Exchange cabinet BDV BS 101 01 is designed to be
furnished with Printed Board Assemblies (hereafter =
boards or PBAs) belonging to ERICSSON’s PBXsystem ASB 150 02. System functions, desired by the
customer, are realised with appropriate boards and
system programming.
The PBX is powered by an internally mounted power
supply that is available in two versions. The standard
version is an AC/DC converter and the version with
battery charger offers the same facility but additionally
provides battery back-up or can be supplied from an
external DC-source.
The installed PBX shall be made operational in
accordance with the stipulations that apply for system
ASB 150 02. See document START OF OPERATION
(1537-ASB 150 02).
NOTE:Boards may only be inserted or re-
moved from the cabinet when the power
supply in the cabinet is switched off.
The new cabinet is adapted for boards with brackets
containing screws to provide a ground connection and
should only be equipped with these boards.These
screws must always be fastened to ensure proper operation.
Each branch on the extension line must have:
1A protective resistor of 10 Ω/1W
(REN 195 42/1) connected in series
between cabinet and MDF
2An overvoltage arrester (gas discharge
tube) for quenching surges to protective
ground shouldbe installed onthe network
side of the protective resistor.
MDF
Overvoltage arresters
Protective
resistors 10 Ω/1W
(REN 195 42/1)
Protective
ground
(NGC 402 01)
Housed in:
overvoltage protection
cassette (769 027/3)
Note: Make sure the MDF is really connected
to protective ground.
Principal circuit drawing.
Don’t use older board revision states in the new
cabinet.
In principle, a cabinet’s board position can be used for
arbitrary furnishing with boards belonging to PBX
system ASB150 02 butthefirst position isreserved for
the CPU-D_.
Due to the limited load of the cabinet’s power supply
units, the definitive board configuration in a cabinet
must follow the prerequisites in section 6.3.
However, it isadvisable to protect trunk lines withextra
overvoltage protectors especially in geographical
areas highly exposed to lightning.
Any lines connected to the PBX that are subjected to
excess voltage (transients) in conjunction with e.g.
lightning discharges must be equipped with excess
voltage protection.
Special considerations must be taken to analogue
extension lines that are placed outdoors. In order to
prevent the analogue extension boards secondary
protection device from blowing in case of lightning.
1.1Supplementary documents
•Document collection EN/LZB 103 1233
•INSTALLATION INSTRUCTION
(1531-BML BS 101 01) for the power supply,
equipped with battery charger
1.2Tools
In addition tocustomaryinstallation tools, the following
are recommended:
•Use theappropriate connectiontool 769027/2 to
connect the cables in the internal MDF.
•Use the appropriate slotting tool LSY138 252 to
connect the cables to the external
MDF SXK 106 4139/1.
•Board extractor for PBAs (handle LTD 117 02
and bottom LTD 117 12)
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
2DECLARATION OF CONFORMITY
5(46)
This page is left blank for the CE-document. Use the link to read the document.
Prepared
Doc respons/ApprovedChecked
Subject responsible
INSTALLATION INSTRUCTION
Documentnumber
1531-BDV BS 101 01 Uen
Date
Rev
Reference
1998-05-29L
6(46)
This page is left blank for the CE-document. Use the link to read the document.
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
7(46)
3HOW TO OPEN THE
CABINET
Unpack the exchange cabinet.
Using ascrew driverliftthe bluelid. Unscrew thescrew
below and remove the cabinets front cover. Check that
everything hasbeen received accordingto the delivery
note and that nothing has been damaged during the
transport.
businessphone
4INSTALLATION
The PBX can be delivered as a customer configured
unit or the add-in boards are delivered separately. The
cabinet is always equipped with a power supply,
suitable for the local mains. Please check the label
stating the permitted mains voltage. The cabinet is to
be mounted on an indoor wall. A mains outlet must be
provided near the equipment and shall be easily
accessible. The premises shall comply with the
following prerequisites:
•The air shall be free from dust and smoke
•Environmental conditions according to
ETS 300 019 (1-4) (Temperature shall be
between + 5°C and +40°C and relative humidity
may vary between 15% and 80%)
•The PBX shall not be exposed to direct sunlight
•The cable shall preferablyrun into the PBX from
below the cabinet to ensure sufficient air flow.
4.1Mounting of the cabinet
2
1
Lift blue lid to access the screw below.
2
Then turn the screw to loosen the cabinet
1
cover and take off the cabinet cover.
Use the enclosed drilling plan and drill four 8 mm
holes. Mountthe cabinet byusingthe enclosed screws
and plugs. Take into consideration the normal working
height above the floor (about 1.30 m to thelower edge
of the cabinet) and leave enough room for access on
both sides of the cabinet.
Overall dimensions of the cabinet:
•485 x 600 x 134 (H x W x D in mm).
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
4.2Safety and EMC
8(46)
To fulfil electrical safety requirements IEC 950 and
EN 60950 respectively EN 41003, the exchange must
be connected toprotective earth via a flexible wire with
a cross sectional area of at least 6 mm2.
Local requirements shall be adhered to.
The connection must be carried out by authorised
personnel.
A
B
BATT.
Shelf
cover
SWIVELSHELF
Turn
out
PSU
MDF
A
Connection
for protective
earth
cross sectional area >6 mm
2
Wrist strap
connector
(only for
AUSTRIA)
Front edge
168
Label
SVB BS 101 02/_
Note: The mains current rating stated on the label
is the maximum current of the charger version.
Bottom view of cabinet BDV BS 101 01
All line interfaces in the PBX are protected in
accordance with K.21 (voltage transients up to 1.5kV).
BTU-A, BTU-A2, BTU-B, BTU-C, BTU-D and BTU-E
are working with interface TNV.
All other boards and the V.24 port work with interface
SELV.
4.2.1EMC
The ferrites, with the ERICSSON ordering number
STF 82 601, should be situatedclose to the slot where
the cablesare led outof the cabinet.Twoturnsthrough
the ferrite core are sufficient to comply with EN 55022
Class B and to avoid disturbances in non-industrial,
residential (home) usage.
snap-on
wrist strap
connector
Protective earth
Before operating,ensure that the chassis isconnected
to a hard wired protective earth.
4.3Access to the boards
NOTE:
Turn out the transport screws (A)about 1 cm at thetop
and bottom of the swivel shelf. See figure in section
4.2. Hold the bottom of the shelf, lift the shelf slightly
and turn the swivel shelf counter clockwise(ccw). Turn
the screw (B) two turns at the top of the shelf cover
and remove the cover.
Makesure thatasound groundconnection to
the exchange has been established. Otherwise this can be hazardous in case of lightning. Use a grounding wrist strap when
handling PBAs sensitive to electrostatic discharges.
