Direct current and alternating currentGround connection
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
Symbols for certain types of information
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Equipotential connection
A connection that has to be connected
to the plant grounding system: This
may be a potential equalization line
or a star grounding system depending
on national or company codes of
practice.
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
SymbolMeaningSymbolMeaning
1, 2, 3,...Item numbers
A, B, C, ...ViewsA-A, B-B, C-C, ... Sections
Hazardous area
Series of steps
Safe area (non-hazardous area)
Flow direction
Function and system design
Measuring principle
Endress+Hauser3
Vortex meters work on the principle of the Karman vortex street. When fluid flows past a bluff body,
vortices are alternately formed on both sides with opposite directions of rotation. These vortices each
generate a local low pressure. The pressure fluctuations are recorded by the sensor and converted to
Page 4
Proline Prowirl C 200
K-Factor =
Pulses
Unit Volume [m³]
electrical pulses. The vortices develop very regularly within the permitted application limits of the
device. Therefore, the frequency of vortex shedding is proportional to the volume flow.
The calibration factor (K-factor) is used as the proportional constant:
A0019373
A0003939-EN
Within the application limits of the device, the K-factor only depends on the geometry of the device.
For Re > 20000 it is:
• Independent of the flow velocity and the fluid properties viscosity and density
• Independent of the type of substance under measurement: steam, gas or liquid
The primary measuring signal is linear to the flow. After production, the K-factor is determined in
the factory by means of calibration. It is not subject to long-time drift or zero-point drift.
The device does not contain any moving parts and does not require any maintenance.
The capacitance sensor
The sensor of a vortex flowmeter has a major influence on the performance, robustness and
reliability of the entire measuring system.
The robust DSC sensor is:
• burst-tested
• tested against vibrations
• tested against thermal shock (thermal shocks of 150 K/s)
The Prowirl uses the tried-and-tested capacitance measuring technology of Endress+Hauser applied
in over 300000 measuring points worldwide.
The DSC (differential switched capacitance) sensor patented by Endress+Hauser has complete
mechanical balancing. It only reacts to the measured variable (vortex) and does not react to
vibrations. Even in the event of pipe vibrations, the smallest of flows can be reliably measured at low
density thanks to the unimpaired sensitivity of the sensor. Thus, the wide turndown is also
maintained even in the event of harsh operating conditions. Vibrations up to 1 g at least, at
frequencies up to 500 Hz in every axis (X, Y, Z), do not affect the flow measurement. Thanks to its
design, the capacitance sensor is also particularly mechanically resistant to temperature shocks and
pressure shocks in steam pipelines.
Temperature measurement
Under the "Sensor version" order code the "Mass flow" option is available(→ 4). With this option
the measuring device can also measure the temperature of the medium.
The temperature is measured via Pt 1000 temperature sensors. These sensors are located in the
paddle of the DSC sensor and are therefore in the direct vicinity of the fluid.
Experience has shown that recalibrated Prowirl devices demonstrate a very high degree of stability
compared to their original calibration: The recalibration values were all within the original
measuring accuracy specifications of the devices.
Various tests and simulation procedures carried out on devices by filing away the edges of Prowirl’s
bluff body found that there was no negative impact on the accuracy up to a rounding diameter of
1 mm (0.04 in).
If the meter’s edges do not show rounding at the edges that exceeds 1 mm (0.04 in), the following
general statements apply (for non-abrasive and non-corrosive media, such as in most water and
steam applications):
• The measuring device does not display an offset in the calibration and the accuracy is still
guaranteed.
• All the edges on the bluff body have a radius that is typically smaller in size. As the measuring
devices are naturally also calibrated with these radii, the measuring device remains within the
specified accuracy rating provided that the additional radius that is produced as a result of wear
and tear does not exceed 1 mm (0.04 in).
Consequently it can be said that the Prowirl product line offers lifelong calibration if the measuring
device is used in non-abrasive and non-corrosive media.
Diagnostic functions
In addition, the device offers extensive diagnostic options, such as tracking fluid and ambient
temperatures, extreme flows etc.
The following minimum and maximum values are tracked in the measuring device and saved for
diagnostic purposes:
• Frequency
• Temperature
• Velocity
• Pressure
Inspection concept
According to the requirements of the ERCB (Canada), in certain applications the owner-operator of a
plant is required to maintain a servicing interval of 12 months.
The condition of the primary measurement element must be checked during these servicing
activities. The aim is to be able to ensure a repeatable measurement. Maintenance can be either by
way of visual inspection or in line with the recommendations of the equipment manufacturer.
Endress+Hauser5
Page 6
Proline Prowirl C 200
With its unique inspection concept for Prowirl C 200 Endress+Hauser has developed a solution that
makes it possible to:
• meet these requirements
• perform maintenance on the installed device
• perform a visual inspection
• deliver an opinion about the measurement quality by measuring the edges of the bluff body.
This inspection concept is available via the order code "Sensor option", option CR "ERCB Dir. 017
inspection ports".
Detailed information on the inspection kit (→ 37)
For detailed information on the inspection ports, see the Special Documentation for the device
(→ 67)
6Endress+Hauser
Page 7
Proline Prowirl C 200
Measuring system
The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version - the transmitter and sensor form a mechanical unit.
• Remote version – the transmitter and sensor are mounted separately from one another.
Transmitter
Prowirl 200Device versions and materials:
Compact or remote version, aluminum coated:
Aluminum, AlSi10Mg, coated
Configuration:
• Via four-line local display with key operation or via four-line,
illuminated local display with touch control and guided menus ("Make-
A0013471
it-run" wizards) for applications
• Via operating tools (e.g. FieldCare)
Sensor
Prowirl CCarbon steel flanged version for use with process pressures, Class 600/
– Process connections: carbon steel, multiple certifications, SA-105,
A0020335
SA-350 LF2 (1)
• Order code for "Sensor option":
ERCB Dir. 017, version with inspection ports
• Also available as butt-weld version
Input
Measured variableDirect measured variables
Order code for "Sensor version":
Option 4 "Volume flow, Alloy 718":
Volume flow
Order code for "Sensor version":
Option 6 "Mass flow, Alloy 718":
– Volume flow
– Temperature
Calculated measured variables
Order code for "Sensor version":
Option 4 "Volume flow, Alloy 718":
– In the case of constant process conditions: Mass flow
– The totalized values for Volume flow, Mass flow, or Corrected volume flow
Order code for "Sensor version":
Option 6 "Mass flow, Alloy 718":
– Corrected volume flow
– Mass flow
– Calculated saturated steam pressure
– Energy flow
– Heat flow difference
– Specific volume
– Degrees of superheat
1)
or Corrected volume flow
1)A fixed density must be entered for calculating the mass flow (Setup menu → Advanced setup submenu → External compensation submenu →
Fixed density parameter).
Endress+Hauser7
Page 8
Proline Prowirl C 200
Re
=
4 · Q·m³[m³/s][kg/]ρ
di [m] · µπ π ·[Pa·s]
Re
=
4 · Q·³[ft³/s][lb/ft ]ρ
di [ft] · µπ ·[0.001 cP]
v
DN 2...6" →
=
min.
4.92
ρ [lb/ft³]
[ft/s]
v
DN 50...150 →=
min.
6
ρ [kg/m³]
[m/s]
Measuring range
The measuring range depends on the fluid and nominal diameter.
Lower range value
Depends on the density and the Reynolds number (Re
= 5000, Re
min
= 20000). The Reynolds
linear
number is dimensionless and indicates the ratio of the inertia force of a fluid to its viscous force. It is
used to characterize the flow. The Reynolds number is calculated as follows:
A0003794
Re = Reynolds number; Q = flow; di = internal diameter; µ = dynamic viscosity, ρ = density
A0020558
Upper range value
Liquids:
The upper range value must be calculated as follows:
v
= 9 m/s (30 ft/s) and v
max
Use the lower value.
‣
= 350/√ρ m/s (130/√ρ ft/s)
max
Gas/steam:
Nominal diameterv
Standard device: DN 50 to 150 (2 to 6")120 m/s (394 ft/s) and 350/√ρ m/s (130/√ρ ft/s)
max
(Use the lower value.)
Calibrated range: up to 75 m/s (246 ft/s)
For information about the Applicator (→ 65)
Operable flow range
Up to 45: 1 (ratio between lower and upper range value)
Input signalExternal measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure
measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
• Various pressure transmitters can be ordered from Endress+Hauser: see "Accessories" section
(→ 66)
• Please comply with the special mounting instructions when using pressure transmitters
(→ 37)
It is recommended to read in external measured values to calculate the following measured variables:
• Energy flow
• Mass flow
• Corrected volume flow
8Endress+Hauser
Page 9
Proline Prowirl C 200
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Current input
The measured values are written from the automation system to the measuring device via the
current input.
