GENERAL INFORMATION
The Foundry Mini Panels offer up to eight zones of DMX controlled lighting with fully rated 20 Amp relays and optional 0-10V control per zone. The Mini Panel features a Demand Response input for energy saving integration and a UL924 emergency lighting control bypass with power loss sense. The Mini Panel is wall-mounted and plenum rated to be easily tucked out of sight.
APPLICATIONS
• Arena and stadium suites
• Office buildings
• Conference and meeting rooms
• Healthcare facilities
• Houses of worship
• Classrooms
• Hospitality and restaurants
• Retail
FEATURES
• Switched power control of four or eight circuits with 0-10V dimming
• 120 or 277VAC power input per zone
• 20 Amp fully rated relays for use with general purpose, tungsten, fluorescent, LED and plug loads
• 0-10V dimming output per zone for direct connection to dimming ballasts and LED drivers
• Demand Response load shedding contact input
• UL924 control bypass via
- Contact closure input
- Normal power loss sense feed terminals
• DMX controlled and RDM configurable
GENERAL
• UL, cUL and UL924 LISTED
• Rated for plenum installation
• Suitable for plug load control
ORDERING INFORMATION
Foundry Mini Panel
MODEL DESCRIPTION
UFMP4 4-zone DMX Mini Panel with four relays and four
0-10V dimming outputs
UFMP8 8-zone DMX Mini Panel with eight relays and
eight 0-10V dimming outputs
Note: Optional voltage divider available for use of mixed normal and emergency circuits in a single controller; where allowed by local code.
FOUNDRY FAMILY OF PRODUCTS
Foundry Distributed Product Series
MODEL DESCRIPTION
UFR2 Dual Zone DMX Relay
UFR2-LV Dual Zone DMX Relay with 0-10V
UFD 600W 120V DMX Dimmer
UFD-277 600W 277V DMX Dimmer
Foundry Mini Panel Product Series
MODEL DESCRIPTION
UFMP4 4 Zone Mini Panel
UFMP8 8 Zone Mini Panel
1 of 3
Unison Foundry Mini PanelsETC
Foundry Mini Panel Series
SPECIFICATIONS
FUNCTIONAL
• Control for up to eight zones of switching for lighting and plug loads
• Control for up to eight zones of 0-10V dimming for LED drivers and fluorescent ballasts
• UL924 emergency-lighting control via contact closure and power loss sense feed terminal
• Demand Response input provided by a power company can enforce a maximum level per circuit while active
• Supports USITT DMX512-A (ANSI E1.11)
• Supports RDM (ANSI E1.20)
MECHANICAL
• Constructed of 16-gauge cold-rolled steel, finished in fine-textured, black powder coat
• Wall-mount installation;
- rated for installation in plenum air space
• Class-1 voltage barrier prevents access to line-voltage wiring with front panel removed
• Optional voltage divider allows for separation of normal and emergency circuits in a single controller where allowed by local codes
ELECTRICAL
• 100-277V, 50/60Hz power input per circuit with support for pass thou to multiple circuits
• Supports 120V and 277V circuits within the same panel
• 20-Amp, fully-rated bi-state latching relay per output
• 0-10VDC control rated for up to 100mA sink per output
- 0-10V outputs are fully isolated from ground to 2500V RMS
• Rising clamp screw terminal wiring connections for:
- Line-voltage relay power input, output and pass-through with support for 14-8 AWG wire
- Low-voltage 0-10V dimming output per zone with support for 22-16 AWG wire
- Separate normal power sense feed input for UL924 emergency lighting bypass
- UL924 emergency lighting control contact closure input with support for 22-16 AWG wire
- Demand Response contact input with support for 22-16 AWG wire
• Demand Response input supports Normally Open (NO) operation
• UL924 contact closure input supports normally open (NO) or normally closed (NC) operation
• Onboard status indicators for controller power, DMX signal, Demand Response input, and UL924 emergency lighting control
• Slide switch configuration for:
- UL924 operation (NO/NC)
- UL924 inclusion per circuit (on/off)
• UL and cUL LISTED
- Conforms to UL508, UL2043, UL916 and UL924
DMX INPUT PORT
• Optically-isolated input from the Mini Panel electronics
• Withstands fault voltages of up to 250VAC
• Integrated DMX/RDM termination
CONFIGURATION
• Remote configuration available via RDM devices such as:
- ETC control console with RDM functionality
- ETC DMX/RDM gateway networked to a device running ETC Net3 Concert software
• Manual configuration of the starting DMX address, UL924 bypass, and Demand Response on the controller
THERMAL
• Ambient room temperature: 0 to 50°C
• Ambient humidity: 5 to 95% non-condensing