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
9(46)
5POWER SUPPLY UNIT
The power supply units (PSU) for the cabinet are
AC/DCswitching powersupplieswith two inputvoltage
ranges. Please check if the label states the proper
mains voltage as required. For mains supplies with
230V to 250V AC, two versions are available:
•BML BS 101 02/1 (PSU 230V standard)
•BML BS 101 01/1 (PSU 230V equipped with
battery charger).
Formainssupplies with 115V to127V AC twoversions
are available:
•BML BS 101 02/2 (PSU 115V standard)
•BML BS 101 01/2 (PSU 115V equipped with
battery charger).
The PSUs deliver 25 W on the PBA supply voltages
and 80 W on the 48 V supply voltage. After switching
on, the power supply has a start-up delay of 8
seconds.
Warning: The power switch does not disconnect
from mains. The mains cord must be unplugged to
disconnect the mains.
The PSU is equipped with a mains fuse rated
5.1Replacement of the power
supply unit
The cabinet is delivered with a PSU already installed.
The procedure how to dismount the unit is described
below.
aSwitch off the PSU (A) and unplug the mains
from the wall outlet. If the unit is a PSU with
battery charger, disconnecttheDC supplyline to
the batteriesand plugoff the alarmconnector on
the unit.
bDisconnect the DC supply cord (D) to the swivel
shelf.
cUnscrew the transport screw(B) completely and
make 3 turns on screw (C) counter clock wise.
dPush the PSU from the bottom and turn out the
PSU clock wise, unhinge and take it out. Then
pull off the mains plug at the bottom of the PSU
and disconnect the ground wire.
eInstall the PSU in the reverse manner.
When installing a power supply unit with battery
charger and battery backup please refer to the
INSTALLATION INSTRUCTION
(1531-BML BS 101 01).
250VAC 6,3 A T.
NOTE: This fuse NGH 243 01/6300 can be ordered
from Ericsson but is a non-accessible and non-user
serviceable part. Only authorised personnel isallowed to change the fuse. Contact the local
supplier in this matter.
Battery backup time
The batteries in the integrated battery pack have a
capacity of 2Ah. The power consumption on the 48 V
should be less than 1.7A. Using fresh batteries a
backup time of 20 minutes is guaranteed and
depending on the system configuration longer backup
times could be achieved.
(D)
Power switch
does not
disconnect
unit from
mains.
Standby only
Ground
(A)
(B)
Label
(C)
Mains power cord plug
IEC 320 C17
Prepared
Subject responsible
INSTALLATION INSTRUCTION
Documentnumber
10(46)
1531-BDV BS 101 01 Uen
Doc respons/ApprovedChecked
Date
Rev
Reference
1998-05-29L
5.2Power feeding with an external DC supply
When the PBX is supplied with power by an external battery with 48V nom. (44 - 56V), the installation of a power
supply equipped with a battery charger (BML BS 101 01/_) is required. The DC supply is connected directly to the
PSU.
An externally accessible fuse 250VAC 6,3 A T isprovided on the PSU,but additionally a fuse must be installed in the
supply line with DC current switching capability greater than 160 A.
Note: To prevent arcing never connect the DC source when the PSU has not started-up.
Use the mains to power up or use an external switch to connect the DC source. This is a precaution to minimise the
contact loads on the plug.
For further details see INSTALLATION INSTRUCTION (1531-BML BS 101 01).
Battery operation often requires different preconditions consequently, only an overview can be provided with regard
to battery capacity/charging capacity. The batteries should be supplied locally. The type is described in detail in
INSTALLATION INSTRUCTION (1531-BML BS 101 01).
6ALLOCATION
In principle, all board positions in cabinet BDV BS 101 01 can be used for arbitrary configurations with PBAs
belonging to PBX-system ASB 150 02.
The boards are equipped with ground brackets on the top and bottom. When installing make sure to fasten the
boards with the supplied screws.
There arerecommendations for configurationsin order to simplifyoperation and maintenance.For further information
see document collection EN/LZB 103 1233.
Sub-equipped boards:
Install sub-equipped boards in the last position after the standard boards to enable easy upgrading without having to
re-number trunks and extensions.
6.1Power supervision of ELU-A
The board is equipped with an automatic traffic limiter restricting the internal power dissipation on the board to a
maximum of 12W. This depends on both the line length and the number of lines busy.
When the power consumption exceeds the limit, no more lines have access for use and at least two lines have to go
on hook for all lines to work normally again.
When connecting external voice systems a maximum of 8 lines are recommended on each board. The remaining
lines on the board are to be connected to low-traffic extensions.
Prepared
Subject responsible
INSTALLATION INSTRUCTION
Documentnumber
11(46)
1531-BDV BS 101 01 Uen
Doc respons/ApprovedChecked
Date
Rev
Reference
1998-05-29L
6.2Connection of CM-Boards
Connect the correct type of call metering board, according to the figure below, on BTU-A board ROF 157 5110/_ or
ROF 157 5127/_ and in the same fashion on the BTU-C board ROF 157 5111/_. The BTU-C cannot be equipped
with a CM50 board as the flat ribbon cable cannot be connected and CM12/16 (ROA 219 5135/1).
Line 0 - 1
CMboard
Line 2 - 3
Note: When installing a CM50-board connect the
cable before mounting the CM50-board. The
BTU-A board must also be connected to
Line 4 - 5
earth.
The following boards are available CM50 ROA 219 5064/1, with flat ribbon cable and CM12/16 ROA 219 5135/1 or
ROA 219 5062/1 without cable.
6.3System Power Consumption
The power demand of the system comprises the sum of the current demands of all extensions, base stations etc.
This total current hastobe delivered by the power supply. Choose the one delivering therated current with a suitable
margin for add on equipment depending on the installation site.
Base Station Power Demand
To minimise the power dissipation on the serial communication wires EPP should be used extensively. Up to 60 BS
can be installed in a cabinet. Short power peaks can be covered by installing a battery cabinet.
The total current for all BS must be less than the power supply(s) capacity. The total 48 VDC load on the power supply has to be calculated as follows:
Cable
length
0m
100m
200m
300m
400m
500m
600m
700m
800m
900m
1,0km
1,1km
1,2km
1,3km
1,4km
1,5km
1,6km
STD EPP
0,5 mm
104
104
110
106
114
110
112
121
115
129
119
121
125
129
133
139
146
152
160
171
183
204
∅
STDEPP
0,6 mm ∅
104
104
108
106
110
108
114
109
118
110
112
114
117
118
121
123
125
127
129
131
135
137
STDEPP
0,5 mm
77
104
83
106
87
110112
94
115
103
119121125
129133
139146152160
171183204
∅
STDEPP0,6 mm∅
104
104
108
106
110
108
114
109
118
110112
114117
118121
123125127129
131135137
This table states the current demand in mA for a Base Station depending on the cable length and cable diameter.
