A terminal to which DC voltage is applied or through which direct current flows.
A0011197
Alternating current
A0011198
A terminal to which alternating voltage (sine-wave) is applied or through which alternating current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
A0011200
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0011199
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential equalization
A0011201
line or a star grounding system depending on national or company codes of practice.
Tool symbols
Symbol
Meaning
Torx screwdriver
A0013442
Flat blade screwdriver
A0011220
Phillips head screwdriver
A0011219
Allen key
A0011221
Hexagon wrench
A0011222
Symbols for certain types of information
Symbol
Meaning
Allowed
Indicates procedures, processes or actions that are allowed.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
Reference to page
Refers to the corresponding page number.
A0011195
Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196
Endress+Hauser3
Page 4
Symbols in graphics
,…,
-
.
SymbolMeaning
1, 2, 3,...
A, B, C, ...
A-A, B-B, C-C, ...
Item numbers
Series of steps
Views
Sections
Flow direction
A0013441
Hazardous area
Indicates a hazardous area.
A0011187
Safe area (non-hazardous area)
Indicates a non-hazardous location.
A0011188
Function and system design
Proline t-mass A 150
Measuring principle
Measuring system
The thermal measuring principle is based on the cooling of a heated resistance thermometer (PT100), from
which heat is extracted by the passing gas. The gas passes two PT100 resistance thermometers in the
measurement section. One of these is used in the conventional way as a temperature probe, while the other
serves as a heating element. The temperature probe monitors and records the effective process temperature
while the heated resistance thermometer is kept at a constant differential temperature (compared to the
measured gas temperature) by controlling the electrical current used by the heating element. The greater the
mass current passing over the heated resistance thermometer, the greater the extent to which cooling takes
place and therefore the stronger the current required to maintain a constant differential temperature. This means
that the heat current measured is an indicator of the mass flow rate of the gas.
A0016823
The device consists of a transmitter and a sensor.
One device version is available: compact version comprising transmitter and sensor.
Transmitter
t-mass 150
Materials:
Aluminum coating AlSi10Mg
Configuration:
• Four-line local display with key operation and guided menu ("Setup") for
applications
• Operating tools (e.g. FieldCare)
A0015480
Other special features:
May also be ordered without local display
4Endress+Hauser
Page 5
Proline t-mass A 150
Sensor
t-mass A
Characteristic values
Measured variableDirect measured variables
• Mass flow
• Gas temperature
Calculated measured variables
• Corrected volume flow
• FAD (free air delivery) volume flow
Measuring range
The available measuring range depends on the choice of gas, the size of the pipe and the use of a flow conditioner.
The measuring device is calibrated with air (under ambient conditions) and the value is converted in order to
adapt it to the customer's gas if necessary.
To obtain information on other gases and process conditions, please contact your Endress+Hauser sales
office.
To calculate the measuring range with and without a flow conditioner (option L (®ä 12)
(®ä 15)), use the Applicator (®ä 31) product selection tool.
The following tables list the ranges available for air (without flow conditioner).
Measuring range "Calibration flow", option G and H (®ä 12)
SI units for EN (DIN) flange versions
DN
[mm]min.Max.min.Max.min.Max.
150.5530.38410.443
2522001.51551.6164
4065554.64294.9453
50109107.77048.2744
[kg/h][Nm3/h] at 0 °C (1.013 bar a)[Nm3/h at 15 °C (1.013 bar a)
US units for ASME flange versions
DN
[in]min.Max.min.Max.min.Max.
½1.11160.23240.2425
14.44400.9911.096
1½13.212202.72522.9266
222.020024.54134.8436
[lb/h][Scf/min] at 32 °F (14.7 psi a)[Scf/min] at 59 °F (14.7 psi a)
Endress+Hauser5
Page 6
Proline t-mass A 150
Measuring range "Calibration flow" option K (®ä 12)
SI units for EN (DIN) flange versions
DN[kg/h][Nm3/h] at 0 °C (1.013 bar a)[Nm3/h at 15 °C (1.013 bar a)
[mm]min.Max.min.Max.min.Max.
150.5800.38620.2465
2523001.52321.0245
4068334.66442.3681
501013657.710564.81116
US units for ASME flange versions
DN
[in]min.Max.min.Max.min.Max.
½1.11740.23360.2438
14.46600.91361.0144
1½13.218302.73782.9399
222.030034.56204.8656
[lb/h][Scf/min] at 32 °F (14.7 psi a)[Scf/min] at 59 °F (14.7 psi a)
Operable flow range
Over 100:1 (over 150:1 for calibration option code K).
