the DRd enclosure per the wire entry plan.
Step 2: Strip each wire pair back 1/4 inch (6mm).
Step 3: Remove the bus connector for outputs 1-6. The pluggable connector is seated
tight in the receptacle. You may need to gently pry the connector free from the board using a small 3,35mm or 1/8” flat blade screwdriver.
Step 4: Notice the connector is labeled for your reference during wire termination. Using
a small 3,35mm or 1/8” flat blade screwdriver, loosen the terminals and insert each of the data “+” and data “–” wires in the wire set into the appropriate terminal.
a: Terminate the violet (typical) control wire of the first pair into the “+” terminal
associated to the power circuit.
b: Terminate the gray (typical) control wire of the first pair into the “–” terminal
associated to the power circuit.
c: Tighten each screw terminal until the wire is held snug.
Step 5: Repeat for the remaining outputs through output 6.
Step 6: Replace the first bus connector to the option board and repeat for the remaining
fluorescent outputs in the system (up to 24 outputs).
5 Install Option Kits 45
Page 50

RideThru Option Kit

Note:
A single DRd supports the use of either the Unison RideThru Option or the Unison BatteryPack Option, but not both in the same enclosure.
Install the RideThru Option Kit
WARNING:
The RideThru Option kit provides power for the Architectural Control Processor for a minimum of 12 seconds during brief power outages or power drop outs. The RideThru Option board fully charges and is ready for operation within ten minutes of the DRd being powered.
Risk of Electric Shock! The Unison RideThru option board retains an electrical charge even when power to the DRd is off.
2008
Step 1: Align the RideThru Option board to the mounting studs in the bottom of the
enclosure.
Notice the mounting holes on the option board. Two are open ended slots used to place the board, and the remaining two standard mounting holes used to secure the board in place.
Align the open ended slots to the studs and rest the other end of the board on the mounting studs.
Step 2: Secure the board to the two mounting studs with the screws provided.
46 DRd Enclosure Installation Manual
Page 51
Connect RideThru Option Wiring
2008
Step 1:
The BatteryPack Option kit provides sustained battery power to the Architectural Control Processor for up to 90 minutes during power outages. The self-contained battery installs on the bottom of the host DRd enclosure.
The Unison RideThru Option board is provided with a wiring harness for connection between the option board and the right I/O board.
Step 1: Connect one end of the wiring harness to the two pin receptacle on the option
board.
Step 2: Connect the other end of the wiring harness to the two pin receptacle labeled
“RideThru/Batt” on the right I/O board. See “DRd Right I/O Data Terminations”
on page 34.
Secure the wiring harness to the DRd enclosure using the cable tie and cable tie mounts supplied with the RideThru Option board.

BatteryPack Option Kit

Note:
A single DRd supports the use of either the Unison RideThru Option or the Unison BatteryPack Option, but not both in the same enclosure.
Install the BatteryPack Option Kit
Step 1: The BatteryPack Option board is provided with a wiring harness for connection
between the BatteryPack and the right I/O board. Install the wiring harness and connector into the enclosure (the connector is keyed for proper orientation).
5 Install Option Kits 47
Page 52
a: Insert the connector end through the opening in the bottom of the enclosure.
DRd enclosure before UBPO cable and connector installation
DRd enclosure after UBPO cable and connector installation
The connector is designed to snap into place without additional hardware, therefore slight force may be required to ensure the connector installs properly.
Step 2: Connect the two pin receptacle labeled “RideThru/Batt” on the DRd right I/O
board. See “DRd Right I/O Data Terminations” on page 34.
Step 3: Secure the wiring harness to the enclosure using the cable tie and cable tie
mount supplied with the BatteryPack Option kit. A loose or poorly routed wiring harness could interfere with option module (DRd-FLO or DRd-DALI) installation.
48 DRd Enclosure Installation Manual
Page 53
Step 4: Install the BatteryPack on to the bottom of the enclosure.
see Note:
Step 4a:
Step 4b:
Note:
a: Insert the tabs from the BatteryPack into the slots in the DRd enclosure.
As the battery is mated to the enclosure, the connector on the BatteryPack and the connector receptacle installed in step 1 also mate.
b: Secure the BatteryPack to the enclosure using the captive screw provided.
5 Install Option Kits 49
Page 54
Chapter 6

