ETC ERP24-FT24, ERP24-FT12, ERP-FT-LVD Data Sheet

Unison Echo Relay Panel FeedthroughETC
Echo Power Control Series
ORDERING INFORMATION
Standard Model Numbers
MODEL DESCRIPTION
ERP24-FT Echo Relay Panel Feedthrough 24-way panel
without relays
ERP24-FT12 Echo Relay Panel Feedthrough 24-way panel
with 12 relays
ERP24-FT24 Echo Relay Panel Feedthrough 24-way panel
with 24 relays
ERP48-FT Echo Relay Panel Feedthrough 48-way panel
without relays
ERP48-FT48 Echo Relay Panel Feedthrough 48-way panel
with 48 – 20 A single pole Relays
ERP48-FT482P Echo Relay Panel Feedthrough 48-way panel
with 48 – 20 A 208 V double-pole relays
Note: Optional voltage divider available for use of both normal and emergency circuits in a single panel; where allowed by local code.
GENERAL INFORMATION
The Echo Relay Panel Feedthrough is a control-oriented switching and power control built with today and tomorrow’s lighting loads in mind. Echo Relay Panel adds ETC’s latest Echo Control package with support for 0–10 V control to our trusted conventional switching system. With built-in station, sensor, DMX and TimeClock controls and Ethernet connectivity, plus optional 0–10 V dimming, DALI output and contact inputs, the Echo Relay Panel Feedthrough integration opportunities are limitless.
APPLICATIONS
• Houses of worship
• Ballrooms and convention centers
• Multi-purpose rooms
• Arenas and stadiums
• Entertainment facilities with DMX control
• Retrofits for lighting systems with existing breaker panels
FEATURES
• 120–277 V single-pole and 208 V or 480 V double-pole switching
• Up to 48 relays per panel
• Switches all relays at once or with configurable delay
• Mechanically latching relays fully rated to 20 A
• Manual ON/OFF override with position indication
• Relays support field installation and replacement
• Echo, sACN, DMX-512, TimeClock, or stand-alone control
• Built-in EchoConnect power supply for up to 6 Echo stations/ sensors and 5 output products
• Built-in network interface provides:
- Advanced control of relays over streaming ACN (sACN)
- Web UI for configuration
• Local control with Astronomical timeclock and manual override per circuit
• UL924 LISTED emergency control bypass contact input
- Voltage barrier for normal/emergency mixed use panels
• cULus LISTED
Custom Build Model Numbering
MODEL QTY SINGLE
POLE 120V/277V
ERP-FT #1P / #2P / #480
Note: Panels support up to 24 or 48 relays. All relays utilize a single position, except 2P 480 V relays which utilize two positions
Examples: ERP-FT-241P/242P – Twenty-four 20A single-pole 120/277 V relays and twenty-four 20 A double-pole 208 V relays and zero double-pole 480 V relays
ERP-FT-241P/122P/6480 – Twenty-four 20 A single-pole 120/277 V relays and twelve 20 A double-pole 208 V relays and six double-pole 480 V relays
/ QTY DOUBLE
POLE 208V
/ QTY DOUBLE
POLE 480V
Echo Power Requirements
EchoConnect: 1 Unit of Output Power
Auxiliary Power: Not Required
Built-in EchoConnect Power Supply
EchoConnect: Provides 6U of control power and
an additional 5U of Output Power*
Auxiliary Power: Not Provided
*Note: Built in power supply can be disabled.