Even in the extended measuring range (above the calibrated end value), the flow rate is captured and provided
as an output signal. However, the extended range is not subject to the specified measuring uncertainty.
Output
Output signalCurrent output
Current output
Maximum output values
Load
Resolution
Damping
Assignable measured
variables
4-20 mA HART, active
• DC 24 V (no flow)
• 22 mA
If the option Defined value is selected in the Failure mode parameter :
22.5 mA
0 to 750 Ω
16 Bit or 0.38 µA
Adjustable: 0 to 999 s
• Mass flow
• Corrected volume flow
• FAD volume flow
• Temperature
Pulse/frequency/switch output
Function
Version
Maximum input values
Voltage drop
Pulse output
Can be set to pulse, frequency or switching output
Passive, open collector
• DC 30 V
• 25 mA
For 25 mA: £ DC 2 V
6Endress+Hauser
Page 7
Proline t-mass A 150
Pulse width
Pulse value
Assignable measured
variables
Frequency output
Maximum frequency
Damping
Pulse/pause ratio
Assignable measured
variables
Switching output
Switching behavior
Switching delay
Number of switching cycles
Assignable functions
Adjustable: 0.5 to 2000 ms ® pulse rate: 0 to 1000 Pulse/s
Adjustable
• Mass flow
• Corrected volume flow
• FAD volume flow
Adjustable: 0 to 1000 Hz
Adjustable: 0 to 999 s
1:1
• Mass flow
• Corrected volume flow
• FAD volume flow
• Temperature
Binary, conductive or non-conductive
Adjustable: 0 to 100 s
Unlimited
• Off
• On
• Diagnostic behavior
• Limit value
• Status
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
Failure mode
Minimum alarm
Maximum alarm
Adjustable value
Can be selected (as per NAMUR recommendation NE 43)
3.6 mA
22 mA
3.59 to 22.5 mA
Pulse/frequency/switch output
Pulse output
Failure mode
Frequency output
Failure mode
Switching output
Failure mode
Choose from:
• Actual value
• No pulses
Choose from:
• Actual value
• Defined value: 0 to 1250 Hz
• 0 Hz
Choose from:
• Current status
• Open
• Closed
Local display
Plain text display
With information on cause and corrective action
Endress+Hauser7
Page 8
Status signal as per NAMUR recommendation NE 107
Operating tool
• Via digital communication: HART protocol
• Via service interface
Proline t-mass A 150
Plain text display
Low flow cut off
Galvanic isolation
The switch point for low flow cut off is programmable.
The following connections are galvanically isolated from each other:
• Outputs
• Voltage supply
Protocol-specific dataHART
Manufacturer ID
Device type ID0x66
HART protocol revision6.0
Device description files (DTM,
DD)
HART loadMin. 250 Ω
Dynamic variablesThe measured variables can be freely assigned to the dynamic variables.
With information on cause and corrective action
Additional information on remote operation(®ä 28)
0x11
Information and files under:
www.endress.com
Measured variables for PV (primary dynamic variable)
• Mass flow
• Corrected volume flow
• FAD volume flow
• Temperature
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Mass flow
• Corrected volume flow
• FAD volume flow
• Temperature
• Totalizer
8Endress+Hauser
Page 9
Proline t-mass A 150
4
1
2
3
12
23
2224
2526
27
Power supply
Terminal assignmentTransmitter
Connection version 4-20 mA HART, pulse/frequency/switching output
1Supply voltage
2Signal transmission: Pulse/frequency/switching output
3Signal transmission: 4-20 mA HART
4Ground terminal for cable shield
A0017178
Power consumption
Supply voltage
Order characteristic for
"Power supply"
Option DDC 24 V (18 to 30 V)
1 (L+)2 (L-)
Terminal numbers
Signal transmission
Order characteristic for
"Output"
Option A4-20 mA HART active-
Option B4-20 mA HART activePulse/frequency/switch output
Option K-Pulse/frequency/switch output
Output 1Output 2
26 (+)27 (-)24 (+)25 (-)
Terminal numbers
Supply voltage
DC 24 V (18 to 30 V)
The power supply circuit must comply with SELV/PELV requirements.
• Error messages (incl. total operated hours) are stored.
