Endress+Hauser Proline Prowirl F 200 Specifications

TI01333D/06/EN/03.19 71439415 2019-07-01
Products Solutions Services
Technical Information
Proline Prowirl F 200
Vortex flowmeter
Versatile flowmeter with wet steam detection and first-rate accuracy
Application
• Preferred measuring principle for wet/saturated/ superheated steam, gases & liquids (also cryogenic)
• Suitable for a wide range of applications; optimized for steam applications
Device properties
• Wet steam capabilities for DN 25 to 300 (1 bis 12")
• Industrial siphon design for pressure measurement
• Display module with data transfer function
• Robust dual-compartment housing
• Plant safety: worldwide approvals (SIL, Haz. area)
Your benefits
• Easy energy management – integrated temperature and pressure measurement for steam and gases
• Space-saving engineering – inlet run compensation
• Same accuracy down to Re 10 000 – most linear Vortex meter body
• Long-term stability – robust drift-free capacitive sensor
• Convenient device wiring – separate connection compartment
• Safe operation – no need to open the device due to display with touch control, background lighting
• Integrated verification – Heartbeat Technology

Table of contents

Proline Prowirl F 200
About this document ........................ 3
Symbols .................................... 3
Function and system design ................... 4
Measuring principle ............................ 4
Measuring system ............................. 8
Input ..................................... 9
Measured variable ............................. 9
Measuring range ............................. 10
Operable flow range ........................... 14
Input signal ................................ 15
Output .................................. 16
Output signal ............................... 16
Signal on alarm .............................. 17
Load ..................................... 18
Ex connection data ........................... 19
Low flow cut off ............................. 24
Galvanic isolation ............................ 24
Protocol-specific data .......................... 24
Power supply ............................. 26
Terminal assignment .......................... 26
Pin assignment, device plug ...................... 28
Supply voltage .............................. 29
Power consumption ........................... 30
Current consumption .......................... 30
Power supply failure .......................... 30
Electrical connection .......................... 30
Potential equalization ......................... 35
Terminals ................................. 35
Cable entries ............................... 35
Cable specification ............................ 35
Overvoltage protection ......................... 37
Electromagnetic compatibility (EMC) ............... 50
Process .................................. 50
Medium temperature range ...................... 50
Pressure-temperature ratings .................... 51
Nominal pressure of sensor ...................... 54
Pressure specifications ......................... 54
Pressure loss ............................... 54
Thermal insulation ........................... 54
Mechanical construction .................... 55
Dimensions in SI units ......................... 55
Dimensions in US units ......................... 68
Weight ................................... 75
Materials .................................. 79
Flange connections ........................... 83
Operability ............................... 83
Operating concept ............................ 83
Languages ................................. 83
Local operation .............................. 84
Remote operation ............................ 85
Service interface ............................. 87
Certificates and approvals ................... 87
CE mark ................................... 87
RCM-tick symbol ............................. 87
Ex approval ................................ 87
Functional safety ............................. 89
HART certification ............................ 90
FOUNDATION Fieldbus certification ................ 90
Certification PROFIBUS ......................... 90
Pressure Equipment Directive .................... 90
Experience ................................. 90
Other standards and guidelines ................... 90
Performance characteristics .................. 38
Reference operating conditions ................... 38
Maximum measured error ....................... 38
Repeatability ............................... 41
Response time .............................. 42
Influence of ambient temperature ................. 42
Installation ............................... 42
Mounting location ............................ 42
Orientation ................................ 42
Inlet and outlet runs .......................... 44
Length of connecting cable ...................... 46
Mounting the transmitter housing ................. 47
Special mounting instructions .................... 47
Environment .............................. 48
Ambient temperature range ..................... 48
Storage temperature .......................... 49
Climate class ............................... 49
Degree of protection .......................... 49
Vibration- and shock-resistance ................... 49
Ordering information ....................... 91
Product generation index ....................... 91
Application packages ....................... 91
Diagnostics functions .......................... 91
Heartbeat Technology ......................... 92
Wet steam detection .......................... 92
Wet steam measurement ....................... 92
Accessories ............................... 92
Device-specific accessories ...................... 93
Communication-specific accessories ................ 94
Service-specific accessories ...................... 95
System components ........................... 95
Supplementary documentation ............... 95
Standard documentation ........................ 96
Supplementary device-dependent documentation ....... 96
Registered trademarks ...................... 97
2 Endress+Hauser
Proline Prowirl F 200
A
1.

About this document

Symbols Electrical symbols

Symbol Meaning
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Communication symbols
Symbol Meaning
Wireless Local Area Network (WLAN)
Communication via a wireless, local network.
Symbols for certain types of information
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Visual inspection.
Symbols in graphics
Symbol Meaning
1, 2, 3, ... Item numbers
, 2., 3., … Series of steps
A, B, C, ... Views
A-A, B-B, C-C, ... Sections
Endress+Hauser 3
Symbol Meaning
-
.
K-Factor =
Pulses
Unit Volume [m³]
Hazardous area
Safe area (non-hazardous area)
Flow direction