Echo Presets
Supports 64 Echo Presets per space; up to 16 Echo spaces
For more information, download the Echo Quick Guide
1 of 4
Unison Echo Relay Panel FeedthroughETC
Echo Power Control Series
SPECIFICATIONS
REGULATORY AND COMPLIANCE
• Underwriters Laboratories tested and listed to the following standards:
- UL508 Listed (File: E92154)
- UL924 Listed (File: E242514)
• Complies with ANSI E1.11 DMX512-A standard
• Complies with ANSI E1.31 streaming ACN standard
USER INTERFACE
• Graphical display with LED backlight
• Button interface with:
- 0-9 number buttons
- Up, down, back and enter navigation buttons
- “Light bulb” test button for local activation of preset, sequence and set level overrides
• USB interface for upload of setup and software updates
• Onboard Web UI for simple configuration
MECHANICAL
• Panel consists of enclosure, covers with locking doors, and internal subpanels
• Enclosure constructed of 16-gauge steel finished in black, fine-textured, scratch-resistant powder coat paint
• Removable conduit panels on top, bottom and sides
• Full front access with no side clearance required
• Removable covers for access to Class 1 and Class 2 wiring
• Locking doors allow controlled access to manual override switch of each relay and Class 2 wiring only
• All low-voltage wiring is physically separated from AC by a mechanical barrier
• Removable subpanels containing the electronics and relays can ship separately – contact ETC
ELECTRICAL
• Discrete feed per circuit supports mixed voltage in a single panel
• Single panel for up to 48 relays, populated in any combination of single- or double-pole
• Separate wiring chambers for Class 1 and Class 2 terminations
• Optional voltage barriers install without tools between relays for separation of normal and emergency circuits
CONTROL ELECTRONICS
• Input: 120–277 V (+/-15%), 50/60 Hz, <16 A
• Multi-tap transformer terminals accept up to 12AWG wire
• Control wiring terminations accessible via flip down door
- Control terminals accept maximum of 12AWG wire
- Control wiring exiting the panel are Class 2
- All control terminations utilize removable connectors
• Relay modes: Normal (priority/HTP), latch-lock or last-action
• Configurable DMX on/off threshold
• Built-in Echo control supports:
- Up to sixteen spaces with 64 presets per space configurable via local UI or Echo Inspire control stations
· Presets 1-16 can be configured remotely via Echo Access or integrated Web UI
- One 16-step sequence per space
- UL924 LISTED emergency control bypass
- Time-of-day and astronomical timeclock with flick-warn and holiday overrides
• Configurable data-loss behavior supports:
- Play preset; Hold last look; Wait and fade
SPECIFICATIONS
RELAY RATINGS
• 20 A 300 V General Purpose
• 20 A 300 V Ballast (HID)
• 20 A Tungsten
• Motor Loads:
- 0.5 HP @ 120 V
- 1.5 HP @ 240/277 V
• SCCR: 18,000 A @ 277 V (1P); 5,000 A @ 277 V (2P & 480)
• Inrush: 2000 A (1P only)
• Isolation: 2,500 V RMS
• State: Latching
• Relays are mechanically held
• Life: 60,000 cycles at full load
• Terminal: Accepts 14-10AWG copper wire
ENVIRONMENTAL
• Thermal: 0°–40° C operating temperature
- 10 A relay - 20 BTU/hr (estimated)
- 15 A relay - 40 BTU/hr (estimated)
- 20 A relay - 60 BTU/hr (estimated)
• Humidity 10–90% (non-condensing)
ECHO RELAY PANEL ACCESSORIES
Echo Relay Panel Accessories
ERP-FT-1PRK 120–277 V Single-Pole, Single-Space Relay Kit
ERP-FT-2PRK 208 V / 240V Double-Pole, Single-Space Relay
Kit
ERP-FT-2P480RK 480 V Double-Pole, Double-Space Relay Kit
ERP-FT-LVD 0–10 V Dimming Control Option
ERP-FT-DALI DALI-Control Option
ERP-FT-CI Contact-Input Option
ERP-FT-RTO Ride-Thru Option
ERP-FT-VB Voltage-Barrier Kit
ERP-FT-RMW 19” Rackmount Kit (15U)
ERP-FT-TPH Tamper-proof Hardware Kit with tool
0-10 Dimming Option
• 24 outputs of 0–10 V sink dimming control rated for 400 mA per output
Contact Input Option
• 24 dry contact inputs which can be used to:
- trigger presets and sequences, which will play at the priority configured for architectural sources, or;
- directly control one or more outputs. The priority of these outputs is configurable. If nothing is configured, the last action takes precedence
DALI Control Option
• 24 control loops of broadcast DALI control
• Each loop supports up to 64 ballasts
• External DALI power supply required
Ride Thru Option
• Short-term power backup of control electronics
• Automatically engages when power is lost
• Recharges during normal power operation
Tamper-proof Hardware Kit
• Special screw heads prevent access to panel interior
2 of 4