A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other
connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Communication symbols
SymbolMeaning
Wireless Local Area Network (WLAN)
Communication via a wireless, local network.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Visual inspection.
Symbols in graphics
SymbolMeaning
1, 2, 3, ...Item numbers
, 2., 3., …Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
Endress+Hauser3
SymbolMeaning
-
.
K-Factor =
Pulses
Unit Volume [m³]
Hazardous area
Safe area (non-hazardous area)
Flow direction
Function and system design
Proline Prowirl F 200
Measuring principle
Vortex meters work on the principle of the Karman vortex street. When fluid flows past a bluff body,
vortices are alternately formed on both sides with opposite directions of rotation. These vortices each
generate a local low pressure. The pressure fluctuations are recorded by the sensor and converted to
electrical pulses. The vortices develop very regularly within the permitted application limits of the
device. Therefore, the frequency of vortex shedding is proportional to the volume flow.
A0033465
1Sample graphic
The calibration factor (K-factor) is used as the proportional constant:
Within the application limits of the device, the K-factor only depends on the geometry of the device.
It is for Re > 10000:
• Independent of the flow velocity and the fluid properties viscosity and density
• Independent of the type of substance under measurement: steam, gas or liquid
The primary measuring signal is linear to the flow. After production, the K-factor is determined in
the factory by means of calibration. It is not subject to long-time drift or zero-point drift.
The device does not contain any moving parts and does not require any maintenance.
The capacitance sensor
The sensor of a vortex flowmeter has a major influence on the performance, robustness and
reliability of the entire measuring system.
4Endress+Hauser
A0003939-EN
Proline Prowirl F 200
12
The robust DSC sensor is:
• burst-tested
• tested against vibrations
• tested against thermal shock (thermal shocks of 150 K/s)
The measuring device uses the tried-and-tested, capacitance measuring technology from
Endress+Hauser, which is already in use in over 450000 measuring points worldwide. Thanks to its
design, the capacitance sensor is also particularly mechanically resistant to temperature shocks and
pressure shocks in steam pipelines.
Temperature measurement
The "mass" option is available under the order code for "Sensor version". With this option the
measuring device can also measure the temperature of the medium.
The temperature is measured via Pt 1000 temperature sensors. These are located in the paddle of
the DSC sensor and are therefore in the direct vicinity of the fluid.
Order code for "Sensor version; DSC sensor; measuring tube":
• Option CA "Mass; 316L; 316L (integrated temperature measurement)"
• Option CB "Mass; Alloy C22; 316L (integrated temperature measurement)"
• Option CC "Mass; Alloy C22; Alloy C22 (integrated temperature measurement)"
A0034068
1Order code for "Sensor version", option "volume" or "volume high-temperature"
2Order code for "Sensor version", option "mass"
Pressure and temperature measurement
The "mass" sensor version (integrated pressure/temperature measurement) is available only for
measuring devices in the HART communication mode.
The "mass steam" or "mass gas/liquid" options are available under the order code for "Sensor version;
DSC sensor; measuring tube". With these options, the measuring device can also measure the
pressure and temperature of the fluid.
The temperature is measured via Pt 1000 temperature sensors. These are located in the paddle of
the DSC sensor and are therefore in the direct vicinity of the fluid. Pressure measurement is located
directly on the meter body at the level of the bluff body. The position of the pressure tapping was
chosen so that pressure and temperature could be measured at the same point. This enables accurate
density and/or energy compensation of the fluid using pressure and temperature. The measured
pressure tends to be somewhat lower than the line pressure. For this reason, Endress+Hauser offers
a correction to the line pressure (integrated in the device).
Order code for "Sensor version; DSC sensor; measuring tube":
• Option DA "Mass steam; 316L; 316L (integrated pressure/temperature measurement)"
• Option DB "Mass gas/liquid; 316L; 316L (integrated pressure/temperature measurement)"
Lifelong calibration
Experience has shown that recalibrated measuring devices demonstrate a very high degree of
stability compared to their original calibration: The recalibration values were all within the original
Endress+Hauser5
Proline Prowirl F 200
measuring accuracy specifications of the devices. This applies to the measured volume flow, the
device's primary measured variable.
