Endress+Hauser PTC31B, PTP33B Operating Manual

Products Solutions Services
Operating Instructions
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Process pressure measurement Pressure switch for safe measurement and monitoring of absolute and gauge pressure
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Order code:
Ext. ord. cd.:
Ser. no.:
www.endress.com/deviceviewer
Endress+Hauser Operations App
XXXXXXXXXXXX
XXXXX-XXXXXX
XXX.XXXX.XX
Serial number
1.
3.
2.
A0023555
• Make sure the document is stored in a safe place such that it is always available when working on or with the device.
• To avoid danger to individuals or the facility, read the "Basic safety instructions" section carefully, as well as all other safety instructions in the document that are specific to working procedures.
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to these Operating Instructions.
2 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Table of contents

Table of contents

1 Document information .............. 5
1.1 Document function ..................... 5
1.2 Symbols used .......................... 5
1.3 Documentation ........................ 6
1.4 Terms and abbreviations ................. 7
1.5 Turn down calculation ................... 8
1.6 Registered trademarks ................... 8
2 Basic safety instructions ............ 9
2.1 Requirements concerning the staff .......... 9
2.2 Designated use ........................ 9
2.3 Workplace safety ...................... 10
2.4 Operational safety ..................... 10
2.5 Product safety ........................ 10
3 Product description ................ 11
3.1 Product design ........................ 11
3.2 Function ............................ 11
4 Incoming acceptance and product
identification ..................... 13
4.1 Incoming acceptance ................... 13
4.2 Product identification ................... 14
4.3 Storage and transport .................. 14
8 System integration ................ 31
8.1 Process data ......................... 31
8.2 Reading out and writing device data (ISDU –
Indexed Service Data Unit) ............... 32
8.3 Overview of diagnostic events ............. 34
9 Commissioning .................... 35
9.1 Function check ....................... 35
9.2 Commissioning with an operating menu ..... 35
9.3 Configuring pressure measurement ........ 36
9.4 Performing position adjustment ........... 38
9.5 Configuring process monitoring ........... 40
9.6 Current output ........................ 40
9.7 Application examples ................... 43
10 Diagnostics and troubleshooting ... 44
10.1 Troubleshooting ...................... 44
10.2 Diagnostic events ...................... 45
10.3 Behavior of the device in the event of a fault .. 47
10.4 Signal on alarm 4 to 20 mA .............. 47
10.5 Behavior of the device in the event of a
voltage drop ......................... 48
10.6 Behavior of the device in the event of an
incorrect entry ....................... 48
10.7 Resetting to factory settings (reset) ........ 48
5 Installation ....................... 16
5.1 Mounting dimensions .................. 16
5.2 Installation conditions .................. 16
5.3 Influence of the installation position ........ 16
5.4 Mounting location ..................... 17
5.5 Mounting instructions for oxygen
applications .......................... 19
5.6 Post-installation check .................. 19
6 Electrical connection .............. 20
6.1 Connecting the measuring unit ............ 20
6.2 Switching capacity ..................... 22
6.3 Connection data ....................... 22
6.4 Post-connection check .................. 23
7 Operation options ................. 24
7.1 Operation with an operating menu ......... 24
7.2 Operation with local display .............. 25
7.3 General value adjustment and rejection of
illegal entries ......................... 26
7.4 Navigation and selection from list ......... 26
7.5 Locking and unlocking operation .......... 28
7.6 Navigation examples ................... 30
7.7 Status LEDs .......................... 30
7.8 Resetting to factory settings (reset) ........ 30
11 Maintenance ...................... 48
11.1 Exterior cleaning ...................... 49
12 Repairs ........................... 50
12.1 General notes ........................ 50
12.2 Return .............................. 50
12.3 Disposal ............................ 50
13 Overview of the onsite display
operating menu ................... 51
14 Overview of the IO-Link operating
menu ............................. 54
15 Description of device parameters ... 56
15.1 Observation ......................... 74
16 Accessories ....................... 75
16.1 Weld-in adapter ...................... 75
16.2 Process adapter M24 ................... 75
16.3 M12 plug connectors ................... 76
Endress+Hauser 3
Table of contents Ceraphant PTC31B, PTP31B, PTP33B IO-Link
17 Technical data .................... 77
17.1 Input ............................... 77
17.2 Output ............................. 80
17.3 Performance characteristics of ceramic
process isolating diaphragm .............. 83
17.4 Performance characteristics of metal process
isolating diaphragm .................... 85
17.5 Environment ......................... 87
17.6 Process ............................. 88
Index .................................. 90
4 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Document information
DANGER
WARNING
CAUTION
NOTICE

