The measuring device described in these Operating Instructions is to be used only for measuring the
flow rate of liquids in closed pipes, e.g.:
• Acids, alkalis, paints, oils
• Liquefied gas
• Ultrapure water with a low conductivity, water, wastewater
In addition to measuring the volume flow, the measuring device also always measures the sound
velocity of the fluid. In this way, different fluids can be distinguished or the fluid quality can be
monitored.
Resulting from incorrect use or from use other than that designated the operational safety of the
measuring devices can be suspended. The manufacturer accepts no liability for damages being
produced from this.
1.2Installation, commissioning and operation
Note the following points:
• Installation, connection to the electricity supply, commissioning and maintenance of the device
must be carried out by trained, qualified specialists authorized to perform such work by the
facility's owner operator. The specialist must have read and understood these Operating
Instructions and must follow the instructions they contain.
• The device must be operated by persons authorized and trained by the facility's owner-operator.
Strict compliance with the instructions in these Operating Instructions is mandatory.
• In the case of special fluids (incl. fluids for cleaning), Endress+Hauser will be happy to assist in
clarifying the corrosion resistance properties of wetted materials. Slight changes to the
temperature, concentration or degree of contamination in the process can, however, alter the
corrosion resistance. Consequently, Endress+Hauser does not accept any guarantee or liability
with regard to the corrosion resistance of wetted materials in a specific application. The user is
responsible for the choice of suitable wetted materials in the process.
• If carrying out welding work on the piping, the welding unit may not be grounded by means of
the measuring device.
• The installer must ensure that the measuring system is correctly wired in accordance with the
wiring diagrams. The transmitter must be grounded, unless the power supply is galvanically
isolated.
• Invariably, local regulations governing the opening and repair of electrical devices apply.
1.3Operational safety
• Measuring systems for use in hazardous environments are accompanied by separate "Ex
documentation", which is an integral part of these Operating Instructions. Strict compliance with
the installation instructions and ratings as listed in this supplementary documentation is
mandatory. The symbol on the front of this supplementary Ex documentation indicates the
approval and the inspection authority (0 Europe, 2 USA, 1 Canada).
• The measuring device complies with the general safety requirements in accordance with EN 61010,
the EMC requirements of IEC/EN 61326 and NAMUR recommendations NE 21 and NE 43.
• The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser distributor will supply you with current information and updates to these
Operating Instructions.
Endress+Hauser5
Safety instructionsProline Prosonic Flow 92F
1.4Return
• Do not return a measuring device if you are not absolutely certain that all traces of hazardous
substances have been removed, e.g. substances which have penetrated crevices or diffused
through plastic.
• Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be
charged to the owner-operator.
• Please note the measures on → ä 58
1.5Notes on safety conventions and icons
The devices are designed to meet state-of-the-art safety requirements, have been tested, and left the
factory in a condition in which they are safe to operate. The devices comply with the applicable
standards and regulations in accordance with EN 61010 "Protection Measures for Electrical
Equipment for Measurement, Control, Regulation and Laboratory Procedures". The devices can,
however, be a source of danger if used incorrectly or for anything other than the designated use.
Consequently, always pay particular attention to the safety instructions indicated in these Operating
Instructions by the following symbols:
#
Warning!
"Warning" indicates an action or procedure which, if not performed correctly, can result in injury
or a safety hazard. Comply strictly with the instructions and proceed with care.
"
!
Caution!
"Caution" indicates an action or procedure which, if not performed correctly, can result in incorrect
operation or destruction of the device. Comply strictly with the instructions.
Note!
"Note" indicates an action or procedure which, if not performed correctly, can have an indirect
effect on operation or trigger an unexpected response on the part of the device.
6Endress+Hauser
Proline Prosonic Flow 92FIdentification
N12895
Prosonic Flow 92
ABCDEFGHJKLMNPQRST
TAGNo.:
Ser.No.:
12345678901
Order Code:
i
IP67 / NEMA/Type4X
-40°F<Ta<+140°F
Ta+10°C/18°F
92FXX-XXXXXXXXXXX
12-35VDC
4...20mA, HART
1.2W
-40°C<Ta<+60°C
1
2
4
5
3
2Identification
2.1Device designation
The "Prosonic Flow 92" flowmeter system consists of the following components:
• Prosonic Flow 92 transmitter
• Prosonic Flow F Inline sensor
Two versions are available:
• Compact version: transmitter and sensor form a single mechanical unit.
• Remote version: transmitter and sensor are installed separately.
