Endress+Hauser Proline Prowirl D 200 Specifications

TI01332D/06/EN/01.18 71386554
Products Solutions Services
Technical Information
Proline Prowirl D 200
Vortex flowmeter
Cost-effective wafer-flange measuring device, available in compact or remote version
Application
• Preferred measuring principle for wet/saturated/ superheated steam, gases & liquids (also cryogenic)
• For all basic applications and for 1-to-1 replacement of orifice plates
Device properties
• No flanges
• Low weight
• Display module with data transfer function
• Robust dual-compartment housing
• Plant safety: worldwide approvals (SIL, Haz. area)
Your benefits
• Integrated temperature measurement for mass/energy flow of saturated steam
• Easy alignment of the sensor – included centering rings
• High availability – proven robustness, resistance to vibrations, temperature shocks & water hammer
• Long-term stability – robust drift-free capacitive sensor
• Convenient device wiring – separate connection compartment
• Safe operation – no need to open the device due to display with touch control, background lighting
• Integrated verification – Heartbeat Technology

Table of contents

Proline Prowirl D 200
About this document ........................ 3
Symbols used ................................ 3
Function and system design ................... 4
Measuring principle ............................ 4
Measuring system ............................. 7
Input ..................................... 7
Measured variable ............................. 7
Measuring range .............................. 8
Operable flow range ........................... 12
Input signal ................................ 13
Output .................................. 13
Output signal ............................... 13
Signal on alarm .............................. 15
Load ..................................... 16
Ex connection data ........................... 17
Low flow cut off ............................. 22
Galvanic isolation ............................ 22
Protocol-specific data .......................... 22
Power supply ............................. 24
Terminal assignment .......................... 24
Pin assignment, device plug ...................... 26
Supply voltage .............................. 26
Power consumption ........................... 27
Current consumption .......................... 27
Power supply failure .......................... 28
Electrical connection .......................... 28
Potential equalization ......................... 32
Terminals ................................. 32
Cable entries ............................... 32
Cable specification ............................ 32
Overvoltage protection ......................... 33
Performance characteristics .................. 34
Reference operating conditions ................... 34
Maximum measured error ....................... 34
Repeatability ............................... 36
Response time .............................. 36
Influence of ambient temperature ................. 37
Installation ............................... 37
Mounting location ............................ 37
Orientation ................................ 37
Inlet and outlet runs .......................... 38
Mounting kit for disc (wafer version) ............... 40
Length of connecting cable ...................... 41
Mounting the transmitter housing ................. 41
Special mounting instructions .................... 42
Environment .............................. 43
Ambient temperature range ..................... 43
Storage temperature .......................... 43
Climate class ............................... 43
Degree of protection .......................... 43
Vibration resistance ........................... 44
Shock resistance ............................. 44
Impact resistance ............................ 44
Electromagnetic compatibility (EMC) ............... 44
Process .................................. 44
Medium temperature range ...................... 44
Pressure-temperature ratings .................... 45
Nominal pressure of sensor ...................... 46
Pressure loss ............................... 46
Thermal insulation ........................... 46
Mechanical construction .................... 47
Dimensions in SI units ......................... 47
Dimensions in US units ......................... 53
Weight ................................... 57
Materials .................................. 60
Operability ............................... 63
Operating concept ............................ 63
Languages ................................. 63
Local operation .............................. 63
Remote operation ............................ 64
Service interface ............................. 66
Certificates and approvals ................... 67
CE mark ................................... 67
C-Tick symbol ............................... 67
Ex approval ................................ 67
Functional safety ............................. 69
HART certification ............................ 69
FOUNDATION Fieldbus certification ................ 69
Certification PROFIBUS ......................... 69
Pressure Equipment Directive .................... 69
Experience ................................. 70
Other standards and guidelines ................... 70
Ordering information ....................... 70
Product generation index ....................... 71
Application packages ....................... 71
Diagnostics functions .......................... 71
Heartbeat Technology ......................... 71
Accessories ............................... 71
Device-specific accessories ...................... 72
Communication-specific accessories ................ 73
Service-specific accessories ...................... 74
System components ........................... 74
Supplementary documentation ............... 75
Standard documentation ........................ 75
Supplementary device-dependent documentation ....... 75
Registered trademarks ...................... 76
2 Endress+Hauser
Proline Prowirl D 200
A
1.