Final Installation and Power Up

This chapter contains the following sections:
Checking the Installation before Installing Modules . . . . . .51
Sealing Air Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Final Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Control Bypass (Test Mode) . . . . . . . . . . . . . . . . . . . . . . . . . .54
Reengage Module Retention Bar . . . . . . . . . . . . . . . . . . . . . .55
50 DRd Enclosure Installation Manual
Page 55

Checking the Installation before Installing Modules

It’s a good idea to look over the entire installation before installing modules or applying power to the enclosure.
WARNING:
Step 1: Clean out dust, metal scraps or other debris from the interior of the enclosure.
Step 2: Check for loose connections, bare wires and damaged insulation.
Step 3: Manually spin the top cooling fan in both directions to be sure it is not obstructed.
Step 4: Correct air leaks caused by misaligned or removed conduit panel openings or
Step 5: Check resistance between phases, Neutral and Earth for short circuits. With the
Step 6: Check Load Wiring. Check resistance between the load terminals and the
Power must be turned OFF when you perform this procedure.
Before service, de-energize main feed to DRd and follow appropriate Lockout/Tagout procedures as described in NFPA Standard 70E. It is important to note that electrical equipment such as dimmer enclosures can present an arc flash safety hazard if improperly serviced. This is due to available large short circuit currents on the feeders of the equipment. Any work on energized equipment must comply with OSHA Electrical Safe Working Practices.
ETC recommends vacuuming the interior before installing modules.
empty screw holes. For complete instructions for this procedure reference
Sealing Air Leaks, page 52.
power connector to the Power Supply/Dimming Engine still removed (this was accomplished prior to installing conduit and terminating any wires, see Remove
the DRd Power Supply/Dimming Engine Access Panel, page 18), and the all
modules removed from the enclosure, including the Station Power Module, check resistance between phases, neutral and ground busses with a digital voltmeter (DVM).
a: Phase to Phase; resistance should be 10M ohm or higher.
b: Phase to Earth (ground); resistance should be 10M ohm or higher.
c: Neutral to Earth (ground); resistance should be less than 1 ohm.
d: Phase to Neutral; resistance should be 10M ohm or higher.
Neutral buss.
a: Above 1M ohm is normal when no load is connected.
b: Between 6-300 ohm is a reasonable reading when loads are connected.
c: Below 1M ohm indicates a dead short in the load wiring and an infinite
reading indicates no load or an open circuit
.
CAUTION:
A dead short can cause module damage.
6 Final Installation and Power Up 51
Page 56

Sealing Air Leaks

After you have attached all the conduit to the enclosure and connected all wiring, you must seal any air leaks in the enclosure that was created during the installation process. ETC recommends use of urethane aerosol foam to fill air gaps in conduit fittings.
Seal all conduit access holes.
Completely cover all conduit openings with fiche paper and/or urethane aerosol foam or duct seal.
Seal any air gaps caused by bent access panels.
Fill in any gaps inside partially filled wiring conduit.
Fill in other gaps or holes in the cabinet created during installation.
Any enclosures that are installed side - by - side (bolted together) should only have minimal airflow between them.
CAUTION:
Air leaks can cause the DRd to overheat during operation and shut down. Air leaks can also cause a DRd to shut down via an overtemp error, meaning that too little air is flowing through the front of the enclosure where it is needed to cool the dimmers.
52 DRd Enclosure Installation Manual
Page 57