2.1.1Nameplate of the transmitter
a0006111
Fig. 1: Nameplate specifications for the "Prosonic Flow" transmitter (example)
1Order code / serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits
2Power supply: 12 to 35 V DC
Power consumption: 1.2 W
3Available outputs
4Permitted ambient temperature range
5Degree of protection
Endress+Hauser7
IdentificationProline Prosonic Flow 92F
2
3
4
5
1
7
6
Switzerland
4153 Reinach
-40°C <Tamb< +80°C
-40° <TambF< +176°F
IP67 / NEMA/Type4X
5P-CAL
TM:
-40°C(-40°F)...+150°C(+302°F)
CF3M / 1.4404 / F316L / F316
Materials:
DN100/4" DIN/EN PN16
1.000/0000
K-factor:
XXXXXXXXXXX
Ser.No.:
Order Code:
Prosonic Flow F
92FXX-XXXXXXXXXXXXX
N12895
i
8
Connector
Plug
Observer manuel d'Instruction.
4..20mA
max. 36VDC
max. 36VDC
max. 15mA
Optional
Betriebsanleitung beachten.
See operating manual.
1
3
4
2
Do not sep rate when energized!a
ATEXII3G / Zone 2:
2.1.2Nameplate of the sensor
a0006107
Fig. 2: Nameplate specifications for the Prosonic Flow F sensor (example)
1Order code/serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits
2Calibration factor with zero point
3Device nominal diameter/nominal pressure
4Measuring tube material
5Medium temperature range
6Degree of protection
7Permitted ambient temperature range
8Additional information (examples):
– 5P-CAL: with 5-point calibration
2.1.3Nameplate for connections
Fig. 3: Nameplate specifications for Proline transmitter (example)
8Endress+Hauser
a0006110
Proline Prosonic Flow 92FIdentification
2.2Certificates and approvals
The devices are designed in accordance with good engineering practice to meet state-of-the-art
safety requirements, have been tested, and left the factory in a condition in which they are safe to
operate.
The measuring device complies with the general safety requirements in accordance with EN 61010,
the EMC requirements of IEC/EN 61326 and NAMUR recommendations NE 21 and NE 43.
The measuring system described in these Operating Instructions thus complies with the statutory
requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by
affixing to it the CE mark.
The measuring system complies with the EMC requirements of the Australian Communications and
Media Authority (ACMA).
!
Note!
A detailed list of all the certificates and approvals is provided in the technical data on Page 66.
2.3Registered trademarks
HART®
Registered trademark of the HART Communication Foundation, Austin, USA
®
HistoROM™ T-DAT
Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH
On receipt of the goods, check the following points:
• Check the packaging and the contents for damage.
• Check the shipment, make sure nothing is missing and that the scope of supply matches your
order.
3.1.2Transport
Please note the following when unpacking or transporting to the measuring point:
• The devices must be transported in the container supplied.
• The covers or caps fitted to the process connections prevent mechanical damage to the sealing
faces and the ingress of foreign matter to the measuring tube during transportation and storage.
Consequently, do not remove these covers or caps until immediately before installation.
• Devices with nominal diameters > DN 40 (> 1½") may not be lifted at the transmitter housing or
at the connection housing of the remote version when transporting. Use carrier slings when
transporting and put the slings around both process connections. Avoid chains as these could
damage the housing.
#
Warning!
Risk of injury if the measuring device slips. The center of gravity of the entire measuring device
might be higher than the points around which the slings are slung.
Therefore, when transporting, make sure that the device does not unintentionally turn or slip.
a0005765
Fig. 4: Instructions for transporting sensors with a nominal diameter > DN 40 (> 1½")
3.1.3Storage
Note the following points:
• Pack the measuring device in such a way as to protect it reliably against impact for storage (and
transportation). The original packaging provides optimum protection.
• The permissible storage temperature is –40 to +80 °C (–40 °F to 176 °F),
preferably +20 °C (68 °F).
• Do not remove the protective covers or caps on the process connections until you are ready to
install the device.
• The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
10Endress+Hauser
Proline Prosonic Flow 92FInstallation
1
2
3
4
5
3.2Installation conditions
Note the following points:
• No special measures such as supports are necessary. External forces are absorbed by the
construction of the instrument.
• The flowmeter flanges must be coplanar with connecting flanges and free from tension.
• The maximum permitted ambient temperatures (→ ä 63) and fluid temperatures (→ ä 63)
must be observed.
• Pay particular attention to the notes on orientation and piping insulation on the following pages.
• The correct operation of the measuring system is not influenced by pipe vibrations.
3.2.1Dimensions
All the dimensions and lengths of the sensor and transmitter are provided in the separate
documentation "Technical Information". → ä 67
3.2.2Mounting location
Accumulated gas bubbles in the measuring tube can result in measuring errors.
Avoid the following locations:
• Highest point of a pipeline. Risk of gas accumulating.
