Endress+Hauser Proline Prosonic Flow 92F Specifications

Page 1
Technical Information
Proline Prosonic Flow 92F
Ultrasonic Flow Measuring System 2-Wire loop powered inline flowmeter

Application

The flowmeter is ideally suited for applications in process control and utility measurement in practically all sectors of industry such as the chemical and petrochemical industry, energy production and district heating.
• Loop powered transmitter (2-Wire)
• Accuracy up to ±0.3%
• Fluid temperatures up to 200 °C (392 °F)
• Process pressures up to 40 bar (ASME Cl. 300)
• Galvanically isolated pulse output available
Approvals for hazardous area:
• ATEX, FM, CSA, TIIS, IECEx, NEPSI
Connection to common process control systems:
• HART, PROFIBUS PA, FOUNDATION Fieldbus
Relevant safety aspects:
• Pressure Equipment Directive (PED)
• Process sealing accoring to ISA 12.27.01

Your benefits

The Prosonic Flow 92F is a calibrated meter capable of measuring flow of conductive and especially non­conductive liquids such as solvents, hydrocarbons and non-conductive water.
The Proline transmitter concept comprises of:
• Diagnostic ability and data back-up capability for increased process quality
• Permanent self-monitoring and diagnosis of transmitter and sensor
The Proline Prosonic Flow sensors comprises:
• Available as a 2, 3 or 4 beam version
• Innovative 3 and 4 fourbeam design facilitates a reduced requirement for upstream pipework ( 5 pipe diameter)
• Calibration traceable to international standards
• No pressure drop
• Maintenance free due to no moving parts
TI00073D/06/EN/13.10 71124142
Page 2

Table of contents

Proline Prosonic Flow 92F
Function and system design. . . . . . . . . . . . . . . . . . . . . 3
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Outputs in general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Low flow cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical connection measuring unit . . . . . . . . . . . . . . . . . . . . . . . 7
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical connection remote version . . . . . . . . . . . . . . . . . . . . . . . 7
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Remote version cable specifications . . . . . . . . . . . . . . . . . . . . . . . . 8
Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operating elements (HART) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 18
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
C-tick . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Certification PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
FOUNDATION Fieldbus certification . . . . . . . . . . . . . . . . . . . . . 19
Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Pressure Equipment Directive . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 20
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . 20
Performance characteristics. . . . . . . . . . . . . . . . . . . . . 9
Reference calibration conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operating conditions: Installation . . . . . . . . . . . . . . . . 9
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operating conditions: Environment . . . . . . . . . . . . . . 12
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . 12
Operating conditions: Process . . . . . . . . . . . . . . . . . . 13
Fluid temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Medium pressure range (nominal pressure) . . . . . . . . . . . . . . . . . 13
Pressure loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 13
Design, dimensions, weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Material load diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2 Endress+Hauser
Page 3
Proline Prosonic Flow 92F
T'
1
T'
1
T
1
T e

Function and system design

Measuring principle A Prosonic Flow inline flowmeter measures the flow rate of the passing fluid by using sensor pairs located on

opposite sides of the meter body and at an angle so that one of the sensors in the pair is slightly downstream. The flow signal is established by alternating an acoustic signal between the sensor pairs and measuring the time of flight of each transmission. Then utilizing the fact that sound travels faster with the flow versus against the flow, this differential time ( T) can be used to determine the fluids velocity between the sensors. The volume flow rate is established by combining all the flow velocities determined by the sensor pairs with the cross sectional area of the meter body and extensive knowledge about fluid flow dynamics. The design of the sensors and their position ensures that only a short straight run of pipe upstream of the meter is required after typical flow obstructions such as bends in one or two planes. Advance digital signal processing facilitates constant validation of the flow measurement reducing susceptibility to multiphase flow conditions and increases the reliability of the measurement.

Measuring system The measuring system consists of a transmitter and a sensor. Two versions are available:

• Compact version: transmitter and sensor form a mechanical unit
• Remote version: transmitter and sensor are mounted physically separate from one another

Transmitter

Prosonic Flow 92
Prosonic Flow 92 remote version
a0005962
• Two line liquid crystal display
• Operation with push buttons
• 2-Wire loop powered
• Optional explosion proof housing
a0005963
a0006215
Endress+Hauser 3
Page 4