1 Document information

1.1 Document function

These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.

1.2 Symbols used

1.2.1 Safety symbols

Symbol Meaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury.
NOTICE!
This symbol contains information on procedures and other facts which do not result in personal injury.

1.2.2 Electrical symbols

Symbol Meaning Symbol Meaning
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.

1.2.3 Tool symbols

Symbol Meaning
Open-ended wrench
A0011222

1.2.4 Symbols for certain types of information

Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Endress+Hauser 5
Document information Ceraphant PTC31B, PTP31B, PTP33B IO-Link
A
,…,
1.
2.
3.
,…,
1.
2.
3.
Symbol Meaning
Reference to documentation
Reference to page
Reference to graphic
Series of steps
Result of a step
Visual inspection

1.2.5 Symbols in graphics

Symbol Meaning
1, 2, 3 ... Item numbers
Series of steps
A, B, C, ... Views

1.3 Documentation

The document types listed are available: In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download

1.3.1 Technical Information (TI): planning aid for your device

PTC31B: TI01130P
PTP31B: TI01130P
PTP33B: TI01246P
The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.

1.3.2 Brief Operating Instructions (KA): getting the 1st measured value quickly

Devices with IO-Link: KA01404P
These instructions contain all the essential information from incoming acceptance to initial commissioning.
6 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Document information
URL OPLMWP
LRL
0
p
LRV
URV
1
2
3
4

1.4 Terms and abbreviations

A0029505
Item Term/
abbreviation
1 OPL The OPL (over pressure limit = sensor overload limit) for the measuring device
2 MWP The MWP (maximum working pressure) for the sensors depends on the lowest-
3 Maximum sensor
measuring range
4 Calibrated/adjusted
span
p - Pressure
- LRL Lower range limit
- URL Upper range limit
- LRV Lower range value
- URV Upper range value
- TD (turn down) Turn down
Explanation
depends on the lowest-rated element, with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes, see the "Pressure specifications" section →  89 . The OPL may only be applied for a limited period of time.
rated element, with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes, see the "Pressure specifications" section →  89 . The MWP may be applied at the device for an unlimited period. The MWP can also be found on the nameplate.
Span between LRL and URL This sensor measuring range is equivalent to the maximum calibratable/adjustable span.
Span between LRV and URV Factory setting: 0 to URL Other calibrated spans can be ordered as customized spans.
Example - see the following section.
Endress+Hauser 7
Document information Ceraphant PTC31B, PTP31B, PTP33B IO-Link
LRV
URLURV
LRL
1 = 2
3

1.5 Turn down calculation

A0029545
1 Calibrated/adjusted span 2 Zero point-based span 3 URL sensor
Example
• Sensor:10 bar (150 psi)
• Upper range value (URL) = 10 bar (150 psi)
Turn down (TD):
• Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)
• Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
TD =
|URV - LRV|
TD =
|5 bar (75 psi) - 0 bar (0 psi)|
In this example, the TD is 2:1. This span is based on the zero point.
URL
10 bar (150 psi)
= 2

1.6 Registered trademarks

is a registered trademark of the IO-Link company group.
8 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Basic safety instructions