Various tests and simulation have shown that once the radii of the edges on the bluff body are less
than 1 mm (0.04 in), the resulting effect does not have a negative impact on accuracy.
If the radii of the edges on the bluff body do not exceed 1 mm (0.04 in), the following general
statements apply (in the case of non-abrasive and non-corrosive media, such as in most water and
steam applications):
• The measuring device does not display an offset in the calibration and the accuracy is still
guaranteed.
• All the edges on the bluff body have a radius that is typically smaller in size. As the measuring
devices are naturally also calibrated with these radii, the measuring device remains within the
specified accuracy rating provided that the additional radius that is produced as a result of wear
and tear does not exceed 1 mm (0.04 in).
Consequently, it can be said that the product line offers lifelong calibration if the measuring device is
used in non-abrasive and non-corrosive media.
Inlet run correction
Inlet run correction makes it possible to shorten the necessary inlet run before the measuring device
to a minimum length of 10 × DN. If the inlet run available is too short, the measuring device can
correct the measured error depending on the preceding disruption in the flow profile. This results in
an additional measured error of ±0.5 %o.r.
The Inlet Run Correction function can be used for the following pressure ratings and nominal
diameters:
DN 15 to 150 (1 to 6")
• EN (DIN)
• ASME B16.5, Sch. 40/80
Inlet run correction is possible for the following flow obstructions:
• Single elbow (90° elbow)
• Double elbow (2 × 90° elbows, opposite)
• Double elbow 3D (2 × 90° elbows, opposite, not on one plane)
• Reduction by one nominal diameter size
Inlet and outlet runs to be considered → 44
1)
For detailed information about inlet run correction, see the Special Documentation for the
device
Air and industrial gases
The measuring device enables users to calculate the density and energy of air and industrial gases.
The calculations are based on time-tested standard calculation methods. It is possible to
automatically compensate for the effect of pressure and temperature via an external or constant
value.
This makes it possible to output the energy flow, standard volume flow and mass flow of the
following gases:
• Single gas
• Gas mixture
• Air
• User-specific gas
For detailed information on the parameters, see the Operating Instructions.→ 96
Natural gas
The device enables users to calculate the chemical properties (gross calorific value, net calorific
value) of natural gases. The calculations are based on time-tested standard calculation methods. It is
possible to automatically compensate for the effect of pressure and temperature via an external or
constant value.
This makes it possible to output the energy flow, standard volume flow and mass flow in accordance
with the following standard methods:
1)= of reading
6Endress+Hauser
Proline Prowirl F 200
Energy can be calculated based on the following standards:
• AGA5
• ISO 6976
• GPA 2172
Density can be calculated based on the following standards:
• ISO 12213-2 (AGA8-DC92)
• ISO 12213-3
• AGA NX19
• AGA8 Gross 1
• SGERG 88
For detailed information on the parameters, see the Operating Instructions.→ 96
Endress+Hauser7
Proline Prowirl F 200
12
Measuring system
The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version – transmitter and sensor form a mechanical unit.
• Remote version - transmitter and sensor are mounted in separate locations.
Transmitter
Prowirl 200Device versions and materials:
• Compact or remote version, aluminum coated:
Aluminum, AlSi10Mg, coated
• Compact or remote version, stainless:
For maximum corrosion resistance: stainless steel CF3M
Configuration:
• Via four-line local display with key operation or via four-line,
illuminated local display with touch control and guided menus ("Make-
A0013471
it-run" wizards) for applications
• Via operating tools (e.g. FieldCare)
Sensor
ProwirlFFlanged version:
• Nominal diameter range: DN 15 to 300 (½ to 12")
• Materials:
• Measuring tubes
DN 15 to 300 (½ to 12"): stainless cast steel, CF3M/1.4408
DN 15 to 150 (½ to 6"): cast, CX2MW similar to Alloy C22/2.4602
• Flange connections
DN 15 to 300 (½ to 12"): stainless steel, triple-certified material,
1.4404/F316/F316L
• DN 15 to 150 (½ to 6"), pressure ratings up to PN40/Class 300: cast,
CX2MW similar to Alloy C22/2.4602
A0034075
Pressure measuring cell
The "mass" sensor version (integrated pressure/temperature measurement) is available only for
measuring devices in the HART communication mode.