Final Installation

Step 3
Step 2a
Step 2.b
Step 2.c
The enclosure door has been removed from this graphic for clarity of this procedure.
Step 1: Reinstall the Power Supply / Dimming
Engine Access Panel that was removed prior to conduit installation and wire termination.
a: Align the guide pins located on the
access panel to the guided slots on the enclosure.
b: Glide the access panel down, so
that it rests fully into the guided slots.
c: Tilt the supply access panel away
from the enclosure.
Note:
All DRd enclosures are shipped with a dimmer module retention bar installed. The dimmer module retention bar prohibits installed modules from being removed from the enclosure without the use of a tool.
Before installing modules into the DRd, loosen the screws retaining this bar in place, then slide the bar to the left side of the enclosure (door hinge side). Complete the final installation procedure outlined below, then reengage the module retention bar (see page 55). This bar is required to be installed in all enclosures in order to maintain proper CE rating and NFPA70 compliance.
.
6 Final Installation and Power Up 53
Step 2: Reconnect the three cable assemblies to the unit.
a: For the cable bundle on the left side, insert the connector into receptacle until
you hear a click.
b: For the ribbon cable on the right rear side; insert the connector into the
receptacle. Press gently on both sides until it clips into place.
c: For the two-wire cable on the right side, gently press the connector straight
into the receptacle. This connection is also keyed and can only install one way.
Step 3: Rotate the access panel closed, then slide the panel up approximately one inch
to align the panel to the captured screws.
Step 4: Tighten the two captive screws, securing the access panel in place.
Step 5: Install modules into the DRd.
a: Align each dimmer module with the correct module slot and firmly press into
place. The face of the dimmer module should be flush with the DRd enclosure.
b: Install the Station Power Module and Architectural Control Processor into
their respective slots. The Architectural Control Processor installs into the lowest module slot. The Station Power Module installs into the slot directly above the ACP.
Page 58
WARNING:
Control Bypass switch
Step 6: Power up the enclosure. Before installing or removing dimmer or control
Step 7: Switch all module circuit breakers to the “On” position.
Step 8: Reference the related Architectural Control Processor Configuration Manual for
Never power up or operate the DRd enclosure without all modules installed. Failure to comply exposes you to dangerously high voltages that may result in death by electrical shock.
modules for service, de-energize main feed to DRd and follow appropriate Lockout/ Tagout procedures as described in NFPA Standard 70E. It is important to note that electrical equipment such as dimmer enclosures can present an arc flash safety hazard if improperly serviced. This is due to available large short circuit currents on the feeders of the equipment. Any work on energized equipment must comply with OSHA Electrical Safe Working Practices.
DRd configuration setup and operation.

Control Bypass (Test Mode)

Test load circuits connected to the DRd enclosure by switching the “Control Bypass” switch to the “Test” position. The Control Bypass switch allows testing of lighting loads and provides temporary lighting before complete system commissioning. Return the switch to its “Normal” setting after the test is complete.
CAUTION:
54 DRd Enclosure Installation Manual
Turning the Control Bypass switch to the “Test” position with all module circuit breakers “On” will bring all lighting loads to full. To select only certain lighting loads for test, switch “Off” undesired module circuit breakers in the DRd enclosure.
Page 59

Reengage Module Retention Bar

Enclosure door removed from graphic only for clarity of the dimmer module retention installation.
Dimmer module
retention bar
Step 1: Check that all required modules have been installed into the DRd enclosure including
dimmer modules, air flow modules, Station Power Module, and Architectural Control
Processor. All module slots should be populated. Step 2: Loosen the screws on the retention bar. Step 3: Slide the retention bar to the right. Notice the retention bar has two tabs that insert into
the ACP and Station Power Module slots for retention. Step 4: Secure the retention bar in place using the screws provided.
6 Final Installation and Power Up 55
Page 60
56 DRd Enclosure Installation Manual
Page 61
Appendix A

