Emerson NetSure 721NPBB System Application Manual

SYSTEM OVERVIEW

Home
Description: -48V DC @ up to 4000 Amperes Power System
The NetSure™ 721NPBB DC Power System is a complete integrated power system containing -48V DC rectifiers or converters, optional +24V DC converters, intelligent control, metering, monitoring, and distribution.
This power system is designed to power a load while charging a positive grounded battery. This power system is capable of operating in a batteryless installation or off battery for maintenance purposes. The power system is designed for operation with the positive output grounded.
This system consists of the following components.
Distribution Cabinet
ACU+ (Advanced Control Unit Plus) Controller
Module Mounting Shelf (Spec. No. 588705000)
SAG582127000
System Application Guide
Spec. No. 582127000 (Model 721
Issue AF, February 26, 2014
The system always includes a minimum of one distribution cabinet, which provides DC distribution through fuses and/or circuit breakers. The distribution cabinet is factory mounted in the relay rack or shipping brackets specified when ordered.
Four different sizes of distribution cabinets are available to accept from one (1) to four (4) distribution panels. A variety of distribution panels are available that provide load distribution, battery distribution, and dual voltage load distribution for use with +24V converters. These distribution panels are configured to accept either bullet nose type circuit breakers and TPS/TLS fuseholders, TPH fuses, TPL-B fuses, or GJ/218 circuit breakers.
The distribution cabinet may be equipped with low voltage load disconnect (LVLD), low voltage battery disconnect (LVBD), and manual battery disconnect.
The controller provides power system control (including optional low voltage battery disconnect (LVBD) and low voltage load disconnect (LVLD) control), rectifier control (including a charge control function), converter control, metering functions, monitoring functions, and local/remote alarm functions. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe(s). Temperature probe(s) may also be designated to monitor ambient temperature and/or battery temperature. The controller also provides data acquisition, system alarm management, and advanced battery and energy management. The controller contains an LCD display and keypad for local access. The controller provides Ethernet connection and supports software upgrade via its USB port. It also comes with a comprehensive web page and SNMP capability for remote system management. Refer to the ACU+ Controller Instructions (UM1M820BNA or UM1M820DNA400) for more information.
The system may contain one or more Spec. No. 588705000 module mounting shelves, each of which houses up to six (6) rectifier modules or six (6) converter modules. Refer to Power Data Sheet PD588705000 for more information.
Rectifier Modules (for use in Spec. No. 588705000)
The system may contain rectifier modules; which provide load power, battery float current, and battery recharge current during normal operating conditions. Refer to the Rectifier Instructions (UM1R483500E) for more information.
Converter Modules (for use in Spec. No. 588705000)
The system may contain converter modules; which provide load power, battery float current, and battery recharge current during normal operating conditions. Refer to the Converter Instructions (UM1C400483500E) for more information.
NPBB)
Page 1 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
(E/W Spec. No. 588705000
Module Mounting Shelves) (E/W Spec. N
o. 588705300 Module
Mounting Shelves)
Main Bay Supplemental B
ayMain Bay Supplement
al Bay
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Module Mounting Shelf (Spec. No. 588705300)
The system may contain one or more Spec. No. 588705300 module mounting shelves, each of which houses rectifier modules and optional DC-DC converter modules. Refer to Power Data Sheet PD588705300 for more information.
Rectifier Modules (for use in Spec. No. 588705300)
The system contains rectifier modules; which provide load power, battery float current, and battery recharge current during normal operating conditions. Refer to the Rectifier Instructions (UM1R482000E3) for more information.
Optional DC-DC Converter Modules (for use in Spec. No. 588705300)
Where +24V DC load power is also required, DC-DC converter modules are available. Refer to the Converter Instructions (UM1C48241500) for more information.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 2 of 125
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
General Specifications
See detailed specifications on page 113.
Family: NetSure™ System Spec. No.: 582127000 System Model: 721
NPBB
System AC Input Voltage: 582127000 List 40, 41, 42: Nominal 208/240 volts AC, single
phase, 50/60 Hz, with an operating range of 176 to 264 volts. Acceptable input frequency range is 45 to 65 Hz.
