A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other
connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Communication symbols
SymbolMeaning
Wireless Local Area Network (WLAN)
Communication via a wireless, local network.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Visual inspection.
Symbols in graphics
SymbolMeaning
1, 2, 3, ...Item numbers
, 2., 3., …Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
Endress+Hauser3
Page 4
SymbolMeaning
-
.
K-Factor =
Pulses
Unit Volume [m³]
Hazardous area
Safe area (non-hazardous area)
Flow direction
Function and system design
Proline Prowirl D 200
Measuring principle
Vortex meters work on the principle of the Karman vortex street. When fluid flows past a bluff body,
vortices are alternately formed on both sides with opposite directions of rotation. These vortices each
generate a local low pressure. The pressure fluctuations are recorded by the sensor and converted to
electrical pulses. The vortices develop very regularly within the permitted application limits of the
device. Therefore, the frequency of vortex shedding is proportional to the volume flow.
A0033465
1Sample graphic
The calibration factor (K-factor) is used as the proportional constant:
Within the application limits of the device, the K-factor only depends on the geometry of the device.
It is for Re > 20000:
• Independent of the flow velocity and the fluid properties viscosity and density
• Independent of the type of substance under measurement: steam, gas or liquid
The primary measuring signal is linear to the flow. After production, the K-factor is determined in
the factory by means of calibration. It is not subject to long-time drift or zero-point drift.
The device does not contain any moving parts and does not require any maintenance.
The capacitance sensor
The sensor of a vortex flowmeter has a major influence on the performance, robustness and
reliability of the entire measuring system.
4Endress+Hauser
A0003939-EN
Page 5
Proline Prowirl D 200
12
The robust DSC sensor is:
• burst-tested
• tested against vibrations
• tested against thermal shock (thermal shocks of 150 K/s)
The measuring device uses the tried-and-tested, capacitance measuring technology from
Endress+Hauser, which is already in use in over 450000 measuring points worldwide. Thanks to its
design, the capacitance sensor is also particularly mechanically resistant to temperature shocks and
pressure shocks in steam pipelines.
Temperature measurement
The "mass" option is available under the order code for "Sensor version". With this option the
measuring device can also measure the temperature of the medium.
The temperature is measured via Pt 1000 temperature sensors. These are located in the paddle of
the DSC sensor and are therefore in the direct vicinity of the fluid.
Order code for "Sensor version; DSC sensor; measuring tube":
• Option AA "volume; 316L; 316L"
• Option BA "volume high-temperature; 316L; 316L"
• Option CA "Mass; 316L; 316L (integrated temperature measurement)"
A0034068
1Order code for "Sensor version", option "volume" or "volume high-temperature"
2Order code for "Sensor version", option "mass"
Lifelong calibration
Experience has shown that recalibrated measuring devices demonstrate a very high degree of
stability compared to their original calibration: The recalibration values were all within the original
measuring accuracy specifications of the devices. This applies to the measured volume flow, the
device's primary measured variable.
Various tests and simulation have shown that once the radii of the edges on the bluff body are less
than 1 mm (0.04 in), the resulting effect does not have a negative impact on accuracy.
If the radii of the edges on the bluff body do not exceed 1 mm (0.04 in), the following general
statements apply (in the case of non-abrasive and non-corrosive media, such as in most water and
steam applications):
• The measuring device does not display an offset in the calibration and the accuracy is still
guaranteed.
• All the edges on the bluff body have a radius that is typically smaller in size. As the measuring
devices are naturally also calibrated with these radii, the measuring device remains within the
specified accuracy rating provided that the additional radius that is produced as a result of wear
and tear does not exceed 1 mm (0.04 in).
Consequently, it can be said that the product line offers lifelong calibration if the measuring device is
used in non-abrasive and non-corrosive media.
Air and industrial gases
The measuring device enables users to calculate the density and energy of air and industrial gases.
The calculations are based on time-tested standard calculation methods. It is possible to
automatically compensate for the effect of pressure and temperature via an external or constant
value.
Endress+Hauser5
Page 6
Proline Prowirl D 200
This makes it possible to output the energy flow, standard volume flow and mass flow of the
following gases:
• Single gas
• Gas mixture
• Air
• User-specific gas
For detailed information on the parameters, see the Operating Instructions.→ 75
Natural gas
The device enables users to calculate the chemical properties (gross calorific value, net calorific
value) of natural gases. The calculations are based on time-tested standard calculation methods. It is
possible to automatically compensate for the effect of pressure and temperature via an external or
constant value.
This makes it possible to output the energy flow, standard volume flow and mass flow in accordance
with the following standard methods:
Energy can be calculated based on the following standards:
• AGA5
• ISO 6976
• GPA 2172
Density can be calculated based on the following standards:
• ISO 12213-2 (AGA8-DC92)
• ISO 12213-3
• AGA NX19
• AGA8 Gross 1
• SGERG 88
For detailed information on the parameters, see the Operating Instructions.→ 75
6Endress+Hauser
Page 7
Proline Prowirl D 200
Measuring system
The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version – transmitter and sensor form a mechanical unit.
• Remote version - transmitter and sensor are mounted in separate locations.
Transmitter
Prowirl 200Device versions and materials:
• Compact or remote version, aluminum coated:
Aluminum, AlSi10Mg, coated
• Compact or remote version, stainless:
For maximum corrosion resistance: stainless steel, CF3M
Configuration:
• Via four-line local display with key operation or via four-line,
illuminated local display with touch control and guided menus ("Make-
Order code for "Sensor version; DSC sensor; measuring tube"
OptionDescriptionMeasured variable
AAVolume; 316L; 316LVolume flow
BAVolume high-temperature; 316L; 316L
Order code for "Sensor version; DSC sensor; measuring tube"
OptionDescriptionMeasured variable
CAMass; 316L; 316L (integrated temperature measurement)• Volume flow
A0009922
• Temperature
Endress+Hauser7
Page 8
Proline Prowirl D 200
Calculated measured variables
Order code for "Sensor version; DSC sensor; measuring tube"
OptionDescriptionMeasured variable
AAVolume; 316L; 316LUnder constant process conditions:
BAVolume high-temperature; 316L; 316L
1)A fixed density must be entered for calculating the mass flow (Setup menu → Advanced setup submenu →
External compensation submenu → Fixed density parameter).
Order code for "Sensor version; DSC sensor; measuring tube"
Option DescriptionMeasured variable
CAMass; 316L; 316L (integrated temperature measurement)• Corrected volume flow
• Mass flow
• Corrected volume flow
The totalized values for:
• Volume flow
• Mass flow
• Corrected volume flow
1)
• Mass flow
• Calculated saturated steam pressure
• Energy flow
• Heat flow difference
• Specific volume
• Degrees of superheat
Measuring range
The measuring range is dependent on the nominal diameter, the fluid and environmental influences.
The following specified values are the largest possible flow measuring ranges (Q
min
to Q
max
) for
each nominal diameter. Depending on the fluid properties and environmental influences, the
measuring range may be subject to additional restrictions. Additional restrictions apply to both
the lower range value and the upper range value.
Flow measuring ranges in SI units
DN
[mm]
150.06 to 4.90.3 to 25
250.18 to 150.9 to 130
400.45 to 372.3 to 310
500.75 to 623.8 to 820
801.7 to 1408.5 to 1800
1002.9 to 24015 to 3200
1506.7 to 54033 to 7300
Liquids
[m³/h]
Gas/steam
[m³/h]
Flow measuring ranges in US units
DNLiquidsGas/steam
[in][ft³/min][ft³/min]
½0.035 to 2.90.18 to 15
10.11 to 8.80.54 to 74
1½0.27 to 221.3 to 180
20.44 to 362.2 to 480
31 to 815 to 1100
41.7 to 1408.7 to 1900
63.9 to 32020 to 4300
8Endress+Hauser
Page 9
Proline Prowirl D 200
D
i
v,Q
v [m/s] =
4 · Q [m /h]³
π · D [m]i²
·
1
3600 [s/h]
v [!/s] =
4 · Q [ /min]ft³
π · D [ft]i²
·
1
60 [s/min]
Re
=
4 · Q [m³/s] · [kg/m³]ρ
· D [m] · µ [Pa · s]π
i
Re
=
4 · Q [ft³/s] · [lbm/ft³]ρ
· D [ft] · µ [lbf · s/ft ]π
i
²
Flow velocity
A0033469
DiInternal diameter of measuring tube (corresponds to dimension K→ 47)
vVelocity in mating pipe
QFlow
The internal diameter of measuring tube Di is denoted in the dimensions as dimension
K.→ 47.
Calculation of flow velocity:
A0034301
Lower range value
A restriction applies to the lower range value due to the turbulent flow profile, which increases only
in the case of Reynolds 5000numbers. The Reynolds number is dimensionless and indicates the ratio
of the inertia force of a fluid to its viscous force when flowing and is used as a characteristic variable
for pipe flows. In the case of pipe flows with Reynolds numbers less than 5000, periodic vortices are
no longer generated and flow rate measurement is no longer possible.
