A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other
connections.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a
potential equalization line or a star grounding system depending on national or
company codes of practice.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
SymbolMeaning
1, 2, 3,...Item numbers
, 2., 3.…Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
Hazardous area
Safe area (non-hazardous area)
Flow direction
4Endress+Hauser
Page 5
Proline Promag D 400
U
e
L
B
I
I
v
Function and system design
Measuring principle
Following Faraday's law of magnetic induction, a voltage is induced in a conductor moving through a
magnetic field.
In the electromagnetic measuring principle, the flowing medium is the moving conductor. The
voltage induced (Ue) is proportional to the flow velocity (v) and is supplied to the amplifier by means
of two measuring electrodes. The flow volume (Q) is calculated via the pipe cross-section (A). The DC
magnetic field is created through a switched direct current of alternating polarity.
Formulae for calculation
• Induced voltage Ue = B · L · v
• Volume flow Q = A · v
Endress+Hauser5
Page 6
Proline Promag D 400
23
6
7
8
4
1
5
Measuring system
The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version – transmitter and sensor form a mechanical unit.
• Remote version - transmitter and sensor are mounted in separate locations.
1Possibilities for integrating measuring devices into a system
1Control system (e.g. PLC)
2EtherNet/IP
3PROFIBUS DP
4Modbus RS485
54-20 mA HART, pulse/frequency/switch output
6Non-hazardous area
7Non-hazardous area and Zone 2/Div. 2
A0021560
Page 7
Proline Promag D 400
SafetyIT security
We only provide a warranty if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any inadvertent
changes to the device settings.
IT security measures in line with operators' security standards and designed to provide additional
protection for the device and device data transfer must be implemented by the operators themselves.
Device-specific IT security
The device offers a range of specific functions to support protective measures on the operator's side.
These functions can be configured by the user and guarantee greater in-operation safety if used
correctly. An overview of the most important functions is provided in the following section.
Protecting access via hardware write protection
Write access to the device parameters via the local display, Web browser or operating tool (e.g.
FieldCare, DeviceCare) can be disabled via a write protection switch (DIP switch on the
motherboard). When hardware write protection is enabled, only read access to the parameters is
possible.
Hardware write protection is disabled when the device is delivered.
Protecting access via a password
Different passwords are available to protect write access to the device parameters or access to the
device via the WLAN interface.
• User-specific access code
Protect write access to the device parameters via the local display, Web browser or operating tool
(e.g. FieldCare, DeviceCare). Is equivalent to hardware write protection in terms of functionality.
• WLAN passphrase
The network key protects a connection between an operating unit (e.g. notebook or tablet) and the
device via the WLAN interface which can be ordered as an option.
User-specific access code
Write access to the device parameters via the local display, Web browser or operating tool (e.g.
FieldCare, DeviceCare) can be protected by the modifiable, user-specific access code.
When the device is delivered, the device does not have an access code and is equivalent to 0000
(open).
WLAN passphrase
A connection between an operating unit (e.g. notebook or tablet) and the device via the WLAN
interface which can be ordered as an option is protected by the network key. The WLAN
authentication of the network key complies with the IEEE 802.11 standard.
When the device is delivered, the network key is pre-defined depending on the device. It can be
changed via the WLAN settings submenu in the WLAN passphrase parameter.
General notes on the use of passwords
• The access code and network key supplied with the device should be changed during
commissioning.
• Follow the general rules for generating a secure password when defining and managing the access
code or network key.
• The user is responsible for the management and careful handling of the access code and network
key.
Access via fieldbus
When communicating via fieldbus, access to the device parameters can be restricted to "Read only"
access. The option can be changed in the Fieldbus writing access parameter.
This does not affect cyclic measured value transmission to the higher-order system, which is always
guaranteed.
Additional information: "Description of Device Parameters" document pertaining to the device .
Endress+Hauser7
Page 8
Access via Web server
The device can be operated and configured via a Web browser with the integrated Web server . The
connection is via the service interface (CDI-RJ45) or the WLAN interface.
The Web server is enabled when the device is delivered. The Web server can be disabled if necessary
(e.g. after commissioning) via the Web server functionality parameter.
The device and status information can be hidden on the login page. This prevents unauthorized
access to the information.
Additional information: "Description of Device Parameters" document pertaining to the device .
Input
Measured variableDirect measured variables
Volume flow (proportional to induced voltage)
Calculated measured variables
Mass flow
Proline Promag D 400
Measuring range
Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy
Electrical conductivity: ≥ 5 μS/cm for liquids in general
Flow characteristic values in SI units
Nominal
diameter
[mm][in][dm3/min][dm3/min][dm3][dm3/min]
2519 to 300750.51
401 ½25 to 7002001.53
50235 to 11003002.55
65–60 to 200050058
80390 to 3000750512
1004145 to 470012001020
Recommended
flow
min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
Flow characteristic values in US units
Nominal
diameter
[in][mm][gal/min][gal/min][gal][gal/min]
1252.5 to 80180.20.25
1 ½407 to 190500.50.75
25010 to 300750.51.25
–6516 to 50013012
Recommended
flow
min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
8Endress+Hauser
Page 9
Proline Promag D 400
Nominal
diameter
[in][mm][gal/min][gal/min][gal][gal/min]
38024 to 80020022.5
410040 to 125030024
Recommended
min./max. full scale value
(v ~ 0.3/10 m/s)
To calculate the measuring range, use the Applicator sizing tool → 59
Recommended measuring range
"Flow limit" section → 37
Operable flow range
Over 1000 : 1
Input signalExternal measured values
Various pressure transmitters and temperature measuring devices can be ordered from Endress
+Hauser: see "Accessories" section → 59
It is recommended to read in external measured values to calculate the following measured variables:
Corrected volume flow
flow
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Digital communication
