A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other
connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Communication symbols
SymbolMeaning
Wireless Local Area Network (WLAN)
Communication via a wireless, local network.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Visual inspection.
Symbols in graphics
SymbolMeaning
1, 2, 3, ...Item numbers
, 2., 3., …Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
Endress+Hauser3
SymbolMeaning
-
.
K-Factor =
Pulses
Unit Volume [m³]
Hazardous area
Safe area (non-hazardous area)
Flow direction
Function and system design
Proline Prowirl D 200
Measuring principle
Vortex meters work on the principle of the Karman vortex street. When fluid flows past a bluff body,
vortices are alternately formed on both sides with opposite directions of rotation. These vortices each
generate a local low pressure. The pressure fluctuations are recorded by the sensor and converted to
electrical pulses. The vortices develop very regularly within the permitted application limits of the
device. Therefore, the frequency of vortex shedding is proportional to the volume flow.
A0033465
1Sample graphic
The calibration factor (K-factor) is used as the proportional constant:
Within the application limits of the device, the K-factor only depends on the geometry of the device.
It is for Re > 20000:
• Independent of the flow velocity and the fluid properties viscosity and density
• Independent of the type of substance under measurement: steam, gas or liquid
The primary measuring signal is linear to the flow. After production, the K-factor is determined in
the factory by means of calibration. It is not subject to long-time drift or zero-point drift.
The device does not contain any moving parts and does not require any maintenance.
The capacitance sensor
The sensor of a vortex flowmeter has a major influence on the performance, robustness and
reliability of the entire measuring system.
4Endress+Hauser
A0003939-EN
Proline Prowirl D 200
12
The robust DSC sensor is:
• burst-tested
• tested against vibrations
• tested against thermal shock (thermal shocks of 150 K/s)
The measuring device uses the tried-and-tested, capacitance measuring technology from
Endress+Hauser, which is already in use in over 450000 measuring points worldwide. Thanks to its
design, the capacitance sensor is also particularly mechanically resistant to temperature shocks and
pressure shocks in steam pipelines.
Temperature measurement
The "mass" option is available under the order code for "Sensor version". With this option the
measuring device can also measure the temperature of the medium.
The temperature is measured via Pt 1000 temperature sensors. These are located in the paddle of
the DSC sensor and are therefore in the direct vicinity of the fluid.
Order code for "Sensor version; DSC sensor; measuring tube":
• Option AA "volume; 316L; 316L"
• Option BA "volume high-temperature; 316L; 316L"
• Option CA "Mass; 316L; 316L (integrated temperature measurement)"
A0034068
1Order code for "Sensor version", option "volume" or "volume high-temperature"
2Order code for "Sensor version", option "mass"
Lifelong calibration
Experience has shown that recalibrated measuring devices demonstrate a very high degree of
stability compared to their original calibration: The recalibration values were all within the original
measuring accuracy specifications of the devices. This applies to the measured volume flow, the
device's primary measured variable.
Various tests and simulation have shown that once the radii of the edges on the bluff body are less
than 1 mm (0.04 in), the resulting effect does not have a negative impact on accuracy.
If the radii of the edges on the bluff body do not exceed 1 mm (0.04 in), the following general
statements apply (in the case of non-abrasive and non-corrosive media, such as in most water and
steam applications):
• The measuring device does not display an offset in the calibration and the accuracy is still
guaranteed.
• All the edges on the bluff body have a radius that is typically smaller in size. As the measuring
devices are naturally also calibrated with these radii, the measuring device remains within the
specified accuracy rating provided that the additional radius that is produced as a result of wear
and tear does not exceed 1 mm (0.04 in).
Consequently, it can be said that the product line offers lifelong calibration if the measuring device is
used in non-abrasive and non-corrosive media.
Air and industrial gases
The measuring device enables users to calculate the density and energy of air and industrial gases.
The calculations are based on time-tested standard calculation methods. It is possible to
automatically compensate for the effect of pressure and temperature via an external or constant
value.