Fieldbuses
The measured values can be written from the automation system to the measuring via:
• PROFIBUS PA
• FOUNDATION Fieldbus
Current input
Current input4 to 20 mA (passive)
Resolution1 µA
Voltage dropTypically: 2.2 to 3 V for 3.6 to 22 mA
Maximum voltage≤ 35 V
Possible input variables• Pressure
• Temperature
• Density
Output
Output signalCurrent output
Current output 14-20 mA HART (passive)
Current output 24-20 mA (passive)
Resolution<1 µA
DampingAdjustable: 0.0 to 999.9 s
Assignable measured
variables
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionPassive, open collector
Maximum input values• DC 35 V
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
• 50 mA
For information on the Ex connection values (→ 12)
Voltage drop• For ≤2 mA: 2 V
• For 10 mA: 8 V
Endress+Hauser9
Page 10
Residual current≤0.05 mA
Pulse output
Pulse widthAdjustable: 5 to 2000 ms
Maximum pulse rate100 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Output frequencyAdjustable: 0 to 1000 Hz
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
Switch output
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
Number of switching
cycles
Assignable functions• Off
• Total volume flow
• Total corrected volume flow
• Total mass flow
• Total energy flow
• Total heat flow difference
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Unlimited
• On
• Diagnostic behavior
• Limit value
– Volume flow
– Corrected volume flow
– Mass flow
– Flow velocity
– Temperature
– Calculated saturated steam pressure
– Steam quality
– Total mass flow
– Energy flow
– Heat flow difference
– Reynolds number
– Totalizer 1-3
• Status
• Status of low flow cut off
Proline Prowirl C 200
FOUNDATION Fieldbus
Signal encodingManchester Bus Powered (MBP)
Data transfer31.25 KBit/s, Voltage mode
10Endress+Hauser
Page 11
Proline Prowirl C 200
PROFIBUS PA
Signal encodingManchester Bus Powered (MBP)
Data transfer31.25 KBit/s, Voltage mode
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
HART
Device diagnosticsDevice condition can be read out via HART Command 48
Pulse/frequency/switch output
Pulse output
Failure modeNo pulses
Frequency output
Failure modeChoose from:
• Actual value
• Defined value: 0 to 1250 Hz
• 0 Hz
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-912
0 mA
PROFIBUS PA
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
Local display
Plain text displayWith information on cause and remedial measures
BacklightAdditionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Endress+Hauser11
Page 12
Operating tool
0
100
200
300
400
500
121416
1820
22242628
U [V]
s
R [ ]bW
1.11.21
30323436
35
• Via digital communication:
– HART protocol
– FOUNDATION Fieldbus
– PROFIBUS PA
• Via service interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation (→ 58)
Proline Prowirl C 200
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply
unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage (→ 22)
• RB ≤ (US - U
term. min
) :0.022 A
• RB ≤500 Ω
A0020417
2Load for a compact version without local operation
1Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i and option C "4-20 mA HART, 4-20 mA"
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with non-Ex and Ex d
Sample calculation
Supply voltage of the supply unit:
– US = 19 V
– U
= 12 V (measuring device) + 1 V (local operation without lighting) = 13 V
term. min
Maximum load: RB≤ (19 V - 13 V) :0.022 A = 273 Ω
The minimum terminal voltage (U
) increases if local operation is used (→ 23).
term. min
Ex connection dataSafety-related values
12Endress+Hauser
Page 13
Proline Prowirl C 200
Type of protection XP
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option C4-20mA HART
4-20mA
Option D4-20mA HARTU
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
IS type of protection
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Endress+Hauser13
Page 14
Proline Prowirl C 200
Order code for "Output"Output typeIntrinsically safe values
4-20mA
Option D4-20mA HARTUi = DC 30 V
Pulse/frequency/switch outputUi = DC 30 V
4 to 20 mA current inputUi = DC 30 V
Option EFOUNDATION FieldbusSTANDARD
Pulse/frequency/switch outputUi = 30 V
Option GPROFIBUS PASTANDARD
Pulse/frequency/switch outputUi = 30 V
Ci = 30 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are user-selectable.
All outputs are galvanically isolated from one another.
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x38
HART protocol revision7
Device description files
(DTM, DD)
HART load• Min. 250 Ω
Information and files under:
www.endress.com
• Max. 500 Ω
14Endress+Hauser
Page 15
Proline Prowirl C 200
Dynamic variablesRead out the dynamic variables: HART command 3
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Condensate mass flow
• Reynolds number
• Totalizer 1
• Totalizer 2
• Totalizer 3
• HART input
• Density
• Pressure
• Specific volume
• Degree of overheating
Device variablesRead out the device variables: HART command 9
The device variables are permanently assigned.
A maximum of 8 device variables can be transmitted:
• 0 = volume flow
• 1 = corrected volume flow
• 2 = Mass flow
• 3 = flow velocity
• 4 = temperature
• 5 = calculated saturated steam pressure
• 6 = steam quality
• 7 = total mass flow
• 8 = energy flow
• 9 = heat flow difference
• 10 = condensate mass flow
• 11 = Reynolds number
• 12 = totalizer 1
• 13 = totalizer 2
• 14 = totalizer 3
• 15 = HART input
• 16 = density
• 17 = pressure
• 18 = specific volume
• 19 = degree of overheating
FOUNDATION Fieldbus
Manufacturer ID0x452B48
Ident number0x1038
Device revision1
Endress+Hauser15
Page 16
DD revisionInformation and files under:
CFF revision
Device Tester Version (ITK
version)
ITK Test Campaign NumberIT094200
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Max. response delayMin. 5
• www.endress.com
• www.fieldbus.org
6.1.1
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
Proline Prowirl C 200
Transducer Blocks
BlockContentsOutput values
Setup Transducer Block
(TRDSUP)
Advanced Setup
Transducer Block
(TRDASUP)
Display Transducer
Block
(TRDDISP)
HistoROM Transducer
Block
(TRDHROM)
All parameters for standard commissioning.No output values
All parameters for more accurate measurement
configuration.
Parameters for configuring the local display.No output values
Parameters for using the HistoROM function.No output values
Parameters that require the user to have indepth knowledge of the operation of the device
in order to configure the parameters
appropriately.
Parameters that provide information about the
state of the device.
Parameters that can only be accessed by Endress
+Hauser Service.
Parameters that provide Endress+Hauser Service
with information about the state of the device.
Parameters for configuring all the totalizers and
the inventory counter.
Parameters for the configuration and
comprehensive information about the results of
the verification.
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
No output values
No output values
No output values
No output values
Process variables (AI Channel)
• Totalizer 1 (16)
• Totalizer 2 (17)
• Totalizer 3 (18)
No output values
Endress+Hauser17
Page 18
Function blocks
Proline Prowirl C 200
BlockNumber
of
blocks
Resource Block
(RB)
Analog Input
Block
(AI)
Discrete Input
Block
(DI)
PID Block
(PID)
Multiple Analog
Output Block
(MAO)
1This Block (extended functionality) contains
4This Block (extended functionality) receives
1This Block (standard functionality) receives a
1This Block (standard functionality) acts as a
1This Block (standard functionality) receives
ContentsProcess variables (Channel)
–
all the data that uniquely identify the device; it
is the equivalent of an electronic nameplate
for the device.
• Temperature (7)
the measurement data provided by the Sensor
Block (can be selected via a channel number)
and makes the data available for other blocks
at the output.
Execution time: 13 ms
discrete value (e.g. indicator that measuring
range has been exceeded) and makes the
value available for other blocks at the output.
Execution time: 12 ms
proportional-integral-differential controller
and can be used universally for control in the
field. It enables cascading and feedforward
control.
Execution time: 13 ms
several analog values and makes them
available for other blocks at the output.
Execution time: 11 ms
• Mass flow (11)
• Volume flow (9)
• Corrected volume flow (13)
• Flow velocity (37)
• Energy flow (38)
• Calculated saturated steam
pressure (45)
• Total mass flow (46)
• Condensate mass flow (47)
• Steam quality (48)
• Heat flow difference (49)
• Reynolds number (50)
• Status switch output (101)
• Low flow cutoff (103)
• Status verification (105)
–
Channel_0 (121)
• Value 1: External
compensation variables
(pressure, gage pressure,
density, temperature or
second temperature)
• Value 2 to 8: Not assigned
The compensation
variables must be
transmitted to the device
in the SI basic unit.
18Endress+Hauser
Page 19
Proline Prowirl C 200
BlockNumber
of
blocks
Multiple Digital
Output Block
(MDO)
Integrator Block
(IT)
1This Block (standard functionality) receives
1This Block (standard functionality) integrates
PROFIBUS PA
ContentsProcess variables (Channel)
Channel_DO (122)
several discrete values and makes them
available for other blocks at the output.
Execution time: 14 ms
a measured variable over time or totalizes the
pulses from a Pulse Input Block. The Block can
be used as a totalizer that totalizes until a
reset, or as a batch totalizer whereby the
integrated value is compared against a target
value generated before or during the control
routine and generates a binary signal when
the target value is reached.