System DC Input Voltage: 582127000 List 45, 46, 47: Input voltage range of 290V DC to
400V DC, with an operating range of 260V DC to 400V DC (when used with 588705000).
System Output Capacity:
System: 4000A, maximum Bay: 2000A @ -48V DC, maximum (when used with 588705000)
1500A @ -48V DC and 930A @ +24V DC, maximum (when used with 588705300)
Distribution Panel: 600A, maximum
588705000 Shelf Ratings: See PD588705000.
1R483200 Rectifier Rating: See UM1R483500E. 1R483200E Rectifier Rating: See UM1R483500E. 1R483500E Rectifier Rating: See UM1R483500E. 1C400483500E Converter Rating: See UM1C400483500E.
588705300 Shelf Ratings: See PD588705300.
1R482000E3 Rectifier Rating: See UM1R482000E. 1C48241500 Converter Rating: See UM1C48241500.
System Agency Approval: UL 1801 Listed (“c UL”),
NEBS (pending when equipped with C400/48-3500e)
Framework Type: Relay Rack Mounting Width: 23 Inches, nominal Mounting Depth:
Distribution Cabinet: 20.09 Inches 588705000 Module
Mounting Shelf: 17.5 Inches 588705300 Module
Mounting Shelf: 20.09 Inches
Battery Tray: 22.5 Inches Access: Front for Installation, Operation, and Maintenance Supplemental Bay(s) Available: Two Control: Microprocessor Color: Bay and Module Faceplates: Textured Gray
Module Mounting Shelf and Module Bodies: Bright Zinc Plating
Environment: -40°C to +40°C (-40°F to +104°F)
Page 3 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Di
str
ibu
tio
n Row
1
D
is
t
ri
b
ut
io
nRow
2
Di
st
r
ib
uti
on
R
ow
3
D
is
t
ri
bu
t
io
n R
o
w 4
DISTRIBUTION CABINET
FRONT ACCESS AC TERMINATION ASSEMBLY
See Also
Rectifier Module:
1R483200
List 30: Module Mounting
Shelf Interface
ACU+ Controller (Main Bay)
(located behind blank panel)
Module Mounting Shelf:
or 58870500032
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
582127000
COMMON EQUIPMENT
List 1: Main Bay List 2: 1st Supplemental Bay,
In-Line w/ Main Bay
List 3: 2
Bay, In-Line w/ Main Bay
List 5: 1
Remote Location
List 6: 2
Bay, Remote Location
nd
Supplemental
st
Supplemental Bay,
nd
Supplemental
List 40: 1 VAC Feed per 1 Rectifier (1-5 Shelves), Single Phase List 41: 1 VAC Feed per 2 Rectifiers (2 or 4 Shelves), Single Phase List 42: 1 VAC Feed per 3 Rectifiers (1-5 Shelves), 3-Phase
DISTRIBUTION PANELS
Single Voltage Distribution Panels
Battery Disconnect Distribution Panels
Return Bar Panel
NPBB)
(4-Row Cabinet Shown)
List 24 (4-Row)
SM-DU (Supplemental Bays):
List 23 (3-Row) List 22 (2-Row) List 21 (1-Row)
1R483500E or 1R483200E or
1M820DNA
58870500021, 58870500022, 58870500031,
BATTERY DISCONNECT CONTACTORS
List CA: 600A List CB: 1200A List CC: 2000A
LOW VOLTAGE DISCONNECT OPTIONS
List LB: Low Voltage Battery
Disconnect (LVBD)
List LL: Low Voltage Load
Disconnect (LVLD)
Other Options
List 4: Distribution Only Bay
Distribution Cabinet Bottom Rear Cover
List 29: Distribution Cabinet
Top Shield
List 31: Module Mounting Shelf
Field Expansion Kit
List 90: Battery Shunt, 800A List 91: Battery Shunt, 2000A List 92: Battery Shunt, 2500A List MB: Manual Battery
Disconnect
System Overview Table of Contents List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 4 of 125
List 93: Optional Battery Tray
System Application Guide SAG582127000
Di
str
ibu
tio
n Row
1
D
is
t
ri
b
ut
io
nRow
2
Di
st
r
ib
uti
on
R
ow
3
D
is
t
ri
bu
t
io
n R
o
w 4
DISTRIBUTION CABINET
FRONT ACCESS DC TERMINATION ASSEMBLY
See Also
Converter Module:
List 34: Module Mounting
Shelf Interface
ACU+ Controller (Main Bay)
(located behind blank panel)
Module Mounting Shelf:
Home
Spec. No. 582127000 (Model 721
582127000
COMMON EQUIPMENT
List 1: Main Bay List 2: 1st Supplemental Bay,
In-Line w/ Main Bay
List 3: 2
Bay, In-Line w/ Main Bay
List 5: 1
Remote Location
List 6: 2
Bay, Remote Location
nd
Supplemental
st
Supplemental Bay,
nd
Supplemental
NPBB) Issue AF, February 26, 2014
List 45: 1 VDC Feed per 1 Converter (1-5 Shelves) List 46: 1 VDC Feed per 2 Converters (2 or 4 Shelves) List 47: 1 VDC Feed per 3 Converters (1-5 Shelves)
DISTRIBUTION PANELS
Single Voltage Distribution Panels
Battery Disconnect Distribution Panels
Return Bar Panel
(4-Row Cabinet Shown)
List 24 (4-Row)
SM-DU (Supplemental Bays):
List 23 (3-Row) List 22 (2-Row) List 21 (1-Row)
58870500040, 58870500041,
or 58870500042
1C400483500E
1M820DNA
BATTERY DISCONNECT CONTACTORS
List CA: 600A List CB: 1200A List CC: 2000A