Endress+Hauser5
Proline Prowirl D 200
This makes it possible to output the energy flow, standard volume flow and mass flow of the
following gases:
• Single gas
• Gas mixture
• Air
• User-specific gas
For detailed information on the parameters, see the Operating Instructions.→ 75
Natural gas
The device enables users to calculate the chemical properties (gross calorific value, net calorific
value) of natural gases. The calculations are based on time-tested standard calculation methods. It is
possible to automatically compensate for the effect of pressure and temperature via an external or
constant value.
This makes it possible to output the energy flow, standard volume flow and mass flow in accordance
with the following standard methods:
Energy can be calculated based on the following standards:
• AGA5
• ISO 6976
• GPA 2172
Density can be calculated based on the following standards:
• ISO 12213-2 (AGA8-DC92)
• ISO 12213-3
• AGA NX19
• AGA8 Gross 1
• SGERG 88
For detailed information on the parameters, see the Operating Instructions.→ 75
6Endress+Hauser
Proline Prowirl D 200
Measuring system
The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version – transmitter and sensor form a mechanical unit.
• Remote version - transmitter and sensor are mounted in separate locations.
Transmitter
Prowirl 200Device versions and materials:
• Compact or remote version, aluminum coated:
Aluminum, AlSi10Mg, coated
• Compact or remote version, stainless:
For maximum corrosion resistance: stainless steel, CF3M
Configuration:
• Via four-line local display with key operation or via four-line,
illuminated local display with touch control and guided menus ("Make-
Order code for "Sensor version; DSC sensor; measuring tube"
OptionDescriptionMeasured variable
AAVolume; 316L; 316LVolume flow
BAVolume high-temperature; 316L; 316L
Order code for "Sensor version; DSC sensor; measuring tube"
OptionDescriptionMeasured variable
CAMass; 316L; 316L (integrated temperature measurement)• Volume flow
A0009922
• Temperature
Endress+Hauser7
Proline Prowirl D 200
Calculated measured variables
Order code for "Sensor version; DSC sensor; measuring tube"
OptionDescriptionMeasured variable
AAVolume; 316L; 316LUnder constant process conditions:
BAVolume high-temperature; 316L; 316L
1)A fixed density must be entered for calculating the mass flow (Setup menu → Advanced setup submenu →
External compensation submenu → Fixed density parameter).
Order code for "Sensor version; DSC sensor; measuring tube"
Option DescriptionMeasured variable
CAMass; 316L; 316L (integrated temperature measurement)• Corrected volume flow
• Mass flow
• Corrected volume flow
The totalized values for:
• Volume flow
• Mass flow
• Corrected volume flow
1)
• Mass flow
• Calculated saturated steam pressure
• Energy flow
• Heat flow difference
• Specific volume
• Degrees of superheat
Measuring range
The measuring range is dependent on the nominal diameter, the fluid and environmental influences.
The following specified values are the largest possible flow measuring ranges (Q
min
to Q
max
) for
each nominal diameter. Depending on the fluid properties and environmental influences, the
measuring range may be subject to additional restrictions. Additional restrictions apply to both
the lower range value and the upper range value.
Flow measuring ranges in SI units
DN
[mm]
150.06 to 4.90.3 to 25
250.18 to 150.9 to 130
400.45 to 372.3 to 310
500.75 to 623.8 to 820
801.7 to 1408.5 to 1800
1002.9 to 24015 to 3200
1506.7 to 54033 to 7300
Liquids
[m³/h]
Gas/steam
[m³/h]
Flow measuring ranges in US units
DNLiquidsGas/steam
[in][ft³/min][ft³/min]
½0.035 to 2.90.18 to 15
10.11 to 8.80.54 to 74
1½0.27 to 221.3 to 180
20.44 to 362.2 to 480
31 to 815 to 1100
41.7 to 1408.7 to 1900
63.9 to 32020 to 4300
8Endress+Hauser
Proline Prowirl D 200
D
i
v,Q
v [m/s] =
4 · Q [m /h]³
π · D [m]i²
·
1
3600 [s/h]
v [!/s] =
4 · Q [ /min]ft³
π · D [ft]i²
·
1
60 [s/min]
Re
=
4 · Q [m³/s] · [kg/m³]ρ
· D [m] · µ [Pa · s]π
i
Re
=
4 · Q [ft³/s] · [lbm/ft³]ρ
· D [ft] · µ [lbf · s/ft ]π
i
²
Flow velocity
A0033469
DiInternal diameter of measuring tube (corresponds to dimension K→ 47)
vVelocity in mating pipe
QFlow
The internal diameter of measuring tube Di is denoted in the dimensions as dimension
K.→ 47.
