Direct current and alternating currentGround connection
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
Symbols for certain types of information
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Equipotential connection
A connection that has to be connected
to the plant grounding system: This
may be a potential equalization line
or a star grounding system depending
on national or company codes of
practice.
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
SymbolMeaningSymbolMeaning
1, 2, 3,...Item numbers
A, B, C, ...ViewsA-A, B-B, C-C, ... Sections
Hazardous area
Series of steps
Safe area (non-hazardous area)
Flow direction
Function and system design
Measuring principle
Endress+Hauser3
Vortex meters work on the principle of the Karman vortex street. When fluid flows past a bluff body,
vortices are alternately formed on both sides with opposite directions of rotation. These vortices each
generate a local low pressure. The pressure fluctuations are recorded by the sensor and converted to
Proline Prowirl C 200
K-Factor =
Pulses
Unit Volume [m³]
electrical pulses. The vortices develop very regularly within the permitted application limits of the
device. Therefore, the frequency of vortex shedding is proportional to the volume flow.
The calibration factor (K-factor) is used as the proportional constant:
A0019373
A0003939-EN
Within the application limits of the device, the K-factor only depends on the geometry of the device.
For Re > 20000 it is:
• Independent of the flow velocity and the fluid properties viscosity and density
• Independent of the type of substance under measurement: steam, gas or liquid
The primary measuring signal is linear to the flow. After production, the K-factor is determined in
the factory by means of calibration. It is not subject to long-time drift or zero-point drift.
The device does not contain any moving parts and does not require any maintenance.
The capacitance sensor
The sensor of a vortex flowmeter has a major influence on the performance, robustness and
reliability of the entire measuring system.
The robust DSC sensor is:
• burst-tested
• tested against vibrations
• tested against thermal shock (thermal shocks of 150 K/s)
The Prowirl uses the tried-and-tested capacitance measuring technology of Endress+Hauser applied
in over 300000 measuring points worldwide.
The DSC (differential switched capacitance) sensor patented by Endress+Hauser has complete
mechanical balancing. It only reacts to the measured variable (vortex) and does not react to
vibrations. Even in the event of pipe vibrations, the smallest of flows can be reliably measured at low
density thanks to the unimpaired sensitivity of the sensor. Thus, the wide turndown is also
maintained even in the event of harsh operating conditions. Vibrations up to 1 g at least, at
frequencies up to 500 Hz in every axis (X, Y, Z), do not affect the flow measurement. Thanks to its
design, the capacitance sensor is also particularly mechanically resistant to temperature shocks and
pressure shocks in steam pipelines.
Temperature measurement
Under the "Sensor version" order code the "Mass flow" option is available(→ 4). With this option
the measuring device can also measure the temperature of the medium.
The temperature is measured via Pt 1000 temperature sensors. These sensors are located in the
paddle of the DSC sensor and are therefore in the direct vicinity of the fluid.
Experience has shown that recalibrated Prowirl devices demonstrate a very high degree of stability
compared to their original calibration: The recalibration values were all within the original
measuring accuracy specifications of the devices.
Various tests and simulation procedures carried out on devices by filing away the edges of Prowirl’s
bluff body found that there was no negative impact on the accuracy up to a rounding diameter of
1 mm (0.04 in).
If the meter’s edges do not show rounding at the edges that exceeds 1 mm (0.04 in), the following
general statements apply (for non-abrasive and non-corrosive media, such as in most water and
steam applications):
• The measuring device does not display an offset in the calibration and the accuracy is still
guaranteed.
• All the edges on the bluff body have a radius that is typically smaller in size. As the measuring
devices are naturally also calibrated with these radii, the measuring device remains within the
specified accuracy rating provided that the additional radius that is produced as a result of wear
and tear does not exceed 1 mm (0.04 in).
Consequently it can be said that the Prowirl product line offers lifelong calibration if the measuring
device is used in non-abrasive and non-corrosive media.
Diagnostic functions
In addition, the device offers extensive diagnostic options, such as tracking fluid and ambient
temperatures, extreme flows etc.
The following minimum and maximum values are tracked in the measuring device and saved for
diagnostic purposes:
• Frequency
• Temperature
• Velocity
• Pressure
Inspection concept
According to the requirements of the ERCB (Canada), in certain applications the owner-operator of a
plant is required to maintain a servicing interval of 12 months.