Versions:
Pressure components
• Pressure measuring cell 2 bar_a
• Pressure measuring cell 4 bar_a
• Pressure measuring cell 10 bar_a
• Pressure measuring cell 40 bar_a
• Pressure measuring cell 100 bar_a
Material
• Wetted parts:
A0034080
1Option DA "mass steam"
2Option DB "mass gas/liquid"
Order code for "Sensor version; DSC sensor; measuring tube"
OptionDescriptionMeasured variable
AAVolume; 316L; 316LUnder constant process conditions:
ABVolume; Alloy C22; 316L
ACVolume; Alloy C22; Alloy C22
BAVolume high-temperature; 316L; 316L
BBVolume high-temperature; Alloy C22; 316L
1)A fixed density must be entered for calculating the mass flow (Setup menu → Advanced setup submenu →
External compensation submenu → Fixed density parameter).
• Mass flow
• Corrected volume flow
The totalized values for:
• Volume flow
• Mass flow
• Corrected volume flow
1)
Order code for "Sensor version; DSC sensor; measuring tube"
Option DescriptionMeasured variable
CAMass; 316L; 316L (integrated temperature measurement)• Corrected volume flow
CBMass; Alloy C22; 316L (integrated temperature
measurement)
CCMass; Alloy C22; Alloy C22 (integrated temperature
measurement)
• Mass flow
• Calculated saturated steam pressure
• Energy flow
• Heat flow difference
• Specific volume
• Degrees of superheat
Endress+Hauser9
Proline Prowirl F 200
Order code for "Sensor version; DSC sensor; measuring tube"
Order code for "Sensor version", option "mass flow (integrated temperature measurement)" combined
with order code for "Application package"
OptionDescriptionMeasured variable
EUWet steam measurement• Steam quality
• Total mass flow
• Condensate mass flow
Measuring range
The measuring range is dependent on the nominal diameter, the fluid and environmental influences.
The following specified values are the largest possible flow measuring ranges (Q
min
to Q
max
) for
each nominal diameter. Depending on the fluid properties and environmental influences, the
measuring range may be subject to additional restrictions. Additional restrictions apply to both
the lower range value and the upper range value.
Flow measuring ranges in SI units
DN
[mm]
150.076 to 4.90.39 to 25
250.23 to 151.2 to 130
400.57 to 372.9 to 310
500.96 to 624.9 to 820
802.2 to 14011 to 1800
1003.7 to 24019 to 3200
1508.5 to 54043 to 7300
20015 to 95075 to 13000
25023 to 1500120 to 20000
30033 to 2100170 to 28000
Liquids
[m³/h]
Gas/steam
[m³/h]
Flow measuring ranges in US units
DNLiquidsGas/steam
[in][ft³/min][ft³/min]
½0.045 to 2.90.23 to 15
10.14 to 8.80.7 to 74
1½0.34 to 221.7 to 180
20.56 to 362.9 to 480
31.3 to 816.4 to 1100
42.2 to 14011 to 1900
65 to 32025 to 4300
88.7 to 56044 to 7500
1014 to 88070 to 12000
1219 to 130099 to 17000
10Endress+Hauser
Proline Prowirl F 200
D
i
v,Q
v [m/s] =
4 · Q [m /h]³
π · D [m]i²
·
1
3600 [s/h]
v [!/s] =
4 · Q [ /min]ft³
π · D [ft]i²
·
1
60 [s/min]
Re
=
4 · Q [m³/s] · [kg/m³]ρ
· D [m] · µ [Pa · s]π
i
Re
=
4 · Q [ft³/s] · [lbm/ft³]ρ
· D [ft] · µ [lbf · s/ft ]π
i
²
Flow velocity
A0033468
DiInternal diameter of measuring tube (corresponds to dimension K→ 55)
vVelocity in measuring tube
QFlow
The internal diameter of measuring tube Di is denoted in the dimensions as dimension
K.→ 55.