Function and system design

Proline Prowirl F 200

Measuring principle

Vortex meters work on the principle of the Karman vortex street. When fluid flows past a bluff body, vortices are alternately formed on both sides with opposite directions of rotation. These vortices each generate a local low pressure. The pressure fluctuations are recorded by the sensor and converted to electrical pulses. The vortices develop very regularly within the permitted application limits of the device. Therefore, the frequency of vortex shedding is proportional to the volume flow.
A0033465
 1 Sample graphic
The calibration factor (K-factor) is used as the proportional constant:
Within the application limits of the device, the K-factor only depends on the geometry of the device. It is for Re > 10 000:
• Independent of the flow velocity and the fluid properties viscosity and density
• Independent of the type of substance under measurement: steam, gas or liquid The primary measuring signal is linear to the flow. After production, the K-factor is determined in
the factory by means of calibration. It is not subject to long-time drift or zero-point drift.
The device does not contain any moving parts and does not require any maintenance.
The capacitance sensor
The sensor of a vortex flowmeter has a major influence on the performance, robustness and reliability of the entire measuring system.
4 Endress+Hauser
A0003939-EN
Proline Prowirl F 200
1 2
The robust DSC sensor is:
• burst-tested
• tested against vibrations
• tested against thermal shock (thermal shocks of 150 K/s) The measuring device uses the tried-and-tested, capacitance measuring technology from
Endress+Hauser, which is already in use in over 450 000 measuring points worldwide. Thanks to its design, the capacitance sensor is also particularly mechanically resistant to temperature shocks and pressure shocks in steam pipelines.
Temperature measurement
The "mass" option is available under the order code for "Sensor version". With this option the measuring device can also measure the temperature of the medium.
The temperature is measured via Pt 1000 temperature sensors. These are located in the paddle of the DSC sensor and are therefore in the direct vicinity of the fluid.
Order code for "Sensor version; DSC sensor; measuring tube":
• Option AA "volume; 316L; 316L"
• Option AB "volume; Alloy C22; 316L"
• Option AC "volume; Alloy C22; Alloy C22"
• Option BA "volume high-temperature; 316L; 316L"
• Option BB "volume high-temperature; Alloy C22; 316L"
• Option CA "Mass; 316L; 316L (integrated temperature measurement)"
• Option CB "Mass; Alloy C22; 316L (integrated temperature measurement)"
• Option CC "Mass; Alloy C22; Alloy C22 (integrated temperature measurement)"
A0034068
1 Order code for "Sensor version", option "volume" or "volume high-temperature" 2 Order code for "Sensor version", option "mass"
Pressure and temperature measurement
The "mass" sensor version (integrated pressure/temperature measurement) is available only for measuring devices in the HART communication mode.
The "mass steam" or "mass gas/liquid" options are available under the order code for "Sensor version; DSC sensor; measuring tube". With these options, the measuring device can also measure the pressure and temperature of the fluid.
The temperature is measured via Pt 1000 temperature sensors. These are located in the paddle of the DSC sensor and are therefore in the direct vicinity of the fluid. Pressure measurement is located directly on the meter body at the level of the bluff body. The position of the pressure tapping was chosen so that pressure and temperature could be measured at the same point. This enables accurate density and/or energy compensation of the fluid using pressure and temperature. The measured pressure tends to be somewhat lower than the line pressure. For this reason, Endress+Hauser offers a correction to the line pressure (integrated in the device).
Order code for "Sensor version; DSC sensor; measuring tube":
• Option DA "Mass steam; 316L; 316L (integrated pressure/temperature measurement)"
• Option DB "Mass gas/liquid; 316L; 316L (integrated pressure/temperature measurement)"
Lifelong calibration
Experience has shown that recalibrated measuring devices demonstrate a very high degree of stability compared to their original calibration: The recalibration values were all within the original
Endress+Hauser 5
Proline Prowirl F 200
measuring accuracy specifications of the devices. This applies to the measured volume flow, the device's primary measured variable.
Various tests and simulation have shown that once the radii of the edges on the bluff body are less than 1 mm (0.04 in), the resulting effect does not have a negative impact on accuracy.
If the radii of the edges on the bluff body do not exceed 1 mm (0.04 in), the following general statements apply (in the case of non-abrasive and non-corrosive media, such as in most water and steam applications):
• The measuring device does not display an offset in the calibration and the accuracy is still guaranteed.
• All the edges on the bluff body have a radius that is typically smaller in size. As the measuring devices are naturally also calibrated with these radii, the measuring device remains within the specified accuracy rating provided that the additional radius that is produced as a result of wear and tear does not exceed 1 mm (0.04 in).
Consequently, it can be said that the product line offers lifelong calibration if the measuring device is used in non-abrasive and non-corrosive media.
Inlet run correction
Inlet run correction makes it possible to shorten the necessary inlet run before the measuring device to a minimum length of 10 × DN. If the inlet run available is too short, the measuring device can correct the measured error depending on the preceding disruption in the flow profile. This results in an additional measured error of ±0.5 %o.r.
The Inlet Run Correction function can be used for the following pressure ratings and nominal diameters: DN 15 to 150 (1 to 6")
• EN (DIN)
• ASME B16.5, Sch. 40/80
Inlet run correction is possible for the following flow obstructions:
• Single elbow (90° elbow)
• Double elbow (2 × 90° elbows, opposite)
• Double elbow 3D (2 × 90° elbows, opposite, not on one plane)
• Reduction by one nominal diameter size
Inlet and outlet runs to be considered →  44
1)
For detailed information about inlet run correction, see the Special Documentation for the device
Air and industrial gases
The measuring device enables users to calculate the density and energy of air and industrial gases. The calculations are based on time-tested standard calculation methods. It is possible to automatically compensate for the effect of pressure and temperature via an external or constant value.
This makes it possible to output the energy flow, standard volume flow and mass flow of the following gases:
• Single gas
• Gas mixture
• Air
• User-specific gas
For detailed information on the parameters, see the Operating Instructions.→  96
Natural gas
The device enables users to calculate the chemical properties (gross calorific value, net calorific value) of natural gases. The calculations are based on time-tested standard calculation methods. It is possible to automatically compensate for the effect of pressure and temperature via an external or constant value.
This makes it possible to output the energy flow, standard volume flow and mass flow in accordance with the following standard methods:
1) = of reading
6 Endress+Hauser
Proline Prowirl F 200
Energy can be calculated based on the following standards:
• AGA5
• ISO 6976
• GPA 2172 Density can be calculated based on the following standards:
• ISO 12213-2 (AGA8-DC92)
• ISO 12213-3
• AGA NX19
• AGA8 Gross 1
• SGERG 88 For detailed information on the parameters, see the Operating Instructions.→  96
Endress+Hauser 7
Proline Prowirl F 200
1 2