The Reynolds number is calculated as follows:
A0034291
ReReynolds number
QFlow
D
µDynamic viscosity
ρDensity
Internal diameter of measuring tube (corresponds to dimension K→ 47)
i
The Reynolds number, 5000 together with the density and viscosity of the fluid and the nominal
diameter, is used to calculate the corresponding flow rate.
Endress+Hauser9
Page 10
Proline Prowirl D 200
Q[m /h] =
Re = 5000
³
5000[Pa· · D [m] ·· s]
i
πμ
· 3600 [s/h]
4[kg/m ]·³ρ
Q[ /h] =
Re = 5000
!³
5000[lbf· · D [ft] ·· s/ft ]i²πμ
· 60 [s/min]
4[lbm/ ]·!³ρ
v[m/s] = max
AmpMin
mf [m/s]
x²
50 [m] · a [m/s ]²
v[!/s] = max
AmpMin
mf [!/s]
x²
164 [!] · a [ft/s ]²
Q[m /h] =
AmpMin
³
v[m/s]
AmpMin
· · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³
1 [kg/m ]³
Q[ /min] =
AmpMin
!³
v[!/s]
AmpMin
· · D [ft]i²π
· 60 [s/min]
4 ·
ρ [lbm/ ]#³
0.0624 [lbm/ ]!³
A0034302
Q
Re = 5000
D
i
Flow rate is dependent on the Reynolds number
Internal diameter of measuring tube (corresponds to dimension K→ 47)
µDynamic viscosity
ρDensity
The measuring signal must have a certain minimum signal amplitude so that the signals can be
evaluated without any errors. Using the nominal diameter, the corresponding flow can also be
derived from this amplitude. The minimum signal amplitude depends on the setting for the
sensitivity of the DSC sensor (s), the steam quality (x) and the force of the vibrations present (a). The
value mf corresponds to the lowest measurable flow velocity without vibration (no wet steam) at a
density of 1 kg/m3 (0.0624 lbm/ft^3). The value mf can be set in the range from
6 to 20 m/s (1.8 to 6 ft/s) (factory setting 12 m/s (3.7 ft/s)) with the Sensitivity parameter (value
range 1 to 9, factory setting 5).
v
AmpMin
Minimum measurable flow velocity based on signal amplitude
mfSensitivity
xSteam quality
aVibration
10Endress+Hauser
A0034303
A0034304
Page 11
Proline Prowirl D 200
Q[m /h] = max
Low
³
Q [m /h]
min
³
Q[m /h]
Re = 5000
³
Q[m /h]
AmpMin
³
Q[! /min] = max
Low
³
Q [ /min]
min
!³
Q[ /min]
Re = 5000
!³
Q[ /min]
AmpMin
!³
Q[m /h] =
AmpMax
³
350[m/s] · · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³
1 [kg/m ]³
Q[ /min] =
AmpMax
!³
1148[!/s] · · D [ft]i²π
· 60 [s/min]
4 ·
ρ [lbm/ ]#³
0.0624 [lbm/ ]!³
Q
v
AmpMin
D
Minimum measurable flow rate based on signal amplitude
AmpMin
Minimum measurable flow velocity based on signal amplitude
Internal diameter of measuring tube (corresponds to dimension K→ 47)
i
ρDensity
The effective lower range value Q
5000
Q
Q
Q
Q
and Q
Low
min
Re = 5000
AmpMin
.
AmpMin
Effective lower range value
Minimum measurable flow rate
Flow rate is dependent on the Reynolds number
Minimum measurable flow rate based on signal amplitude
is determined using the largest of the three values Q
Low
min
, Q
Re =
A0034313
The Applicator is available for calculation purposes.
Upper range value
The measuring signal amplitude must be below a certain limit value to ensure that the signals can be
evaluated without error. This results in a maximum permitted flow rate Q
Q
D
ρDensity
Maximum measurable flow rate based on signal amplitude
AmpMax
Internal diameter of measuring tube (corresponds to dimension K→ 47)
i
AmpMax
:
A0034316
Endress+Hauser11
For gas applications, an additional restriction applies to the upper range value with regard to the
Mach number in the measuring device, which must be less than 0.3. The Mach number Ma describes
the ratio of the flow velocity v to the sound velocity c in the fluid.
Page 12
Ma =
v [m/s]
c [m/s]
Ma =
v [!/s]
c [!/s]
MaMach number
Q[m /h] =
Ma = 0.3
³
0.3 · c [m/s] · · D [m]i²
π
4
· 3600 [s/h]
Q[ /min] =
Ma = 0.3
!³
0.3 · c [ft/s] · · D [ft]i²
π
4
· 60 [s/min]
Q[m /h] = min
High
³
Q[m /h]
max
³
Q[m /h]
AmpMax
³
Q[m /h]
Ma = 0.3
³
Q[! /min] = min
High
³
Q[ /min]
max
!³
Q[ /min]
AmpMax
!³
Q[ /min]
Ma = 0.3
!³
v
Flow velocity
cSound velocity
The corresponding flow rate can be derived using the nominal diameter.
Proline Prowirl D 200
A0034321
Q
Ma = 0.3
Restricted upper range value is dependent on Mach number
cSound velocity
D
i
Internal diameter of measuring tube (corresponds to dimension K→ 47)
ρDensity
The effective upper range value Q
Q
AmpMax
Q
High
Q
max
Q
AmpMax
Q
Ma = 0.3
and Q
Ma=0.3
.
Effective upper range value
Maximum measurable flow rate
Maximum measurable flow rate based on signal amplitude
Restricted upper range value is dependent on Mach number
is determined using the smallest of the three values Q
High
max
A0034337
,
A0034338
For liquids, the occurrence of cavitation may also restrict the upper range value.
The Applicator is available for calculation purposes.
Operable flow range
12Endress+Hauser
The value, which is typically up to 49: 1, may vary depending on the operating conditions (ratio
between upper range value and lower range value)
Page 13
Proline Prowirl D 200
Input signalCurrent input
Current input4-20 mA (passive)
Resolution1 µA
Voltage dropTypically: 2.2 to 3 V for 3.6 to 22 mA
Maximum voltage≤ 35 V
Possible input variables• Pressure
External measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure
measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
• Various pressure measuring devices can be ordered as accessories from Endress+Hauser.
• If using pressure measuring devices, pay attention to outlet runs when installing external
devices→ 40.
If the device does not have temperature compensation, it is recommended that external pressure
measurement values be read in so that the following measured variables can be calculated:
• Energy flow
• Mass flow
• Corrected volume flow
• Temperature
• Density
Current input
The measured values are written from the automation system to the measuring device via the
current input → 13.
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS PA
Output
Output signalCurrent output
Current output 14-20 mA HART (passive)
Current output 24-20 mA (passive)
Resolution< 1 µA
Endress+Hauser13
Page 14
DampingAdjustable: 0.0 to 999.9 s
Assignable measured
variables
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionPassive, open collector
Maximum input values• DC 35 V
• 50 mA
For information on the Ex connection values → 17
Proline Prowirl D 200
Voltage drop• For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current≤ 0.05 mA
Pulse output
Pulse widthAdjustable: 5 to 2000 ms
Maximum pulse rate100 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Output frequencyAdjustable: 0 to 1000 Hz
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
Switch output
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
• Mass flow
• Volume flow
• Corrected volume flow
• Total mass flow
• Energy flow
• Heat flow difference
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
• Pressure
14Endress+Hauser
Page 15
Proline Prowirl D 200
Number of switching
cycles
Assignable functions• Off
Unlimited
• On
• Diagnostic behavior
• Limit value
– Volume flow
– Corrected volume flow
– Mass flow
– Flow velocity
– Temperature
– Calculated saturated steam pressure
– Total mass flow
– Energy flow
– Heat flow difference
– Pressure
– Reynolds number
– Totalizer 1-3
• Status
• Status of low flow cut off
FOUNDATION Fieldbus
FOUNDATION FieldbusH1, IEC 61158-2, galvanically isolated
Data transfer31.25 kbit/s
Current consumption15 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
Signal on alarm
PROFIBUS PA
PROFIBUS PAIn accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically
isolated
Data transfer31.25 kbit/s
Current consumption10 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure modeChoose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Pulse/frequency/switch output
Pulse output
Failure modeNo pulses
Endress+Hauser15
Page 16
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1250 Hz
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Proline Prowirl D 200
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-891
0 mA
PROFIBUS PA
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
Local display
Plain text displayWith information on cause and remedial measures
BacklightAdditionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
– HART protocol
– FOUNDATION Fieldbus
– PROFIBUS PA
• Via service interface
CDI service interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 64
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply
unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage
16Endress+Hauser
Page 17
Proline Prowirl D 200
0
100
200
300
400
500
121416
1820
22242628
U [V]
s
R [W]
b
1.11.21
30323436
• RB ≤ (US - U
term. min
): 0.022 A
• RB ≤ 500 Ω
2Load for a compact version without local operation
1Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i and option C "4-20 mA HART + 4-20 mA analog"
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" for non-hazardous area and Ex d
Sample calculation
Supply voltage of power supply unit:
– US = 19 V
– U
= 12 V (measuring device) + 1 V (local operation without lighting) = 13 V
term. min
Maximum load: RB ≤ (19 V - 13 V): 0.022 A = 273 Ω
The minimum terminal voltage (U
) increases if local operation is used..