Execution time: 16 ms
• Value 1: Reset totalizer 1
• Value 2: Reset totalizer 2
• Value 3: Reset totalizer 3
• Value 4: Flow override
• Value 5: Start heartbeat
verification
• Value 6: Status switch output
• Value 7: Not assigned
• Value 8: Not assigned
–
Manufacturer ID0x11
Ident number0x1564
Profile version3.02
Device description files (GSD,
DTM, DD)
Output values
(from measuring device to
automation system)
Input values
(from automation system to
measuring device)
Information and files under:
• www.endress.com
• www.profibus.org
Analog input 1 to 4
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Pressure
• Specific volume
• Degree of overheating
Digital input 1 to 2
• Status
• Low flow cut off
• Switch output
Totalizer 1 to 3
• Mass flow
• Volume flow
• Corrected volume flow
Analog output
External pressure, gage pressure, density, temperature or second temperature
(for delta heat measurement)
Digital output 1 to 3 (fixed assignment)
• Digital output 1: switch positive zero return on/off
• Digital output 2: switch switch output on/off
• Digital output 3: Start verification
Totalizer 1 to 3
• Totalize
• Reset and hold
• Preset and hold
Endress+Hauser19
Page 20
Supported functions• Identification & Maintenance
–
4
+
1
–
2
+
3
1
2
4
–
6
+
5
3
+
1
–
2
–
4
+
3
–
6
+
5
3
1
2
4
Configuration of the device
address
Power supply
Terminal assignmentTransmitter
Connection versions
Proline Prowirl C 200
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e.g. FieldCare)
A0020738
Maximum number of terminals
Terminals 1 to 6:
Without integrated overvoltage protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Input (passive): supply voltage and signal transmission
4
Ground terminal for cable shield
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
Option A4-20 mA HART (passive)--
Option B
Option C
Option D
1)
1)
1) 2)
4-20 mA HART (passive)
4-20 mA HART (passive)4-20 mA (passive)-
4-20 mA HART (passive)
Maximum number of terminals for order code for
"Accessory mounted", option NA "Overvoltage
protection"
• Terminals 1 to 4:
With integrated overvoltage protection
• Terminals 5 to 6:
Without integrated overvoltage protection
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
A0020739
-
4-20 mA current input
(passive)
20Endress+Hauser
Page 21
Proline Prowirl C 200
4
1
2
3
1
2
+
–
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
1) 3)
Option E
Option G
1)Output 1 must always be used; output 2 is optional.
2)The integrated overvoltage protection is not used with option D: Terminals 5 and 6 (current input) are not
protected against overvoltage.
3)FOUNDATION Fieldbus with integrated reverse polarity protection.
4)PROFIBUS PA with integrated reverse polarity protection.
1) 4)
FOUNDATION Fieldbus
PROFIBUS PA
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
-
-
Remote version
In the case of the remote version, the sensor and transmitter are mounted separately from one
another and connected by a connecting cable. The sensor is connected via the connection housing
while the transmitter is connected via the connection compartment of the wall holder unit.
The way the transmitter wall holder is connected depends on the measuring device approval
and the version of the connecting cable used.
Connection is only possible via terminals:
• For approvals Ex n, Ex tb and cCSAus Div. 1
• If a reinforced connecting cable is used
The connection is via an M12 connector:
• For all other approvals
• If the standard connecting cable is used
Connection to the connection housing of the sensor is always via terminals.
A0019335
3Terminals for connection compartment in the transmitter wall holder and the sensor connection housing
1Terminals for connecting cable
2Grounding via the cable strain relief
Terminal numberAssignmentCable color
Connecting cable
1Supply voltageBrown
2GroundingWhite
3RS485 (+)Yellow
4RS485 (–)Green
Endress+Hauser21
Page 22
Pin assignment, device plugPROFIBUS PA
1
2
4
3
1
2
4
3
Device plug for signal transmission (device side)
FOUNDATION Fieldbus
Device plug for signal transmission (device side)
Proline Prowirl C 200
PinAssignmentCodingPlug/socket
1+PROFIBUS PA +APlug
2Grounding
A0019021
A0019021
3-PROFIBUS PA –
4Not assigned
PinAssignmentCodingPlug/socket
1+Signal +APlug
2-Signal –
3Not assigned
4Grounding
Supply voltageTransmitter
An external power supply is required for each output.
Supply voltage for a compact version without a local display
Order code for "Output"Minimum
Option A: 4-20 mA HART≥DC 12 VDC 35 V
Option B: 4-20 mA HART, pulse/
frequency/switch output
Option C: 4-20 mA HART, 4-20 mA≥DC 12 VDC 30 V
Option D: 4-20 mA HART, pulse/
frequency/switch output, 4-20 mA current
3)
input
Option E : FOUNDATION Fieldbus, pulse/
frequency/switch output
The way the transmitter wall holder is connected depends on the measuring device approval
and the version of the connecting cable used.
Connection is only possible via terminals:
• For approvals Ex n, Ex tb and cCSAus Div. 1
• If a reinforced connecting cable is used
The connection is via an M12 connector:
• For all other approvals
• If the standard connecting cable is used
Connection to the connection housing of the sensor is always via terminals.
24Endress+Hauser
A0019727
Page 25
Proline Prowirl C 200
2
4
4...20 mA
5
631
+
-
7
+
-
2
4...20 mA
3
1
+
-
4
+
–
+
-
Connection examples
Current output 4-20 mA HART
A0015511
5Connection example for 4-20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Active barrier for power supply (e.g. RN221N) (→ 29)
3Cable shield, observe cable specifications (→ 29)
4Resistor for HART communication (≥ 250 Ω): observe maximum load (→ 12)
5Connection for HART operating devices (→ 58)
6Analog display unit: observe maximum load (→ 12)
7Transmitter
Current output 4-20 mA
6Connection example for 4-20 mA current output (passive)
1Automation system with current input (e.g. PLC)
2Active barrier for power supply (e.g. RN221N) (→ 22)
3Analog display unit: observe maximum load (→ 12)
4Transmitter
A0015512
Endress+Hauser25
Page 26
Pulse/frequency output
1
+
_
12345
2
+
–
+
–
3
1
+
_
+
_
2
+
_
3
7Connection example for pulse/frequency output (passive)
1Automation system with pulse/frequency input (e.g. PLC)
2Power supply
3Transmitter: observe input values (→ 9)
Switch output
Proline Prowirl C 200
A0016801
8Connection example for switch output (passive)
1Automation system with switch input (e.g. PLC)
2Power supply
3Transmitter: observe input values (→ 9)
A0016802
26Endress+Hauser
Page 27
Proline Prowirl C 200
213
+
-
+
-
+
-
4
5
5
78
6
6
6
6
6
6
.
-
PROFIBUS-PA
A0019004
9Connection example for PROFIBUS-PA
1Control system (e.g. PLC)
2Segment coupler PROFIBUS DP/PA
3Cable shield
4T-box
5Measuring device
6Local grounding
7Bus terminator
8Potential matching line
Endress+Hauser27
Page 28
FOUNDATION Fieldbus
213
+
-
+
-
+
-
4
5
5
78
6
6
6
6
6
6
.
-
1
+
-
3
+
-
2
Proline Prowirl C 200
10Connection example for FOUNDATION Fieldbus
1Control system (e.g. PLC)
2Power Conditioner (FOUNDATION Fieldbus)
3Cable shield
4T-box
5Measuring device
6Local grounding
7Bus terminator
8Potential matching line
Current input
11Connection example for 4-20 mA current input
1Power supply
2External measuring device (for reading in pressure or temperature, for instance)
3Transmitter: observe input values (→ 9)
A0019004
A0020741
28Endress+Hauser
Page 29
Proline Prowirl C 200
3
4...20 mA
5
1
+
-
3
6
+
–
+
+
–
+
–
+
–
+
–
–
2
4
4
7
+
-
HART input
A0016029
12Connection example for HART input with a common negative
1Automation system with HART output (e.g. PLC)
2Resistor for HART communication (≥ 250 Ω): observe maximum load (→ 12)
3Active barrier for power supply (e.g. RN221N) (→ 22)
4Cable shield, observe cable specifications (→ 29)
5Analog display unit: observe maximum load (→ 12)
6Pressure transmitter (e.g. Cerabar M, Cerabar S): see requirements (→ 8)
7Transmitter
Potential equalizationRequirements
Please consider the following to ensure correct measurement:
• Same electrical potential for the fluid and sensor
• Remote version: same electrical potential for the sensor and transmitter
• Company-internal grounding concepts
• Pipe material and grounding
For devices intended for use in hazardous locations, please observe the guidelines in the Ex
documentation (XA).
Terminals
• For device version without integrated overvoltage protection: plug-in spring terminals for wire
cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• For device version with integrated overvoltage protection: screw terminals for wire cross-sections
0.2 to 2.5 mm2 (24 to 14 AWG)
Cable entries
• Cable gland (not for Ex d): M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
– For non-Ex and Ex: NPT ½"
– For non-Ex and Ex (not for CSA Ex d/XP): G ½"
– For Ex d: M20 × 1.5
Cable specificationPermitted temperature range
• –40 °C (–40 °F) to +80 °C (+176 °F)
• Minimum requirement: cable temperature range ≥ ambient temperature +20 K
Signal cable
Current output
For 4-20 mA HART: Shielded cable recommended. Observe grounding concept of the plant.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Endress+Hauser29
Page 30
Proline Prowirl C 200
Current input
Standard installation cable is sufficient.