The condition of the primary measurement element must be checked during these servicing
activities. The aim is to be able to ensure a repeatable measurement. Maintenance can be either by
way of visual inspection or in line with the recommendations of the equipment manufacturer.
Endress+Hauser5
Proline Prowirl C 200
With its unique inspection concept for Prowirl C 200 Endress+Hauser has developed a solution that
makes it possible to:
• meet these requirements
• perform maintenance on the installed device
• perform a visual inspection
• deliver an opinion about the measurement quality by measuring the edges of the bluff body.
This inspection concept is available via the order code "Sensor option", option CR "ERCB Dir. 017
inspection ports".
Detailed information on the inspection kit (→ 37)
For detailed information on the inspection ports, see the Special Documentation for the device
(→ 67)
6Endress+Hauser
Proline Prowirl C 200
Measuring system
The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version - the transmitter and sensor form a mechanical unit.
• Remote version – the transmitter and sensor are mounted separately from one another.
Transmitter
Prowirl 200Device versions and materials:
Compact or remote version, aluminum coated:
Aluminum, AlSi10Mg, coated
Configuration:
• Via four-line local display with key operation or via four-line,
illuminated local display with touch control and guided menus ("Make-
A0013471
it-run" wizards) for applications
• Via operating tools (e.g. FieldCare)
Sensor
Prowirl CCarbon steel flanged version for use with process pressures, Class 600/
– Process connections: carbon steel, multiple certifications, SA-105,
A0020335
SA-350 LF2 (1)
• Order code for "Sensor option":
ERCB Dir. 017, version with inspection ports
• Also available as butt-weld version
Input
Measured variableDirect measured variables
Order code for "Sensor version":
Option 4 "Volume flow, Alloy 718":
Volume flow
Order code for "Sensor version":
Option 6 "Mass flow, Alloy 718":
– Volume flow
– Temperature
Calculated measured variables
Order code for "Sensor version":
Option 4 "Volume flow, Alloy 718":
– In the case of constant process conditions: Mass flow
– The totalized values for Volume flow, Mass flow, or Corrected volume flow
Order code for "Sensor version":
Option 6 "Mass flow, Alloy 718":
– Corrected volume flow
– Mass flow
– Calculated saturated steam pressure
– Energy flow
– Heat flow difference
– Specific volume
– Degrees of superheat
1)
or Corrected volume flow
1)A fixed density must be entered for calculating the mass flow (Setup menu → Advanced setup submenu → External compensation submenu →
Fixed density parameter).
Endress+Hauser7
Proline Prowirl C 200
Re
=
4 · Q·m³[m³/s][kg/]ρ
di [m] · µπ π ·[Pa·s]
Re
=
4 · Q·³[ft³/s][lb/ft ]ρ
di [ft] · µπ ·[0.001 cP]
v
DN 2...6" →
=
min.
4.92
ρ [lb/ft³]
[ft/s]
v
DN 50...150 →=
min.
6
ρ [kg/m³]
[m/s]
Measuring range
The measuring range depends on the fluid and nominal diameter.
Lower range value
Depends on the density and the Reynolds number (Re
= 5000, Re
min
= 20000). The Reynolds
linear
number is dimensionless and indicates the ratio of the inertia force of a fluid to its viscous force. It is
used to characterize the flow. The Reynolds number is calculated as follows:
A0003794
Re = Reynolds number; Q = flow; di = internal diameter; µ = dynamic viscosity, ρ = density
A0020558
Upper range value
Liquids:
The upper range value must be calculated as follows:
v
= 9 m/s (30 ft/s) and v
max
Use the lower value.
‣
= 350/√ρ m/s (130/√ρ ft/s)
max
Gas/steam:
Nominal diameterv
Standard device: DN 50 to 150 (2 to 6")120 m/s (394 ft/s) and 350/√ρ m/s (130/√ρ ft/s)
max
(Use the lower value.)
Calibrated range: up to 75 m/s (246 ft/s)
For information about the Applicator (→ 65)
Operable flow range
Up to 45: 1 (ratio between lower and upper range value)
Input signalExternal measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure
measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
• Various pressure transmitters can be ordered from Endress+Hauser: see "Accessories" section
(→ 66)
• Please comply with the special mounting instructions when using pressure transmitters
(→ 37)
It is recommended to read in external measured values to calculate the following measured variables:
• Energy flow
• Mass flow
• Corrected volume flow
8Endress+Hauser
Proline Prowirl C 200
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Current input
The measured values are written from the automation system to the measuring device via the
current input.