Electrical connectionConnecting the transmitter
Maximum current
consumption
185 mA
Maximum switch-on
current
< 2.5 A
1
Cable entry for supply voltage
2Cable entry for signal transmission
Connection examples
å 1Connection example for current output, 4-20 mA active
1
Control system (e.g. PLC)
2
Analog display unit: observe maximum load (®ä 6)
A0017179
A0016960
10Endress+Hauser
Page 11
Proline t-mass A 150
4
4...20 mA
+
–
5
2
1
3
6
+
_
1
+
_
12345
2
+
–
+
–
3
1
+
_
+
_
2
+
_
3
å 2Connection example for current output, 4-20 mA HART active
1Control system (e.g. PLC)
2
Observe cable specification (®ä 12)
3Connection for Field Communicator 375/475 or Commubox FXA191/195
4
Resistor for HART communication (³ 250 W): observe maximum load (®ä 6)
5
Analog display unit: observe maximum load (®ä 6)
A0016800
Potential equalization
å 3Connection example for pulse/frequency output (passive)
1
Automation system with pulse/frequency input (e.g. PLC)
2
Power supply (®ä 12)
3
Transmitter: Observe input values (®ä 6)
å 4Connection example for switching output (passive)
Control system with switch input (e.g. PLC)
1
2
Power supply (®ä 12)
3
Transmitter: Observe input values (®ä 6)
No special measures for potential equalization are required.
A0016801
A0016802
Terminals
Cable entries
Endress+Hauser11
Plug-in screw terminals for specified wire cross-sections
•
Cable gland: M20 × 1.5 with cable Æ 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
– NPT ½"
– G ½"
Page 12
Cable specificationWire cross-sectional area
0.5 to 1.5 mm2 (21 to 16 AWG)
Permitted temperature range
•
–40 °C (–40 °F)...³ 80 °C (176 °F)
•
Minimum requirement: cable temperature range ³ ambient temperature + 20 K
Signal cable
Current output
For 4-20 mA HART: Shielded cable recommended. Observe grounding concept of the plant.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Supply voltage cable
Standard installation cable is sufficient.
Proline t-mass A 150
Reference operating
conditions
Maximum measured error
Performance characteristics
• Calibration systems traceable to national standards
• Accredited in accordance with ISO/IEC 17025
•
Air controlled to 24 °C ± 0.5 °C (75.2 °F ± 0.9 °F) at atmospheric pressure
•
Humidity controlled < 40 % RH
o.r. = of reading; o.f.s. = of full scale value
• The full scale value depends upon the nominal diameter of the measuring device and the max. flow of
the calibration rig.
•
Full scale values of the calibrated measuring range.(®ä 5)
12Endress+Hauser
Page 13
Proline t-mass A 150
0 10
[% kg/h]
±10
0
5080
[%]
90 100
±5
±15
20 30 4060 70
±20
110 120 130 140 150
[% lb/h]
H
G
K, L
A0016921
å 5Maximum measured error (% mass flow) as % of measured value/full scale value. G, H, K, L: Order code options
for "Calibration flow", see the following table
Order code option
for "Calibration
flow"
K
L
H• Q = 20 to 100 %
GQ = 1 to 100 %
AccuracyDescription
• Q = 100 to 150 %:
from ±3 %to ±6.5 % of the current
measured value increasing linearly as
expressed in the following equation:
±3 ± (Xn -100) × 0.07[% o.r.]
(100 %< Xn £150 %; Xn = current flow
as a % o.f.s. )
• Q = 15 to 100 %:
±3 % of current measured value
• Q = 1 to 15 %
±0.45 % o.f.s.
(all data under reference conditions)
±4 % of current measured value
• Q = 1 to 20 %
±0.8 % o.f.s.
(all data under reference conditions)
±5 % o.f.s.
(under reference conditions)
Accuracy of outputs
The measuring device is calibrated and adjusted on an
accredited and traceable calibration rig . The accuracy is
certified with a calibration protocol.
The measuring performance of the device is tested, and a
verification protocol confirms that the device measures
within the specified tolerance.
This version is subject to neither a calibration nor a
verification of measuring performance.
Current output
Repeatability
Response time
Influence of medium pressure
Accuracy
±0.5 % of value for velocities > 1.0 m/s (3.3 ft/s)
Typically < 3 s for 63 % of a given step change (in both directions)
Air: 0.35 % of value per bar (0.02 % per psi) of process pressure change
Max. ±0.05 % o.f.s. or ±10 µA
Endress+Hauser13
Page 14
Installation
a
Proline t-mass A 150
Mounting location
Orientation
Thermal measuring devices require a fully developed flow profile as a prerequisite for correct flow
measurement. For this reason, please pay attention to the following points and document sections
when installing the device:
• Avoid flow disturbances, as the thermal measuring principle reacts sensitively to them.
• Take measures to avoid condensation (e.g. condensation trap, thermal insulation etc.).
The direction of the arrow on the sensor helps you to install the sensor according to the flow direction (direction
of medium flow through the piping).