The measured values can be written from the automation system to the measuring via:
• PROFIBUS DP
• Modbus RS485
• EtherNet/IP
Status input
Maximum input values• DC 30 V
• 6 mA
Response timeAdjustable: 5 to 200 ms
Input signal level• Low signal: DC –3 to +5 V
• High signal: DC 12 to 30 V
Assignable functions• Off
• Reset totalizers 1-3 separately
• Reset all totalizers
• Flow override
Endress+Hauser9
Page 10
Output
Output signalCurrent output
Current outputCan be set as:
Maximum output values• DC 24 V (no flow)
Load0 to 700 Ω
Resolution0.5 µA
DampingAdjustable: 0.07 to 999 s
Assignable measured
variables
Proline Promag D 400
• 4-20 mA NAMUR
• 4-20 mA US
• 4-20 mA HART
• 0-20 mA
• 22.5 mA
• Volume flow
• Mass flow
• Flow velocity
• Electronic temperature
Pulse/frequency/switch output
Function• With the order code for "Output; Input", option H: output 2 can be set as a pulse
or frequency output
• With the order code for "Output; Input", option I: output 2 and 3 can be set as a
pulse, frequency or switch output
VersionPassive, open collector
Maximum input values• DC 30 V
• 250 mA
Voltage dropFor 25 mA: ≤ DC 2 V
Pulse output
Pulse widthAdjustable: 0.05 to 2000 ms
Maximum pulse rate10000 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Output frequencyAdjustable: 0 to 12500 Hz
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
Switch output
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
• Volume flow
• Mass flow
• Volume flow
• Mass flow
• Flow velocity
• Electronic temperature
10Endress+Hauser
Page 11
Proline Promag D 400
Number of switching
cycles
Assignable functions• Off
Unlimited
• On
• Diagnostic behavior
• Limit value:
– Off
– Volume flow
– Mass flow
– Flow velocity
– Totalizer 1-3
– Electronic temperature
• Flow direction monitoring
• Status
– Empty pipe detection
– Low flow cut off
PROFIBUS DP
Signal encodingNRZ code
Data transfer9.6 kBaud…12 MBaud
Modbus RS485
Physical interfaceIn accordance with EIA/TIA-485-A standard
Terminating resistorIntegrated, can be activated via DIP switch on the transmitter electronics module
Signal on alarm
EtherNet/IP
StandardsIn accordance with IEEE 802.3
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure modeChoose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
0 to 20 mA
Failure modeChoose from:
• Maximum alarm: 22 mA
• Freely definable value between: 0 to 22.5 mA
HART current output
Device diagnosticsDevice condition can be read out via HART Command 48
Endress+Hauser11
Page 12
Pulse/frequency/switch output
Pulse output
Failure modeChoose from:
• Actual value
• No pulses
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value: 0 to 12500 Hz
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
PROFIBUS DP
Proline Promag D 400
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
Modbus RS485
Failure modeChoose from:
• NaN value instead of current value
• Last valid value
EtherNet/IP
Device diagnosticsDevice condition can be read out in Input Assembly
Local display
Plain text displayWith information on cause and remedial measures
BacklightRed backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
– HART protocol
– PROFIBUS DP
– Modbus RS485
– EtherNet/IP
• Via service interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 50
12Endress+Hauser
Page 13
Proline Promag D 400
Web server
Plain text displayWith information on cause and remedial measures
Light emitting diodes (LED)
Status informationStatus indicated by various light emitting diodes
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• EtherNet/IP network available
• EtherNet/IP connection established
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are user-selectable.
The following connections are galvanically isolated from each other:
• Inputs
• Outputs
• Power supply
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x69
HART protocol revision7
Device description files
(DTM, DD)
HART loadMin. 250 Ω
Dynamic variablesRead out the dynamic variables: HART command 3
Device variablesRead out the device variables: HART command 9
Information and files under:
www.endress.com
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Off
• Volume flow
• Mass flow
• Conductivity
• Flow velocity
• Electronic temperature
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Mass flow
• Flow velocity
• Electronic temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
The device variables are permanently assigned.
A maximum of 8 device variables can be transmitted:
• 0 = volume flow
• 1 = mass flow
• 3 = flow velocity
• 4 = electronic temperature
• 5 = totalizer 1
• 6 = totalizer 2
• 7 = totalizer 3
Endress+Hauser13
Page 14
PROFIBUS DP
Manufacturer ID0x11
Ident number0x1562
Profile version3.02
Device description files (GSD,
DTM, DD)
Output values
(from measuring device to
automation system)
Input values
(from automation system to
measuring device)
Supported functions• Identification & Maintenance
Configuration of the device
address
Information and files under:
• www.endress.com
• www.profibus.org
Analog input 1 to 4
• Mass flow
• Volume flow
• Flow velocity
• Electronic temperature
Digital input 1 to 2
• Empty pipe detection
• Low flow cut off
• Verification status
Totalizer 1 to 3
• Mass flow
• Volume flow
Analog output 1 (fixed assignment)
External density
Digital output 1 to 2 (fixed assignment)
• Digital output 1: switch positive zero return on/off
• Digital output 2: start verification
Totalizer 1 to 3
• Totalize
• Reset and hold
• Preset and hold
• Stop
• Operating mode configuration:
– Net flow total
– Forward flow total
– Reverse flow total
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
Option I: 4-20mA HART, 2 x pulse/frequency/switch
output, status input
Order code for "Output"Maximum power consumption
20Endress+Hauser
Page 21
Proline Promag D 400
1
2
1233
AB
1
2
A
2
1
B
Option L: PROFIBUS DP30 VA/8 W
Option M: Modbus RS48530 VA/8 W
Option N: EtherNet/IP30 VA/8 W
Current consumptionTransmitter
Order code for "Output"Maximum power consumption
Order code for "Power supply"Maximum
Option L: AC 100 to 240 V145 mA25 A (< 5 ms)
Option L: AC/DC 24 V350 mA27 A (< 5 ms)
Power supply failure
• Totalizers stop at the last value measured.
• Configuration is retained in the plug-in memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.
Electrical connectionConnecting the transmitter
3Supply voltage and signal transmission connection
ACompact version
BRemote version wall-mount housing
1Cable entry for supply voltage
2Cable entry for signal transmission
3Cable entry for signal transmission
Current consumption
Maximum
switch-on current
A0032041
Endress+Hauser21
Remote version connection
Connecting cable
A0032042
4Connecting cable connection: electrode and coil current cable
• Fix the cable run or route it in an armored conduit.
Cable movements can influence the measuring signal especially in the case of low fluid
conductivities.
• Route the cable well clear of electrical machines and switching elements.
• Ensure potential equalization between sensor and transmitter .