Measuring system

The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version – transmitter and sensor form a mechanical unit.
• Remote version - transmitter and sensor are mounted in separate locations.
Transmitter
Prowirl 200 Device versions and materials:
• Compact or remote version, aluminum coated: Aluminum, AlSi10Mg, coated
• Compact or remote version, stainless: For maximum corrosion resistance: stainless steel CF3M
Configuration:
• Via four-line local display with key operation or via four-line, illuminated local display with touch control and guided menus ("Make-
A0013471
it-run" wizards) for applications
• Via operating tools (e.g. FieldCare)
Sensor
ProwirlF Flanged version:
• Nominal diameter range: DN 15 to 300 (½ to 12")
• Materials:
• Measuring tubes
DN 15 to 300 (½ to 12"): stainless cast steel, CF3M/1.4408 DN 15 to 150 (½ to 6"): cast, CX2MW similar to Alloy C22/2.4602
• Flange connections
DN 15 to 300 (½ to 12"): stainless steel, triple-certified material,
1.4404/F316/F316L
• DN 15 to 150 (½ to 6"), pressure ratings up to PN40/Class 300: cast,
CX2MW similar to Alloy C22/2.4602
A0034075
Pressure measuring cell
The "mass" sensor version (integrated pressure/temperature measurement) is available only for measuring devices in the HART communication mode.
Versions: Pressure components
• Pressure measuring cell 2 bar_a
• Pressure measuring cell 4 bar_a
• Pressure measuring cell 10 bar_a
• Pressure measuring cell 40 bar_a
• Pressure measuring cell 100 bar_a
Material
• Wetted parts:
A0034080
1 Option DA "mass steam" 2 Option DB "mass gas/liquid"
• Process connection
Stainless steel, 1.4404/316L
• Membrane
Stainless steel, 1.4435/316L
• Non-wetted parts: Housing Stainless steel ,1.4404
8 Endress+Hauser
Proline Prowirl F 200

Input

Measured variable Direct measured variables

Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
AA Volume; 316L; 316L Volume flow
AB Volume; Alloy C22; 316L
AC Volume; Alloy C22; Alloy C22
BA Volume high-temperature; 316L; 316L
BB Volume high-temperature; Alloy C22; 316L
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
CA Mass; 316L; 316L (integrated temperature measurement) • Volume flow
CB Mass; Alloy ; C22; 316L (integrated temperature measurement)
CC Mass; Alloy C22; Alloy C22 (integrated temperature measurement)
• Temperature
The "mass" sensor version (integrated pressure/temperature measurement) is available only for measuring devices in the HART communication mode.
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
DA Mass steam; 316L; 316L (integrated pressure/temperature measurement) • Volume flow
DB Mass gas/liquid; 316L; 316L (integrated pressure/temperature measurement),
• Temperature
• Pressure
Calculated measured variables
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
AA Volume; 316L; 316L Under constant process conditions:
AB Volume; Alloy C22; 316L
AC Volume; Alloy C22; Alloy C22
BA Volume high-temperature; 316L; 316L
BB Volume high-temperature; Alloy C22; 316L
1) A fixed density must be entered for calculating the mass flow (Setup menu → Advanced setup submenu → External compensation submenu → Fixed density parameter).
• Mass flow
• Corrected volume flow
The totalized values for:
• Volume flow
• Mass flow
• Corrected volume flow
1)
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
CA Mass; 316L; 316L (integrated temperature measurement) • Corrected volume flow
CB Mass; Alloy C22; 316L (integrated temperature
measurement)
CC Mass; Alloy C22; Alloy C22 (integrated temperature
measurement)
• Mass flow
• Calculated saturated steam pressure
• Energy flow
• Heat flow difference
• Specific volume
• Degrees of superheat
Endress+Hauser 9
Proline Prowirl F 200
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
DA Mass steam; 316L; 316L (integrated pressure/temperature
measurement)
DB Mass gas/liquid; 316L; 316L (integrated pressure/
temperature measurement)
Order code for "Sensor version", option "mass flow (integrated temperature measurement)" combined with order code for "Application package"
Option Description Measured variable
EU Wet steam measurement • Steam quality
• Total mass flow
• Condensate mass flow