Vertical orientation
A0017337
Horizontal orientation, transmitter head up
A0015589
Horizontal orientation, transmitter head
down
A0015590
Inclined mounting position, transmitter head
down
1)
2)
3)
Requirement for pipework
A0015773
1)In the case of saturated or unclean gases, upward flow in a vertical pipe section is preferred to minimize condensation
or contamination.
2)Suitable only for clean and dry gases. If buildup or condensate are always present: Mount the sensor in an inclined
position.
3)
Select inclined mounting position (a = approx. 135°) if the gas is very wet or saturated with water.
The measuring device must be professionally installed, and the following points must be observed:
• Piping must be professionally welded.
• Seals must be sized correctly.
• Flanges and seals must be correctly aligned.
• The internal pipe diameter on the inlet side must match the internal diameter of the process connection
ordered. The maximum permitted deviation between the internal diameters is:
1 mm (0.04 in)
• Following installation, the pipe must be free from dirt and particles in order to avoid damage to the sensors.
Further information ® ISO standard 14511
A0005103
Correctly aligned flanges and seals
14Endress+Hauser
Page 15
Proline t-mass A 150
15 × DN
2 × DN
1
4
2
6
3
15 × DN
2 × DN
15 × DN
2 × DN
20 × DN
2 × DN
35 × DN
2 × DN
5
50 × DN
2 × DN
PT
2…5 × DN
TT
Inlet and outlet runs
A0005105
Incorrectly sized sealIncorrectly aligned flanges and seals Internal diameter of pipe does not correspond to
A0005106
internal diameter of process connection ordered
A0005104
The thermal measuring principle is sensitive to disturbed flow conditions.
• As a general rule, the measuring device should always be installed as far away as possible from any flow
disturbances. For further information, please refer to ® ISO 14511.
• If possible, the sensor should be installed upstream from valves, T-pieces, elbows etc. To attain the specified
level of accuracy of the measuring device, the below mentioned inlet and outlet runs must be maintained at
minimum. If there are several flow disturbances present, the longest specified inlet run must be maintained.
Recommended inlet and outlet runs (without flow conditioner)
Outlet run for pressure or temperature transmitter
If a pressure or temperature measuring device is installed downstream of the measuring device, make sure there
is sufficient distance between the two devices.
A0015548
Pressure measuring device
PT
TT Temperature transmitter
Flow conditioner (19 hole) for use with fixed flanges
If the inlet runs cannot be observed, the use of a flow conditioner is recommended.
Endress+Hauser15
Page 16
Proline t-mass A 150
2 × DN5 × DN
1
2
2
3
4
1
1
1
A0015547
å 6Recommended inlet and outlet runs when using a flow conditioner
This is a special Endress+Hauser design which was developed for the sensor t-mass A 150 (DN 40 to 50 / 1
½ to 2"). The arrangement of the individual screw holes and their diameter means that the flow conditioner
can be used for different flange pressure ratings.
The flow conditioner and the seals are installed between the pipe flange and the measuring system. To ensure
correct centering of the flow conditioner, use only standard screws which match the screw holes .
Please note that the flow conditioner must be mounted in such a way that the alignment notch is pointing in
the direction of the transmitter. Incorrect installation could have a negative effect on the measurement accuracy.
A0005116
1
Flow conditioner
2Seal
3Alignment notch
4Correctly align the alignment notch and transmitter.
• Not suitable for lap joint flange or threaded versions!
• Order the sensor and the flow conditioner together to ensure that they are calibrated together. Joint
calibration guarantees optimum performance. Ordering the flow conditioner separately and using it
with the device will further increase measurement uncertainty.
• The use of flow conditioners from other suppliers will affect the flow profile and pressure drop and will
have an adverse effect on performance.
• Screws, nuts, seals etc. are not included in the scope of supply and must be provided by the customer.
16Endress+Hauser
Page 17
Proline t-mass A 150
Dp = K
g
2
r
D
4
1
Pressure loss
The pressure loss for flow conditioners is calculated as follows:
Dp = Pressure loss [mbar]
r = Density [kg/m3]
K = Constant 1876 (SI units) or 8.4 · 10-7 (US units)
–20 to +60 °C (–4 to +140 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
Avoid direct sunlight, particularly in warm climatic regions.
–40 to +80 °C (–40 to +176 °F), preferably at +20 °C (+68 °F)
Transmitter
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure
Sensor
IP66/67, type 4X enclosure
As per IEC/EN 60068-2-31
Acceleration up to 2 g, 10 to 150 Hz, as per IEC/EN 60068-2-6
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21).
Details are provided in the Declaration of Conformity.
Process
Medium temperature range
Pressure-temperature ratings
Endress+Hauser17
Sensor
–40 to +100 °C (–40 to +212 °F)
The following material load diagrams refer to the entire device and not just the process connection.