FOUNDATION Fieldbus
Twisted, shielded two-wire cable.
For further information on planning and installing FOUNDATION Fieldbus networks see:
• Operating Instructions for "FOUNDATION Fieldbus Overview" (BA00013S)
• FOUNDATION Fieldbus Guideline
• IEC 61158-2 (MBP)
PROFIBUS PA
Twisted, shielded two-wire cable. Cable type A is recommended.
For further information on planning and installing PROFIBUS PA networks see:
• Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning"
(BA00034S)
• PNO Directive 2.092 "PROFIBUS PA User and Installation Guideline"
• IEC 61158-2 (MBP)
Connecting cable for remote version
Connecting cable (standard)
Standard cable
Flame resistanceAccording to DIN EN 60332-1-2
Oil-resistanceAccording to DIN EN 60811-2-1
ShieldingGalvanized copper-braid, opt. density approx. 85%
Cable length5 m (16 ft), 10 m (32 ft), 20 m (65 ft), 30 m (98 ft)
Operating temperatureWhen mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
4 × 2 × 0.34 mm2 (22 AWG) PVC cable with common shield (4 pairs, pairstranded)
can move freely: –25 to +105 °C (–13 to +221 °F)
Connecting cable (reinforced)
Cable, reinforced
Flame resistanceAccording to DIN EN 60332-1-2
Oil-resistanceAccording to DIN EN 60811-2-1
ShieldingGalvanized copper-braid, opt. density approx. 85%
Strain relief and
reinforcement
Cable length5 m (16 ft), 10 m (32 ft), 20 m (65 ft), 30 m (98 ft)
Operating temperatureWhen mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
4 × 2 × 0.34 mm2 (22 AWG) PVC cable with common shield (4 pairs, pairstranded) and additional steel-wire braided sheath
Steel-wire braid, galvanized
can move freely: –25 to +105 °C (–13 to +221 °F)
Overvoltage protection
The device can be ordered with integrated overvoltage protection for diverse approvals:
Order code for "Accessory mounted", option NA "Overvoltage protection"
Input voltage rangeValues correspond to supply voltage specifications (→ 22)
Resistance per channel2 ⋅0.5 Ω max
DC sparkover voltage400 to 700 V
Trip surge voltage<800 V
Capacitance at 1 MHz<1.5 pF
1)
30Endress+Hauser
Page 31
Proline Prowirl C 200
Re
min
Re
max
Re
Re
max
A2
A1
-A1
-A2
R1
R2
Nominal discharge current
(8/20 μs)
Temperature range–40 to +85 °C (–40 to +185 °F)
1)The voltage is reduced by the amount of the internal resistance I
Depending on the temperature class, restrictions apply to the ambient temperature for device
versions with overvoltage protection (→ 38)
Performance characteristics
Reference operating
conditions
Maximum measured errorBase accuracy
• Error limits following ISO/DIN 11631
• +20 to +30 °C (+68 to +86 °F)
• 2 to 4 bar (29 to 58 psi)
• Calibration system traceable to national standards
• Calibration with the process connection corresponding to the particular standard
To obtain measured errors, use the Applicator sizing tool (→ 65)
o.r. = of reading, Re = Reynolds number
Volume flow
The measured error for the volume flow is as follows depending on the Reynolds number and the
compressibility of the medium under measurement:
10 kA
min
⋅ R
i
Deviation of volume flow value (absolute) from the reading
Re rangeMeasured value deviationStandardStandard
R1 to R2A2< 10 %< 10 %
R2 to Re
max
1)Accuracy specifications valid up to 75 m/s (246 ft/s)
Medium typeIncompressibleCompressible
A1< 0.75 %< 1.0 %
Endress+Hauser31
A0019703
1)
Page 32
Proline Prowirl C 200
Reynolds numbers
R15000
R220000
IncompressibleCompressible
StandardStandard
Temperature
• Saturated steam and liquids at room temperature if T > 100 °C (212 °F) applies: < 1 °C (1.8 °F)
• Gas: < 1 % o.r. [K]
Rise time 50 % (stirred under water, following IEC 60751): 8 s
Mass flow (saturated steam)
• Flow velocities 20 to 50 m/s (66 to 164 ft/s), T > 150 °C (302 °F) or (423 K)
– Re > 20000: < 1.7 % o.r.
– Re between 5000 to 20000: < 10 % o.r.
• Flow velocities 10 to 70 m/s (33 to 210 ft/s), T > 140 °C (284 °F) or (413 K)
– Re > 20000: < 2 % o.r.
– Re between 5000 to 20000: < 10 % o.r.
The use of a Cerabar S is required for the measured errors listed in the following section. The
measured error used to calculate the error in the measured pressure is 0.15%.
Mass flow of superheated steam and gas (single gas, gas mixture, air: NEL40; natural gas: ISO
12213-2 contains AGA8-DC92, AGA NX-19, ISO 12213-3 contains SGERG-88 and AGA8 Gross
Method 1)
• Re > 20000 and process pressure < 40 bar abs. (580 psi abs.): 1.7 % o.r.
• Re between 5000 to 20000 and process pressure < 40 bar abs. (580 psi abs.): 10 % o.r.
• Re > 20000 and process pressure < 120 bar abs. (1740 psi abs.): 2.6 % o.r.
• Re between 5000 to 20000 and process pressure < 120 bar abs. (1740 psi abs.): 10 % o.r.
abs. = absolute
Mass flow (water)
• Re 20000: < 0.85 % o.r.
• Re between 5000 to 20000: < 10 % o.r.
Mass flow (user-defined liquids)
To specify the system accuracy, Endress+Hauser requires information about the type of liquid and its
operating temperature or information in table form about the dependency between the liquid
density and the temperature.
Example
• Acetone is to be measured at fluid temperatures between +70 to +90 °C (+158 to +194 °F).
• For this purpose the Reference temperature parameter (7703) (here 80 °C (176 °F)), Referencedensity parameter (7700) (here 720.00 kg/m3) and Linear expansion coefficient parameter
(7621) (here 18.0298 × 10-4 1/°C) must be entered in the transmitter.
• The overall system uncertainty, which is smaller than 0.9 % for the example above, is comprised of
the following uncertainties of measurement: uncertainty of volume flow measurement,
uncertainty of temperature measurement, uncertainty of the density-temperature correlation used
(incl. the resulting uncertainty of density).
Mass flow (other media)
Depends on the selected fluid and the pressure value, which is specified in the parameters. Individual
error analysis must be performed.
Accuracy of outputs
o.r. = of reading
Current output
Accuracy±10 µA
Pulse/frequency output
AccuracyMax. ±100 ppm o.r.
32Endress+Hauser
Page 33
Proline Prowirl C 200
Repeatability
Response time
Influence of ambient
temperature
o.r. = of reading
±0.2 % o.r.
If all the configurable functions for filter times (flow damping, display damping, current output time
constant, frequency output time constant, status output time constant) are set to 0, in the event of
vortex frequencies of 10 Hz and higher a response time of max(Tν,100 ms) can be expected.
In the event of measuring frequencies < 10 Hz, the response time is > 100 ms and can be up to 10 s.
Tν is the average vortex period duration of the flowing fluid.
o.r. = of reading
Current output
Additional error, in relation to the span of 16 mA:
Temperature coefficient at
zero point (4 mA)
Temperature coefficient
with span (20 mA)
0.02 %/10 K
0.05 %/10 K
Pulse/frequency output
Temperature coefficientMax. ±100 ppm o.r.
Mounting location
Orientation
Installation
A0015543
The direction of the arrow on the sensor nameplate helps you to install the sensor according to the
flow direction (direction of medium flow through the piping).
Vortex meters require a fully developed flow profile as a prerequisite for correct volume flow
measurement. Therefore, please note the following:
OrientationCompact versionRemote version
A Vertical orientation
1)
A0015545
B Horizontal orientation, transmitter head up
A0015589
2) 3)
Endress+Hauser33
Page 34
Proline Prowirl C 200
A
L
OrientationCompact versionRemote version
C Horizontal orientation, transmitter head down
A0015590
D Horizontal orientation, transmitter head at side
A0015592
1)In the case of liquids, there should be upward flow in vertical pipes to avoid partial pipe filling (Fig. A).
Disruption in flow measurement! In the case of vertical orientation and downward flowing liquid, the pipe
always needs to be completely filled to ensure correct liquid flow measurement.
2)Danger of electronics overheating! If the fluid temperature is ≥ 200 °C (392 °F) orientation B is not
permitted for the wafer version (Prowirl D) with nominal diameters DN 100 (4") and DN 150 (6").