Calculation example:
Line length to Base Station:
Resistance of loop:
Cable diameter (
φ):
200m
0.18 Ω/m
0,6 mm
Assuming 4 Base Stations are already
connected they consume a current of:
440 mA
Power demand taken from Power Calculations below, for telephones:
984 mA
Total load on power supply:1424 mA
This total load for the exchange can be
suppliedby thepowersupply asitis less
than 1.7A.
Prepared
Doc respons/ApprovedChecked
Subject responsible
Extension Power Demand
INSTALLATION INSTRUCTION
Documentnumber
1531-BDV BS 101 01 Uen
Date
Rev
Reference
1998-05-29L
12(46)
TELEPHONES
BASIC
ECONOMY
ECONOMY
plus
STANDARD
EXECUTIVE
DBC 213 with 2 DBY 409 01
DBC 213 with 4 DBY 409 02*)
1
) provides current on trunk lines in active state to public exchange.
CURRENT CONSUMPTION
Typ (mA)Max (mA)
DBC 210
DBC 199
DBC 601
DBC 751
DBC 211
DBC 201
DBC 212
DBC 202
DBC 631
DBC 755
DBC 752
DBC 213
DBC 203
DBC 662
DBC 753
14
25
27
38
14
30
14
30
65
50
50
35
35
70
75
42
3570
35
35
32
35
50
35
50
70
73
73
70
70
73
70
TELEPHONES
OPERATOR
CONSOLE
DBC 214 with 2 DBY 409 01
DBC 214 with 4 DBY 409 02*)
ANALOGUE
(in active state)
TAU 2610
Desktop Adapter
BTU-B (S-interface
per physical link)
BTU-C
index (/1,/2)1)
Radio base station:
CURRENT CONSUMPTION
Typ (mA)Max (mA)
DBC 214
DBC 663
DBC 754
40
67
75
35
35
40
4
(per trunk)
refer to table above
14
50
120
110
70
70
4
23
50
35
The maximum values for telephones result when all LEDs are lit and if available, loudspeaking is on at max. volume.
*) with connected external power supply.
Power calculation example
LINE
EQUIPMENT
QUANTITY
DBC 210354
DBC 2015150
DBC 20213390
DBC 20310350
CURRENT
(mA)
Calculation example:
selected
line equipment
3 x DBC 210
5 x DBC 201
13 x DBC 202
10 x DBC 203
1 x DBC 663
Total: 32 system telephones
DBC 214140
TOTAL32984
The calculation above shows howto calculate the current demand fora given installation. This amount of currenthas
to be supplied by the installed power supply.
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
13(46)
6.4BTU-A (ROF 157 5110/-) and
BTU-A2 (ROF 157 5120/_)
On delivery from the factory both contacts are in the OFF
position, and the line is a normal trunk.
When both contacts on a DIP-switch are set to position
ON, the line is to be regarded as a music source input.
Different contact positions are not allowed.
Note: Only lines4-7canbeused as a music source
input. Not available on BTU-A subequipped ROF
157 5127/_.
.
The DIP-switch is shown
with both contacts in
OFF position
ON
1 2
86
85
Line 4
Line 5
Line 6
6.5Power failure circuit (PFC)
In the event of mains failure and if no battery back up
is available for the PBX, there are normally 2 lines on
the BTU-A and BTU-C (see under BTU-C on next
page) board which automatically switch the trunk lines
to analogue telephones connected to this board.
On power failure, these telephones will automatically
be connected to the public exchange.
It is also possible to use the power failure telephones
during normal operation, if an ELU-A board is installed.
BTU-A & BTU-C1
bPFb
ELUA
a
PFa
Power failure set
La
Trunk
Lb
BTC
Indicator
87
88
Line 7
Connection field 6
C
LA0
LB0
LA2
LB2
LA4
LB4
LA6
LB6
*)
A
18
20
22
24
26
28
30
32
LA1
LB1
LA3
LB3
LA5
LB5
LA7
LB7
Line wires for
connection to
Public Exchange
*)
Not available on sub-equipped board see below
Relay shown in power fail position
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
14(46)
Connection field 4
Not always mounted
(market-dependent)
18
PFa0
4
PFb0
PFa1
PFb1
20
22
24
18
20
22
24
Connection
to analogue
telephone(s)
PFa2
PFb2
PFa3
PFb3
A
26
28
30
32
A
C
analogue telephone
a0
Connection to
ELU-A board
b0
a1
b1
On the BTU-A2 the
bottom half of this
connector is used
to connect to PTT
signalling ground
Connection to
ELU-A board
C
Connection of
a0
Only mounted if the BTU-A
has 4 PFC circuits (market
b0
dependent).
This connector is used
a1
for PFC circuits on the
BTU-A2
b1
6.6BTU-C (ROF 157 5111/-)
Connection field 4 and 6
RED
YELLOW
GREEN
The index number
refers to the individual
on the board
power failure (field 4)
PFa0
PFb0
A C
a0
b0
trunk lines (field 6)
La_0
Lb_0
La_2
Lb_2
La_4
Lb_4
La_6
Lb_6
A C
La_1
Lb_1
La_3
Lb_3
La_5
Lb_5
La_7
Lb_7
Earth connection on BTU-A2 (Austria only)
Some markets require an earth connection of the incoming PTT earth (functional earth) to the exchange.
This is provided on the connector installed above the
PFC circuit connectoron pins A22, A24, C22and C24.
Use an extra Krone bar toconnect the PTT earth wires
to the wires going to the board connector.
The BTU-C (ROF 1575 111/1)features eight incoming
trunk lines with DID. The first four individuals can also
be used for outgoing traffic.
BTU-A & BTU-C1
BTC
PFa
Power failure set
bPFb
ELUA
a
La
Trunk
Lb
Indicator
Relay shown in power fail position
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
15(46)
6.7BTU-B (ROF 157 5121/_)
Applies for indices 1 and 3
The BTU-B provides connection for up to 8 physical
links and every physicallink can be configured as a Sor T-interface. On the S-interface every link provides
remote power feeding with 40V/50 mA = 2W and connection for up to 8 terminals.
A
B
C
ON
D
418
6.8BTU-B2 (ROF 157 5121/_)
Applies for indices 4 and 5
418
A
B
410411
ON
ON
ON
ON
Insert PROM "RYS 102 521/ 1
A
Insert PROM "RYS 102 521/ 2
B
Insert PROM "RYS 102 521/ 3
C
Insert PROM "RYS 102 521/4
D
ON
ON
ON
ON
410411
412413
414415
416417
412413
414415
416417
Insert PROM "RYS 102 521/ 3
A
Insert PROM "RYS 102 521/ 4
B
DIP-switches position 410-417
These switches control S- and T-interface termination
and S-interface power feeding on the link 0...7.
