ETC ERMC4-G2 Data Sheet

®
Unison Echo® Room ControllerETC
Echo Distributed Power Series
GENERAL INFORMATION
The Echo Room Controller offers a full power and control solution for standalone and integrated room controls. With up to eight zones of relay switching with 0-10V control fully rated at 20 amps, the Echo Room Controller is the perfect solution for a single mid-sized room with stand-alone TimeClock and sensor control. The controller can also be used for full room integration utilizing an integral station power supply, contact input, Demand Response input and UL924 emergency bypass. The controller can be wall-mounted or in an air plenum to be easily tucked out of sight.
APPLICATIONS
• Arena and Stadium suites
• Houses of worship
• Education
• Hospitality
• Healthcare facilities
• Office buildings
• Conference rooms
• Meeting rooms
• Retail
FEATURES
• Four- and eight-output options patchable to zones in multiple spaces
• A 20A fully rated relays for use with general purpose, tungsten, fluorescent, LED and plug loads
• Fully isolated 0-10V dimming for direct connection to dimming ballasts and LED drivers
• 120 or 277VAC power input per zone
• A/V integration via single contact input
• Demand Response load shedding
• Supports Unison Echo control stations, responsive controls and interfaces
• EchoConnect
- 6 Echo control products and 5 additional Echo output products (built-in station power supply)
- Up to 16 Echo control products and 15 additional Echo output products (via external station power supply)
- Up to 500 meters (1640 feet) of control wire per system
GENERAL
• UL, cUL and UL924 LISTED
• Rated for plenum installation
®
topology free station bus with support for:
ORDERING INFORMATION
Room Controller
MODEL DESCRIPTION
and four 0-10V dimming outputs
ERMC4-TC-G2 Echo 4-zone Room Controller with four relays,
four 0-10V dimming outputs and TimeClock
ERMC8-G2 Echo 8-zone Room Controller with eight relays
and eight 0-10V dimming outputs
ERMC8-TC-G2 Echo 8-zone Room Controller with eight relays,
eight 0-10V dimming outputs and TimeClock
Note: Optional voltage divider available for use of mixed normal and emergency circuits in a single controller; where allowed by local code.
Echo Power Requirements
EchoConnect: 1 Unit of Output Power
Auxiliary Power: Not Required
Built-in EchoConnect Power Supply
EchoConnect: Provides 6U of control power and
an additional 5U of Output Power*
Auxiliary Power: Provides 40mA for TimeClock power
*Note: Built in power supply can be disabled when used with external 16U EchoConnect Power Supply or when multiple room controllers are used in a single
system
Echo Presets
Supports 16 Echo Presets
1 of 4
Unison Echo Room ControllerETC
Echo Distributed Power Series
SPECIFICATIONS
FUNCTIONAL
• Control for up to eight zones of relay control for lighting and plug loads
• Control for up to eight zones of fully isolated 0-10V dimming control for LED drivers and fluorescent ballasts
• Each pair of power and 0-10V outputs can be patched to a space and zone via the EchoAccess mobile app
• Contact Input responds to closure to place the lighting into a configurable, presentation-friendly preset, playback a lighting control sequence, trigger room combine, or any other Echo contact input function
• UL924 emergency-lighting control via contact closure or integrated normal sense feed
• Demand Response input sent from a power company can enforce a maximum level per circuit while active
- Demand Response commands can be transmitted to additional Echo devices via the EchoConnect bus
• Time-of-day, astronomical and calendar events for the installed room, and up to 15 additional rooms (TimeClock versions only)
• Plug and Play: ready to go out of the box, no software or external programming required
• Supports up to 6 Echo control products and 5 additional Echo output products with internal Echo Station Power Supply
• Supports up to 16 Echo control products and 15 additional Echo output products with external Echo Station Power Supply
MECHANICAL