About this document

Symbols used Electrical symbols

Symbol Meaning
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Communication symbols
Symbol Meaning
Wireless Local Area Network (WLAN)
Communication via a wireless, local network.
Symbols for certain types of information
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Visual inspection.
Symbols in graphics
Symbol Meaning
1, 2, 3, ... Item numbers
, 2., 3., … Series of steps
A, B, C, ... Views
A-A, B-B, C-C, ... Sections
Endress+Hauser 3
Symbol Meaning
-
.
K-Factor =
Pulses
Unit Volume [m³]
Hazardous area
Safe area (non-hazardous area)
Flow direction

Function and system design

Proline Prowirl D 200

Measuring principle

Vortex meters work on the principle of the Karman vortex street. When fluid flows past a bluff body, vortices are alternately formed on both sides with opposite directions of rotation. These vortices each generate a local low pressure. The pressure fluctuations are recorded by the sensor and converted to electrical pulses. The vortices develop very regularly within the permitted application limits of the device. Therefore, the frequency of vortex shedding is proportional to the volume flow.
A0033465
 1 Sample graphic
The calibration factor (K-factor) is used as the proportional constant:
Within the application limits of the device, the K-factor only depends on the geometry of the device. It is for Re > 20 000:
• Independent of the flow velocity and the fluid properties viscosity and density
• Independent of the type of substance under measurement: steam, gas or liquid The primary measuring signal is linear to the flow. After production, the K-factor is determined in
the factory by means of calibration. It is not subject to long-time drift or zero-point drift.
The device does not contain any moving parts and does not require any maintenance.
The capacitance sensor
The sensor of a vortex flowmeter has a major influence on the performance, robustness and reliability of the entire measuring system.
4 Endress+Hauser
A0003939-EN
Proline Prowirl D 200
1 2
The robust DSC sensor is:
• burst-tested
• tested against vibrations
• tested against thermal shock (thermal shocks of 150 K/s) The measuring device uses the tried-and-tested, capacitance measuring technology from
Endress+Hauser, which is already in use in over 450 000 measuring points worldwide. Thanks to its design, the capacitance sensor is also particularly mechanically resistant to temperature shocks and pressure shocks in steam pipelines.
Temperature measurement
The "mass" option is available under the order code for "Sensor version". With this option the measuring device can also measure the temperature of the medium.
The temperature is measured via Pt 1000 temperature sensors. These are located in the paddle of the DSC sensor and are therefore in the direct vicinity of the fluid.
Order code for "Sensor version; DSC sensor; measuring tube":
• Option AA "volume; 316L; 316L"
• Option BA "volume high-temperature; 316L; 316L"
• Option CA "Mass; 316L; 316L (integrated temperature measurement)"
A0034068
1 Order code for "Sensor version", option "volume" or "volume high-temperature" 2 Order code for "Sensor version", option "mass"
Lifelong calibration
Experience has shown that recalibrated measuring devices demonstrate a very high degree of stability compared to their original calibration: The recalibration values were all within the original measuring accuracy specifications of the devices. This applies to the measured volume flow, the device's primary measured variable.
Various tests and simulation have shown that once the radii of the edges on the bluff body are less than 1 mm (0.04 in), the resulting effect does not have a negative impact on accuracy.
If the radii of the edges on the bluff body do not exceed 1 mm (0.04 in), the following general statements apply (in the case of non-abrasive and non-corrosive media, such as in most water and steam applications):
• The measuring device does not display an offset in the calibration and the accuracy is still guaranteed.
• All the edges on the bluff body have a radius that is typically smaller in size. As the measuring devices are naturally also calibrated with these radii, the measuring device remains within the specified accuracy rating provided that the additional radius that is produced as a result of wear and tear does not exceed 1 mm (0.04 in).
Consequently, it can be said that the product line offers lifelong calibration if the measuring device is used in non-abrasive and non-corrosive media.
Air and industrial gases
The measuring device enables users to calculate the density and energy of air and industrial gases. The calculations are based on time-tested standard calculation methods. It is possible to automatically compensate for the effect of pressure and temperature via an external or constant value.
Endress+Hauser 5
Proline Prowirl D 200
This makes it possible to output the energy flow, standard volume flow and mass flow of the following gases:
• Single gas
• Gas mixture
• Air
• User-specific gas For detailed information on the parameters, see the Operating Instructions.→  75
Natural gas
The device enables users to calculate the chemical properties (gross calorific value, net calorific value) of natural gases. The calculations are based on time-tested standard calculation methods. It is possible to automatically compensate for the effect of pressure and temperature via an external or constant value.
This makes it possible to output the energy flow, standard volume flow and mass flow in accordance with the following standard methods:
Energy can be calculated based on the following standards:
• AGA5
• ISO 6976
• GPA 2172
Density can be calculated based on the following standards:
• ISO 12213-2 (AGA8-DC92)
• ISO 12213-3
• AGA NX19
• AGA8 Gross 1
• SGERG 88 For detailed information on the parameters, see the Operating Instructions.→  75
6 Endress+Hauser
Proline Prowirl D 200