Connection examples
Current output 4 to 20 mA HART
A0029055
5Connection example for 4 to 20 mA HART current output (active)
1Automation system with current input (e.g. PLC)
2Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications → 27
3Connection for HART operating devices → 50
4Resistor for HART communication (≥ 250 Ω): observe maximum load → 10
5Analog display unit: observe maximum load → 10
6Transmitter
A0028762
6Connection example for 4 to 20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Power supply
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
1Automation system with status output (e.g. PLC)
2Power supply
3Transmitter: Observe input values
Potential equalizationRequirements
Please consider the following to ensure correct measurement:
• Same electrical potential for the fluid and sensor
• Remote version: same electrical potential for the sensor and transmitter
• Company-internal grounding concepts
• Pipe material and grounding
Connection example, standard scenario
Metal, grounded pipe
This connection method also applies:
• For plastic pipes
• For pipes with insulating liner
A0028764
A0032048
Endress+Hauser25
Page 26
Proline Promag D 400
+
–
1.
2.
3.
Connection example in special situations
Unlined and ungrounded metal pipe
This connection method also applies in situations where:
• The customary potential equalization is not used
• Equalizing currents are present
Ground cableCopper wire, at least 6 mm2 (0.0093 in2)
A0032049
Note the following when installing:
• Connect both pipe flanges to one another via a ground cable and ground them.
• Connect the connection housing of the transmitter or sensor to ground potential by means of the
ground terminal provided for the purpose. Mount the ground cable directly on the conductive
flange coating of the pipe with the flange screws.
For remote device versions, the ground terminal in the example always refers to the sensor and
not to the transmitter.
You can order the necessary ground cable from Endress+Hauser: → 57.
Pipe with a cathodic protection unit
This connection method is only used if the following two conditions are met:
• Metal pipe without liner or pipe with electrically conductive liner
• Cathodic protection is integrated in the personal protection equipment
Ground cableCopper wire, at least 6 mm2 (0.0093 in2)
A0032050
Note the following when installing:
The sensor is installed in the pipe in a way that provides electrical insulation.
For remote device versions, the ground terminal in the example always refers to the sensor and
not to the transmitter.
You can order the necessary ground cable from Endress+Hauser: → 57.
26Endress+Hauser
Page 27
Proline Promag D 400
Terminals
Transmitter
• Supply voltage cable: plug-in spring terminals for wire cross-sections
0.5 to 2.5 mm2 (20 to 14 AWG)
• Signal cable: plug-in spring terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Electrode cable: spring terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Coil current cable: spring terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
Sensor connection housing
Spring terminals for wire cross-sections0.5 to 2.5 mm2 (20 to 14 AWG)
Cable entries
Cable entry thread
• M20 x 1.5
• Via adapter:
– NPT ½"
– G ½"
Cable gland
• For standard cable: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• For reinforced cable: M20 × 1.5 with cable 9.5 to 16 mm (0.37 to 0.63 in)
If metal cable entries are used, use a grounding plate.
Cable specificationPermitted temperature range
Minimum requirement: cable temperature range ≥ ambient temperature +20 K
Power supply cable
Standard installation cable is sufficient.
Signal cable
Current output 0/4 to 20 mA
Standard installation cable is sufficient.
Current output 4 to 20 mA HART
A shielded cable is recommended. Observe grounding concept of the plant.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
PROFIBUS DP
The IEC 61158 standard specifies two types of cable (A and B) for the bus line which can be used for
every transmission rate. Cable type A is recommended.
Cable typeA
Characteristic impedance135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance< 30 pF/m
Wire cross-section
Cable typeTwisted pairs
Loop resistance≤110 Ω/km
Signal dampingMax. 9 dB over the entire length of the cable cross-section
ShieldCopper braided shielding or braided shielding with foil shield. When grounding
> 0.34 mm2 (22 AWG)
the cable shield, observe the grounding concept of the plant.
Endress+Hauser27
Page 28
Proline Promag D 400
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used
for every transmission rate. Cable type A is recommended.
Cable typeA
Characteristic impedance135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance< 30 pF/m
Wire cross-section
Cable typeTwisted pairs
Loop resistance≤110 Ω/km
Signal dampingMax. 9 dB over the entire length of the cable cross-section
ShieldCopper braided shielding or braided shielding with foil shield. When grounding
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a cable
used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to the
"Media Planning and Installation Manual. EtherNet/IP" of ODVA Organization
> 0.34 mm2 (22 AWG)
the cable shield, observe the grounding concept of the plant.
Connecting cable for remote version
Electrode cable
Standard cable
Conductor resistance≤50 Ω/km (0.015 Ω/ft)
Capacitance: core/shield≤420 pF/m (128 pF/ft)
Operating temperature–20 to +80 °C (–68 to +176 °F)
3 ×0.38 mm2 (20 AWG) with common, braided copper shield ( ~9.5 mm
(0.37 in)) and individual shielded cores
Coil current cable
Standard cable
Conductor resistance≤37 Ω/km (0.011 Ω/ft)
Capacitance: core/core,
shield grounded
Operating temperature–20 to +80 °C (–68 to +176 °F)
Test voltage for cable
insulation
3 ×0.75 mm2 (18 AWG) with common, braided copper shield ( ~9 mm
(0.35 in))
Operation in zones of severe electrical interference
The measuring system meets the general safety requirements → 56 and EMC specifications
→ 36.
Grounding is by means of the ground terminal provided for the purpose inside the connection
housing. The stripped and twisted lengths of cable shield to the ground terminal must be as short as
possible.
Performance characteristics
Reference operating
conditions
Maximum measured errorError limits under reference operating conditions
Endress+Hauser29
• Error limits following DIN EN 29104, in future ISO 20456
• Water, typically +15 to +45 °C (+59 to +113 °F); 0.5 to 7 bar (73 to 101 psi)
• Data as indicated in the calibration protocol
• Accuracy based on accredited calibration rigs according to ISO 17025
o.r. = of reading
Volume flow
±0.5 % o.r. ± 1 mm/s (0.04 in/s)
Fluctuations in the supply voltage do not have any effect within the specified range.
A0032055
15Maximum measured error in % o.r.
Page 30
Proline Promag D 400
h
Accuracy of outputs
The outputs have the following base accuracy specifications.
Current output
AccuracyMax. ±5 µA
Pulse/frequency output
o.r. = of reading
AccuracyMax. ±50 ppm o.r. (across the entire ambient temperature range)
Repeatability
Influence of ambient
temperature
Mounting location
o.r. = of reading
Volume flow
max. ±0.1 % o.r. ± 0.5 mm/s (0.02 in/s)
Current output
o.r. = of reading
Temperature coefficientMax. ±0.005 % o.r./°C
Pulse/frequency output
Temperature coefficientNo additional effect. Included in accuracy.