Modules Specification

120 VAC Modules
Module Type
AFM Air Flow Module 7083A1072 CC15 Dual 15A Constant Circuit Breaker Module 7083A1021 2.1 lbs / 1.0 kgs CC20 Dual 20A Constant Circuit Breaker Module 7083A1025 2.2 lbs / 1.0 kgs D15 Dual 15A, 1.8KW, 350µS Dimmer Module 7083A1018 5 lbs / 2.3 kgs D15E Dual 15A, 1.8KW, 500µS Dimmer Module 7083A1019 5 lbs / 2.3 kgs D15F Single 15A, Fluorescent Dimmer Module 7083A1020 2.4 lbs / 1.1 kgs D15FB Single 15A, Fluorescent / Battery Dimmer Module 7183A1073 2.4 lbs / 1.1 kgs D20 Dual 20A, 2.4KW, 350µS Dimmer Module 7083A1022 5 lbs / 2.3 kgs D20E Dual 20A, 2.4KW, 500µS Dimmer Module 7083A1023 5 lbs / 2.3 kgs D20F Single 20A, 2.4KW Fluorescent Dimmer Module 7083A1024 2.4 lbs / 1.1 kgs D20FB Single 20A, Fluorescent / Battery Dimmer Module 7183A1074 2.4 lbs / 1.1 kgs ELV10 Dual 1.2KW, Reverse Phase 10A Dimmer Module 7183A1017 2.6 lbs / 1.2 kgs R15 Dual 15A at 120 VAC Relay Module 7083A1084 2.6 lbs / 1.2 kgs R20 Dual 20A at 120 VAC, Relay Module 7083A1085 2.6 lbs / 1.2 kgs L10 Reverse Phase 10A at 120 VAC, Dimmer Module 7083A1078 2.4 lbs / 1.1 kgs
L10F
Description Part Number
3 wire, Reverse Phase 10A at 120 VAC, Dimmer Module
7083A1079 2.4 lbs / 1.1 kgs
Module Weight (lbs/kg)
1.3 lbs / 0.59 kgs
230 VAC Modules
Module Type
AFM Air Flow Module 7083A1072 1.3 lbs / 0.59 kgs ECC6 Dual 6A, 1.3KW, Constant Circuit Module 7183A1091 2.7 lbs / 1.2 kgs ECC6N Dual 6A, 1.3KW, Neutral Disconnect Constant Circuit Module 7183A1089 5 lbs / 2.3 kgs ECC10 Dual 10A, 2.3KW Constant Circuit Module 7183A1092 5 lbs / 2.3 kgs ECC10N Dual 10A, 2.3KW Neutral Disconnect Constant Circuit Module 7183A1090 5 lbs / 2.3 kgs ECC15 Dual 15A, 3KW Constant Circuit Module 7070A1046 2.7 lbs / 1.2 kgs ECC25 Dual 25A, 5KW Constant Circuit Module 7070lA1047 2.5 lbs / 1.1 kgs ED6 Dual 6A, 1.3KW 400µS Dimmer Module 7170A1073 5.5 lbs / 2.5 kgs
ED6E
ED6N Dual 6A, 1.3KW, 400µS Dimmer Module 7070A1081 5.5 lbs / 2.5 kgs ED6NE Dual 6A, 1.3KW, 400µS Neutral Disconnect Dimmer Module 7183A1079 5 lbs / 2.3 kgs ED10 Dual 10A, 2.3KW 400µS Dimmer Module 7070A1074 5.5 lbs / 2.5 kgs ED10E Dual 10A, 2.3KW, 400µS Dimmer Module 7083A1086 5 lbs / 2.3 kgs
ED10N
ED10NE Dual 10A, 2.3KW, 400µS Neutral Disconnect Dimmer Module 7070A1080 5.5 lbs / 2.5 kgs
ED15
Description Part Number
Dual 6A, 1.3KW, 400µS Dimmer Module
Dual 10A, 2.3KW, 400
Dual 15A, 3KW, 225µS Dimmer Module
µS Neutral Disconnect Dimmer Module
7183A1085 5 lbs / 2.3 kgs
7070A1082 5.5 lbs / 2.5 kgs
7083A1035 1.3 lbs / 0.59 kgs
Module Weight (lbs/kg)
A Modules Specification 57
Page 62
230 VAC Modules
Module Type
ED15E
ED15N
ED15NE
ED15RS Dual 15A, 3KW, 225µS RCD Module 7083A1045 5 lbs / 2.3 kgs
ED15RE
ED25S Single 25A, 225µS Dimmer Module 7083A1033 5.5 lbs / 2.5 kgs
ED25E
ED25NE
ED25NS Single 25A, 5KW, 225µS Neutral Disconnect Dimmer Module 7083A1043 5.5 lbs / 2.5 kgs ED25RS Single 25A, 5KW, 225µS RCD Module 7083A1047 5 lbs / 2.3 kgs