Measuring system

The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version – transmitter and sensor form a mechanical unit.
• Remote version - transmitter and sensor are mounted in separate locations.
Transmitter
Prowirl 200 Device versions and materials:
• Compact or remote version, aluminum coated: Aluminum, AlSi10Mg, coated
• Compact or remote version, stainless: For maximum corrosion resistance: stainless steel, CF3M
Configuration:
• Via four-line local display with key operation or via four-line, illuminated local display with touch control and guided menus ("Make-
A0013471
it-run" wizards) for applications
• Via operating tools (e.g. FieldCare)
Sensor
Prowirl D Disc (wafer version):
• Nominal diameter range: DN 15 to 150 (½ to 6")
• Materials: Measuring tubes: stainless steel, CF3M/1.4408

Input

Measured variable Direct measured variables

Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
AA Volume; 316L; 316L Volume flow
BA Volume high-temperature; 316L; 316L
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
CA Mass; 316L; 316L (integrated temperature measurement) • Volume flow
A0009922
• Temperature
Endress+Hauser 7
Proline Prowirl D 200
Calculated measured variables
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
AA Volume; 316L; 316L Under constant process conditions:
BA Volume high-temperature; 316L; 316L
1) A fixed density must be entered for calculating the mass flow (Setup menu → Advanced setup submenu →
External compensation submenu → Fixed density parameter).
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
CA Mass; 316L; 316L (integrated temperature measurement) • Corrected volume flow
• Mass flow
• Corrected volume flow
The totalized values for:
• Volume flow
• Mass flow
• Corrected volume flow
1)
• Mass flow
• Calculated saturated steam pressure
• Energy flow
• Heat flow difference
• Specific volume
• Degrees of superheat