Fieldbuses
The measured values can be written from the automation system to the measuring via:
• PROFIBUS PA
• FOUNDATION Fieldbus
Current input
Current input4 to 20 mA (passive)
Resolution1 µA
Voltage dropTypically: 2.2 to 3 V for 3.6 to 22 mA
Maximum voltage≤ 35 V
Possible input variables• Pressure
• Temperature
• Density
Output
Output signalCurrent output
Current output 14-20 mA HART (passive)
Current output 24-20 mA (passive)
Resolution<1 µA
DampingAdjustable: 0.0 to 999.9 s
Assignable measured
variables
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionPassive, open collector
Maximum input values• DC 35 V
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
• 50 mA
For information on the Ex connection values (→ 12)
Voltage drop• For ≤2 mA: 2 V
• For 10 mA: 8 V
Endress+Hauser9
Residual current≤0.05 mA
Pulse output
Pulse widthAdjustable: 5 to 2000 ms
Maximum pulse rate100 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Output frequencyAdjustable: 0 to 1000 Hz
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
Switch output
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
Number of switching
cycles
Assignable functions• Off
• Total volume flow
• Total corrected volume flow
• Total mass flow
• Total energy flow
• Total heat flow difference
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Unlimited
• On
• Diagnostic behavior
• Limit value
– Volume flow
– Corrected volume flow
– Mass flow
– Flow velocity
– Temperature
– Calculated saturated steam pressure
– Steam quality
– Total mass flow
– Energy flow
– Heat flow difference
– Reynolds number
– Totalizer 1-3
• Status
• Status of low flow cut off
Proline Prowirl C 200
FOUNDATION Fieldbus
Signal encodingManchester Bus Powered (MBP)
Data transfer31.25 KBit/s, Voltage mode
10Endress+Hauser
Proline Prowirl C 200
PROFIBUS PA
Signal encodingManchester Bus Powered (MBP)
Data transfer31.25 KBit/s, Voltage mode
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
HART
Device diagnosticsDevice condition can be read out via HART Command 48
Pulse/frequency/switch output
Pulse output
Failure modeNo pulses
Frequency output
Failure modeChoose from:
• Actual value
• Defined value: 0 to 1250 Hz
• 0 Hz
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-912
0 mA
PROFIBUS PA
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
Local display
Plain text displayWith information on cause and remedial measures
BacklightAdditionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Endress+Hauser11
Operating tool
0
100
200
300
400
500
121416
1820
22242628
U [V]
s
R [ ]bW
1.11.21
30323436
35
• Via digital communication:
– HART protocol
– FOUNDATION Fieldbus
– PROFIBUS PA
• Via service interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation (→ 58)
Proline Prowirl C 200
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply
unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage (→ 22)
• RB ≤ (US - U
term. min
) :0.022 A
• RB ≤500 Ω
A0020417
2Load for a compact version without local operation
1Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i and option C "4-20 mA HART, 4-20 mA"
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with non-Ex and Ex d
Sample calculation
Supply voltage of the supply unit:
– US = 19 V
– U
= 12 V (measuring device) + 1 V (local operation without lighting) = 13 V
term. min
Maximum load: RB≤ (19 V - 13 V) :0.022 A = 273 Ω
The minimum terminal voltage (U
) increases if local operation is used (→ 23).
term. min
Ex connection dataSafety-related values
12Endress+Hauser
Proline Prowirl C 200
Type of protection XP
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option C4-20mA HART
4-20mA
Option D4-20mA HARTU
Pulse/frequency/switch outputU
4 to 20 mA current inputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
nom
U
max
nom
U
max
P
max
U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 30 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= 1 W
= DC 35 V
= 250 V
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
IS type of protection
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option C4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Endress+Hauser13
Proline Prowirl C 200
Order code for "Output"Output typeIntrinsically safe values
4-20mA
Option D4-20mA HARTUi = DC 30 V
Pulse/frequency/switch outputUi = DC 30 V
4 to 20 mA current inputUi = DC 30 V
Option EFOUNDATION FieldbusSTANDARD
Pulse/frequency/switch outputUi = 30 V
Option GPROFIBUS PASTANDARD
Pulse/frequency/switch outputUi = 30 V
Ci = 30 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are user-selectable.
All outputs are galvanically isolated from one another.
