ETC Unison DRd DALI Option Kit User Manual

ETC® Setup Guide
Step 2:
Step 3:
Step 4:
Unison® DALI Option Kit Installation
Note:
It is best to install rack options after conduit rough-in and the line, load and control terminations are complete to reduce the likelihood of damage to the option board.
DALI Option Kit

Overview

The Digital Addressable Lighting Interface option kit (DRd-DALI) controls 24 loops of 64 DALI compatible fluorescent ballasts in a broadcast mode. Each of the 24 DALI loops are linked one to one with a rack circuit for power control. For example, DALI loop 1 is controlled by DRd rack dimmer 1, DALI loop 2 is controlled by DRd rack dimmer 2, etc.
To control DALI fluorescent ballasts, the rack circuit must be populated with a dimmer or relay module and assigned to DALI dimmer mode within the ACP software. Reference the related architectural control processor programming guide for instruction to change dimmer mode.
Note:
The DALI option kit is limited to 64 DALI compatible fluorescent ballasts per DALI loop. All DALI fluorescent ballasts connected to that loop will respond at the same time and to the same level as sent by the broadcast command.
A single DRd rack supports the use of either the DALI option kit or the FLO option kit, but not both in the same rack.
The DALI ballast is powered by an external DALI loop power supply (supplied by others). This supply is connected externally of the DRd rack. Each DALI loop requires its own power supply and possibly more than one power supply depending on the load.

Install the DALI Option Board

Step 1: Align the DALI option board to
the mounting studs in the bottom right side of the DRd rack.
• Notice the mounting holes on the DALI option board. One is a slotted keyhole, another is an open ended slot, and the remaining two on the other end of the board are standard mounting holes used to secure the board in place.
Step 2: Set the rear left stud through
the slotted keyhole and align the open ended slot with the back right side mounting stud.
Step 3: Gently slide the DALI board toward the right I/O board aligning the five prong
connector to the receptacle on the right I/O board.
Step 4: Secure the bottom two mounting studs with the screws provided.
Corporate Headquarters London, UK Rome, IT  Holzkirchen, DE Hong Kong  Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong  Tel +852 2799 1220  Fax +852 2799 9325 Service: Web: 7183M2210
 Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK  Tel +44 (0)20 8896 1000  Fax +44 (0)20 8896 2000
Via Pieve Torina, 48, 00156 Rome, Italy  Tel +39 (06) 32 111 683  Fax +44 (0) 20 8752 8486
 Ohmstrasse 3, 83607 Holzkirchen, Germany  Tel +49 (80 24) 47 00-0  Fax +49 (80 24) 47 00-3 00
(Americas) service@etcconnect.com
www.etcconnect.com
 Rev C  Released 2012-02  ETC intends this document to be provided in its entirety.
 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA  Tel +608 831 4116  Fax +608 836 1736
Copyright © 2012 ETC. All Rights Reserved.  Product information and specifications subject to change.
(UK) service@etceurope.com  (DE) techserv-hoki@etcconnect.com
(Asia) service@etcasia.com
Unison DALI Option Kit Setup Guide Page 1 of 2 Electronic Theatre Controls, Inc.
ETC Setup Guide
2008
Each of the four bus connectors on the option board provide termination for six DALI loops. Each bus connector is labeled for ease of loop identification and is pluggable for ease of wiring termination. Terminals accept 12-24 AWG (4 - .25mm
2
) Class
1 wire.

Connect DALI Option Wiring

*Maximum Run Lengths for Class 1 wiring
Unison® DALI Option Kit
18 AWG
2
1mm
16 AWG
1.3 mm
14 AWG
2
1.6 mm
2
12 AWG
2
2 mm
**Max.
aggregate run
length
feet meter feet meter feet meter feet meter feet meter
570 175 900 275 1,430 435 2,280 700 3000 900
*Maximum Run Length - the longest distance between any device and any power supply on the DALI bus. **Maximum Aggregate Run Length - the longest total length of all total wiring connected to the DALI bus.
It is important to label the DALI fluorescent ballast load and control wiring sets with the circuit designation. Control wires terminate on the associated DALI board output loop terminal.
Note:
For example: If circuit 1 is configured as a D20 in DALI dimmer mode, DALI fluorescent ballast control wiring should terminate to the DALI board loop output terminals labeled “1”.
Step 1: Remove the DALI bus connector for loop outputs 1-6. Step 2: Strip each wire in the pair back 1/4 inch (6mm). Step 3: Using a jewelers screwdriver, loosen the terminals and insert each wire into the data
Step 4: Tighten the terminal screw until the wire is held snugly. Step 5: Repeat steps 1 through 4 for the remaining DALI loops through loop 6. Step 6: Replace the DALI bus connector on the DALI board and repeat for the remaining
Note:
The associated output loop terminal number should always match the straight power circuit numbering label inside the rack, regardless of straight or balanced rack dimmer configuration.
“+” or data “-” terminals for the specific circuit loop. Data wires in the wire set are polarity independent.
DALI loops in the system (up to 24 loops).
DALI wiring can be run in the same conduit as the power wiring for the same ballast.
Unison DALI Option Kit Setup Guide Page 2 of 2 Electronic Theatre Controls, Inc.
Loading...