Page 18
Flange connection (fixed flange) as per EN 1092-1 (DIN 2501)
[°F]
[°C]1008060400
-30
35
40
[bar][psi]
400
500
600
300
PN 40
201030507090
30
25
20
45
-10-20
-40
160 1801401008060400-40200-2020120220
0
10
20
[bar]
-40
-30
-20
-10 0
10 20 30 40
[°C]
-20
0
-40
20 40
60
80 100 120
[°F]
300
400
500
600
200
100
0
[psi]
50
60 70 80 90
30
40
Cl. 300
140 160 180
200
100
220
5
15
25
35
0
5
10
[bar]
-40
-30
-20
-10 0
10 20 30 40
[°C]
-20
0
-40
20 40
60
80 100 120
[°F]
200
100
50
0
[psi]
50
60 70 80 90
140 160 180
200
100
220
PN 10
å 7Flange material 1.4404
Flange connection (fixed flange) as per ASME B16.5
Proline t-mass A 150
A0016015
å 8Flange material 316L
Flange connection (lap joint flange) as per EN 1092-1 (DIN 2501)
18Endress+Hauser
å 9Flange material 1.4301
A0016016
A0016017
Page 19
Proline t-mass A 150
0
10
20
[bar]
-40
-30
-20
-10 0
10 20 30 40
[°C]
-20
0
-40
20 40
60
80 100 120
[°F]
300
200
100
0
[psi]
50
60 70 80 90
140 160 180
200
100
220
5
15
25
400
PN16
0
10
20
[bar]
-40
-30
-20
-10 0
10 20 30 40
[°C]
-20
0
-40
20 40
60
80 100 120
[°F]
300
200
100
0
[psi]
50
60 70 80 90
140 160 180
200
100
220
5
15
25
400
Cl.150
[°F]
[°C]1008060400
-30
35
40
[bar][psi]
400
500
600
300
201030507090
30
25
20
45
-10-20
-40
160 1801401008060400-40200-2020120220
Flange connection (lap joint flange) as per EN 1092-1 (DIN 2501)
A0016018
å 10 Flange material S235JR/1.0038
Flange connection (lap joint flange) as per ASME B16.5
A0016019
å 11 Flange material A105
External thread as per EN (DIN), ASME
A0017627
å 12 Flange material 1.4404/316L
Flow limit
See "Measuring range"(®ä 5) section
The velocity in the measuring tube should not exceed 70 m/s (230 ft/s).
Pressure loss
Endress+Hauser19
Negligible (without flow conditioner).
For a precise calculation, use the Applicator.
Page 20
Proline t-mass A 150
F
E
B
A
C
D
L
+1,5 (+0.06)
-2,0 (-0.08)
System pressure
Thermal insulation
Sensor
Depending on the version, please note the details on the name plate .
Max. 40 bar g (580 psi g)
If the gas is very humid or saturated with water, the pipe and the sensor housing should be insulated to prevent
water droplets condensing on the transducer.
A0015521
Mechanical construction
Design, dimensionsCompact version
Dimensions in SI units
DN
[mm]
1514613312910915392245
2514613312911515392245
40146133129110200120320
50146133129116250150400
1)
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
F
[mm]
A0015522
L
[mm]
20Endress+Hauser
1)For version without local display: values - 7 mm
Page 21
Proline t-mass A 150
C
D
A
B
E
Dimensions in US units
DN
[in]
½5.755.245.084.296.023.629.65
15.755.245.084.536.023.629.65
1½5.755.245.084.337.874.7212.6
25.755.245.084.579.845.9115.75
1)For version without local display: values -0.28 in
A
[in]
1)
B
[in]
C
[in]
D
[in]
E
[in]
F
[in]
Process connections in SI units
Fixed flanges as per EN (DIN), ASME
L
[in]
Fixed flange as per EN 1092-1 / B2 / PN40
DN
[mm]
1595654 × Ø141615.8
25115854 × Ø141827.9
401501104 × Ø181842.8
501651254 × Ø182054.8
Fixed flanges as per ASME B16.5 / Cl 300
DN
[in]
½9566.74 × Ø15.92315.8
112588.94 × Ø19.12727.9
1½155114.34 × Ø22.23142.8
21651278 × Ø19.13454.8
A
[mm]
A
[mm]
B
[mm]
B
[mm]
[mm]
C
[mm]
C
D
[mm]
D
[mm]
A0017274
E
[mm]
E
[mm]
Endress+Hauser21
Page 22
Proline t-mass A 150
C
D
A
B
F
E
Lap joint flanges as per EN (DIN), ASME
Lap joint flange, stamping plate as per EN 1092-1/ PN 10
DN
[mm]
1595654 × Ø13.511.534.915.8
25115854 × Ø13.51650.827.9
401501104 × Ø17.51873.042.8
501651254 × Ø17.52092.154.8
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
A0017272
F
[mm]
Lap joint flange as per EN 1092-1/ PN 16