LOW VOLTAGE DISCONNECT OPTIONS
List LB: Low Voltage Battery
Disconnect (LVBD)
List LL: Low Voltage Load
Disconnect (LVLD)
Other Options
List 4: Distribution Only Bay
Distribution Cabinet Bottom Rear Cover
List 29: Distribution Cabinet
Top Shield
List 35: Module Mounting Shelf
Field Expansion Kit
List 90: Battery Shunt, 800A List 91: Battery Shunt, 2000A List 92: Battery Shunt, 2500A List MB: Manual Battery
Disconnect
System Overview Table of Contents List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 5 of 125
List 93: Optional Battery Tray
SAG582127000 System Application Guide
Distribution Row 1
Distribution Row 2
Distribution Row 3
Distribution Row 4
DISTRIBUTION CABINET
FRONT ACCESS AC TERMINATION ASSEMBLY
Optional DC-DC
1C48241500
See Also
Rectifier Module:
List 32: Module Mounting
Shelf Interface
ACU+ Controller (Main Bay)
Module Mounting
Shelf: 588705300
Home
List 60: DC-DC
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
582127000
COMMON EQUIPMENT
List 1: Main Bay
List 40: 1 VAC Feed per 1 Rectifier (1-5 Shelves), Single Phase List 41: 1 VAC Feed per 2 Rectifiers (2 or 4 Shelves), Single Phase List 42: 1 VAC Feed per 3 Rectifiers (1-5 Shelves), 3-Phase
List 2: 1st Supplemental Bay,
In-Line w/ Main Bay
List 3: 2
Bay, In-Line w/ Main Bay
List 5: 1
Remote Location
List 6: 2
nd
Supplemental
st
Supplemental Bay,
nd
Supplemental
Bay, Remote Location
DISTRIBUTION PANELS
Single Voltage Distribution Panels
Dual Volage Distribution Panels
Battery Disconnect Distribution Panels
Return Bar Panel
NPBB)
SM-DU (Supplemental Bays):
(4-Row Cabinet Shown)
List 24 (4-Row) List 23 (3-Row) List 22 (2-Row) List 21 (1-Row)
1M820DNA
(located behind blank panel)
1R482000E3
Converter Module:
Converter Option
System Overview Table of Contents List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation
BATTERY DISCONNECT CONTACTORS
List CA: 600A List CB: 1200A List CC: 2000A
LOW VOLTAGE DISCONNECT OPTIONS
List LB: Low Voltage Battery
Disconnect (LVBD)
List LL: Low Voltage Load
Disconnect (LVLD)
Other Options
List 4: Distribution Only Bay
Distribution Cabinet Bottom Rear Cover
List 29: Distribution Cabinet
Top Shield
List 33: Module Mounting Shelf
Field Expansion Kit
List 90: Battery Shunt, 800A List 91: Battery Shunt, 2000A List 92: Battery Shunt, 2500A List MB: Manual Battery
Disconnect
List 93: Optional Battery Tray
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 6 of 125
System Application Guide SAG582127000 Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

TABLE OF CONTENTS

System
Overview
SYSTEM OVERVIEW................................................................................................................................................. 1
TABLE OF CONTENTS ............................................................................................................................................. 7
LIST DESCRIPTIONS (582127000) ........................................................................................................................ 11
List Numbers (582127000) ................................................................................................................................ 11
List 1: Main Bay Common Equipment (Power and Distribution) ................................................................... 11
List 2: 1st Supplemental Bay Common Equipment (Power and Distribution or Distribution Only),
Located In-Line with Main Bay ....................................................................................................................... 12
List 3: 2nd Supplemental Bay Common Equipment (Power and Distribution or Distribution Only),
Located In-Line with Main Bay ....................................................................................................................... 14
List 4: Distribution Only Bay Distribution Cabinet Bottom Rear Cover ......................................................... 15
List 5: 1st Supplemental Bay Common Equipment (Power and Distribution or Distribution Only),
Located Remote from Main Bay ..................................................................................................................... 15
List 6: 2nd Supplemental Bay Common Equipment (Power and Distribution or Distribution Only),