Sensor

Proline Prosonic Flow 92F
F
F (remote Version)
• Nominal diameters DN 25 to 100 (1 to 4")
• Process sensor for fluid temperatures up to 150 °C /302 °F (optional 200 °C /392 °F)
• Tube material: stainless steel
• Process pressures up to 40 bar
Remote version:
• IP67 housing (Optional IP68)
a0005966
• Standard remote cable length of 10 and 30 m (30 and 90 ft)
• Optional remote cable length up to
a0005967
F
F (remote Version)
a maximum 50 m (150 ft)
• Nominal diameters DN 150 to 300 (6 to 12")
• Process sensor for fluid temperatures up to 150 °C /302 °F (optional 200 °C /392 °F)
• Tube material: stainless steel, carbon steel
• Process pressures up to 40 bar
Remote version:
• IP67 housing (Optional IP68)
• Standard remote cable length of 10 and 30 m
a0014351
(30 and 90 ft)
• Optional remote cable length up to
a0014352
a maximum 50 m (150 ft)

Input

Measured variable Flow velocity (transit time difference proportional to flow velocity)

Measuring range Typically v = –10 to 10 m/s with the specified accuracy

Nominal diameter Range for full scale values (liquids) m
mm inch SI-Unit US-Unit
25 1" 0 to 300 dm
40 1½" 0 to 750 dm
50 2" 0 to 1100 dm
80 3" 0 to 3000 dm
100 4" 0 to 4700 dm
150 6" 0 to 10 m
200 8" 0 to 20 m³/min 0 to 5280 gal/min
250 10" 0 to 30 m³/min 0 to 7930 gal/min
300 12" 0 to 40 m³/min 0 to 10570 gal/min
3
/min 0 to 80 gal/min
3
/min 0 to 200 gal/min
3
/min 0 to 300 gal/min
3
/min 0 to 800 gal/min
3
/min 0 to 1250 gal/min
3
/min 0 to 2800 gal/min

Output

Outputs in general The following measured variables can generally be output via the outputs:

min(F)…mmax(F)
Current output Freq. output Pulse output Status output
Volume flow X X X Limit value
Calculated Mass flow X X X Limit value
Sound velocity X X Limit value
Flow velocity X X Limit value
Signal strength X X Limit value
4 Endress+Hauser
Page 5
Proline Prosonic Flow 92F

Output signal Current output:

Current output:

• 4 to 20 mA with HART
• Full scale value and time constant (0 to 100 s) can be set

Pulse/status output/Frequency output:

Open collector, passive, galvanically isolated
• Non-Ex, Ex d - version: = 35 V, with 15 mA current limiting, Ri = 500
U
max
• Ex i version: = 30 V, with 15 mA current limiting, Ri = 500
U
max
The pulse/status output can be configured as:
• Pulse output:
– Pulse value and pulse polarity can be selected, – Pulse width can be configured (0.005 to 2s) – Pulse frequency max. 100 Hz
• Status output:
Can be configured for diagnosis code messages or flow limit values
• Frequency output:
End frequency 0 to 1000 Hz (f
= 1250 Hz)
max

PROFIBUS PA interface

• PROFIBUS PA in accordance with IEC 61158 (MBP), galvanically isolated
• Profile Version 3.01
• Data transmission rate: 31.25 kBaud
• Current consumption: 16 mA
• Permitted supply voltage: 9 to 32 V; 0.5 W
• Bus connection with integrated reverse polarity protection
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Signal coding: Manchester II
• Bus address can be configured via miniature switches at the device or operating program

FOUNDATION Fieldbus interface:

• FOUNDATION Fieldbus H1, IEC 61158-2, galvanically isolated
• Data transmission rate: 31.25 kBit/s
• Current consumption: 16 mA
• Permitted supply voltage: 9 to 32 V
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Bus connection with integrated reverse polarity protection
• Signal encoding: Manchester II
• ITK Version 5.0
• Function blocks: 4 × Analog Input, 1 × Analog Output, 1 × Digital Input, 1 × Digital Output, 1 × PID
• Output data: Volume flow, Sound velocity, Flow velocity, Signal strength, Totalizers 1 to 2
• Input data: Positive zero return (ON/OFF), Zero point adjustment, Reset totalizer
• Link Master (LM) function is supported

Signal on alarm Current output:

Failsafe mode selectable (e.g. in accordance with NAMUR Recommendation NE 43)
Status output:
"Non conductive" in the event of fault or power supply failure.
Endress+Hauser 5
Page 6

Load

00
100 100
200 200
300 300
400 400
500 500
600 600
700 700
800 800
900 900
1000 1000
1100 1100
BB
RR
[] []
10 1020 2025 2530 3036 3615 15
18
21
W
0
100
200
300
400
500
600
700
800
900
1000
1100
B
S
R
U
V
[]
[
10
20 25 30
15
18
W
Ex i
Exi/Exn
W
Ex d
Ex
RB=
(U
SKl
–U )
(I )
max
-3
– 10 0.022
=
(U
SKl
–U )
Proline Prosonic Flow 92F
a0001921
Behavior of load and supply voltage
The area marked in gray indicates the permissible load (with HART: min. 250 .) The load is calculated as follows:
Load, load resistance
R
B
Supply voltage:
U
S
- Non-Ex = 12 to 35 V DC
- Ex d = 15 to 35 V DC
- Ex i = 12 to 30 V DC Terminal voltage:
U
KL
- Non-Ex = min. 12 V DC
- Ex d = min. 15 V DC
- Ex i = min. 12 V DC Output current (22.6 mA)
I
max.