• Directly upstream of a free pipe outlet in a vertical pipeline.
a0006081
Fig. 5: Mounting location
The proposed configuration in the following diagram, however, permits installation in a vertical
pipeline. Pipe restrictors or the use of an orifice plate with a smaller cross section than the nominal
diameter prevent the sensor from running empty during measurement.
Fig. 6: Installation in a vertical pipe (e.g. for batching applications)
No additional pressure loss results from installing the device. It is important to ensure that cavitation
or degassing does not occur at fittings upstream from the measuring device as this can affect sound
transmission in the fluid.
No special measures need to be taken for fluids which have properties similar to water under normal
conditions.
In the case of liquids with a low boiling point (hydrocarbons, solvents, liquefied gases) or in suction
lines, it is important to ensure that pressure does not drop below the vapor pressure and that the
liquid does not start to boil. It is also important to ensure that the gases that occur naturally in many
liquids do not outgas. Such effects can be prevented when system pressure is sufficiently high.
For this reason, preference should be given to the following mounting locations:
• Downstream from pumps (no danger of vacuum)
• At the lowest point in a vertical pipe
3.2.3Orientation
Make sure that the direction of the arrow on the nameplate of the sensor matches the direction of
flow (direction in which the fluid flows through the pipe).
Fig. 7: Orientations A, B and C recommended, orientation D only recommended under certain circumstances
3.2.4Heating
Some fluids require heat to be transfered at the sensor. Heating can be electric, e.g. with heated
elements, or by hot water or steam.
Caution!
"
• Danger of electronics overheating!
Make sure that the adapter between the sensor and transmitter and the connection housing of
the remote version always remain free of insulating material.
• When using electrical heat tracing whose heat is regulated using phase control or by pulse packs,
it cannot be ruled out that the measured values are influenced by magnetic fields which may
occur, (i.e. at values greater than those permitted by the EC standard (Sinus 30 A/m)). In such
cases, the sensor must be magnetically shielded.
a0005971
12Endress+Hauser
Proline Prosonic Flow 92FInstallation
max. 20 (0.8)
max. 20 (0.8)
mm (inch)
2
A
1
3
A
A
4
A
5DN×
10 DN×
B
3 DN×
15 DN×
5 × DN
B
3 DN×
B
3 DN×
B
3 DN×
3.2.5Thermal insulation
Some fluids require suitable measures to avoid loss of heat at the sensor. A wide range of materials
can be used to provide the required thermal insulation.
a0005763-ae
Fig. 8: A maximum insulation thickness of 20 mm (0.8 inch) must be observed in the area of the electronics/neck.
If the device is installed horizontally (with transmitter head pointing upwards), an insulation
thickness of min. 10 mm (0.4") is recommended to reduce convection. The maximum insulation
thickness of 20 mm (0.8") must not be exceeded.
3.2.6Inlet and outlet run
If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc. As a
minimum, the inlet and outlet runs shown below must be observed to achieve the specified
accuracy of the device. The longest inlet run shown must be observed if two or more flow
disturbances are present.
A0006267
Fig. 9: Minimum inlet and outlet runs with various flow obstructions (values given for 3 and 4 pathversions)
A = Inlet run, B = Outlet run, 1 = 90° elbow or T-piece, 2 = Pump, 3 = 2 × 90° elbow, 3-dimensional, 4 = Control valve
3.2.7Limiting flow
Information on limiting flow is provided under "Measuring range" in the technical data section.
Endress+Hauser13
InstallationProline Prosonic Flow 92F
180°
180°
3.3Installation instructions
3.3.1Mounting the sensor
• Prior to installing the measuring device in the piping, remove all traces of transport packaging and
any protective covers from the sensor.
• Make sure that the internal diameters of seals are the same as, or greater than, those of the
measuring device and piping. If seals with a smaller internal diameter are used, this affects the
flow and results in inaccurate measurement.
• Ensure that the arrow on the measuring tube matches the direction of flow in the piping.
• For Carbon steel option remove transport protection coating using mineral spirit (optional).
3.3.2Turning the transmitter housing
1.Loosen the safety screw.
2.Turn the transmitter housing to the desired position (max. 180° in each direction to the stop).
Note!
!
There are recesses in the rotating groove at 90° stages (only compact version).
These help you align the transmitter easier.
3.Retighten the securing screw.
Fig. 10: Turning the transmitter housing
3.3.3Turning the local display
1.Unscrew the cover of the electronics compartment from the transmitter housing.
2.Remove the display module from the transmitter retainer rails.
3.Turn the display to the desired position (max. 4 x 45° in each direction) and
reset it onto the retaining rails.