2 Basic safety instructions

2.1 Requirements concerning the staff

The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements:
Trained, qualified specialists: must have a relevant qualification for this specific
function and task Are authorized by the plant owner/operator
Are familiar with federal/national regulations
Before beginning work, the specialist staff must have read and understood the
instructions in the Operating Instructions and supplementary documentation as well as in the certificates (depending on the application) Following instructions and basic conditions
The operating personnel must fulfill the following requirements:
Being instructed and authorized according to the requirements of the task by the
facility's owner-operator Following the instructions in these Operating Instructions

2.2 Designated use

2.2.1 Application and media

The Ceraphant is a pressure switch for measuring and monitoring absolute and gauge pressure in industrial systems. The process-wetted materials of the measuring device must have an adequate level of resistance to the media.
The measuring device may be used for the following measurements (process variables)
• in compliance with the limit values specified under "Technical data"
• in compliance with the conditions that are listed in this manual.
Measured process variable
Gauge pressure or absolute pressure
Calculated process variable
Pressure

2.2.2 Incorrect use

The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance
in verifying the corrosion resistance of process-wetted materials, but does not accept any warranty or liability.

2.2.3 Residual risks

When in operation, the housing may reach a temperature close to the process temperature.
Danger of burns from contact with surfaces!
For elevated process temperatures, ensure protection against contact to prevent burns.
Endress+Hauser 9
Basic safety instructions Ceraphant PTC31B, PTP31B, PTP33B IO-Link

2.3 Workplace safety

For work on and with the device:
Wear the required personal protective equipment according to federal/national
regulations. Switch off the supply voltage before connecting the device.

2.4 Operational safety

Risk of injury!
Operate the device in proper technical condition and fail-safe condition only.
The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers.
If, despite this, modifications are required, consult with Endress+Hauser.
Hazardous area
To eliminate the risk of danger to persons or the facility when the device is used in the approval-related area (e.g. pressure equipment safety):
Check the nameplate to verify if the device ordered can be put to its intended use in the
approval-related area.

2.5 Product safety

This measuring device is designed in accordance with good engineering practice to meet state-of-the-art safety requirements, has been tested, and left the factory in a condition in which it is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.
10 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Product description
A
B
C
D
E
D
E
D
E

3 Product description

3.1 Product design

Overview Item Description
A Valve plug
B Cable
C M12 plug
Housing cap made of plastic
A0022015
A0037236
A0037238
D
Housing
E
Process connection (sample illustration)
A0027226
A0027215
A0027227

3.2 Function

3.2.1 Calculating the pressure

Endress+Hauser 11
Devices with ceramic process isolating diaphragm (Ceraphire®)
The ceramic sensor is an oil-free sensor, i.e. the process pressure acts directly on the robust ceramic process isolating diaphragm and causes it to deflect. A pressure-dependent
Product description Ceraphant PTC31B, PTP31B, PTP33B IO-Link
change in capacitance is measured at the electrodes of the ceramic substrate and the process isolating diaphragm. The measuring range is determined by the thickness of the ceramic process isolating diaphragm.
Devices with metallic process isolating diaphragm
The process pressure deflects the metal process isolating diaphragm of the sensor and a fill fluid transfers the pressure to a Wheatstone bridge (semiconductor technology). The pressure-dependent change in the bridge output voltage is measured and evaluated.
12 Endress+Hauser

Ceraphant PTC31B, PTP31B, PTP33B IO-Link Incoming acceptance and product identification

DELIVERY NOTE
1 = 2
E
E
DELIVERYNOTE
E
4 Incoming acceptance and product
identification

4.1 Incoming acceptance

A0028673
A0016870
Is the order code on the delivery note (1) identical to the order code on the product sticker (2)?
A0028673
A0028673
A0022099
A0022101
Are the goods undamaged?
A0022104
Do the data on the nameplate correspond to the order specifications and the delivery note?
If one of these conditions does not apply, please contact your Endress+Hauser sales office.
Endress+Hauser 13
Incoming acceptance and product identification Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Ser. no.:
Ord. cd.:
Ext. ord. cd.:
D-79689 Maulburg
Made in Germany,
Ceraphant
5
1 2
3 4
Date:
TAG:

4.2 Product identification

The following options are available for the identification of the measuring device:
• Nameplate specifications
• Order code with a breakdown of the device features on the delivery note
• Enter the serial numbers from the nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All the information about the measuring device is displayed.
For an overview of the technical documentation provided, enter the serial number from the nameplates in W@M Device Viewer (www.endress.com/deviceviewer)

4.2.1 Manufacturer address

Endress+Hauser SE+Co. KG Hauptstraße 1 79689 Maulburg, Germany
Address of the manufacturing plant: See nameplate.

4.2.2 Nameplate

A0030101
1 Manufacturer's address 2 Device name 3 Order number 4 Serial number 5 Extended order number

4.3 Storage and transport

4.3.1 Storage conditions

Use original packaging.
Store the measuring device in clean and dry conditions and protect from damage caused by shocks (EN 837-2).
Storage temperature range
–40 to +85 °C (–40 to +185 °F)
14 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Incoming acceptance and product identification

4.3.2 Transporting the product to the measuring point

WARNING
L
Incorrect transport!
Housing and diaphragm may become damaged, and there is a risk of injury!
Transport the measuring device to the measuring point in its original packaging or by
the process connection.
Endress+Hauser 15
Installation Ceraphant PTC31B, PTP31B, PTP33B IO-Link
1
1
1
1
C
A
B

5 Installation

5.1 Mounting dimensions

For dimensions, see the "Mechanical construction" section in the Technical Information.

5.2 Installation conditions

• Moisture must not penetrate the housing when mounting the device, establishing the
electrical connection and during operation.
• Do not clean or touch process isolating diaphragms with hard and/or pointed objects.
• Do not remove process isolating diaphragm protection until shortly before installation.
• Always tighten the cable entry firmly.
• Point the cable and connector downwards where possible to prevent moisture from
entering (e.g. rain or condensation water).
• Protect housing against impact.
• For devices with gauge pressure sensor, the following applies:
NOTICE
If a heated device is cooled in the course of a cleaning process (by cold water, for example), a vacuum develops for a short time causing moisture to penetrate the sensor via the pressure compensation element (1).
Device could be destroyed!
In the event of this happening, mount the device in such a way that the pressure
compensation element (1) is pointing downwards at an angle or to the side, if possible.
A0022252

5.3 Influence of the installation position

Any orientation is possible. However, the orientation may cause a zero point shift i.e. the measured value does not show zero when the vessel is empty or partially full.
A0024708
16 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Installation
1
2
Type Process isolating
diaphragm axis is horizontal (A)
PTP31B PTP33B
PTC31B < 1 bar (15 psi)
PTC31B ≥1 bar (15 psi)
Calibration position, no effect
Calibration position, no effect
Calibration position, no effect
Process isolating diaphragm pointing upwards (B)
Up to +4 mbar (+0.058 psi) Up to –4 mbar (–0.058 psi)
Up to +0.3 mbar (+0.0044 psi)
Up to +3 mbar (+0.0435 psi) Up to –3 mbar (–0.0435 psi)
Process isolating diaphragm pointing downwards (C)
Up to –0.3 mbar (–0.0044 psi)
A position-dependent zero shift can be corrected on the device .