On factory delivery all
switches are set to OFF
4
Connects power feeding ground
3
Connects -40V for power feeding
21
Connects 100 Ω receive side termination
ON
Connects 100 Ω send side termination
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
16(46)
Note: at the end of each line a termination resistor
must be installed (e.g. in the last wall outlet).
The switch 1 selects the termination on the transmitter
interface and switch 2 selects the termination on the
receiver interface. Switches 3 and 4 enable remote
power feeding to ISDN terminals connected to a link.
When connected as S-interface switches 1...4 should
be set to ON.
Settings of the S-interface relevant on
board indices -3,-4,-5
DIP-switch position 418
When selecting which link is to be configured
as a S-/Q-/T-interfaces start with switch:
Line pairs:
Q/T-interface
OFF... Q/T-Interface
ON ...S-Interface
ON
4
3
21
0 + 1
2 + 3
4 + 5
6 + 7
S-interface
On factory delivery all switches are set to OFF
Note: When selecting S- or T-interfaces start by
setting the T-interfaces using switches 4, 3, 2
and 1 in consecutive order then set the Sinterfaces starting with switches 1, 2, 3 and 4.
Settings of the S-interface
Choose with RASC the configuration of the interface:
Extended passive busdefault setting
and Short passive bus.
Ranges on the interface
The BTU-B is equipped with the S/T Bus Interface Circuit eXtended (SBCX). This circuit offers the advantage of covering a higher attenuation on cables.
(refer to documentation of the TE) is also equipped
with a SBCX or equivalent.
1 km (standard range)
TE TE
TE TE TE
Ranges on the extended passive bus
TE
and up to 2 km with
TEs equipped with SBCX
TE
up to 500 m (standard range)
and up to 1.5 km with
TEs equipped with SBCX
SBCX
SBCX
BTU-B
Short passive bus
d1
TE
d4
TETE
d3
BTU-B
d4 - up to 1m
with TR
in outlet
d1 - 150m to 250m (standard range)
d3 - line to terminal up to 10m
Extended passive bus
d1
d2
TE
d4
TE
BTU-B
d3
25 to 50 meters
d4 - up to 1m
with TR
in outlet
TE
d1 - up to 500m (standard range),d2 - between terminals
1,5 km on 30 nF cables with
TEs equipped with SBCX
d3 - line to terminal up to 10m
Abbreviations:
TETerminal Equipment
TRTermination Resistor (
installed at the end of the
interface line. Use outlets with resistor mounted
Outlet according to IEC 603-7 with termination
Outlet according to IEC 603-7 without termina-
tion
)
The standard S/T-interface specification considers cableswith 6,5 dBattenuation equivalent toabout 1000m
cable length in single terminal configuration.
Using the S/T Bus Interface Circuit eXtended (SBCX)
up to13 dB line attenuationcanbe covered. The figure
below shows the ranges using standard 0.6 mm diameter twisted pair unshielded cables with a capacitive
load of max. 30nF per km and the terminal equipment
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
6.9BTU-D (ROF 157 5112/1) and
Connection field 6
A
T0A
T0B
T1A
T1B
T2A
T2B
T3A
T3B
T4A
T4B
T5A
T5B
T6A
T6B
T7A
T7B
C
02
04
06
08
10
12
14
16
18
20
22
24
26
28
30
32
R0A
R0B
R1A
R1B
R2A
R2B
R3A
R3B
R4A
R4B
R5A
R5B
R6A
R6B
R7A
R7B
The DIP-switch is
shown with
both contacts in
OFF position
S/T-Interface for
connecting trunks
and S-terminals
REG (ROF 157 5112/2)
A
B
ON
1 2
197
200
17(46)
Wall outlet connection
4
5
6
3
8
1
7
2
Wiring side of 8-pole
wall outlet e.g.
KRONE RJ-K LN
Pin desig-
nation
optional
1
EIA/TIA 568 Wiring Schemes
NT function:TE function:
(polarity of remote
Transmit (-)
5
4
Transmit (-)
Receive (+)
3
6
Receive (+)
1
Power sink 3 (+)
2
Power sink 3 (-)
7
Power source 2(-)
8
Power source 2(+)
S-interface in
socket
(polarity of remote
power feeding)power feeding)
Receive (-)
Receive (-)
Transmit (+)
Transmit (+)
Power source 3(+)
Power source 3(-)
Power sink 2(-)
Power sink 2(+)
T-interface on
plug
199
198
Insert PROM "RYS 102 5xx/1
A
Insert PROM "RYS 102 5xx/2
B
6.9.1DIP-switches in position 197 and 200
Depending on the firmware used, this board enables
either ISDN or CAS function. The PROM set is available for CAS (LZY203 2212/1) or ISDN PRA
(LZY203 2213/1). DIP-switch pos. 197 on BTU-D selects the register function of the board. The switch 200
is reserved for future use.
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
18(46)
197/1197/2FUNCTION
OFFOFF
ON
ONOFF
ON
digital trunk MFC
digital trunk MFE
Register MFC
Register MFE
only
BTU-D
BTU-D
or
REG.
6.9.2DIP-switches in positions 198 and 199
Selection of ground strapping for the coax 75 Ω or selection of the 120 Ω twisted pair interface.
On factory delivery the switches are set to OFF-position = no ground thus enabling 120 Ω interface with a
twisted pair cable. These DIP-switches connect the
75 Ω interface coaxscreento ground, either directly to
0Vorviaa1nFcapacitor.DIP-switch 198 switches the
receiver and199the transmitter side. The screenshall
normally be grounded on the transmitter side. Normally, the screen on the reception side isnot connected to
ground. Refer to local market requirements
Ranges on the interface of the BTU-D
This interface coversthe short distance to the next NT
or Line Terminating Unit as the end point of a public or
private network. The range is only defined in terms of
the covered attenuation by the interface that is 6 dB. If
required choosecables with low attenuationto achieve
a maximum distance.
For ranges exceeding 6 dB attenuation additional digital data transmission equipment is required. Line Terminating Unit (LTU) ASB 501 04 is available for such
purposes.
Connection field 6
A
C
18
19
20
22
23
24
26
28
30
32
RING_OUT
TIP_OUT
RING_IN
TIP_IN
LA1
Outgoing
wires
LB1
LA2
Incoming
wires
LB2
Connection for 75 Ω
coaxial cable
Connection for
120 Ω twisted pairs
0 V
There are specificrequirements for thedigital interface
wiring to meet the demands of EMC.