Installation
No special measures such as supports etc. are necessary. External forces are absorbed by the
construction of the device.
A0029343
Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the next pipe
elbow: h ≥ 2 × DN
To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid
the following mounting locations in the pipe:
• Highest point of a pipeline.
• Directly upstream of a free pipe outlet in a down pipe.
30Endress+Hauser
Page 31
Proline Promag D 400
h
2
1
2 x DN³
5 x DN³
Installation in down pipes
Install a siphon with a vent valve downstream of the sensor in down pipes whose length h ≥ 5 m
(16.4 ft). This precaution is to avoid low pressure and the consequent risk of damage to the
measuring tube. This measure also prevents the system losing prime.
For information on the liner's resistance to partial vacuum
A0028981
16Installation in a down pipe
1Vent valve
2Pipe siphon
hLength of down pipe
Orientation
Installation in partially filled pipes
A partially filled pipe with a gradient necessitates a drain-type configuration. The empty pipe
detection (EPD) function offers additional protection by detecting empty or partially filled pipes.
A0029257
The direction of the arrow on the sensor nameplate helps you to install the sensor according to the
flow direction (direction of medium flow through the piping).
An optimum orientation position helps avoid gas and air accumulations and deposits in the
measuring tube.
Vertical
A0015591
Optimum for self-emptying pipe systems.
Endress+Hauser31
Page 32
Proline Promag D 400
11
≥ 5 x DN
≥ 2 x DN
100
10
0.5
d / D
[mbar]
0.60.7 0.80.9
1 m/s
2 m/s
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
1
D
d
max. 8°
Horizontal
1Measuring electrodes for signal detection
Ideally, the measuring electrode plane should be horizontal. This prevents brief insulation of
the two measuring electrodes by entrained air bubbles.
A0017195
Inlet and outlet runs
Adapters
If possible, install the sensor upstream from fittings such as valves, T-pieces or elbows.
Observe the following inlet and outlet runs to comply with accuracy specifications:
A0028997
Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in largerdiameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very
slow-moving fluids.
The nomogram shown here can be used to calculate the pressure loss caused by reducers and
expanders:
• Calculate the ratio of the diameters d/D.
• From the nomogram read off the pressure loss as a function of flow velocity (downstream from
the reduction) and the d/D ratio.
The nomogram only applies to liquids with a viscosity similar to that of water.
32Endress+Hauser
A0029002
Page 33
Proline Promag D 400
5
1
2
3
4
200
100
5
10100200
[m]
[ S/cm]µ
L
max
[ ]ft
2006000400
L
max
Mounting kit
The sensor is installed between the pipe flanges using a mounting kit. The device is centered using
the recesses on the sensor. Centering sleeves are also provided depending on the flange standard or
the diameter of the pitch circle.
A mounting kit – consisting of mounting bolts, seals, nuts and washers – can be ordered
separately (see "Accessories" section → 58).
To ensure correct measuring results when using the remote version,
observe the maximum permitted length of the connecting cable L
max
the conductivity of the fluid.
If measuring liquids in general: 5 µS/cm
18Permitted length of connecting cable for remote version
Colored area = permitted range
L
=
length of connecting cable in [m] ([ft])
max
[µS/cm] = fluid conductivity
. This length is determined by
A0016539
Endress+Hauser33
Page 34
Proline Promag D 400
149 (5.85)
210.5 (8.29)
=
5.8 (0.23)
17 (0.67)=
14 (0.55)
5.8 (0.23)
ø 20…70
( 0.79…2.75)ø
~102 (~ 4.0)
4 x
SW 10
3 x
TX 25
Installing the wall-mount
housing
Wall mounting
A0020523
19Engineering unit mm (in)
Post mounting
20Engineering unit mm (in)
Special mounting
instructions
Display protection
To ensure that the optional display protection can be easily opened, maintain the following
minimum head clearance: 350 mm (13.8 in)
34Endress+Hauser
A0029051
Page 35
Proline Promag D 400
Environment
Ambient temperature range
Transmitter–40 to +60 °C (–40 to +140 °F)
Local display–20 to +60 °C (–4 to +140 °F), the readability of the display may be
impaired at temperatures outside the temperature range.
Sensor–20 to +60 °C (–4 to +140 °F)
Mount the transmitter separately from the sensor if both the ambient
and fluid temperatures are high.
LinerDo not exceed or fall below the permitted temperature range of the liner .
If operating outdoors:
• Install the measuring device in a shady location.
• Avoid direct sunlight, particularly in warm climatic regions.
• Avoid direct exposure to weather conditions.
• If the compact version of the device is insulated at low temperatures, the insulation must also
include the device neck.
• Protect the display against impact.
• Protect the display from abrasion by sand in desert areas.
You can order a display guard from Endress+Hauser : → 57
Temperature tables
Observe the interdependencies between the permitted ambient and fluid temperatures when
operating the device in hazardous areas.
For detailed information on the temperature tables, see the separate document entitled "Safety
Instructions" (XA) for the device.
Storage temperature
Atmosphere
Degree of protection
Vibration resistance
The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors.→ 35
• Protect the measuring device against direct sunlight during storage in order to avoid unacceptably
high surface temperatures.
• Select a storage location where moisture cannot collect in the measuring device as fungus or
bacteria infestation can damage the liner.
• If protection caps or protective covers are mounted these should never be removed before
installing the measuring device.
If a plastic transmitter housing is permanently exposed to certain steam and air mixtures, this can
damage the housing.
If you are unsure, please contact your Endress+Hauser Sales Center for clarification.