Calculation of flow velocity:
A0034301
Lower range value
A restriction applies to the lower range value due to the turbulent flow profile, which only occurs
with Reynolds numbers greater than 5000. The Reynolds number is dimensionless and indicates the
ratio of the inertia force of a fluid to its viscous force when flowing and is used as a characteristic
variable for pipe flows. In the case of pipe flows with Reynolds numbers less than 5000, periodic
vortices are no longer generated and flow rate measurement is no longer possible.
The Reynolds number is calculated as follows:
A0034291
ReReynolds number
QFlow
D
i
µDynamic viscosity
ρDensity
Internal diameter of measuring tube (corresponds to dimension K→ 55)
The Reynolds number, 5000 together with the density and viscosity of the fluid and the nominal
diameter, is used to calculate the corresponding flow rate.
Endress+Hauser11
Proline Prowirl F 200
Q[m /h] =
Re = 5000
³
5000[Pa· · D [m] ·· s]
i
πμ
· 3600 [s/h]
4[kg/m ]·³ρ
Q[ /h] =
Re = 5000
!³
5000[lbf· · D [ft] ·· s/ft ]i²πμ
· 60 [s/min]
4[lbm/ ]·!³ρ
v[m/s] = max
AmpMin
mf [m/s]
x²
v[!/s] = max
AmpMin
mf [!/s]
x²
0.062 [lb/! ]³
ρ [lb/!]³
1 [kg/]m³
ρ [kg/]m³
⋅
⋅
Q[m /h] =
AmpMin
³
v[m/s]
AmpMin
· · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³
1 [kg/m ]³
Q[ /min] =
AmpMin
!³
v[!/s]
AmpMin
· · D [ft]i²π
· 60 [s/min]
4 ·
ρ [lbm/ ]#³
0.0624 [lbm/ ]!³
A0034302
Q
Re = 5000
D
i
µDynamic viscosity
ρDensity
Flow rate is dependent on the Reynolds number
Internal diameter of measuring tube (corresponds to dimension K→ 55)
The measuring signal must have a certain minimum signal amplitude so that the signals can be
evaluated without any errors. Using the nominal diameter, the corresponding flow can also be
derived from this amplitude. The minimum signal amplitude depends on the setting for the
sensitivity of the DSC sensor (s), the steam quality (x) and the force of the vibrations present (a). The
value mf corresponds to the lowest measurable flow velocity without vibration (no wet steam) at a
density of 1 kg/m3 (0.0624 lbm/ft^3). The value mf can be set in the range from
6 to 20 m/s (1.8 to 6 ft/s) (factory setting 12 m/s (3.7 ft/s)) with the Sensitivity parameter (value
range 1 to 9, factory setting 5).
The lowest flow velocity that can be measured on account of the signal amplitude v
AmpMin
is derived
from the Sensitivity parameter and the steam quality (x) or from the force of vibrations present (a).
v
AmpMin
mfSensitivity
xSteam quality
ρDensity
12Endress+Hauser
Q
AmpMin
v
AmpMin
Minimum measurable flow velocity based on signal amplitude
Minimum measurable flow rate based on signal amplitude
Minimum measurable flow velocity based on signal amplitude
A0034303
A0034304
Proline Prowirl F 200
Q[m /h] = max
Low
³
Q [m /h]
min
³
Q[m /h]
Re = 5000
³
Q[m /h]
AmpMin
³
Q[! /min] = max
Low
³
Q [ /min]
min
!³
Q[ /min]
Re = 5000
!³
Q[ /min]
AmpMin
!³
Q[m /h] =
AmpMax
³
350[m/s] · · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³
1 [kg/m ]³
Q[ /min] =
AmpMax
!³
1148[!/s] · · D [ft]i²π
· 60 [s/min]
4 ·
ρ [lbm/ ]#³
0.0624 [lbm/ ]!³
D
i
Internal diameter of measuring tube (corresponds to dimension K→ 55)
ρDensity
The effective lower range value Q
5000
Q
Low
Q
min
Q
Re = 5000
Q
AmpMin
and Q
.
