Endress+Hauser Deltabar FMD71, Deltabar FMD72 Operating Instructions Manual

BA01044P/00/EN/04.14 71243974
01.00.00
Products Solutions Services
Operating Instructions
Deltabar FMD71, FMD72
Level measurement with electronic differential pressure Electronic differential pressure transmitter with ceramic and metal sensors
Deltabar FMD71, FMD72 Table of contents

Table of contents

1 Document information .............. 5
1.1 Document function ..................... 5
1.2 Symbols used .......................... 5
1.3 Documentation ........................ 7
1.4 Registered trademarks ................... 8
2 Basic safety instructions ............ 9
2.1 Requirements concerning the staff .......... 9
2.2 Designated use ........................ 9
2.3 Workplace safety ...................... 10
2.4 Operational safety ..................... 10
2.5 Product safety ........................ 10
3 Product description ................ 11
3.1 Product design ........................ 11
3.2 Function ............................ 12
3.3 Registered trademarks .................. 12
4 Incoming acceptance and product
identification ..................... 13
4.1 Incoming acceptance ................... 13
4.2 Product identification ................... 14
4.3 Nameplates .......................... 14
8 Operation without an operating
menu ............................. 30
8.1 Position of operating elements ............ 30
9 Operation with an operating
menu ............................. 32
9.1 Operating concept ..................... 32
9.2 Structure of the operating menu ........... 32
9.3 Operating options ..................... 33
9.4 Operating the device using onsite display
(optional) ........................... 33
9.5 Operation using Endress+Hauser operating
program ............................ 36
9.6 Direct access to parameters .............. 37
9.7 Locking/unlocking operation ............. 37
9.8 Resetting to factory settings (reset) ........ 38
10 Integrating transmitter using
HART® protocol ................... 40
10.1 HART process variables and measured
values .............................. 40
10.2 Device variables and measured values ....... 41
5 Storage and transport ............. 17
5.1 Storage conditions ..................... 17
5.2 Transporting the product to the measuring
point ............................... 17
6 Installation ....................... 18
6.1 Mounting dimensions .................. 18
6.2 Mounting location ..................... 18
6.3 Orientation .......................... 18
6.4 General installation instructions ........... 18
6.5 Thermal insulation - FMD71 high-
temperature version .................... 19
6.6 Installing the sensor modules ............. 20
6.7 Installing the transmitter ................ 21
6.8 Closing the housing covers ............... 22
6.9 Seal for flange mounting ................ 22
6.10 Post-installation check .................. 23
7 Electrical connection .............. 24
7.1 Connecting the sensor module LP to the
sensor module HP ..................... 24
7.2 Connecting the sensor module HP to the
transmitter .......................... 25
7.3 Connecting the measuring unit ............ 26
7.4 Connection conditions .................. 27
7.5 Connection data ....................... 28
7.6 Post-connection check .................. 29
11 Commissioning .................... 42
11.1 Function check ....................... 42
11.2 Unlocking/locking configuration .......... 42
11.3 Commissioning without an operating menu .. 42
11.4 Commissioning with an operating menu ..... 45
11.5 Selecting the language, measuring mode, high-pressure side, and pressure engineering
unit ................................ 45
11.6 Pos. Zero Adjust ....................... 47
11.7 Configuring level measurement ........... 48
11.8 Linearization ......................... 58
11.9 Configuring pressure measurement ........ 61
11.10 Backing up or duplicating the device data .... 62
11.11 Configuring the local display ............. 63
11.12 Protecting settings from unauthorized
access .............................. 63
12 Diagnostics and troubleshooting ... 64
12.1 Troubleshooting ...................... 64
12.2 Diagnostic events ...................... 64
12.3 Response of output to errors .............. 68
12.4 Firmware history ...................... 68
12.5 Disposal ............................ 68
13 Maintenance ...................... 69
13.1 Exterior cleaning ...................... 69
3
Table of contents Deltabar FMD71, FMD72
14 Repair ............................ 70
14.1 General notes ........................ 70
14.2 Spare parts .......................... 71
15 Return ............................ 72
16 Overview of the operating menu .... 73
17 Description of device parameters ... 78
18 Registered trademarks ........... 108
18.1
HARTâ ............................ 108
19 Technical data ................... 109
Index ................................. 110
4
Deltabar FMD71, FMD72 Document information
DANGER
WARNING
CAUTION
NOTICE

1 Document information

1.1 Document function

These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.

1.2 Symbols used

1.2.1 Safety symbols

Symbol Meaning
DANGER!
A0011189-EN
A0011190-EN
A0011191-EN
A0011192-EN
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury.
NOTICE!
This symbol contains information on procedures and other facts which do not result in personal injury.

1.2.2 Electrical symbols

Symbol Meaning
Direct current
A0011197
A terminal to which DC voltage is applied or through which direct current flows.
Alternating current
A0011198
A terminal to which alternating voltage is applied or through which alternating current flows.
Direct current and alternating current
• A terminal to which alternating voltage or DC voltage is applied.
A0017381
• A terminal through which alternating current or direct current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding
A0011200
system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0011199
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
A0011201
equalization line or a star grounding system depending on national or company codes of practice.
5
Document information Deltabar FMD71, FMD72
,…,
,…,

1.2.3 Tool symbols

Symbol Meaning
Torx screwdriver
A0013442
Flat blade screwdriver
A0011220
Cross-head screwdriver
A0011219
Allen key
A0011221
Hexagon wrench
A0011222

1.2.4 Symbols for certain types of information

Symbol Meaning
Permitted
Indicates procedures, processes or actions that are permitted.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
Reference to page
Refers to the corresponding page number.
A0011195
Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196
Series of steps
Result of a sequence of actions
Help in the event of a problem
A0013562
Visual inspection
A0015502

1.2.5 Symbols in graphics

Symbol Meaning
1, 2, 3 ... Item numbers
Series of steps
A, B, C, ... Views
A-A, B-B, C-C, ... Sections
6
Deltabar FMD71, FMD72 Document information
-
.
Symbol Meaning
Hazardous area
Indicates a hazardous area.
A0011187
Safe area (non-hazardous area)
Indicates the non-hazardous area.
A0011188

1.3 Documentation

The document types listed are available:
• On the CD supplied with the device
• In the Download Area of the Endress+Hauser Internet site: www.endress.com  Download

1.3.1 Technical Information TI01033P: helps in planning your device

The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.

1.3.2 Brief Operating Instructions KA01105P: getting the 1st measured value quickly

The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning.

1.3.3 Description of Device Parameters GP01013P: reference for your parameters

The document provides a detailed explanation of each individual parameter in the operating menu. The description is aimed at those who work with the device over the entire life cycle and perform specific configurations.

1.3.4 Safety Instructions (XA)

Safety Instructions (XA) are supplied with the device depending on the approval. These instructions are an integral part of the Operating Instructions.
Device Certificate/type of protection Documentation Version
FMD71, FMD72 ATEX II 1/2G Ex ia IIC T6 Ga/Gb XA00619P BA
FMD71, FMD72 ATEX II 1/2G Ex d [ia] IIC T6 Ga/Gb XA00620P BC
FMD71, FMD72 ATEX II 3G Ex nA IIC T6 GC XA00621P BD
FMD71, FMD72 IEC Ex ia IIC T6 Ga/Gb XA00622P IA
FMD71, FMD72 IEC Ex d [ia] IIC T6 Ga/Gb XA00623P IB
FMD71, FMD72 CSA General Purpose - CD
FMD71 FM C/US IS Cl.I Div.1 Gr.A-D, AEx ia, Zone 0,1,2 XA00628P FA
FMD71 FM C/US XP AIS Cl.I Div.1 Gr.A-D, Exd [ia] Zone 0,1,2 XA00629P FB
FMD71 CSA C/US XP Cl.I Div.1 Gr.A-D, Ex d [ia], Zone 0,1,2 XA00631P CB
FMD71 FM C/US NI Cl.I Div.2 Gr.A-D, Zone 2 XA00668P FD
FMD71 CSA C/US NI, Cl.I Div. 2, Gr.A-D Cl.I, Zone 2, IIC XA00670P CC
FMD71 CSA C/US IS Cl.I Div.1 Gr.A-D, Ex ia Zone 0,1,2 XA00630P CA
FMD72 CSA C/US IS Cl.I Div.1 Gr.A-D, Ex ia Zone 0,1,2 XA00626P CA
1)
7
Document information Deltabar FMD71, FMD72
Device Certificate/type of protection Documentation Version
FMD72 CSA C/US XP Cl.I Div.1 Gr.A-D, Ex d [ia], Zone 0,1,2 XA00627P CB
FMD72 CSA C/US NI, Cl.I Div.2 Gr.A-D, Zone 2 XA00671P CC
FMD72 FM C/US IS Cl.I Div.1 Gr.A-D, AEx ia, Zone 0,1,2 XA00624P FA
FMD72 FM C/US XP AIS Cl.I Div.1 Gr.A-D, Exd [ia] Zone 0,1,2 XA00625P FB
FMD72 FM C/US NI Cl.I Div.2 Gr.A-D, Zone 2 XA00669P FD
1) Product Configurator, "Approval" section
The nameplate provides information on the Safety Instructions (XA) that are relevant for the device.

1.4 Registered trademarks

1.4.1
Registered trademark of the HART Communication Foundation, Austin, USA

HARTâ

1)
8
Deltabar FMD71, FMD72 Basic safety instructions

2 Basic safety instructions

2.1 Requirements concerning the staff

The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements:
Trained, qualified specialists: must have a relevant qualification for this specific
function and task Are authorized by the plant owner/operator
Are familiar with federal/national regulations
Before beginning work, the specialist staff must have read and understood the
instructions in the Operating Instructions and supplementary documentation as well as in the certificates (depending on the application) Following instructions and basic conditions
The operating personnel must fulfill the following requirements:
Being instructed and authorized according to the requirements of the task by the
facility's owner-operator Following the instructions in these Operating Instructions

2.2 Designated use

2.2.1 Application and media

The Deltabar FMD72 is a differential pressure transmitter for measuring differential pressure and level in pressurized tanks. The device has two sensor modules, which measure the operating pressure (High Pressure HP and Low Pressure LP). The differential pressure/hydrostatic level is calculated in the transmitter unit. The sensor signal is transmitted digitally. In addition, sensor temperatures and the individual process pressures present at the respective sensor modules can be individually evaluated and transmitted. If the limit values specified in the "Technical Data" and the conditions listed in the instructions and additional documentation are observed, the measuring device may be used for the following measurements (process variables):
Measured process variables
• Pressure HP and Pressure LP
• Sensor temperature
Calculated process variables
• Differential pressure
• Level (level, volume or mass)

2.2.2 Incorrect use

The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance
in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.

2.2.3 Residual risks

Due to heat transfer from the process as well as power loss in the electronics, the temperature of the electronics housing and the assemblies contained therein (e.g. display module, main electronics module and I/O electronics module) may rise up to 80 °C (176
9
Basic safety instructions Deltabar FMD71, FMD72
°F). When in operation, the sensor may reach a temperature close to the medium temperature.
Danger of burns from contact with surfaces!
For elevated fluid temperature, ensure protection against contact to prevent burns.

2.3 Workplace safety

For work on and with the device:
Wear the required personal protective equipment according to federal/national
regulations. Switch off the supply voltage before connecting the device.

2.4 Operational safety

Risk of injury!
Operate the device in proper technical condition and fail-safe condition only.
The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers
If, despite this, modifications are required, consult with Endress+Hauser.
Repair
To ensure continued operational safety and reliability,
Carry out repairs on the device only if they are expressly permitted.
Observe federal/national regulations pertaining to repair of an electrical device.
Use original spare parts and accessories from Endress+Hauser only.
Hazardous area
To eliminate a danger for persons or for the facility when the device is used in the hazardous area (e.g. explosion protection, pressure vessel safety):
Based on the nameplate, check whether the ordered device is permitted for the
intended use in the hazardous area. Observe the specifications in the separate supplementary documentation that is an
integral part of these Instructions.

2.5 Product safety

This measuring device is designed in accordance with good engineering practice to meet state-of-the- art safety requirements, has been tested, and left the factory in a condition in which they are safe to operate.
It fulfills general safety requirements and legal requirements. It also conforms to the EC directives listed in the device-specific EC declaration of conformity. Endress+Hauser confirms this fact by applying the CE mark.
10
Deltabar FMD71, FMD72 Product description
2
1
3

3 Product description

3.1 Product design

Level measurement (level, volume and mass) with Deltabar:
A0016449
1 Sensor module LP 2 Sensor module HP 3 Transmitter
The FMD71/FMD72 is best suited to level measurement in tanks with pressure overlay or vacuum vessels and tanks, high distillation columns and other vessels with changing ambient temperatures.
The sensor module HP is mounted on the lower measuring connection and the sensor module LP is mounted above the maximum level. The transmitter can be mounted on pipes or walls with the mounting bracket.
The sensor signal is transmitted digitally. In addition, sensor temperatures and the individual process pressures present at the respective sensor modules can be individually evaluated and transmitted.
11
Product description Deltabar FMD71, FMD72

3.2 Function

3.2.1 Differential pressure generation

The measurement chain for the calculation of the differential pressure can be represented by the following diagram:
LP
HP
Sensor press.
LP
Sensor
calibration LP
Sensor
calibration HP
Sensor press.
HP
Sensor trim LP
Sensor trim
HP
All the process values represented on the diagram are updated in a measurement cycle. The sensor module allocation is determined by the configuration when setting up the device. The connection to the transmitter defines the corresponding sensor module as the master. After commissioning, the second sensor module is detected as the slave. This configuration can be modified as desired. However, a modification must take place with the unit disconnected from the power supply.
The sensor modules have a designation independent of the master/slave configuration. This indicates where the sensor module is typically installed:
• Sensor module LP LP = Low pressure; top
• Sensor module HP HP = High pressure; bottom
For identical sensor module ranges, this assignment can likewise be changed, but this then has to be configured in the menu.
If you change both sensor modules or the electronics, this allocation must likewise be carried out. See "Connect transm. (286)" parameter .
Measured
pressure LP
Pressure
simulation LP
Differential
pressure +
pressure inversion
Pressure
simulation HP
Measured
pressure HP
Corrected
pressure
Pos. zero
adjust (calib.
offset)
Differential
pressure
simulation
Pressure after
damping
Damping P
Measured
differential
pressure
12

3.3 Registered trademarks

3.3.1
Registered trademark of the HART Communication Foundation, Austin, USA

HARTâ

Deltabar FMD71, FMD72 Incoming acceptance and product identification

DELIVERY NOTE
1 = 2
DELIVERYNOTE
Span
Ser. no.:
Order code:
P
U:
Deltabar
Ext. order code:
Order Code: Ser.-No.:
MWP
Span
U=
Mat.
-
Dat.:
0044
Mat.:
P
Ser. no.:
MWP
Sensor module Deltabar
4 Incoming acceptance and product
identification

4.1 Incoming acceptance

A0015502
A0016870
Is the order code on the delivery note (1) identical to the order code on the product sticker (2)?
A0016052
A0015502
A0016053
Are the goods undamaged?
A0015502
A0016054
Do the data on the nameplate correspond to the order specifications and the delivery note?
13
Incoming acceptance and product identification Deltabar FMD71, FMD72
Ser. no.:
Order code: Ext. order code:
2
5
6
3
4
1
A0015502
A0016055
Are the CD-ROM (product documentation) and documentation present? If required (see nameplate): Are the safety instructions (XA) present?
If one of these conditions is not met, please contact your Endress+Hauser sales office.

4.2 Product identification

The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
www.endress.com/deviceviewer): All information about the measuring device is
( displayed.
For an overview of the technical documentation provided, enter the serial number from the nameplates in the W@M Device Viewer (www.endress.com/deviceviewer)

4.3 Nameplates

4.3.1 Nameplates of the T14 transmitter housing

1 Device name 2 Order number (shortened for re-ordering) 3 Extended order number (complete) 4 Technical data 5 Serial number (for clear identification) 6 Manufacturer's address
A0016056
14
Deltabar FMD71, FMD72 Incoming acceptance and product identification
2
1
1
2
7
3 4 5
6
1
Ser. no.:
Order code: Ext. ord. cd.:
Additional nameplate for devices with Ex approval
A0021222
1 Approval-specific information 2 Document number of Safety Instructions or drawing number
Additional nameplate for devices with PVDF process connection
A0022683
1 Application limits

4.3.2 Nameplates of the T17 transmitter housing

A0021552
1 Device name 2 Manufacturer's address 3 Order number (shortened for re-ordering) 4 Extended order number (complete) 5 Serial number (for clear identification) 6 Technical data 7 Approval-related information and document number of Safety Instructions or drawing number
15
Incoming acceptance and product identification Deltabar FMD71, FMD72
0044
Mat.:
P
Ser. no.:
MWP
Sensor module Deltabar
2
1

4.3.3 Nameplate of the sensor housing

A0021224
1 Sensor serial number 2 Identification of sensor type (HP/LP)
16
Deltabar FMD71, FMD72 Storage and transport

5 Storage and transport

5.1 Storage conditions

Use original packaging.