Transmitter
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
Sensor
As standard: IP66/67, type 4X enclosure
Compact version
• Vibration, sinusoidal according to IEC 60068-2-6
– 2 to 8.4 Hz, 3.5 mm peak
– 8.4 to 2000 Hz, 1 g peak
• Vibration broad-band random, according to IEC 60068-2-64
– 10 to 200 Hz, 0.003 g2/Hz
– 200 to 2000 Hz, 0.001 g2/Hz
– Total: 1.54 g rms
Endress+Hauser35
Page 36
Remote version
405060708090100 110120 130 140 15030
[°F]
[psi]
40
0
80
0
[bar]
510152025303540554550
6065
0
[°C]
4
8
12
16
20
405060708090100 110 120 130 140 15030
[°F]
[psi]
40
0
80
0
[bar]
510152025303540554550
6065
0
[°C]
4
8
12
16
20
• Vibration, sinusoidal according to IEC 60068-2-6
– 2 to 8.4 Hz, 7.5 mm peak
– 8.4 to 2000 Hz, 2 g peak
• Vibration broad-band random, according to IEC 60068-2-64
– 10 to 200 Hz, 0.01 g2/Hz
– 200 to 2000 Hz, 0.003 g2/Hz
– Total: 1.54 g rms
Proline Promag D 400
Shock resistance
Impact resistance
Mechanical load
Electromagnetic
compatibility (EMC)
Medium temperature range
Shock, half-sine according to IEC 60068-2-27
6 ms 50 g
Rough handling shocks according to IEC 60068-2-31
• Protect the transmitter housing against mechanical effects, such as shock or impact; the use of the
remote version is sometimes preferable.
• Never use the transmitter housing as a ladder or climbing aid.
• As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
• Complies with emission limits for industry as per EN 55011 (Class A)
• Device version with PROFIBUS DP: Complies with emission limits for industry as per EN 50170
Volume 2, IEC 61784
The following applies for PROFIBUS DP: If baud rates > 1.5 MBaud, an EMC cable entry must be
used and the cable shield must continue as far as the terminal wherever possible.
For details, refer to the Declaration of Conformity.
Process
0 to +60 °C (+32 to +140 °F) for polyamide
Pressure-temperature
ratings
Pressure tightness
36Endress+Hauser
Permitted process pressure
Measuring tube: 0 mbar abs. (0 psi abs.) at a medium temperature of ≤ +60 °C (+140 °F)
A0032066-EN
Page 37
Proline Promag D 400
L
Flow limit
Pressure loss
System pressure
The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The
optimum velocity of flow is between 2 to 3 m/s (6.56 to 9.84 ft/s). Also match the velocity of flow
(v) to the physical properties of the fluid:
• v < 2 m/s (6.56 ft/s): for abrasive fluids (e.g. potter's clay, lime milk, ore slurry)
• v > 2 m/s (6.56 ft/s): for fluids producing buildup (e.g. wastewater sludge)
A necessary increase in the flow velocity can be achieved by reducing the sensor nominal
diameter.
For an overview of the full scale values for the measuring range, see the "Measuring range"
section → 8
• No pressure loss occurs if the sensor is installed in a pipe with the same nominal diameter.
• Pressure losses for configurations incorporating adapters according to DIN EN 545 → 32
A0028777
Never install the sensor on the pump suction side in order to avoid the risk of low pressure, and thus
damage to the liner.
Furthermore, install pulse dampers if reciprocating, diaphragm or peristaltic pumps are used.
Vibrations
• For information on the liner's resistance to partial vacuum → 36
• For information on the shock resistance of the measuring system
• For information on the vibration resistance of the measuring system
In the event of very strong vibrations, the pipe and sensor must be supported and fixed.
It is also advisable to mount the sensor and transmitter separately.
• For information on the shock resistance of the measuring system
• For information on the vibration resistance of the measuring system
A0029004
21Measures to avoid device vibrations (L > 10 m (33 ft))
Endress+Hauser37
Page 38
Mechanical construction
d1
e1
d1
d2
d1
d2
e1
e1
e2
d2
DN 25…40
(1 to 1½")
DN 50
(2")
DN 65…100
(2½ to 4")
A
B
D
E
F
G
H
C
Dimensions in SI unitsCompact version
Order code for "Housing", option M "Compact, polycarbonate" or option A "Compact, aluminum, coated"
Proline Promag D 400
A0020356
22Engineering unit mm (in)
1)
DN
[mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm]
25193103901671904323355862468
401931039016720152253691043887
5019310390167212622748312450106
6519310390167222702929313960125
80193103901672267530111715176135
100193103901672408932914817997160
1)EN (DIN), JIS
2)max. Ø seals
ABCDEFGHd1d2e1
2)
38Endress+Hauser
Page 39
Proline Promag D 400
d1
e1
d1
d2
d1
d2
e1
e1
e2
d2
DN 25…40
(1 to 1½")
DN 50
(2")
DN 65…100
(2½ to 4")
22.5°
A
B
D
E
F
G
L
C
Order code for "Housing", option Q "Compact, polycarbonate, inclined" or option R "Compact, aluminum,
coated, inclined"
A0020357
23Engineering unit mm (in)
1)
DN
[mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm]
25199119801672354327855862468
401991198016724652298691043887
5019911980167257623198312450106
6519911980167267703379313960125
80199119801672717534611715176135
100199119801672858937414817997160
ABCDEFGHd1d2e1
2)
1)EN (DIN), JIS
2)max. Ø seals
Endress+Hauser39
Page 40
Proline Promag D 400
C
B
D
E
F
A
E
C
B
A
D
F
H
G
d1
e1
d1
d2
d1
d2
e1
e1
e2
d2
DN 25…40
(1 to 1½")
DN 65…100
(2½ to 4")
DN 50
(2")
Transmitter remote version
Order code for "Housing", option N "Remote, polycarbonate" or option P "Remote, aluminum coated"
A0020522
A
[mm]
167211872423280
B
[mm]
C
[mm]
D
[mm]
E
[mm]
F
[mm]
Sensor remote version
40Endress+Hauser
24Engineering unit mm (in)
A0021694
Page 41
Proline Promag D 400
d1
e1
d1
d2
d1
d2
e1
e1
e2
d2
DN 25…40
(1 to 1½")
DN 50
(2")
DN 65…100
(2½ to 4")
A
B
D
E
F
G
H
C
1)
DN
[mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm]
251291631435510219243235862468
4012916314369102203522551043887
50129163143831022146227612450106
65129163143931022247029413960125
801291631431171022287530315176135
1001291631431481022428933117997160
1)EN (DIN), JIS
2)max. Ø seals
ABCDEFGHd 1d 2e 1
Dimensions in US unitsCompact version
Order code for "Housing", option M "Compact, polycarbonate" or option A "Compact, aluminum, coated"
• JIS B2220
For information on the different materials used in the process connections → 48
Operability
Operating concept
48Endress+Hauser
Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Page 49
Proline Promag D 400
Fast and safe commissioning
• Guided menus ("Make-it-run" wizards) for applications
• Menu guidance with brief explanations of the individual parameter functions
• Device access via Web server
• Optional: WLAN access to device via mobile handheld terminal
Reliable operation
• Operation in local language
• Uniform operating philosophy applied to device and operating tools
• If replacing electronic modules, transfer the device configuration via the integrated memory
(integrated HistoROM) which contains the process and measuring device data and the event
logbook. No need to reconfigure.