Kl min
A0033472
Ex connection dataSafety-related values
Type of protection Ex d
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Option C4-20mA HART
Option D4-20mA HARTU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
4-20mA analog
Pulse/frequency/switch outputU
4 to 20 mA current inputU
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
Endress+Hauser17
Page 18
Proline Prowirl D 200
Order code for "Output"Output typeSafety-related values
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
1)Internal circuit limited by Ri = 760.5 Ω
Type of protection Ex ec
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option C4-20mA HART
4-20mA analog
Option D4-20mA HARTU
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Type of protection XP
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
nom
U
max
nom
U
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
18Endress+Hauser
Page 19
Proline Prowirl D 200
Order code for "Output"Output typeSafety-related values
Pulse/frequency/switch outputU
Option C4-20mA HART
4-20mA analog
Option D4-20mA HARTU
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
Type of protection Ex ia
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Option D4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 30 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Endress+Hauser19
Page 20
Proline Prowirl D 200
Order code for "Output"Output typeIntrinsically safe values
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Type of protection Ex ic
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Option D4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 30 nF
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
20Endress+Hauser
Page 21
Proline Prowirl D 200
Order code for "Output"Output typeIntrinsically safe values
Pulse/frequency/switch outputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Type of protection IS
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
4-20mA analog
Option D4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 30 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Endress+Hauser21
Page 22
Proline Prowirl D 200
Order code for "Output"Output typeIntrinsically safe values
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
4 to 20 mA current inputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are preset and can be configured.
All inputs and outputs are galvanically isolated from one another.
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x0038
HART protocol revision7
Device description files
(DTM, DD)
HART load• Min. 250 Ω
System integrationFor information on system integration, see Operating Instructions.→ 75
FOUNDATION Fieldbus
Manufacturer ID0x452B48
Ident number0x1038
Device revision2
Information and files under:
www.endress.com
• Max. 500 Ω
• Measured variables via HART protocol
• Burst Mode functionality
22Endress+Hauser
Page 23
Proline Prowirl D 200
DD revisionInformation and files under:
CFF revision
Device Tester Version (ITK
version)
ITK Test Campaign NumberInformation:
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Max. response delayMin. 5
System integrationFor information on system integration, see Operating Instructions.→ 75
• www.endress.com
• www.fieldbus.org
6.2.0
• www.endress.com
• www.fieldbus.org
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
• Read events
• Read trend data
• Cyclic data transmission
• Description of the modules
• Execution times
• Methods
PROFIBUS PA
Manufacturer ID0x11
Ident number0x1564
Profile version3.02
Device description files (GSD,
DTM, DD)
Information and files under:
• www.endress.com
• www.profibus.org
Endress+Hauser23
Page 24
Supported functions• Identification & Maintenance
3412
4
56
+–+–+–
123
Configuration of the device
address
System integrationFor information on system integration, see Operating Instructions.→ 75
Power supply
Terminal assignmentTransmitter
Proline Prowirl D 200
Simple device identification via control system and nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e. g. FieldCare)
• Cyclic data transmission
• Block model
• Description of the modules
Connection versions
Maximum number of terminals
Terminals 1 to 6:
Without integrated overvoltage protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Input (passive): supply voltage and signal transmission
4
Ground terminal for cable shield
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
Option A4-20 mA HART (passive)--
Option B
Option C
Option D
1)
1)
1) 2)
4-20 mA HART (passive)
4-20 mA HART (passive) 4-20 mA analog (passive)-
4-20 mA HART (passive)
Maximum number of terminals for order code for
"Accessory mounted", option NA "Overvoltage
protection"
• Terminals 1 to 4:
With integrated overvoltage protection
• Terminals 5 to 6:
Without integrated overvoltage protection
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
A0033475
-
4-20 mA current input
(passive)
24Endress+Hauser
Page 25
Proline Prowirl D 200
+–
+–
2
1
1
2
1234
1234
GNYEWHBN
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
1) 3)
Option E
1) 4)
Option G
1)Output 1 must always be used; output 2 is optional.
2)The integrated overvoltage protection is not used with option D: Terminals 5 and 6 (current input) are not
protected against overvoltage.
3)FOUNDATION Fieldbus with integrated reverse polarity protection.
4)PROFIBUS PA with integrated reverse polarity protection.
FOUNDATION Fieldbus
PROFIBUS PA
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
-
-
Connecting cable for remote version
Transmitter and sensor connection housing
In the case of the remote version, the sensor and transmitter are mounted separately from on
another and connected by a connecting cable. Connection is performed via the sensor connection
housing and the transmitter housing.
How the connecting cable is connected in the transmitter housing depends on the measuring
device approval and the version of the connecting cable used.
In the following versions, only terminals can be used for connection in the transmitter housing:
• Certain approvals: Ex nA, Ex ec, Ex tb and Division 1
• Use of reinforced connecting cable
In the following versions, an M12 device connector is used for connection in the transmitter
housing:
• All other approvals
• Use of connecting cable (standard)
Terminals are always used to connect the connecting cable in the sensor connection housing
(tightening torques for screws for cable strain relief: 1.2 to 1.7 Nm).
Connecting cable (standard, reinforced)
A0033476
3Terminals for connection compartment in the transmitter wall holder and the sensor connection housing
1Terminals for connecting cable
Endress+Hauser25
2Grounding via the cable strain relief
Terminal numberAssignmentCable color
Connecting cable
1Supply voltageBrown
2GroundingWhite
Page 26
Terminal numberAssignmentCable color
1
2
4
3
1
2
4
3
Pin assignment, device plugPROFIBUS PA
FOUNDATION Fieldbus
Proline Prowirl D 200
Connecting cable
3RS485 (+)Yellow
4RS485 (–)Green
PinAssignmentCodingPlug/socket
1+PROFIBUS PA +APlug
2Grounding
3-PROFIBUS PA –
4Not assigned
PinAssignmentCodingPlug/socket
1+Signal +APlug
2-Signal –
3Grounding
4Not assigned
Supply voltageTransmitter
An external power supply is required for each output.
Supply voltage for a compact version without a local display
Order code for "Output; input"Minimum
Option A: 4-20 mA HART≥ DC 12 VDC 35 V
Option B: 4-20 mA HART, pulse/
frequency/switch output
Option C: 4-20 mA HART + 4-20 mA
analog
Option D: 4-20 mA HART, pulse/
frequency/switch output, 4-20 mA current
3)
input
Option E: FOUNDATION Fieldbus, pulse/
frequency/switch output
How the connecting cable is connected in the transmitter housing depends on the measuring
device approval and the version of the connecting cable used.
In the following versions, only terminals can be used for connection in the transmitter housing:
• Certain approvals: Ex nA, Ex ec, Ex tb and Division 1
• Use of reinforced connecting cable
In the following versions, an M12 device connector is used for connection in the transmitter
housing:
• All other approvals
• Use of connecting cable (standard)
Terminals are always used to connect the connecting cable in the sensor connection housing
(tightening torques for screws for cable strain relief: 1.2 to 1.7 Nm).
28Endress+Hauser
Page 29
Proline Prowirl D 200
2
3
4...20 mA
41
5
1
2
3
12345
1
2
3
Connection examples
Current output 4-20 mA HART
A0028762
5Connection example for 4 to 20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Power supply
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
4Analog display unit: observe maximum load
5Transmitter
Pulse/frequency output
6Connection example for pulse/frequency output (passive)
1Automation system with pulse/frequency input (e.g. PLC)
2Power supply
3Transmitter: Observe input values
Switch output
A0028761
A0028760
7Connection example for switch output (passive)
1Automation system with switch input (e.g. PLC)
2Power supply
3Transmitter: Observe input values
Endress+Hauser29
Page 30
FOUNDATION Fieldbus
2134
78
66
6
6
5
6
6
5
Proline Prowirl D 200
A0028768
8Connection example for FOUNDATION Fieldbus
1Control system (e.g. PLC)
2Power Conditioner (FOUNDATION Fieldbus)
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
1Control system (e.g. PLC)
2PROFIBUS PA segment coupler
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
4T-box
5Measuring device
6Local grounding
7Bus terminator
8Potential matching line
Current input
10Connection example for 4-20 mA current input
1Active barrier for power supply (e.g. RN221N)
2Terminal box
3External measuring device (for reading in pressure or temperature, for instance)
4Transmitter: Observe input values → 13
A0028768
specifications
A0028915
Endress+Hauser31
Page 32
Proline Prowirl D 200
2
4...20 mA
4
1
2
3
3
6
5
HART input
A0028763
11Connection example for HART input with a common negative (passive)
1Automation system with HART output (e.g. PLC)
2Active barrier for power supply (e.g. RN221N)
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
4Analog display unit: observe maximum load
5Pressure measuring device (e.g. Cerabar M, Cerabar S): see requirements
6Transmitter
Potential equalizationRequirements
Please consider the following to ensure correct measurement:
• Same electrical potential for the fluid and sensor
• Remote version: same electrical potential for the sensor and transmitter
• Company-internal grounding concepts
• Pipe material and grounding
Terminals
• For device version without integrated overvoltage protection: plug-in spring terminals for wire
cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• For device version with integrated overvoltage protection: screw terminals for wire cross-sections
0.2 to 2.5 mm2 (24 to 14 AWG)
Cable entries
• Cable gland (not for Ex d): M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
– For non-hazardous and hazardous areas: NPT ½"
– For non-hazardous and hazardous areas (not for XP): G ½"
– For Ex d: M20 × 1.5
Cable specificationPermitted temperature range
• The installation guidelines that apply in the country of installation must be observed.