4.Screw the cover of the electronics compartment firmly back onto the transmitter housing.
a0005766
14Endress+Hauser
Proline Prosonic Flow 92FInstallation
ANSCHLUSSKLEMMEN - FIELD TERMINALS
ANSCHLUSSKLEMMEN - FIELD TERMINALS
AB
232 (9.13)
227 (8.94)
mm (inch)
*226 (*8.90)
*221 (*8.70)
3.3.4Mounting the remote version
The transmitter can be mounted in the following ways:
When mounting on a pipe, the ambient temperature range may not be exceeded.
→ ä 63
The transmitter and the sensor must be mounted separate in the following circumstances:
• Poor accessibility
• Lack of space
• Extreme ambient temperatures
Mount the transmitter as illustrated in the diagram.
Fig. 11: Mounting the transmitter (remote version)
ADirect wall mounting
BPipe mounting
* Dimensions for version without local display
3.4Post-installation check
Perform the following checks after installing the measuring device:
Device condition and specificationsNotes
Is the device damaged (visual inspection)?-
Do the process temperature/pressure, ambient temperature, measuring range etc. correspond to the
specifications of the device?
InstallationNotes
Does the arrow on the sensor or sensor neck match the direction of flow through the pipe?-
Are the measuring point number and labeling correct (visual inspection)?–
Process environment / process conditionsNotes
Is the measuring device protected against direct sunlight?-→ ä 63
→ ä 5
a0005947-ae
Endress+Hauser15
WiringProline Prosonic Flow 92F
a
c
b
d
1
G
1
GROUND
2
GROUND
2
G
1G2
G
1
GROUND
2
GROUND
3G
3
GROUND
4
GROUND
4 G
3
GROUND
4
GROUND
5G
5
GROUND
6
GROUND
6G
5
GROUND
6
GROUND
7
G
7
GROUND
8
GROUND
8G
7
GROUND
8
GROUND
3G
4
G5G6G7G8G
1
2
3
4
5
67
8
e
f
4Wiring
4.1Connecting the remote version
4.1.1Connecting cable for sensor/transmitter
!
Note!
• The remote version must be grounded. In doing so, the sensor and transmitter must be connected
to the same potential matching (see Fig. 12, d).
• You may only connect the sensor to the transmitter with the same serial number (see nameplate).
Communication errors can occur if this is not observed when connecting the devices.
Procedure
1.Remove the covers of the connection compartments (a/b).
2.Feed the connecting cable (c) through the appropriate cable entries.
3.Wire the sensor and transmitter in accordance with the electrical connection diagram:
see Fig. 12 or the wiring diagram in the cover of the connection compartment.
4.Connect the appropriate cable shield (e/f).
5.Firmly tighten the glands of the cable entries.
6.Screw the covers of the connection compartments (a/b) back on.
Fig. 12: Connecting the remote version
aCover of the connection compartment (transmitter)
bCover of the connection compartment (sensor)
cConnecting cable (signal cable)
dIdentical potential matching for sensor and transmitter
eConnect the shielding to the ground terminal in the transmitter housing and keep it as short as possible
fConnect the shielding to the ground terminal in the connection housing
4.1.2Cable specification for connecting cable
Only use the cables supplied by Endress+Hauser and pre-terminated at the factory. The cables are
16Endress+Hauser
available with a fixed length of 10 m (30 feet) and 30 m (90 feet) and optionally available with
variable lengths ranging from 1 m (3 feet) to max. 50 m (150 feet). The cable sheathing is made of
PVC.
a0005764
Proline Prosonic Flow 92FWiring
4.2Connecting the measuring unit
4.2.1Connecting the transmitter
#
!
Warning!
When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to
these Operating Instructions. Please do not hesitate to contact your Endress+Hauser representative
if you have any questions.
Note!
• Observe national regulations governing the installation of electrical equipment.
• The remote version must be grounded. In doing so, the sensor and transmitter must be connected
to the same potential matching.
• When connecting the transmitter, use a connecting cable with a continuous service temperature
range between –40 °C (–40 °F) and the permitted max. ambient temperature plus 10 °C (plus 18 °F)
Connecting the transmitter, non-Ex/Ex-i version (→ å 13)
1.Unscrew the cover (a) of the electronics compartment from the transmitter housing.
2.Remove the display module (b) from the retaining rails (c) and refit onto the right retaining rail
with the left side of the display (this secures the display module).
3.Loosen screw (d) of the cover of the connection compartment and fold the cover down.
4.Push the cable for the power supply current output through the cable gland (e).
Optional: push the cable for the pulse output/frequency output through the cable gland (f).
5.Pull the terminal connector (g) out of the transmitter housing and connect the cable for the
power supply/current output. (→ Fig. 14, A)
Optional: pull terminal connector (h) out of the transmitter housing and connect the cable for
the pulse output/frequency output. (→ Fig. 14, B)
Note!