5.1.1 Storage temperature range

–40 to +80 °C (–40 to +176 °F)

5.2 Transporting the product to the measuring point

WARNING
Risk of damage to housing!
Risk of injury.
Transport the measuring device to the measuring point in its original packaging or by
the process connection. Follow the safety instructions and transport conditions for devices weighing more than
18 kg (39.6 lbs).
A0016058
17
Installation Deltabar FMD71, FMD72

6 Installation

When measuring in media containing solids, such as dirty liquids, installing separators and drain valves is useful for capturing and removing sediment.

6.1 Mounting dimensions

For dimensions, see the "Mechanical construction" section in TI01033P.

6.2 Mounting location

The FMD71/FMD72 is best suited to level measurement in vessels with pressure overlay or vacuum tanks, high distillation columns and other vessels with changing ambient temperatures.
The sensor module HP is mounted on the lower measuring connection and the sensor module LP is mounted above the maximum level. The transmitter can be mounted on pipes or walls with the mounting bracket.

6.3 Orientation

• Transmitter: Any orientation.
• Sensor modules: The orientation can cause a zero point shift . This position-dependent zero point shift can be corrected directly at the device via the operating key, and also in hazardous areas in the case of devices with external operation (position adjustment).

6.4 General installation instructions

Mounting the sensor modules and transmitter is very easy
• The housings of the sensor modules can be rotated up to 480°.
• The transmitter is freely rotatable in the mounting bracket.
The sensor modules and transmitter can be easily aligned when mounted.
Your benefits
• Easy mounting due to optimum alignment of housing
• Easily accessible device operation
• Optimum readability of the onsite display (optional)
• Easy pipe installation due to optional alignment of the modules.
18
Deltabar FMD71, FMD72 Installation
2 mm
3 mm
A
B
1 2
A0017506

6.5 Thermal insulation - FMD71 high-temperature version

The FMD71 high-temperature version may only be insulated up to a certain height. The maximum permitted insulation height is indicated on the devices and applies to an insulation material with a heat conductivity ≤ 0.04 W/(m x K) and to the maximum permitted ambient and process temperature. The insulation height is not indicated on hygienic connections.
• Ambient temperature (TA): ≤ 70 °C (158 °F)
• Process temperature (TP): ≤ 150 °C (302 °F)
The data were determined under the most critical application "quiescent air".
A Ambient temperature B Process temperature 1 Insulation height 2 Insulation material
A0021075
19
Installation Deltabar FMD71, FMD72
2
3
1

6.6 Installing the sensor modules

6.6.1 General installation instructions

• The nameplate on the sensor module specifies where the sensor module is typically installed: HP (bottom) LP (top) For further information, see the "Function" (  12) section.
• Due to the orientation of the sensor modules, there may be a shift in the zero point, i.e. when the vessel is empty or partially full, the measured value does not display zero. You can correct this zero point shift: see "Commissioning without an operating menu" (  42) or the "Position adjustment" section(  47) .
• Always install the sensor module HP below the lowest measuring point.
• Always install the sensor module LP above the highest measuring point.
• Do not mount the sensor modules in the filling curtain or at a point in the tank which could be affected by pressure pulses from an agitator.
• Do not mount the sensor modules in the suction area of a pump.
• The adjustment and functional test can be carried out more easily if you mount the sensor modules downstream of a shutoff device.
• If a heated sensor module is cooled during the cleaning process (e.g. by cold water), a vacuum develops for a short time, whereby moisture can penetrate the sensor through the pressure compensation (3). If this is the case, mount the sensor with the pressure compensation (3) pointing downwards.
• Keep the pressure compensation and GORE-TEX® filter (3) free from contamination.
• Do not clean or touch process isolating diaphragms with hard or pointed objects.
A0017512

6.6.2 Mounting sensor modules with PVDF process connections

WARNING
Risk of damage to process connection!
Risk of injury!
Sensor modules with PVDF process connections must be installed with the mounting
bracket supplied!
The mounting bracket can be installed on pipes with a diameter of 1¼" to 2" or on walls.
In the case of pipe mounting, the nuts on the bracket must be tightened uniformly with a
20
torque of at least 5 Nm (3.69 lbf ft).
Deltabar FMD71, FMD72 Installation
1.
4.
3.
2.
A0017514

6.7 Installing the transmitter

The transmitter is installed with the mounting bracket supplied. The mounting bracket can be installed on pipes with a diameter of 1¼" to 2" or on walls.
In the case of pipe mounting, the nuts on the bracket must be tightened uniformly with a torque of at least 5 Nm (3.69 lbf ft).
A0021145

6.7.1 Turning the display module

A0017524
WARNING
Supply voltage switched off?
Risk of electric shock and/or explosion!
Switch off the supply voltage before connecting the device.
1. If present (i.e. in devices with Ex d and Ex na approval), release the securing clamp of the electronics compartment cover with an Allen key.
21
Installation Deltabar FMD71, FMD72
1 2
2. Unscrew the electronics compartment cover from the transmitter housing.
3. Pull out the display module with a gentle rotational movement.
4. Rotate the display module into the desired position: max. 4 × 90° in each direction.
5. Fit the display module on the electronics compartment in the desired position until it clicks into place.
6. Screw the electronics compartment cover back onto the transmitter housing.
7. If present (i.e. in devices with Ex d and Ex na approval), tighten the securing clamp with an Allen key (1 Nm (0.225 lbf)).

6.8 Closing the housing covers

CAUTION
The housing cover can no longer be closed.
Damaged thread!
When closing the housing covers make sure that the threads on the covers and the
housing are free from dirt, such as sand. If you encounter resistance when closing the covers, then check the threads again for dirt or fouling.

6.8.1 Closing the covers on the hygienic stainless steel housing (T17)

The covers for the terminal compartment and electronics compartment are hooked into the housing and closed with a screw in each case. These screws must be tightened finger­tight (2 Nm (1.48 lbf ft)) to the stop to ensure that the covers are securely seated and leak-tight.

6.9 Seal for flange mounting

NOTICE
Distorted measurement results.
The seal is not allowed to press against the process isolating diaphragm as this could affect the measurement result.
Ensure that the seal is not touching the process isolating diaphragm.
22
A0017743
1 Process isolating diaphragm 2 Seal
Deltabar FMD71, FMD72 Installation

6.10 Post-installation check

m Is the device undamaged (visual inspection)?
Does the device conform to the measuring point specifications?
For example:
• Process temperature
m
• Process pressure
• Ambient temperature
• Measuring range
m Are the measuring point identification and labeling correct (visual inspection)? m Is the device adequately protected from precipitation and direct sunlight? m Are the securing screw and securing clamp tightened securely?
23
Electrical connection Deltabar FMD71, FMD72
6
7
5
5
6
2 3 4
3
4
1
21
6
NPT ½"
M20
8

7 Electrical connection

WARNING
If the operating voltage is > 35 VDC: Dangerous contact voltage at terminals.
Risk of electric shock!
In a wet environment, do not open the cover if voltage is present.
The sensor modules have a designation independent of the master/slave configuration. This indicates where the sensor module is typically installed:
• Sensor module LP LP = Low pressure; top
• Sensor module HP HP = High pressure; bottom
For further information, see the "Function" (  12)section.

7.1 Connecting the sensor module LP to the sensor module HP

WARNING
Supply voltage might be connected!
Risk of electric shock and/or explosion!
Switch off the supply voltage before connecting the device.
• Screw on the housing cover of the terminal compartment of the sensor module LP.
• Guide the cable of the sensor module HP through the cable gland of the sensor module
LP. Use the shielded 4-wire cable that is provided. The wire ends are color-coded to match the corresponding terminal.
• Connect device in accordance with the following diagrams.
• Screw down housing cover.
24
1 BK (black) 2 BU (blue) 3 WH (white) 4 BN (brown) 5 Sensor module LP 6 Sensor module HP 7 Ground terminal 8 Torque 0.4 Nm
A0017528
Deltabar FMD71, FMD72 Electrical connection
6
5
5
7
2 3 4
3
4
1
21
6
5
NPT ½"
M20
8
8

7.1.1 Screening with cable shield

Screening with cable shield is described in the associated documentation SD00354P. The documentation is provided with the connecting cables.

7.2 Connecting the sensor module HP to the transmitter

WARNING
Supply voltage might be connected!
Risk of electric shock and/or explosion!
Switch off the supply voltage before connecting the device.
• Screw on the housing cover of the terminal compartment of the sensor module HP.
• Guide the cable of the transmitter through the cable gland of the sensor module HP. Use the shielded 4-wire cable that is provided. The wire ends are color-coded to match the corresponding terminal.
• Connect device in accordance with the following diagram.
• Screw down housing cover.
A0017529
1 BK (black) 2 BU (blue) 3 WH (white) 4 BN (brown) 5 Sensor module HP 6 Transmitter 7 Ground terminal 8 Torque 0.4 Nm

7.2.1 Screening with cable shield

Screening with cable shield is described in the associated documentation SD00354P. The documentation is provided with the connecting cables.
25
Electrical connection Deltabar FMD71, FMD72
4... 20mA
Test
Test
Test
4... 20mA Test
1
8
6
7
2
3
4
5

7.3 Connecting the measuring unit

7.3.1 Terminal assignment

WARNING
Supply voltage might be connected!
Risk of electric shock and/or explosion!
Switch off the supply voltage before connecting the device.
NOTICE
Limitation of electrical safety due to incorrect connection!
When using the measuring device in hazardous areas, installation must comply with
the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings. All explosion protection data are given in separate documentation which is available
upon request. The Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas. Devices with integrated overvoltage protection must be grounded.
Protective circuits against reverse polarity, HF influences and overvoltage peaks are
integrated. The supply voltage must match the power supply specified on the nameplate (see
"Nameplate" (  14)) Switch off the supply voltage before connecting the device.
Remove the housing cover of the terminal compartment.
Guide cable through the gland. Preferably use twisted, screened two-wire cable.
Connect device in accordance with the following diagram.
Screw down housing cover.
Switch on supply voltage.
A0019989
1 Housing 2 Supply voltage 3 4 to 20 mA 4 Devices with integrated overvoltage protection are labeled "OVP" (overvoltage protection) here. 5 External ground terminal 6 4 to 20 mA test signal between positive and test terminal 7 Internal ground terminal, minimum supply voltage = 12 V DC, jumper is set as illustrated in the diagram. 8 Jumper for 4 to 20 mA test signal
26
Deltabar FMD71, FMD72 Electrical connection
Test
Test

7.3.2 Supply voltage

WARNING
Supply voltage might be connected!
Risk of electric shock and/or explosion!
When using the measuring device in hazardous areas, installation must comply with
the corresponding national standards and regulations as well as the Safety Instructions. All explosion protection data are given in separate documentation which is available
upon request. The Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
Electronic version Jumper for 4 to 20 mA test signal in
"Test" position (delivery status)
4 to 20 mA HART, version for non-hazardous areas
13 to 45 V DC 12 to 45 V DC
Jumper for 4 to 20 mA test signal in "Non-test" position
Measuring a 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the positive and test terminal without interrupting the measurement. The minimum supply voltage of the device can be reduced by simply changing the position of the jumper. As a result, operation is also possible with a lower supply voltage. To keep the corresponding measured error below 0.1 %, the current measuring device should exhibit an internal resistance of <0.7Ω. Observe the position of the jumper in accordance with the following table.
Jumper position for test signal
Description
• Measurement of 4 to 20 mA test signal via the positive and test terminal: possible. (Thus, the output current can be measured without interruption via the diode.)
• Delivery status
• Minimum supply voltage: 13 V DC
A0019992
• Measurement of 4 to 20 mA test signal via positive and test terminal: not possible.
• Minimum supply voltage: 12 V DC
A0019993

7.4 Connection conditions

7.4.1 Cable specification for transmitter connection

• Endress+Hauser recommends using twisted, shielded two-wire cables.
• Terminals for core cross-sections0.5 to 2.5 mm2 (20 to 14 AWG)
• The cable outer diameter depends on the cable entry used.
27
Electrical connection Deltabar FMD71, FMD72

7.4.2 Cable glands

Explosion protection Cable gland Permitted cable diameter Permitted wire cross-sections
• Standard
• Ex ia
• Ex ic
• Ex tD
• Ex nA
• FM approval
• CSA approval
Plastic M20x1.5 5 to 10 mm (0.2 to 0.39 in) 0.5 to 2.5 mm2 (20 to 14 AWG)
Metal M20 x 1.5 7 to 10.5 mm (0.28 to 0.41 in)

7.4.3 Overvoltage protection

Standard version
The standard version of the pressure instruments does not contain any special elements to protect against overvoltage ("wire to ground"). Nevertheless the requirements of the applicable EMC standard EN 61000-4-5 (testing voltage 1kV EMC wire/ground) are met.
Optional overvoltage protection
Devices showing version "NA" in feature 610 "Accessory Mounted" in the order code are equipped with overvoltage protection.
• Overvoltage protection: – Nominal functioning DC voltage: 600 V – Nominal discharge current: 10 kA
• Surge current check î = 20 kA satisfied as per DIN EN 60079-14: 8/20 μs
• Arrester AC current check I = 10 A satisfied
NOTICE
Device could be destroyed!
Devices with integrated overvoltage protection must be grounded.

7.5 Connection data

7.5.1 Maximum load

In order to guarantee sufficient terminal voltage in two-wire devices, a maximum load resistance R (including line resistance) must not be exceeded depending on the supply voltage U0 of the supply unit.
In the following load diagrams, observe the position of the jumper and the explosion protection:
28
Deltabar FMD71, FMD72 Electrical connection
U – 12 V
U – 13 V
R
L
max
23 mA
23 mA
£
30
20
12
U
[V]
40 45
1217
1435
783
348
[ ]W
[ ]W
R
L
max
R
L
max
30
20
13
40 45
1174
1391
739
304
Test
Test
£
3
A B
1
3
2
1
2
R
L
max
U
[V]
A0017533
A Jumper for 4 to 20 mA test signal set to "Non-test" position B Jumper for 4 to 20 mA test signal set to "Test" position 1 Power supply for II 1/2 G Ex ia, FM IS, CSA IS 2 Power supply for devices for the non-hazardous area, 2 G Ex d, 3 G Ex nA, FM XP, FM NI, CSA XP, CSA dust
ignition-proof
3 R U Supply voltage
maximum load resistance
Lmax

7.5.2 Shielding

• You achieve optimum shielding against disturbances if the shielding is connected on both sides (in the cabinet and on the device). If potential equalization currents are expected in the plant, only ground shielding on one side, preferably at the transmitter.
• When using in hazardous areas, you must observe the applicable regulations. Separate Ex documentation with additional technical data and instructions is included with all Ex systems as standard.