ED25RE
EELV6 Dual 10A, Reverse Phase 230V AC, Dimmer Module 7070A1300 5 lbs / 2.3 kgs ER6 Dual 6A, 1.3KW at 230V AC, Relay Module 7183A1083 5 lbs / 2.3 kgs ER10 Dual 10A, 2.3KW at 230V AC, Relay Module 7083A1084 5 lbs / 2.3 kgs ER15 Dual 15A, 3KW at 230V AC, Relay Module 7083A1086 3.1 lbs / 1.42 kgs ER25 Dual 25A, 5KW at 230V AC, Relay Module 7083A1087 3.1 lbs / 1.42 kgs
Description Part Number
Dual 15A, 3KW, 400µS Dimmer Module
Dual 15A, 3KW, 225
Dual 15A, 3KW, 400
Single 15A, 3KW, 400µS RCD Module
Single 25A, 5KW, 400µS Dimmer Module
Single 25A, 5KW, 400 Module
Single 25A, 5KW, 400
µS Neutral Disconnect Dimmer Module µS Neutral Disconnect Dimmer Module
µS, Neutral Disconnect Dimmer
µS RCD Module
7083A1032 5 lbs / 2.3 kgs
7083A1041 5.6 lbs / 2.5 kgs
7083A1042 5.6 lbs / 2.5 kgs
7083A1046 5 lbs / 2.3 kgs
7083A1034 5.5 lbs / 2.5 kgs
7083A1044 5 lbs / 2.3 kgs
7083A1048 5 lbs / 2.3 kgs
Module Weight (lbs/kg)
240 VAC Modules
Module Type
AFM Air Flow Module 7083A1072 1.3 lbs / 0.59 kgs HD15 Dual 15A, 3.0KW at 240 V AC, 165µS Dimmer Module 7183A1047 5 lbs / 2.3 kgs HD15F Single 15A, Fluorescent Dimmer Module 7183A1056 5 lbs / 2.3 kgs HELV5 Dual 5A, Reverse Phase 240 V AC, Dimmer Module 7183A1055 2.4 lbs / 1.1 kgs HR15 Dual 15A at 240 V AC, Relay Module 7183A1057 3.1 lbs / 1.42 kgs HCC15 Dual 15A, Constant Circuit Module 7183A1058 2.6 lbs / 1.2 kgs
Description Part Number
Module Weight (lbs/kg)
58 DRd Enclosure Installation Manual
Page 63
277 VAC Modules
Module Type
AFM Air Flow Module 7083A1072 1.3 lbs / .59 kgs ACC15 Dual 15A at 277V AC, Constant Circuit Breaker Module 7183A1048 2.7 lbs / 1.2 kgs ACC20 Dual 20A at 277V AC, Constant Circuit Breaker Module 7083A1090 2.7 lbs / 1.2 kgs AD15 Dual 15A, 4.1KW at 277V AC, Dimmer Module 7083A1006 5 lbs / 2.3 kgs AD15F Single 15A, 4.1KW at 277V AC, Dimmer Module 7083A1008 2.4 lbs / 1.1 kgs
Material description Part Number
Module Weight (lbs/kg)
AD15FB Single 15A, Fluorescent / Battery Dimmer Module 7183A1075 2.4 lbs / 1.1 kgs
AD20 Dual 20A, 5.5KW at 277V AC, Dimmer Module 7083A1007 5 lbs / 2.3 kgs AD20F Single 20A, 5.5KW at 277V AC, Fluorescent Dimmer Module 7083A1009 2.4 lbs / 1.1 kgs
AD20FB Single 20A, Fluorescent / Battery Dimmer Module 7183A1076 2.4 lbs / 1.1 kgs AL5 Dual 5A at 277V AC Reverse Phase Dimmer Module 7083A1075 2.4 lbs / 1.1 kgs
AL5F
AELV5 Dual 5A at 277V AC Reverse Phase Dimmer Module 7183A1028 2.6 lbs / 1.2 kgs AR15 Dual 15A at 277V AC Relay Module 7083A1082 2.6 lbs / 1.2 kgs AR20 Dual 20A at 277V AC Relay Module 7083A1083 2.6 lbs / 1.2 kgs
Single, 3 wire, 5A at 277V AC Reverse Phase Dimmer Module
7083A1076 2.4 lbs / 1.1 kgs
A Modules Specification 59
Page 64
60 DRd Enclosure Installation Manual
Page 65
Appendix B
Figure 1: Emergency Module Circuit
Module Circuit Breaker
Dimming Circuit
Dimmed Output
Constant Output