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x38
HART protocol revision7
Device description files
(DTM, DD)
HART load• Min. 250 Ω
Information and files under:
www.endress.com
• Max. 500 Ω
14Endress+Hauser
Proline Prowirl C 200
Dynamic variablesRead out the dynamic variables: HART command 3
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Condensate mass flow
• Reynolds number
• Totalizer 1
• Totalizer 2
• Totalizer 3
• HART input
• Density
• Pressure
• Specific volume
• Degree of overheating
Device variablesRead out the device variables: HART command 9
The device variables are permanently assigned.
A maximum of 8 device variables can be transmitted:
• 0 = volume flow
• 1 = corrected volume flow
• 2 = Mass flow
• 3 = flow velocity
• 4 = temperature
• 5 = calculated saturated steam pressure
• 6 = steam quality
• 7 = total mass flow
• 8 = energy flow
• 9 = heat flow difference
• 10 = condensate mass flow
• 11 = Reynolds number
• 12 = totalizer 1
• 13 = totalizer 2
• 14 = totalizer 3
• 15 = HART input
• 16 = density
• 17 = pressure
• 18 = specific volume
• 19 = degree of overheating
FOUNDATION Fieldbus
Manufacturer ID0x452B48
Ident number0x1038
Device revision1
Endress+Hauser15
DD revisionInformation and files under:
CFF revision
Device Tester Version (ITK
version)
ITK Test Campaign NumberIT094200
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Max. response delayMin. 5
• www.endress.com
• www.fieldbus.org
6.1.1
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
Proline Prowirl C 200
Transducer Blocks
BlockContentsOutput values
Setup Transducer Block
(TRDSUP)
Advanced Setup
Transducer Block
(TRDASUP)
Display Transducer
Block
(TRDDISP)
HistoROM Transducer
Block
(TRDHROM)
All parameters for standard commissioning.No output values
All parameters for more accurate measurement
configuration.
Parameters for configuring the local display.No output values
Parameters for using the HistoROM function.No output values
Parameters that require the user to have indepth knowledge of the operation of the device
in order to configure the parameters
appropriately.
Parameters that provide information about the
state of the device.
Parameters that can only be accessed by Endress
+Hauser Service.
Parameters that provide Endress+Hauser Service
with information about the state of the device.
Parameters for configuring all the totalizers and
the inventory counter.
Parameters for the configuration and
comprehensive information about the results of
the verification.
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
No output values
No output values
No output values
No output values
Process variables (AI Channel)
• Totalizer 1 (16)
• Totalizer 2 (17)
• Totalizer 3 (18)
No output values
Endress+Hauser17
Function blocks
Proline Prowirl C 200
BlockNumber
of
blocks
Resource Block
(RB)
Analog Input
Block
(AI)
Discrete Input
Block
(DI)
PID Block
(PID)
Multiple Analog
Output Block
(MAO)
1This Block (extended functionality) contains
4This Block (extended functionality) receives
1This Block (standard functionality) receives a
1This Block (standard functionality) acts as a
1This Block (standard functionality) receives
ContentsProcess variables (Channel)
–
all the data that uniquely identify the device; it
is the equivalent of an electronic nameplate
for the device.
• Temperature (7)
the measurement data provided by the Sensor
Block (can be selected via a channel number)
and makes the data available for other blocks
at the output.
Execution time: 13 ms
discrete value (e.g. indicator that measuring
range has been exceeded) and makes the
value available for other blocks at the output.
Execution time: 12 ms
proportional-integral-differential controller
and can be used universally for control in the
field. It enables cascading and feedforward
control.
Execution time: 13 ms
several analog values and makes them
available for other blocks at the output.
Execution time: 11 ms
• Mass flow (11)
• Volume flow (9)
• Corrected volume flow (13)
• Flow velocity (37)
• Energy flow (38)
• Calculated saturated steam
pressure (45)
• Total mass flow (46)
• Condensate mass flow (47)
• Steam quality (48)
• Heat flow difference (49)
• Reynolds number (50)
• Status switch output (101)
• Low flow cutoff (103)
• Status verification (105)
–
Channel_0 (121)
• Value 1: External
compensation variables
(pressure, gage pressure,
density, temperature or
second temperature)
• Value 2 to 8: Not assigned
The compensation
variables must be
transmitted to the device
in the SI basic unit.