• Constructed of 16-gauge cold-rolled steel, finished in fine-textured, black powder coat
• Supports wall-mount and plenum installation
• Rotary dials for selection of space and starting zone number
• Class one voltage barrier prevents access to line-voltage wiring with front panel removed
• Optional voltage divider allows for separation of normal and emergency circuits in a single controller where allowed by local codes
• Discrete-feed mains power input: 100-277V
- Supports pass-through of input to multiple circuits up to the full circuit capacity of the controller
ELECTRICAL
• 100-277V, 60Hz power input per circuit
• Supports 120V and 277V circuits within the same controller
• 20-amp, fully-rated bi-state latching relay per output
• 0-10VDC control rated for 100mA maximum sink per zone, fully isolated from ground
• Supports rising clamp screw terminal wiring connections for:
- Line-voltage relay power input, output and pass-through with support for 14-8AWG wire
- Controller power input and UL924 Sense circuit with support for 20-12AWG wire
- Low-voltage 0-10V dimming output with support for 22-16AWG wire
- Separate normal power sense feed input for UL924 emergency lighting bypass
- UL924 emergency lighting contact input (NO/NC) with support for 22-16AWG wire
- Contact Input (NO/NC) terminals with support for 22-16AWG wire
- Demand Response contact input (NO) with support for 22-16AWG wire
- EchoConnect control connection for Belden 8471 wire (or approved equal)
- 24V auxiliary power for integral timeclock with support for 22-16AWG wire
• Built-in EchoConnect station power supply with support for up to six control products and five external output products
• Onboard status indicators for station power , UL924 input, Contact Input, Demand Response, and Room Controller power
• Dip switch configuration for:
- Onboard EchoConnect Power Supply (on/off)
- Contact input type (NO/NC)
- UL924 sense feed active (on/off)
- UL924 input type (NO/NC)
- UL924 inclusion per circuit (on/off)
• MicroSD for field software upgrades
• UL and cUL LISTED
- Conforms to UL508, UL2043 and UL924
ECHOCONNECT STATION BUS
• Topology-free wiring using Belden 8471 or equivalent plus one #18 ESD drain wire
• Wiring may be bus, loop, homerun or any combination of these
• Up to 500 meters (1640 feet) of control wiring per system
• Optional Cat5/5e EchoConnect wiring supported using Belden 1583A or equivalent
- Requires optional Cat5 termination accessories
THERMAL
• Ambient room temperature: 0 to 45°C
• Ambient humidity: 5 to 95% non-condensing
2 of 5
Unison Echo Room ControllerETC
Echo Distributed Power Series
SPECIFICATIONS
DEFAULT CONTACT INPUT FUNCTIONALITY
• Basic Mode
- Inputs control Presets 1-4 (momentary)
- Close / Open event: Toggle Preset
- Contact held closed: Space Raise
- Contact closed in rapid succession: Quick Toggle Preset
• Custom Mode without EchoAccess Configuration
- Inputs control Presets 1-4 (maintained)
- Close/ Open event: Toggle Preset
CUSTOM MODE FUNCTIONALITY
(Requires Programing with EchoAccess
• Contact Input Interface (Momentary)
- Push: No Function, Preset Toggle, Preset Activate, Zone Toggle, Zone Lower, Zone Raise, Zone Set to Level, Space Off, Space Toggle,
Space Lower, Space Raise, Space Set to Level, Space Combine Toggle, Space Combine, Space Uncombine, Space Lockout Toggle, Sequence Toggle, Zone Set to Color, Space Set to Color
- Double Tap: No Function, Preset Toggle, Preset Activate, Zone Toggle, Zone Set to Level, Space Off, Space Toggle, Space Set to Level, Zone Set to Color, Space Set to Color
- Hold: No Function, Zone Lower, Zone Raise, Space Lower, Space Raise
• Contact Input Interface (Maintained)
- Maintained Open: No Function, Preset Activate, Zone Set to Level, Space Off, Space Set to Level, Space Combine, Space
Uncombine, Sequence Toggle, Zone Set to Color, Space Set to Color
- Maintained Closed: No Function, Preset Activate, Zone Set to Level, Space Off, Space Set to Level, Space Combine, Space Uncombine, Sequence Toggle, Zone Set to Color, Space Set to Color