DN
[mm]
1595654 × Ø141434.915.8
25115854 × Ø141650.827.9
401501104 × Ø181873.042.8
501651254 × Ø182092.154.8
Lap joint flanges as per ASME B16.5 / Cl 150
DN
[in]
½9060.34 × Ø15.91634.915.8
111079.44 × Ø15.91850.827.9
1½12598.44 × Ø15.92373.042.8
2150120.74 × Ø19.12692.154.8
A
[mm]
A
[mm]
B
[mm]
B
[mm]
C
[mm]
C
[mm]
D
[mm]
D
[mm]
E
[mm]
E
[mm]
F
[mm]
F
[mm]
22Endress+Hauser
Page 23
Proline t-mass A 150
ABC
1:16
C
D
A
B
E
External thread as per EN (DIN), ASME
R external thread as per EN 10226-1, ISO 7-1
DN
[mm]
15R ½8.215.8
25R 110.426.7
40R 1½12.740.9
50R 215.952.5
A
[in]
B
[mm]
A0017273
C
[mm]
NPT external thread as per ASME B1.20.1
DN
[in]
½½ NPT8.1315.8
11 NPT10.1626.7
1½1½ NPT10.6740.9
22 NPT11.752.5
A
[in]
Process connections in US units
Fixed flanges as per ASME
B
[mm]
C
[mm]
Fixed flanges as per ASME B16.5 / Cl 300
DN
[in]
½3.742.634 × Ø5/80.910.62
14.923.54 × Ø3/41.061.1
A
[in]
B
[in]
C
[in]
D
[in]
Endress+Hauser23
A0017274
E
[in]
Page 24
Proline t-mass A 150
C
D
A
B
F
E
ABC
1:16
Fixed flanges as per ASME B16.5 / Cl 300
DN
[in]
1½6.14.54 × Ø7/81.221.69
26.554 × Ø9/41.342.16
Lap joint flanges as per ASME
A
[in]
B
[in]
C
[in]
D
[in]
E
[in]
A0017272
Lap joint flanges as per ASME B16.5 / Cl 150
DN
[in]
½3.542.374 × Ø5/80.631.370.62
14.333.134 × Ø5/80.712.001.10
1½4.923.874 × Ø5/80.912.871.69
25.914.764 × Ø3/41.023.632.16
A
[in]
B
[in]
C
[in]
D
[in]
E
[in]
External thread as per ASME B1.20.1
F
[in]
A0017273
NPT external thread as per ASME B1.20.1
DN
[in]
½½ NPT0.320.62
11 NPT0.41.05
1½1½ NPT0.421.61
22 NPT0.462.07
A
[in]
B
[in]
C
[in]
24Endress+Hauser
Page 25
Proline t-mass A 150
D2
D1
ÆF
S
A
R
Q
B
D3
D2
D1
ÆF
Flow conditioner as per EN(DIN)/ASME
A0015542
Dimensions in SI units
As per EN(DIN) / PN 40
DN
[mm][mm][mm][mm][mm][mm][mm][kg]
40A1351081752.57.00.7
50A1501231752.58.51.0
TypeD1D2FQRSWeight
As per ASME / Cl 300 Sched 40
DN
[mm][in][mm][mm][mm][mm][mm][mm][mm][kg]
401 ½B140109.521.552.56.50.9
502B150122115.51952.58.51.3
TypeD1D2D3FQRSWeight
Dimensions in US units
As per ASME / Cl 300 Sched 40
DN
[in][in][in][in][in][in][in][in][lbs]
1 ½B5.54.31–0.850.20.10.261.9
2B5.94.804.550.70.20.10.332.8
TypeD1D2D3FQRSWeight
WeightWeight in SI units
Endress+Hauser25
Compact version
DN
[mm]
154.03.94.13.23.42.6
255.54.85.03.54.32.6
Fixed flangeLap joint flangeThreaded
CL300PN40PN16PN10CL150
Weight [kg]
version
Page 26
Proline t-mass A 150
DN
[mm]
407.97.07.54.96.13.1
509.99.39.45.98.03.8
Fixed flangeLap joint flangeThreaded
CL300PN40PN16PN10CL150
Weight [kg]
Weight in US units
Compact version
DN
[mm]
158.88.69.07.17.55.7
2512.110.611.07.79.55.7
4017.415.416.510.813.56.8
5021.820.520.713.017.68.4
Fixed flangeLap joint flangeThreaded
CL300PN40PN16PN10CL150
Weight [lbs]
version
version
MaterialsTransmitter housing
• Order characteristic for "Housing", option A: aluminum costing AlSi10Mg
• Window material: glass
Sensor
Process connections
Fixed flanges: EN 1092-1/ ASME B16.5
• Stainless steel 1.4404 as per EN 10222-5
• Stainless steel F316/F316L as per ASTM A182
Lap joint flanges: EN 1092-1/ ASME B16.5
• Stub end:
– Stainless steel 1.4404/1.4435 as per EN 10216-5; cold worked
– Stainless steel 316L as per ASTM A312; cold worked
• Lap-joint flange:
– Carbon steel, zinc-plated 1.0038 as per EN 10025-2
– Stainless steel 1.4301/1.4307 as per EN 10028-7
Threaded version: R external thread as per EN 10226-1, ISO 7/1 and NPT external thread as per ASME B1.20.1
• Stainless steel 1.4404/1.4435 as per EN 10216-5
• Stainless steel 316L as per ASTM A312
Measuring tube
• DN 15(½ in)
– Stainless steel 1.4404 as per EN 10272/EN10216-5