5.4 Mounting location

5.4.1 Pressure measurement

Pressure measurement in gases
Mount the device with shutoff device above the tapping point so that any condensate can flow into the process.
A0025920
1 Device 2 Shutoff device
Pressure measurement in vapors
For pressure measurement in vapors, use a siphon. The siphon reduces the temperature to almost ambient temperature. Preferably mount the device with the shutoff device and siphon below the tapping point.
Advantage:
• defined water column causes only minor/negligible measuring errors and
• only minor/negligible heat effects on the device.
Mounting above the tapping point is also permitted.
Note the max. permitted ambient temperature of the transmitter!
Take the influence of the hydrostatic water column into consideration.
Endress+Hauser 17
Installation Ceraphant PTC31B, PTP31B, PTP33B IO-Link
1
1
2
2
3
4
1
2
3
A0025921
1 Device 2 Shutoff device 3 Siphon 4 Siphon
Pressure measurement in liquids
Mount the device with a shutoff device and siphon below or at the same height as the tapping point.
Advantage:
• defined water column causes only minor/negligible measuring errors and
• air bubbles can be released to the process.
Take the influence of the hydrostatic water column into consideration.
A0025922
1 Device 2 Shutoff device 3 Siphon

5.4.2 Level measurement

• Always install the device below the lowest measuring point.
• Do not install the device at the following positions:
– In the filling curtain – In the tank outlet – in the suction area of a pump – Or at a point in the tank which could be affected by pressure pulses from the agitator.
18 Endress+Hauser
• A functional test can be carried out more easily if you mount the device downstream
from a shutoff device.
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Installation
A0025923

5.5 Mounting instructions for oxygen applications

Oxygen and other gases can react explosively to oils, grease and plastics, such that, among other things, the following precautions must be taken:
• All components of the system, such as measuring devices, must be cleaned in accordance with the BAM requirements.
• Dependent on the materials used, a certain maximum temperature and a maximum pressure for oxygen applications must not be exceeded.
• The following table lists devices (devices only, not accessories or enclosed accessories), which are suitable for gaseous oxygen applications.
Device p
PTC31B 40 bar (600 psi) –10 to +60 °C (+14 to +140 °F) HB
1) Product Configurator, order code for "Service"
for oxygen applications T
max
for oxygen applications Option
max

5.6 Post-installation check

 Is the device undamaged (visual inspection)?
Does the device comply with the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature range
• Measuring range
 Are the measuring point identification and labeling correct (visual inspection)?
 Is the device adequately protected against precipitation and direct sunlight?
 Are the securing screws tightened securely?
 Is the pressure compensation element pointing downwards at an angle or to the side?
 To prevent moisture from penetrating, ensure that the connecting cables/plugs are pointing downwards.
1)
Endress+Hauser 19
Electrical connection Ceraphant PTC31B, PTP31B, PTP33B IO-Link
L–
L+
0.63A
2
1
3
4
R1
R1
"
L–
L+
1
2
3
4
0.63A
L–
L+
1
2a
3 4 2b
R1
"
(a)
0.63A

6 Electrical connection

6.1 Connecting the measuring unit

6.1.1 Terminal assignment

WARNING
L
Risk of injury from the uncontrolled activation of processes!
Switch off the supply voltage before connecting the device.
Make sure that downstream processes are not started unintentionally.
WARNING
L
Electrical safety is compromised by an incorrect connection!
In accordance with IEC/EN61010 a separate circuit breaker must be provided for the
device . The device must be operated with a 630 mA fine-wire fuse (slow-blow).
Protective circuits against reverse polarity are integrated.
NOTICE
Damage to analog input of PLC resulting from incorrect connection
Do not connect the active PNP switch output of the device to the 4 to 20 mA input of a
PLC.
Connect the device in the following order:
1. Check that the supply voltage corresponds to the supply voltage indicated on the nameplate.
2. Connect the device in accordance with the following diagram.
Switch on supply voltage.
1 x PNP switch output R1 (not with IO-Link functionality)
M12 plug Valve plug Cable
A0029268
A0023271
1 brown = L+ 2a black = switch output 1 2b white = not in use 3 blue = L­4 green/yellow = ground (a) reference air hose
A0022801
20 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Electrical connection
L–
L+
2
1
3
4
R1
R2
0.63A
L–
L+
1
2b
2a
3 4
R2
(a)
0.63A
R1
"
L–
L+
C/Q1
2
1
3
4
SIO
IO-Link
0.63 A
R1
Q2
L–
L+
2
1
3
4
R1
0.63A
L–
L+
1
2b
2a
3 4
(a)
0.63A
R1
"
0.63 A
C/Q L–
L+
2
1
3
4
SIO
IO-Link
2 x PNP switch output R1 and R2 (not with IO-Link functionality)
M12 plug Valve plug Cable
-
A0023248
A0023282
1 brown = L+ 2a black = switch output 1 2b white = switch output 2 3 blue = L­4 green/yellow = ground (a) reference air hose
IO-Link: 2 x PNP switch output R1 and R2
M12 plug
A0036997
1 x PNP switch output R1 with additional analog output 4 to 20 mA (active), (not with IO­Link functionality)
M12 plug Valve plug Cable
-
A0023249
1 brown = L+ 2a black = switch output 1 2b white = analog output 4 to 20 mA 3 blue = L­4 green/yellow = ground (a) reference air hose
A0030519
IO-Link: 1 x PNP switch output R1 with additional analog output 4 to 20 mA (active)
M12 plug
A0036998
Endress+Hauser 21
Electrical connection Ceraphant PTC31B, PTP31B, PTP33B IO-Link