• The cables must be suitable for the minimum and maximum temperatures to be expected.
Signal cable
Current output 4 to 20 mA HART
A shielded cable is recommended. Observe grounding concept of the plant.
Current output 4 to 20 mA
Standard installation cable is sufficient.
Pulse/frequency/switch output
Standard installation cable is sufficient.
32Endress+Hauser
Page 33
Proline Prowirl D 200
Current input
Standard installation cable is sufficient.
FOUNDATION Fieldbus
Twisted, shielded two-wire cable.
For further information on planning and installing FOUNDATION Fieldbus networks see:
• Operating Instructions for "FOUNDATION Fieldbus Overview" (BA00013S)
• FOUNDATION Fieldbus Guideline
• IEC 61158-2 (MBP)
PROFIBUS PA
Twisted, shielded two-wire cable. Cable type A is recommended .
For further information on planning and installing PROFIBUS PA networks see:
• Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning"
(BA00034S)
• PNO Directive 2.092 "PROFIBUS PA User and Installation Guideline"
• IEC 61158-2 (MBP)
Connecting cable for remote version
Connecting cable (standard)
Standard cable
Flame resistanceAccording to DIN EN 60332-1-2
Oil-resistanceAccording to DIN EN 60811-2-1
ShieldingGalvanized copper-braid, opt. density approx.85 %
Cable length5 m (16 ft), 10 m (32 ft), 20 m (65 ft), 30 m (98 ft)
Operating temperatureWhen mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
1)UV radiation may cause damage to the outer jacket of the cable. Protect the cable from exposure to sun as
much as possible.
2 × 2 × 0.5 mm2 (22 AWG) PVC cable with common shield (2 pairs, pairstranded)
can move freely: –25 to +105 °C (–13 to +221 °F)
1)
Connecting cable (reinforced)
Cable, reinforced
Flame resistanceAccording to DIN EN 60332-1-2
Oil-resistanceAccording to DIN EN 60811-2-1
ShieldingGalvanized copper-braid, opt. density approx. 85%
Strain relief and
reinforcement
Cable length5 m (16 ft), 10 m (32 ft), 20 m (65 ft), 30 m (98 ft)
Operating temperatureWhen mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
2 × 2 × 0.34 mm2 (22 AWG) PVC cable with common shield (2 pairs, pairstranded) and additional steel-wire braided sheath
Steel-wire braid, galvanized
can move freely: –25 to +105 °C (–13 to +221 °F)
1)
1)UV radiation may cause damage to the outer jacket of the cable. Protect the cable from exposure to sun as
much as possible.
Overvoltage protection
The device can be ordered with integrated overvoltage protection for diverse approvals:
Order code for "Accessory mounted", option NA "Overvoltage protection"
Endress+Hauser33
Page 34
Proline Prowirl D 200
Re
min
Re
max
Re
Re
max
A2
A1
-A2
Re
1
Re
2
Reference operating
conditions
Input voltage rangeValues correspond to supply voltage specifications → 26
Resistance per channel2 ⋅ 0.5 Ω max.
DC sparkover voltage400 to 700 V
Trip surge voltage< 800 V
Capacitance at 1 MHz< 1.5 pF
Nominal discharge current
(8/20 μs)
Temperature range–40 to +85 °C (–40 to +185 °F)
1)The voltage is reduced by the amount of the internal resistance I
10 kA
min
⋅ R
i
Depending on the temperature class, restrictions apply to the ambient temperature for device
versions with overvoltage protection .
For detailed information on the temperature tables, see the "Safety Instructions" (XA) for the
device.
Performance characteristics
• Error limits following ISO/DIN 11631
• +20 to +30 °C (+68 to +86 °F)
• 2 to 4 bar (29 to 58 psi)
• Calibration system traceable to national standards
• Calibration with the process connection corresponding to the particular standard
To obtain measured errors, use the Applicator sizing tool → 74
1)
Maximum measured errorBase accuracy
o.r. = of reading
Re
Re
1
2
Reynolds numbers
A0034077
IncompressibleCompressible
StandardStandard
5000
20000
34Endress+Hauser
Page 35
Proline Prowirl D 200
Volume flow
Medium typeIncompressibleCompressible
Reynolds number rangeMeasured value deviationStandardStandard
Re1 to Re
Re2 to Re
2
max
A2< 10 %< 10 %
A1< 0.75 %< 1.0 %
1)Accuracy specifications valid up to 75 m/s (246 ft/s)
Temperature
• Saturated steam and liquids at room temperature, if T > 100 °C (212 °F) applies:
< 1 °C (1.8 °F)
• Gas:
< 1 % o.r. [K]
• Volume flow if > 70 m/s (230 ft/s):
2 % o.r.
Rise time 50 % (stirred under water, following IEC 60751): 8 s
Mass flow saturated steam
Flow velocity
[m/s (ft/s)]
20 to 50
(66 to 164)
10 to 70
(33 to 210)
< 10 (33)–Re > Re
Temperature
[°C (°F)]
150 (302) or
(423 K)
> 140 (284) or
(413 K)
Reynolds number
range
Re2 to Re
Re1 to Re
Re2 to Re
Re1 to Re
max
2
max
2
1
Maximum
Standard
measured error
A1< 1.7 %
A2< 10 %
A1< 2 %
A2< 10 %
A2, A15%
1)
max
2
max
2
1)
Measured value deviationStandard
A11.7 %
A210 %
A12.6 %
A210 %
1)
Mass flow of superheated steam/gases
Process pressure
[bar abs. (psi abs.)]
< 40 (580)Re2 to Re
< 120 (1740)Re2 to Re
Reynolds number
range
Re1 to Re
Re1 to Re
1)The use of a Cerabar S is required for the measured errors listed in the following section. The measured
error used to calculate the error in the measured pressure is 0.15 %.
Water mass flow
Reynolds number rangeMeasured value deviationStandard
Re = Re
Re1 to Re
2
2
A1< 0.85 %
A2< 10 %
1)single gas, gas mixture, air: NEL40; natural gas: ISO 12213-2 contains AGA8-DC92, AGA NX-19, ISO 12213-3 contains SGERG-88 and AGA8
Gross Method 1
Endress+Hauser35
Page 36
Proline Prowirl D 200
Mass flow (user-specific liquids)
To specify the system accuracy, Endress+Hauser requires information about the type of liquid and its
operating temperature or information in table form about the dependency between the liquid
density and the temperature.
Example
• Acetone is to be measured at fluid temperatures from +70 to +90 °C (+158 to +194 °F).
• For this purpose, the Reference temperature parameter (7703) (here 80 °C (176 °F)), Referencedensity parameter (7700) (here 720.00 kg/m3) and Linear expansion coefficient parameter
(7621) (here 18.0298 × 10-4 1/°C) must be entered in the transmitter.
• The overall system uncertainty, which is less than 0.9 % for the example above, is comprised of the
following measurement uncertainties: uncertainty of volume flow measurement, uncertainty of
temperature measurement, uncertainty of the density-temperature correlation used (including the
resulting uncertainty of density).
Mass flow (other media)
Depends on the selected fluid and the pressure value, which is specified in the parameters. Individual
error analysis must be performed.
Diameter mismatch correction
Prowirl 200 can correct shifts in the calibration factor which are caused, for example, by diameter
mismatch between the device flange (e.g. ASME B16.5/Sch. 80, DN 50 (2")) and the mating pipe
(e.g. ASME B16.5/Sch. 40, DN 50 (2")). Only apply diameter mismatch correction within the
following limit values (listed below) for which test measurements have also been performed.
If the standard internal diameter of the ordered process connection differs from the internal
diameter of the mating pipe, an additional measuring uncertainty of approx. 2 % o.r. must be
expected.
Example
Influence of the diameter mismatch without using the correction function:
• Mating pipe DN 100 (4"), schedule 80
• Device flange DN 100 (4"), schedule 40
• This installation position results in a diameter mismatch of 5 mm (0.2 in). If the correction
function is not used, an additional measuring uncertainty of approx. 2 % o.r. must be expected.
For detailed information about diameter mismatch correction, refer to the Operating
Instructions
Repeatability
Response time
Accuracy of outputs
The outputs have the following base accuracy specifications.
Current output
Accuracy±10 µA
Pulse/frequency output
o.r. = of reading
AccuracyMax. ±100 ppm o.r.
o.r. = of reading
±0.2 % o.r.
If all the configurable functions for filter times (flow damping, display damping, current output time
constant, frequency output time constant, status output time constant) are set to 0, in the event of
vortex frequencies of 10 Hz and higher a response time of max(Tν,100 ms) can be expected.
In the event of measuring frequencies < 10 Hz, the response time is > 100 ms and can be up to 10 s.