AmpMin
Effective lower range value
Minimum measurable flow rate
Flow rate is dependent on the Reynolds number
Minimum measurable flow rate based on signal amplitude
is determined using the largest of the three values Q
Low
min
, Q
Re =
A0034313
The Applicator is available for calculation purposes.
Upper range value
The measuring signal amplitude must be below a certain limit value to ensure that the signals can be
evaluated without error. This results in a maximum permitted flow rate Q
Q
AmpMax
D
i
ρDensity
Maximum measurable flow rate based on signal amplitude
Internal diameter of measuring tube (corresponds to dimension K→ 55)
AmpMax
:
A0034316
Endress+Hauser13
For gas applications, an additional restriction applies to the upper range value with regard to the
Mach number in the measuring device, which must be less than 0.3. The Mach number Ma describes
the ratio of the flow velocity v to the sound velocity c in the fluid.
Ma =
v [m/s]
c [m/s]
Ma =
v [!/s]
c [!/s]
MaMach number
Q[m /h] =
Ma = 0.3
³
0.3 · c [m/s] · · D [m]i²
π
4
· 3600 [s/h]
Q[ /min] =
Ma = 0.3
!³
0.3 · c [ft/s] · · D [ft]i²
π
4
· 60 [s/min]
Q[m /h] = min
High
³
Q[m /h]
max
³
Q[m /h]
AmpMax
³
Q[m /h]
Ma = 0.3
³
Q[! /min] = min
High
³
Q[ /min]
max
!³
Q[ /min]
AmpMax
!³
Q[ /min]
Ma = 0.3
!³
v
Flow velocity
cSound velocity
The corresponding flow rate can be derived using the nominal diameter.
Proline Prowirl F 200
A0034321
Q
Ma = 0.3
Restricted upper range value is dependent on Mach number
cSound velocity
D
i
Internal diameter of measuring tube (corresponds to dimension K→ 55)
ρDensity
The effective upper range value Q
Q
AmpMax
Q
High
Q
max
Q
AmpMax
Q
Ma = 0.3
and Q
Ma=0.3
.
Effective upper range value
Maximum measurable flow rate
Maximum measurable flow rate based on signal amplitude
Restricted upper range value is dependent on Mach number
is determined using the smallest of the three values Q
High
max
A0034337
,
A0034338
For liquids, the occurrence of cavitation may also restrict the upper range value.
The Applicator is available for calculation purposes.
Operable flow range
14Endress+Hauser
The value, which is typically up to 49: 1, may vary depending on the operating conditions (ratio
between upper range value and lower range value)
Proline Prowirl F 200
Input signalCurrent input
Current input4-20 mA (passive)
Resolution1 µA
Voltage dropTypically: 2.2 to 3 V for 3.6 to 22 mA
Maximum voltage≤ 35 V
Possible input variables• Pressure
External measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure
measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
• Various pressure measuring devices can be ordered as accessories from Endress+Hauser.
• If using pressure measuring devices, pay attention to outlet runs when installing external
devices→ 46.
If the measuring device does not have pressure or temperature compensation
that external pressure measurement values be read in so that the following measured variables can
be calculated:
• Energy flow
• Mass flow
• Corrected volume flow
• Temperature
• Density
2)
, it is recommended
Integrated pressure and temperature measurement
The measuring device can also directly record external variables for density and energy
compensation.
This product version offers the following benefits:
• Measurement of pressure, temperature and flow in a true 2-wire version
• Recording of pressure and temperature at the same point, thus ensuring maximum accuracy of
density and energy compensation.
• Continuous monitoring of pressure and temperature, thus enabling complete integration in
Heartbeat.