• Contact Input Interface (Occupancy) - One per interface
- Occupancy: No Function, Preset Activate, Zone Set to Level, Space Set to Level
- Vacancy: No Function, Preset Activate, Zone Set to Level, Space Off, Space Set to Level
®
Mobile App and additional Echo hardware)
3 of 5
ECHO FAMILY OF PRODUCTS
Unison Echo Room ControllerETC
Echo Distributed Power Series
EchoConnect Power Supplies
MODEL DESCRIPTION
E-SPS 6U Room Station Power Supply, Knockout Mount
E-SPS-DIN 16U DIN rail Station Power Supply with 24V Aux
E-SPM 16U DRd Station Power Module
E-SPM-A 16U DRd Station Power Module with 24V Aux
E-SPM-RM 16U Rack-Mount Station Power Module Aux
E-SPM-RM-A 16U Rack-Mount Station Power Module 24V Aux
E-SPM-WM 16U Wall-Mount Station Power Module
E-SPM-WM-A 16U Wall-Mount Station Power Module 24V Aux
E-APS 24V Aux Power Supply, Knockout Mount
EchoTouch
MODEL DESCRIPTION
ETS EchoTouch Controller
Echo Stations
MODEL DESCRIPTION
E1001 Inspire One Button Station
E1002 Inspire Two Button Station
E1004 Inspire Four Button Station
E1006 Inspire Six Button Station
E1008 Inspire Eight Button Station
E1104 Inspire Four Button with Fader Station
EPS05 Echo Preset Station - 5 Button
EPS10 Echo Preset Station - 10 Button
EPSLO Echo Lockout Station
E-ATC Echo TimeClock
Echo Interfaces
MODEL DESCRIPTION
EACC EchoAccess Interface
EEB Echo Expansion Bridge
EDMXC Echo DMX Scene Controller
EEI Echo-Echofl ex Interface
ECII Echo Contact Input Interface
ECOI Echo Contact Output Interface
EDRI Echo Demand Response Interface
EBI Echo BACnet Interface
Zone Controllers
MODEL DESCRIPTION
ERC-G2 One Zone Relay Controller
EDRC-G2 Two Zone Relay Controller
ELD-G2 One Zone 0-10V Controller
EDLD-G2 Two Zone 0-10V Controller
ESSC-G2 One Zone SmartSpace Controller
EDSSC-G2 Two Zone SmartSpace Controller
ELVD-G2 600-Watt Phase Adaptive Dimmer
ELVD-277-G2 600-Watt Phase Adaptive Dimmer- 277V
Room Controllers
MODEL DESCRIPTION
ERMC4-G2 Four Zone Room Controller
ERMCT4-G2 Four Zone Room Controller with TimeClock
ERMC8-G2 Eight Zone Room Controller
ERMCT8-G2 Eight Zone Room Controller with TimeClock
Echo Responsive Controls
MODEL DESCRIPTION
ELS Light Sensor
EOCC Ceiling-Mount PIR Occupancy Sensor
EVAC Ceiling-Mount PIR Vacancy Sensor
E-DOC-C Ceiling-Mount Dual Tech Occupancy Sensor
E-DVAC-C Ceiling-Mount Dual Tech Vacancy Sensor
E-DOC-W Wall-Mount Dual Tech Occupancy Sensor
E-DVAC-W Wall-Mount Dual Tech Vacancy Sensor
E-DOC-SM1 Switch-Mount Dual Tech Sensor - One Button
E-DOC-SM2 Switch-Mount Dual Tech Sensor - Two Button
Panel Products
MODEL DESCRIPTION
ERP Echo Relay Panel Mains Feed
ERP-FT Echo Relay Panel Feed Through
SensorIQ Sensor IQ Intelligent Breaker System
SR3 Sensor3 Power Control System
DRd Unison DRd with Echo Control
4 of 5
12.00”
0.06”
3.00”
10.00”
12.00”
0.06”
3.00”
10.00”
PHYSICAL
Unison Echo Room ControllerETC
Echo Distributed Power Series
Echo Room Controller Dimensions
MODEL HEIGHT WIDTH DEPTH
inches mm inches mm inches mm
ERMC4-G2/ ERMC4-TC-G2
ERMC8-G2/ ERMC8-TC-G2
9.0 229 12 301 3 76
14.0 356 12 301 3 76
ERMC4-G2 AND ERMC4-TC-G2
301mm
9.00”
229mm
1.7mm
Echo Room Controller Weights
MODEL WEIGHT
lbs kgs
ERMC4-G2/ ERMC4-TC-G2
ERMC8-G2/ ERMC8-TC-G2
76mm
7.00”
178mm
MOUNTING REFERENCE
6 2.72
9 4.08
MOUNTING REFERENCE
254mm
301mm
ERMC8-G2 AND ERMC8-TC-G2
1.7mm
14.00”
356mm
Corporate Headquarters n 3031 Pleasant View Rd, PO Box 620979, Middleton WI 53562 0979 USA n +1 608 831 4116 London, UK n Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK n +44 (0) 20 8896 1000 Rome, IT n Via Bruno Pontecorvo 10, 00012 Guidonia Montecelio, Roma, Italy n +39 06 32 111 683` Holzkirchen, DE n Ohmstrasse 3, 83607 Holzkirchen, Germany n +49 (80 24) 47 00-0 Hong Kong n Room 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong n +852 2799 1220 Web n etcconnect.com n Copyright©2018 ETC. All Rights Reserved. All product information and specifications subject to change. 7187L1005 Rev H 04/18
5 of 5
76mm
12.00”
301mm
MOUNTING REFERENCE
254mm
MOUNTING REFERENCE
Loading...