!
The terminal connectors (g / h) are pluggable, i.e. they can be plugged out of the transmitter
housing to connect the cables.
6.Plug the terminal connectors (g / h) into the transmitter housing.
Note!
!
The connectors are coded so you cannot mix them up.
7.Only remote version:
secure the ground cable to the ground terminal (→ Fig. 14, C).
8.Tighten the cable glands (e / f) (see alsoPage 21).
9.Fold up the cover of the connection compartment and tighten the screws (d).
10. Remove the display module (b) and fit on the retaining rails (c).
11. Screw the cover of the electronics compartment (a) onto the transmitter housing.
Endress+Hauser17
WiringProline Prosonic Flow 92F
e
f
g
h
d
a
c
b
d
a0001895
Fig. 13: Connecting the transmitter, non-Ex/Ex i version
aCover of electronics compartment
bDisplay module
cRetaining rail for display module
dConnection compartment cover
eCable gland for power supply/current output cable
fCable gland for pulse output/frequency output cable (optional)
gTerminal connector for power supply/current output
hTerminal connector for pulse output/frequency output (optional)
Connecting the transmitter, Ex-d → å 14
1.Open the clamp (a) securing the cover of the connection compartment.
2.Unscrew the cover (b) of the connection compartment from the transmitter housing.
3.Push the cable for the power supply/current output through the cable gland (c).
Optional: push the cable for the pulse output/frequency output through the cable gland (d).
4.Pull the terminal connector (e) out of the transmitter housing and connect the cable for the
power supply/current output. (→ Fig. 14, A)
Optional: pull terminal connector (f) out of the transmitter housing and connect the cable for
the pulse output/frequency output. (→ Fig. 14, B)
Note!
!
The terminal connectors (e/f) are pluggable, i.e. they can be plugged out of the transmitter
housing to connect the cables.
5.Plug the terminal connectors (e / f) into the transmitter housing.
Note!
!
The connectors are coded so you cannot mix them up.
6.Only remote version:
secure the ground cable to the ground terminal (→ Fig. 14, C).
7.Tighten the cable glands (c / d) (see alsoPage 21).
8.Secure the ground cable to the ground terminal (only remote version)
9.Screw the cover (b) of the connection compartment onto the transmitter housing.
10. Tighten the clamp (a) securing the cover of the connection compartment.
18Endress+Hauser
Proline Prosonic Flow 92FWiring
f
e
b
a
c
d
12 34
A
C
++
--
B
a0001896
Fig. 14: Connecting the transmitter, Ex d version
aClamp securing cover of connection compartment
bCover of connection compartment
cCable gland for power supply/current output cable
dCable gland for pulse output/frequency output cable (optional)
eTerminal connector for power supply/current output
fTerminal connector for pulse output/frequency output (optional)
HART current output
Galvanically isolated, 4 to 20 mA with HART
Pulse/status output
Open collector, passive, galvanically isolated, Umax = 30 V, with 15 mA current limiting, Ri = 500 Ω, can be configured
as pulse output or status output
Pulse/status output/
frequency output
Endress+Hauser19
WiringProline Prosonic Flow 92F
+1
–2
1
3
4
1
# % &
Copy
G H I
PQ R S
, ( )‘
AB C
Paste
Page
On
Page
Up
DeleteBksp
Insert
J K L
TU V
_ < >
D E F
Hot Key
+ Hot Key
M N O
W XYZ
+ * /
4
7
.
2
5
8
0
375
FIELD COMMUNICATOR
3
6
9
-
9
6
³W250
12 34
++
--
2
+26
-27
RS 232
1
3
5
4
³W250
12 34
++
--
2
4.2.3HART connection
Users have the following connection options at their disposal:
• Direct connection to transmitter by means of terminals 1 (+) / 2 (−)
• Connection by means of the 4 to 20 mA circuit
!
Note!
• The measuring circuit's minimum load must be at least 250 Ω .
• After commissioning, make the following setting:
Switch HART write protection on or off (see Page 38)→ Page 37
• For connecting, please refer also to the documentation issued by the HART Communication
Foundation, in particular HCF LIT 20: "HART, a technical summary".
Connecting the HART handheld terminal
For the connection, also refer to the documentation issued by the HART Communication
Foundation, and in particular HCF LIT 20: "HART, a technical summary".
A0014632
Fig. 16: Electrical connection to the HART operating terminal
1HART operating terminal
2Power supply
3Shielding
4Additional switching units or PLC with passive input
Connecting a PC with operating software
A HART modem (e.g. "Commubox FXA195") is required for connecting a PC with operating
software (e.g. "FieldCare").