Tν is the average vortex period duration of the flowing fluid.
36Endress+Hauser
Page 37
Proline Prowirl D 200
Influence of ambient
temperature
Mounting location
Current output
o.r. = of reading
Additional error, based on span of 16 mA:
Temperature coefficient at
zero point (4 mA)
Temperature coefficient
with span (20 mA)
0.02 %/10 K
0.05 %/10 K
Pulse/frequency output
o.r. = of reading
Temperature coefficientMax. ±100 ppm o.r.
Installation
Orientation
A0015543
The direction of the arrow on the sensor nameplate helps you to install the sensor according to the
flow direction (direction of medium flow through the piping).
Vortex meters require a fully developed flow profile as a prerequisite for correct volume flow
measurement. Therefore, please note the following:
OrientationCompact versionRemote version
A Vertical orientation
A0015545
B Horizontal orientation, transmitter head up
A0015589
1)
2) 3)
Endress+Hauser37
Page 38
Proline Prowirl D 200
OrientationCompact versionRemote version
C Horizontal orientation, transmitter head down
A0015590
D Horizontal orientation, transmitter head at side
A0015592
1)In the case of liquids, there should be upward flow in vertical pipes to avoid partial pipe filling (Fig. A).
Disruption in flow measurement! In the case of vertical orientation and downward flowing liquid, the pipe
always needs to be completely filled to ensure correct liquid flow measurement.
2)Danger of electronics overheating! If the fluid temperature is ≥ 200 °C (392 °F), orientation B is not
permitted for the wafer version (Prowirl D) with nominal diameters of DN 100 (4") and DN 150 (6").
3)In the case of hot media (e.g. steam or fluid temperature (TM) ≥ 200 °C (392 °F): orientation C or D
4)In the case of very cold media (e.g. liquid nitrogen): orientation B or D
4)
Inlet and outlet runs
To attain the specified level of accuracy of the measuring device, the inlet and outlet runs mentioned
below must be maintained at the very minimum.
38Endress+Hauser
Page 39
Proline Prowirl D 200
1
15 DN×
5 × DN
3
25 × DN
5 × DN
40 × DN
5 × DN
4
2
20 × DN
5 × DN
5
20 × DN
5 × DN
6
17 × DN + 8 × h
5 × DN
h
7
50 × DN
5 × DN
9
40 × DN
5 × DN
8
5 × DN
DN 25 (1"):≤
DN 40 (1½"):≥
A0019189
12Minimum inlet and outlet runs with various flow obstructions
hDifference in expansion
1Reduction by one nominal diameter size
2Single elbow (90° elbow)
3Double elbow (2 × 90° elbows, opposite)
4Double elbow 3D (2 × 90° elbows, opposite, not on one plane)
5T-piece
6Expansion
7Control valve
8Two measuring devices in a row where DN ≤ 25 (1"): directly flange on flange
9Two measuring devices in a row where DN ≥ 40 (1½"): for spacing, see graphic
• If there are several flow disturbances present, the longest specified inlet run must be
maintained.
• If the required inlet runs cannot be observed, it is possible to install a specially designed flow
conditioner → 39.
Flow conditioner
If the inlet runs cannot be observed, the use of a flow conditioner is recommended.
The flow conditioner is fitted between two pipe flanges and centered by the mounting bolts.
Generally this reduces the inlet run needed to 10 × DN with full accuracy.
Endress+Hauser39
Page 40
8 DN×
5 DN×
1
1Flow conditioner
3…5 × DN
4…8 × DN
PT
TT
Proline Prowirl D 200
A0019208
The pressure loss for flow conditioners is calculated as follows: ∆ p [mbar] = 0.0085 ⋅ ρ [kg/m3] ⋅ v
[m/s]
Example for steamExample for H2O condensate (80 °C)
p = 10 bar abs.ρ = 965 kg/m
t = 240 °C → ρ = 4.39 kg/m
v = 40 m/s∆ p = 0.0085 ⋅ 965 ⋅ 2.5 2 = 51.3 mbar
∆ p = 0.0085 ⋅ 4.394.39 ⋅ 40 2 = 59.7 mbar
ρ : density of the process medium
v: average flow velocity
abs. = absolute
3
v = 2.5 m/s
3
A specially designed flow conditioner is available from Endress+Hauser: → 50
Outlet runs when installing external devices
If installing an external device, observe the specified distance.
2
A0019205
PT Pressure
TT Temperature device
Mounting kit for disc (wafer
version)
The centering rings supplied are used to mount and center the wafer-style devices.
A mounting kit comprises:
• Tie rods
• Seals
• Nuts
• Washers
40Endress+Hauser
Page 41
Proline Prowirl D 200
1
2
3
80 (3.15)
80 (3.15)
19 (0.6)
! 8.6 (0.39)
M8
A0019875
13Mounting kit for wafer version
1Nut, washer, tie rod
2Seal
3Centering ring (is supplied with the measuring device)
Length of connecting cable
Mounting the transmitter
housing
To ensure correct measuring results when using the remote version,
• observe the maximum permitted cable length: L
= 30 m (90 ft).
max
• The value for the cable length must be calculated if the cable cross-section differs from the
specification.
For detailed information about calculating the length of the connecting cable, refer to the
Operating Instructions for the device on the CD-ROM provided
Wall mounting
14mm (in)
A0033484
Endress+Hauser41
Page 42
Post mounting
!…20 70
(! 0.79 to 2.75)
4 x
SW 13
Q
TT
1
2
3
15mm (in)
Proline Prowirl D 200
A0033486
Special mounting
instructions
Installation for delta heat measurements
The second temperature measurement is taken using a separate temperature sensor. The measuring
device reads in this value via a communication interface.
• In the case of saturated steam delta heat measurements, the measuring device must be installed
on the steam side.
• In the case of water delta heat measurements, the device can be installed on the cold or warm side.
A0019209
16Layout for delta heat measurement of saturated steam and water
Observe the following minimum head clearance: 222 mm (8.74 in)
For information on the weather protection cover, see → 72
42Endress+Hauser
Page 43
Proline Prowirl D 200
Environment
Ambient temperature range
Compact version
Measuring deviceNon-hazardous area:–40 to +80 °C (–40 to +176 °F)
Ex i, Ex nA, Ex ec:–40 to +70 °C (–40 to +158 °F)
Ex d, XP:–40 to +60 °C (–40 to +140 °F)
Ex d, Ex ia:–40 to +60 °C (–40 to +140 °F)
Local display–40 to +70 °C (–40 to +158 °F)
1)Additionally available as order code for "Test, certificate", option JN "Transmitter ambient temperature –
50 °C (–58 °F)".
2)At temperatures < –20 °C (–4 °F), depending on the physical characteristics involved, it may no longer be
possible to read the liquid crystal display.
1)
1)
1)
1)
2) 1)
Remote version
TransmitterNon-hazardous area:–40 to +80 °C (–40 to +176 °F)
Ex i, Ex nA, Ex ec:–40 to +80 °C (–40 to +176 °F)
Ex d:–40 to +60 °C (–40 to +140 °F)
Ex d, Ex ia:–40 to +60 °C (–40 to +140 °F)
SensorNon-hazardous area:–40 to +85 °C (–40 to +185 °F)
Ex i, Ex nA, Ex ec:–40 to +85 °C (–40 to +185 °F)
Ex d:–40 to +85 °C (–40 to +185 °F)
Ex d, Ex ia:–40 to +85 °C (–40 to +185 °F)
Local display–40 to +70 °C (–40 to +158 °F)
1)
1)
1)
1)
1)
1)
1)
1)
2) 1)
Storage temperature
Climate class
Degree of protection
1)Additionally available as order code for "Test, certificate", option JN "Transmitter ambient temperature –
50 °C (–58 °F)".
2)At temperatures < –20 °C (–4 °F), depending on the physical characteristics involved, it may no longer be
possible to read the liquid crystal display.
If operating outdoors:
‣
Avoid direct sunlight, particularly in warm climatic regions.
You can order a weather protection cover from Endress+Hauser. → 72.
All components apart from the display modules:
–50 to +80 °C (–58 to +176 °F)
Display modules
All components apart from the display modules:
–50 to +80 °C (–58 to +176 °F)
Remote display FHX50:
–50 to +80 °C (–58 to +176 °F)
DIN EN 60068-2-38 (test Z/AD)
Transmitter
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure
Sensor
IP66/67, type 4X enclosure
Endress+Hauser43
Page 44
Connector
IP67, only in screwed situation
Proline Prowirl D 200
Vibration resistance
Shock resistance
Vibration, sinusoidal according to IEC 60068-2-6
• Order code for "Housing", option C "GT20 two-chamber, aluminum, coated, compact", J "GT20 twochamber, aluminum, coated, remote", K "GT18 two-chamber, 316L, remote"
– 2 to 8.4 Hz, 7.5 mm peak
– 8.4 to 500 Hz, 2 g peak
• Order code for "Housing", option B "GT18 two-chamber, 316L, compact"
– 2 to 8.4 Hz, 3.5 mm peak
– 8.4 to 500 Hz, 1 g peak
Vibration broad-band random, according to IEC 60068-2-64
• Order code for "Housing", option C "GT20 two-chamber, aluminum, coated, compact", J "GT20 twochamber, aluminum, coated, remote", K "GT18 two-chamber, 316L, remote"
– 10 to 200 Hz, 0.01 g2/Hz
– 200 to 500 Hz, 0.003 g2/Hz
– Total 2.7 g rms
• Order code for "Housing", option B "GT18 two-chamber, 316L, compact"
– 10 to 200 Hz, 0.003 g2/Hz
– 200 to 500 Hz, 0.001 g2/Hz
– Total 1.54 g rms
Shock, half-sine according to IEC 60068-2-27
• Order code for "Housing", option C "GT20 two-chamber, aluminum, coated, compact", J "GT20 twochamber, aluminum, coated, remote", K "GT18 two-chamber, 316L, remote"
6 ms, 50 g
• Order code for "Housing", option B "GT18 two-chamber, 316L, compact"
6 ms, 30 g
Impact resistance
Electromagnetic
compatibility (EMC)
Medium temperature range
Rough handling shocks according to IEC 60068-2-31
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
Details are provided in the Declaration of Conformity.
