Emerson S4K4U-6kVA, S4K6U-10kVA Specification Sheet

S4KC Series Industrial On-Line UPS
208 V, 6000 & 10000 VA User Manual
While every precaution has been taken to ensure accuracy and completeness in this manual, EGS Electrical Group, LLC. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
The SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Oce. All other product or service names are the property of their registered owners.
©2013 EGS Electrical Group, LLC. All rights reserved. Specications are subject to change without notice.
Contents
Important Safety Precautions 6
Save these Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Glossary of Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.0 Introduction 9
2.0 System Description 10
2.1 Surge Protection Devices (SPD) & EMI/RFI Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2 Rectier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5 Dc-to-Dc Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7 Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.0 Major Components 12
3.1 Main Frame & Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 Removable Power Distribution Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Internal Battery Packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.0 Preinstallation 17
4.1 Unpacking & Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.2 What’s Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.0 Installation 18
5.1 Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.2 Installing the Main Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4 Connect Input/Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
iv | Contents
6.0 Conguration Program 29
6.1 Conguration Program Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.0 Controls & Indicators 30
7.1 On/Alarm Silence/Manual Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7.2 Standby/Manual Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.3 Load Level Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.4 Battery Level Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.5 UPS Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8.0 Operation 34
8.1 Startup Checklist for the S4KC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.2 Initial Startup & Electrical Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.3 Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.4 Put the S4KC in Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.5 Shut Down the S4KC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.6 Disconnecting Input Power from the S4KC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.7 Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.0 Communication 36
9.1 Communication Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.2 Terminal Block Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.3 UPS IntelliSlot Communication Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9.4 Remote Emergency Power O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.0 Maintenance 39
10.1 Replacing the Internal Battery Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
10.2 Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.3 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
10.4 Checking UPS Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.5 Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.6 Replacing the Power Module on S4K6U10KC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
S4KC SERIES USER MANUAL | v
11.0 Troubleshooting 44
11.1 UPS Symptoms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
11.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
12.0 Specications 48
12.1 Auto-learning Battery Backup Times. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
13.0 Warranty & Support 55
13.1 Warranty Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
13.2 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6 | Important Safety Precautions
IMPORTANT SAFETY PRECAUTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individuals without previous training.
This product is designed for commercial/industrial use only. It is not intended for use with life support or other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your dealer or local SolaHD representative.
This UPS is designed for use on a properly grounded (earthed) 50 or 60 Hz supply. The factory default setting is 120/208 V ac, 60 Hz. Installation instructions and warning notices are in this manual.
The S4KC is designed for use with a four-wire input (L1, L2, N, G).
!
WARNING
Although the S4KC has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or re. To ensure safety, observe the following precautions:
• Turn o the UPS and disconnect it from the power source before cleaning.
• Clean the UPS with a soft, dry cloth. Do not use liquid or aerosol cleaners.
• Never block or insert any objects into the ventilation holes or other openings of the UPS.
• If using the UPS power cord, place it in a location where it will not be damaged.
Operate the UPS in an indoor environment only, in an ambient temperature range of 0°C to +40°C (+32°F to +104°F).
Temperature Rating (all models): Units are considered acceptable for use in a maximum ambient of +30°C for ambient operation without derating. In addition, output derating (90%) may be applied for use in a maximum ambient between +30°C and +40°C. Please see Table 8 for details of the derating declaration.
Install the UPS in a clean environment, free from moisture, ammable liquids, gases, and corrosive substances.
The S4K4U6000C contains no user-serviceable parts. The S4K6U10KC contains no user-serviceable parts, except for the power module. The UPS On/O buttons do not electrically isolate internal parts. Under no circumstances should you attempt to gain access internally due to the risk of electric shock or burn. The internal battery pack may be replaced by qualied service personnel only.
Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or the UPS performance alters in use. Refer all faults to your SolaHD representative.
DO NOT CONNECT equipment that could overload the UPS or demand dc current from the UPS, such as: electric drills, vacuum cleaners, laser printers, hair dryers, or any appliance using half-wave rectication.
Storing magnetic media on top of the UPS may result in data loss or corruption.
The UPS handle is not for transit.
S4KC SERIES USER MANUAL | 7
Battery Safety Notes
!
CAUTION
Do not dispose of batteries in a re; they may explode. Dispose of used batteries according to local regulations.
Do not open or mutilate the batteries. Released electrolyte is toxic and harmful to skin and eyes. If electrolyte comes in contact with the skin, wash the aected area immediately and get medical attention.
!