Low flow cutoff Switch points for low flow cutoff can be selected as required.

Galvanic isolation All circuits for inputs, outputs, and power supply are galvanically isolated from each other.

6 Endress+Hauser
Page 7
Proline Prosonic Flow 92F
12 34
A
C
++
B
a
c
b
d
1
G
1
GROUND
2
GROUND
2
G
1G2
G
1
GROUND
2
GROUND
3G
3
GROUND
4
GROUND
4 G
3
GROUND
4
GROUND
5G
5
GROUND
6
GROUND
6G
5
GROUND
6
GROUND
7
G
7
GROUND
8
GROUND
8G
7
GROUND
8
GROUND
3G
4
G5G6G7G8G
1
2
3
4
5
6 7
8
e
f

Electrical connection measuring unit

Power supply

A0010962
A – HART: power supply, current output
– PROFIBUS PA: 1 = PA+, 2 = PA– – FOUNDATION Fieldbus: 1 = FF+, 2 = FF–
B Optional frequency output (not for PROFIBUS PA , FOUNDATION Fieldbus),
can also be operated as Pulse or status output
C Ground terminal (relevant for remote version)

Terminal assignment

Electrical connection remote version

Terminal No. (inputs/outputs)
Order version 1 2 3 4
92***-***********W HART current output
92***-***********A HART current output Pulse/status output/frequency output
92F**-***********H PA+ PA–
92F**-***********K FF+ FF–
Endress+Hauser 7
a0005764
Connecting the remote version
a Cover of the connection compartment (transmitter) b Cover of the connection compartment (sensor) c Connecting cable (signal cable) d Identical potential matching for sensor and transmitter e Connect the shielding to the ground terminal in the transmitter housing and keep it as short as possible f Connect the shielding to the ground terminal in the connection housing
Page 8

Supply voltage HART:

Non-Ex: 12 to 35 V DC (with HART: 18 to 35 V DC) Ex i: 12 to 30 V DC (with HART 18 to 30 V DC) Ex d: 15 to 35 V DC (with HART: 21 to 35 V DC)

PROFIBUS PA and FOUNDATION Fieldbus:

• Non-Ex: 9 to 32 V DC
• Ex i/IS and Ex n: 9 to 30 V DC
• Ex d/XP: 9 to 35 V DC
• Current consumption PROFIBUS PA: 16 mA, FOUNDATION Fieldbus: 16 mA

Cable entries Power supply and signal cables (inputs/outputs):

• Cable entry M20 × 1.5
• Thread for cable entries, ½" NPT, G ½" (not for threaded version)
• Optional processing sealing according ISA 12.27.01
Proline Prosonic Flow 92F

Remote version cable specifications

Power supply failure • Totalizer stops at the last value determined (can be configured).

• Use a connecting cable with a continuous service temperature range of at least: –40 °C /–40 °F (permitted max. ambient temperature plus 10 °C /18 °F)
• The cables are available with a fixed length of 10 m and 30 m and optionally available with variable lengths ranging from 1 m (3.3 ft) to max. 50 m (164 ft).
• All settings are kept in the HISTO-RAM, T-DAT.
• Diagnosis code messages (incl. value of operated hours counter) are stored.
8 Endress+Hauser
Page 9
Proline Prosonic Flow 92F

Performance characteristics

Reference calibration conditions

Maximum measured error

Repeatability ±0.2% of reading

Error limits following ISO/DIN 11631:
• 20 to 30 °C (68 to 86 °F); 2 to 4 bar
• Calibration systems as per national norms
• Zero point calibrated under operating conditions
DN 25 to DN 300 (1 to 12")
0.5 to 10 m/s (1.6 ft to 33 ft/s) ±0.5% of reading *
Optional for DN 80 to DN 300 (3 to 12")
0.5 to 10 m/s (1.6 ft to 33 ft/s) ±0.3% of reading *
* For a Reynolds number > 10000

Operating conditions: Installation

Note the following points:
• No special measures such as supports are necessary. External forces are absorbed by the construction of the instrument.
• The flowmeter flanges must be coplanar with connecting flanges and free from tension.
• The maximum permitted ambient temperatures (ä 12) and fluid temperatures (ä 13) must be observed.
• Pay particular attention to the notes on orientation and piping insulation on the following pages.
• The correct operation of the measuring system is not influenced by pipe vibrations.