– Stainless steel 316/316L as per ASTM A479/ ASTM A312
• DN 25 to 50 (1 to 2 in)
– Stainless steel 1.4404 as per EN 10216-5
– Stainless steel 316/316L as per ASTM A312
Transducer
• Stainless steel 1.4404/1.4435 as per EN 10216-5/ EN10272/ EN 10028-7
• Stainless steel 316L as per ASTM A269/ ASTM A479/ ASTM A240
26Endress+Hauser
Page 27
Proline t-mass A 150
Cable entries
Order characteristic for "Housing", option A: compact, aluminum coating
• Remedial information is integrated in plain text
• Diverse simulation options and optional line recorder functions
Endress+Hauser27
Page 28
Local operation"Display; Operation" Order code option C
Esc
1
1
2
35
46
7
1 Display module (pushbutton operation)
Display elements
• 4-line display
• Format for displaying measured variables and status variables can be individually configured
•
Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
Operating elements
Local operation with 3 push buttons (
, , E)
Proline t-mass A 150
A0017279
Additional functionality
• Data backup function
The device configuration can be saved in the display module.
• Data comparison function
The device configuration saved in the display module can be compared to the current device configuration.
• Data transfer function
The transmitter configuration can be transmitted to another device using the display module.
Remote operationVia HART protocol
This communication interface is present in the following device version:
• Order characteristic for "Outlet", option A: 4-20 mA HART
• Order characteristic for "Outlet", option B: 4-20 mA HART, pulse/frequency/switching output
A0017373
å 13 Options for remote operation via HART protocol
Control system (e.g. PLC)
1
2Field Communicator 475
3Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
4Commubox FXA195 (USB)
5Field Xpert SFX100
6VIATOR Bluetooth modem with connecting cable
7Transmitter
28Endress+Hauser
Page 29
Proline t-mass A 150
123
E
+
–
Via service interface (CDI)
A0017253
1Service interface (CDI) of the measuring device
2Commubox FXA291
3Computer with "FieldCare" operating tool
Languages
CE mark
C-Tick symbol
Ex approval
Can be operated in the following languages:
• Via local display:
English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Japanese, Chinese,
Korean, Bahasa (Indonesian), Vietnamese, Czech
The measuring system is in conformity with the statutory requirements of the applicable EC Directives. These
are listed in the corresponding EC Declaration of Conformity along with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
The measuring system meets the EMC requirements of the "Australian Communications and Media Authority
(ACMA)".
CSA
C
US
The following hazardous area versions currently available:
NI
Class 1, Division 2, Groups A, B, C and D T4 or Class I, Zone 2 IIC T4
Pressure Equipment Directive
The devices can be ordered with or without a PED approval. If a device with a PED approval is required, this
must be explicitly stated in the order.
• With the PED/G1/x (x = category) marking on the sensor nameplate, Endress+Hauser confirms compliance
with the "Essential Safety Requirements" specified in Annex I of the Pressure Equipment Directive 97/23/
EC.
• Devices bearing this marking (PED) are suitable for the following types of medium:
Media in Group 1 and 2 with a vapor pressure greater than, or smaller and equal to 0.5 bar (7.3 psi)
• Devices not bearing this marking (PED) are designed and manufactured according to good engineering
practice. They meet the requirements of Art.3 Section 3 of the Pressure Equipment Directive 97/23/EC.