Measuring range

The measuring range is dependent on the nominal diameter, the fluid and environmental influences.
The following specified values are the largest possible flow measuring ranges (Q
min
to Q
max
) for each nominal diameter. Depending on the fluid properties and environmental influences, the measuring range may be subject to additional restrictions. Additional restrictions apply to both the lower range value and the upper range value.
Flow measuring ranges in SI units
DN [mm]
15 0.06 to 4.9 0.3 to 25
25 0.18 to 15 0.9 to 130
40 0.45 to 37 2.3 to 310
50 0.75 to 62 3.8 to 820
80 1.7 to 140 8.5 to 1 800
100 2.9 to 240 15 to 3 200
150 6.7 to 540 33 to 7 300
Liquids [m³/h]
Gas/steam [m³/h]
Flow measuring ranges in US units
DN Liquids Gas/steam
[in] [ft³/min] [ft³/min]
½ 0.035 to 2.9 0.18 to 15
1 0.11 to 8.8 0.54 to 74
0.27 to 22 1.3 to 180
2 0.44 to 36 2.2 to 480
3 1 to 81 5 to 1 100
4 1.7 to 140 8.7 to 1 900
6 3.9 to 320 20 to 4 300
8 Endress+Hauser
Proline Prowirl D 200
D
i
v,Q
v [m/s] =
4 · Q [m /h]³
π · D [m]
·
1
3600 [s/h]
v [!/s] =
4 · Q [ /min]ft³
π · D [ft]
·
1
60 [s/min]
Re
=
4 · Q [m³/s] · [kg/m³]ρ
· D [m] · µ [Pa · s]π
i
Re
=
4 · Q [ft³/s] · [lbm/ft³]ρ
· D [ft] · µ [lbf · s/ft ]π
i
²
Flow velocity
A0033469
DiInternal diameter of measuring tube (corresponds to dimension K→  47) v Velocity in mating pipe
Q Flow
The internal diameter of measuring tube Di is denoted in the dimensions as dimension K.→  47.
Calculation of flow velocity:
A0034301
Lower range value
A restriction applies to the lower range value due to the turbulent flow profile, which increases only in the case of Reynolds 5 000numbers. The Reynolds number is dimensionless and indicates the ratio of the inertia force of a fluid to its viscous force when flowing and is used as a characteristic variable for pipe flows. In the case of pipe flows with Reynolds numbers less than 5 000, periodic vortices are no longer generated and flow rate measurement is no longer possible.
The Reynolds number is calculated as follows:
A0034291
Re Reynolds number
Q Flow
D
µ Dynamic viscosity
ρ Density
Internal diameter of measuring tube (corresponds to dimension K→  47)
i
The Reynolds number, 5 000 together with the density and viscosity of the fluid and the nominal diameter, is used to calculate the corresponding flow rate.
Endress+Hauser 9
Proline Prowirl D 200
Q [m /h] =
Re = 5000
³
5000 [Pa· · D [m] · · s]
i
π μ
· 3600 [s/h]
4 [kg/m ]· ³ρ
Q [ /h] =
Re = 5000
5000 [lbf· · D [ft] · · s/ft ]i²π μ
· 60 [s/min]
4 [lbm/ ]· ρ
v [m/s] = max
AmpMin
mf [m/s]
50 [m] · a [m/s ]²
v [!/s] = max
AmpMin
mf [!/s]
164 [!] · a [ft/s ]²
Q [m /h] =
AmpMin
³
v [m/s]
AmpMin
· · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³ 1 [kg/m ]³
Q [ /min] =
AmpMin
v [!/s]
AmpMin
· · D [ft]i²π
· 60 [s/min]
4 ·
ρ [lbm/ ]
0.0624 [lbm/ ]
A0034302
Q
Re = 5000
D
i
Flow rate is dependent on the Reynolds number
Internal diameter of measuring tube (corresponds to dimension K→  47)
µ Dynamic viscosity
ρ Density