• Easy testing of pressure measurement accuracy:
• Application of pressure by pressure calibration unit, followed by input into measuring device
• Automatic error correction performed by device in the event of a deviation
• Availability of calculated line pressure.
Current input
The measured values are written from the automation system to the measuring device via the
current input → 15.
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS PA
2)Order code for "Sensor option", option DA, DB
Endress+Hauser15
Output
Output signalCurrent output
Current output 14-20 mA HART (passive)
Current output 24-20 mA (passive)
Resolution< 1 µA
DampingAdjustable: 0.0 to 999.9 s
Assignable measured
variables
Proline Prowirl F 200
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionPassive, open collector
Maximum input values• DC 35 V
• 50 mA
For information on the Ex connection values → 19
Voltage drop• For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current≤ 0.05 mA
Pulse output
Pulse widthAdjustable: 5 to 2000 ms
Maximum pulse rate100 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Output frequencyAdjustable: 0 to 1000 Hz
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Total mass flow
• Energy flow
• Heat flow difference
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Pressure
16Endress+Hauser
Proline Prowirl F 200
Switch output
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
Number of switching
cycles
Assignable functions• Off
Unlimited
• On
• Diagnostic behavior
• Limit value
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Pressure
• Reynolds number
• Totalizer 1-3
• Status
• Status of low flow cut off
Signal on alarm
FOUNDATION Fieldbus
FOUNDATION FieldbusH1, IEC 61158-2, galvanically isolated
Data transfer31.25 kbit/s
Current consumption15 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
PROFIBUS PA
PROFIBUS PAIn accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically
isolated
Data transmission31.25 kbit/s
Current consumption16 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure modeChoose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Endress+Hauser17
Pulse/frequency/switch output
Pulse output
Failure modeNo pulses
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1250 Hz
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Proline Prowirl F 200
Status and alarm
messages
Failure current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-891
0 mA
PROFIBUS PA
Status and alarm
messages
Failure current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
Local display
Plain text displayWith information on cause and remedial measures
BacklightAdditionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
• HART protocol
• FOUNDATION Fieldbus
• PROFIBUS PA
• Via service interface
CDI service interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 85
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply
unit
18Endress+Hauser
Proline Prowirl F 200
0
100
200
300
400
500
161820
2224
26283032
U [V]
S
RB[Ω]
3436
AB
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage
• For US = 17.9 to 18.9 V: RB ≤ (US - 17.9 V): 0.0036 A
• For US = 18.9 to 24 V: RB ≤ (US - 13 V): 0.022 A
• For US = ≥ 24 V: RB ≤ 500 Ω
AOperating range for order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/
frequency/switch output" with Ex i and option C "4-20 mA HART + 4-20 mA analog"
BOperating range for order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/
frequency/switch output" with non-Ex and Ex d
Sample calculation
Supply voltage of power supply unit: US =19 V
Maximum load: RB ≤ (19 V - 13 V): 0.022 A = 273 Ω
Ex connection dataSafety-related values
Type of protection Ex d
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Option C4-20mA HART
Option D4-20mA HARTU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
4-20mA analog
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Pulse/frequency/switch outputU
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
A0013563
Endress+Hauser19
Proline Prowirl F 200
Order code for "Output"Output typeSafety-related values
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
1)Internal circuit limited by Ri = 760.5 Ω
Type of protection Ex ec Ex nA
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option C4-20mA HART
4-20mA analog
Option D4-20mA HARTU
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Type of protection XP
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option C4-20mA HARTU
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
20Endress+Hauser
Proline Prowirl F 200
Order code for "Output"Output typeSafety-related values
4-20mA analog
Option D4-20mA HARTU
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
Type of protection Ex ia
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 30 nF
Endress+Hauser21
Proline Prowirl F 200
Order code for "Output"Output typeIntrinsically safe values
Option D4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Type of protection Ex ic
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 30 nF
22Endress+Hauser
Proline Prowirl F 200
Order code for "Output"Output typeIntrinsically safe values
Option D4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Type of protection IS
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 30 nF
Endress+Hauser23
Proline Prowirl F 200
Order code for "Output"Output typeIntrinsically safe values
Option D4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are preset and can be configured.