Measuring range

The measuring range is dependent on the nominal diameter, the fluid and environmental influences.
The following specified values are the largest possible flow measuring ranges (Q
min
to Q
max
) for each nominal diameter. Depending on the fluid properties and environmental influences, the measuring range may be subject to additional restrictions. Additional restrictions apply to both the lower range value and the upper range value.
Flow measuring ranges in SI units
DN [mm]
15 0.076 to 4.9 0.39 to 25
25 0.23 to 15 1.2 to 130
40 0.57 to 37 2.9 to 310
50 0.96 to 62 4.9 to 820
80 2.2 to 140 11 to 1 800
100 3.7 to 240 19 to 3 200
150 8.5 to 540 43 to 7 300
200 15 to 950 75 to 13 000
250 23 to 1 500 120 to 20 000
300 33 to 2 100 170 to 28 000
Liquids [m³/h]
Gas/steam [m³/h]
Flow measuring ranges in US units
DN Liquids Gas/steam
[in] [ft³/min] [ft³/min]
½ 0.045 to 2.9 0.23 to 15
1 0.14 to 8.8 0.7 to 74
0.34 to 22 1.7 to 180
2 0.56 to 36 2.9 to 480
3 1.3 to 81 6.4 to 1 100
4 2.2 to 140 11 to 1 900
6 5 to 320 25 to 4 300
8 8.7 to 560 44 to 7 500
10 14 to 880 70 to 12 000
12 19 to 1 300 99 to 17 000
10 Endress+Hauser
Proline Prowirl F 200
D
i
v,Q
v [m/s] =
4 · Q [m /h]³
π · D [m]
·
1
3600 [s/h]
v [!/s] =
4 · Q [ /min]ft³
π · D [ft]
·
1
60 [s/min]
Re
=
4 · Q [m³/s] · [kg/m³]ρ
· D [m] · µ [Pa · s]π
i
Re
=
4 · Q [ft³/s] · [lbm/ft³]ρ
· D [ft] · µ [lbf · s/ft ]π
i
²
Flow velocity
A0033468
DiInternal diameter of measuring tube (corresponds to dimension K→  55) v Velocity in measuring tube
Q Flow
The internal diameter of measuring tube Di is denoted in the dimensions as dimension K.→  55.
Calculation of flow velocity:
A0034301
Lower range value
A restriction applies to the lower range value due to the turbulent flow profile, which only occurs with Reynolds numbers greater than 5 000. The Reynolds number is dimensionless and indicates the ratio of the inertia force of a fluid to its viscous force when flowing and is used as a characteristic variable for pipe flows. In the case of pipe flows with Reynolds numbers less than 5 000, periodic vortices are no longer generated and flow rate measurement is no longer possible.
The Reynolds number is calculated as follows:
A0034291
Re Reynolds number
Q Flow
D
i
µ Dynamic viscosity
ρ Density
Internal diameter of measuring tube (corresponds to dimension K→  55)
The Reynolds number, 5 000 together with the density and viscosity of the fluid and the nominal diameter, is used to calculate the corresponding flow rate.
Endress+Hauser 11
Proline Prowirl F 200
Q [m /h] =
Re = 5000
³
5000 [Pa· · D [m] · · s]
i
π μ
· 3600 [s/h]
4 [kg/m ]· ³ρ
Q [ /h] =
Re = 5000
5000 [lbf· · D [ft] · · s/ft ]i²π μ
· 60 [s/min]
4 [lbm/ ]· ρ
v [m/s] = max
AmpMin
mf [m/s]
v [!/s] = max
AmpMin
mf [!/s]
0.062 [lb/! ]³
ρ [lb/!]³
1 [kg/ ]
ρ [kg/ ]
Q [m /h] =
AmpMin
³
v [m/s]
AmpMin
· · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³ 1 [kg/m ]³
Q [ /min] =
AmpMin
v [!/s]
AmpMin
· · D [ft]i²π
· 60 [s/min]
4 ·
ρ [lbm/ ]
0.0624 [lbm/ ]
A0034302
Q
Re = 5000
D
i
µ Dynamic viscosity
ρ Density
Flow rate is dependent on the Reynolds number
Internal diameter of measuring tube (corresponds to dimension K→  55)
The measuring signal must have a certain minimum signal amplitude so that the signals can be evaluated without any errors. Using the nominal diameter, the corresponding flow can also be derived from this amplitude. The minimum signal amplitude depends on the setting for the sensitivity of the DSC sensor (s), the steam quality (x) and the force of the vibrations present (a). The value mf corresponds to the lowest measurable flow velocity without vibration (no wet steam) at a density of 1 kg/m3 (0.0624 lbm/ft^3). The value mf can be set in the range from 6 to 20 m/s (1.8 to 6 ft/s) (factory setting 12 m/s (3.7 ft/s)) with the Sensitivity parameter (value range 1 to 9, factory setting 5).
The lowest flow velocity that can be measured on account of the signal amplitude v
AmpMin
is derived
from the Sensitivity parameter and the steam quality (x) or from the force of vibrations present (a).
v
AmpMin
mf Sensitivity
x Steam quality
ρ Density
12 Endress+Hauser
Q
AmpMin
v
AmpMin
Minimum measurable flow velocity based on signal amplitude
Minimum measurable flow rate based on signal amplitude
Minimum measurable flow velocity based on signal amplitude
A0034303
A0034304
Proline Prowirl F 200
Q [m /h] = max
Low
³
Q [m /h]
min
³
Q [m /h]
Re = 5000
³
Q [m /h]
AmpMin
³
Q [! /min] = max
Low
³
Q [ /min]
min
Q [ /min]
Re = 5000
Q [ /min]
AmpMin
Q [m /h] =
AmpMax
³
350[m/s] · · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³ 1 [kg/m ]³
Q [ /min] =
AmpMax
1148[!/s] · · D [ft]π
· 60 [s/min]
4 ·
ρ [lbm/ ]
0.0624 [lbm/ ]
D
i
Internal diameter of measuring tube (corresponds to dimension K→  55)
ρ Density
The effective lower range value Q
5000
Q
Low
Q
min
Q
Re = 5000
Q
AmpMin
and Q
.
AmpMin
Effective lower range value
Minimum measurable flow rate
Flow rate is dependent on the Reynolds number
Minimum measurable flow rate based on signal amplitude
is determined using the largest of the three values Q
Low
min
, Q
Re =
A0034313
The Applicator is available for calculation purposes.
Upper range value
The measuring signal amplitude must be below a certain limit value to ensure that the signals can be evaluated without error. This results in a maximum permitted flow rate Q
Q
AmpMax
D
i
ρ Density
Maximum measurable flow rate based on signal amplitude
Internal diameter of measuring tube (corresponds to dimension K→  55)
AmpMax
:
A0034316
Endress+Hauser 13
For gas applications, an additional restriction applies to the upper range value with regard to the Mach number in the measuring device, which must be less than 0.3. The Mach number Ma describes the ratio of the flow velocity v to the sound velocity c in the fluid.
Ma =
v [m/s] c [m/s]
Ma =
v [!/s] c [!/s]
Ma Mach number
Q [m /h] =
Ma = 0.3
³
0.3 · c [m/s] · · D [m]i²
π
4
· 3600 [s/h]
Q [ /min] =
Ma = 0.3
0.3 · c [ft/s] · · D [ft]i²
π
4
· 60 [s/min]
Q [m /h] = min
High
³
Q [m /h]
max
³
Q [m /h]
AmpMax
³
Q [m /h]
Ma = 0.3
³
Q [! /min] = min
High
³
Q [ /min]
max
Q [ /min]
AmpMax
Q [ /min]
Ma = 0.3
v
Flow velocity
c Sound velocity
The corresponding flow rate can be derived using the nominal diameter.
Proline Prowirl F 200
A0034321
Q
Ma = 0.3
Restricted upper range value is dependent on Mach number
c Sound velocity
D
i
Internal diameter of measuring tube (corresponds to dimension K→  55)
ρ Density
The effective upper range value Q Q
AmpMax
Q
High
Q
max
Q
AmpMax
Q
Ma = 0.3
and Q
Ma=0.3
.
Effective upper range value
Maximum measurable flow rate
Maximum measurable flow rate based on signal amplitude
Restricted upper range value is dependent on Mach number
is determined using the smallest of the three values Q
High
max
A0034337
,
A0034338
For liquids, the occurrence of cavitation may also restrict the upper range value.
The Applicator is available for calculation purposes.