If a twisted pair connection shouldbeinstalled and the
requirements of EN 55022, class Bhave to be fulfilled,
a ferrite is available with the ERICSSON ordering
number STF 82 601. Taking the cable and making
three turns around the ferrite core meets the demand
of sufficient noise reduction. The ferrite should be
situated close to the slot where the cables are led out
of the cabinet. In most cases this cable is supplied by
the PTT and should not be fed via the MDF.
Some markets (e.g. Austrian PTT) require the use ofa
double-shielded interface cable. The outer shield
should be connected to frame earth and the inner
shield shouldbe connected to0V on the board.A 20 m
long standard cable is available with the ERICSSON
ordering number TSR 901 0481/20000.
Coax 75 Ω and twisted pair 120 Ω interface
d1
Line terminating unitBTU-D
d1 - The line length depends on cable type used. The board
allows 6 dB cable attenuation at 1.024 MHz. Check cable
attenuation at 1,024 MHz per 100m.
Prepared
Doc respons/ApprovedChecked
Subject responsible
6.10BTU-E (ROF 157 5113/_)
INSTALLATION INSTRUCTION
Documentnumber
1531-BDV BS 101 01 Uen
Date
Rev
Reference
1998-05-29L
19(46)
SPEECH CONNECTION SETTINGS
2-wire connection
106...406
on
1 2 3 4
S1 S2
S3 S4
108/308
on
1 2
S5
INDIVIDUAL 0
uses switches 106 and 108/1
INDIVIDUAL 2
uses switches 306 and 308/1
SPEECH CONNECTION SETTINGS
4-wire connection
106...406
on
1 2 3 4
S1 S2
S3 S4
INDIVIDUAL 1
uses switches 206 and 108/2
INDIVIDUAL 3
uses switches 406 and 308/2
Switches select between 2- or 4-wire speech
connection. Two individualsshare switches 108
and 308
On boardswith Rev. R2Athese switchesare replaced byrelays. These relays are setautomatically by programming the filter coefficients.
Connection field 4 and 6 at front of BTU-E_
Speech (field 4)
AC
18
LA_0
LB_0
LA_1
LB_1
LA_2
LB_2
LA_3
LB_3
M2_0
M20_0
M2_1
M20_1
M2_2
1
M20_2
M2_3
M20_3
M1_0
M0_0
M1_1
M0_1
M1_2
1
M0_2
M1_3
M0_3
20
22
24
26
28
30
32
Signalling (field 6)
AC
LC_0
LD_0
LC_1
LD_1
LC_2
LD_2
LC_3
LD_3
E2_0
E20_0
E2_1
E20_1
E2_2
E20_2
E2_3
E20_3
E1_0
E0_0
E1_1
E0_1
E1_2
E0_2
E1_3
E0_3
LA & LB - 2-wire send/receive or 4-wire send.
LC & LD - 4-wire receive.
108/308
on
1 2
RED
YELLOW
GREEN
YELLOW
GREEN
S5
M-WIRE CONNECTION SETTINGS
APPLICATION
PAGING
SPEECH M-WIRES
2-wire
S6..off
S7..off
S8..off
AMERICAN
E&M
SIGNALLING
DOUBLE
M-WIRE
SIGNALLING
CAILHO E&M
SIGNALLING
4-wire
4-wire
4-wire
S6, S7 and S8
see local
requirements
S6..on
S7..on
S8..off
S6..off
S7..off
S8..off
CEPT L1/SSAC 15
Only on /2 boards
4-wire
S6..off
S7..off
S8..off
S6 connects -48V to M1 terminal via 6.2 Kohm
S7 connects 0V to M0 wire locally.
S8 connects 0V to M20-wire.
108
106
206
306
406
308
0
1
2
INDIVIDUALS
3
109
209
10
2
on
1 2 3
S6 S7 S8
309
INDIVIDUALS
3
409
1
M20_ and M0_ can be switched by S7 and S8 to 0V on
the BTU-E_ locally.
M-WIRE SETTINGS
Prepared
Subject responsible
INSTALLATION INSTRUCTION
Documentnumber
20(46)
1531-BDV BS 101 01 Uen
Doc respons/ApprovedChecked
Date
Rev
Reference
1998-05-29L
6.10.1Paging connection
The figure shows howto connect the paging equipment Ericall Contactor with 2 wire speech. The PBX sends paging
information to paging system (pin 6A18) using M1 contact, and information about ’paging in progress’ or ’paging
equipment not present’ is received on the E1-wire (pin 6C18) from the paging equipment.
Switch settings
on
This switch setting is used for
signalling on E1 and M1.
1 2 3
S6 S7 S8
Applies for switches 109, 209, 309 and 409.
Z
DSLAC
0V
-48V
0V
S7
S5
M1
Detector
autom. 2/4wire
0V
PBX
4A18
4A20
6A18
6A20
6C18
6C20
LA
LB
M1E1
M0E0
E1M1
E0M0
Paging equipment
Detector
-48V
0V
0V
Figure showing Paging equipment and 2-wire speech with ’loop connection’ of the E&M-wires.
Prepared
Subject responsible
INSTALLATION INSTRUCTION
Documentnumber
21(46)
1531-BDV BS 101 01 Uen
Doc respons/ApprovedChecked
Date
Rev
Reference
1998-05-29L
6.10.2Four wire speech connection
The four wire speech and signalling connection has the benefit of not needing additional signalling wires. There are
two different types of signalling supported:
Cailho E&M-signalling (balanced battery). The two way signalling utilises common mode DC pulses via the centre
tap of the transformer. On one side a detector is connected between the -48 VDC and the centre tap of the
transformer.The other end uses opto relay M4 to switch the line to 0V (Ground). The detector reads the current flow
to ground every time M4 closes.
CEPT L1/SSAC 15 with 2280 Hz tones. In this case no DC signalling is used but instead signalling is performed by
switching on and off a 2280 Hz tone, which is detected by a tone receiver on the other side. This is only available on
index 2 boards.
Switch settings
on
This switch setting inhibits signalling on E1 and M1. Only AC or DC
signalling on the four wire speech connection is used.
1 2 3
S6 S7 S8
Applies for switches 109, 209, 309 and 409.
2280 Hz
DSLAC
2280 Hz
detector
R
0V
autom. 2/4wire
0V
M4
1uF
Detector
560
PBX
LA
4A18
0V
Ω
-48V
4A20
4C18
4C20
LB
LC
LD
PBX or channel equipment
Detector
-48V
0V
Figure showing Cailho E&M signalling and CEPT L1 or SSAC 15 with tone signalling
Prepared
Subject responsible
INSTALLATION INSTRUCTION
Documentnumber
22(46)
1531-BDV BS 101 01 Uen
Doc respons/ApprovedChecked
Date
Rev
Reference
1998-05-29L
6.10.3E&M-signalling
Signalling on E & M wires is done either using one or two E&M pairs depending on what is required. Using just E1
and M1 is a very common practice. One case to mention is the American E&M signalling where the M1 wire toggles
between -48VDC and 0V.