6.1.2 Supply voltage

Supply voltage IO-Link: 10 to 30 V DC at a DC power unit
IO-Link communication is guaranteed only if the supply voltage is at least 18 V.

6.1.3 Current consumption and alarm signal

Intrinsic power consumption Alarm current (for devices with analog output)
≤ 60 mA ≥21 mA (factory setting)
Maximum current consumption: ≤ 300 mA
1) Setting min. alarm current ≤3.6mA can be ordered via the product order structure. Min. alarm current ≤3.6mA can be configured at the device or via IO-Link.
1)

6.2 Switching capacity

• Switch state ON
1)
: Ia ≤ 200 mA
• Switch cycles: >10,000,000
• Voltage drop PNP: ≤2 V
• Overload protection: Automatic load testing of switching current;
– Max. capacitive load: 1 μF at max. supply voltage (without resistive load) – Max. cycle duration: 0.5 s; min. ton: 40 μs – Periodic disconnection from protective circuit in the event of overcurrent (f = 2 Hz) and
"F804" displayed
2)
; switch state OFF: Ia ≤100 μA

6.3 Connection data

6.3.1 Load (for devices with analog output)

In order to guarantee sufficient terminal voltage, a maximum load resistance RL (including line resistance) must not be exceeded depending on the supply voltage UB of the supply unit.
The maximum load resistance depends on the terminal voltage and is calculated according to the following formula:
1) 100 mA can be guaranteed over the entire temperature range for the switch outputs "2 x PNP" and "1 x PNP + 4 to 20 mA output". For lower ambient temperatures, higher currents are possible but cannot be guaranteed. Typical value at 20 °C (68 °F) approx. 200 mA. 200 mA can be guaranteed over the entire temperature range for the "1 x PNP" current output.
2) Larger currents are supported, thus deviating from the IO-Link standard.
22 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Electrical connection
[ ]W
20 30
10
0
1022
587
152
U [V]
1
2
R
R
L
L
max
max
£
-U 6.5V
23mA
B
B
A0031107
1 Power supply 10 to 30 V DC 2 R
UBSupply voltage
maximum load resistance
Lmax
If load is too great:
• failure current is output and "S803" displayed (output: MIN alarm current)
• Periodic checking to establish if it is possible to quit fault state
• In order to guarantee sufficient terminal voltage, a maximum load resistance RL (including line resistance) must not be exceeded depending on the supply voltage UB of the supply unit.