Operable flow range

14 Endress+Hauser
The value, which is typically up to 49: 1, may vary depending on the operating conditions (ratio between upper range value and lower range value)
Proline Prowirl F 200

Input signal Current input

Current input 4-20 mA (passive)
Resolution 1 µA
Voltage drop Typically: 2.2 to 3 V for 3.6 to 22 mA
Maximum voltage ≤ 35 V
Possible input variables • Pressure
External measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the automation system can continuously write different measured values to the measuring device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
• Various pressure measuring devices can be ordered as accessories from Endress+Hauser.
• If using pressure measuring devices, pay attention to outlet runs when installing external devices→  46.
If the measuring device does not have pressure or temperature compensation that external pressure measurement values be read in so that the following measured variables can be calculated:
• Energy flow
• Mass flow
• Corrected volume flow
• Temperature
• Density
2)
, it is recommended
Integrated pressure and temperature measurement
The measuring device can also directly record external variables for density and energy compensation.
This product version offers the following benefits:
• Measurement of pressure, temperature and flow in a true 2-wire version
• Recording of pressure and temperature at the same point, thus ensuring maximum accuracy of density and energy compensation.
• Continuous monitoring of pressure and temperature, thus enabling complete integration in Heartbeat.
• Easy testing of pressure measurement accuracy:
• Application of pressure by pressure calibration unit, followed by input into measuring device
• Automatic error correction performed by device in the event of a deviation
• Availability of calculated line pressure.
Current input
The measured values are written from the automation system to the measuring device via the current input →  15.
HART protocol
The measured values are written from the automation system to the measuring device via the HART protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS PA
2) Order code for "Sensor option", option DA, DB
Endress+Hauser 15