• Troubleshooting measures can be called up via the device and in the operating tools
• Diverse simulation options, logbook for events that occur and optional line recorder functions
Languages
Can be operated in the following languages:
• Via local operation:
English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese,
Japanese, Bahasa (Indonesian), Vietnamese, Czech, Swedish
• Via "FieldCare", "DeviceCare" operating tool:
English, German, French, Spanish, Italian, Chinese, Japanese
• Via Web browser (only available for device versions with HART, PROFIBUS DP and EtherNet/IP):
English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese,
Japanese, Bahasa (Indonesian), Vietnamese, Czech, Swedish
Local displayVia display module
Two display modules are available:
• Standard:
4-line, illuminated, graphic display; touch control
• Optionally via order code for "Display", option W1 "WLAN display":
4-line, illuminated, graphic display; touch control + WLAN
Information about WLAN interface → 52
A0032074
29Operation with touch control
Display elements
• 4-line, illuminated, graphic display
• White background lighting; switches to red in event of device errors
• Format for displaying measured variables and status variables can be individually configured
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
Operating elements
• External operation via touch control (3 optical keys) without opening the housing: , ,
• Operating elements also accessible in various hazardous areas
Endress+Hauser49
Page 50
Remote operationVia HART protocol
1235
7
46
12
3
444
This communication interface is available in device versions with a HART output.
30Options for remote operation via HART protocol
1Control system (e.g. PLC)
2Field Communicator 475
3Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
4Commubox FXA195 (USB)
5Field Xpert SFX350 or SFX370
6VIATOR Bluetooth modem with connecting cable
7Transmitter
Proline Promag D 400
A0028747
Via PROFIBUS DP network
This communication interface is available in device versions with PROFIBUS DP.
31Options for remote operation via PROFIBUS DP network
1Automation system
2Computer with PROFIBUS network card
3PROFIBUS DP network
4Measuring device
A0020903
Via Modbus RS485 protocol
This communication interface is available in device versions with a Modbus-RS485 output.
50Endress+Hauser
Page 51
Proline Promag D 400
12
3
4
213
555
A0029437
32Options for remote operation via Modbus-RS485 protocol (active)
1Control system (e.g. PLC)
2Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP" or Modbus DTM
3Transmitter
Via Ethernet-based fieldbus
This communication interface is available in device versions with EtherNet/IP.
Service interfaceVia service interface (CDI-RJ45)
Endress+Hauser51
33Options for remote operation via Ethernet-based fieldbus
1Automation system, e.g. "RSLogix" (Rockwell Automation)
2Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell
Automation) or with Electronic Data Sheet (EDS)
3Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"
4Ethernet switch
5Measuring device
This communication interface is present in the following device version:
• Order code for "Output", option H: 4-20/0-20 mA HART, pulse/frequency/switch output
• Order code for "Output", option I: 4-20/0-20 mA HART, pulse/frequency/switch output, status
input
• Order code for "Output", option L: PROFIBUS DP
• Order code for "Output", option N: EtherNet/IP
• Order code for "Output", option M: Modbus RS485
A0032078
Page 52
Proline Promag D 400
open
press
2
3
4
5
1
2
3
A0029163
34Connection via service interface (CDI-RJ45)
1Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated
device Web server or with "FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"
or Modbus DTM
2Standard Ethernet connecting cable with RJ45 plug
3Service interface (CDI-RJ45) of the measuring device with access to the integrated Web server
Via WLAN interface
The optional WLAN interface is available on the following device version:
Order code for "Display", option W1 "WLAN display":
4-line, illuminated, graphic display; touch control + WLAN
A0032079
1Transmitter with integrated WLAN antenna
2LED lit constantly: WLAN reception is enabled on measuring device
3LED flashing: WLAN connection established between operating unit and measuring device
4Computer with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for
accessing the integrated device Web server or with operating tool (e.g. FieldCare, DeviceCare)
5Mobile handheld terminal with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft
Edge) for accessing the integrated device Web server or operating tool (e.g. FieldCare, DeviceCare)
Wireless LANIEEE 802.11 b/g (2.4 GHz) WLAN
EncryptionWPA2 PSK/TKIP AES-128
Supported operating tools
Configurable channels1 to 11
FunctionAccess point with DHCP
Range with integrated
antenna
Different operating tools can be used for local or remote access to the measuring device. Depending
on the operating tool used, access is possible with different operating units and via a variety of
Max. 10 m (32 ft)
interfaces.
52Endress+Hauser
Page 53
Proline Promag D 400
Supported operating
tools
Web browserNotebook, PC or tablet
DeviceCare SFE100Notebook, PC or tablet
FieldCare SFE500Notebook, PC or tablet
Device XpertField Xpert SFX
Operating unitInterfaceAdditional information
with Web browser
with Microsoft Windows
system
with Microsoft Windows
system
100/350/370
• CDI-RJ45 service
interface
• WLAN interface
• Ethernet-based
fieldbus (EtherNet/IP)
• CDI-RJ45 service
interface
• WLAN interface
• Fieldbus protocol
• CDI-RJ45 service
interface
• WLAN interface
• Fieldbus protocol
HART and
FOUNDATION Fieldbus
fieldbus protocol
Special Documentation for the
device
→ 59
→ 59
Operating Instructions
BA01202S
Device description files:
Use update function of
handheld terminal
Other operating tools based on FDT technology with a device driver such as DTM/iDTM or
DD/EDD can be used for device operation. These operating tools are available from the
individual manufacturers. Integration into the following operating tools, among others, is
supported:
• Process Device Manager (PDM) by Siemens → www.siemens.com
• Asset Management Solutions (AMS) by Emerson → www.emersonprocess.com
• FieldCommunicator 375/475 by Emerson → www.emersonprocess.com
• Field Device Manager (FDM) by Honeywell → www.honeywellprocess.com
• FieldMate by Yokogawa → www.yokogawa.com
• PACTWare → www.pactware.com
The associated device description files are available at: www.endress.com → Downloads
Web server
Thanks to the integrated Web server, the device can be operated and configured via a Web browser
and via a service interface (CDI-RJ45) or via a WLAN interface. The structure of the operating menu
is the same as for the local display. In addition to the measured values, status information on the
device is also displayed and allows the user to monitor the status of the device. Furthermore the
device data can be managed and the network parameters can be configured.