7.6 Post-connection check

m Is the device or cable undamaged (visual check)? m Do the cables comply with the requirements ? m Do the cables have adequate strain relief? m Are all the cable glands installed, firmly tightened and leak-tight? m Does the supply voltage match the specifications on the nameplate? m Is the terminal assignment correct ? m If required: Has protective ground connection been established ? m If supply voltage is present, is the device ready for operation and do values appear on the display module? m Are all housing covers installed and firmly tightened? m Is the securing clamp tightened correctly?
29
Operation without an operating menu Deltabar FMD71, FMD72
on
off
damp.
Display
Sensor
HART
R
FIELD COMMUNICATION PROTOCOL
SW /min
t
on
off
1 2
3
4
5
6
SW/min
7 8

8 Operation without an operating menu

8.1 Position of operating elements

8.1.1 Operating keys on the exterior of the device

With the T14 housing (aluminum or stainless steel), the operating keys are located either outside of the housing, under the protection cap or inside on the electronic insert. In addition, devices with an onsite display and a 4 to 20 mA HART electronic insert have operating keys on the onsite display.
A0016499
The operating keys on the outside of the device make it unnecessary to open the housing. This guarantees:
• Complete protection against environmental influences such as moisture and contamination.
• Simple operation without any tools.
• No wear.
8.1.2 Operating keys and elements located internally on the
electronic insert
30
1 DIP switch for locking/unlocking parameters relevant to the measured value 2 DIP switch for switching damping on/off 3 DIP switch for alarm current SW/Alarm min (3.6 mA)
4...5 Not assigned
6 Green LED to indicate value being accepted 7 Operating keys 8 Slot for optional display
A0016500
Deltabar FMD71, FMD72 Operation without an operating menu

8.1.3 Function of the DIP switches

Switch Symbol/
labeling
1
2
damping t
3 SW/Alarm min The alarm current is defined via the
Switch position
"off" "on"
The device is unlocked. Parameters relevant to the measured value can be modified.
A0011978
Damping is switched off. The output signal follows measured value changes without any delay.
configuration in the operating menu. ("Setup"  "Extended Setup"  "Current Output"  "Output Fail Mode")
2)
The device is locked. Parameters relevant to the measured value cannot be modified.
Damping is switched on. The output signal follows measured value changes with the delay time t.
1)
The alarm current is 3.6 mA (min), regardless of the setting in the operating menu.
1) The value for the delay time can be configured via the operating menu ("Setup"  "Damping"). Factory setting: t = 2 s or as per order specifications.
2) Factory setting: 22 mA

8.1.4 Function of the operating elements

Operating key(s) Meaning
Press for at least 3 seconds Adopt lower range value. A reference
pressure is present at the device.
A0017535
Press for at least 3 seconds Adopt upper range value. A reference
A0017536
Press for at least 3 seconds Position adjustment
For a detailed description, see also "Pressure measuring mode" section, (  42), or "Level measuring mode" section (  43).
pressure is present at the device. For a detailed description, see also "Pressure measuring mode" section, (  42), or "Level measuring mode" section (  43).
A0017535
and
A0017536
and
A0017537
Press for at least 6 seconds Reset all parameters. The reset via
operating keys corresponds to the
A0017537
software reset code 7864.
31
Operation with an operating menu Deltabar FMD71, FMD72

9 Operation with an operating menu

9.1 Operating concept

Operation with an operating menu is based on an operation concept with "user roles" .
User role Meaning
Operator Operators are responsible for the devices during normal "operation". This is usually limited to
reading process values either directly at the device or in a control room. If the work with the devices goes beyond reading, it concerns simple, application-specific functions that are used in operation. Should an error occur, these users simple forward the information on the errors but do not intervene themselves.
Maintenance Service engineers usually work with the devices in the phases following device commissioning.
They are primarily involved in maintenance and troubleshooting activities for which simple settings have to be made at the device. Technicians work with the devices over the entire life cycle of the product. Thus, commissioning and advanced settings and configurations are some of the tasks they have to carry out.
Expert Experts work with the devices over the entire life cycle of the device, but, in part, have high
requirements on the devices. Individual parameters/functions from the overall functionality of the devices are required for this purpose time and again. In addition to technical, process­oriented tasks, experts can also perform administrative tasks (e.g. user administration). "Experts" can avail of the entire parameter set.

9.2 Structure of the operating menu

User role Submenu Meaning/use
Operator Language Only consists of the "Language" parameter (000) where the operating language
for the device is specified. The language can always be changed even if the device is locked.
Display/ operat.
Maintenance Setup Contains all the parameters that are needed to commission measuring operations.
Contains parameters that are needed to configure the measured value display (selecting the values displayed, display format, etc.). With this submenu, users can change the measured value display without affecting the actual measurement.
This submenu has the following structure:
Standard setup parameters A wide range of parameters, which can be used to configure a typical application, is available at the start. The measuring mode selected determines which parameters are available. After making settings for all these parameters, the measuring operation should be completely configured in the majority of cases.
"Extended Setup" submenu The "Extended Setup" submenu contains additional parameters for more in­depth configuration of the measurement operation to convert the measured value and to scale the output signal. This menu is split into additional submenus depending on the measuring mode selected.
32
Deltabar FMD71, FMD72 Operation with an operating menu
1
User role Submenu Meaning/use
Diagnostics Contains all the parameters that are needed to detect and analyze operating
errors. This submenu has the following structure:
Diagnostic list Contains up to 10 currently pending error messages.
Event logbook Contains the last 10 error messages (no longer pending).
Instrument info Contains information for identifying the device.
Measured values Contains all current measured values.
Simulation Is used to simulate pressure, level, flow, current and alarm/warning.
Reset
Sensor LP
Sensor HP
Expert Expert Contains all the parameters of the device (including those already in one of the
submenus). The "Expert" submenu is structured by the function blocks of the device. It thus contains the following submenus:
System Contains all device parameters that neither affect measurement nor integration into a distributed control system.
Measurement Contains all parameters for configuring the measurement.
Output Contains all parameters for configuring the current output.
Communication Contains all parameters for configuring the HART interface.
Diagnostics Contains all the parameters that are needed to detect and analyze operating errors.

9.3 Operating options

9.3.1 Local operation

A0017650
1 Display and operating module with push buttons. Cover must be opened for operation.

9.4 Operating the device using onsite display (optional)

A 4-line liquid crystal display (LCD) is used for display and operation. The onsite display shows measured values, dialog text as well as fault and notice messages in plain text, thereby supporting the user in every stage of operation. The device display can be turned in 90° steps. Depending on the installation position of the device, this makes it easy to operate the device and read the measured value.
Functions:
33
Operation with an operating menu Deltabar FMD71, FMD72
1
3
2
4
5
E
+
• 8-digit measured value display incl. sign and decimal point, bargraph for 4 to 20 mA HART as current display.
• Simple and complete menu guidance thanks to separation of the parameters into several levels.
• Each parameter is given a 3-digit ID number for easy navigation.
• Option for configuring the display according to individual requirements and preferences, such as language, alternating display, display of other measured values such as sensor temperature, contrast setting.
• Comprehensive diagnostic functions (fault and warning message, peak-hold indicators, etc.).
• Quick and safe commissioning

9.4.1 Setting the contrast on the display module

•  and  (press simultaneously): increases the contrast.
•  and  (press simultaneously): decreases the contrast.

9.4.2 Overview

1 Operating keys 2 Bargraph 3 Symbol 4 Header 5 Parameter ID number

9.4.3 Symbols on the onsite display

Error symbols
Symbol Meaning
Error message "Out of specification"
The device is being operated outside its technical specifications (e.g. during warm-up or cleaning processes).
A0012088
Error message "Service mode"
The device is in service mode (e.g. during a simulation).
A0012100
Error message "Maintenance required"
Maintenance is required. The measured value remains valid.
A0012101
Error message "Failure detected"
An operating error has occurred. The measured value is no longer valid.
A0012086
A0016498
34
Deltabar FMD71, FMD72 Operation with an operating menu
Display symbols for locking status
Symbol Meaning
Lock symbol
The operation of the device is locked. To unlock device, see section on "Unlocking/locking
A0011978
configuration"(  42).
Display symbols for communication
Symbol Meaning
Communication symbol
Data transfer via communication
A0017652

9.4.4 Navigation and selection from list

The operating keys are used to navigate through the operating menu and to select an option from a picklist.
Operating key(s) Meaning
• Navigate downwards in the picklist
• Edit the numerical values and characters within a function
A0017879
• Navigate upwards in the picklist
• Edit the numerical values and characters within a function
A0017880
• Confirm entry
• Jump to the next item
A0017881
• Selection of a menu item and activation of edit mode
Contrast setting of onsite display: darker
and
A0017879
A0017881
Contrast setting of onsite display: brighter
and
A0017880
A0017881
ESC functions:
A0017879
and
• Exit edit mode for a parameter without saving the changed value.
A0017880
• You are in a menu at a selection level. Each time you press the keys simultaneously, you go up a level in the menu.

9.4.5 Navigation examples

Parameters with a picklist
Language 000 Operation
1  German "English" is set as the menu language (default value).
Spanish
A  in front of the menu text indicates the active option.
2 German Select the menu language "Spanish" using  or .
 Spanish
3  Spanish Confirm your choice with .
German
A  in front of the menu text indicates the active option ("Spanish" is the language selected). Exit edit mode for the parameter with .
35
Operation with an operating menu Deltabar FMD71, FMD72
Accepting the pressure present
Example: setting position adjustment.
Menu path: Main menu  Setup  Pos. Zero Adjust
Pos. Zero Adjust 007 Operation
1  Cancel The pressure for position adjustment is present at the device.
Confirm
2 Cancel Use  or  to switch to the "Confirm" option. The active option is
 Confirm
highlighted in black.
3 Adjustment has
been accepted!
4  Cancel Exit edit mode for the parameter with .
Confirm
Accept the applied pressure as a position adjustment with the  key. The device confirms the adjustment and goes back to the "Pos. zero adjust" parameter.
User-definable parameters
Example: setting parameter "Set URV (014)" from 100 mbar (1.5 psi) to 50 mbar (0.75 psi).
Menu path: Setup  Advanced. Setup  Current output  Set URV
Set URV 014 Operation
1
1 0 0 . 0 0 0
2
1 0 0 . 0 0 0
3
5 0 0 . 0 0 0
mbar
mbar
mbar
The onsite display shows the parameter to be changed. The "mbar" unit is defined in another parameter and cannot be changed here.
Press  or  to get to edit mode. The first digit is highlighted in black.
Use the  key to change "1" to "5". Press the  key to confirm "5". Cursor jumps to the next position. Use the  key to confirm (second position).
36
4
5 0 0 . 0 0 0
5
5 0¿. 0 0 0
6
5 0 . 0 0 0
mbar
mbar
mbar
The third digit is highlighted in black and can now be edited.
Use the  key to change to the "¿" symbol. Use  to save the new value and exit edit mode. See next graphic.
The new value for the full scale value is 50.0 mbar (0.75 psi). Exit edit mode for the parameter with . You can get back to edit mode with  or .

9.5 Operation using Endress+Hauser operating program

The FieldCare operating program is an Endress+Hauser plant asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard.
Hardware and software requirements can be found on the Internet:
Deltabar FMD71, FMD72 Operation with an operating menu
www.de.endress.com  Search: FieldCare  FieldCare  Technical data.
FieldCare supports the following functions:
• Configuration of transmitters in online/offline mode
• Loading and saving device data (upload/download)
• Documentation of the measuring point

9.6 Direct access to parameters

The parameters can only be accessed directly via the "Expert" user role.
Direct access (119)
Navigation Expert  Direct Access
Read permission Operators/Service engineers/Expert
Write permission Operators/Service engineers/Expert
Description Enter the direct access code to go directly to a parameter.
Options Enter the desired parameter code.
Factory setting 0
Note For direct access, it is not necessary to enter leading zeros.

9.7 Locking/unlocking operation

Once you have entered all the parameters, you can lock your entries against unauthorized and undesired access.
You have the following options for locking/unlocking operation:
• Via the DIP switch on the electronic insert, local at the device.
• Via the local display (optional)
• Via communication e.g. FieldCare and HART handheld terminal.
The symbol on the local display indicates that operation is locked. Parameters which refer to how the display appears, e.g. "Language" and "Display contrast", can still be altered.
If operation is locked by means of the DIP switch, you can only unlock operation again by means of the DIP switch. If operation is locked by means of local display or remote operation e.g. FieldCare, you can unlock operation either using the local display or remote operation.
The "Operator Code" parameter is used to lock and unlock the device.
The parameters can only be accessed directly via the "Expert" user role.
Operator Code (021)
Navigation Setup  Extended Setup  Operator Code
Read permission Operators/Service engineers/Expert
37
Operation with an operating menu Deltabar FMD71, FMD72
Write permission Operators/Service engineers/Expert
Description Use this function to enter a code to lock or unlock operation.
User entry
To lock: Enter a number ¹ the release code (value range: 1 to 9999).
• To unlock: Enter the release code.
Factory setting 0
Note The release code is "0" in the order configuration. Another release code can be defined in
the "Code Definition" parameter. If the user has forgotten the release code, the release code can be visible by entering the number "5864".
The release code is defined in the "Code Definition" parameter.
Code Definition (023)
Navigation Setup  Extended Setup  Code Definition
Read permission Operators/Service engineers/Expert
Write permission Operators/Service engineers/Expert
Description Use this function to enter a release code with which the device can be unlocked.
User entry A number from 0 to 9999
Factory setting 0

9.8 Resetting to factory settings (reset)

By entering a certain code, you can completely, or partially, reset the entries for the parameters to the factory settings "Diagnosis"  "Reset").
There are various reset codes for the device. The following table illustrates which parameters are reset by the particular reset codes. Operation must be unlocked to reset parameters (see "Locking/unlocking operation" section (  37)).
1)
. Enter the code via the "Reset" parameter (menu path:
1) . The factory setting for the individual parameters is specified in the parameter description
38
Deltabar FMD71, FMD72 Operation with an operating menu
Any customer-specific configuration carried out at the factory is not affected by a reset (customer-specific configuration remains). If you want to change the customer­specific configuration carried out at the factory, please contact Endress+Hauser Service.
Reset code
62 PowerUp reset (warm start)
333 User reset
7864 Total reset
1)
Description and effect
• The device is restarted.
• Data is read back anew from the EEPROM (process is reinitialized).
• Any simulation which may be running is ended.
• This code resets all the parameters apart from:
- Device tag (022)
- Linearization table
- Operating hours (162)
- Event logbook
- Curr. trim 4 mA (135)
- Curr. trim 20 mA (136)
- Lo trim sensor (131)
- Hi trim sensor (132)
- Lo trim sensor (277)
- Hi trim sensor (278)
• Any simulation which may be running is ended.
• The device is restarted.
• This code resets all the parameters apart from:
- Operating hours (162)
- Event logbook
- Lo trim sensor (131)
- Hi trim sensor (132)
- Lo trim sensor (277)
- Hi trim sensor (278)
• Any simulation which may be running is ended.
• The device is restarted.
1) To be entered in "System"  "Management"  "Reset" (124)
After a "Total reset" in FieldCare you have to press the "refresh" button in order to ensure that the measuring units are also reset.
39

Integrating transmitter using HART® protocol

Deltabar FMD71, FMD72
10
Integrating transmitter using HART® protocol
Version data for the device
Firmware version 01.00.zz • On the title page of the Operating instructions
• On nameplate
Firmware Version parameter Diagnostics  Device info Firmware version
Manufacturer ID 17 (0x11) Manufacturer ID. parameter
Diagnosis  Instrument info Manufacturer ID
Device type ID 39 (0x27) Parameter Device ID
Diagnosis  Instrument info  Device ID
HART protocol revision 6.0 ---
Device revision 1 • On transmitter nameplate
Device revision parameter Diagnostics  Device info  Device revision
The suitable device description file (DD) for the individual operating tools is listed in the table below, along with information on where the file can be acquired.
Operating tools
Operating tool Reference sources for device descriptions (DD and DTM)
FieldCare www.endress.com  Download Area
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
AMS Device Manager (Emerson Process Management)
SIMATIC PDM (Siemens)
Field Communicator 375, 475 (Emerson Process Management)
www.endress.com  Download Area
www.endress.com  Download Area
Use update function of handheld terminal

10.1 HART process variables and measured values

The following numbers are assigned to the process variables in the factory:
Process variable Pressure Level
Linear Table active
First process variable
(Primary variable)
differential pressure)
Second process variable
(Secondary variable)
Third process variable
(Tertiary variable)
Fourth process variable
(Quaternary variable)
0
(Measured
2
(Measured
pressure HP)
5
(Measured
pressure LP)
4
(Sensor
temperature HP)
8
(Level before
linearization)
0
(Measured
differential pressure)
2
(Measured
pressure HP)
5
(Measured
pressure LP)
(Tank content)
9
8
(Level before
linearization)
2
(Measured
pressure HP)
5
(Measured
pressure LP)
40
Deltabar FMD71, FMD72
Integrating transmitter using HART® protocol
The assignment of the device variables to the process variable is displayed in the Expert → Communication → HART output menu.
The assignment of the device variables to the process variable can be changed using HART command 51.
An overview of the possible device variables can be found in the following section.

10.2 Device variables and measured values

The following measured values are assigned to the individual device variables:
Device variable code Measured value
0 Measured differential pressure
1 Corrected pressure
2 Measured pressure HP
3 Sensor press. HP
4 Sensor temperature HP
5 Measured pressure LP
6 Sensor press. LP
7 Sensor temperature LP
8 Level before linearization
9 Tank content
10 Process density
11 Temperature of electronics
12 HART input value
The device variables can be queried from a HART® master using HART® command 9 or
33.
41
Commissioning Deltabar FMD71, FMD72

11 Commissioning

NOTICE
If a pressure smaller than the minimum permitted pressure or greater than the maximum permitted pressure is present at the device, the following messages are output in succession:
"S140 Working range P LP/HP" or "F140 Working range P LP/HP" (depending on the
setting in the "Alarm Behav. P" (050) parameter) "S841 Sensor range LP/HP" or "F841 Sensor range LP/HP" (depending on the setting in
the "Alarm Behav. P" (050) parameter) "S945/F945 Pressure limit LP"
"S971 Calibration"

11.1 Function check

Before commissioning your measuring point, ensure that the post-installation and post­connection check have been performed.
• "Post-installation check" checklist
• "Post-connection check" checklist

11.2 Unlocking/locking configuration

If the device is locked to prevent configuration, it must first be unlocked.