CAUTION
A battery can present a risk of electrical shock and high short-circuit current. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions.
The following precautions should be observed when working with batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves, boots, and safety glasses.
• Do not lay tools or metal parts on top of batteries.
• If the battery pack is damaged in any way or shows signs of leakage, please contact your SolaHD representative
immediately.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the source from the
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded supply circuit).
• When replacing batteries, replace with the same type and number of batteries or battery packs.
Electromagnetic Compatibility
The S4KC complies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and (2) This device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
The S4KC Series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by SolaHD.
NOTICE: This product is for restricted sales distribution to informed partners. Installation restrictions or additional measures may be needed to prevent radio interference.
Information for the Protection of the Environment
UPS Servicing: The UPS makes use of components dangerous for the environment (e.g. batteries, electronic cards, and
electronic components). The discarded components must be taken to a specialized collection and disposal center.
8 | Important Safety Precautions
Glossary of Symbols
Risk of electrical shock
!
i
-
PbH2SO4
R
Indicates caution followed by important instructions
Ac input
Ac output
Requests the user to consult the manual
+
Indicates the unit contains a valve-regulated lead acid battery
Recycle
Dc voltage
Equipment grounding conductor
Bonded to ground
Ac voltage
ON/Alarm Silence/Battery Test
OFF/Bypass
WEEE
S4KC SERIES USER MANUAL | 9
1.0 Introduction
Congratulations on your choice of the SolaHD S4KC Uninterruptible Power System (UPS). The S4KC is available in nominal power ratings of 6,000 VA and 10,000 VA.
The S4KC is a compact, on-line Uninterruptible Power System (UPS) which continuously conditions and regulates its output voltage, whether utility power is present or not. It is designed to supply microcomputers and other sensitive equipment with clean sine wave power.
The S4KC features a light-emitting diode (LED) display to indicate both load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm Silence/Manual Battery Test button, and a Standby/Manual Bypass button.
The S4KC has an IntelliSlot® port for communication between the UPS and a network server or other computer system. This port provides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with MultiLink®. MultiLink can also remotely control UPS operation.
10 | 2.0 System Description
2.0 System Description
Input
Static
Bypass
L1
L2
N
G G
Figure 1: Operating principle diagram
SPD &
EMI/RFI
Filters
Battery
Rectier/PFC
Dc to Dc
Converter
Inverter
Battery Charger
2.1 Surge Protection Devices (SPD) & EMI/RFI Filters
Output
L1
L2
N
These UPS components provide surge protection and lter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.
2.2 Rectier/Power Factor Correction (PFC) Circuit
In normal operation, the rectier/power factor correction (PFC) circuit converts utility ac power to regulated dc power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sine wave input current achieves two objectives:
• The utility power is used as eciently as possible by the UPS.
• The amount of distortion reected on the utility is reduced.
This results in cleaner power being available to other devices in the building not protected by the S4KC.
2.3 Inverter
In normal operation, the inverter utilizes the dc output of the power factor correction circuit and inverts it into precise, regulated sine wave ac power. Upon a utility power failure, the inverter receives its required energy from the battery through the dc-to-dc converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated ac output power.
S4KC SERIES USER MANUAL | 11
2.4 Battery Charger
The battery charger utilizes energy from the utility power and precisely regulates it to continuously oat charge the batteries. The batteries are being charged whenever the S4KC is connected to utility power.
2.5 Dc-to-Dc Converter
The dc-to-dc converter utilizes energy from the battery system and raises the dc voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum eciency and voltage, thus increasing reliability.
2.6 Battery
The S4KC utilizes valve-regulated, non-spillable, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of -15°C to +25°C (+59°F to +77°F). Optional external battery cabinets are available to extend battery backup times. For backup times, see Table 13.
2.7 Dynamic Bypass
The S4KC provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature, or any other UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an audible alarm and an illuminated amber Bypass LED. (Other LEDs may be illuminated to indicate a diagnosed problem.) To manually transfer the connected load from the inverter to bypass, press the Standby/Manual Bypass button once and hold it for about 2 seconds.
NOTE: The bypass power path does NOT protect the connected equipment from disturbances in the utility supply.
12 | 3.0 Major Components
USB Port
3.0 Major Components
The S4KC is composed of three major assemblies to provide easier handling, installation, and versatility.
3.1 Main Frame & Electronics
All models of the S4KC are shipped without the internal batteries installed. Power distribution varies by model and rating.
The S4K4U6000C ships with a basic hardwire distribution box attached and is ready to be connected to the load (see Figure 3).