A device that has a WLAN interface (can be ordered as an option) is required for the WLAN
connection: order code for "Display", option W1 "WLAN display": 4-line, illuminated; touch control +
WLAN. The device acts as an Access Point and enables communication by computer or a mobile
handheld terminal.
Supported functions
Data exchange between the operating unit (such as a notebook for example) and the measuring
device:
– Uploading the configuration from the measuring device (XML format, configuration backup)
– Save the configuration to the measuring device (XML format, restore configuration)
– Export event list (.csv file)
– Export parameter settings (.csv file, create documentation of the measuring point configuration)
– Export the Heartbeat verification log (PDF file, only available with the "Heartbeat Verification"
application package)
– Flash firmware version for device firmware upgrade, for instance
– Download driver for system integration
Endress+Hauser53
Page 54
Proline Promag D 400
HistoROM data management
The measuring device features HistoROM data management. HistoROM data management
comprises both the storage and import/export of key device and process data, making operation and
servicing far more reliable, secure and efficient.
When the device is delivered, the factory settings of the configuration data are stored as a
backup in the device memory. This memory can be overwritten with an updated data record, for
example after commissioning.
Additional information on the data storage concept
There are different types of data storage units in which device data are stored and used by the device:
Device memoryT-DATS-DAT
Available data• Device firmware package
• Driver for system integration e.g.:
– DD for HART
– GSD for PROFIBUS DP
– EDS for EtherNet/IP
Storage location Fixed on the user interface board in
the connection compartment
• Event history, such as diagnostic events
• Measured value memory ("Extended
HistoROM" order option)
• Current parameter data record (used by
firmware at run time)
• Maximum indicators (min/max values)
• Totalizer values
Can be plugged into the user interface board
in the connection compartment
• Sensor data: diameter etc.
• Serial number
• User-specific access code (to use the
"Maintenance" user role)
• Calibration data
• Device configuration (e.g. SW options,
fixed I/O or multi I/O)
In the sensor plug in the transmitter neck
part
Data backup
Automatic
• The most important device data (sensor and transmitter) are automatically saved in the DAT
modules
• If the transmitter or measuring device is replaced: once the T-DAT containing the previous device
data has been exchanged, the new measuring device is ready for operation again immediately
without any errors
• If the sensor is replaced: once the sensor has been replaced, new sensor data are transferred from
the S-DAT in the measuring device and the measuring device is ready for operation again
immediately without any errors
Data transfer
Manual
Transfer of a device configuration to another device using the export function of the specific
operating tool, e.g. with FieldCare, DeviceCare or Web server: to duplicate the configuration or to
store in an archive (e.g. for backup purposes)
Event list
Automatic
• Chronological display of up to 20 event messages in the events list
• If the Extended HistoROM application package (order option) is enabled: up to 100 event
messages are displayed in the events list along with a time stamp, plain text description and
remedial measures
• The events list can be exported and displayed via a variety of interfaces and operating tools e.g.
DeviceCare, FieldCare or Web server
Data logging
Manual
If the Extended HistoROM application package (order option) is enabled:
• Record up to 1000 measured values via 1 to 4 channels
• User configurable recording interval
• Record up to 250 measured values via each of the 4 memory channels
• Export the measured value log via a variety of interfaces and operating tools e.g. FieldCare,
DeviceCare or Web server
• Use the recorded measured value data in the integrated device simulation function in the
Diagnostics submenu.
54Endress+Hauser
Page 55
Proline Promag D 400
Certificates and approvals
CE mark
C-Tick symbol
Ex approval
Drinking water approval
HART certificationHART interface
The measuring system is in conformity with the statutory requirements of the applicable EU
Directives. These are listed in the corresponding EU Declaration of Conformity along with the
standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
The measuring device is certified for use in hazardous areas and the relevant safety instructions are
provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on
the nameplate.
The separate Ex documentation (XA) containing all the relevant explosion protection data is
available from your Endress+Hauser sales center.
ATEX, IECEx
Currently, the following versions for use in hazardous areas are available:
• ACS
• KTW/W270
• NSF 61
• WRAS BS 6920
The measuring device is certified and registered by the FieldComm Group. The measuring system
meets all the requirements of the following specifications:
• Certified according to HART 7
• The device can also be operated with certified devices of other manufacturers (interoperability)
Certification PROFIBUSPROFIBUS interface
The measuring device is certified and registered by the PROFIBUS User Organization (PNO). The
measuring system meets all the requirements of the following specifications:
• Certified in accordance with PROFIBUS PA Profile 3.02
• The device can also be operated with certified devices of other manufacturers (interoperability)
EtherNet/IP certification
Radio approval
The measuring device is certified and registered by the ODVA (Open Device Vendor Association).
The measuring system meets all the requirements of the following specifications:
• Certified in accordance with the ODVA Conformance Test
• EtherNet/IP Performance Test
• EtherNet/IP PlugFest compliance
• The device can also be operated with certified devices of other manufacturers (interoperability)
Europe:
RED 2014/53/EU
United States of America:
CFR Title 47, FCC Part 15.247
Canada:
RSS-247 Issue 1
Japan:
Article 2 clause 1 item 19
Additional country-specific approvals on request.
Endress+Hauser55
Page 56
Proline Promag D 400
Other standards and
guidelines
• EN 60529
Degrees of protection provided by enclosures (IP code)
• EN 61010-1
Safety requirements for electrical equipment for measurement, control and laboratory use general requirements
• IEC/EN 61326
Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC
requirements).