Installation instructions Mounting location

Entrained air or gas bubbles in the measuring tube can result in an increase in measuring errors or loss of measurment. Avoid the following mounting locations in the pipe:
• Highest point of a pipeline. Risk of air accumulating.
• Directly upstream from a free pipe outlet in a vertical pipeline.

Mounting location

a0006081
Endress+Hauser 9
Page 10
Proline Prosonic Flow 92F
1
2
3
4
5
A BC D
Notwithstanding the above, the installation proposal below permits installation in an open vertical pipeline. Pipe restrictions or the use of an orifice with a smaller cross section than the nominal diameter prevent the sensor running empty while measurement is in progress.
a0006082
Installation in a down pipe (e.g. for batching applications)
1 = Supply tank , 2 = Sensor, 3 = Orifice plate, pipe restriction , 4 = Valve, 5 = Batching tank

Orientation

Make sure that the direction of the arrow on the nameplate of the sensor matches the direction of flow (direction of fluid flow through the pipe).
Orientations A, B and C recommended, orientation D only recommended under certain circumstances

Heating

Some fluids require heat to be transfered at the sensor. Heating can be electrical, such as electrical heat tracing or by heat jacketing, the meter.
Caution!
"
• Risk of electronics overheating! Consequently, make sure that the adapter between the sensor and transmitter and the connection housing of the remote version always remain free of insulating material. Note that the orientation of the meter could significantly reduce the temperature at the electronics.
• If using an electric trace heating system whose heating is regulated via phase angle control or pulse packages, influence on the measured values cannot be ruled out due to magnetic fields (i.e. for values that are greater than the values approved by the EN standard (sine 30 A/m)). In such instances, it is necessary to magnetically shield the sensor
a0005971
10 Endress+Hauser
Page 11
Proline Prosonic Flow 92F
max. 20
max. 20
2
A
1
3
A
A
4
A
5 DN×
10 DN×
B
3 DN×
15 DN×
5 × DN
B
3 DN×
B
3 DN×
B
3 DN×

Thermal insulation

Some fluids require suitable measures to avoid heat transfer at the sensor. A wide range of materials can be used to provide the required thermal insulation.
a0005763-en
A maximum insulation thickness of 20 mm must be observed in the area of the electronics/neck..
If the device is installed horizontally (with transmitter head pointing upwards), an insulation thickness of min. 10 mm is recommended to reduce convection. The maximum insulation thickness of 20 mm must not be exceeded.

Limiting flow

Information on limiting flow is provided under "Measuring range" in the technical data section.

Inlet and outlet runs If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc. As a minimum, the inlet

and outlet runs shown below must be observed to achieve the specified accuracy of the device. The longest inlet run shown must be observed if two or more flow disturbances are present.
A0006267
Minimum inlet and outlet runs with various flow obstructions (values given for 3 and 4 path versions)
A = Inlet run, B = Outlet run, 1 = 90° elbow or T-piece, 2 = Pump, 3 = 2 × 90° elbow, out of plane, 4 = Control valve
Endress+Hauser 11
Page 12

Operating conditions: Environment

Ambient temperature range Compact version

• Standard: –40 to +60 °C (–40 to 140 °F)
• EEx-d / EEx-i version: –40 to +60 °C (–40 to 140 °F)
Display can be read between –20 to +70 °C (–4 to 158 °F)
Remote version
•Sensor: – Standard: –40 to +80 °C (–40 to 176 °F) – EEx-d / EEx-i version: –40 to +80 °C (–40 to 176 °F)
• Transmitter: – Standard: –40 to +60 °C (–40 to 140 °F) – EEx-i version: –40 to +60 °C (–40 to 140 °F) – EEx-d version: –40 to +60 °C (–40 to 140 °F)
Display can be read between –20 to +70 °C (–40 to 158 °F)
!

Storage temperature Standard: –40 to +80 °C (–40 to 176 °F)

Note! When mounting outside, protect from direct sunlight with a protective cover (order number 543199), especially in warmer climates with high ambient temperatures.
EEx-d / EEx-i version: –40 to +80 °C (–40 to 176 °F)
Proline Prosonic Flow 92F

Degree of protection • Transmitter Prosonic Flow 92: IP67 (NEMA 4X)

• Sensor Prosonic Flow F Inline: IP67 (NEMA 4X) Optional: IP 68 (NEMA 6P)
!