For the connection, also refer to the documentat
ion issued by the HART Communication
Foundation, and in particular HCF LIT 20: "HART, a technical summary".
20Endress+Hauser
Fig. 17: Electrical connection of a PC with operating software
1PC with operating software
2Power supply
3Shielding
4Additional switching units or PLC with passive input
5HART modem e.g. Commubox FXA195
A0014633
Proline Prosonic Flow 92FWiring
ab
4.3Degree of protection
The devices fulfill all the requirements for IP 67 (optional IP 68) degree of protection. Compliance
with the following points is mandatory following installation in the field or servicing in order to
ensure that IP 67 protection is maintained:
• The housing seals must be clean and undamaged when inserted into their grooves. The seals must
be dried, cleaned or replaced if necessary.
• All housing screws and screw caps must be firmly tightened.
• The cables used for connection must be of the specified outside diameter.
• Firmly tighten the cable entries.
• The cables must loop down before they enter the cable entries ("water trap").
This arrangement prevents moisture penetrating the entry. Always install the measuring device
in such a way that the cable entries do not point up.
• Replace all unused cable entries with dummy plugs.
• Do not remove the grommet from the cable entry.
"
!
a0001914
Fig. 18: Installation instructions for cable entries
Caution!
The cable glands of the sensor housing must not be released as the degree of protection guaranteed
by Endress+Hauser would no longer apply.
Note!
The Prosonic Flow 92F can be supplied with IP 68 rating (permanent immersion in water to a depth
ot 3 meters /10 ft). In this case the transmitter must be installed remote from the sensor.
Endress+Hauser21
WiringProline Prosonic Flow 92F
4.4Post-connection check
Perform the following checks after completing electrical installation of the measuring device:
Device condition and specificationsNotes
Are cables or the device damaged (visual inspection)?−
Electrical connectionNotes
Does the supply voltage match the specifications on the nameplate?
• Non-Ex: 12 to 35 V DC (with HART: 18 to 35 V DC)
• Ex i and Ex n: 12 to 30 V DC (with HART 18 to 30 V DC)
• Ex d: 15 to 35 V DC (with HART 21 to 35 V DC)
Do the cables used comply with the specifications?→ ä 16, → ä 62
Do the cables have adequate strain relief?−
Are the cables for power supply/current output, frequency output (optional) and
grounding connected correctly?
Remote version only:
Is the connecting cable between the sensor and transmitter connected correctly?
Remote version only:
Are the sensor and transmitter connected to the same potential matching?
Are all screw terminals firmly tightened?−
Are all the cable entries installed, tightened and sealed?
Cable run with "water trap"?
Are all the housing covers installed and tightened?−
−
→ ä 17
→ ä 16
→ ä 16
→ ä 21
22Endress+Hauser
Proline Prosonic Flow 92FOperation
Esc
E
+
-
1
32
+48.25 xx/yy
+3702.6 x
5Operation
5.1Display and operating elements
The local display enables you to read important parameters directly at the measuring point and
configure the device using the "Quick Setup" or the function matrix.
The display consists of two lines; this is where measured values and/or status variables (e.g. bar
graph) are displayed.
By means of local operation, you can change the assignment of the display lines to different variables
to suit your needs and preferences. See Device Functions in the Appendix → ä 68
a0001141
Fig. 19: Display and operating elements
1Liquid crystal display
The two-line liquid-crystal display shows measured values and diagnosis messages.
– Top line: shows main measured values, e.g. volume flow in [dm/h] or in [%].
– Bottom line: shows additional measured variables and status variables, e.g. totalizer reading in [dm], bar graph,
tag name.
– During commissioning or in the event of a fault in normal measuring operation, a diagnosis message flashes on
the screen.
The first line shows the diagnosis code beginning with the letters F, C, S or M and a short text containing the
2Plus/minus keys
3Enter key
diagnosis message appears on the second line.
– Enter numerical values, select parameters
– Select different function groups within the function matrix
Press the +/- keys simultaneously to trigger the following functions:
– Exit the function matrix step by step → HOME position
– Press and hold down +/- keys for longer than 3 seconds → return directly to the HOME position
–Cancel data entry
–HOME position→ enter the function matrix
– Save the numerical values you input or settings you changed
Endress+Hauser23
OperationProline Prosonic Flow 92F
>3s
-
+
E
Esc
E
E
E
E
EEEEE
–
+
+
Esc
–
+
Esc
–
+
Esc
–
E
m
n
o
p
5.2Operation via the function matrix
!
Note!