Double E&M signalling requires the E1/M1 wires for the signalling of information and the E2/M2 wires indicate
blocking of the connection. The E1/M1-wires are used for signalling and E2/M2-wires are used for blocking. The
figure shows 0V connection to the M-wires in both ends.
Switch settings
Standard E & M signalling
on
This switch setting is used
forsignallingon E1and M1.
1 2 3
S6 S7 S8
Double E & M signalling
on
This is the switch setting when
E1, E2, M1 andM2are used for
signalling.
1 2 3
S6 S7 S8
Applies for switches 109, 209, 309 and 409.
R
DSLAC
0V
autom. 2/4wire
S8**
0V
-48V
0V
-48V
S7
M3**
M1
Detector
**application specific
toggles between 0 and -48VDC
(e.g. American signalling)
PBX
4A18
4A20
4C18
4C20
6A18
6A20
6C18
LA
LB
LC
LD
M1E1
M0
E1M1
E0
PBX or channel equipment
Detector
-48V
0V
-48V
0V
E0M0
0V
0V
-48V
0V
S6
M2
Detector
6C20
6A02
6A04
6C02
6C04
M2E2
M20
E2M2
E20
Figure showing four wire speech and standard (double) E&M signalling.
E20
M20
Detector
-48V
0V
0V
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
23(46)
6.11CPU-D_ (ROF 157 5118/_) and
AUX_(ROF1575 119/_)
Before installing the board mount the system software
PROMs in the appropriate positions.
Connections on the CPU-D_
For connection of TEMPERATURE SENSOR KIT, see
INSTALLATION INSTRUCTION (1531-RPM 603 339).
CA
18
Factory test
20
-48 VDC
22
24
26
28
30
32
10
12
14
16
18
20
22
24
26
28
30
32
ALARM
ALARM
External
sensor 3
0 V
Not used
Not used
RTS
DTR
DCD
CTS
RTS
DTR
DCD
CTS
RTS
DTR
DCD
CTS
Polarity
independent
input
only this V.24
port is active
on the AUX3
board
red
yellow
green
red
Cold
start
strap
BS2 9727
CPU-D
R1A
ROF1575118
Audio
Audio
ALARM
(out)
0 V
External
sensor 1
0 V
External
sensor 2
0 V
TXD
0 V
RXD
DSR
TXD
0 V
RXD
DSR
TXD
0 V
RXD
DSR
AB
A
Insert PROM "RYS 102 1x9/ xx
Insert PROM "RYS 102 1x8/ xx
B
r additional CIL storage capacity up to two additional
battery backup RAMs can be added.
The ALARM input is optically isolated and the voltage
has to be between 20 - 60 VDC.
The ALARM output is equipped with an open collector
transistor with a capacity of 20 mA at 12 VDC
(Maximum 14 VDC).
Use the following prefabricated cables to connect the
peripheral data equipment to CPU-D_ and AUX_:
•PC is TSR 902 0448/1
•printer is TSR 902 0476/1
•modem is TSR 902 0466/1
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
24(46)
6.12CPU-D4 (ROF 157 5124/_)
FW PROMS
RYS 102 533/1
RYS 102 533/2
Connections on the CPU-D4
Similar tothe previous versionsthis board providesthe
V.24 interfacesbut additionallythe RS-485interface for
longer ranges. With the software key (FECU)
KDU BS 130 06/_ new functionalities can be accessed.
red
yellow
green
alarm relay
B18
B22
B20
CA
B
ROF1575130
BS2 9727
CPU
R1A
Audio
Audio
red
yellow
green
RTC
FECU
connector
ALARM
(out)
0 V
External
Temp1
0 V
External
Temp2
0 V
18
Factory test
20
-48 VDC
22
ALARM (in)
24
0 V
26
External
Temp3
28
0 V
30
Not used
32
Not used
Battery RAM
Battery RAM
st
1
Battery RAM
KDY BS 101 02/1
Insert PROM "RYS 102 xx1/ x"
A
Insert PROM "RYS 102 xx2/ x"
B
Insert PROM "RYS 102 xx3/ x"
C
Battery RAM
rd
nd
3
2
SW PROMS
C B A
To put the board in operation mount the system software PROMsin the appropriate positions.The number
of battery RAMs mounted on the CPU-D4 board is
functionality dependent.
red
Coldstart
strap
TXD
0 V
RXD
DSR
TXD
0 V
RXD
DSR
TXD
0 V
RXD
DSR
RTS
10
DTR
12
DCD
14
CTS
16
+
RTS
18
-
DTR
20
+
DCD
22
-
CTS
24
RTS
26
DTR
28
DCD
30
CTS
32
Transmit
RS 485
loop
Receive
RS 485
To connect the RS-485 data interface use plug
RNV 321 01 02 be sure to loop RTS with CTS other-
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
wise data is lost if printer is OFF. The range of the interface is up to 1200m.
Several converters may be used but with the following
successful tests were accomplished:
IC-485SI from ARP DATACON and
232<->485/422 Converter Plus IC-109AE from Black
Box Corp.
6.12.1Feature Enabling Control Unit (FECU)
Connecting this plug activates the appropriate applications and features asordered depending on the FECU
index number. If no plug is connected only a limited
Version 3.0 system functionality is available. The indices 2 to 10 always include the Basic Version 3 functionality (index 1).
25(46)
For detailed information of the featuresenabled by the
different FECUs refer to 15534-ASB 150 02 Uen
FACILITY DESCRIPTION GENERAL.
FECU numberFunctionality Version 3.1
KDU BS 130 06/1 Basic Version 3.0 functionality
KDU BS 130 06/2 + std. digital networking for max.
32 interfaces
KDU BS 130 06/3 + std. digital networking
KDU BS 130 06/4 + full. digital networking for max.