Process
DSC sensor
Order code for "Sensor version; DSC sensor; measuring tube"
Option DescriptionMedium temperature range
AAVolume; 316L; 316L–40 to +260 °C (–40 to +500 °F), stainless steel
BAVolume high-temperature; 316L; 316L–200 to +400 °C (–328 to +750 °F), stainless steel
CAMass; 316L; 316L–200 to +400 °C (–328 to +750 °F), stainless steel
1)Capacitance sensor
Seals
Order code for "DSC sensor seal"
OptionDescriptionMedium temperature range
AGraphite (standard)–200 to +400 °C (–328 to +752 °F)
BViton–15 to +175 °C (+5 to +347 °F)
CGylon–200 to +260 °C (–328 to +500 °F)
DKalrez–20 to +275 °C (–4 to +527 °F)
1)
44Endress+Hauser
Page 45
Proline Prowirl D 200
0
10
20
30
40
50
60
-200-1000100200300400
[°C]
[°F]
[bar][psi]
0
100
200
300
400
500
600
700
800
900
-400-2000800200600400
PN10
PN16
PN25
PN40
0
10
20
30
40
50
60
-200-1000100200300400
[°C]
[°F]
[bar][psi]
0
100
200
300
400
500
600
700
800
900
-400-2000800200600400
PN10
PN16
PN25
PN40
-400
0
10
20
30
40
50
60
-200-1000100200300400
[°C]
[°F]
[bar][psi]
0
100
200
300
400
500
600
700
800
900
-2000800200600400
PN40
Class 300
PN40
Class 150
0
10
20
30
40
50
60
-200-1000100200300400
[°C]
[°F]
[bar][psi]
0
100
200
300
400
500
600
700
800
900
-2000800200600400
PN40
Class 300
PN40
Class 150
Pressure-temperature
ratings
The following pressure/temperature diagrams apply to all pressure-bearing parts of the device and
not just the process connection. The diagrams show the maximum permissible medium pressure
depending on the specific medium temperature.
The pressure-temperature rating for the specific measuring device is programmed into the software.
If values exceed the curve range a warning is displayed. Depending on the system configuration and
sensor version, the pressure and temperature are determined by entering, reading in or calculating
values.
Wafer flange for pressure ratings according to EN 1092-1, material group 13E0
A0034042-EN
17Material: stainless steel, CF3M/1.4408
Wafer flange for pressure ratings according to ASME B16.5, material group 2.2
A0034040-EN
18Material: stainless steel, CF3M/1.4408
Endress+Hauser45
Page 46
Wafer flange for connection to flanges according to JIS B2220
0
10
20
30
40
50
60
-200-1000100200300400
[°C]
[°F]
[bar][psi]
0
100
200
300
400
500
600
700
800
900
-400-2000800200600400
20K
10K
0
10
20
30
40
50
60
-200-1000100200300400
[°C]
[°F]
[bar][psi]
0
100
200
300
400
500
600
700
800
900
-400-2000800200600400
20K
10K
19Material: stainless steel, CF3M/1.4408
Proline Prowirl D 200
A0034043-EN
Nominal pressure of sensor
Pressure loss
Thermal insulation
The following overpressure resistance values apply to the sensor shaft in the event of a membrane
rupture:
For a precise calculation, use the Applicator→ 74.
For optimum temperature measurement and mass calculation, heat transfer at the sensor must be
avoided for some fluids. This can be ensured by installing thermal insulation. A wide range of
materials can be used for the required insulation.
This applies for:
• Compact version
• Remote sensor version
The maximum insulation height permitted is illustrated in the diagram:
46Endress+Hauser
1Maximum insulation height
When insulating, ensure that a sufficiently large area of the housing support remains exposed.
‣
The uncovered part serves as a radiator and protects the electronics from overheating and excessive
cooling.
A0019212
Page 47
Proline Prowirl D 200
A
B
C
E
F
K
D
G
H
I
LM
Mechanical construction
Dimensions in SI unitsCompact version
Order code for "Housing", option J "GT20 two-chamber, aluminum, coated, remote"; option K "GT18
two-chamber, 316L, remote"
A0033795
Wafer flange according to:
• EN 1092-1-B1 (DIN 2501): PN 10/16/25/40
• ASME B16.5: Class 150/300, Schedule 40
• JIS B2220: 10/20K, Schedule 40
1.4404/F316/F316L
Order code for "Process connection", option DDS/DES/D1S/D2S/AAS/ABS/NDS/NES
• Order code for "Housing" option J "GT20 two-chamber, aluminum, coated, remote"2.4 kg (5.2 lb):
• Order code for "Housing", option K "GT18 two-chamber, 316L, remote"6.0 kg (13.2 lb):
Sensor remote version
Weight data:
• Including sensor connection housing:
– Order code for "Housing" option J "GT20 two-chamber, aluminum, coated, remote"0.8 kg (1.8 lb):
– Order code for "Housing", option K "GT18 two-chamber, 316L, remote"2.0 kg (4.4 lb):
• Excluding the connecting cable
• Excluding packaging material
Weight in SI units
1)
DN
[mm]
"GT20 two-chamber, aluminum, coated, remote"
152.13.3
252.33.5
402.94.1
503.24.4
804.65.8
1005.66.8
1508.19.3
1)For high-temperature/low-temperature version: values + 0.2 kg
English, German, French, Spanish, Italian, Chinese, Japanese
• Uniform operating philosophy applied to device and operating tools
• If replacing the electronic module, transfer the device configuration via the integrated memory
(integrated HistoROM) which contains the process and measuring device data and the event
logbook. No need to reconfigure.
• Troubleshooting measures can be called up via the device and in the operating tools
• Diverse simulation options, logbook for events that occur and optional line recorder functions
Can be operated in the following languages:
• Via local display:
English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Swedish, Turkish,
Chinese, Japanese, Korean, Bahasa (Indonesian), Vietnamese, Czech
• Via "FieldCare" operating tool:
English, German, French, Spanish, Italian, Chinese, Japanese
Local operationVia display module
Two display modules are available:
Order code for "Display; Operation", option C "SD02"Order code for "Display; Operation", option E "SD03"
1Operation with pushbuttons1Operation with touch control
Display elements
• 4-line, illuminated, graphic display
• White background lighting; switches to red in event of device errors
• Format for displaying measured variables and status variables can be individually configured
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
A0032219 A0032221
Endress+Hauser63
Page 64
Proline Prowirl D 200
12
Operating elements
• Operation with 3 push buttons with open housing: , ,
or
• External operation via touch control (3 optical keys) without opening the housing: , ,
• Operating elements also accessible in the various zones of the hazardous area
Additional functionality
• Data backup function
The device configuration can be saved in the display module.
• Data comparison function
The device configuration saved in the display module can be compared to the current device
configuration.
• Data transfer function
The transmitter configuration can be transmitted to another device using the display module.
Via remote display FHX50
The remote display FHX50 can be ordered as an optional extra→ 72.
21FHX50 operating options
1SD02 display and operating module, push buttons: cover must be opened for operation
2SD03 display and operating module, optical buttons: operation possible through cover glass
Display and operating elements
The display and operating elements correspond to those of the display module .
Remote operationVia HART protocol
This communication interface is available in device versions with a HART output.
A0032215
64Endress+Hauser
Page 65
Proline Prowirl D 200
1457
9
68
3
2
3
1
76
5
4
A0028746
22Options for remote operation via HART protocol (passive)
1Control system (e.g. PLC)
2Transmitter power supply unit, e.g. RN221N (with communication resistor)
3Connection for Commubox FXA195 and Field Communicator 475
4Field Communicator 475
5Computer with web browser (e.g. Internet Explorer) for accessing computers with operating tool (e.g.
FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) with COM DTM "CDI Communication TCP/IP"
6Commubox FXA195 (USB)
7Field Xpert SFX350 or SFX370
8VIATOR Bluetooth modem with connecting cable
9Transmitter
Via PROFIBUS PA network
This communication interface is available in device versions with PROFIBUS PA.