Calculation of flow velocity:
A0034301
Lower range value
A restriction applies to the lower range value due to the turbulent flow profile, which increases only
in the case of Reynolds 5000numbers. The Reynolds number is dimensionless and indicates the ratio
of the inertia force of a fluid to its viscous force when flowing and is used as a characteristic variable
for pipe flows. In the case of pipe flows with Reynolds numbers less than 5000, periodic vortices are
no longer generated and flow rate measurement is no longer possible.
The Reynolds number is calculated as follows:
A0034291
ReReynolds number
QFlow
D
µDynamic viscosity
ρDensity
Internal diameter of measuring tube (corresponds to dimension K→ 47)
i
The Reynolds number, 5000 together with the density and viscosity of the fluid and the nominal
diameter, is used to calculate the corresponding flow rate.
Endress+Hauser9
Proline Prowirl D 200
Q[m /h] =
Re = 5000
³
5000[Pa· · D [m] ·· s]
i
πμ
· 3600 [s/h]
4[kg/m ]·³ρ
Q[ /h] =
Re = 5000
!³
5000[lbf· · D [ft] ·· s/ft ]i²πμ
· 60 [s/min]
4[lbm/ ]·!³ρ
v[m/s] = max
AmpMin
mf [m/s]
x²
50 [m] · a [m/s ]²
v[!/s] = max
AmpMin
mf [!/s]
x²
164 [!] · a [ft/s ]²
Q[m /h] =
AmpMin
³
v[m/s]
AmpMin
· · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³
1 [kg/m ]³
Q[ /min] =
AmpMin
!³
v[!/s]
AmpMin
· · D [ft]i²π
· 60 [s/min]
4 ·
ρ [lbm/ ]#³
0.0624 [lbm/ ]!³
A0034302
Q
Re = 5000
D
i
Flow rate is dependent on the Reynolds number
Internal diameter of measuring tube (corresponds to dimension K→ 47)
µDynamic viscosity
ρDensity
The measuring signal must have a certain minimum signal amplitude so that the signals can be
evaluated without any errors. Using the nominal diameter, the corresponding flow can also be
derived from this amplitude. The minimum signal amplitude depends on the setting for the
sensitivity of the DSC sensor (s), the steam quality (x) and the force of the vibrations present (a). The
value mf corresponds to the lowest measurable flow velocity without vibration (no wet steam) at a
density of 1 kg/m3 (0.0624 lbm/ft^3). The value mf can be set in the range from
6 to 20 m/s (1.8 to 6 ft/s) (factory setting 12 m/s (3.7 ft/s)) with the Sensitivity parameter (value
range 1 to 9, factory setting 5).
v
AmpMin
Minimum measurable flow velocity based on signal amplitude
mfSensitivity
xSteam quality
aVibration
10Endress+Hauser
A0034303
A0034304
Proline Prowirl D 200
Q[m /h] = max
Low
³
Q [m /h]
min
³
Q[m /h]
Re = 5000
³
Q[m /h]
AmpMin
³
Q[! /min] = max
Low
³
Q [ /min]
min
!³
Q[ /min]
Re = 5000
!³
Q[ /min]
AmpMin
!³
Q[m /h] =
AmpMax
³
350[m/s] · · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³
1 [kg/m ]³
Q[ /min] =
AmpMax
!³
1148[!/s] · · D [ft]i²π
· 60 [s/min]
4 ·
ρ [lbm/ ]#³
0.0624 [lbm/ ]!³
Q
v
AmpMin
D
Minimum measurable flow rate based on signal amplitude
AmpMin
Minimum measurable flow velocity based on signal amplitude
Internal diameter of measuring tube (corresponds to dimension K→ 47)
i
ρDensity
The effective lower range value Q
5000
Q
Q
Q
Q
and Q
Low
min
Re = 5000
AmpMin
.
AmpMin
Effective lower range value
Minimum measurable flow rate
Flow rate is dependent on the Reynolds number
Minimum measurable flow rate based on signal amplitude
is determined using the largest of the three values Q
Low
min
, Q
Re =
A0034313
The Applicator is available for calculation purposes.