11.2.1 Locking/unlocking hardware

If the device is locked via the hardware (write protection switch) and an attempt is made to write to a parameter, the message "HW lock state is ON" appears.
In addition, the key symbol appears in the measured value display. To unlock, toggle the write protection switch, which is located under the display module (  37) .

11.2.2 Locking/unlocking software

If the device is locked via the software (device access code), the key symbol appears in the measured value display. If an attempt is made to write to a parameter, a prompt for the device access code appears. To unlock, enter the user-defined device access code. .

11.3 Commissioning without an operating menu

11.3.1 Pressure measuring mode

If no local display is connected, the following functions are possible via the three keys on the electronic insert or externally on the device:
• Position adjustment (zero point correction)
• Setting lower range value and upper range value
• Device reset, see "Function of the operating elements" section, table (  31).
• The pressure applied must be within the nominal pressure limits of the respective sensor module. See information on the nameplate.
• Operation must be unlocked, see "Unlocking/locking configuration" section (  42).
• The device is configured for the "Level" measuring mode as standard. You can change the measuring mode using the "Measuring mode" parameter, see "Commissioning with an operating menu" section (  45).
42
Deltabar FMD71, FMD72 Commissioning
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked and
readjusted if necessary.
Perform position adjustment (see information at the start of "Commissioning" section.)
1 Device is installed. Process pressure is not present.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 Applied pressure for position adjustment has been
accepted.
Setting lower range value.
1 Desired pressure for lower range value is present at device.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 Applied pressure for lower range value has been
accepted.
Applied pressure for position adjustment has not been
accepted. Observe the input limits.
Applied pressure for lower range value has not been
accepted. Observe the input limits.
Setting upper range value.
1 Desired pressure for upper range value is present at device.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 Applied pressure for upper range value has been
accepted.
Applied pressure for upper range value has not been
accepted. Observe the input limits.

11.3.2 Level measuring mode

If no local display is connected, the following functions are possible via the three keys on the electronic insert or externally on the device:
• Position adjustment (zero point correction)
• Setting the lower and upper pressure value and assigning to the lower or upper level value
• Device reset, see "Function of the operating elements" section, table (  31).
43
Commissioning Deltabar FMD71, FMD72
• The pressure applied must be within the nominal pressure limits of the respective sensor module. See information on the nameplate.
• Operation must be unlocked, see "Unlocking/locking configuration" section (  42).
• The  and  keys have a function only in the case of the "Calibration Mode Wet" setting. The keys have no function at other settings.
• "Overview of level measurement" (  48)
• The device is configured for the "Level" measuring mode as standard. You can change the measuring mode using the "Measuring mode" parameter, see "Commissioning with an operating menu" section. The following parameters are set to the following values at the factory: (  45).
- "Level Selection": In pressure
- "Calibration Mode": Wet "Unit Before Lin." or "Linear Range Limit": %
- "Empty Calib.": 0.0 (corresponds to 4 mA value)
- "Full Calib.": 100.0 (corresponds to 20 mA value)
- "Empty Pressure": 0.0
- "Full Pressure": 100.0 These parameters can be changed only via the local display or remote control, such as FieldCare.
• "Calibration Mode", "Level Type", "Empty Calib.", "Full Calib.", "Empty Pressure", and "Full Pressure" are parameter names that are used for the local display or remote control, such as FieldCare.
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked and
readjusted if necessary.
Perform position adjustment (see information at the start of "Commissioning" section.)
1 Device is installed. Process pressure is not present.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 Applied pressure for position adjustment has been
accepted.
Set the lower pressure value.
1 Desired pressure for lower pressure value ("Empty Pressure") is present at the device.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 Applied pressure was saved as the lower pressure value
("Empty Pressure") and assigned to the lower level value
("Empty Calib.").
Applied pressure for position adjustment has not been
accepted. Observe the input limits.
Applied pressure was not saved as the lower
pressure value. Observe the input limits.
44
Set the upper pressure value.
1 Desired pressure for upper pressure value ("Full Pressure" ) is present at device.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
Deltabar FMD71, FMD72 Commissioning
Set the upper pressure value.
4 Yes No
5 Applied pressure was saved as the upper pressure value
("Full Pressure") and assigned to the upper level value
("Full Calib.").
Applied pressure was not saved as the upper
pressure value. Observe the input limits.

11.4 Commissioning with an operating menu

Commissioning comprises the following steps:
• Function check (  42)
• Selecting the language, measuring mode, high-pressure side, and pressure engineering unit (  45)
• Position adjustment (  47)
• Configuring measurement: – Pressure measurement (  61) – Level measurement (  48)
11.5 Selecting the language, measuring mode, high-
pressure side, and pressure engineering unit

11.5.1 Configure language via onsite display

Language (000)
Navigation Main menu  Language
Write permission Operators/Service engineers/Expert
Description Select the menu language for the local display.
Options • English
• Another language (as selected when ordering the device)
• Possibly a third language (language of the manufacturing plant)
Factory setting English
45
Commissioning Deltabar FMD71, FMD72

11.5.2 Configuring language via operating tool (FieldCare)

A0017654-EN

11.5.3 Measuring mode selection

Measuring mode (005)
Navigation Setup  Measuring mode
Write permission Operators/Service engineers/Expert
Description Select the measuring mode.
The operating menu is structured differently depending on the measuring mode selected.
Options • Pressure
• Level
Factory setting Level
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in
the "Setup" operating menu and readjusted if necessary.

11.5.4 Defining the high-pressure side

High Press. Side (183)
Navigation Setup  High Press. Side
Write permission Operators/Service engineers/Expert
46
Deltabar FMD71, FMD72 Commissioning
Description Define which sensor module corresponds to the high-pressure side.
Options • Sensor module HP
• Sensor module LP
Factory setting Sensor module HP

11.5.5 Press. Eng. Unit selection

Press. Eng. Unit (125)
Navigation Setup  Press. Eng. Unit
Write permission Operators/Service engineers/Expert
Description Select the pressure engineering unit. If a new pressure engineering unit is selected, all
pressure-specific parameters are converted and displayed with the new unit.
Options • mbar, bar
• mmH2O, mH2O,
• in H2O, ftH2O
• Pa, kPa, MPa
• psi
• mmHg, inHg
• kgf/cm
Factory setting mbar, bar or psi depending on the sensor module nominal measuring range, or as per
order specifications
2

11.6 Pos. Zero Adjust

The pressure resulting from the orientation of the device can be corrected here.
Corrected press. (172)
Navigation Setup  Corrected Press.
Write permission Operators/Service engineers/Expert
Description Displays the measured pressure after the differential pressure buildup and position
adjustment.
Note If this value is not equal to "0", it can be corrected to "0" by the position adjustment.
Pos. Zero Adjust (007)
Navigation Setup  Pos. Zero Adjust
47
Commissioning Deltabar FMD71, FMD72
Write permission Operators/Service engineers/Expert
Description Position adjustment – the pressure difference between zero (set point) and the measured
differential pressure need not be known.
Options • Confirm
• Cancel
Example • Measured value = 2.2 mbar (0.033 psi)
• You correct the measured value via the "Pos. Zero Adjust" parameter with the "Confirm" option. This means that you are assigning the value 0.0 to the pressure present.
• Measured value (after pos. zero adjust) = 0.0 mbar
• The current value is also corrected.
Factory setting Cancel

11.7 Configuring level measurement

11.7.1 Information on level measurement

You have a choice of two methods for calculating the level: "In pressure" and "In height". The table in the "Overview of level measurement" section that follows provides you with an overview of these two measuring tasks.
• The limit values are not checked, i.e. the values entered must be appropriate for the sensor module and the measuring task for the device to be able to measure correctly.
• Customer-specific units are not possible.
• There is no unit conversion.
• The values entered for "Empty Calib./Full Calib.", "Empty Pressure/Full Pressure", "Empty Height/Full Height", and "Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a warning message displayed, if the values are too close together.

11.7.2 Overview of level measurement

Measuring task Level
Selection
Calibration is performed by entering two pressure-level value pairs.
Calibration is performed by entering the density and two height-level value pairs.
"In pressure"
"In height" • Calibration with
Measured variable options
Via the "Unit before lin. (025)" parameter (  85): %, level, volume or mass units.
Description Measured value
display
• Calibration with reference pressure (wet calibration) (  49)
• Calibration without reference pressure (dry calibration) (  51)
reference pressure (wet calibration) (  53)
• Calibration without reference pressure (dry calibration) (  55)
The measured value display and the "Level before lin (019)" (  82) parameter show the measured value.
48
Deltabar FMD71, FMD72 Commissioning
A
B

11.7.3 "In pressure" level selection Calibration with reference pressure (wet calibration)

Example:
In this example, the level in a tank should be measured in "m". The maximum level is 3 m (9.8 ft). The pressure range is derived from the level and the density of the medium. In this situation, the device sets the pressure range to 0 to 300 mbar (4.5 psi).
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled and emptied.
The values entered for "Empty Calib./Full Calib.", "Set LRV/Set URV", and the applied pressures must be at least 1% apart. The value will be rejected, and a warning message displayed, if the values are too close together. Further limit values are not checked, i.e. the values entered must be appropriate for the sensor module and the measuring task for the device to be able to measure correctly.
Description
1 Carrying out "Position adjustment"(  47)
2 Select the "Level" measuring mode via the
"Measuring mode (005)" parameter. Menu path: Setup  Measuring Mode
3 Select a pressure engineering unit via the
"Press Eng. Unit (125)" parameter, here "mbar" for example. Menu path: Setup  Press Eng. Unit
4 Select the "In pressure" level mode via the "Level
Selection (024)" parameter. Menu path: Setup  Extended Setup  Level  Level Selection.
A0017661
A See table, step 7. B See table, step 8.
49
Commissioning Deltabar FMD71, FMD72
C
D
E
F
h
p
i
h
Description
5 Select a level unit via the "Unit before lin.
(025)" parameter, here "m" for example. Menu path: Setup  Extended Setup  Level Unit Before Lin.
6 Select the "Wet" option via the "Calibration
mode (027)" parameter. Menu path: Setup  Extended Setup  Level  Calibration Mode
7 The vessel is filled to the lower calibration
point. The pressure here is, for example, 0 mbar (0 psi).
Select "Empty Calib. (028)" parameter. Menu path: Setup  Extended Setup  Level  Empty Calibration
Enter the level value, here 0 m for example. The pressure value present is assigned to the lower level value by confirming the value.
8 The vessel is filled to the upper calibration
point. The pressure here is, for example, 300 mbar (4.35 psi).
Select the "Full Calib. (031)" parameter. Menu path: Setup  Extended Setup  Level  Full Calibration
Enter the level value, here 3 m (9.8 ft) for example. The pressure value present is assigned to the upper level value by confirming the value.
9 If calibration is performed with a medium
other than the process medium, enter the density of the calibration medium in "Adjust density (034)". Menu path: Setup  Extended Setup  Level  Adjust Density
10 Use the "Set LRV (166)" parameter to set the
level value for the lower current value (4 mA) (0 m (0 ft)). Menu path: Setup  Extended Setup  Current Output  Set LRV
11 Use the "Set URV (167)" parameter to set the
level value for the upper current value (20 mA) (3 m (9.8 ft)). Menu path: Setup  Extended Setup  Current Output  Set URV
12 If the process uses a medium other than that
on which the calibration was based, the new density must be specified in the "Process Density (035)" parameter. Menu path: Setup  Extended Setup  Level  Process Density.
13 Result:
The measuring range is set for 0 to 3 m (9.8 ft).
C See table, step 7. D See table, step 8. E See table, step 10. F See table, step 11. h Height i Current value p Pressure
A0017658
For this level mode, the measured variables %, level, volume and mass are available, see "Unit before lin. (025)" (  85).
50
Deltabar FMD71, FMD72 Commissioning
A
B

11.7.4 "In pressure" level selection Calibration without reference pressure (dry calibration)

Example:
In this example, the volume in a tank should be measured in liters. The maximum volume of 1000 liters (264 gal) corresponds to a pressure of 450 mbar (6.53 psi). The minimum volume of 0 liters corresponds to a pressure of 50 mbar (0.73 psi) since the device is mounted below the start of the level measuring range.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration i.e. the pressure and volume values for the lower and
upper calibration point must be known.
• The values entered for "Empty Calib./Full Calib.", "Empty Pressure/Empty Pressure" and "Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a warning message displayed, if the values are too close together. Further limit values are not checked, i.e. the values entered must be appropriate for the sensor module and the measuring task for the device to be able to measure correctly.
• Due to the orientation of the device, there may be pressure shifts in the measured value, i.e. when the vessel is empty or partly filled, the measured value is not zero. For information on how to perform position adjustment, see (  47).
Description
1 Select the "Level" measuring mode via the
"Measuring mode (005)" parameter. Menu path: Setup  Measuring Mode
2 Select a pressure engineering unit via the
"Press Eng. Unit (125)" parameter, here "mbar" for example. Menu path: Setup  Press Eng. Unit
3 Select the "In pressure" level mode via the "Level
Selection (024)" parameter. Menu path: Setup  Extended Setup  Level  Level Selection.
4 Select a volume unit via the "Unit before lin.
(025)" parameter, here "l" (liters) for example. Menu path: Setup  Extended Setup  Level Unit Before Lin.
A0017661
A See table, steps 6 and 7. B See table, steps 8 and 9.
51
Commissioning Deltabar FMD71, FMD72
C
D
E
F
G
H
v
p
i
v
Description
5 Select the "Dry" option via the "Calibration mode
(027)" parameter. Menu path: Setup  Extended Setup  Level  Calibration Mode
6 Enter the volume value for the lower
calibration point via the "Empty Calib. (028)" parameter, here 0 liters for example. Menu path: Setup  Extended Setup  Level  Empty Calibration
7 Enter the pressure value for the lower
calibration point via the "Empty Pressure (029)" parameter, here 50 mbar (0.75 psi), for example. Menu path: Setup  Extended Setup  Level  Empty Pressure
8 Enter the volume value for the upper
calibration point via the "Full Calib. (031)" parameter, here 1000 liters (264 gal) for example. Menu path: Setup  Extended Setup  Level  Full Calibration
9 Enter the pressure value for the upper
calibration point via the "Full Pressure (032)" parameter, here 450 mbar (6.75 psi), for example. Menu path: Setup  Extended Setup  Level  Full Pressure
10 "Adjust density (034)" contains the factory
setting 1.0, but this value can be changed if required. Menu path: Setup  Extended Setup  Level  Adjust Density
11 Set the volume value for the lower current
value (4 mA) via the "Set LRV (166)" parameter (0 l). Menu path: Setup  Extended Setup  Current Output  Set LRV
12 Set the volume value for the upper current
value (20 mA) via the "Set URV (167)" parameter (1000 l (264 gal)). Menu path: Setup  Extended Setup  Current Output  Set URV
13 If the process uses a medium other than that
on which the calibration was based, the new density must be specified in the "Process Density" parameter. Menu path: Setup  Extended Setup  Current Output  Process Density.
14 Result:
The measuring range is set for 0 to 1000 l (264 gal).
C See table, step 6. D See table, step 7. E See table, step 8. F See table, step 9. G See table, step 11. H See table, step 12. i Current value p Pressure v Volume
A0017662
For this level mode, the measured variables %, level, volume and mass are available, see "Unit before lin. (025)" (  85).
52
Deltabar FMD71, FMD72 Commissioning
A
B

11.7.5 "In height" level selection Calibration with reference pressure (wet calibration)