• Please refer to the general notes → ä 25
• Function descriptions → see the "Description of Device Functions" manual
1.HOME position → F → enter the function matrix
2.Select a function group e.g. CURRENT OUTPUT
3.Select a function (e.g. TIME CONSTANT)
Change parameter/enter numerical values:
P → select or enter enable code, parameters, numerical values
F → save your entries
4.Exit the function matrix:
– Press and hold down the Esc key (X) for more than 3 seconds → HOME position
– Repeatedly press Esc key (X) → return step by step to HOME position
Fig. 20: Selecting and configuring functions (function matrix)
24Endress+Hauser
a0001142
Proline Prosonic Flow 92FOperation
5.2.1General notes
The Quick Setup menu is adequate for commissioning with the necessary standard settings.
Complex measuring operations on the other hand necessitate additional functions that you can
configure as necessary and customize to suit your process conditions. The function matrix,
therefore, comprises a multiplicity of additional functions which, for the sake of clarity, are arranged
in a number of function groups.
Comply with the following instructions when configuring functions:
• You select functions as described already.
• You can switch off certain functions (OFF). If you do so, related functions in other function groups
will no longer be displayed.
• Certain functions prompt you to confirm your data entries. Press P to select "SURE [ YES ]" and
press F to confirm. This saves your setting or starts a function, as applicable.
• Return to the HOME position is automatic if no key is pressed for 5 minutes.
• Programming mode is automatically disabled if you do not press a key within 60 seconds
following return to the HOME position.
!
!
"
Note!
A detailed description of all the functions required for commissioning is provided in Section 11.1
"Description of device functions".
Note!
• The transmitter continues to measure while data entry is in progress, i.e. the current measured
values are output via the signal outputs in the normal way.
• If the power supply fails, all preset and configured values remain safely stored in the EEPROM.
5.2.2Enabling the programming mode
The function matrix can be disabled. Disabling the function matrix rules out the possibility of
inadvertent changes to device functions, numerical values or factory settings. A numerical code
(factory setting = 92) has to be entered before settings can be changed.
If you use a code number of your choice, you exclude the possibility of unauthorized persons
accessing data ( → see "Description of Device Functions" manual).
Comply with the following instructions when entering codes:
• If programming is disabled and the P operating elements are pressed in any function, a prompt
for the code automatically appears on the display.
• If "0" is entered as the private code, programming is always enabled.
• Your Endress+Hauser service organization can be of assistance if you are locked out of the device.
Caution!
Changing certain parameters influences numerous functions of the entire measuring device, and
may effect measuring accuracy!
There is no need to change these parameters under normal circumstances and consequently, they
are protected by a special service code known only to the Endress+Hauser service organization.
Please contact Endress+Hauser if you have any questions.
5.2.3Disabling the programming mode
Programming mode is disabled if you do not press an operating element within 60 seconds following
automatic return to the HOME position.
You can also disable programming by entering any number (other than the private code) in the
ACCESS CODE function.
Endress+Hauser25
OperationProline Prosonic Flow 92F
5.3Communication
In addition to via local operation, the measuring device can also be configured and measured values
obtained by means of the HART protocol. Digital communication takes place using the 4–20 mA
current output HART.
The HART protocol allows the transfer of measuring and device data between the HART master and
the field devices for configuration and diagnostics purposes. HART masters, such as a handheld
terminal or PC-based operating programs (such as FieldCare), require device description (DD) files.
They are used to access all the information in a HART device. Such information is transferred solely
via "commands". There are three different command classes:
There are three different command classes:
• Universal commands
All HART devices support and use universal commands. The following functionalities are linked
to them:
– Recognizing HART devices
– Reading off digital measured values (volume flow, totalizer, etc.)
• Common practice commands:
Common practice commands offer functions which are supported and can be executed by many
but not all field devices.
• Device-specific commands:
These commands allow access to device-specific functions which are not HART standard. Such
commands access individual field device information, (among other things), such as empty-pipe/
full-pipe adjustment values, low flow cutoff settings etc.
!
Note!
The measuring device has all three command classes.
List of all "Universal Commands" and "Common Practice Commands": → ä 30
26Endress+Hauser
Proline Prosonic Flow 92FOperation
5.3.1Operating options
For the complete operation of the measuring device, including device-specific commands, there are
device description (DD) files available to the user to provide the following operating aids and
programs:
!
Note!
• The HART protocol requires the "4 to 20 mA HART" setting (individual options see device
function) in the CURRENT SPAN function (current output 1).
HART Field Communicator Field Xpert
Selecting device functions with a HART Communicator is a process involving a number of menu
levels and a special HART function matrix.
The HART operating instructions in the carrying case of the HART handheld terminal contain more
detailed information on the device.
Operating program "FieldCare"
FieldCare is Endress+Hauser’s FDT-based plant asset management tool and allows the configuration
and diagnosis of intelligent field devices. By using status information, you also have a simple but
effective tool for monitoring devices.