Shock resistance In accordance with IEC 68-2-31

Vibration resistance Acceleration up to 1 g, 10 to 150 Hz, following IEC 68-2-6

Electromagnetic compatibility (EMC)

Note! The Prosonic Flow 92 F can be supplied with IP 68 rating (permanent immersion in water to a depth of 3 meters /98 ft). In this case the transmitter must be installed remote from the sensor.
To IEC/EN 61326 and NAMUR recommendation NE 21
12 Endress+Hauser
Page 13
Proline Prosonic Flow 92F
Esc
E
-
+
D
G
H J*
K*
C
E
F
B
A*

Operating conditions: Process

Fluid temperature range

Medium pressure range
Size Range DN 25 to 100
(1 to 4")
Standard ASME & AD2000 ASME & AD2000 ASME AD2000
Version Stainless Steel Stainless Steel Carbon Steel Carbon Steel
Standard –40 to 150 °C
(–40 to 302 °F)
Optional –40 to 200 °C
(–40 to 392 °F)
*For PED device minimum temperature is –10 °C (14 °F)
–40 to 150 °C
(–40 to 302 °F)
–40 to 200 °C
(–40 to 392 °F)
DN 150 to 300
(6 to 12")
–29 to 130 °C* (–84 to 266 °F)
–29 to 200 °C* (–20 to 392 °F)
EN PN 16 to 40 / ASME Cl 150, Cl 300 / JIS 10K, 20K
(nominal pressure)

Pressure loss Pressure loss is negligible if the sensor is installed in a pipe of the same nominal diameter.

Mechanical construction

Design, dimensions, weights Dimensions of transmitter, remote version

–10 to 130 °C
(–14 to 266 °F)
–10 to 200 °C
(–14 to 392 °F)
Endress+Hauser 13
A B C D E F G H J K
[mm]
(inch)
232
9.13
* The following dimensions differ depending on the version: – The dimension 232 mm (9.13 inch) changes to 226 mm (8.9 inch) in the blind version (without local operation). – The dimension 170 mm (6.9 inch) changes to 183 mm (7.2 inch) in the Ex d/XP version. – The dimension 340 mm (13.4 inch) changes to 353 mm (13.9 inch) in the Ex d/XP version.
!
The transmitter housing has one cable gland or cable entry. Measuring devices with a pulse, frequency or status output have two cable glands or cable entries (devices with TIIS approval only have one cable gland).
Note!
[mm]
(inch)
8.6 (M8)
0.3
[mm]
(inch)
100
3.9
[mm]
(inch)
123
4.8
[mm]
(inch)
100
3.9
[mm]
(inch)
23
0.9
[mm] (inch)
144
5,7
[mm]
(inch)
170
6.7
[mm]
(inch)
170
6.7
A0003594
[mm]
(inch)
340
13.4
Page 14
Proline Prosonic Flow 92F
A*
F*
E
H
L
X
D
H + 7 (0.28)
mm (inch)
H
42 (1.65)
d
I N
E
X
P
L
O
S
I
V
E
A
T
M
O
S
P
H
E
R
E
K
E E
P
H
T
I
G
H
T
W
E
N
C
I
R
C
U
I
T
A
L
I
V
E
WARNING
N
I
C
H
T
U
N
T
E
R
S
P
A
N
N
U
N
G
Ö
F
F
N
E
N
AVERTISSEMENT
N
E
S
P
A
S
O
U
V
R
I
R
O
U
S
T
E
N
S
I
O N
WARNUNG
E
+
Esc
B1** B2**
C
G
1
2
3
4
E
E
N25 – 100 (1…4")D
N150 – 300 (612")D
161
181**
141
151**
H42 (1.65)