Example:
In this example, the volume in a tank should be measured in liters. The maximum volume of 1000 liters (264 gal) corresponds to a level of 4.5 m (15 ft). The minimum volume of 0 liters corresponds to a level of 0.5 m (1.6 ft) since the device is mounted below the start of the level measuring range. The density of the fluid is 1 g/cm3 (1 SGU).
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled and emptied.
The values entered for "Empty Calib./Full Calib.", "Set LRV/Set URV", and the applied pressure values must be at least 1% apart. The value will be rejected, and a warning message displayed, if the values are too close together. Further limit values are not checked, i.e. the values entered must be appropriate for the sensor module and the measuring task for the device to be able to measure correctly.
Description
1 Perform "position adjustment" (  47).
2 Select the "Level" measuring mode via the
"Measuring mode (005)" parameter. Menu path: Setup  Measuring Mode
3 Select a pressure engineering unit via the
"Press Eng. Unit (125)" parameter, here "mbar" for example. Menu path: Setup  Press Eng. Unit
4 Select the "In height" level mode via the "Level
selection (024)" parameter. Menu path: Setup  Extended Setup  Level  Level Selection.
A0017661
A See table, step 8. B See table, step 9.
53
Commissioning Deltabar FMD71, FMD72
h
p
v
h
i
v
C
D
E
F
G
Description
5 Select a volume unit via the "Unit before lin.
(025)" parameter, here "l" (liters) for example. Menu path: Setup  Extended Setup  Level Unit Before Lin.
6 Select a level unit via the "Height unit (026)"
parameter, here "m" for example. Menu path: Setup  Extended Setup  Level  Height Unit
7 Select the "Wet" option via the "Calibration
mode (027)" parameter. Menu path: Setup  Extended Setup  Level  Calibration Mode
8 Vessel is filled up to 0.5 m (1.6 ft), (49 mbar
(0.72 psi)).
Enter the volume value for the lower calibration point via the "Empty Calib. (028)" parameter, here 0 liters for example. Menu path: Setup  Extended Setup  Level  Empty Calibration
9 Vessel is filled up to 4.5 m (15 ft), (441 mbar
(6.40 psi)).
Enter the volume value for the upper calibration point via the "Full Calib. (031)" parameter, here "1000 liters" (264 gal), for example. Menu path: Setup  Extended Setup  Level  Full Calibration
10 Enter the density of the calibration medium in
"Adjust density (034)", here 1 g/cm3 (1 SGU), for example. Menu path: Setup  Extended Setup  Level  Adjust Density
11 Set the volume value for the lower current
value (4 mA) via the "Set LRV (166)" parameter (0 l). Menu path: Setup  Extended Setup  Current Output  Set LRV
12 Set the volume value for the upper current
value (20 mA) via the "Set URV (167)" parameter (1000 l (264 gal)). Menu path: Setup  Extended Setup  Current Output  Set URV
13 If the process uses a medium other than that
on which the calibration was based, the new density must be specified in the "Process Density (035)" parameter. Menu path: Setup  Extended Setup  Level  Process Density.
14 Result:
The measuring range is set for 0 to 1000 l (264 gal).
C See table, step 10. D See table, step 8. E See table, step 9. F See table, step 11. G See table, step 12. h Height i Current value p Pressure v Volume
For this level mode, the measured variables %, level, volume and mass are available, see "Unit before lin. (025)" (  85).
A0017666
54
Deltabar FMD71, FMD72 Commissioning
A
B

11.7.6 "In height" level selection Calibration without reference pressure (dry calibration)

Example:
In this example, the volume in a tank should be measured in liters. The maximum volume of 1000 liters (264 gal) corresponds to a level of 4.5 m (15 ft). The minimum volume of 0 liters corresponds to a level of 0.5 m (1.6 ft) since the device is mounted below the start of the level measuring range.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration i.e. the height and volume values for the lower and upper
calibration point must be known.
• The values entered for "Empty Calib./Full Calib.", "Empty height/Full height" and "Set
LRV/Set URV" must be at least 1% apart. The value will be rejected, and a warning message displayed, if the values are too close together. Further limit values are not checked, i.e. the values entered must be appropriate for the sensor module and the measuring task for the device to be able to measure correctly.
• Due to the orientation of the device, there may be pressure shifts in the measured value,
i.e. when the vessel is empty or partly filled, the measured value is not zero. For information on how to perform position adjustment, see (  47).
Description
1 Select the "Level" measuring mode via the
"Measuring mode (005)" parameter. Menu path: Setup  Measuring Mode
2 Select a pressure engineering unit via the
"Press Eng. Unit (125)" parameter, here "mbar" for example. Menu path: Setup  Press Eng. Unit
3 Select the "In height" level mode via the "Level
selection (024)" parameter. Menu path: Setup  Extended Setup  Level  Level Selection.
4 Select a volume unit via the "Unit before lin.
(025)" parameter, here "l" (liters) for example. Menu path: Setup  Extended Setup  Level Unit Before Lin.
A0017661
A See table, steps 7 and 8. B See table, steps 9 and 10.
55
Commissioning Deltabar FMD71, FMD72
h
p
v
h
i
v
C
D
E
F
G
Description
5 Select a level unit via the "Height unit (026)"
parameter, here "m" for example. Menu path: Setup  Extended Setup  Level  Height Unit
6 Select the "Dry" option via the "Calibration mode
(027)" parameter. Menu path: Setup  Extended Setup  Level  Calibration Mode
7 Enter the volume value for the lower
calibration point via the "Empty Calib. (028)" parameter, here 0 liters for example. Menu path: Setup  Extended Setup  Level  Empty Calibration
8 Enter the height value for the lower calibration
point via the "Empty height (030)" parameter, here 0.5 m (1.6 ft) for example. Menu path: Setup  Extended Setup  Level  Empty Height
9 Enter the volume value for the upper
calibration point via the "Full Calib. (031)" parameter, here 1000 liters (264 gal) for example. Menu path: Setup  Extended Setup  Level  Full Calibration
10 Enter the height value for the upper calibration
point via the "Full height (033)" parameter, here 4.5 m (15 ft) for example. Menu path: Setup  Extended Setup  Level  Full Height
11 Enter the density of medium via the "Adjust
density (034)" parameter, here "1 g/cm3" (1 SGU) for example. Menu path: Setup  Extended Setup  Level  Adjust Density
12 Set the volume value for the lower current
value (4 mA) via the "Set LRV (166)" parameter (0 l). Menu path: Setup  Extended Setup  Current Output  Set LRV
13 Set the volume value for the upper current
value (20 mA) via the "Set URV (167)" parameter (1000 l (264 gal)). Menu path: Setup  Extended Setup  Current Output  Set URV
13 If the process uses a medium other than that
on which the calibration was based, the new density must be specified in the "Process Density" parameter. Menu path: Setup  Extended Setup  Current Output  Process Density.
14 Result:
The measuring range is set for 0 to 1000 l (264 gal).
C See table, step 11. D See table, step 7. E See table, step 9. F See table, step 12. G See table, step 13. h Height i Current value p Pressure v Volume
A0017666
For this level mode, the measured variables %, level, volume and mass are available, see "Unit before lin. (025)" (  85).
56
Deltabar FMD71, FMD72 Commissioning
B
A

11.7.7 Calibration with partially-filled vessel (wet calibration)

Example:
This example explains a wet calibration for cases in which it is not possible to empty the vessel and then fill it to 100%. During this wet calibration, a level of 20% is used as the calibration point for "Empty" and a level of "80%" is used as the calibration point for "Full". The calibration is then extended to 0% to 100% and lower range-value (LRV)/upper range-value (URV) are adapted accordingly.
Prerequisite:
• The default value in level mode for the calibration mode is "Wet".
• This value can be adjusted: Menu path: Setup  Extended Setup  Level  Calibration
Mode
Description
1 Select the "Level" measuring mode via the
"Measuring mode (005)" parameter. Menu path: Setup  Measuring Mode
2 Select a unit via the "Unit before lin. (025)"
parameter, here "%" for example. Menu path: Setup  Extended Setup  Level Unit Before Lin.
3 20% of the vessel is full. Enter the level value
for the lower calibration value via the "Empty Calib. (028)" parameter, here 20% for example. Menu path: Setup  Extended Setup  Level  Empty Calibration
4 80% of the vessel is full. Enter the level value
for the upper calibration value via the "Full Calib. (031)" parameter, here 80% for example. Menu path: Setup  Extended Setup  Level  Full Calibration
5 The pressure values for full/empty calibration
are automatically recorded and applied. The upper range value (URV) and lower range value (LRV) automatically accept the values that were entered in "Empty Calib. (028)" and "Full Calib. (031)". These automatically entered values can be edited if necessary and, for example, changed to a value ranging from 0 to 100%.
A0017668
A See table, step 3 B See table, step 4
If the process uses a medium other than that on which the calibration was based, the new density must be specified in the "Process Density (035)" parameter. In this case, you have to enter the various densities via the following menu path:
• Setup  Extended Setup  Level Adjust Density (034) (e.g. 1.0 kg/l for water)
• Setup  Extended Setup  Level  Process Density (035) (e.g. 0.8 kg/l for oil)
57
Commissioning Deltabar FMD71, FMD72
v
h

11.8 Linearization

11.8.1 Manual entry of a linearization table

Example:
In this example, the volume in a tank with a conical outlet should be measured in m3.
Prerequisite:
• This is a theoretical calibration, i.e. the points for the linearization table are known.
• The "Level" measuring mode has been selected.
• A level calibration has been performed.
• The linearization characteristic must rise or fall continuously.
• For a description of the parameters mentioned, see the "Description of device parameters" section (  78).
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in
the "Setup" operating menu and readjusted if necessary.
Description
1 Select the "Manual entry" option via the "Lin.
mode (037)" parameter. Menu path: Setup  Extended Setup  Linearization  Lin. Mode
2 Select using the "Unit after lin. (038)"
parameter, e.g. m3. Menu path: Setup  Extended Setup  Linearization  Unit After Lin.
3 Enter the number of the point in the table (e.g.
1) via the "Line numb. (039)" parameter. Menu path: Setup  Extended Setup  Linearization  Line-numb
The level is entered via the "X-value (040)" parameter, here 0 m for example. Confirm your entry. Menu path: Setup  Extended Setup  Linearization  X-value
Using the "Y-val. (041)" parameter, enter the corresponding volume value, here 0 m3 for example, and confirm the value. Menu path: Setup  Extended Setup  Linearization  Y-val.
A0017669
h Height v Volume
58
Deltabar FMD71, FMD72 Commissioning
v
h
i
v
Description
4 To enter another point in the table, select the
"Next point" option via the "Edit Table (042)" parameter. Enter the next point as explained in Step 3. Menu path: Setup  Extended Setup  Linearization  Edit Table
5 Once all the points have been entered in the
table, select the "Activate table" option via the "Lin. mode (037)" parameter. Menu path: Setup  Extended Setup  Linearization  Lin. Mode
6 Result:
Result: The measured value after linearization is displayed.
A0017670
h Height i Current value v Volume
• Error message F510 "Linearization" and alarm current as long as the table is being entered and until the table is activated.
• Error message F511/F512 "Linearization" and alarm current as long as the linearization table consists of fewer than 2 points.
• The lower range value (= 4mA) is defined by the smallest point in the table. The upper range value (= 20mA) is defined by the greatest point in the table.
• Using the parameters "Set LRV" and "Set URV", you can change the allocation of the volume/mass values to the current values.

11.8.2 Manual entry of a linearization table via operating tool

Using an operating tool based on FDT technology (e.g. FieldCare), you can enter linearization using a module specially designed for this purpose. This provides you with an overview of the selected linearization, even during entry. In addition, it is possible to configure different tank shapes in FieldCare (menu "Device Operation"  "Device Functions"  "Additional Functions"  "Linearization Table".
The linearization table may also be entered manually point by point in the operating tool menu (see (  58) section).

11.8.3 Semi-automatic entry of a linearization table

Example:
In this example, the volume in a tank with a conical outlet should be measured in m3.
59
Commissioning Deltabar FMD71, FMD72
v
h
v
h
i
v
Prerequisite:
• The tank can be filled or emptied. The linearization characteristic must rise or fall continuously.
• The "Level" measuring mode has been selected.
• Level calibration is performed (see section from (  48))
• For a description of the parameters mentioned, see the "Description of device parameters" section (  78).
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in
the "Setup" operating menu and readjusted if necessary.
Description
1 Select the "Semiautom. entry" option via the
"Lin. mode (037)" parameter. Menu path: Setup  Extended Setup  Linearization  Lin. Mode
2 Select using the "Unit after lin. (038)"
parameter, e.g. m3. Menu path: Setup  Extended Setup  Linearization  Unit After Lin.
3 Fill the tank to the height of the 1st point.
A0017669
h Height v Volume
4 Enter the number of the point in the table (e.g.
1) via the "Line numb. (039)" parameter. Menu path: Setup  Extended Setup  Linearization  Line-numb
The level at the current time is displayed using the "X-value (193)" parameter. Menu path: Setup  Extended Setup  Linearization  X-value
Using the "Y-val. (041)" parameter, enter the corresponding volume value, here 0 m3 for example, and confirm the value. Menu path: Setup  Extended Setup  Linearization  Y-val.
5 To enter another point in the table, continue
filling the tank and select the "Next point" option via the "Edit Table (042)" parameter. Enter the next point as explained in Step 4. Menu path: Setup  Extended Setup  Linearization  Edit Table
6 Once all the points have been entered in the
table, select the "Activate table" option via the "Lin. mode (037)" parameter. Menu path: Setup  Extended Setup  Linearization  Lin. Mode
7 Result:
Result: The measured value after linearization is displayed.
A0017670
h Height i Current value v Volume
60
Deltabar FMD71, FMD72 Commissioning
i
p
A
B
• Error message F510 "Linearization" and alarm current as long as the table is being entered and until the table is activated.
• The lower range value (= 4mA) is defined by the smallest point in the table. The upper range value (= 20mA) is defined by the greatest point in the table.
• Using the parameters "Set LRV" and "Set URV", you can change the allocation of the volume/mass values to the current values.

11.9 Configuring pressure measurement

11.9.1 Calibration without reference pressure (dry calibration)

Example:
In this example, a device with a 400 mbar (6 psi) sensor module is configured for the 0 to +300 mbar (4.4 psi) measuring range, i.e. the 4 mA value and the 20 mA value are assigned 0 mbar and 300 mbar (4.4 psi) respectively.
Prerequisite:
This is a theoretical calibration, i.e. the pressure values for the lower and upper range are known. It is not necessary to apply pressure.
Due to the orientation of the device, there may be pressure shifts in the measured value, i.e. the measured value is not zero in a pressureless condition. For information on how to perform position adjustment, see Pos. Zero Adjust(  47) section.
Description
1 Select the "Level" measuring mode via the
"Measuring mode (005)" parameter. Menu path: Setup  Measuring Mode
2 Select a pressure engineering unit via the
"Press Eng. Unit (125)" parameter, here "mbar" for example. Menu path: Setup  Press Eng. Unit
3 Select "Set LRV (013)" parameter.
Menu path: Setup  Set LRV
Enter and confirm the value (here 0 mbar (0 psi)) for the "Set LRV" parameter. This pressure value is assigned to the lower current value (4 mA).
4 Select the "Set URV (014)" parameter.
Menu path: Setup  Set URV
Enter and confirm the value (here 300 mbar (4.5 psi)) for the "Set URV (014)" parameter. This pressure value is assigned to the upper current value (20 mA).
5 Result:
The measuring range is configured for 0 to +300 mbar (4.5 psi).
A0017671
A See table, step 3. B See table, step 4. i Current value p Pressure
61
Commissioning Deltabar FMD71, FMD72
i
p
A
B

11.9.2 Calibration with reference pressure (wet calibration)

Example:
In this example, a device with a 400 mbar (6 psi) sensor module is configured for the 0 to +300 mbar (4.4 psi) measuring range, i.e. the 4 mA value and the 20 mA value are assigned 0 mbar and 300 mbar (4.4 psi) respectively.
Prerequisite:
The pressure values 0 mbar and 300 mbar (4.4 psi) can be specified. For example, the device is already installed.
For a description of the parameters mentioned, see the "Description of device parameters" section (  78).
Description
1 Perform position adjustment (  47).
2 Select the "Pressure" measuring mode via the
"Measuring mode (005)" parameter. Menu path: Setup  Measuring Mode
3 Select a pressure engineering unit via the
"Press Eng. Unit (125)" parameter, here "mbar" for example. Menu path: Setup  Press Eng. Unit
4 The pressure for the LRV (4 mA value) is
present at the device, here 0 mbar (0 psi) for example.
Select the "Get LRV (015)" parameter. Menu path: Setup  Extended Setup  Current output  Get LRV.
Confirm the present value by selecting "Apply". The present pressure value is assigned to the lower current value (4 mA).
5 The pressure for the URV (20 mA value) is
present at the device, here 300 mbar (4.4 psi) for example.
Select the "Get URV (016)" parameter. Menu path: Setup  Extended Setup  Current output  Get URV
Confirm the present value by selecting "Apply". The present pressure value is assigned to the upper current value (20 mA).
6 Result:
The measuring range is configured for 0 to +300 mbar (4.5 psi).
A See table, step 4. B See table, step 5. i Current value p Pressure
A0017671

11.10 Backing up or duplicating the device data

The following options are available to you with an operating tool that is based on FDT technology (e.g. FieldCare):
• Storage/recovery of configuration data.
Download select. (visible only in FieldCare)
62
• Duplication of device parameters.
• Transfer of all relevant parameters when replacing electronic inserts.
Use the following parameter for this:
Deltabar FMD71, FMD72 Commissioning
Navigation
Write permission Operators/Service engineers/Expert
Description Selection of data packages for up/download function in Fieldcare and PDM.
Prerequisite DIP switch set to "SW" and "Damping" set to "on". If you download using the factory setting
Options • Configuration copy: This option overwrites general configuration parameters with the
Factory setting Configuration copy
Expert  System  Management  Download select.
"Configuration copy", all parameters required for a measurement will be downloaded. The functionality of the "Electronics replace" setting is reserved for Endress+Hauser Service and can be accessed only if the correct device access code is entered.
exception of the serial number, order number, calibration, pos. zero adjust, application and day information.
• Device replacement: This option overwrites general configuration parameters with the exception of the serial number, order number, calibration and pos. zero adjust.
• Electronics replace: This option overwrites general configuration parameters.