The range of application is indicated in tables 6 to 9 in Annex II of the Pressure Equipment Directive.
Endress+Hauser29
Page 30
Proline t-mass A 150
Other standards and
guidelines
• EN 60529
Degrees of protection provided by enclosures (IP code)
• EN 61010-1
Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory
Procedures.
• IEC/EN 61326
Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC requirements)
• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.
• NAMUR NE 32
Data retention in the event of a power failure in field and control instruments with microprocessors
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with analog output
signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics
• NAMUR NE 105
Specifications for integrating fieldbus devices in engineering tools for field devices
• NAMUR NE 107
Status classification as per NE107
Ordering information
Your Endress+Hauser sales center can provide detailed ordering information and information on the extended
order code.
Comprises extended functions concerning the event log and the activation of the measured
value memory.
Event log:
• Memory volume is extended from 20 message entries (basic version) to up to 100 entries.
• Message entries are visualized via the local display or FieldCare.
Data logging (line recorder):
• Memory capacity for up to 1000 measured values is activated.
• 250 measured values can be output via each of the 4 memory channels. The recording
interval can be defined and configured by the user.
• Data logging is visualized via the local display or FieldCare.
Description
Order the t-mass A sensor and the flow conditioner together to ensure that they are
calibrated together. Joint calibration guarantees optimum performance. Ordering the flow
conditioner separately and using it with the device will further increase measurement
uncertainty.
Communication-specific
Accessories
Description
accessories
30Endress+Hauser
Page 31
Proline t-mass A 150
Commubox FXA195 HART For intrinsically safe HART communication with FieldCare via the USB interface.
For details, see "Technical Information" TI00404F
HART Loop Converter
HMX50
Wireless HART adapter
SWA70
Fieldgate FXA320Gateway for the remote monitoring of connected 4-20 mA measuring devices via a Web
Fieldgate FXA520Gateway for the remote diagnostics and remote configuration of connected HART measuring
Field Xpert SFX100Compact, flexible and robust industry handheld terminal for remote configuration and for
Is used to evaluate and convert dynamic HART process variables to analog current signals
or limit values.
For details, see "Technical Information" TI00429F and Operating Instructions
BA00371F
Is used for the wireless connection of field devices.
The WirelessHART adapter can be easily integrated into field devices and existing
infrastructures, offers data protection and transmission safety and can be operated in parallel
with other wireless networks with minimum cabling complexity.
For details, see Operating Instructions BA00061S
browser.
For details, see "Technical Information" TI00025S and Operating Instructions
BA00053S
devices via a Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions
BA00051S
obtaining measured values via the HART current output (4-20 mA).
For details, see Operating Instructions BA00060S
Service-specific accessories
Commubox FXA291Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser Common
Data Interface) and the USB port of a computer or laptop.
For details, see "Technical Information" TI00405C
Accessories
ApplicatorSoftware for selecting and sizing Endress+Hauser measuring devices:
W@MLife cycle management for your plant
Description
• Calculation of all the necessary data for identifying the optimum flowmeter: e.g. nominal
diameter, pressure loss, accuracy or process connections.
• Graphic illustration of the calculation results
Administration, documentation and access to all project-related data and parameters over
the entire life cycle of a project.
Applicator is available:
• Via the Internet: https://wapps.endress.com/applicator
• On CD-ROM for local PC installation.
W@M supports you with a wide range of software applications over the entire process: from
planning and procurement, to the installation, commissioning and operation of the
measuring devices. All the relevant device information, such as the device status, spare parts
and device-specific documentation, is available for every device over the entire life cycle.
The application already contains the data of your Endress+Hauser device. Endress+Hauser
also takes care of maintaining and updating the data records.
W@M is available:
• Via the Internet: www.endress.com/lifecyclemanagement
• On CD-ROM for local PC installation.
Endress+Hauser31
Page 32
FieldCareFDT-based plant asset management tool from Endress+Hauser.
It can configure all smart field units in your system and helps you manage them. By using
the status information, it is also a simple but effective way of checking their status and
condition.
For details, see Operating Instructions BA00027S and BA00059S
Proline t-mass A 150
System components
Standard documentation
Supplementary devicedependent documentation
AccessoriesDescription
Memograph M graphic
display recorder
The Memograph M graphic data manager provides information on all the relevant measured
variables. Measured values are recorded correctly, limit values are monitored and measuring
points analyzed. The data are stored in the 256 MB internal memory and also on a SD card
or USB stick.
For details, see "Technical Information" TI00133R and Operating Instructions
BA00247R
Documentation
The following document types are available:
• On the CD-ROM supplied with the device
•
In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download