Output

Output signal Current output

Current output 1 4-20 mA HART (passive)
Current output 2 4-20 mA (passive)
Resolution < 1 µA
Damping Adjustable: 0.0 to 999.9 s
Assignable measured variables
Proline Prowirl F 200
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Pulse/frequency/switch output
Function Can be set to pulse, frequency or switch output
Version Passive, open collector
Maximum input values • DC 35 V
• 50 mA
For information on the Ex connection values →  19
Voltage drop • For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current ≤ 0.05 mA
Pulse output
Pulse width Adjustable: 5 to 2 000 ms
Maximum pulse rate 100 Impulse/s
Pulse value Adjustable
Assignable measured variables
Frequency output
Output frequency Adjustable: 0 to 1 000 Hz
Damping Adjustable: 0 to 999 s
Pulse/pause ratio 1:1
Assignable measured variables
• Mass flow
• Volume flow
• Corrected volume flow
• Total mass flow
• Energy flow
• Heat flow difference
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Pressure
16 Endress+Hauser
Proline Prowirl F 200
Switch output
Switching behavior Binary, conductive or non-conductive
Switching delay Adjustable: 0 to 100 s
Number of switching cycles
Assignable functions • Off
Unlimited
• On
• Diagnostic behavior
• Limit value
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Pressure
• Reynolds number
• Totalizer 1-3
• Status
• Status of low flow cut off

Signal on alarm

FOUNDATION Fieldbus
FOUNDATION Fieldbus H1, IEC 61158-2, galvanically isolated
Data transfer 31.25 kbit/s
Current consumption 15 mA
Permitted supply voltage 9 to 32 V
Bus connection With integrated reverse polarity protection
PROFIBUS PA
PROFIBUS PA In accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically
isolated
Data transmission 31.25 kbit/s
Current consumption 16 mA
Permitted supply voltage 9 to 32 V
Bus connection With integrated reverse polarity protection
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure mode Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Endress+Hauser 17
Pulse/frequency/switch output
Pulse output
Failure mode No pulses
Frequency output
Failure mode Choose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1 250 Hz
Switch output
Failure mode Choose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Proline Prowirl F 200
Status and alarm messages
Failure current FDE (Fault Disconnection Electronic)
Diagnostics in accordance with FF-891
0 mA
PROFIBUS PA
Status and alarm messages
Failure current FDE (Fault Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
Local display
Plain text display With information on cause and remedial measures
Backlight Additionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
• HART protocol
• FOUNDATION Fieldbus
• PROFIBUS PA
• Via service interface CDI service interface
Plain text display With information on cause and remedial measures
Additional information on remote operation →  85

Load

Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply unit
18 Endress+Hauser
Proline Prowirl F 200
0
100
200
300
400
500
16 18 20
22 24
26 28 30 32
U [V]
S
RB[Ω]
34 36
A B
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including line resistance must be observed to ensure adequate terminal voltage at the device. In doing so, observe the minimum terminal voltage
• For US = 17.9 to 18.9 V: RB ≤ (US - 17.9 V): 0.0036 A
• For US = 18.9 to 24 V: RB ≤ (US - 13 V): 0.022 A
• For US = ≥ 24 V: RB ≤ 500 Ω
A Operating range for order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/
frequency/switch output" with Ex i and option C "4-20 mA HART + 4-20 mA analog"
B Operating range for order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/
frequency/switch output" with non-Ex and Ex d
Sample calculation
Supply voltage of power supply unit: US =19 V Maximum load: RB ≤ (19 V - 13 V): 0.022 A = 273 Ω

Ex connection data Safety-related values

Type of protection Ex d
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
Option C 4-20mA HART
Option D 4-20mA HART U
Option E FOUNDATION Fieldbus U
Pulse/frequency/switch output U
4-20mA analog
Pulse/frequency/switch output U
4 to 20 mA current input U
Pulse/frequency/switch output U
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 30 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 35 V = 250 V
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
A0013563
Endress+Hauser 19
Proline Prowirl F 200
Order code for "Output" Output type Safety-related values
Option G PROFIBUS PA U
Pulse/frequency/switch output U
1) Internal circuit limited by Ri = 760.5 Ω
Type of protection Ex ec Ex nA
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
Pulse/frequency/switch output U
Option C 4-20mA HART
4-20mA analog
Option D 4-20mA HART U
Pulse/frequency/switch output U
4 to 20 mA current input U
Option E FOUNDATION Fieldbus U
Pulse/frequency/switch output U
Option G PROFIBUS PA U
Pulse/frequency/switch output U
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
= DC 35 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 30 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
= 1 W
= DC 35 V = 250 V
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
= 1 W
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
= 1 W
1) Internal circuit limited by Ri = 760.5 Ω
Type of protection XP
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
Pulse/frequency/switch output U
Option C 4-20mA HART U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
= DC 35 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 30 V = 250 V
20 Endress+Hauser
Proline Prowirl F 200
Order code for "Output" Output type Safety-related values
4-20mA analog
Option D 4-20mA HART U
Pulse/frequency/switch output U
4 to 20 mA current input U
Option E FOUNDATION Fieldbus U
Pulse/frequency/switch output U
Option G PROFIBUS PA U
Pulse/frequency/switch output U
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 35 V = 250 V
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
1) Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
Type of protection Ex ia
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
Option C 4-20mA HART Ui = DC 30 V
4-20mA analog
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 30 nF
Endress+Hauser 21
Proline Prowirl F 200
Order code for "Output" Output type Intrinsically safe values
Option D 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
4 to 20 mA current input Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Option G PROFIBUS PA STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
Type of protection Ex ic
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 6 nF
Option C 4-20mA HART Ui = DC 30 V
4-20mA analog
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 30 nF
22 Endress+Hauser
Proline Prowirl F 200
Order code for "Output" Output type Intrinsically safe values
Option D 4-20mA HART Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 6 nF
4 to 20 mA current input Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 32 V li = 300 mA Pi = n.a. Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 35 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Option G PROFIBUS PA STANDARD
Ui = 32 V li = 300 mA Pi = n.a. Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 35 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = n.a. Pi = n.a. Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = n.a. Pi = n.a. Li = 10 µH Ci = 5 nF
Type of protection IS
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
Option C 4-20mA HART Ui = DC 30 V
4-20mA analog
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 30 nF
Endress+Hauser 23
Proline Prowirl F 200
Order code for "Output" Output type Intrinsically safe values
Option D 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
4 to 20 mA current input Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Option G PROFIBUS PA STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF

Low flow cut off

Galvanic isolation

The switch points for low flow cut off are preset and can be configured.
All inputs and outputs are galvanically isolated from one another.

Protocol-specific data HART

Manufacturer ID 0x11
Device type ID 0x0038
HART protocol revision 7
Device description files (DTM, DD)
HART load • Min. 250 Ω
System integration For information on system integration, see Operating Instructions.→  96
Information and files under:
www.endress.com
• Max. 500 Ω
• Measured variables via HART protocol
• Burst Mode functionality
24 Endress+Hauser
Proline Prowirl F 200
FOUNDATION Fieldbus
Manufacturer ID 0x452B48
Ident number 0x1038
Device revision 2
DD revision Information and files under:
CFF revision
Device Tester Version (ITK version)
ITK Test Campaign Number Information:
Link Master capability (LAS) Yes
Choice of "Link Master" and "Basic Device"
Node address Factory setting: 247 (0xF7)
Supported functions The following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs 44
Number of link objects in VFD 50
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Device Link Capabilities
Slot time 4
Min. delay between PDU 8
Max. response delay Min. 5
System integration For information on system integration, see Operating Instructions.→  96
www.endress.com
www.fieldbus.org
6.2.0
www.endress.com
www.fieldbus.org
Yes Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
• Read events
• Read trend data
• Cyclic data transmission
• Description of the modules
• Execution times
• Methods
PROFIBUS PA
Manufacturer ID 0x11
Ident number 0x1564
Profile version 3.02
Device description files (GSD, DTM, DD)
Information and files under:
www.endress.com
www.profibus.org
Endress+Hauser 25
Supported functions • Identification & Maintenance
3 4 1 2
4
5 6
+ + +
123
Configuration of the device address
System integration For information on system integration, see Operating Instructions.→  96

Power supply

Terminal assignment Transmitter

Proline Prowirl F 200
Simple device identification via control system and nameplate
• PROFIBUS upload/download Reading and writing parameters is up to ten times faster with PROFIBUS upload/download
• Condensed status Simplest and self-explanatory diagnostic information by categorizing diagnostic messages that occur
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e. g. FieldCare)
• Cyclic data transmission
• Block model
• Description of the modules
Connection versions
Maximum number of terminals Terminals 1 to 6: Without integrated overvoltage protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Input (passive): supply voltage and signal transmission
4
Ground terminal for cable shield
Order code for "Output" Terminal numbers
Output 1 Output 2 Input
1 (+) 2 (-) 3 (+) 4 (-) 5 (+) 6 (-)
Option A 4-20 mA HART (passive) - -
Option B
Option C
Option D
1)
1)
1) 2)
4-20 mA HART (passive)
4-20 mA HART (passive) 4-20 mA analog (passive) -
4-20 mA HART (passive)
Maximum number of terminals for order code for "Accessory mounted", option NA "Overvoltage protection"
Terminals 1 to 4:
With integrated overvoltage protection
Terminals 5 to 6:
Without integrated overvoltage protection
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
A0033475
-
4-20 mA current input
(passive)
26 Endress+Hauser
Proline Prowirl F 200
+
+
2
1
1
2
1 2 3 4
1 2 3 4
GNYEWHBN
Order code for "Output" Terminal numbers
Output 1 Output 2 Input
1 (+) 2 (-) 3 (+) 4 (-) 5 (+) 6 (-)
Option E
Option G
1) Output 1 must always be used; output 2 is optional.
2) The integrated overvoltage protection is not used with option D: Terminals 5 and 6 (current input) are not protected against overvoltage.
3) FOUNDATION Fieldbus with integrated reverse polarity protection.
4) PROFIBUS PA with integrated reverse polarity protection.
1) 3)
1) 4)
FOUNDATION Fieldbus
PROFIBUS PA
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
-
-
Connecting cable for remote version
Transmitter and sensor connection housing
In the case of the remote version, the sensor and transmitter are mounted separately from on another and connected by a connecting cable. Connection is performed via the sensor connection housing and the transmitter housing.
How the connecting cable is connected in the transmitter housing depends on the measuring device approval and the version of the connecting cable used.
In the following versions, only terminals can be used for connection in the transmitter housing:
• Certain approvals: Ex nA, Ex ec, Ex tb and Division 1
• Use of reinforced connecting cable
• Order code for "Sensor version; DSC sensor; measuring tube", option DA, DB In the following versions, an M12 device connector is used for connection in the transmitter
housing:
• All other approvals
• Use of connecting cable (standard) Terminals are always used to connect the connecting cable in the sensor connection housing
(tightening torques for screws for cable strain relief: 1.2 to 1.7 Nm).
Connecting cable (standard, reinforced)
A0033476
 2 Terminals for connection compartment in the transmitter wall holder and the sensor connection housing
1 Terminals for connecting cable 2 Grounding via the cable strain relief
Terminal number Assignment Cable color
Connecting cable
1 Supply voltage Brown
2 Grounding White
Endress+Hauser 27
Terminal number Assignment Cable color
+
+
2
1
1
2
1 2 3 4
1 2 3 4556677
RDGNWHBN BK YE BU
+
+
RES
VCC
GND
RES
VCC
GND
1
2
4
3
1
2
4
3
3 RS485 (+) Yellow
4 RS485 (–) Green
Connecting cable (option "mass pressure-/temperature-compensated")
Order code for "Sensor version; DSC sensor; measuring tube", option DA, DB
Proline Prowirl F 200
Connecting cable
 3 Terminals for connection compartment in the transmitter wall holder and the sensor connection housing
1 Terminals for connecting cable 2 Grounding via the cable strain relief
Terminal number Assignment Cable color