6.4 Post-connection check

 Is the device or cable undamaged (visual check)?
 Do the cables comply with the requirements?
 Do the cables have adequate strain relief?
 Are all the cable glands installed, firmly tightened and leak-tight?
 Does the supply voltage match the specifications on the nameplate?
 Is the terminal assignment correct?
 If required: has protective ground connection been established?
If supply voltage is present: is the device ready for operation and do values appear on the display module or
is the green status LED lit?
Endress+Hauser 23
Operation options Ceraphant PTC31B, PTP31B, PTP33B IO-Link

7 Operation options

7.1 Operation with an operating menu

7.1.1 IO-Link

IO-Link information
IO-Link is a point-to-point connection for communication between the measuring device and an IO-Link master. The measuring device features an IO-Link communication interface type 2 with a second IO function on pin 4. This requires an IO-Link-compatible assembly (IO-Link master) for operation. The IO-Link communication interface enables direct access to the process and diagnostic data. It also provides the option of configuring the measuring device on the fly.
Physical layer, the measuring device supports the following features:
• IO-Link specification: version 1.1
• IO-Link Smart Sensor Profile 2nd Edition (supports minimum scope of IdentClass)
• SIO mode: yes
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: 2.5 msec.
• Process data width: 32 bit
• IO-Link data storage: yes
• Block parameterization: yes
IO-Link download
http://www.endress.com/download
• Select "Software" as the media type.
• Select "Device Driver" as the software type. Select IO-Link (IODD).
• In the "Text Search" field enter the device name.
https://ioddfinder.io-link.com/
Search by – Manufacturer – Article number – Product type

7.1.2 Operating concept

Operation with an operating menu is based on an operation concept with "user roles" .
User role Meaning
Operator (display level)
Maintenance (user level)
Operators are responsible for the devices during normal "operation". This is usually limited to reading process values either directly at the device or in a control room. Should an error occur, these users simply forward the information on the errors but do not intervene themselves.
Service engineers usually work with the devices in the phases following device commissioning. They are primarily involved in maintenance and troubleshooting activities for which simple settings have to be made on the device. Technicians work with the devices over the entire life cycle of the product. Thus, commissioning and advanced settings and configurations are some of the tasks they have to carry out.
24 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Operation options
2
E
54
3
1

7.1.3 Structure of the operating menu

The menu structure has been implemented according to VDMA 24574-1 and complemented by Endress+Hauser-specific menu items.
User role Submenu Meaning/use
Operator (display level)
Maintenance (user level)
For an overview of the operating menu, see →  51 and →  54
Display/operat. Display of measured values, fault and information messages
Parameters on the topmost menu level.
EF The submenu "EF" (Extended Functions) contains additional
DIAG Contains all the parameters that are needed to detect and analyze
Contains all the parameters that are needed to commission measuring operations. A wide range of parameters, which can be used to configure a typical application, is available at the start. After making settings for all these parameters, the measuring operation should be completely configured in the majority of cases.
parameters which allow more accurate configuration of the measurement, conversion of the measured value and scaling of the output signal.
operating errors.

7.2 Operation with local display

7.2.1 Overview

A 1-line liquid crystal display (LCD) is used for display and operation. The local display shows measured values, fault messages and information messages and therefore supports the user through each operating step.
The display is fixed to the housing and can be electronically rotated 180° (see parameter description for "DRO" →  73). This ensures optimum readability of the local display and allows the device to be mounted upside down also.
During measuring operation, the display shows measured values, fault messages and notice messages. In addition, it is possible to switch to menu mode via the operating keys.
A0022121
1 Operating keys 2 Status LED 3 Switch output LEDs 4 Measured value 5 Unit
The second switch output is not used for the device version with current output.
Endress+Hauser 25
Operation options Ceraphant PTC31B, PTP31B, PTP33B IO-Link

7.2.2 Information on the operational states

Operational states Function of status-LED and onsite display
Operation • Status LED is lit green
• LEDs of switch output 1 and switch output 2 signal the status of each switch output
• No activity of LED for switch output 2 if current output is active
• White background lighting
Problem • Status LED lit steady red
• Red display background
• LED of switch output 1 and switch output 2 off (switch output is deactivated)
Warning • Status LED flashing red
• White display background
• LEDs of switch output 1 and switch output 2 signal the status of each switch output
For Device Search • The green LED is lit (= operational) on the device and starts to flash with increased
luminosity. Flash frequency   
• LEDs of switch output 1 and switch output 2 signal the status of each switch output
• Display background depending on the device status
IO-Link communication
• Status LED flashes green as per IO-Link specification (regardless of measuring operation, error or warning). Flash frequency
• Display background depending on the device status
• The state of switch output 1 is also indicated via the LED of switch output 1 at the same time as the process data are displayed