3)In the case of hot media (e.g. steam or fluid temperature (TM) ≥ 200 °C (392 °F): orientation C or D
4)In the case of very cold media (e.g. liquid nitrogen): orientation B or D
5)For "wet steam detection/measurement" option: orientation C
Minimum spacing and cable length
4) 5)
4)
Inlet and outlet runs
A0019211
AMinimum spacing in all directions
LRequired cable length
The following dimensions must be observed to guarantee problem-free access to the device for
service purposes:
• A =100 mm (3.94 in)
• L = L + 150 mm (5.91 in)
Rotating the electronics housing and the display
The electronics housing can be rotated continuously by 360 °° on the housing support. The display
unit can be rotated in 45 ° stages. This means you can read the display comfortably from all
directions.
To attain the specified level of accuracy of the measuring device, the inlet and outlet runs mentioned
below must be maintained at the very minimum.
34Endress+Hauser
Page 35
Proline Prowirl C 200
15 × DN
5 × DN
1
3
25 × DN
5 × DN
40 × DN
5 × DN
4
2
20 × DN
5 × DN
5
20 × DN
5 × DN
6
17 × DN + 8 × h
5 × DN
h
7
50 × DN
5 × DN
9
40 × DN
5 × DN
8
5 × DN
DN 25 (1"):≤
DN 40 (1½"):≥
PT
TT
3...5 x DN
4...8 x DN
A0019189
13Minimum inlet and outlet runs with various flow obstructions
hDifference in expansion
1Reduction by one nominal diameter size
2Single elbow (90° elbow)
3Double elbow (2 × 90° elbows, opposite)
4Double elbow 3D (2 × 90° elbows, opposite, not on one plane)
5T-piece
6Expansion
7Control valve
8Two measuring devices in a row where DN ≤ 25 (1"): directly flange on flange
9Two measuring devices in a row where DN ≥ 40 (1½"): for spacing, see graphic
Length of connecting cable
Outlet runs when installing external devices
If installing an external device, observe the specified distance.
PT Pressure transmitter
TT Temperature transmitter
To ensure correct measuring results when using the remote version,
• observe the maximum permitted cable length L
max
.
• The value for the cable length must be calculated if the cable cross-section differs from the
specification.
For detailed information about calculating the length of the connecting cable, refer to the
Operating Instructions for the device on the CD-ROM provided
A0019205
Endress+Hauser35
Page 36
Proline Prowirl C 200
80 (3.15)
80 (3.15)
19 (0.6)
! 8.6 (0.39)
M 8
! 20…70
(! 0.79 to 2.75)
1
4 x
SW 13
Installing the wall-mount
housing
Wall mounting
A0019864
14Engineering unit mm (in)
Post mounting
15Engineering unit mm (in)
1Post retainer kit for post mounting
36Endress+Hauser
A0019862
Page 37
Proline Prowirl C 200
Q
1
2
3
Special mounting
instructions
Inspection kit
The inspection kit contains the necessary parts for the annual visual inspection of the primary
measurement element (bluff body) in accordance with ERCB Dir. 017.
Consists of:
• 2 inspection centering sleeves
• 8 screws
• 2 inspection seals
• 2 inspection covers
The centering sleeve supports the user by centering the calipers in the inspection ports. This makes it
easier to measure the distance from the sealing surface to the bluff body. In addition, the kit also
contains screws, seals and covers for the inspection ports.
An inspection kit can be ordered separately (see the "Accessories" section (→ 64)).
Installation for delta heat measurements
Order code for "Sensor version", option 3 "Mass flow (integrated temperature measurement)"
The second temperature measurement is taken using a separate temperature sensor. The measuring
device reads in this value via a communication interface.
• In the case of saturated steam delta heat measurements, the Prowirl 200 must be installed on the
steam side.
• In the case of water delta heat measurements, the Prowirl 200 can be installed on the cold or
warm side.
A0019209
16Layout for delta heat measurement of saturated steam and water
Observe the following minimum head clearance: 222 mm (8.74 in)
For information the weather protection cover, see (→ 63)
Endress+Hauser37
Page 38
Environment
Proline Prowirl C 200
Ambient temperature range
Compact version
Measuring deviceNon-Ex:–40 to +80 °C (–40 to +176 °F)
Ex i:–40 to +70 °C (–40 to +158 °F)
EEx d/XP version:–40 to +60 °C (–40 to +140 °F)
ATEX II1/2G Ex d, Ex ia:–40 to +60 °C (–40 to +140 °F)
Local display–20 to +60 °C (–4 to +140 °F)
1)Additionally available as order code for "Test, certificate", option JN "Transmitter ambient temperature –50
°C (–58 °F)".
1)
1)
1)
1)
Remote version
TransmitterNon-Ex:–40 to +80 °C (–40 to +176 °F)
Ex i:–40 to +80 °C (–40 to +176 °F)
Ex d:–40 to +60 °C (–40 to +140 °F)
ATEX II1/2G Ex d, Ex ia:–40 to +60 °C (–40 to +140 °F)
SensorNon-Ex:–40 to +85 °C (–40 to +185 °F)
Ex i:–40 to +85 °C (–40 to +185 °F)
Ex d:–40 to +85 °C (–40 to +185 °F)
ATEX II1/2G Ex d, Ex ia:–40 to +85 °C (–40 to +185 °F)
Local display–20 to +60 °C (–4 to +140 °F)
1)
1)
1)
1)
1)
1)
1)
1)
1)Additionally available as order code for "Test, certificate", option JN "Transmitter ambient temperature –50
°C (–58 °F)".
If operating outdoors:
‣
Avoid direct sunlight, particularly in warm climatic regions.
Weather protection covers can be ordered from Endress+Hauser: see "Accessories" section
(→ 63)
Temperature tables
Tm = fluid temperature, Ta = ambient temperature
The following interdependencies between the permitted ambient and fluid temperatures apply when
operating the device in hazardous areas:
Compact version
Order code for "Sensor version", option 4 "Volume flow Alloy 718"; option 6 "Mass flow Alloy 718"
Order code for "Output", option A "4-20mA HART"
Order code for "Approval", all options
CSAUS IS, CCSAUS XP, CCSAUS NI
C
SI units
Version with max. Tm = 280 °C
1)
T
a
[ºC]
408095130195280–
60–95130195280–
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
T1
[450 °C]
38Endress+Hauser
Page 39
Proline Prowirl C 200
Version with max. Tm = 280 °C
1)
T
a
[ºC]
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
T1
[450 °C]
65––130195280–
70––130–––
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 2 °C
US units
Version with max. Tm = 536 °F
1)
T
a
[ºF]
104176203266383536–
140–203266383536–
149––266383536–
158––266–––
T6
[185 °F]
T5
[212 °F]
T4
[275 °F]
T3
[392 °F]
T2
[572 °F]
T1
[842 °F]
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 35.6 °F
Order code for "Output", option B "4-20mA HART, pulse/frequency/switch output"
Order code for "Approval", options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2
CSAUS IS
C
SI units
Version with max. Tm = 280 °C
1)
T
a
[ºC]
2)
35
3)
50
60––130195280–
65––130195280
70––130195
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 2 °C
2)Ta = 40 °C for pulse/frequency/switch output Pi = 0.85 W
3)Ta = 55 °C for pulse/frequency/switch output Pi = 0.85 W
4)Ta = 65 °C for pulse/frequency/switch output Pi = 0.7 W
5)Ta = 70 °C for pulse/frequency/switch output Pi = 0.7 W
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
8095130195280–
–95130195280–
4)
5)
280
5)
T1
[450 °C]
–
–
US units
Version with max. Tm = 536 °F
1)
T
[ºF]
95
122
a
2)
3)
T6
[185 °F]
T5
[212 °F]
T4
[275 °F]
T3
[392 °F]
T2
[572 °F]
176203266383536–
–203266383536–
T1
[842 °F]
140––266383536–
Endress+Hauser39
Page 40
Proline Prowirl C 200
Version with max. Tm = 536 °F
1)
T
a
[ºF]
149––266383536
158––266383
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 35.6 °F
2)Ta = 104 °F for pulse/frequency/switch output Pi = 0.85 W
3)Ta = 131 °F for pulse/frequency/switch output Pi = 0.85 W
4)Ta = 149 °F for pulse/frequency/switch output Pi = 0.7 W
5)Ta = 158 °F for pulse/frequency/switch output Pi = 0.7 W
Order code for "Approval", options BC, BG, BK, B3, IC, IG, IK, I5, C3
CSAUS XP
C
SI units
Version with max. Tm = 280 °C
T
a
[ºC]
408095130195280–
55–95130195280–
65––130195280
70––130195
[185 °F]
T6
[85 °C]
T6
[212 °F]