Dimensions of Prosonic Flow 92F

Flanged version to:
• EN 1092-1 (DIN 2501), Ra = 6.3 to 12.5 μm Raised face to: EN 1092-1 Form B1 (DIN 2526 Form C), PN 10 to 40, Ra = 6.3 to 12.5 μm
• ASME B16.5, Class 150 to 300, Ra = 125 to 250 μin
• AARH/Ra = 125 to 250 μin
• JIS B2220, 10 to 40K, Ra = 125 to 250 μin
A0006033
1 Standard- and Ex -i version 2 Ex d version (Transmitter) 3 Remote version DN 25 to 100 (1 to 4") 4 Remote version DN 150 to 300 (6 to 12")
Dimensions of Prosonic Flow 92F
mm 149 121 105 151 161 inch 5.87 6.34…7.13 5.55…5.94 4.76 4.13 5.94 6.34 * The following dimensions change as follows in the blind version (without local operation): – Standard, and Ex i version: the dimension 149 mm (5.87 inch) changes to 142 mm (5.60 inch) in the blind version. –Ex d version: the dimension 151 mm (5.94 inch) changes to 144 mm (5.67 inch) in the blind version. ** The dimension depends on the cable gland used.
A B1** B2** C E F* G
14 Endress+Hauser
Page 15
Proline Prosonic Flow 92F
!
Note! The weight data refer to the compact version. The weight of the remote version is approx. 0.9 kg (1.98 lbs) greater.
Flange according to EN 1092-1
DN Pressure rating d [mm] D [mm] H [mm] L [mm]* X [mm]* Weight [kg]
25 PN 40 28.5 115.0 284.5 300 18 10 40 PN 40 43.1 150.0 287.0 315 18 12 50 PN 40 54.5 165.0 291.5 325 20 14 80 PN 40 82.5 200.0 310.5 390 24 24
100
150
200
250
300
*including raised face
PN 16 107.1 220.0 PN 40 107.1 235.0 24 35 PN 16 159.3 285.0 PN 40 159.3 300.0 400 33 53.9 PN 16 207.3 340.0 PN 40 206.5 375.0 400 41 92.0 PN 16 260.4 405.0 PN 40 258.8 450.0 450 47 130.9 PN 16 309.7 460.0 PN 40 307.9 515.0 500 55 174.3
323.5 460
439.2
464.6
491.6
517.0
400 23 33.0
400 25 44.2
400 28 62.7
500 32 82.1
20 32
Flange according to ASME B16.5 (SI-Units)
Size Pressure rating d [mm] D [mm] H [mm] L [mm]* X [mm]* Weight [kg]
Schedule 40
25
Schedule 80
Schedule 40
40
Schedule 80
Schedule 40
50
Schedule 80
Schedule 40
80
Schedule 80
Schedule 40
100
Schedule 80
150 Schedule 40
200 Schedule 40
250 Schedule 40
300 Schedule 40
*including raised face
Cl. 150 26.7 107.9 Cl. 300 26.7 123.8 19.1 10 Cl. 150 24.3 107.9 15.7 9 Cl. 300 24.3 123.8 19.1 10 Cl. 150 40.9 127.0 Cl. 300 40.9 155.6 20.6 13 Cl. 150 38.1 127.0 17.5 11 Cl. 300 38.1 155.6 20.6 13 Cl. 150 52.6 152.4 Cl. 300 52.6 165.0 22.4 14 Cl. 150 49.2 152.4 19.1 13 Cl. 300 49.2 165.0 22.4 15 Cl. 150 78.0 190.5 Cl. 300 78.0 210.0 28.4 28 Cl. 150 73.7 190.5 23.9 25 Cl. 300 73.7 210.0 28.4 28 Cl. 150 102.4 228.6 Cl. 300 102.4 254.0 31.8 44 Cl. 150 97.0 228.6 24.4 36 Cl. 300 97.0 254.0 31.8 44 Cl. 150 154.1 279.4 Cl. 300 154.1 317.5 450 36.7 56.5 Cl. 150 202.7 342.9 Cl. 300 202.7 381.0 450 41.1 82.6 Cl. 150 254.5 406.4 Cl. 300 254.5 444.5 500 47.8 118.3 Cl. 150 303.2 482.5 Cl. 300 303.2 520.7 550 50.8 164.5
284.5 300
287.0 315
291.5 325
310.5 390
330.0 460
439.2
464.6
491.6
517.0
400 25.4 38.9
400 28.4 57.6
450 30.2 79.9
500 31.8 113.5
15.7 9
17.5 11
19.1 13
23.9 24
24.4 36
Endress+Hauser 15
Page 16
Proline Prosonic Flow 92F
Flange according to ASME B16.5 (US-Units)
DN Druckstufe d [inch] D [inch] H [inch] L [inch]* X [inch]* Gewicht [lbs]
Schedule 40
1 "
Schedule 80
Schedule 40
1½"
Schedule 80
Schedule 40
2"
Schedule 80
Schedule 40
3"
Schedule 80
Schedule 40
4"
Schedule 80
6" Schedule 40
8" Schedule 40
10" Schedule 40
12" Schedule 40
*including raised face
Cl. 150 1.05 4.25 Cl. 300 1.05 4.87 0.75 22.1 Cl. 150 0.96 4.25 0.62 19.9 Cl. 300 0.96 4.87 0.75 22.1 Cl. 150 1.61 5.00 Cl. 300 1.61 6.13 0.81 28.7 Cl. 150 1.50 5.00 17.5 24.3 Cl. 300 1.50 6.13 0.81 28.7 Cl. 150 2.07 6.00 Cl. 300 2.07 6.50 0.88 14.0 Cl. 150 1.94 6.00 0.75 28.7 Cl. 300 1.94 6.50 0.88 33.1 Cl. 150 3.07 7.50 Cl. 300 3.07 8.27 1.12 61.8 Cl. 150 2.90 7.50 0.94 55.1 Cl. 300 2.90 8.27 1.12 61.8 Cl. 150 4.03 9.00 Cl. 300 4.03 10.0 1.25 97.0 Cl. 150 3.82 9.00 0.96 79.4 Cl. 300 3.82 10.0 1.25 79.4 Cl. 150 6.07 11.0 Cl. 300 6.07 12.5 17.7 1.44 124.6 Cl. 150 7.98 13.5 Cl. 300 7.98 15.0 17.7 1.62 182.1 Cl. 150 10.0 16.0 Cl. 300 10.0 17.5 19.7 1.88 260.8 Cl. 150 11.9 19.0 Cl. 300 11.9 20.5 21.7 2.00 362.7
11.2 11.8
11.3 12.4
11.5 12.8
12.2 15.40
13.0 18.1
17.3
18.3
19.4
20.4
15.8 1.00 85.8
15.8 1.12 127.0
17.7 1.19 176.1
19.7 1.25 250.2
0.62 19.9
17.5 24.3
0.75 28.7
0.94 52.9
0,96 79.4
Flange according to JIS B2220
DN Pressure rating d [mm] D [mm] H [mm] L [mm] X [mm] Weight [kg]
Schedule 40 20K 27.2 125.0
25
Schedule 80 20K 24.3 125.0 16 Schedule 40 20K 41.2 140.0
40
Schedule 80 20K 38.1 140.0 18
Schedule 40
50
Schedule 80
Schedule 40
80
Schedule 80
Schedule 40
100
Schedule 80
10K 52.7 155.0 20K 52.7 155.0 18 10K 49.2 155.0 16 20K 49.2 155.0 18 10K 78.1 185.0 20K 78.1 200.0 22 28 10K 73.7 185.0 18 25 20K 73.7 200.0 22 28 10K 102.3 210.0 20K 102.3 225.0 24 44 10K 97.0 210.0 18 36 20K 97.0 225.0 24 44
284.5 300
287.0 315
291.5 325
310.5 390
323.5 460