11.11 Configuring the local display

11.11.1 Adjusting the onsite display

The onsite display can be adjusted in the following menu:
Display/operat. (  73)

11.12 Protecting settings from unauthorized access

The settings can be protected from unauthorized access in two ways:
• Locking via write protection switch (hardware locking)
• Locking via parameter (software locking)
63
Diagnostics and troubleshooting Deltabar FMD71, FMD72

12 Diagnostics and troubleshooting

12.1 Troubleshooting

General errors
Error Possible cause Remedy
Device is not responding. Supply voltage does not match that
specified on the nameplate.
Supply voltage has incorrect polarity. Reverse polarity of supply voltage.
Connecting cables are not in contact with the terminals.
No display Onsite display is set too bright or too
dark.
Connector for local display is not properly connected.
Onsite display is defective. Replace onsite display.
Output current < 3.6 mA Signal line is not wired correctly. Check wiring.
Electronics unit is defective. Replace electronics.
HART communication is not working.
Device measures incorrectly. Configuration error Check and correct parameter
Missing or incorrectly installed communication resistor.
Commubox is not properly connected. Connect Commubox correctly .
Commubox is not set to "HART". Set Commubox selector switch to
Apply correct voltage.
Check the connection of the cables and correct if necessary.
• Set the local display brighter by simultaneously pressing  and .
• Set the local display darker by simultaneously pressing  and .
Ensure connector is properly connected.
Install the communication resistor (250 Ω) correctly.
"HART".
configuration (see below).

12.2 Diagnostic events

12.2.1 Diagnostic message

Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the measured value display.
Status signals
The table (  65) lists the messages that can occur. The ALARM STATUS parameter shows the message with the highest priority. The device has four different status information codes according to NE107:
"Failure"
A device error has occurred. The measured value is no longer valid.
A0013956
"Maintenance required"
Maintenance is required. The measured value is still valid.
A0013957
"Function check"
The device is in service mode (e.g. during a simulation).
A0013959
"Out of specification"
The device is being operated:
• Outside its technical specifications (e.g. during warmup or cleaning processes).
A0013958
• Outside the parameter configuration undertaken by the user (e.g. level outside of configured range)
64
Deltabar FMD71, FMD72 Diagnostics and troubleshooting
Diagnostics event and event text
The fault can be identified by means of the diagnostic event. The event text helps you by providing information about the fault.
Diagnostic event
Status signal Event number Event text
Example
A0013958
841 Sensor range
3-digit number
If two or more diagnostic events are pending simultaneously, only the message with the highest priority is shown. Other diagnostic messages that are pending can be viewed in the Diagnostic list submenu (  93).
Past diagnostic messages that are no longer pending are shown in the Event logbook submenu (  94).

12.2.2 List of diagnostic events

General messages
Diagnostic event Cause Corrective measure
Code Description
0 No error - -
"F" messages
Diagnostic event Cause Corrective measure
Code Description
F002 Sens. unknown
LP/HP
F062 Sensor conn. • Electromagnetic effects are greater than
F081 Initialization • Electromagnetic effects are greater than
F083 Permanent mem.
LP/HP
F140 Working range P
LP/HP
F162 Sensor conn. • Sensor module defective (master).
Sensor module does not suit the device (electronic sensor module nameplate).
specifications in the technical data. This message appears for a short time only.
• Sensor module defective.
• Cable connection between sensor module and main electronics disconnected.
specifications in the technical data. This message appears for a short time only.
• Sensor module defective.
• Cable connection between sensor module and main electronics disconnected.
• Electromagnetic effects outside the permitted range. This message appears for a short time only.
• Sensor module defective.
• Overpressure and low pressure present.
• Electromagnetic effects outside the permitted range.
• Sensor module defective.
• Electromagnetic effects outside the permitted range. This message appears for a short time only.
Contact Endress+Hauser Service
• Contact Endress+Hauser Service
• Replace electronics
• Check the sensor module cable
• Contact Endress+Hauser Service
• Check sensor cable
• Perform a reset
• Contact Endress+Hauser Service
• Restart the device
• Check the process pressure
• Check sensor module range
• Check sensor cable
• Replace sensor
• Contact Endress+Hauser Service
65
Diagnostics and troubleshooting Deltabar FMD71, FMD72
Diagnostic event Cause Corrective measure
Code Description
F162 Sensor conn. HP
Sensor conn. LP
F163 Sensor conn. • Cable connection between sensor modules HP and
F164 Sensor sync. • The sensor modules cannot be synchronized with
F165 Sensor
assignment
F261 Electronics
module
F282 Memory • Main electronics defective.
F283 Memory content • Main electronics defective.
F411 Upload/download • The file is defective.
F510 Linearization The linearization table is being edited. • Conclude entries
F511 Linearization The linearization table consists of less than 2 points. • Table too small
F512 Linearization The linearization table is not monotonic increasing
F841 Sensor range • Overpressure or low pressure present.
F882 Input signal External measured value is not received or displays a
F945 Pressure limit LP • The configured overpressure or underpressure
• Electromagnetic effects outside the permitted range. This message appears for a short time only.
• Sensor module defective.
LP interrupted.
• Sensor module defective (slave).
• Electromagnetic effects outside the permitted range. This message appears for a short time only.
each other.
• Electromagnetic effects outside the permitted range. This message appears for a short time only.
• Sensor module(s) defective.
The assignment of the transmitter to sensor module LP or HP is unknown (e.g. after changing the sensor module). See also (  70) "Replacement of sensor modules".
• Main electronics defective.
• Fault in the main electronics.
• Sensor module defective.
• Fault in the main electronics.
• Electromagnetic effects are greater than specifications in the technical data.
• The supply voltage is disconnected when writing.
• An error occurred when writing.
• During the download, the data are not correctly transmitted to the processor, e.g. because of open cable connections, spikes (ripple) on the supply voltage or electromagnetic effects.
or decreasing.
• Sensor module defective.
failure status.
limit of sensor module LP is exceeded.
• Sensor module LP defective.
• Check sensor cable
• Replace sensor
• Contact Endress+Hauser Service
• Restart the device
• Check the sensor module cable
• Contact Endress+Hauser Service
• Restart the device
• Replace sensor module
• Contact Endress+Hauser Service
• Connect transm. set.
• Restart the device
• Contact Endress+Hauser Service
• Restart the device
• Replace electronics
• Replace electronics
• Restart the device
• Perform a reset
• Replace electronics
• Repeat download
• Use other file
• Perform a reset
• Select "linear"
• Correct table
• Accept the table
• Tab. not monotonic
• Correct table
• Accept the table
• Check the pressure value
• Contact Endress+Hauser Service
• Check the bus
• Check source device
• Check the setting
• Check the pressure value
• Change pressure limit value
• Contact Endress+Hauser Service
66
Deltabar FMD71, FMD72 Diagnostics and troubleshooting
"M" messages
Diagnostic event Cause Corrective measure
Code Description
M002 Sens. unknown Sensor module does not suit the device (electronic
sensor module nameplate). Device continues measuring.
M283 Memory
content
M431 Adjustment The calibration carried out would cause the nominal
M434 Scaling • Values for calibration (e.g. lower range value and
M438 Data record • The supply voltage is disconnected when writing.
• Cause as indicated for F283.
• Correct measurement can continue as long as you do not need the peakhold indicator function.
sensor module range to be exceeded or undershot.
upper range value) are too close together.
• Lower range value and/or upper range value undershoot or overshoot the sensor module range limits.
• The sensor module was replaced and the customer­specific configuration does not suit the sensor.
• Unsuitable download carried out.
• An error occurred when writing.
Contact Endress+Hauser Service
• Perform a reset
• Replace electronics
• Check the measuring range
• Check position adjustment
• Check the setting
• Check the measuring range
• Check the setting
• Contact Endress+Hauser Service
• Check the setting
• Restart the device
• Replace electronics
"C" messages
Diagnostic event Cause Corrective measure
Code Description
C412 Write Backup Downloading. Wait for download to
complete.
C482 Simul. output Simulation of the current output is switched on, i.e. the
device is not measuring at present.
C484 Error simul. Fault state simulation is switched on, i.e. the device is
not measuring at present.
C824 Process pressure • Electromagnetic effects outside the permitted range.
• Overpressure or low pressure present.
• This message appears for a short time only.
End the simulation
End the simulation
• Check the pressure value
• Restart the device
• Perform a reset
"S" messages
Diagnostic event Cause Corrective measure
Code Description
S110 Operational
range T
S140 Working range P
LP/HP
S822 Process temp.
LP/HP
• Electromagnetic effects outside the permitted range.
• Sensor module defective.
• Overpressure or low pressure present.
• Electromagnetic effects outside the permitted range.
• Sensor module defective.
• The temperature measured in the sensor module is greater than the upper nominal temperature of the sensor module.
• The temperature measured in the sensor module is smaller than the lower nominal temperature of the sensor module.
• Check the process pressure
• Check the temperature range
• Check the process pressure
• Check the pressure value
• Check temperature
• Check the setting
67
Diagnostics and troubleshooting Deltabar FMD71, FMD72
Diagnostic event Cause Corrective measure
Code Description
S841 Sensor range • Overpressure or low pressure present.
• Sensor module defective.
S945 Pressure limit LP • The configured overpressure or underpressure
limit of sensor module LP is exceeded.
• Sensor module LP defective.
S971 Adjustment • The current is outside the permitted range from
3.8 to 20.5 mA.
• The present pressure value is outside the configured measuring range (but within the sensor module range, if applicable).
• Check the pressure value
• Contact Endress+Hauser Service
• Check the pressure value
• Change pressure limit value
• Contact Endress+Hauser Service
• Check the pressure value
• Check the measuring range
• Check the setting

12.3 Response of output to errors

The behavior of the current output in case of fault is defined by the following parameters:
• "Alarm Behav. P (050)" (  91)
• "Output fail mode (190)" (  102)
• "High Alarm Curr. (052)" (  91)

12.4 Firmware history

Date Firmware version Modifications Documentation
Operating Instructions Description of Device Parameters
01.2012 01.00.00 Original firmware. Can be operated using FieldCare from version 2.08.00
BA01044P/00/EN/01.12 GP01013P/00/EN/01.12
BA01044P/00/EN/02.12 GP01013P/00/EN/02.12
BA01044P/00/EN/03.12 GP01013P/00/EN/03.12
BA01044P/00/EN/04.12 GP01013P/00/EN/04.12

12.5 Disposal

When disposing, separate and recycle the device components based on the materials.
68
Deltabar FMD71, FMD72 Maintenance
1
1
1

13 Maintenance

No special maintenance work is required.
Keep the pressure compensation (only sensor modules) and GORE-TEX® filter (1) free from contamination.
A0017750

13.1 Exterior cleaning

Please note the following points when cleaning the device:
• The cleaning agents used should not corrode the surface and the seals.
• Mechanical damage to the process isolating diaphragm, e.g. due to pointed objects, must be avoided.
• Observe the degree of protection of the device. See the nameplate if necessary (  14).
69
Repair Deltabar FMD71, FMD72

14 Repair

14.1 General notes

14.1.1 Repair concept

The Endress+Hauser repair concept requires for devices to have a modular design and for repairs to be carried out by Endress+Hauser Service or by properly trained customers.
Spare parts are grouped into logical kits with the associated replacement instructions.
For more information on service and spare parts, please contact Endress+Hauser Service.

14.1.2 Repair of Ex-certified devices

When repairing Ex-certified devices, please also note the following:
• Only specialist personnel or Endress+Hauser-Service can carry out repairs to Ex certified devices.
• Relevant standards and national regulations as well as safety instructions (XA) and certificates must be observed.
• Only genuine Endress+Hauser spare parts may be used.
• When ordering spare parts, please check the device designation on the nameplate. Identical parts may only be used as replacements.
• Carry out repairs according to the instructions. Following a repair, the device must fulfill the requirements of the individual tests specified for that device.
• A certified device may be converted to another certified device version by Endress +Hauser Service only.
• All repairs and modifications must be documented.

14.1.3 Replacing sensor modules or main electronics

Once both sensor modules or the main electronics have been replaced, the sensor module that is connected to the transmitter must be selected. To do this, follow these steps:
1. Switch off the supply voltage
2. Replacing the sensor module or main electronics
3. Switch on the supply voltage.
4. Select sensor module LP or sensor module HP: Menu path: Expert  System  Management  Connect transm. (286)"
For additional information, see "Function" (  12) section.

14.1.4 Replacing a device

Once a complete device has been replaced, the parameters can be transferred back into the device using FieldCare:
Prerequisite: The configuration of the old device was saved previously to the computer using FieldCare.
You can continue to measure without performing a new calibration.
70
Deltabar FMD71, FMD72 Repair

14.2 Spare parts

• Some replaceable measuring device components are identified by means of a spare part nameplate. This contains information about the spare part.
• All the spare parts for the measuring device along with the order code are listed In the W@M Device Viewer ( users can also download the associated Installation Instructions.
Measuring device serial number:
• Located on the device and spare part nameplate.
• Can be read out via the "Serial number" parameter in the "Instrument info" submenu.
www.endress.com/deviceviewer) and can be ordered. If available,
71
Return Deltabar FMD71, FMD72

15 Return

The measuring device must be returned if repairs or a factory calibration are required, or if the wrong measuring device has been ordered or delivered. According to legal regulations Endress+Hauser, as an ISO-certified company, is required to follow certain procedures when handling returned products that are in contact with the medium. To ensure swift, safe and professional device returns, please read the return procedures and conditions on the Endress+Hauser website at
Select country.
 The web site of the responsible sales office opens with all of the relevant
information relating to returns.
1. If the desired country is not listed: Click on the "Choose your location" link.  An overview of Endress+Hauser sales offices and representatives opens.
2. Contact your Endress+Hauser sales office or representative.
www.services.endress.com/return-material
72
Deltabar FMD71, FMD72 Overview of the operating menu