• ANSI/ISA-61010-1 (82.02.01): 2004
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use - Part
1 General Requirements
• CAN/CSA-C22.2 No. 61010-1-04
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use - Part
1 General Requirements
• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment
• NAMUR NE 32
Data retention in the event of a power failure in field and control instruments with
microprocessors
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with
analog output signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics
• NAMUR NE 105
Specifications for integrating fieldbus devices in engineering tools for field devices
• NAMUR NE 107
Self-monitoring and diagnosis of field devices
• NAMUR NE 131
Requirements for field devices for standard applications
Product generation index
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field ->
Open product page -> The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Release dateProduct rootModification
01.07.20125D4BOriginal
01.11.20165D4C• Web server: current version
• Logbook: current concept, including Parameter Change
• Upload/download: current concept
• Heartbeat Technology: new hardware, diagnostics, events
More information is available from your Sales Center or at:
www.service.endress.com → Downloads
56Endress+Hauser
Page 57
Proline Promag D 400
Application packages
Many different application packages are available to enhance the functionality of the device. Such
packages might be needed to address safety aspects or specific application requirements.
The application packages can be ordered with the device or subsequently from Endress+Hauser.
Detailed information on the order code in question is available from your local Endress+Hauser sales
center or on the product page of the Endress+Hauser website: www.endress.com.
Diagnostics functions
Heartbeat Technology
PackageDescription
Extended HistoROMComprises extended functions concerning the event log and the activation of the
measured value memory.
Event log:
Memory volume is extended from 20 message entries (standard version) to up to
100 entries.
Data logging (line recorder):
• Memory capacity for up to 1000 measured values is activated.
• 250 measured values can be output via each of the 4 memory channels. The
recording interval can be defined and configured by the user.
• Measured value logs can be accessed via the local display or operating tool e.g.
FieldCare, DeviceCare or Web server.
PackageDescription
Heartbeat Verification
+Monitoring
Heartbeat Monitoring
Continuously supplies data, which are characteristic of the measuring principle, to
an external condition monitoring system for the purpose of preventive
maintenance or process analysis. These data enable the operator to:
• Draw conclusions - using these data and other information - about the impact
process influences (such as corrosion, abrasion, buildup etc.) have on the
measuring performance over time.
• Schedule servicing in time.
• Monitor the process or product quality, e.g. gas pockets.
Heartbeat Verification
Meets the requirement for traceable verification to DIN ISO 9001:2008 Chapter
7.6 a) "Control of monitoring and measuring equipment".
• Functional testing in the installed state without interrupting the process.
• Traceable verification results on request, including a report.
• Simple testing process via local operation or other operating interfaces.
• Clear measuring point assessment (pass/fail) with high test coverage within the
framework of manufacturer specifications.
• Extension of calibration intervals according to operator's risk assessment.
Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are
available for the device. Detailed information on the order code in question is available from your
local Endress+Hauser sales center or on the product page of the Endress+Hauser website:
www.endress.com.
Device-specific accessoriesFor the transmitter
AccessoriesDescription
Display protectionIs used to protect the display against impact or scoring from sand in desert areas.
For details, see Special Documentation SD00333F
Connecting cable for
remote version
Endress+Hauser57
Coil current and electrode cables, various lengths, reinforced cables available on
request.
Page 58
Post mounting kitPost mounting kit for transmitter.
Compact → Remote
conversion kit
For the sensor
AccessoriesDescription
Mounting kitConsists of:
For converting a compact device version to a remote device version.
• 2 process connections
• Screws
• Seals
Proline Promag D 400
Communication-specific
accessories
AccessoriesDescription
Commubox FXA195
HART
Commubox FXA291Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
HART Loop Converter
HMX50
Wireless HART adapter
SWA70
Fieldgate FXA320Gateway for the remote monitoring of connected 4 to 20 mA measuring devices via
Fieldgate FXA520Gateway for the remote diagnostics and remote configuration of connected HART
Field Xpert SFX350Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
For intrinsically safe HART communication with FieldCare via the USB interface.
For details, see "Technical Information" TI00404F
Common Data Interface) and the USB port of a computer or laptop.
For details, see the "Technical Information" document TI405C/07
Is used to evaluate and convert dynamic HART process variables to analog current
signals or limit values.
For details, see "Technical Information" TI00429F and Operating Instructions
BA00371F
Is used for the wireless connection of field devices.
The WirelessHART adapter can be easily integrated into field devices and existing
infrastructures, offers data protection and transmission safety and can be operated
in parallel with other wireless networks with minimum cabling complexity.
For details, see Operating Instructions BA00061S
a Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions
BA00053S
measuring devices via a Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions
BA00051S
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices in the non-Ex area.
For details, see Operating Instructions BA01202S
Field Xpert SFX370Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices in the non-Ex area and the Ex area.
For details, see Operating Instructions BA01202S
58Endress+Hauser
Page 59
Proline Promag D 400
Service-specific accessories
AccessoriesDescription
ApplicatorSoftware for selecting and sizing Endress+Hauser measuring devices:
• Choice of measuring devices for industrial requirements
• Calculation of all the necessary data for identifying the optimum flowmeter: e.g.
nominal diameter, pressure loss, flow velocity and accuracy.
• Graphic illustration of the calculation results
• Determination of the partial order code, administration, documentation and
access to all project-related data and parameters over the entire life cycle of a
project.
Applicator is available:
• Via the Internet: https://wapps.endress.com/applicator
• As a downloadable DVD for local PC installation.
W@MW@M Life Cycle Management
Improved productivity with information at your fingertips. Data relevant to a plant
and its components is generated from the first stages of planning and during the
asset’s complete life cycle.
W@M Life Cycle Management is an open and flexible information platform with
online and on-site tools. Instant access for your staff to current, in-depth data
shortens your plant’s engineering time, speeds up procurement processes and
increases plant uptime.
Combined with the right services, W@M Life Cycle Management boosts
productivity in every phase. For more information, visit
www.endress.com/lifecyclemanagement
FieldCareFDT-based plant asset management tool from Endress+Hauser.
It can configure all smart field units in your system and helps you manage them. By
using the status information, it is also a simple but effective way of checking their
status and condition.
For details, see Operating Instructions BA00027S and BA00059S
System components
DeviceCareTool for connecting and configuring Endress+Hauser field devices.
For details, see Innovation brochure IN01047S
Commubox FXA291Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
Common Data Interface) and the USB port of a computer or laptop.
For details, see "Technical Information" TI00405C
AccessoriesDescription
Memograph M graphic
display recorder
The Memograph M graphic display recorder provides information on all relevant
measured variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on a SD card or USB stick.
For details, see "Technical Information" TI00133R and Operating Instructions
BA00247R
Supplementary documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
2-D matrix code (QR code) on the nameplate.
Endress+Hauser59
Page 60
Standard documentationBrief Operating Instructions