32 interfaces
KDU BS 130 06/5 + full. digital networking
KDU BS 130 06/6 + CTI
KDU BS 130 06/7 + CTI and std. digital networking
for max. 32 interfaces
KDU BS 130 06/8 + CTI and std. digital networking
KDU BS 130 06/9 + CTI + full. digital networking for
max. 32 interfaces
KDU BS 130 06/10 + CTI + full. digital networking for
unlimited number of interfaces
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
6.13ELU-A and ELU-D
Connection field6 at frontof ELU-D(3)and ELU-A
The relevant boards are:
•ELU-D (ROF 1575 116/_)
26(46)
•ELU-A (ROF 1575 114/1)
•ELU-A2 (ROF 1575 114/2)
•ELU-D3 (ROF 157 5130/_)
This switch is mount-
RYS 102 532/2
RYS 102 532/1
ON
3 4
ed for future use
1 2
(LA16)
(LB16)
(LA18)
(LB18)
(LA20)
(LB20)
(LA22)
(LB22)
(LA24)
(LB24)
(LA26)
(LB26)
(LA28)
(LB28)
(LA30)
(LB30)
LA0
LB0
LA2
LB2
LA4
LB4
LA6
LB6
LA8
LB8
LA10
LB10
LA12
LB12
LA14
LB14
02
04
06
08
10
12
14
16
18
20
22
24
26
28
30
32
C
A
LA1
LB1
LA3
LB3
LA3
LB5
LA7
LB7
LA9
LB9
LA11
LB11
LA13
LB13
LA15
LB15
(LA17)
(LB17)
(LA19)
(LB19)
(LA21)
(LB21)
(LA23)
(LB23)
(LA25)
(LB25)
(LA27)
(LB27)
(LA29)
(LB29)
(LA31)
(LB31)
Extension Line
connector to
terminal
equipment
View of the ELU-D3 board
The connections in field 4 are in brackets (only on
ELU-D3 for individuals 16 to 31)
On the first ELU-D_ board in the system the first three
extension positions should be used to connect the
OPERATOR telephones.
On sub-equipped ELU-A and ELU-D_ boards the connection for extensions 8...15 (32) are not mounted.
INSTALLATION INSTRUCTION
Subject responsible
Doc respons/ApprovedCheckedReference
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
DateRev
1998-05-29
L
27(46)
6.14VMU-HD (ROF 157 5126/1)
To install unpack the VMU-HDboard with the mounted
hard disk.The Flash disksare availablewith a capacity
of 60 MB. Removethe transport protection forthehard
disk and keep it in case of re-shipment e.g. factory repair. Install and configure the VMU-HD in the cabinet
according to the stipulations in 1537-ASB15002Uen
START OF OPERATION.
Note: The VMU-HD will not start up without internal
directories created on the hard disk.
The DIP-switch is shown with
both contacts in OFF position
(factory setting)
ON
1 2
990
990/2990/1FUNCTION
OFF
ON
Structure of directories on hard disk or Flash card
\Info0\message2\anno0
\Info1\message3\anno1
Removal of hard disk or Flash card
To remove the hard disk take out the board from the
system. Disengagethehard disk with leverand pull
out the hard disk.
ON or
OFF
OFF
ON
\message4\anno2
\message5\anno3
16 channels, no register function
8 channels with MFC detection
and DTMF / Tone receiver
8 channels with MFE detection
and DTMF / Tone receiver
\annoF
A
6.15VMU-D (ROF 157 5117/1)
PCMCIA Hard/
Flash disk
type III and II
A
Press button to disengage the hard disk and
Pressbuttontodisengagethehard
A
take it out.
disk and take it out.
DIP switch on VMU-HD
DIP switch 990 selects whether register function is enabled or not.
Limitations:
Only one VMU-HD can be mounted per cabinet and
just one type either VMU-HD or VMU-D can be installed in a system.
The VMU-D has no switches, but is equipped with a
back up battery, RNV 991 942/001 to prevent loss of
data in case of power failure. Install the battery to connection field4. beforethe exchange isstarted. Forsafe
operation, replace this battery periodically every five
years in accordance with document MAINTENANCE
INSTRUCTION (1541-ASB 150 02 Uen).
Installation of battery back-up on VMU-D
Connection
field 4
Battery RNV 991 942/001
INSTALLATION INSTRUCTION
Subject responsible
DocumentnumberPrepared
1531-BDV BS 101 01 Uen
Doc respons/ApprovedCheckedReference
DateRev
1998-05-29
L
28(46)
7INTEGRATED CORDLESS
The Integrated Cordless (IC) is a digital cordless telephone solution complying to the DECT standard providing wireless connection for up to 108portables with
the A-protocol and 210 portables in GAP-protocol applications. Several components comprise a complete
system.
After the system has been physically installed use
RASC and the Cordless System Manager (CSM) for
initialization, maintenance, updating, fault finding and
when possible to recover the PBX from errors. The
CSM is orderable under LZYNB 201 01 R6A or higher
forthe A-protocol and LZYNB201 05 R1B orhigher for
GAP applications.
7.1Board Descriptions
7.1.1IC-Control Unit2 (IC-CU2)
The IC-CU2 is the control board supporting the DECT
GAP-protocol. The IC-CU2 includes 8 voice channel
units and is equipped with 4 BSs interfaces.
The wiring distance with remote power feeding to the
BSs using only the serial communication wires SC0
and SC1 is limited to 400m. For line lengths up to
900m additional Express Power feeding Pairs (EPP)
need to be wired. The maximum wire length between
BS (fed locally) and IC-CU2 is only data limited and
may reach up to 900 meters.
The board offers the following connections:
•the Cordless System Manager (on a PC)
•a printer to log errors
•4 Base Stations
•the Feature Enabling Control Unit (FECU).
7.1.2Feature Enabling Control Unit (FECU)
plug is available for various numbers of cordless telephones. For up to 8 portables no plug is required.
The traffic capacity of the Cordless part of the PBX is
mainly determined by the IC-CU_ and in exceptional
cases also by the Base Stations. The IC-CU can handle a maximum of 56 simultaneous calls and the ICCU2 can handle up to 60 simultaneous calls. Each
Base Station has a capacity of 8 simultaneous calls.
The traffic capacity of the IC-CU_ is determined by:
•the Grade Of Service (GOS) required by the
customer
•the number of speech circuits available, with a
limit of 64.
The Grade Of Service is the probability that acall is rejected because of system congestion. The customer
has to indicate which Grade Of Service is acceptable.
A Grade Of Service of 1%, or 0.01, means an average
of 1 lost call in every 100 calls. The IC-CU2 is
equipped with a SPU providing 8 speech circuits.
The two parametersmentioned above (GOS and the8
speech circuits) and the totalamountof traffic (Erlang)
that is required, are related to each other. The table
below shows the capacity at a required GOS.
This plug determines which maximum number of portables are allowed to be connected to the system. This
Prepared
Subject responsible
INSTALLATION INSTRUCTION
Documentnumber
29(46)
1531-BDV BS 101 01 Uen
Doc respons/ApprovedChecked
Date
Rev
Reference
1998-05-29L
Practically, this table is used to calculate from a given GOS and Erlang value the number of portable users.