The measuring signal must have a certain minimum signal amplitude so that the signals can be evaluated without any errors. Using the nominal diameter, the corresponding flow can also be derived from this amplitude. The minimum signal amplitude depends on the setting for the sensitivity of the DSC sensor (s), the steam quality (x) and the force of the vibrations present (a). The value mf corresponds to the lowest measurable flow velocity without vibration (no wet steam) at a density of 1 kg/m3 (0.0624 lbm/ft^3). The value mf can be set in the range from 6 to 20 m/s (1.8 to 6 ft/s) (factory setting 12 m/s (3.7 ft/s)) with the Sensitivity parameter (value range 1 to 9, factory setting 5).
v
AmpMin
Minimum measurable flow velocity based on signal amplitude
mf Sensitivity
x Steam quality
a Vibration
10 Endress+Hauser
A0034303
A0034304
Proline Prowirl D 200
Q [m /h] = max
Low
³
Q [m /h]
min
³
Q [m /h]
Re = 5000
³
Q [m /h]
AmpMin
³
Q [! /min] = max
Low
³
Q [ /min]
min
Q [ /min]
Re = 5000
Q [ /min]
AmpMin
Q [m /h] =
AmpMax
³
350[m/s] · · D [m]i²π
· 3600 [s/h]
4 ·
ρ [kg/m ]³ 1 [kg/m ]³
Q [ /min] =
AmpMax
1148[!/s] · · D [ft]π
· 60 [s/min]
4 ·
ρ [lbm/ ]
0.0624 [lbm/ ]
Q
v
AmpMin
D
Minimum measurable flow rate based on signal amplitude
AmpMin
Minimum measurable flow velocity based on signal amplitude
Internal diameter of measuring tube (corresponds to dimension K→  47)
i
ρ Density
The effective lower range value Q
5000
Q
Q
Q
Q
and Q
Low
min
Re = 5000
AmpMin
.
AmpMin
Effective lower range value
Minimum measurable flow rate
Flow rate is dependent on the Reynolds number
Minimum measurable flow rate based on signal amplitude
is determined using the largest of the three values Q
Low
min
, Q
Re =
A0034313
The Applicator is available for calculation purposes.
Upper range value
The measuring signal amplitude must be below a certain limit value to ensure that the signals can be evaluated without error. This results in a maximum permitted flow rate Q
Q
D
ρ Density
Maximum measurable flow rate based on signal amplitude
AmpMax
Internal diameter of measuring tube (corresponds to dimension K→  47)
i
AmpMax
:
A0034316
Endress+Hauser 11
For gas applications, an additional restriction applies to the upper range value with regard to the Mach number in the measuring device, which must be less than 0.3. The Mach number Ma describes the ratio of the flow velocity v to the sound velocity c in the fluid.
Ma =
v [m/s] c [m/s]
Ma =
v [!/s] c [!/s]
Ma Mach number
Q [m /h] =
Ma = 0.3
³
0.3 · c [m/s] · · D [m]i²
π
4
· 3600 [s/h]
Q [ /min] =
Ma = 0.3
0.3 · c [ft/s] · · D [ft]i²
π
4
· 60 [s/min]
Q [m /h] = min
High
³
Q [m /h]
max
³
Q [m /h]
AmpMax
³
Q [m /h]
Ma = 0.3
³
Q [! /min] = min
High
³
Q [ /min]
max
Q [ /min]
AmpMax
Q [ /min]
Ma = 0.3
v
Flow velocity
c Sound velocity
The corresponding flow rate can be derived using the nominal diameter.
Proline Prowirl D 200
A0034321
Q
Ma = 0.3
Restricted upper range value is dependent on Mach number
c Sound velocity
D
i
Internal diameter of measuring tube (corresponds to dimension K→  47)
ρ Density
The effective upper range value Q Q
AmpMax
Q
High
Q
max
Q
AmpMax
Q
Ma = 0.3
and Q
Ma=0.3
.
Effective upper range value
Maximum measurable flow rate
Maximum measurable flow rate based on signal amplitude
Restricted upper range value is dependent on Mach number
is determined using the smallest of the three values Q
High
max
A0034337
,
A0034338
For liquids, the occurrence of cavitation may also restrict the upper range value.
The Applicator is available for calculation purposes.