16 Overview of the operating menu

Depending on the parameter configuration, not all submenus and parameters are available. Information on this can be found in the parameter description under "Prerequisite".
Direct access Description
Language 000 (  78)
Display/operat. Direct access Description
Display mode 001 (  78)
Value 2 display 002 (  78)
Value 3 display 288 (  106)
Format 1st Value 004 (  79)
HART Input Form. 157 (  100)
Setup Direct access Description
Operating mode 005
182
High Press. Side 183 (  101)
Press. Eng. Unit 125 (  99)
Corrected Press. (read only) 172 (  101)
Pos. Zero Adjust 007 (  80)
Empty Calib. ("Level" measuring mode and "Calibration Mode" = wet) 028
011
Full Calib. ("Level" measuring mode and "Calibration Mode" = wet") 031
012
Set LRV ("Pressure" measuring mode) 013 (  81)
Set URV ("Pressure" measuring mode) 014 (  81)
Damping switch (read only) 164 (  100)
Damping value Damping value (read only)
Level before Lin ("Level" measuring mode) 019 (  82)
Meas.Diff.Press. (read only) 020 (  83)
017 184
(  79)
(  80)
(  80)
(  82)
Setup→ Extended Setup Direct access Description
Code Definition 023 (  84)
Device tag 022 (  84)
Operator Code 021 (  83)
Setup→ Extended Setup→ Level
("Level" measuring mode)
Level Selection 024 (  84)
Unit before lin. 025 (  85)
Height Unit 026 (  85)
Calibration Mode 027 (  85)
Direct access Description
73
Overview of the operating menu Deltabar FMD71, FMD72
Setup→ Extended Setup→ Level
("Level" measuring mode)
Empty Calib. Empty Calib. (read only)
Empty Pressure Empty Pressure (read only)
EMPTY HEIGHT Empty height (read only)
Full Calib. Full Calib. (read only)
FULL PRESSURE Full Pressure (read only)
FULL HEIGHT Full height (read only)
Adjust Density 034 (  88)
Process Density 035 (  88)
Level Before Lin (read only) 019 (  82)
Setup→ Extended Setup→ Linearization Direct access Description
Lin. mode 037 (  89)
Unit after lin. 038 (  89)
Line number 039 (  89)
X-value.: (edit mode) X-value: (semi-automatic) X-value: (read only)
Y-val: (edit mode) Y-val: (semi-automatic) Y-val: (read only)
Edit table 042 (  90)
TANK DESCRIPTION 173 (  101)
Tank Content (read only) 043 (  91)
Direct access Description
028 011
029 185
030 186
031 012
032 187
033 188
040 193 123
041 041 194
(  86)
(  86)
(  87)
(  87)
(  87)
(  88)
(  90)
(  90)
Setup→ Extended Setup→ Current output Direct access Description
Alarm Behav. P 050 (  91)
Alarm cur.switch (read only)
Output fail mode Output fail mode (read only)
High Alarm Curr. 052 (  91)
Set Min. Current 053 (  92)
Output current (read only) 054 (  92)
Get LRV (only "Pressure") 015 (  81)
Set LRV 013 (  81)
Get URV (only "Pressure") 016 (  82)
Set URV 014 (  81)
165 (  101)
190 051
(  102)
74
Deltabar FMD71, FMD72 Overview of the operating menu
Diagnostics Direct access Description
Diagnostic Code (read only) 071 (  92)
Last Diag. Code (read only) 072 (  92)
Diagnostics→ Sensor HP Direct access Description
Min. Meas.Press. (read only) 073 (  93)
Counter P < Pmin (read only) 262 (  102)
Max. Meas.Press. (read only) 074 (  93)
Counter P > Pmax (read only) 263 (  102)
Min. Meas.Temp. (read only) 264 (  103)
Max. Meas.Temp. (read only) 265 (  103)
Diagnostics→ Sensor LP Direct access Description
Min. Meas.Press. (read only) 266 (  103)
Counter P < Pmin (read only) 267 (  103)
Max. Meas.Press. (read only) 268 (  104)
Counter P > Pmax (read only) 269 (  104)
Min. Meas.Temp. (read only) 270 (  104)
Max. Meas.Temp. (read only) 271 (  104)
Diagnostics→ Diagnostics list Direct access Description
Diagnostic 1 (read only) 075 (  93)
Diagnostic 2 (read only) 076 (  93)
Diagnostic 3 (read only) 077 (  93)
Diagnostic 4 (read only) 078 (  93)
Diagnostic 5 (read only) 079 (  93)
Diagnostic 6 (read only) 080 (  93)
Diagnostic 7 (read only) 081 (  93)
Diagnostic 8 (read only) 082 (  93)
Diagnostic 9 (read only) 083 (  93)
Diagnostic 10 (read only) 084 (  93)
Diagnostics→ Event logbook Direct access Description
Last Diag. 1 (read only) 085 (  94)
Last Diag. 2 (read only) 086 (  94)
Last Diag. 3 (read only) 087 (  94)
Last Diag. 4 (read only) 088 (  94)
Last Diag. 5 (read only) 089 (  94)
Last Diag. 6 (read only) 090 (  94)
Last Diag. 7 (read only) 091 (  94)
Last Diag. 8 (read only) 092 (  94)
Last Diag. 9 (read only) 093 (  94)
Last Diag. 10 (read only) 094 (  94)
75
Overview of the operating menu Deltabar FMD71, FMD72
Diagnostics→ Device info Direct access Description
Firmware Version (read only) 095 (  94)
Serial Number (read only) 096 (  94)
Ext. Order Code (read only) 097 (  94)
Order Code (read only) 098 (  95)
Cust. tag number 254 (  102)
Device tag 022 (  84)
ENP Version (read only) 099 (  95)
Config Counter (read only) 100 (  95)
Manufacturer ID (read only) 103 (  96)
Device ID (read only) 279 (  105)
Device Revision (read only) 108 (  96)
Diagnostics→ Device info→ Sens. Limit HP Direct access Description
LRL Sensor (read only) 101 (  95)
URL Sensor (read only) 102 (  96)
Diagnostics→ Device info→ Sens. Limit LP Direct access Description
LRL Sensor (read only) 272 (  104)
URL Sensor (read only) 273 (  105)
Diagnostics→ Measured values Direct access Description
Level Before Lin (read only) 019 (  82)
Tank Content (read only) 043 (  91)
Meas.Diff.Press. (read only) 020 (  83)
Sensor Press. HP (read only) 109 (  96)
Sensor Press. LP (read only) 280 (  105)
Meas. Press. HP (read only) 281 (  105)
Meas. Press. LP (read only) 282 (  105)
Corrected Press. (read only) 172 (  101)
Sensor Temp. HP (read only) 110 (  96)
Sensor Temp. LP (read only) 283 (  106)
Diagnostics→ Simulation Direct access Description
Simulation mode 112 (  97)
Sim. diff.press. 113 (  98)
Sim. Press. HP 284 (  106)
Sim. Press. LP 285 (  106)
Sim. level 115 (  98)
Sim. tank cont. 116 (  98)
Sim. Current 117 (  99)
Sim. error no. 118 (  99)
76
Deltabar FMD71, FMD72 Overview of the operating menu
Diagnostics→ Reset Direct access Description
Reset 124 (  99)
77
Description of device parameters Deltabar FMD71, FMD72