T5
[100 °C]
T5
T4
[275 °F]
T4
[135 °C]
T3
[392 °F]
T3
[200 °C]
2)
T2
[572 °F]
4)
5)
536
5)
T2
[300 °C]
1)
2)
280
T1
[842 °F]
–
–
T1
[450 °C]
–
–
1)Ta = 65 °C for pulse/frequency/switch output Pi = 0.7 W
2)Ta = 70 °C for pulse/frequency/switch output Pi = 0.7 W
US units
Version with max. Tm = 536 °F
T
[ºF]
a
T6
[185 °F]
T5
[212 °F]
T4
[275 °F]
T3
[392 °F]
T2
[572 °F]
104176203266383536–
131–203266383536–
536
1)
2)
149––266383536
158––266383
2)
1)Ta = 149 °F for pulse/frequency/switch output Pi = 0.7 W
2)Ta = 158 °F for pulse/frequency/switch output Pi = 0.7 W
Order code for "Output", option C "4-20mA HART, 4-20mA"
Order code for "Approval", all options
CSAUS IS, CCSAUS XP, CCSAUS NI
C
SI units
Version with max. Tm = 280 °C
1)
T
a
[ºC]
408095130195280–
55–95130195280–
60––130195280–
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
T1
[842 °F]
–
–
T1
[450 °C]
40Endress+Hauser
Page 41
Proline Prowirl C 200
Version with max. Tm = 280 °C
1)
T
a
[ºC]
65––130195280
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
2)
T1
[450 °C]
–
70––130–––
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 2 °C
2)Ta = 65 °C for pulse/frequency/switch output Pi = 0 W
US units
Version with max. Tm = 536 °F
1)
T
a
[ºF]
104176203266383536–
131–203266383536–
140––266383536–
149––266383536
158––266–––
T6
[185 °F]
T5
[212 °F]
T4
[275 °F]
T3
[392 °F]
T2
[572 °F]
2)
T1
[842 °F]
–
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 35.6 °F
2)Ta = 149 °F for pulse/frequency/switch output Pi = 0 W
Order code for "Output", option D "4-20 mA HART, PFS output; 4-20 mA input"
Order code for "Approval", all options
CSAUS IS, CCSAUS XP, CCSAUS NI
C
SI units
Version with max. Tm = 280 °C
1)
T
a
[ºC]
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
T1
[450 °C]
358095130195280–
50–95130195280–
55–––195280–
60–––195––
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 2 °C
US units
Version with max. Tm = 536 °F
1)
T
a
[ºF]
95176203266383536–
122–203266383536–
131–––383536–
140–––383––
T6
[185 °F]
T5
[212 °F]
T4
[275 °F]
T3
[392 °F]
T2
[572 °F]
T1
[842 °F]
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 35.6 °F
Endress+Hauser41
Page 42
Proline Prowirl C 200
Order code for "Output", option E "FOUNDATION Fieldbus, pulse/frequency/switch output" and
option G "PROFIBUS PA, pulse/frequency/switch output"
Order code for "Approval", all options
CSAUS IS, CCSAUS XP, CCSAUS NI
C
SI units
Version with max. Tm = 280 °C
1)
T
a
[ºC]
408095130195280–
2)
50
60––130195280–
65––130195280
70––130195
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 2 °C
2)Ta = 60 °C for pulse/frequency/switch output Pi = 0 W
3)Ta = 65 °C for pulse/frequency/switch output Pi = 0 W
4)Ta = 70 °C for pulse/frequency/switch output Pi = 0 W
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
–95130195280–
3)
4)
280
4)
T1
[450 °C]
–
–
US units
Version with max. Tm = 536 °F
1)
T
[°F]
a
T6
[185 °F]
T5
[212 °F]
T4
[275 °F]
T3
[392 °F]
T2
[572 °F]
T1
[842 °F]
104176203266383536–
2)
122
–203266383536–
140––266383536–
536
3)
4)
–
–
149––266383536
158––266383
4)
1)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 35.6 °F
2)Ta = 140 °F for pulse/frequency/switch output Pi = 0 W
3)Ta = 149 °F for pulse/frequency/switch output Pi = 0 W
4)Ta = 158 °F for pulse/frequency/switch output Pi = 0 W
Remote version
Transmitter
Order code for "Housing", option J "GT20 two-chamber, remote G314, aluminum coated"; option K
"GT20 two-chamber, remote G315, 316L"
SI units
Order code for "Output", optionOrder code for
"Approval", option
AAll406075
BBA, BB, BD, BH, BJ, B2, IA,
IB, ID, IH, IJ, I4, C2
BC, BG, BK, B3, IC, IG, IK,
I5, C3
CAll405570
T6
[85 °C]
1)
35
T5
[100 °C]T4[135 °C]
2)
50
405570
70
3)
3)
4)
42Endress+Hauser
Page 43
Proline Prowirl C 200
Order code for "Output", optionOrder code for
"Approval", option
DAll35
E
All405570
T6
[85 °C]
5)
T5
[100 °C]T4[135 °C]
5)
50
65
4)
G
1)Ta = 40 °C for pulse/frequency/switch output Pi = 0.85 W
2)Ta = 60 °C for pulse/frequency/switch output Pi = 0.85 W
3)Ta = 75 °C for pulse/frequency/switch output Pi = 0.85 W
4)Ta = 75 °C for pulse/frequency/switch output Pi = 0 W
5)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 2 °C
US units
Order code for "Output", optionOrder code for
"Approval", option
AAll104140167
BBA, BB, BD, BH, BJ, B2, IA,
IB, ID, IH, IJ, I4, C2
BC, BG, BK, B3, IC, IG, IK,
I5, C3
CAll104131158
DAll95
E
All104131158
G
T6
[185 °F]T5[212 °F]T4[275 °F]
1)
95
104131158
5)
122
122
2)
5)
158
149
3)
3)
4)
4)
1)Ta = 104 °F for pulse/frequency/switch output Pi = 0.85 W
2)Ta = 140 °F for pulse/frequency/switch output Pi = 0.85 W
3)Ta = 167 °F for pulse/frequency/switch output Pi = 0.85 W
4)Ta = 167 °F for pulse/frequency/switch output Pi = 0 W
5)The following applies for installations with overvoltage protection in conjunction with temperature class
T5, T6 and approval options BA, BB, BD, BH, BJ, B2, IA, IB, ID, IH, IJ, I4, C2: Ta = Ta - 35.6 °F
Sensor
Order code for "Sensor version", option 4 "Volume flow Alloy 718"; option 6 "Mass flow Alloy 718"
SI units
Version with max. Tm = 280 °C
T
[ºC]
a
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
T1
[450 °C]
558095130195280–
70–95130195280–
85––130195280–
US units
Version with max. Tm = 536 °F
T
a
[°F]
104176203266383536–
122–203266383536–
149––266383536–
T6
[185 °F]
T5
[212 °F]
T4
[275 °F]
T3
[392 °F]
T2
[572 °F]
T1
[842 °F]
Endress+Hauser43
Page 44
Proline Prowirl C 200
Storage temperature
Climate class
Degree of protection
Vibration resistance
Electromagnetic
compatibility (EMC)
All components apart from the display modules:
–50 to +80 °C (–58 to +176 °F)
Display modules:
–40 to +80 °C (–40 to +176 °F)
DIN EN 60068-2-38 (test Z/AD)
Transmitter
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure
Sensor
IP66/67, type 4X enclosure
Device plug
IP67, only in screwed situation
• For compact/remote version made of coated aluminum and remote version made of stainless steel:
Acceleration up to 2g (if gain set to factory setting), 10 to 500 Hz, following IEC 60068-2-6
• For the compact version made of stainless steel:
Acceleration up to 1g (if gain set to factory setting), 10 to 500 Hz, following IEC 60068-2-6
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
For details refer to the Declaration of Conformity.
Medium temperature range
Pressure-temperature
ratings
Process
DSC sensor
Order code for "Sensor version":
• Option 4 "Volume flow, Alloy 718":
–40 to +400 °C (–40 to +752 °F)
• Option 6 "Mass flow, Alloy 718":
–40 to +400 °C (–40 to +752 °F)
Seals
• –200 to +400 °C (–328 to +752 °F) for graphite (standard)
• –15 to +175 °C (+5 to +347 °F) for Viton
• –20 to +275 °C (–4 to +527 °F) for Kalrez
• –200 to +260 °C (–328 to +500 °F) for Gylon
The following pressure-temperature ratings refer to the entire device and not just the process
connection.
The pressure-temperature rating for the specific measuring device is programmed into the software.
If values exceed the curve range a warning is displayed. Depending on the system configuration and
sensor version, the pressure and temperature are determined by entering, reading in or calculating
values.
2)
2)Capacitance sensor
44Endress+Hauser
Page 45
Proline Prowirl C 200
600[°F]7005004003002001000
[°C]
400300200100
0
-60
800
60
80
100
120
140
160
180
[bar][psi]
1200
1600
2000
2400
Cl.900
Cl.600
1
Process connection: flange to ASME B16.5 ed. 2009, Group 1.1 materials
If the device is used for a prolonged period at a temperature of over 375 °C, it is the
responsibility of the owner-operator to perform additional tests. These can include:
Dimensional tests to monitor deformation caused by corrosion or creepage.
‣
A0020882-EN
Pressure loss
Thermal insulation
For a precise calculation, use the Applicator(→ 65).