Pin assignment, device plug PROFIBUS PA

A0034571
Connecting cable
1 RS485 (-) DPC Brown
2 RS485 (+) DPC White
3 Reset Green
4 Supply voltage red
5 Grounding Black
6 RS485 (+) Yellow
7 RS485 (–) Blue
Pin Assignment Coding Plug/socket
1 + PROFIBUS PA + A Plug
2 Grounding
3 - PROFIBUS PA –
4 Not assigned
28 Endress+Hauser
FOUNDATION Fieldbus
Pin Assignment Coding Plug/socket
1 + Signal + A Plug
2 - Signal –
Proline Prowirl F 200

Supply voltage Transmitter

An external power supply is required for each output.
3 Grounding
4 Not assigned
Supply voltage for a compact version without a local display
Order code for "Output; input" Minimum
terminal voltage
Option A: 4-20 mA HART ≥ DC 12 V DC 35 V
Option B: 4-20 mA HART, pulse/ frequency/switch output
Option C: 4-20 mA HART + 4-20 mA analog
Option D: 4-20 mA HART, pulse/ frequency/switch output, 4-20 mA current
3)
input
Option E: FOUNDATION Fieldbus, pulse/ frequency/switch output
Option G: PROFIBUS PA, pulse/frequency/ switch output
1) In event of external supply voltage of the power supply unit with load, the PROFIBUS DP/PA coupler or FOUNDATION Fieldbus power conditioners
2) The minimum terminal voltage increases if local operation is used: see the following table
3) Voltage drop 2.2 to 3 V for 3.59 to 22 mA
1)
2)
≥ DC 12 V DC 35 V
≥ DC 12 V DC 30 V
≥ DC 12 V DC 35 V
≥ DC 9 V DC 32 V
≥ DC 9 V DC 32 V
Maximum
terminal voltage
Increase in minimum terminal voltage
Order code for "Display; operation"
Option C: Local operation SD02
Option E: Local operation SD03 with lighting (backlighting not used)
Option E: Local operation SD03 with lighting (backlighting used)
Increase in minimum
terminal voltage
+ DC 1 V
+ DC 1 V
+ DC 3 V
Order code for "Sensor version; DSC sensor; measuring tube"
Option DA: Mass steam; 316L; 316L (integrated pressure/temperature measurement)
Option DB: Mass gas/liquid; 316L; 316L (integrated pressure/temperature measurement)
Increase in minimum
terminal voltage
+ DC 1 V
+ DC 1 V
For information about the load see →  18
Various power supply units can be ordered from Endress+Hauser: →  95
For information on the Ex connection values →  19
Endress+Hauser 29

Power consumption Transmitter

Order code for "Output; input" Maximum power consumption
Option A: 4-20 mA HART 770 mW
Option B: 4-20 mA HART, pulse/ frequency/switch output
Option C: 4-20 mA HART + 4-20 mA analog
Option D: 4-20 mA HART, pulse/ frequency/switch output, 4-20 mA current input
Option E: FOUNDATION Fieldbus, pulse/ frequency/switch output
Option G: PROFIBUS PA, pulse/frequency/ switch output
For information on the Ex connection values →  19
Proline Prowirl F 200
• Operation with output 1: 770 mW
• Operation with output 1 and 2: 2 770 mW
• Operation with output 1: 660 mW
• Operation with output 1 and 2: 1 320 mW
• Operation with output 1: 770 mW
• Operation with output 1 and 2: 2770 mW
• Operation with output 1 and input: 840 mW
• Operation with output 1, 2 and input: 2840 mW
• Operation with output 1: 512 mW
• Operation with output 1 and 2: 2 512 mW
• Operation with output 1: 512 mW
• Operation with output 1 and 2: 2 512 mW

Current consumption Current output

For every 4-20 mA or 4-20 mA HART current output: 3.6 to 22.5 mA
If the option Defined value is selected in the Failure mode parameter : 3.59 to 22.5 mA
Current input
3.59 to 22.5 mA
Internal current limiting: max. 26 mA
FOUNDATION Fieldbus
15 mA
PROFIBUS PA
15 mA

Power supply failure

• Totalizers stop at the last value measured.
• Depending on the device version, the configuration is retained in the device memoryor in the pluggable data memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.

Electrical connection Connecting the transmitter

A0033480
1 Cable entries for inputs/outputs
30 Endress+Hauser
Loading...
+ 68 hidden pages