Upper range value
The measuring signal amplitude must be below a certain limit value to ensure that the signals can be
evaluated without error. This results in a maximum permitted flow rate Q
Q
D
ρDensity
Maximum measurable flow rate based on signal amplitude
AmpMax
Internal diameter of measuring tube (corresponds to dimension K→ 47)
i
AmpMax
:
A0034316
Endress+Hauser11
For gas applications, an additional restriction applies to the upper range value with regard to the
Mach number in the measuring device, which must be less than 0.3. The Mach number Ma describes
the ratio of the flow velocity v to the sound velocity c in the fluid.
Ma =
v [m/s]
c [m/s]
Ma =
v [!/s]
c [!/s]
MaMach number
Q[m /h] =
Ma = 0.3
³
0.3 · c [m/s] · · D [m]i²
π
4
· 3600 [s/h]
Q[ /min] =
Ma = 0.3
!³
0.3 · c [ft/s] · · D [ft]i²
π
4
· 60 [s/min]
Q[m /h] = min
High
³
Q[m /h]
max
³
Q[m /h]
AmpMax
³
Q[m /h]
Ma = 0.3
³
Q[! /min] = min
High
³
Q[ /min]
max
!³
Q[ /min]
AmpMax
!³
Q[ /min]
Ma = 0.3
!³
v
Flow velocity
cSound velocity
The corresponding flow rate can be derived using the nominal diameter.
Proline Prowirl D 200
A0034321
Q
Ma = 0.3
Restricted upper range value is dependent on Mach number
cSound velocity
D
i
Internal diameter of measuring tube (corresponds to dimension K→ 47)
ρDensity
The effective upper range value Q
Q
AmpMax
Q
High
Q
max
Q
AmpMax
Q
Ma = 0.3
and Q
Ma=0.3
.
Effective upper range value
Maximum measurable flow rate
Maximum measurable flow rate based on signal amplitude
Restricted upper range value is dependent on Mach number
is determined using the smallest of the three values Q
High
max
A0034337
,
A0034338
For liquids, the occurrence of cavitation may also restrict the upper range value.
The Applicator is available for calculation purposes.
Operable flow range
12Endress+Hauser
The value, which is typically up to 49: 1, may vary depending on the operating conditions (ratio
between upper range value and lower range value)
Proline Prowirl D 200
Input signalCurrent input
Current input4-20 mA (passive)
Resolution1 µA
Voltage dropTypically: 2.2 to 3 V for 3.6 to 22 mA
Maximum voltage≤ 35 V
Possible input variables• Pressure
External measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure
measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
• Various pressure measuring devices can be ordered as accessories from Endress+Hauser.
• If using pressure measuring devices, pay attention to outlet runs when installing external
devices→ 40.
If the device does not have temperature compensation, it is recommended that external pressure
measurement values be read in so that the following measured variables can be calculated:
• Energy flow
• Mass flow
• Corrected volume flow
• Temperature
• Density
Current input
The measured values are written from the automation system to the measuring device via the
current input → 13.