A0028838
23Options for remote operation via PROFIBUS PA network
1Automation system
2Computer with PROFIBUS network card
3PROFIBUS DP network
4Segment coupler PROFIBUS DP/PA
5PROFIBUS PA network
6T-box
7Measuring device
Via FOUNDATION Fieldbus network
This communication interface is available in device versions with FOUNDATION Fieldbus.
Endress+Hauser65
Page 66
12
3
1
9898
4
66
5
24Options for remote operation via FOUNDATION Fieldbus network
12
+
E
–
1Automation system
2Computer with FOUNDATION Fieldbus network card
3Industry network
4High Speed Ethernet FF-HSE network
5Segment coupler FF-HSE/FF-H1
6FOUNDATION Fieldbus FF-H1 network
7Power supply FF-H1 network
8T-box
9Measuring device
Proline Prowirl D 200
A0028837
Service interfaceVia service interface (CDI)
1Service interface (CDI = Endress+Hauser Common Data Interface) of the measuring device
2Commubox FXA291
3Computer with FieldCare operating tool with COM DTM CDI Communication FXA291
A0034056
66Endress+Hauser
Page 67
Proline Prowirl D 200
Certificates and approvals
CE mark
C-Tick symbol
Ex approval
The measuring system is in conformity with the statutory requirements of the applicable EU
Directives. These are listed in the corresponding EU Declaration of Conformity along with the
standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
The measuring device is certified for use in hazardous areas and the relevant safety instructions are
provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on
the nameplate.
The separate Ex documentation (XA) containing all the relevant explosion protection data is
available from your Endress+Hauser sales center.
ATEX, IECEx
Currently, the following versions for use in hazardous areas are available:
Ex d
CategoryType of protection
II2G/Zone 1Ex d[ia] IIC T6 … T1
II1/2G/Zone 0/1Ex d[ia] IIC T6 … T1
Ex ia
Ex ic
Ex Ec
Ex tb
CategoryType of protection
II2G/Zone 1Ex ia IIC T6 … T1
II1G/Zone 0Ex ia IIC T6 … T1
II1/2G/Zone 0/1Ex ia IIC T6 … T1
CategoryType of protection
II3G/Zone 2Ex ic IIC T6 … T1
II1/3G/Zone 0/2Ex ic[ia] IIC T6 … T1
CategoryType of protection
II3G/Zone 2Ex ec IIC T6 ... T1
CategoryType of protection
II2D/Zone 21Ex tb IIIC Txxx
cCSAus
Currently, the following versions for use in hazardous areas are available:
Endress+Hauser67
Page 68
XP
CategoryType of protection
Class I, II, III, Division 1 for Group A-GXP (Ex d Flameproof version)
IS
CategoryType of protection
Class I, II, III, Division 1 for Group A-GIS (Ex i Intrinsically safe version)
NI
CategoryType of protection
Class I, Division 2 for Group ABCDNI (Non-incendive version), NIFW-Parameter*
*= Entity and NIFW parameters according to control drawings
NEPSI
Currently, the following versions for use in hazardous areas are available:
Proline Prowirl D 200
Ex d
Ex ia
Ex ic
Ex nA
CategoryType of protection
Zone 1Ex d[ia] IIC T1 ~ T6
Ex d[ia Ga] IIC T1 ~ T6
Zone 0/1Ex d[ia] IIC T1 ~ T6 DIP A21
Ex d[ia Ga] IIC T1 ~ T6 DIP A21
CategoryType of protection
Zone 1Ex ia IIC T1 ~ T6
Zone 0/1Ex ia IIC T1 ~ T6 DIP A21
CategoryType of protection
II3G/Zone 2Ex ic IIC T1 ~ T6
II1/3G/Zone 0/2Ex ic[ia Ga] IIC T1 ~ T6
CategoryType of protection
Zone 2Ex nA IIC T1 ~ T6
Ex nA[ia Ga] IIC T1 ~ T6
INMETRO
Currently, the following versions for use in hazardous areas are available:
Ex d
CategoryType of protection
–Ex d[ia] IIC T6 … T1
68Endress+Hauser
Page 69
Proline Prowirl D 200
Ex ia
CategoryType of protection
–Ex ia IIC T6 … T1
Ex nA
CategoryType of protection
II3G/Zone 2Ex nA IIC T6 … T1
EAC
Ex d
CategoryType of protection
Zone 11Ex d [ia Ga] IIC T6 ... T1 Gb
Ga/Gb Ex d [ia Ga] IIC T6 ... T1
Ex nA
Functional safety
The measuring device can be used for flow monitoring systems (min., max., range) up to SIL 2
(single-channel architecture; order code for "Additional approval", option LA) and SIL 3
(multichannel architecture with homogeneous redundancy) and is independently evaluated and
certified by the TÜV in accordance with IEC 61508.
The following types of monitoring in safety equipment are possible:
Volume flow
Functional Safety Manual with information on the SIL device → 76
HART certificationHART interface
The measuring device is certified and registered by the FieldComm Group. The measuring system
meets all the requirements of the following specifications:
• Certified according to HART
• The device can also be operated with certified devices of other manufacturers (interoperability)
FOUNDATION Fieldbus
certification
FOUNDATION Fieldbus interface
The measuring device is certified and registered by the FieldComm Group. The measuring system
meets all the requirements of the following specifications:
• Certified in accordance with FOUNDATION Fieldbus H1
• Interoperability Test Kit (ITK), revision version 6.2.0 (certificate available on request)
• Physical Layer Conformance Test
• The device can also be operated with certified devices of other manufacturers (interoperability)
CategoryType of protection
Zone 22Ex nA [ia Ga] IIC T6 ... T1 Gc
Certification PROFIBUSPROFIBUS interface
The measuring device is certified and registered by the PNO (PROFIBUS User Organization
Organization). The measuring system meets all the requirements of the following specifications:
• Certified in accordance with PROFIBUS PA Profile 3.02
• The device can also be operated with certified devices of other manufacturers (interoperability)
Pressure Equipment
Directive
The devices can be ordered with or without a PED approval. If a device with a PED approval is
required, this must be explicitly stated in the order.
Endress+Hauser69
Page 70
Proline Prowirl D 200
• With the identification PED/G1/x (x = category) on the sensor nameplate, Endress+Hauser
confirms conformity with the "Essential Safety Requirements" specified in Appendix I of the
Pressure Equipment Directive 2014/68/EC.
• Devices bearing this marking (PED) are suitable for the following types of medium:
Media in Group 1 and 2 with a vapor pressure greater than, or smaller and equal
to0.5 bar (7.3 psi)
• Devices not bearing this marking (PED) are designed and manufactured according to good
engineering practice. They meet the requirements of Art. 4, Par. 3 of the Pressure Equipment
Directive 2014/68/EU. The range of application is indicated in tables 6 to 9 in Annex II of the
Pressure Equipment Directive 2014/68/EC.
Experience
Other standards and
guidelines
The Prowirl 200 measuring system is the official successor to Prowirl 72 and Prowirl 73.
• EN 60529
Degrees of protection provided by enclosures (IP code)
• DIN ISO 13359
Measurement of conductive liquid flow in closed conduits - Flanged-type electromagnetic
flowmeters - Overall length
• EN 61010-1
Safety requirements for electrical equipment for measurement, control and laboratory use general requirements
• IEC/EN 61326
Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC
requirements).
• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment
• NAMUR NE 32
Data retention in the event of a power failure in field and control instruments with
microprocessors
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with
analog output signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics
• NAMUR NE 105
Specifications for integrating fieldbus devices in engineering tools for field devices
• NAMUR NE 107
Self-monitoring and diagnosis of field devices
• NAMUR NE 131
Requirements for field devices for standard applications
Ordering information
Detailed ordering information is available as follows:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field ->
Open product page -> The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center:www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
70Endress+Hauser
Page 71
Proline Prowirl D 200
Product generation index
Diagnostics functions
Release dateProduct rootOn change
01.09.20137D2BTI01083D
01.11.20177D2CTI01332D
More information is available from your Sales Center or at:
www.service.endress.com → Downloads
Application packages
Many different application packages are available to enhance the functionality of the device. Such
packages might be needed to address safety aspects or specific application requirements.
The application packages can be ordered with the device or subsequently from Endress+Hauser.
Detailed information on the order code in question is available from your local Endress+Hauser sales
center or on the product page of the Endress+Hauser website: www.endress.com.
Detailed information on the application packages:
Special Documentation for the device
PackageDescription
Extended HistoROMComprises extended functions concerning the event log and the activation of the
measured value memory.
Event log:
Memory volume is extended from 20 message entries (standard version) to up to
100 entries.
Data logging (line recorder):
• Memory capacity for up to 1000 measured values is activated.
• 250 measured values can be output via each of the 4 memory channels. The
recording interval can be defined and configured by the user.
• Measured value logs can be accessed via the local display or operating tool e.g.
FieldCare, DeviceCare or Web server.
Heartbeat Technology
PackageDescription
Heartbeat VerificationHeartbeat Verification
Meets the requirement for traceable verification to DIN ISO 9001:2008 Chapter
7.6 a) "Control of monitoring and measuring equipment".
• Functional testing in the installed state without interrupting the process.