18Endress+Hauser
Proline Prowirl C 200
BlockNumber
of
blocks
Multiple Digital
Output Block
(MDO)
Integrator Block
(IT)
1This Block (standard functionality) receives
1This Block (standard functionality) integrates
PROFIBUS PA
ContentsProcess variables (Channel)
Channel_DO (122)
several discrete values and makes them
available for other blocks at the output.
Execution time: 14 ms
a measured variable over time or totalizes the
pulses from a Pulse Input Block. The Block can
be used as a totalizer that totalizes until a
reset, or as a batch totalizer whereby the
integrated value is compared against a target
value generated before or during the control
routine and generates a binary signal when
the target value is reached.
Execution time: 16 ms
• Value 1: Reset totalizer 1
• Value 2: Reset totalizer 2
• Value 3: Reset totalizer 3
• Value 4: Flow override
• Value 5: Start heartbeat
verification
• Value 6: Status switch output
• Value 7: Not assigned
• Value 8: Not assigned
–
Manufacturer ID0x11
Ident number0x1564
Profile version3.02
Device description files (GSD,
DTM, DD)
Output values
(from measuring device to
automation system)
Input values
(from automation system to
measuring device)
Information and files under:
• www.endress.com
• www.profibus.org
Analog input 1 to 4
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Pressure
• Specific volume
• Degree of overheating
Digital input 1 to 2
• Status
• Low flow cut off
• Switch output
Totalizer 1 to 3
• Mass flow
• Volume flow
• Corrected volume flow
Analog output
External pressure, gage pressure, density, temperature or second temperature
(for delta heat measurement)
Digital output 1 to 3 (fixed assignment)
• Digital output 1: switch positive zero return on/off
• Digital output 2: switch switch output on/off
• Digital output 3: Start verification
Totalizer 1 to 3
• Totalize
• Reset and hold
• Preset and hold
Endress+Hauser19
Supported functions• Identification & Maintenance
–
4
+
1
–
2
+
3
1
2
4
–
6
+
5
3
+
1
–
2
–
4
+
3
–
6
+
5
3
1
2
4
Configuration of the device
address
Power supply
Terminal assignmentTransmitter
Connection versions
Proline Prowirl C 200
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e.g. FieldCare)
A0020738
Maximum number of terminals
Terminals 1 to 6:
Without integrated overvoltage protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Input (passive): supply voltage and signal transmission
4
Ground terminal for cable shield
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
Option A4-20 mA HART (passive)--
Option B
Option C
Option D
1)
1)
1) 2)
4-20 mA HART (passive)
4-20 mA HART (passive)4-20 mA (passive)-
4-20 mA HART (passive)
Maximum number of terminals for order code for
"Accessory mounted", option NA "Overvoltage
protection"
• Terminals 1 to 4:
With integrated overvoltage protection
• Terminals 5 to 6:
Without integrated overvoltage protection
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
A0020739
-
4-20 mA current input
(passive)
20Endress+Hauser
Proline Prowirl C 200
4
1
2
3
1
2
+
–
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
1) 3)
Option E
Option G
1)Output 1 must always be used; output 2 is optional.
2)The integrated overvoltage protection is not used with option D: Terminals 5 and 6 (current input) are not
protected against overvoltage.
3)FOUNDATION Fieldbus with integrated reverse polarity protection.
4)PROFIBUS PA with integrated reverse polarity protection.
1) 4)
FOUNDATION Fieldbus
PROFIBUS PA
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
-
-
Remote version
In the case of the remote version, the sensor and transmitter are mounted separately from one
another and connected by a connecting cable. The sensor is connected via the connection housing
while the transmitter is connected via the connection compartment of the wall holder unit.
The way the transmitter wall holder is connected depends on the measuring device approval
and the version of the connecting cable used.
Connection is only possible via terminals:
• For approvals Ex n, Ex tb and cCSAus Div. 1
• If a reinforced connecting cable is used
The connection is via an M12 connector:
• For all other approvals
• If the standard connecting cable is used
Connection to the connection housing of the sensor is always via terminals.
A0019335
3Terminals for connection compartment in the transmitter wall holder and the sensor connection housing
1Terminals for connecting cable
2Grounding via the cable strain relief
Terminal numberAssignmentCable color
Connecting cable
1Supply voltageBrown
2GroundingWhite
3RS485 (+)Yellow
4RS485 (–)Green
Endress+Hauser21
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.