The S4K6U10KC ships with a cover plate installed over the power distribution box connections (see Figure 5). Several optional power distribution boxes are available.
Upper Bezel
Status Indicators and Controls
Figure 2: Front view—rack-mount and tower congurations
IntelliSlot Port
REPO
Terminal block communication
Input breaker
Lower Bezel and Battery Access Door
External battery connector
Figure 3: Rear view—S4K4U6000C
Knockouts for hardwired power input
S4KC SERIES USER MANUAL | 13
Terminal block
Maintenance bypass breaker
Input breaker
S4KPAD2-HDWRC for S4K4U6000C
Input breaker
S4KPAD2-HDWR-MBSC for S4K4U6000C
*
Figure 4: Input power hardwire boxes—S4K4U6000C
NOTE: Hardwire and hardwire/receptacle boxes that include a manual bypass switch permit ac power to continue to ow from the utility input to the load while the box is removed from the UPS. For details, refer to “3.2 Removable Power Distribution Box”.
Cover for power distribution box connections
Output breaker switch
External battery connector
Figure 5: Rear view—S4K6U10KC
IntelliSlot Port
communication
Maintenance bypass breaker
REPO connection block
USB Port
Input breaker switch
Knockouts for hardwired power input
*Standard on S4K4U6000C units
14 | 3.0 Major Components
3.2 Removable Power Distribution Box
The UPS is shipped with a power distribution box. This box contains the UPS input circuit breaker.
Input power breaker
L14-30 Input power connector
Receptacles: two 5-20R; two L6-20R
Maintenance bypass breaker
S4KPAD2-002C
Output power breakers for pigtails
S4KPAD2-001C
Receptacles: four 5-20; one L14-30; one L6-30R
*
Receptacles: four L5-20R; two L6-30R
Push button output power breakers for two L5-20 receptacles (second push button breaker obscured)
S4KPAD2-005C
S4KPAD2-003C
Receptacles: four 5-20R; two L6-30
S4KPAD2-004C
Receptacles: four L5-20R; two L5-30R
Figure 6: Power distribution models for S4K4U6000C
*S4KPAD2-001C shown as an example; similar features on other distribution boxes are arranged dierently
S4KPAD2-006C
Receptacles: four L6-20R
S4KC SERIES USER MANUAL | 15
5-20R output receptacles
Push button circuit breakers for 5-20R receptacles
5-20R output receptacles
S4KPAD2-101C* Receptacles: two L6-30; eight 5-20R
S4KPAD2-102C Receptacles: four L6-20R four 5-20R
Output circuit breaker switch for L6-30R pigtail #1
L6-30R output receptacles
22
11
Output circuit breaker switch for L6-30R pigtail #2
S4KPAD2-105C Receptacles: four 5-20R two L5-30R two L5-20R
S4KPAD2-103C Receptacles: four L6-30R four 5-20R
S4KPAD2-104C Receptacles: four 5-20R two L6-30R two L6-20R
Figure 7: Power distribution models for S4K6U10KC
*S4KPAD2-101C shown as an example; similar features on other distribution boxes are arranged dierently
S4KPAD2-106C Receptacles: four L6-20R four L5-20R
16 | 3.0 Major Components
3.3 Internal Battery Packs
The UPS has two internal battery packs behind a battery access door on the front of the unit. Each internal battery pack is tted with a connector to link it to the UPS.
Battery Handle
Battery Connector
Front of Battery Pack
S4K6U10KC battery packs shown; S4K4U6000C battery packs have the same features
Figure 8: Internal battery pack features
S4KC SERIES USER MANUAL | 17
4.0 Preinstallation
4.1 Unpacking & Inspection
Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer
or SolaHD representative immediately.
• Check the accessories against the delivery list. If there are any discrepancies, contact your local dealer or SolaHD
representative immediately.
4.2 What’s Included
The S4KC is shipped with the following items:
• Compact disk with: MultiLink, Conguration program, and User manual (electronic version)
• One USB cable, 6-1/2 ft. (2 m) long
• Rack handles with mounting hardware
• Power distribution box (installed on UPS)
• Terminal block communication terminals
• One plastic tower set
• Warnings, safety instructions booklet, and WEEE recycling sheet (ISO 14001 compliance)
The S4KC external battery cabinet is shipped with the following items:
• One battery cabinet
• Two spacers for S4K4U6000C models and four spacers for S4K6U10KC models (for tower conguration)
• One dc power cable