7.3 General value adjustment and rejection of illegal entries

Parameter (not numerical value) is flashing: parameter can be adjusted or selected.
When adjusting a numerical value: the numerical value does not flash. The first digit of the numerical value starts to flash only when the  key is pressed by way of confirmation. Enter the desired value with the  or  key and press the  key to confirm. Following confirmation, the data are recorded directly and are active. – Entry is OK: value is accepted and shown for one second on the display against a white
background.
– Entry is not OK: the message "FAIL" appears for one second on the display against a red
background. The value entered is rejected. In the event of an incorrect setting which affects the TD, an diagnostic message is displayed.

7.4 Navigation and selection from list

The capacitive operating keys are used for navigation in the operating menu and to select an option from a picklist.
Operating key(s) Meaning
• Navigate downwards in the picklist
A0017879
A0017880
A0017881
• Edit the numerical values or characters within a function
• Navigate upwards in the picklist
• Edit the numerical values or characters within a function
• Confirm entry
• Jump to the next item
• Select a menu item and activate the edit mode
• The key lock function (KYL) is accessed by pressing the key for longer than 2 seconds
26 Endress+Hauser
Ceraphant PTC31B, PTP31B, PTP33B IO-Link Operation options
Operating key(s) Meaning
Simultaneously ESC functions:
• Exit edit mode for a parameter without saving the changed value.
• You are in a menu at a selection level. Each time you press the keys simultaneously, you
A0017880
go up a level in the menu.
• Long ESC: press the keys for longer than 2 seconds
A0017879
and
Endress+Hauser 27
Operation options Ceraphant PTC31B, PTP31B, PTP33B IO-Link

7.5 Locking and unlocking operation

The device features
• Automatic key locking
• Parameter settings lock.
Key locking is indicated on the local display by "E > 2".
Locking of the parameter settings is indicated as soon as an attempt is made to change a parameter.

7.5.1 Disabling the key lock

The keys are locked automatically if the device remains at the topmost menu level (display of pressure measurement value) for 60 seconds.
Call up the key lock function (KYL)
1. Press the  key for at least 2 seconds and then release it
2. By confirming with  "ON" is displayed
3. Use  and  to toggle between "ON" and "OFF"
4. Key locking is disabled as soon as  is pressed to confirm "OFF"
The display changes to the main value level (topmost menu level) if the  key is pressed briefly. The display changes to the key locking if the  key is pressed for at least 2 seconds.
If in the case of "KYL", "ON" or "OFF", more than 10 seconds elapse without a key being pressed, you return to the topmost menu level with active key locking.
The function can be accessed anytime outside the main measured value display and within the operating menu, i.e. if the  key is pressed for at least 2 seconds key locking can be performed anytime at any menu item. Locking is effective immediately. If you quit the context menu, you will return to the same point from which key locking was selected.

7.5.2 Locking and unlocking parameter settings

The device settings can be protected from unauthorized access.
COD parameter: define the locking code
0000 Device is permanently unlocked (factory setting)
0001-9999 Device is locked
LCK parameter: unlock parameter locking (enter the COD)
If parameters are locked, the word "LCK" appears on the local display as soon as an attempt is made to change a parameter.
Examples:
Locking the device with a customer-specific code
1. EF → ADM → COD
2. Enter a COD not equal to 0000 (value range: 0001 to 9999)
3. Wait 60 seconds or restart the device
4. Parameters are locked (protected against changes)
Changing a parameter when the device is locked (taking the example of STL)
1. STL, LCK is displayed
28 Endress+Hauser
Loading...
+ 64 hidden pages