• Traceable verification results on request, including a report.
• Simple testing process via local operation or other operating interfaces.
• Clear measuring point assessment (pass/fail) with high test coverage within the
framework of manufacturer specifications.
• Extension of calibration intervals according to operator's risk assessment.
Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are
available for the device. Detailed information on the order code in question is available from your
local Endress+Hauser sales center or on the product page of the Endress+Hauser website:
www.endress.com.
Endress+Hauser71
Page 72
Device-specific accessoriesFor the transmitter
AccessoriesDescription
Prowirl 200 transmitterTransmitter for replacement or storage. Use the order code to define the following
Remote display
FHX50
Overvoltage protection for
2-wire devices
Protective coverIs used to protect the measuring device from the effects of the weather: e.g.
Proline Prowirl D 200
specifications:
• Approvals
• Output, Input
• Display/operation
• Housing
• Software
Installation Instructions EA01056D
(Order number: 7X2CXX)
FHX50 housing for accommodating a display module .
• Length of connecting cable: up to max. 60 m (196 ft)
(cable lengths available for order: 5 m (16 ft), 10 m (32 ft), 20 m (65 ft),
30 m (98 ft))
The measuring device can be ordered with the FHX50 housing and a display
module. The following options must be selected in the separate order codes:
• Order code for measuring device, feature 030:
Option L or M "Prepared for FHX50 display"
• Order code for FHX50 housing, feature 050 (device version):
Option A "Prepared for FHX50 display"
• Order code for FHX50 housing, depends on the desired display module in feature
020 (display, operation):
– Option C: for an SD02 display module (push buttons)
– Option E: for an SD03 display module (touch control)
The FHX50 housing can also be ordered as a retrofit kit. The measuring device
display module is used in the FHX50 housing. The following options must be
selected in the order code for the FHX50 housing:
• Feature 050 (measuring device version): option B "Not prepared for FHX50
display"
Ideally, the overvoltage protection module should be ordered directly with the
device. See product structure, characteristic 610 "Accessory mounted", option NA
"Overvoltage protection". Separate order necessary only if retrofitting.
• OVP10: For 1-channel devices (characteristic 020, option A):
• OVP20: For 2-channel devices (characteristic 020, options B, C, E or G)
Special Documentation SD01090F
(Order number OVP10: 71128617)
(Order number OVP20: 71128619)
rainwater, excess heating from direct sunlight or extreme cold in winter.
Special Documentation SD00333F
(Order number: 71162242)
72Endress+Hauser
Page 73
Proline Prowirl D 200
AccessoriesDescription
Connecting cable for
remote version
Post mounting kitPost mounting kit for transmitter.
For the sensor
AccessoriesDescription
Mounting kitMounting set for disc (wafer version) comprising:
Flow conditionerIs used to shorten the necessary inlet run.
• Connecting cable available in various lengths:
– 5 m (16 ft)
– 10 m (32 ft)
– 20 m (65 ft)
– 30 m (98 ft)
• Reinforced cables available on request.
Standard length: 5 m (16 ft)
Is always supplied if no other cable length has been ordered.
The post mounting kit can only be ordered together with a transmitter.
(Order number: DK8WM-B)
• Tie rods
• Seals
• Nuts
• Washers
Installation Instructions EA00075D
(Order number: DK7D)
(Order number: DK7ST)
Communication-specific
accessories
AccessoriesDescription
Commubox FXA195
HART
Commubox FXA291Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
HART Loop Converter
HMX50
Wireless HART adapter
SWA70
Fieldgate FXA320Gateway for the remote monitoring of connected 4-20 mA measuring devices via a
Fieldgate FXA520Gateway for the remote diagnostics and remote configuration of connected HART
For intrinsically safe HART communication with FieldCare via the USB interface.
Technical Information TI00404F
Common Data Interface) and the USB port of a computer or laptop.
Technical Information TI405C/07
Is used to evaluate and convert dynamic HART process variables to analog current
signals or limit values.
• Technical Information TI00429F
• Operating Instructions BA00371F
Is used for the wireless connection of field devices.
The WirelessHART adapter can be easily integrated into field devices and existing
infrastructures, offers data protection and transmission safety and can be operated
in parallel with other wireless networks with minimum cabling complexity.
Operating Instructions BA00061S
Web browser.
Technical Information TI00025S
Operating Instructions BA00053S
measuring devices via a Web browser.
Technical Information TI00025S
Operating Instructions BA00051S
Endress+Hauser73
Page 74
Proline Prowirl D 200
Field Xpert SFX350Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices and can be used in non-hazardous areas.
Operating Instructions BA01202S
Field Xpert SFX370Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices and can be used in the non-hazardous area and in the hazardous
area.
Operating Instructions BA01202S
Service-specific accessories
AccessoriesDescription
ApplicatorSoftware for selecting and sizing Endress+Hauser measuring devices:
• Choice of measuring devices for industrial requirements
• Calculation of all the necessary data for identifying the optimum flowmeter: e.g.
nominal diameter, pressure loss, flow velocity and accuracy.
• Graphic illustration of the calculation results
• Determination of the partial order code, administration, documentation and
access to all project-related data and parameters over the entire life cycle of a
project.
Applicator is available:
• Via the Internet: https://portal.endress.com/webapp/applicator
• As a downloadable DVD for local PC installation.
W@MW@M Life Cycle Management
Improved productivity with information at your fingertips. Data relevant to a plant
and its components is generated from the first stages of planning and during the
asset’s complete life cycle.
W@M Life Cycle Management is an open and flexible information platform with
online and on-site tools. Instant access for your staff to current, in-depth data
shortens your plant’s engineering time, speeds up procurement processes and
increases plant uptime.
Combined with the right services, W@M Life Cycle Management boosts
productivity in every phase. For more information, visit
www.endress.com/lifecyclemanagement
FieldCareFDT-based plant asset management tool from Endress+Hauser.
It can configure all smart field units in your system and helps you manage them. By
using the status information, it is also a simple but effective way of checking their
status and condition.
Operating Instructions BA00027S and BA00059S
DeviceCareTool to connect and configure Endress+Hauser field devices.
Innovation brochure IN01047S
System components
AccessoriesDescription
Memograph M graphic
data manager
RN221NActive barrier with power supply for safe separation of 4-20 mA standard signal
RNS221Supply unit for powering two 2-wire measuring devices solely in the non-
The Memograph M graphic data manager provides information on all the relevant
measured variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on a SD card or USB stick.
• Technical Information TI00133R
• Operating Instructions BA00247R
circuits. Offers bidirectional HART transmission.
• Technical Information TI00073R
• Operating Instructions BA00202R
hazardous area. Bidirectional communication is possible via the HART
communication jacks.
• Technical Information TI00081R
• Brief Operating Instructions KA00110R
74Endress+Hauser
Page 75
Proline Prowirl D 200
Supplementary documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
2-D matrix code (QR code) on the nameplate.
Standard documentationBrief Operating Instructions
Brief Operating Instructions for the sensor
Measuring deviceDocumentation code
Prowirl D 200KA01322D
Brief Operating Instructions for transmitter
Measuring deviceDocumentation code
HARTFOUNDATION FieldbusPROFIBUS PA
Proline 200KA01326DKA01327DKA01328D
Supplementary devicedependent documentation
Operating Instructions
Measuring deviceDocumentation code
HARTFOUNDATION FieldbusPROFIBUS PA
Prowirl D 200BA01685DBA01693DBA01689D
Description of Device Parameters
Measuring deviceDocumentation code
HARTFOUNDATION FieldbusPROFIBUS PA
Prowirl 200GP01109DGP01111DGP01110D
Safety Instructions
ContentsDocumentation code
ATEX/IECEx Ex d, Ex tbXA01635D
ATEX/IECEx Ex ia, Ex tbXA01636D
ATEX/IECEx Ex ic, Ex ecXA01637D
CSAUS XPXA01638D
C
CSAUS ISXA01639D
C
NEPSI Ex dXA01643D
NEPSI Ex iXA01644D
NEPSI Ex ic, Ex nAXA01645D
INMETRO Ex dXA01642D
INMETRO Ex iXA01640D
INMETRO Ex nAXA01641D
EAC Ex dXA01684D
EAC Ex nAXA01685D
Endress+Hauser75
Page 76
Proline Prowirl D 200
Special documentation
ContentsDocumentation code
Information on the Pressure Equipment DirectiveSD01614D
Functional Safety ManualSD02025D
ContentsDocumentation code
HARTFOUNDATION FieldbusPROFIBUS PA
Heartbeat TechnologySD02029DSD02030DSD02031D
Installation Instructions
ContentsComment
Installation instructions for spare part sets and accessoriesDocumentation code: specified for each individual accessory → 72.
Registered trademarks
HART®
Registered trademark of the FieldComm Group, Austin, Texas, USA
PROFIBUS®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
FOUNDATION™ Fieldbus
Registration-pending trademark of the FieldComm Group, Austin, Texas, USA
KALREZ®, VITON®
Registered trademarks of DuPont Performance Elastomers L.L.C., Wilmington, DE USA
GYLON®
Registered trademark of Garlock Sealing Technologies, Palmyar, NY, USA
www.addresses.endress.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.