Operating program "SIMATIC PDM" (Siemens)
SIMATIC PDM is a standardized, manufacturer independent tool for the operation, configuration,
maintenance and diagnosis of intelligent field devices.
Operating program "AMS" (Emerson Process Management)
AMS (Asset Management Solutions): program for operating and configuring devices.
Endress+Hauser27
OperationProline Prosonic Flow 92F
5.3.2Current device description files
The following table illustrates the suitable device description file for the operating tool in question
and then indicates where these can be obtained.
HART protocol:
Valid for software:1.01.XX→ Function "Device software"
Device data HART
Manufacturer ID:
Device ID:
HART version data:Device Revision 6/ DD Revision 1
Software release:12.2010
Operating program:Sources for obtaining device descriptions:
Handheld terminal Field Xpert • Use update function of handheld terminal
FieldCare / DTM• www.endress.com → Download
AMS• www.endress.com → Download
SIMATIC PDM• www.endress.com → Download
(ENDRESS+HAUSER)
11
hex
61
hex
• CD-ROM (Endress+Hauser order number 56004088)
• DVD (Endress+Hauser order number 70100690)
→ Function "Manufact ID"
→ Function "Device ID"
!
Tester/simulator:Sources for obtaining device descriptions:
Fieldcheck• Update by means of FieldCare via the Flow Device FXA193/291 DTM
in the Fieldflash module
Note!
The "Fieldcheck" tester/simulator is used for testing flowmeters in the field. When used in
conjunction with the "FieldCare" software package, test results can be imported into a database,
printed out and used for official certification. Contact your Endress+Hauser representative for more
information.
28Endress+Hauser
Proline Prosonic Flow 92FOperation
5.3.3Device variables and process variables
Device variables:
The following device variables are available via the HART protocol:
ID (decimal)Device variable
30Volume flow
40Sound velocity
43Signal strength
49Flow velocity
240Totalizer 1
241Totalizer 2
Process variables:
At the factory, the process variables are assigned to the following device variables:
• Primary process variable (PV) → volume flow
• Secondary process variable (SV) → totalizer
• Third process variable (TV) → sound velocity
• Fourth process variable (FV) → flow velocity
!
Note!
You can set or change the assignment of device variables to process variables using Command 51
→ ä 33.
Endress+Hauser29
OperationProline Prosonic Flow 92F
5.3.4Universal/common practice HART commands
The following table contains all the universal commands supported by the device.
Command No.
HART command/access type
Universal commands
0Read the unique device identifier
Access type = Read
1Read the primary process variable
Access type = Read
2Read the primary process variable as
current in mA and percentage of the
set measuring range
Access type = Read
3Read the primary process variable as
current in mA and four (preset
using command 51) dynamic
process variables
Access type = Read
Command data
(numeric data in decimal form)
NoneThe device identifier provides information on the device
None– Byte 0: HART unit ID of the primary process variable
None– Byte 0-3: current current of the primary process
None24 bytes are sent as a response:
Response data
(numeric data in decimal form)
and manufacturer; it cannot be altered.
The response consists of a 12-byte device ID:
– Byte 0: fixed value 254
– Byte 1: manufacturer ID, 17 = E+H
– Byte 2: device type ID, e.g. 0x61 = Prosonic 92
– Byte 3: number of preambles
– Byte 4: rev. no. universal commands
– Byte 5: rev. no. device-spec. Commands
– Byte 6: software revision
– Byte 7: hardware revision
– Byte 8: additional device information
– Byte 9-11: device identification
– Byte 1-4: primary process variable
Factory setting:
Primary process variable = volume flow
Note!
!
• You can set the assignment of device variables to
process variables using Command 51.
• Manufacturer-specific units are represented using the
HART unit ID "240".
variable in mA
– Byte 4-7: percentage of the set measuring range
Factory setting:
Primary process variable = volume flow
Note!
!
You can set the assignment of device variables to process
variables using Command 51.
– Byte 0-3: current of the primary process variable in
mA
– Byte 4: HART unit ID of the primary process variable
– Byte 5-8: primary process variable
– Byte 9: HART unit ID of the secondary process
variable
– Byte 10-13: secondary process variable
– Byte 14: HART unit ID of the third process variable
– Byte 15-18: third process variable
– Byte 19: HART unit ID of the fourth process variable
– Byte 20-23: fourth process variable
Factory setting:
• Primary process variable = volume flow
• Secondary process variable = totalizer 1
• Third process variable = sound velocity
• Fourth process variable = flow velocity
Note!
!
• You can set the assignment of device variables to
process variables using Command 51.
• Manufacturer-specific units are represented using the
HART unit ID "240".
30Endress+Hauser
Loading...
+ 86 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.