For optimum temperature measurement and mass calculation, heat transfer at the sensor must be
avoided for some fluids. This can be ensured by installing thermal insulation. A wide range of
materials can be used for the required insulation.
This applies for:
• Compact version
• Remote sensor version
The maximum insulation height permitted is illustrated in the diagram:
A0019212
1Maximum insulation height
When insulating, ensure that a sufficiently large area of the housing support remains exposed.
‣
The uncovered part serves as a radiator and protects the electronics from overheating and excessive
cooling.
Vibrations
Design, dimensionsCompact version
Endress+Hauser45
The correct operation of the measuring system is not affected by plant vibrations up to 1 g,
10 to 500 Hz. Therefore no special measures are needed to secure the sensors.
Mechanical construction
Order code for "Housing", option C "GT20, two-chamber, aluminum coated"
Page 46
Flanged version
D
E
A
G
B
C
F
L
1
Proline Prowirl C 200
A0020234
1Optional inspection ports: order code for "Sensor option", option CR "ERCB Dir. 017 inspection ports"
Dimensions in SI units
DNAB
1)
CD
[mm][mm][mm][mm][mm][mm][mm][mm][mm]
50162102601657590310
80162102601657590321
100162102601657590331
150162102601657590352
1)For version without local display: values - 7 mm
2)For version with overvoltage protection: values + 8 mm
3)For version without local display: values - 10 mm
4)dependent on respective process connection
2)
EF
2)
3)
G
L
4)
4)
4)
4)
Dimensions in US units
DNAB
1)
CD
[in][in][in][in][in][in][in][in][in]
26.384.022.366.502.953.5412.4
36.384.022.366.502.953.5412.64
46.384.022.366.502.953.5413.03
66.384.022.366.502.953.5413.86
2)
EF
2)
3)
G
L
4)
4)
4)
4)
1)For version without local display: values - 0.28 in
2)For version with overvoltage protection: values + 0.31 in
3)For version without local display: values - 0.39 in
4)dependent on respective process connection
Butt-weld version
Order code for "Process connection", option CAC "ASME Cl. 600/Sch.80 butt-weld"; option CAD "ASME
Cl. 900/Sch.160 butt-weld";
46Endress+Hauser
Page 47
Proline Prowirl C 200
D
E
A
G
H
B
C
F
L
±2.5
()±0.10
K
M
1
di
2
A0020317
18Engineering unit mm (in)
1Groove type as per ASME B31.3
2Inspection ports
Dimensions in SI units
Cl. 600/Sch. 80: SA-106 Gr. B, SA-333 Gr. 6 (order code for "Process connection", option CAC)
English, German, French, Spanish, Italian, Chinese, Japanese
• Uniform operating philosophy applied to device and operating tools
• If replacing the electronic module, transfer the device configuration via the integrated memory
(integrated HistoROM) which contains the process and measuring device data and the event
logbook. No need to reconfigure.
• Troubleshooting measures can be called up via the device and in the operating tools
• Diverse simulation options, logbook for events that occur and optional line recorder functions
Local operationVia display module
Order code for "Display; Operation", option C "SD02"Order code for "Display; Operation", option E "SD03"
A0015544
1Operation with pushbuttons1Operation with touch control
A0015546
Display elements
• 4-line display
• With order code for "Display; operation", option E:
White background lighting; switches to red in event of device errors
• Format for displaying measured variables and status variables can be individually configured
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
Operating elements
• With order code for "Display; operation", option C:
Local operation with 3 push buttons:
, ,
• With order code for "Display; operation", option E:
External operation via touch control; 3 optical keys:
, ,
• Operating elements also accessible in various hazardous areas
Endress+Hauser57
Page 58
Proline Prowirl C 200
3
2
1
1
2
457
9
68
3
Additional functionality
• Data backup function
The device configuration can be saved in the display module.
• Data comparison function
The device configuration saved in the display module can be compared to the current device
configuration.
• Data transfer function
The transmitter configuration can be transmitted to another device using the display module.
Via remote display and operating module FHX50
23Operating options via FHX50
1Housing of remote display and operating module FHX50
2SD02 display and operating module, push buttons: cover must be opened for operation
3SD03 display and operating module, optical buttons: operation possible through cover glass
A0013137
Remote operationVia HART protocol
24Options for remote operation via HART protocol
1Control system (e.g. PLC)
2Transmitter power supply unit, e.g. RN221N (with communication resistor)
3Connection for Commubox FXA195 and Field Communicator 475
4Field Communicator 475
5Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
6Commubox FXA195 (USB)
7Field Xpert SFX350 or SFX370
8VIATOR Bluetooth modem with connecting cable
9Transmitter
A0013764
Via FOUNDATION Fieldbus network
This communication interface is present in the following device version:
Order code for "Output", option E: FOUNDATION Fieldbus
58Endress+Hauser
Page 59
Proline Prowirl C 200
12
3
1
99889988
4
66
77
5
132
4
5
666777
A0023460
1Automation system
2Computer with FOUNDATION Fieldbus network card
3Industry network
4High Speed Ethernet FF-HSE network
5Segment coupler FF-HSE/FF-H1
6FOUNDATION Fieldbus FF-H1 network
7Power supply FF-H1 network
8T-box
9Measuring device
Via PROFIBUS PA network
This communication interface is present in the following device version:
Order code for "Output", option G: PROFIBUS PA
1Automation system
2Segment coupler PROFIBUS DP/PA
3Computer with PROFIBUS network card
4PROFIBUS DP network
5PROFIBUS PA network
6Measuring device
7T-box
A0019013
Endress+Hauser59
Page 60
Service interfaceService interface (CDI)
12
3
+
E
–
1Service interface (CDI = Endress+Hauser Common Data Interface) of the measuring device
2Commubox FXA291
3Computer with "FieldCare" operating tool with COM DTM "CDI Communication FXA291"
Proline Prowirl C 200
A0020545
C-Tick symbol
Ex approval
Certificates and approvals
The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
The measuring device is certified for use in hazardous areas and the relevant safety instructions are
provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on
the nameplate.
The separate Ex documentation (XA) containing all the relevant explosion protection data is
available from your Endress+Hauser sales center.
cCSAus
Currently, the following versions for use in hazardous areas are available:
XP
CategoryType of protection
Class I, II, III Division 1 Groups A-GXP (Ex d Flameproof version)
IS
CategoryType of protection
Class I, II, III Division 1 Groups A-GIS (Ex i Intrinsically safe version)
NI
CategoryType of protection
Class I Division 2 Groups ABCDNI (Non-incentive version), NIFW-Parameter*
*= Entity- und NIFW-Parameter gemäß Control Drawings
60Endress+Hauser
Page 61
Proline Prowirl C 200
Functional safety
FOUNDATION Fieldbus
certification
Certification PROFIBUSPROFIBUS interface
Experience
The measuring device can be used for flow monitoring systems (min., max., range) up to SIL 2
(single-channel architecture) and SIL 3 (multichannel architecture with homogeneous redundancy)
and is independently evaluated and certified by the TÜV in accordance with IEC 61508.
The following types of monitoring in safety equipment are possible:
Volume flow
Functional Safety Manual with information on the SIL device (→ 66)
FOUNDATION Fieldbus interface
The measuring device is certified and registered by the Fieldbus FOUNDATION. The measuring
system meets all the requirements of the following specifications:
• Certified in accordance with FOUNDATION Fieldbus H1
• Interoperability Test Kit (ITK), revision version 6.1.1 (certificate available on request)
• Physical Layer Conformance Test
• The device can also be operated with certified devices of other manufacturers (interoperability)
The measuring device is certified and registered by the PROFIBUS User Organization (PNO). The
measuring system meets all the requirements of the following specifications:
• Certified in accordance with PROFIBUS PA Profile 3.02
• The device can also be operated with certified devices of other manufacturers (interoperability)
The Prowirl 200 measuring system is the official successor to Prowirl 72 and Prowirl 73.
Other standards and
guidelines
• EN 60529
Degrees of protection provided by enclosures (IP code)
• DIN ISO 13359
Measurement of conductive liquid flow in closed conduits - Flanged-type electromagnetic
flowmeters - Overall length
• EN 61010-1
Safety requirements for electrical equipment for measurement, control and laboratory use
• IEC/EN 61326
Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC
requirements).
• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment
• NAMUR NE 32
Data retention in the event of a power failure in field and control instruments with
microprocessors
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with
analog output signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics
• NAMUR NE 105
Specifications for integrating fieldbus devices in engineering tools for field devices
• NAMUR NE 107
Self-monitoring and diagnosis of field devices
• NAMUR NE 131
Requirements for field devices for standard applications
• ASME BPVC Section VIII, Division 1
Rules for Construction of Pressure Vessels
Endress+Hauser61
Page 62
Proline Prowirl C 200
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser web site: www.endress.com → Choose your
country → Products → Select measuring technology, software or components → Select product
(picklists: measurement method, product family etc.) → Device support (right-hand column):
Configure the selected product → The Product Configurator for the selected product is opened.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Application packages
Many different application packages are available to enhance the functionality of the device. Such
packages might be needed to address safety aspects or specific application requirements.