Operable flow range

12 Endress+Hauser
The value, which is typically up to 49: 1, may vary depending on the operating conditions (ratio between upper range value and lower range value)
Proline Prowirl D 200

Input signal Current input

Current input 4-20 mA (passive)
Resolution 1 µA
Voltage drop Typically: 2.2 to 3 V for 3.6 to 22 mA
Maximum voltage ≤ 35 V
Possible input variables • Pressure
External measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the automation system can continuously write different measured values to the measuring device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
• Various pressure measuring devices can be ordered as accessories from Endress+Hauser.
• If using pressure measuring devices, pay attention to outlet runs when installing external devices→  40.
If the device does not have temperature compensation, it is recommended that external pressure measurement values be read in so that the following measured variables can be calculated:
• Energy flow
• Mass flow
• Corrected volume flow
• Temperature
• Density
Current input
The measured values are written from the automation system to the measuring device via the current input →  13.
HART protocol
The measured values are written from the automation system to the measuring device via the HART protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS PA

Output

Output signal Current output

Current output 1 4-20 mA HART (passive)
Current output 2 4-20 mA (passive)
Resolution < 1 µA
Endress+Hauser 13
Damping Adjustable: 0.0 to 999.9 s
Assignable measured variables
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
Pulse/frequency/switch output
Function Can be set to pulse, frequency or switch output
Version Passive, open collector
Maximum input values • DC 35 V
• 50 mA
For information on the Ex connection values →  17
Proline Prowirl D 200
Voltage drop • For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current ≤ 0.05 mA
Pulse output
Pulse width Adjustable: 5 to 2 000 ms
Maximum pulse rate 100 Impulse/s
Pulse value Adjustable
Assignable measured variables
Frequency output
Output frequency Adjustable: 0 to 1 000 Hz
Damping Adjustable: 0 to 999 s
Pulse/pause ratio 1:1
Assignable measured variables
Switch output
Switching behavior Binary, conductive or non-conductive
Switching delay Adjustable: 0 to 100 s
• Mass flow
• Volume flow
• Corrected volume flow
• Total mass flow
• Energy flow
• Heat flow difference
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
• Pressure
14 Endress+Hauser
Proline Prowirl D 200
Number of switching cycles
Assignable functions • Off
Unlimited
• On
• Diagnostic behavior
• Limit value – Volume flow – Corrected volume flow – Mass flow – Flow velocity – Temperature – Calculated saturated steam pressure – Total mass flow – Energy flow – Heat flow difference – Pressure – Reynolds number – Totalizer 1-3
• Status
• Status of low flow cut off
FOUNDATION Fieldbus
FOUNDATION Fieldbus H1, IEC 61158-2, galvanically isolated
Data transfer 31.25 kbit/s
Current consumption 15 mA
Permitted supply voltage 9 to 32 V
Bus connection With integrated reverse polarity protection

Signal on alarm

PROFIBUS PA
PROFIBUS PA In accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically
isolated
Data transfer 31.25 kbit/s
Current consumption 10 mA
Permitted supply voltage 9 to 32 V
Bus connection With integrated reverse polarity protection
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure mode Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Pulse/frequency/switch output
Pulse output
Failure mode No pulses
Endress+Hauser 15
Frequency output
Failure mode Choose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1 250 Hz
Switch output
Failure mode Choose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Proline Prowirl D 200
Status and alarm messages
Error current FDE (Fault Disconnection Electronic)
Diagnostics in accordance with FF-891
0 mA
PROFIBUS PA
Status and alarm messages
Error current FDE (Fault Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
Local display
Plain text display With information on cause and remedial measures
Backlight Additionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication: – HART protocol – FOUNDATION Fieldbus – PROFIBUS PA
• Via service interface CDI service interface
Plain text display With information on cause and remedial measures
Additional information on remote operation →  64

Load

Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including line resistance must be observed to ensure adequate terminal voltage at the device. In doing so, observe the minimum terminal voltage
16 Endress+Hauser
Proline Prowirl D 200
0
100
200
300
400
500
12 14 16
18 20
22 24 26 28
U [V]
s
R [W]
b
1.1 1.21
30 32 34 36
• RB ≤ (US - U
term. min
): 0.022 A
• RB ≤ 500 Ω
 2 Load for a compact version without local operation
1 Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch output" with Ex i and option C "4-20 mA HART + 4-20 mA analog"
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch output" for non-hazardous area and Ex d
Sample calculation
Supply voltage of power supply unit: – US = 19 V – U
= 12 V (measuring device) + 1 V (local operation without lighting) = 13 V
term. min
Maximum load: RB ≤ (19 V - 13 V): 0.022 A = 273 Ω
The minimum terminal voltage (U
) increases if local operation is used..
Kl min
A0033472