Weight See dimension tables ä 14 ff.

Material Transmitter housing and connection housing, sensor (remote version):

Compact housing: powder coated die cast aluminium
DN25 to 100 DN150 to 300
Standard ASME & AD2000 ASME & AD2000 ASME AD2000
Meter body A351-CF3M 1.4404+TP316+TP316L A106 Grd. B A106 Grd. B
1.4462
Sensor 1.4404+316L+316
Flanges 1.4404+F316+F316L 1.4404+F316+F316L A105+1.0432 1.0426 Designed for NACE MR0175/ISO 15156 and NACE MR0103 It is the equipment user‘s responsibility to select the materials suitable for the intended services.
Carbon steel with outer protective painting to 130 °C (266 °F) or optional 200 °C (392 °F)
1.4404+316L+316
1.4462
1.4404+316L+316
16
18
16
18 24
18 36
1.4404+316L+316
10
12
13
1.4462
16 Endress+Hauser
Page 17
Proline Prosonic Flow 92F
0
10
20
30
40
50
[bar]
300
400
500
700 600
200 100
0
800
[psi]
-60
-40
-20
020
40 60 80 100 120 140
180
200
160
C]
-40
0
-80
40 80 120 160 200 240 280 320 360 400
[°F]
PN40
PN16
PN
25
-60
-40
-20
020
40 60 80 100 120 140
180
200
160
C]
-40
0
-80
40 80 120 160 200 240 280 320 360 400
[°F]
Cl.150
Cl.300
0
10
20
30
40
50
[bar]
300
400
500
700 600
200 100
0
800
[psi]
-60
-40
-20
020
40 60 80 100 120 140
180
200
160
C]
0
10
20
30
[bar]
10K
20K

Material load diagram Pressure-temperature curve to EN 1092-1, stainless steel

Pressure-temperature curve to ASME B16.5, stainless steel

Class 150 to 300
A0010911
A0010909

Pressure-temperature curve to JIS B2220, stainless steel

10 to 40 K
A0010910
Endress+Hauser 17
Page 18

Pressure-temperature curve to EN 1092-1, carbon steel

-40
-20
020
40 60 80 100 120 140
180
200
160
C]
-40
0
40 80 120 160 200 240 280 320 360 400
[°F]
40
[bar]
[psi]
600 500 400 300 200 100
00
30
20
10
N40P
N16P
0
10
20
30
40
50
[bar]
300
400
500
700 600
200 100
0
800
[psi]
-60
-40
-20
020
40 60 80 100 120 140
180
200
160
C]
-40
0
-80
40 80 120 160 200 240 280 320 360 400
[°F]
Cl.150
Cl.300

Pressure-temperature curve to ASME B16.5, carbon steel

Proline Prosonic Flow 92F
A0014656

Human interface

Display elements • Liquid crystal display: double spaced with 16 characters per line

• Selectable display of different measured values and status variables
• At ambient temperatures below –20 °C (–4 °F) the readability of the display may be impaired.