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS PA
Output
Output signalCurrent output
Current output 14-20 mA HART (passive)
Current output 24-20 mA (passive)
Resolution< 1 µA
Endress+Hauser13
DampingAdjustable: 0.0 to 999.9 s
Assignable measured
variables
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionPassive, open collector
Maximum input values• DC 35 V
• 50 mA
For information on the Ex connection values → 17
Proline Prowirl D 200
Voltage drop• For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current≤ 0.05 mA
Pulse output
Pulse widthAdjustable: 5 to 2000 ms
Maximum pulse rate100 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Output frequencyAdjustable: 0 to 1000 Hz
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
Switch output
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
• Mass flow
• Volume flow
• Corrected volume flow
• Total mass flow
• Energy flow
• Heat flow difference
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
• Pressure
14Endress+Hauser
Proline Prowirl D 200
Number of switching
cycles
Assignable functions• Off
Unlimited
• On
• Diagnostic behavior
• Limit value
– Volume flow
– Corrected volume flow
– Mass flow
– Flow velocity
– Temperature
– Calculated saturated steam pressure
– Total mass flow
– Energy flow
– Heat flow difference
– Pressure
– Reynolds number
– Totalizer 1-3
• Status
• Status of low flow cut off
FOUNDATION Fieldbus
FOUNDATION FieldbusH1, IEC 61158-2, galvanically isolated
Data transfer31.25 kbit/s
Current consumption15 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
Signal on alarm
PROFIBUS PA
PROFIBUS PAIn accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically
isolated
Data transfer31.25 kbit/s
Current consumption10 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure modeChoose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Pulse/frequency/switch output
Pulse output
Failure modeNo pulses
Endress+Hauser15
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1250 Hz
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Proline Prowirl D 200
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-891
0 mA
PROFIBUS PA
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
Local display
Plain text displayWith information on cause and remedial measures
BacklightAdditionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
– HART protocol
– FOUNDATION Fieldbus
– PROFIBUS PA
• Via service interface
CDI service interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 64
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply
unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage
16Endress+Hauser
Proline Prowirl D 200
0
100
200
300
400
500
121416
1820
22242628
U [V]
s
R [W]
b
1.11.21
30323436
• RB ≤ (US - U
term. min
): 0.022 A
• RB ≤ 500 Ω
2Load for a compact version without local operation
1Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i and option C "4-20 mA HART + 4-20 mA analog"
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" for non-hazardous area and Ex d
Sample calculation
Supply voltage of power supply unit:
– US = 19 V
– U
= 12 V (measuring device) + 1 V (local operation without lighting) = 13 V
term. min
Maximum load: RB ≤ (19 V - 13 V): 0.022 A = 273 Ω
The minimum terminal voltage (U
) increases if local operation is used..
Kl min
A0033472
Ex connection dataSafety-related values
Type of protection Ex d
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Option C4-20mA HART
Option D4-20mA HARTU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
4-20mA analog
Pulse/frequency/switch outputU
4 to 20 mA current inputU
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
Endress+Hauser17
Proline Prowirl D 200
Order code for "Output"Output typeSafety-related values
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
1)Internal circuit limited by Ri = 760.5 Ω
Type of protection Ex ec
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option C4-20mA HART
4-20mA analog
Option D4-20mA HARTU
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Type of protection XP
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
nom
U
max
nom
U
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
18Endress+Hauser
Proline Prowirl D 200
Order code for "Output"Output typeSafety-related values
Pulse/frequency/switch outputU
Option C4-20mA HART
4-20mA analog
Option D4-20mA HARTU
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
Type of protection Ex ia
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Option D4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 30 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Endress+Hauser19
Proline Prowirl D 200
Order code for "Output"Output typeIntrinsically safe values
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Type of protection Ex ic
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Option D4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 30 nF
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
20Endress+Hauser
Proline Prowirl D 200
Order code for "Output"Output typeIntrinsically safe values
Pulse/frequency/switch outputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Type of protection IS
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Option D4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 30 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Endress+Hauser21
Proline Prowirl D 200
Order code for "Output"Output typeIntrinsically safe values
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are preset and can be configured.
All inputs and outputs are galvanically isolated from one another.
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x0038
HART protocol revision7
Device description files
(DTM, DD)
HART load• Min. 250 Ω
System integrationFor information on system integration, see Operating Instructions.→ 75
FOUNDATION Fieldbus
Manufacturer ID0x452B48
Ident number0x1038
Device revision2
Information and files under:
www.endress.com
• Max. 500 Ω
• Measured variables via HART protocol
• Burst Mode functionality
22Endress+Hauser
Proline Prowirl D 200
DD revisionInformation and files under:
CFF revision
Device Tester Version (ITK
version)
ITK Test Campaign NumberInformation:
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Max. response delayMin. 5
System integrationFor information on system integration, see Operating Instructions.→ 75
• www.endress.com
• www.fieldbus.org
6.2.0
• www.endress.com
• www.fieldbus.org
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
• Read events
• Read trend data
• Cyclic data transmission
• Description of the modules
• Execution times
• Methods
PROFIBUS PA
Manufacturer ID0x11
Ident number0x1564
Profile version3.02
Device description files (GSD,
DTM, DD)
Information and files under:
• www.endress.com
• www.profibus.org
Endress+Hauser23
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.