17 Description of device parameters

: Indicates how to navigate to the parameter using the display and operating module
: Indicates how to navigate to the parameter using operating tools (e.g. FieldCare)
Language (000)
Navigation Main menu  Language
Write permission Operators/Service engineers/Expert
Description Select the menu language for the local display.
Options • English
• Another language (as selected when ordering the device)
• Possibly a third language (language of the manufacturing plant)
Factory setting English
Display mode (001)
Navigation Display/operat.  Display mode (001)
Write permission Operators/Service engineers/Expert
Description Specify the contents for the first line of the local display in measuring mode.
Options • Primary value
• External value
• All alternating
Factory setting Primary value
2nd disp. value (002)
Navigation Display/operat.  2nd disp. value (002)
Write permission Operators/Service engineers/Expert
Description Specify the contents for the second value in the alternating display mode in measuring
mode.
78
Deltabar FMD71, FMD72 Description of device parameters
Options • No value
• Differential pressure
• Pressure HP
• Pressure LP
• Sensor Temp. HP
• Sensor Temp. LP
• Level before linearization
• Current
• Main measured value (%)
The options depend on the measuring mode chosen.
Factory setting No value
Format 1st Value (004)
Navigation Display/operat.  Format 1st Value (004)
Write permission Operators/Service engineers/Expert
Description Specify the number of places after the decimal point for the value displayed in the main
line.
Options • Auto
• x
• x.x
• x.xx
• x.xxx
• x.xxxx
• x.xxxxx
Factory setting Auto
Measuring mode (005/182)
Navigation Setup  Measuring Mode (005/182)
Write permission Operators/Service engineers/Expert
Description Select the measuring mode. The operating menu is structured differently depending on the
measuring mode selected.
Options • Pressure
• Level
Factory setting Level or according to order specifications
79
Description of device parameters Deltabar FMD71, FMD72
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in
the "Setup" operating menu and readjusted if necessary.
Pos. Zero Adjust (007)
Navigation Setup  Pos. Zero Adjust (007)
Write permission Operators/Service engineers/Expert
Description Position adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known.
Example • Measured value = 2.2 mbar (0.033 psi)
• You correct the measured value via the "Pos. Zero Adjust" parameter with the "Confirm" option. This means that you are assigning the value 0.0 to the pressure present.
• Measured value (after pos. zero adjust) = 0.0 mbar
• The current value is also corrected.
Options • Confirm
• Cancel
Factory setting Cancel
Empty Calib. (011/28)
Navigation Setup  Empty Calib. (011/028)
Write permission Operators/Service engineers/Expert
Description Enter the output value for the lower calibration point (vessel empty). The unit defined in
"Unit Before Lin." must be used.
Note • In the case of wet calibration, the level (vessel empty) must actually be available. The
associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel empty) does not have to be available. The associated pressure has to be entered in the "Empty Pressure (029)" parameter for the "In pressure" level selection. The associated height has to be entered in the "Empty height" (030) parameter for the "In height" level selection.
Factory setting 0.0
Full Calib. (012/031)
80
Deltabar FMD71, FMD72 Description of device parameters
Navigation
Write permission Operators/Service engineers/Expert
Description Enter the output value for the upper calibration point (vessel full). The unit defined in "Unit
Note • In the case of wet calibration, the level (vessel full) must actually be available. The
Factory setting 100.0
Set LRV (013, 056, 166, 168)
Navigation Setup  Set LRV (013, 056, 166, 168)
Setup  Full Calib. (012/031)
Before Lin." must be used.
associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel full) does not have to be available. The associated pressure has to be entered in the "Full Pressure" parameter for the "In pressure" level selection. The associated height has to be entered in the "Full height" parameter for the "In height" level selection.
Setup  Advanced Setup  Current Output  Set LRV (013, 056, 166, 168)
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the lower current value (4 mA).
Factory setting • 0.0 % in Level measuring mode
• 0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode
Set URV (014, 057, 167, 169)
Navigation Setup  Set URV (014, 057, 167, 169)
Setup  Advanced Setup  Current output  Set URV (014, 057, 167, 169)
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the upper current value (20 mA).
Factory setting • 100.0 % in Level measuring mode
• URL Sensor or according to ordering information in Pressure measuring mode
Get LRV (015)
Navigation Setup  Advanced Setup  Current Output  Get LRV (015)
Write permission Operators/Service engineers/Expert
81
Description of device parameters Deltabar FMD71, FMD72
Description Setting lower range value. The pressure for the lower current value (4 mA) is present at
the device. Use the "Confirm" option to assign the lower current value to the applied pressure value.
Prerequisite Pressure measuring mode
Options • Cancel
• Confirm
Factory setting Cancel
Get URV (016)
Navigation Setup  Advanced Setup  Current Output  Get URV (016)
Write permission Operators/Service engineers/Expert
Description Setting upper range value. The pressure for the upper current value (20 mA) is present at
the device. Use the "Confirm" option to assign the applied pressure value to the upper current value.
Prerequisite Pressure measuring mode
Options • Cancel
• Confirm
Factory setting Cancel
Damping (017)/(184)
Navigation Setup  Damping (017)/(184)
Write permission Operators/Service engineers/Expert
(if the "Damping" DIP switch is set to "on")
Description
Enter damping time (time constant t) ("Damping" DIP switch set to "on") Display damping time (time constant t) ("Damping" DIP switch set to "off"). The damping affects the speed at which the measured value reacts to changes in pressure.
Input range 0.0 to 999.0 s
Factory setting 2.0 sec. or according to order specifications
Level before lin. (019)
82
Deltabar FMD71, FMD72 Description of device parameters
Navigation
Setup  Level Before Lin. (019) Setup  Advanced Setup  Level  Level Before Lin. (019) Diagnosis  Measured Values  Level Before Lin. (019)
Write permission No write permissions. Parameter is read only.
Description Displays the level value prior to linearization.
Meas.Diff.Press. (020)
Navigation Setup  Meas.Diff.Press. (020)
Diagnosis  Measured Values  Meas.Diff.Press. (020)
Write permission No write permissions. Parameter is read only.
Description Displays the measured differential pressure after sensor trim, position adjustment and
damping.
LP
HP
Sensor press.
LP
Sensor
calibration LP
Sensor
calibration HP
Sensor press.
HP
Sensor trim LP
Sensor trim
HP
Measured
pressure LP
Pressure
simulation LP
Differential
pressure +
pressure
inversion
Pressure
simulation HP
Measured
pressure HP
Corrected
pressure
Pos. zero
adjust (calib.
offset)
Differential
pressure
simulation
Pressure after
damping
Damping P
Measured
differential
pressure
Operator Code (021)
Navigation Setup  Advanced Setup  Operator Code (021)
Write permission Operators/Service engineers/Expert
Description Use this function to enter a code to lock or unlock operation.
User entry
To lock: Enter a number ¹ the release code (value range: 1 to 9999).
• To unlock: Enter the release code.
83
Description of device parameters Deltabar FMD71, FMD72
Note The release code is "0" in the order configuration. Another release code can be defined in
the "Code Definition" parameter. If the user has forgotten the release code, the release code can be visible by entering the number "5864".
Factory setting 0
Device tag (022)
Navigation Setup  Advanced Setup  Device tag (022)
Write permission Operators/Service engineers/Expert
Description Enter the device tag, e.g. TAG number (max. 32 alphanumeric characters).
Factory setting No entry or according to order specifications
Code Definition (023)
Navigation Setup  Advanced Setup  Code Definition (023)
Write permission Operators/Service engineers/Expert
Description Use this function to enter a release code with which the device can be unlocked.
Options A number from 0 to 9999
Factory setting 0
Level Selection (024)
Navigation Setup  Advanced Setup  Level  Level Selection (024)
Write permission Operators/Service engineers/Expert
Description Select the method for calculating the level
Options • In pressure
If this option is selected, specify two pressure/level value pairs. The level value is displayed directly in the unit that you select via the "Unit Before Lin." parameter.
• In height If this option is selected, specify two height/level value pairs. From the measured pressure, the device first calculates the height using the density. This information is then used to calculate the level in the "Unit Before Lin." selected using the two value pairs specified.
Factory setting In pressure
84
Deltabar FMD71, FMD72 Description of device parameters
Unit before lin. (025)
Navigation Setup  Advanced Setup  Level  Unit Before Lin. (025)
Write permission Operators/Service engineers/Expert
Description Select the unit for the measured value display for the level before linearization.
Example • Current measured value: 0.3 ft
• New output unit: m
• New measured value: 0.3 m
Options • %
• mm, cm, dm, m
• ft, in
• m3, in
3
• l, hl
3
• ft
• gal, Igal
• kg, t
• lb
Note The unit selected is only used to describe the measured value. This means that when
selecting a new output unit, the measured value is not converted.
Factory setting %
Height unit (026)
Navigation Setup  Advanced Setup  Level  Height Unit (026)
Write permission Operators/Service engineers/Expert
Description Select the height unit. The measured pressure is converted to the selected height unit
using the "Adjust Density" parameter.
Prerequisite "Level Selection" = "In height"
Options • mm
• m
• in
• ft
Factory setting m
Calibration mode (027)
85
Description of device parameters Deltabar FMD71, FMD72
Navigation
Write permission Operators/Service engineers/Expert
Description Select the calibration mode.
Options • Wet
Factory setting Wet
Empty Calib. (028)/(011)
Navigation Setup  Advanced Setup  Level  Empty Calib. (028)/(011)
Setup  Advanced Setup  Level  Calibration Mode (027)
Wet calibration takes place by filling and emptying the vessel. In the case of two different levels, the level, volume, mass or percentage value entered is assigned to the pressure measured at this point in time ("Empty Calib." and "Full Calib." parameters).
• Dry Dry calibration is a theoretical calibration. For this calibration, you specify two pressure­level value pairs or height-level value pairs via the following parameters: "Empty Calib.", "Empty Pressure", "Empty Height", "Full Calib.", "Full Pressure", "Full Height".
Write permission Operators/Service engineers/Expert
Description Enter the output value for the lower calibration point (vessel empty). The unit defined in
"Unit Before Lin." must be used.
Note • In the case of wet calibration, the level (vessel empty) must actually be available. The
associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel empty) does not have to be available. The associated pressure has to be entered in the "Empty Pressure (029)" parameter for the "In pressure" level selection. The associated height has to be entered in the "Empty height" (030) parameter for the "In height" level selection.
Factory setting 0.0
Empty Pressure (029)/(185)
Navigation Setup  Advanced Setup  Level  Empty Pressure (029)/(185)
Write permission Operators/Service engineers/Expert
Description Enter the pressure value for the lower calibration point (vessel empty). See also "Empty
Calib. (028)".
Prerequisite • "Level Selection" = In pressure
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting 0.0
86
Deltabar FMD71, FMD72 Description of device parameters
Empty height (030)/(186)
Navigation Setup  Advanced Setup  Level  Empty Height (030)/(186)
Write permission Operators/Service engineers/Expert
Description Enter the height value for the lower calibration point (vessel empty). The unit is selected
via the "Height unit (026)" parameter.
Prerequisite • "Level Selection" = "In height"
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting 0.0
Full Calib. (031)/(012)
Navigation Setup  Advanced Setup  Level  Full Calib. (031)/(012)
Write permission Operators/Service engineers/Expert
Description Enter the output value for the upper calibration point (vessel full). The unit defined in "Unit
Before Lin." must be used.
Note • In the case of wet calibration, the level (vessel full) must actually be available. The
associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel full) does not have to be available. The associated pressure has to be entered in the "Full Pressure" parameter for the "In pressure" level selection. The associated height has to be entered in the "Full height" parameter for the "In height" level selection.
Factory setting 100.0
Full Pressure (032)/(187)
Navigation Setup  Advanced Setup  Level  Full Pressure (032)/(187)
Write permission Operators/Service engineers/Expert
Description Enter the pressure value for the upper calibration point (vessel full). See also "Full Calib.".
Prerequisite • "Level Selection" = In pressure
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting URL of the sensor module
87
Description of device parameters Deltabar FMD71, FMD72
Full height (033)/(188)
Navigation Setup  Advanced Setup  Level  Full height (033)/(188)
Write permission Operators/Service engineers/Expert
Description Enter the height value for the upper calibration point (vessel full). The unit is selected via
the "Height unit" parameter.
Prerequisite • "Level Selection" = "In height"
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting URL is converted to a level unit
Adjust density (034)
Navigation Setup  Advanced Setup  Level  Adjust Density (034)
Write permission Operators/Service engineers/Expert
Description Enter the density of the medium used to perform the calibration. The measured pressure is
converted to a height using the "Height unit" and "Adjust Density" parameters.
Factory setting 1.0
Process Density (035)
Navigation Setup  Advanced Setup  Level  Process Density (035)
Write permission Operators/Service engineers/Expert
Description Enter a new density value for density correction. The calibration was carried out with the
medium water, for example. Now the vessel is to be used for another medium with another density. The calibration is corrected appropriately by entering the new density value in the "Process Density" parameter.
Note If you change to dry calibration after completing a wet calibration using the "Calibration
mode" parameter, the density for the "Adjust Density" and "Process Density" parameters must be entered correctly before changing the calibration mode.
Factory setting 1.0
88
Deltabar FMD71, FMD72 Description of device parameters
Lin. mode (037)
Navigation Setup  Advanced Setup  Linearization  Lin. Mode (037)
Write permission Operators/Service engineers/Expert
Description Select the linearization mode.
Options • Linear
The level is output without being converted beforehand. "Level before Lin" is output.
• Erase table The existing linearization table is deleted.
• Manual entry (sets the table to edit mode, an alarm is output): The value pairs of the table (X-value (193/040) and Y-val. (041)) are entered manually.
• Semi-automatic entry (sets the table to edit mode, an alarm is output): The vessel is emptied or filled in stages in this entry mode. The device automatically records the level value (X-value (193/040)). The associated volume, mass or % value is entered manually (Y-val (041)).
• Activate table The table entered is activated and checked with this option. The device shows the level after linearization.
Factory setting Linear
Unit after lin. (038)
Navigation Setup  Advanced Setup  Linearization  Unit After Lin. (038)
Write permission Operators/Service engineers/Expert
Description Select volume unit, mass, height or % (unit of the Y-val).
Options • %
• cm, dm, m, mm
• hl
• in3, ft3, m3,
• l
• in, ft
• kg, t
• lb
• gal
• Igal
Factory setting %
Line numb. (039)
Navigation Setup  Advanced Setup  Linearization  Line-numb. (039)
89
Description of device parameters Deltabar FMD71, FMD72
Write permission Operators/Service engineers/Expert
Description Enter the number of the current point in the table. The subsequent entries in "X-value" and
"Y-val." refer to this point.
Input range 1...32
X-value (040)/(123)/(193)
Navigation Setup  Advanced Setup  Linearization  X-value (040)/(123)/(193)
Write permission Operators/Service engineers/Expert
Description Enter the X-value (level before linearization) for the specific point in the table and confirm.
Note • If "Lin. mode" = "Manual", the level value must be entered.
• If "Lin. mode" = "Semiautomatic", the level value is displayed and has to be confirmed by entering the paired Y-val.
Y-val (041)/(194)
Navigation Setup  Advanced Setup  Linearization  Y-val (041)/(194)
Write permission Operators/Service engineers/Expert
Description Enter the Y-val (value after linearization) for the specific point in the table. The unit is
determined by "Unit after lin."
Note The linearization table must be monotonic (increasing or decreasing).
Edit table (042)
Navigation Setup  Advanced Setup  Linearization  Edit Table (042)
Write permission Operators/Service engineers/Expert
Description Select the function for entering the table.
Options • Next point: enter the next point.
• Current point: stay on the current point to correct a mistake for example.
• Last input point: skip back to previous point to correct a mistake for example.
• Insert point: insert an additional point (see example below).
• Delete point: delete the current point (see example below).
90
Deltabar FMD71, FMD72 Description of device parameters
Example Add point, in this case between the 4th and 5th point for example
• Select point 5 via the "Line-numb." parameter.
• Select the "Insert point" option via the "Edit table" parameter.
• Point 5 is displayed for the "Line-numb" parameter. Enter new values for the "X-value" and "Y-val." parameters.
Delete point, in this case the 5th point for example
• Select point 5 via the "Line-numb." parameter.
• Select the "Delete point" option via the "Edit table" parameter.
• The 5th point is deleted. All of the following points are pushed up one number i.e. following deletion, the 6th point becomes Point 5.
Factory setting Current point
Tank content (043)
Navigation Setup  Advanced Setup  Linearization  Tank Content (043)
Diagnosis  Measured values  Tank Content (043)
Write permission Operators/Service engineers/Expert
Description Displays the level value after linearization.
Alarm Behav. P (050)
Navigation Setup  Advanced Setup  Current output  Alarm Behav. P (050)
Write permission Operators/Service engineers/Expert
Description Set current output if sensor module limits are overshot or undershot.
Options • Warning
The device continues to measure. An error message is displayed.
• Alarm The output signal assumes a value that can be defined by the "Output fail mode (190)/ (051)" function.
• Special – The lower sensor module limit is undershot (sensor module LP or HP or complete
system): Current output = 3.6 mA
– The upper sensor module limit is overshot (sensor module LP or HP or complete
system): Current output assumes a value of 21 - 23 mA, depending on the setting of the "High Alarm Curr." parameter (052).
Factory setting Warning
High Alarm Curr. (052)
91
Description of device parameters Deltabar FMD71, FMD72
Navigation
Write permission Operators/Service engineers/Expert
Description Enter the current value for maximum alarm current. See also "Output fail mode".
Input range 21 to 23 mA
Factory setting 22 mA
Set Min. Current (053)
Navigation Setup  Advanced Setup  Current Output  Set Min. Current (053)
Write permission Operators/Service engineers/Expert
Description Enter lower current limit.
Options • 3.8 mA
Setup  Advanced Setup  Current Output  High Alarm Curr. (052)
Some switching units accept no current smaller than 4.0 mA.
• 4.0 mA
Factory setting 3.8 mA
Output current (054)
Navigation Setup  Advanced Setup  Current Output  Output Current (054)
Write permission Operators/Service engineers/Expert
Description Displays the current current value.
ALARM STATUS (071)
Navigation Diagnosis  Diagnostic Code (071)
Write permission No write permissions. Parameter is read only.
Description Displays the diagnostic message with the highest priority currently present.
Last diag. code (072)
92
Deltabar FMD71, FMD72 Description of device parameters
Navigation
Diagnosis  Last Diag. Code (072)
Write permission No write permissions. Parameter is read only.
Description Displays the last diagnostic message that occurred and was rectified.
Note • Digital communication: the last message is displayed.
• Use the "Reset logbook" parameter to clear the messages listed in the parameter "Last diag. code".
Min. meas. press. (073)
Navigation Diagnosis  Sensor HP  Minimum Pressure (073)
Write permission No write permissions. Parameter is read only.
Description Displays the lowest pressure value measured (peakhold indicator). You can reset this
indicator by means of the "Reset peakhold" parameter.
Max. meas. press. (074)
Navigation Diagnosis  Sensor HP  Maximum Pressure (074)
Write permission No write permissions. Parameter is read only.
Description Displays the highest pressure value measured (peakhold indicator). You can reset this
indicator by means of the "Reset peakhold" parameter.
Diagnostic list
Diagnostic 1 (075) Diagnostic 2 (076) Diagnostic 3 (077) Diagnostic 4 (078) Diagnostic 5 (079) Diagnostic 6 (080) Diagnostic 7 (081) Diagnostic 8 (082) Diagnostic 9 (083) Diagnostic 10 (084)
Navigation Diagnosis  Diagnostic list
Write permission No write permissions. Parameter is read only.
Description This parameter contains up to ten diagnosis messages that are currently pending,
arranged in order of priority.
93
Description of device parameters Deltabar FMD71, FMD72
Event logbook
Last diag. 1 (085) Last diag. 2 (086) Last diag. 3 (087) Last diag. 4 (088) Last diag. 5 (089) Last diag. 6 (090) Last diag. 7 (091) Last diag. 8 (092) Last diag. 9 (093) Last diag. 10 (094)
Navigation Diagnosis  Event Logbook
Write permission No write permissions. Parameter is read only.
Description This parameter contains the last 10 diagnosis messages to occur and be rectified. They can
be reset using the "Reset logbook" parameter. Errors which have occurred multiple times are displayed once only. Errors may also appear multiple times if another error has occurred in the meantime. The messages are displayed in chronological order.
Firmware version (095)
Navigation Diagnosis  Instrument info Firmware Version (095)
Write permission No write permissions. Parameter is read only.
Description Displays the firmware version.
Serial number (096)
Navigation Diagnosis  Instrument info  Serial Number (096)
Write permission Parameter is read only. Only Endress+Hauser Service has write permission.
Description Displays the serial number of the device (11 alphanumeric characters).
Ext. order code (097)
Navigation Diagnosis  Instrument info  Ext. Order Code (097)
Write permission Parameter is read only. Only Endress+Hauser Service has write permission.
94
Deltabar FMD71, FMD72 Description of device parameters
Description Displays extended order number.
Factory setting According to order specifications
Order code (098)
Navigation Diagnosis  Instrument info  Order Code (098)
Write permission Parameter is read only. Only Endress+Hauser Service has write permission.
Description Displays the order identifier.
Factory setting According to order specifications
ENP version (099)
Navigation Diagnosis  Instrument info  ENP Version (099)
Write permission Operators/Service engineers/Expert
Description Displays the ENP version
(ENP = electronic nameplate)
Config. counter (100)
Navigation Diagnosis  Instrument info  Config. Counter (100)
Write permission Operators/Service engineers/Expert
Description Displays the configuration counter.
This counter is increased by one every time a parameter or group is changed. The counter counts up to 65535 and then starts again at zero.
LRL sensor (101)
Navigation Diagnosis  Instrument info  Sens. Limit HP  LRL Sensor (101)
Write permission No write permissions. Parameter is read only.
Description Displays the lower-range limit of the sensor module.
95
Description of device parameters Deltabar FMD71, FMD72
URL sensor (102)
Navigation Diagnosis  Instrument info  Sens. Limit HP  URL sensor (102)
Write permission No write permissions. Parameter is read only.
Description Displays the upper-range limit of the sensor module.
Manufacturer ID (103)
Navigation Diagnosis  Instrument info  Manufacturer ID (103)
Write permission No write permissions. Parameter is read only.
Description Displays the HART manufacturer ID in a decimal digit format.
Here: 17
Device revision (108)
Navigation Diagnosis  Instrument info  Device Revision (108)
Write permission No write permissions. Parameter is read only.
Description Display of Device Revision (e.g. 1)
Sensor pressure HP (109)
Navigation Diagnosis  Measured Values  Sensor Press. HP (109)
Write permission No write permissions. Parameter is read only.
Description Displays the measured pressure before the sensor trim.
Sensor Temp. HP (110)
Navigation Diagnosis  Measured values  Sensor Temp. HP (110)
Write permission No write permissions. Parameter is read only.
96
Deltabar FMD71, FMD72 Description of device parameters
Description Displays the temperature currently measured in the sensor module. This can deviate from
the process temperature.
Simulation mode (112)
Navigation Diagnosis  Simulation  Simulation mode (112)
Write permission Operators/Service engineers/Expert
Description Switch on simulation and select the simulation mode. When changing the measuring
mode or the level type (Lin. Mode (037)) or when the device is restarted, any simulation running is switched off.
Options • None
• Differential pressure,  see this table, "Sim. pressure" parameter
• Level,  see this table, "Sim. level" parameter
• Press. HP,  see this table, "Sim. Press. HP" parameter
• Press. LP,  see this table, "Sim. Press. LP" parameter
• Tank content,  see this table, Sim. tank cont." parameter
• Current,  see this table, "Sim. Current" parameter
• Alarm/warning,  see this table, "Sim. error no."
Factory setting None
LP
HP
Simulation
pressure LP
Processing
Sensor LP measurement
Processing
Sensor HP measurement
Simulation
pressure HP
. . .
Measured
pressure LP
Measured
pressure HP
P
(Measured
differential
pressure)
+
Position adjustment + pressure
-
Simulation
level
Processing level linear
Corrected
pressure
inversion
L(Level before
linearization)
Simulation differential
pressure
Pressure
simulation
Processing differential pressure
Simulation
tank content
Processing
tank content
(lin.tab)
t
T
(Tank
content)
. . .
Only level measuring mode
97
Description of device parameters Deltabar FMD71, FMD72
Simulation
Error number
Measuring
Measured
differential
pressure
mode
Linearization
mode
P
Diagnostics/
device status
Simulation
current
Level before linearization
Tank content T
L  PV(Measured
value)
Processing current output  Current output
Sim. diff.press. (113)
Navigation Diagnosis  Simulation  Sim.diff.press. (113)
Write permission Operators/Service engineers/Expert
Description Enter the simulation value. See also "Simulation Mode".
Prerequisite "Simulation mode" = Differential pressure
Value at switch-on Current differential pressure measured value
Sim. level (115)
Navigation Diagnosis  Simulation  Sim. level (115)
Write permission Operators/Service engineers/Expert
Description Enter the simulation value. See also "Simulation Mode".
Prerequisite "Measuring mode" = Level and "Simulation mode" = Level
Value at switch-on Current level measured value
Sim. tank cont. (116)
Navigation Diagnosis  Simulation  Sim. tank cont. (116)
Write permission Operators/Service engineers/Expert
98
Deltabar FMD71, FMD72 Description of device parameters
Description Enter the simulation value. See also "Simulation Mode".
Prerequisite "Measuring Mode" = level, Lin mode "Activate table" and "Simulation Mode" = Tank content
Value at switch-on Current tank content
Sim. Current (117)
Navigation Diagnosis  Simulation  Sim. Current (117)
Write permission Operators/Service engineers/Expert
Description Enter the simulation value. See also "Simulation Mode".
Prerequisite "Simulation Mode" = Current value
Value at switch-on Current current value
Sim. error no. (118)
Navigation Diagnosis  Simulation  Sim. error no. (118)
Write permission Operators/Service engineers/Expert
Description Enter the diagnostic message number. See also "Simulation Mode".
Prerequisite "Simulation Mode" = Alarm/Warning
Value at switch-on 484 (Simulation active)
Enter reset code (124)
Navigation Diagnosis  Reset  Reset (124)
Write permission Operators/Service engineers/Expert
Description Reset parameters completely or partially to the factory values or order configuration by
entering a reset code, see "Resetting to factory settings (reset)" section.(  38)
Factory setting 0
Press. Eng. Unit (125)
99
Description of device parameters Deltabar FMD71, FMD72
Navigation
Setup  Press. Eng. Unit (125)
Write permission Operators/Service engineers/Expert
Description Select the pressure engineering unit. If a new pressure engineering unit is selected, all
pressure-specific parameters are converted and displayed with the new unit.
Options • mbar, bar
• mmH2O, mH2O,
• in, H2O, ftH2O
• Pa, kPa, MPa
• psi
• mmHg, inHg
• kgf/cm
2
Factory setting mbar, bar or psi depending on the sensor module nominal measuring range, or as per
order specifications
HART Input Form. (157)
Navigation Display/operat.  HART Input Form. (157)
Write permission Operators/Service engineers/Expert
Description Number of decimal places of the displayed input value.
Options • x.x
• x.xx
• x.xxx
• x.xxxx
• x.xxxxx
Factory setting x.x
Damping switch (164)
Navigation Setup  Damping switch (164)
Write permission No write permissions. Parameter is read only.
Description Displays the switch position of DIP switch 2 which is used to switch the damping of the
output signal on and off.
Display • Off
The output signal is not damped.
• On The output signal is damped. The attenuation constant is specified in the "Damping" (017) (184) parameter
Factory setting On
100
Loading...