All inputs and outputs are galvanically isolated from one another.
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x0038
HART protocol revision7
Device description files
(DTM, DD)
HART load• Min. 250 Ω
System integrationFor information on system integration, see Operating Instructions.→ 96
Information and files under:
www.endress.com
• Max. 500 Ω
• Measured variables via HART protocol
• Burst Mode functionality
24Endress+Hauser
Proline Prowirl F 200
FOUNDATION Fieldbus
Manufacturer ID0x452B48
Ident number0x1038
Device revision2
DD revisionInformation and files under:
CFF revision
Device Tester Version (ITK
version)
ITK Test Campaign NumberInformation:
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Max. response delayMin. 5
System integrationFor information on system integration, see Operating Instructions.→ 96
• www.endress.com
• www.fieldbus.org
6.2.0
• www.endress.com
• www.fieldbus.org
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
• Read events
• Read trend data
• Cyclic data transmission
• Description of the modules
• Execution times
• Methods
PROFIBUS PA
Manufacturer ID0x11
Ident number0x1564
Profile version3.02
Device description files (GSD,
DTM, DD)
Information and files under:
• www.endress.com
• www.profibus.org
Endress+Hauser25
Supported functions• Identification & Maintenance
3412
4
56
+–+–+–
123
Configuration of the device
address
System integrationFor information on system integration, see Operating Instructions.→ 96
Power supply
Terminal assignmentTransmitter
Proline Prowirl F 200
Simple device identification via control system and nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e. g. FieldCare)
• Cyclic data transmission
• Block model
• Description of the modules
Connection versions
Maximum number of terminals
Terminals 1 to 6:
Without integrated overvoltage protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Input (passive): supply voltage and signal transmission
4
Ground terminal for cable shield
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
Option A4-20 mA HART (passive)--
Option B
Option C
Option D
1)
1)
1) 2)
4-20 mA HART (passive)
4-20 mA HART (passive) 4-20 mA analog (passive)-
4-20 mA HART (passive)
Maximum number of terminals for order code for
"Accessory mounted", option NA "Overvoltage
protection"
• Terminals 1 to 4:
With integrated overvoltage protection
• Terminals 5 to 6:
Without integrated overvoltage protection
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
A0033475
-
4-20 mA current input
(passive)
26Endress+Hauser
Proline Prowirl F 200
+–
+–
2
1
1
2
1234
1234
GNYEWHBN
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
Option E
Option G
1)Output 1 must always be used; output 2 is optional.
2)The integrated overvoltage protection is not used with option D: Terminals 5 and 6 (current input) are not
protected against overvoltage.
3)FOUNDATION Fieldbus with integrated reverse polarity protection.
4)PROFIBUS PA with integrated reverse polarity protection.
1) 3)
1) 4)
FOUNDATION Fieldbus
PROFIBUS PA
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
-
-
Connecting cable for remote version
Transmitter and sensor connection housing
In the case of the remote version, the sensor and transmitter are mounted separately from on
another and connected by a connecting cable. Connection is performed via the sensor connection
housing and the transmitter housing.
How the connecting cable is connected in the transmitter housing depends on the measuring
device approval and the version of the connecting cable used.
In the following versions, only terminals can be used for connection in the transmitter housing:
• Certain approvals: Ex nA, Ex ec, Ex tb and Division 1
• Use of reinforced connecting cable
• Order code for "Sensor version; DSC sensor; measuring tube", option DA, DB
In the following versions, an M12 device connector is used for connection in the transmitter
housing:
• All other approvals
• Use of connecting cable (standard)
Terminals are always used to connect the connecting cable in the sensor connection housing
(tightening torques for screws for cable strain relief: 1.2 to 1.7 Nm).
Connecting cable (standard, reinforced)
A0033476
2Terminals for connection compartment in the transmitter wall holder and the sensor connection housing
1Terminals for connecting cable
2Grounding via the cable strain relief