Operating elements (HART) • Local operation with three keys (–, +, E)

• Application specific Quick Setup menus for straightforward commissioning
• Operating elements accessible also in Ex-zones
Remote operation Remote operation possible via:
•HART
• PROFIBUS PA
• FOUNDATION Fieldbus
• FieldCare

CE mark The device is in conformity with the statutory requirements of the EC Directives.

18 Endress+Hauser

Certificates and approvals

Endress+Hauser confirms successful testing of the device by affixing the CE mark.
A0014674
Page 19
Proline Prosonic Flow 92F

C-tick The measuring system meets the EMC requirements of the Australian Communications and Media Authority

(ACMA).

Ex approval Information about currently available Ex versions (ATEX, FM, CSA) can be supplied by your Endress+Hauser

sales organization. All explosion protection data are given in a separate documentation which is available upon request.

Certification PROFIBUS PA The flowmeter has successfully passed all test procedures and is certified and registered by the PNO (PROFIBUS

User Organization). The device thus meets all the requirements of the specifications following:
• Certified to PROFIBUS PA Profile Version 3.0 (device certification number: on request)
• The device can also be operated with certified devices of other manufacturers (interoperability)

FOUNDATION Fieldbus certification

Other standards and guidelines

The flowmeter has passed all the test procedures implemented and has been certified and registered by the Fieldbus Foundation. The flowmeter thus meets all the requirements of the specifications listed below:
• Certified to FOUNDATION Fieldbus specification
• The flowmeter meets all the specifications of the FOUNDATION Fieldbus-H1.
• Interoperability Test Kit (ITK), revision status 5.0: The device can also be operated in conjunction with other-make certified devices
• Physical Layer Conformance Test of the Fieldbus Foundation
• EN 60529 Degrees of protection by housing (IP code).
• EN 61010-1 Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures.
• IEC/EN 61326 "Emission in accordance with Class A requirements". Electromagnetic compatibility (EMC- requirements).
• NAMUR NE 21 Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.
• NAMUR NE 43 Standardization of the signal level for the breakdown information of digital transmitters with analogue output signal.
• NAMUR NE 53 Software of field devices and signal processing devices with digital electronics.
• ASME/ISA-S.61010-1(82.02.01) CSA-C22.2 No. 1010.1 ASME/UL 61010-1 Safety requirements for Electrical Equipment for Measurement and Control and Laboratory Use. Pollution degree 2
• NACE Standard MR0103 Standard Material Requirements - Materials Resistant to Sulfide Stress Cracking in Corrosive Petroleum Refining Environments
• NACE Standard MR0175 Standard Material Requirements - Sulfide Stress Cracking Resistant Metallic Materials for Oilfield Equipment

Pressure Equipment Directive The measuring devices can be ordered with or without PED (Pressure Equipment Directive). If a device with

PED is required, this must be ordered explicitly. For devices with nominal diameters less than or equal to DN 25 (1"), this is neither possible nor necessary.
• With the identification PED/G1/III on the sensor nameplate, Endress+Hauser confirms conformity with the "Basic safety requirements" of Appendix I of the Pressure Equipment Directive 97/23/EC.
• Devices with this identification (with PED) are suitable for the following types of fluid:
- Fluids of Group 1 and 2 with a steam pressure of greater or less than 0.5 bar (7.3 psi)
- Unstable gases
• Devices without this identification (without PED) are designed and manufactured according to good engineering practice. They correspond to the requirements of Art. 3, Section 3 of the Pressure Equipment Directive 97/23/EC. Their application is illustrated in Diagrams 6 to 9 in Appendix II of the Pressure Equipment Directive 97/23/EC.
Endress+Hauser 19
Page 20

Ordering information

Instruments International
Endress+Hauser Instruments International AG Kaegenstrasse 2 4153 Reinach Switzerland
Tel.+41 61 715 81 00 Fax +41 61 715 25 00 www.endress.com info@ii.endress.com
The Endress+Hauser service organization can provide detailed ordering information and information on the order codes on request.

Accessories

Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter and the sensor.

Documentation

• Flow measuring technology (FA005D/06)
• Supplementary documentation on Ex-ratings: ATEX, FM, CSA
• Operating Instructions Prosonic Flow 92 (BA00121D/06)
• Operating Instructions Prosonic Flow 92 PROFIBUS PA (BA00122D/06)

Registered trademarks

HART® Registered trademark of HART Communication Foundation, Austin, USA
PROFIBUS Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
FOUNDATION™ Fieldbus Registered trademark of the Fieldbus FOUNDATION, Austin, USA
HistoROM™ T-DAT Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH
®
®
, FieldCare ®, Fieldcheck®, FieldXpert™, Applicator
®
TI00073D/06/EN/13.10 71124142 FM+SGML6.0/ProMoDo
Loading...