Ex connection data Safety-related values

Type of protection Ex d
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
Option C 4-20mA HART
Option D 4-20mA HART U
Option E FOUNDATION Fieldbus U
Pulse/frequency/switch output U
4-20mA analog
Pulse/frequency/switch output U
4 to 20 mA current input U
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
= DC 35 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 30 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 35 V = 250 V
= DC 32 V = 250 V
= 0.88 W
Endress+Hauser 17
Proline Prowirl D 200
Order code for "Output" Output type Safety-related values
Pulse/frequency/switch output U
Option G PROFIBUS PA U
Pulse/frequency/switch output U
1) Internal circuit limited by Ri = 760.5 Ω
Type of protection Ex ec
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
Pulse/frequency/switch output U
Option C 4-20mA HART
4-20mA analog
Option D 4-20mA HART U
Pulse/frequency/switch output U
4 to 20 mA current input U
Option E FOUNDATION Fieldbus U
Pulse/frequency/switch output U
Option G PROFIBUS PA U
Pulse/frequency/switch output U
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
= DC 35 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 30 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 35 V = 250 V
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
1) Internal circuit limited by Ri = 760.5 Ω
Type of protection XP
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
nom
U
max
nom
U
max
= DC 35 V = 250 V
= DC 35 V = 250 V
18 Endress+Hauser
Proline Prowirl D 200
Order code for "Output" Output type Safety-related values
Pulse/frequency/switch output U
Option C 4-20mA HART
4-20mA analog
Option D 4-20mA HART U
Pulse/frequency/switch output U
4 to 20 mA current input U
Option E FOUNDATION Fieldbus U
Pulse/frequency/switch output U
Option G PROFIBUS PA U
Pulse/frequency/switch output U
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V = 250 V
1)
= 1 W
= DC 30 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 35 V = 250 V
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
1) Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
Type of protection Ex ia
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
Option C 4-20mA HART Ui = DC 30 V
4-20mA analog
Option D 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 30 nF
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Endress+Hauser 19
Proline Prowirl D 200
Order code for "Output" Output type Intrinsically safe values
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
4 to 20 mA current input Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Option G PROFIBUS PA STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
Type of protection Ex ic
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 6 nF
Option C 4-20mA HART Ui = DC 30 V
4-20mA analog
Option D 4-20mA HART Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 30 nF
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
20 Endress+Hauser
Proline Prowirl D 200
Order code for "Output" Output type Intrinsically safe values
Pulse/frequency/switch output Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 6 nF
4 to 20 mA current input Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 32 V li = 300 mA Pi = n.a. Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 35 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Option G PROFIBUS PA STANDARD
Ui = 32 V li = 300 mA Pi = n.a. Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 35 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = n.a. Pi = n.a. Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = n.a. Pi = n.a. Li = 10 µH Ci = 5 nF
Type of protection IS
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
Option C 4-20mA HART Ui = DC 30 V
4-20mA analog
Option D 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 30 nF
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Endress+Hauser 21
Proline Prowirl D 200
Order code for "Output" Output type Intrinsically safe values
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
4 to 20 mA current input Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Option G PROFIBUS PA STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF

Low flow cut off

Galvanic isolation

The switch points for low flow cut off are preset and can be configured.
All inputs and outputs are galvanically isolated from one another.

Protocol-specific data HART

Manufacturer ID 0x11
Device type ID 0x0038
HART protocol revision 7
Device description files (DTM, DD)
HART load • Min. 250 Ω
System integration For information on system integration, see Operating Instructions.→  75
FOUNDATION Fieldbus
Manufacturer ID 0x452B48
Ident number 0x1038
Device revision 2
Information and files under:
www.endress.com
• Max. 500 Ω
• Measured variables via HART protocol
• Burst Mode functionality
22 Endress+Hauser
Proline Prowirl D 200
DD revision Information and files under:
CFF revision
Device Tester Version (ITK version)
ITK Test Campaign Number Information:
Link Master capability (LAS) Yes
Choice of "Link Master" and "Basic Device"
Node address Factory setting: 247 (0xF7)
Supported functions The following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs 44
Number of link objects in VFD 50
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Device Link Capabilities
Slot time 4
Min. delay between PDU 8
Max. response delay Min. 5
System integration For information on system integration, see Operating Instructions.→  75
www.endress.com
www.fieldbus.org
6.2.0
www.endress.com
www.fieldbus.org
Yes Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
• Read events
• Read trend data
• Cyclic data transmission
• Description of the modules
• Execution times
• Methods
PROFIBUS PA
Manufacturer ID 0x11
Ident number 0x1564
Profile version 3.02
Device description files (GSD, DTM, DD)
Information and files under:
www.endress.com
www.profibus.org
Endress+Hauser 23
Loading...
+ 53 hidden pages