CE 230V Emergency Modules

230V CE Emergency modules are non-standard for DRd 230V enclosures. On the occasion that your installation requires use of these modules, refer to the information outlined below for installation.
Note:
When configuring the dimmer modules at the Architectural Control Processor, configure as either the ED15 or the ER15 module type.

About Emergency Modules

The 230V CE Emergency modules provide two live outputs, one of which is dimmed or switched, and one of which is live whenever the breaker is turned “On”. This setup allows the modules to control battery-backed lighting, which requires both a constant and a switched or dimmed feed.
ETC offers two varieties of Emergency Modules - ED15AFE (15A Dimmer), and ER15AFE(15A Relay), painted red for easy identification.

Wire Termination

The constant output from the module is connected to the Neutral lugs at the left of the enclosure. Therefore, unlike Neutral Disconnect modules, Emergency modules provide a live output at these lugs, not a neutral connection.
Note:
B CE 230V Emergency Modules 61
ETC does not offer a Neutral Disconnect or RCD version of the emergency modules.
Step 1: Locate the module slot in the enclosure where the Emergency module is to be
fitted.
Step 2: Terminate the outgoing dimmed line to the terminals at the right hand side of the
enclosure.
Step 3: Terminate the outgoing (constant feed) line to the terminals at the left side of the
enclosure.
Step 4: Terminate the outgoing (Earth) line to the earth bar terminals.
Page 66
Step 5: Terminate the Neutral as described in the following section, dependant on your
Figure 2: Emergency Module Connections
Constant live line is landed on the Neutral lugs
Dimmed or switched line is landed on live lugs
DRd enclosure model.

Non Neutral Disconnect

For enclosures which have neutral jumpers fitted, the Neutral of the load, fed by the Emergency module, must be connected to the Neutral terminal of an adjacent module.

Neutral Disconnect

In enclosures without neutral jumpers (Neutral Disconnect enclosures), the Neutral of the load should not be connected to another load’s Neutral terminal. This can cause unwanted tripping of RCD modules.
Instead, an auxiliary neutral terminal must be fitted to the neutral plate and the loads should be connected to the terminal. If your enclosure was ordered with Emergency modules from the factory, the auxiliary neutral terminal will be factory fitted. If you require an auxiliary neutral terminal for field installation, please contact ETC as shown using the details in
Contacting ETC, page 2.
62 DRd Enclosure Installation Manual
Page 67
B CE 230V Emergency Modules 63
Page 68
Corporate Headquarters London, UK Rome, IT 
 Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK  Tel +44 (0)20 8896 1000  Fax +44 (0)20 8896 2000
Via Pieve Torina, 48, 00156 Rome, Italy  Tel +39 (06) 32 111 683  Fax +44 (0) 20 8752 8486
Holzkirchen, DE
 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA  Tel +608 831 4116  Fax +608 836 1736
 Ohmstrasse 3, 83607 Holzkirchen, Germany  Tel +49 (80 24) 47 00-0  Fax +49 (80 24) 47 00-3 00
Hong Kong  Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong  Tel +852 2799 1220  Fax +852 2799 9325 Service:
(Americas) service@etcconnect.com
Web:
www.etcconnect.com
7183M2100
 Rev D  Released 2014-07
Copyright © 2014 ETC. All Rights Reserved.  Product information and specifications subject to change.
(UK) service@etceurope.com  (DE) techserv-hoki@etcconnect.com
ETC intends this document to be provided in its entirety.
(Asia) service@etcasia.com
Loading...