IC-CU2
1
SpeechGrade of service (GOS)
circuits
2%1%0.5%0.1%
83.63.22.72.1
For the calculation it is necessary to estimate the time the portables actually make calls. The table below shows the
Erlang value depending on the estimated mean call-minutes fora portable telephone. These values may be different
between departments depending on their activities. These values multiplied by the number of portables result in a
traffic capacity that has to be provided.
mErlangMinutes
25015
30018
50030
75045
per hour
mErlangMinutes
per hour
503
1006
1509
20012
Example:
A customer ordering a system with 24 portable telephones. He estimates that each portable generates 200 mE
each in average. These values requirea system with a traffic capacityof3,6 E (0,15x24). With an acceptedGOS of
2.0% the traffic capacity can be met.
7.2.1Traffic Capacity of Base Stations
A Base Station, having 8 channels available, has an Erlang value of 2.7 with a GOS of 0.5%. This means that each
Base Station can serve 18 portables, assuming each portable generates 150 mE during busy hour or 13.5 portables
generating 200 mE each.
Example:
Assuming a full coverage in a building canbeachieved with 2 Base Stations means that 20portables generate
together 20 x 0.150 = 3 E. Every Base Station has a traffic capacity of 2.7 Erlang. To have a sufficient
coverage two Base Stations covering the area of the busiest part of the company are needed.
Practically, the total capacity offered by the cordless network is generally more than sufficient, but this is from an average point of view. In certain places, traffic demands may vary such that locally the network is often blocked, or has
a lower GOS than required. For instance a purchase department may easily generate 300 mE per Portable during
busy hour, thus, when e.g. with 6 persons giving a very high load on the Base Station close by. It may be necessary
to add aBase Station in this areatohave enough capacityfor others to callas well. Also think ofe.g. canteens during
lunch time etc.
INSTALLATION INSTRUCTION
Prepared
Subject responsible
Documentnumber
1531-BDV BS 101 01 Uen
Doc respons/ApprovedChecked
Date
1998-05-29L
7.3IC-CU2 (ROF 157 5131/_) (GAP-Protocol)
LEDs
Rev
30(46)
Reference
RP error
Individual blocked
Individual busy
CPU error/DCT error log
SPU error
DECT Sync port
SYNCH A IN
SYNCH B IN
SYNCH A OUT
SYNCH B OUT
CLU error
0 V
0 V
(KDU 130 05/__)
External power input
via front connector (to enable
set switch 1and 2 to OFF)
to power supply BML 351 048
Express Power feeding to base stations
(-)
To BS 4
EPP
TSR BS 101 12/1500
AC
18
20
22
(-)
To BS 3
EPP
EPP
EPP
(+)
(+)
red
yellow
green
green
red
red
V0
V1
(-)
(+)
BS2 9727
IC-CU2
R1A
ROF1575131/1
Switch 1 and 2 must have the
same position. ON (default)
48V from the backplane. OFF
activatesexternal DC inputand
disconnects the backplane.
RYS 102 531/1
DECT
synchronization
RYSNB 101 19
RYS 102 531/2
+
RYS 102 553/1
ON
1 2
ON
RYS 102 554/1
RYSNB 101 20
24
To BS 2
EPP
26
(-)
28
To BS 1
EPP
30
(-)
32
Serial communication to base stations
AC
To BS 4
SC0
02
04
06
To BS 3
SC0
08
To BS 2
SC0
10
12
14
To BS 1
SC0
16
EPP
EPP
(+)
(+)
SC1
SC1
SC1
SC1
RYSNB 101 23/2
Maintenance port
TXM
0 V
RCV
n.c.
TXM
0 V
RCV
DSR
18
20
22
24
26
28
30
32
RTS
DTR
PRINTER
DCD
PORT
CTS
RTS
DTR
MAINTENANCE
DCD
PORT
CTS
remove paper
insulation
Prepared
Subject responsible
INSTALLATION INSTRUCTION
Documentnumber
31(46)
1531-BDV BS 101 01 Uen
Doc respons/ApprovedChecked
Date
Rev
Reference
1998-05-29L
7.4Base Station (KRCNB 201 03/_ and KRCNB 301 01/_)
The Base Station (BS) enables radio communication between the Integrated Cordless system and the portable
telephones. The communication via two2B+D interfaces, requires two twisted pair cables. Both interfaces provide in
total eight 32 kbit/s speech paths between a BS and IC-CU2, enabling a BS to handle eight simultaneous calls. The
BS is connected to the IC-CU2 via two wire pairs called serial communication wires (SC0 & SC1) carrying up to 8
simultaneousdigitalvoiceconnectionsandthecentralpowerfeeding.Apart fromdatacommunicationthesetwotwisted
pairs are alsobe used to distribute power to theBSs. Two additional pairs canbe wired to provide agreater powering
range. There are three methods to power BSs:
1.centrally via backplane (with or without EPP)
2.centrally via external input (with / w.o EPP)
3.via local power supply (optional).
With the first and second methods power is distributed via the IC-CU2 to the BS. The cable length between BS and
IC-CU2 depends on thenumber wires used for power feeding,the type of cable and environmentalnoise. In the third
case (local feeding),BSs are powered by anAC-adapter or another power source which isnot routed via the cabinet.
The number of BSs used in a system depends on the area to be covered and the traffic density. Typical in-house
coverageis upto 30meter radius.In practicethecell sizemayvary between10 metersindoorsin worstcasesituations,
up to 300 meters outdoor in free space.
The BS has two main functions:
•to modulate a carrier with the digital encoded information (TDMA frame directed to portable)
•to demodulate a modulated carrier (TDMA frame received from portable).
A special cover (KRY NB 101 01) is available to mount the BS (KRCNB 201 03) outdoors providing splash proof
housing and water tight sealings for the wiring.
7.4.1Base Station Planning
The major task when providing a wireless service is to estimate the number of BSs and to find their most suitable
location. A number of factors tend to limit the range of a BS like the materials the wall is composed of or the location
and size of machines, furniture, air-conditioning systems, elevators etc. This results in unexpected reflections or
absorption of radio waves. Generally BSs should not be located on outer walls, except if the outdoor area has to be
covered as well, as this reduces the area actually covered. All of these unpredictable influencing factors makes it
extremely difficulttodefine rules for how to cover an areawith a suitable number of BSs.In difficult environments the
use of a site survey tool (LTT NB 101 01/_) is recommended.
Establish a Base Station plan for the installation site to determine the best location for the BSs.
Base Station aerial range
•Inan officeenvironment in asteel concretebuilding up to30 mindiameter canbe coveredand including,
under normal conditions, the neighbouring floors.
•Production halls up to 200 m in diameter are covered but ranges can be less if bulky machines, cranes
etc. are part of the interior.
•Outdoor ranges can be up to 300m.
When installing a BS, position it, then walk around to determine cell coverage area either by listening to the speech
quality- whethermutesor cracklingsounds areheardin theportable -or measuretheRQIindicator usingtheportables
Service Display facility (see FAULT TRACING 1545-ASB15002Uen).
Loading...
+ 195 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.