The application packages can be ordered from Endress+Hauser either directly with the device or
subsequently. Detailed information on the order code in question is available from your local Endress
+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
Detailed information on the application packages:
Special Documentation on the device (→ 67)
Diagnostics functions
Heartbeat Technology
PackageDescription
HistoROM extended
function
PackageDescription
Heartbeat VerificationHeartbeat Verification:
Comprises extended functions concerning the event log and the activation of the
measured value memory.
Event log:
Memory volume is extended from 20 message entries (basic version) to up to 100
entries.
Data logging (line recorder):
• Memory capacity for up to 1000 measured values is activated.
• 250 measured values can be output via each of the 4 memory channels. The
recording interval can be defined and configured by the user.
• Data logging is visualized via the local display or FieldCare.
Makes it possible to check the device functionality on demand when the device is
installed, without having to interrupt the process.
• Access via onsite operation or other operating interfaces, such as FieldCare for
instance.
• Documentation of device functionality within the framework of manufacturer
specifications, for proof testing for instance.
• End-to-end, traceable documentation of the verification results, including report.
• Makes it possible to extend calibration intervals in accordance with operator's
risk assessment.
62Endress+Hauser
Page 63
Proline Prowirl C 200
Air and industrial gases
Natural gas
PackageDescription
Air and industrial gasesThis application package enables users to calculate the density and energy of air
and industrial gases. The calculations are based on time-tested standard
calculation methods. It is possible to automatically compensate for the effect of
pressure and temperature via an external or constant value.
With this application package it is possible to output the energy flow, standard
volume flow and mass flow of the following fluids:
• Air
• Single gas
• Gas mixture
• User-specific gas
PackageDescription
Natural gasThis application package enables users to calculate the chemical properties (gross
calorific value, net calorific value) of natural gases. The calculations are based on
time-tested standard calculation methods. It is possible to automatically
compensate for the effect of pressure and temperature via an external or constant
value.
With this application package it is possible to output the energy flow, standard
volume flow and mass flow based on the following standard methods:
Energy can be calculated based on the following standards:
• AGA5
• ISO 6976
• GPA 2172
Density can be calculated based on the following standards:
• ISO 12213-2 (AGA8-DC92)
• ISO 12213-3
• AGA NX19
• AGA8 Gross 1
• SGERG 88
Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are
available for the device. Detailed information on the order code in question is available from your
local Endress+Hauser sales center or on the product page of the Endress+Hauser website:
www.endress.com.
Device-specific accessoriesFor the transmitter
AccessoriesDescription
Prowirl 200 transmitterTransmitter for replacement or for stock. Use the order code to define the following
specifications:
• Approvals
• Output
• Display / operation
• Housing
• Software
For details, see Installation Instructions EA01056D
Endress+Hauser63
Page 64
Proline Prowirl C 200
Remote display
FHX50
FHX50 housing to accommodate a display module (→ 58).
• Length of connecting cable: up to max. 60 m (196 ft)
(cable lengths available for order: 5 m (16 ft), 10 m (32 ft), 20 m (65 ft),
30 m (98 ft))
The measuring device can be ordered with the FHX50 housing and a display
module. The following options must be selected in the separate order codes:
• Order code for measuring device, feature 030:
Option L or M "Prepared for FHX50 display"
• Order code for FHX50 housing, feature 050 (device version):
Option A "Prepared for FHX50 display"
• Order code for FHX50 housing, depends on the desired display module in feature
020 (display, operation):
– Option C: for an SD02 display module (push buttons)
– Option E: for an SD03 display module (touch control)
The FHX50 housing can also be ordered as a retrofit kit. The measuring device
display module is used in the FHX50 housing. The following options must be
selected in the order code for the FHX50 housing:
• Feature 050 (measuring device version): option B "Not prepared for FHX50
display"
Weather protection cover Is used to protect the measuring device from the effects of the weather: e.g.
Connecting cable for
remote version
Post mounting kitPost mounting kit for transmitter.
Ideally, the overvoltage protection module should be ordered directly with the
device. See product structure, characteristic 610 "Accessory mounted", option NA
"Overvoltage protection". Separate order necessary only if retrofitting.
• OVP10: For 1-channel devices (characteristic 020, option A):
• OVP20: For 2-channel devices (characteristic 020, options B, C, E or G)
For details, see Special Documentation SD01090F.
rainwater, excess heating from direct sunlight or extreme cold in winter.
For details, see Special Documentation SD00333F
• Connecting cable available in various lengths:
– 5 m (16 ft)
– 10 m (32 ft)
– 20 m (65 ft)
– 30 m (98 ft)
• Reinforced cables available on request.
Standard length: 5 m (16 ft)
Is always supplied if no other cable length has been ordered.
The post mounting kit can only be ordered together with a transmitter.
For the sensor
AccessoriesDescription
Inspection kitThe inspection kit comprises:
• 2 inspection centering sleeves
• 8 screws
• 2 inspection seals
• 2 inspection covers
For details, see Installation Instructions EA01058D
64Endress+Hauser
Page 65
Proline Prowirl C 200
Communication-specific
accessories
AccessoriesDescription
Commubox FXA195
HART
Commubox FXA291Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
HART Loop Converter
HMX50
Wireless HART adapter
SWA70
Fieldgate FXA320Gateway for the remote monitoring of connected 4-20 mA measuring devices via a
Fieldgate FXA520Gateway for the remote diagnostics and remote configuration of connected HART
Field Xpert SFX350Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
For intrinsically safe HART communication with FieldCare via the USB interface.
For details, see "Technical Information" TI00404F
Common Data Interface) and the USB port of a computer or laptop.
For details, see the "Technical Information" document TI405C/07
Is used to evaluate and convert dynamic HART process variables to analog current
signals or limit values.
For details, see "Technical Information" TI00429F and Operating Instructions
BA00371F
Is used for the wireless connection of field devices.
The WirelessHART adapter can be easily integrated into field devices and existing
infrastructures, offers data protection and transmission safety and can be operated
in parallel with other wireless networks with minimum cabling complexity.
For details, see Operating Instructions BA00061S
Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions
BA00053S
measuring devices via a Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions
BA00051S
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices in the non-Ex area.
For details, see Operating Instructions BA01202S
Service-specific accessories
Field Xpert SFX370Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices in the non-Ex area and the Ex area.
For details, see Operating Instructions BA01202S
AccessoriesDescription
ApplicatorSoftware for selecting and sizing Endress+Hauser measuring devices:
• Calculation of all the necessary data for identifying the optimum flowmeter: e.g.
nominal diameter, pressure loss, accuracy or process connections.
• Graphic illustration of the calculation results
Administration, documentation and access to all project-related data and
parameters over the entire life cycle of a project.
Applicator is available:
• Via the Internet: https://wapps.endress.com/applicator
• On CD-ROM for local PC installation.
Endress+Hauser65
Page 66
Proline Prowirl C 200
W@MLife cycle management for your plant
W@M supports you with a wide range of software applications over the entire
process: from planning and procurement, to the installation, commissioning and
operation of the measuring devices. All the relevant device information, such as
the device status, spare parts and device-specific documentation, is available for
every device over the entire life cycle.
The application already contains the data of your Endress+Hauser device. Endress
+Hauser also takes care of maintaining and updating the data records.
W@M is available:
• Via the Internet: www.endress.com/lifecyclemanagement
• On CD-ROM for local PC installation.
FieldCareFDT-based plant asset management tool from Endress+Hauser.
It can configure all smart field units in your system and helps you manage them. By
using the status information, it is also a simple but effective way of checking their
status and condition.
For details, see Operating Instructions BA00027S and BA00059S
System components
AccessoriesDescription
Memograph M graphic
display recorder
RN221NActive barrier with power supply for safe separation of 4-20 mA standard signal
RNS221Supply unit for powering two 2-wire measuring devices solely in the non-Ex area.
Cerabar MThe pressure transmitter for measuring the absolute and gauge pressure of gases,
Cerabar SThe pressure transmitter for measuring the absolute and gauge pressure of gases,
The Memograph M graphic display recorder provides information on all relevant
measured variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on a SD card or USB stick.
For details, see "Technical Information" TI00133R and Operating Instructions
BA00247R
circuits. Offers bidirectional HART transmission.
For details, see "Technical Information" TI00073R and Operating Instructions
BA00202R
Bidirectional communication is possible via the HART communication jacks.
For details, see "Technical Information" TI00081R and Brief Operating
Instructions KA00110R
steam and liquids. It can be used to read in the operating pressure value.
For details, see "Technical Information" TI00426P, TI00436P and Operating
Instructions BA00200P, BA00382P
steam and liquids. It can be used to read in the operating pressure value.
For details, see "Technical Information" TI00383P and Operating Instructions
BA00271P
Documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• The CD-ROM provided for the device (depending on the device version, the CD-ROM might
not be part of the delivery!)
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
2-D matrix code (QR code) on the nameplate.
Standard documentationBrief Operating Instructions