Located Remote from Main Bay ..................................................................................................................... 17
List 21: One-Row Distribution Cabinet .......................................................................................................... 18
List 22: Two-Row Distribution Cabinet .......................................................................................................... 19
List 23: Three-Row Distribution Cabinet ....................................................................................................... 19
List 24: Four-Row Distribution Cabinet ......................................................................................................... 20
List 29: Top Shield for Distribution Cabinet ................................................................................................... 20
List 30: Module Mounting Shelf Interface Components (for Spec. No. 58870500021, 58870500022,
58870500031, 58870500032) ........................................................................................................................ 20
List 31: Module Mounting Shelf Field Expansion Kit (for Spec. No. 58870500022, 58870500031,
58870500032) ................................................................................................................................................ 21
List 32: Module Mounting Shelf Interface Components (for Spec. No. 588705300) .................................... 22
List 33: Module Mounting Shelf Field Expansion Kit (for Spec. No. 588705300) ......................................... 22
List 34: Module Mounting Shelf Interface Components (for Spec. No. 58870500040, 58870500041,
58870500042) ................................................................................................................................................ 23
List 35: Module Mounting Shelf Field Expansion Kit (for Spec. No. 58870500041, 58870500042) ............. 23
List 40: Front Access AC Input Termination Assembly (1 AC Feed per 1 Rectifier, Single Phase, 1-
5 Shelves) ...................................................................................................................................................... 24
List 41: Front Access AC Input Termination Assembly (1 AC Feed per 2 Rectifiers, Single Phase, 2
or 4 Shelves) .................................................................................................................................................. 24
List 42: Front Access AC Input Termination Assembly (1 AC Feed per 3 Rectifiers, 3-Phase, 1-5
Shelves) ......................................................................................................................................................... 24
List 45: Front Access DC Input Termination Assembly (1 DC Feed per 1 Converter, 1-5 Shelves) ............ 25
List 46: Front Access DC Input Termination Assembly (1 DC Feed per 2 Converters, 2 or 4
Shelves) ......................................................................................................................................................... 25
List 47: Front Access DC Input Termination Assembly (1 DC Feed per 3 Converters, 1-5 Shelves) .......... 25
List 60: Converter Interface Components (for Spec. No. 588705300).......................................................... 26
List 90: Optional Battery Shunt, 800A ........................................................................................................... 26
List 91: Optional Battery Shunt, 2000A ......................................................................................................... 27
List 92: Optional Battery Shunt, 2500A ......................................................................................................... 27
List 93: Optional Battery Tray, Pre-Cabled ................................................................................................... 28
Single Voltage Distribution Panels .................................................................................................................. 29
List AA: -48V Distribution Panel (with Return Busbar) and List AB: -48V Distribution Panel (without
Return Busbar), (24) Bullet/TPS/TLS Circuit Breaker/Fuse Positions ........................................................... 29
Picture
List
Descriptions
Accessory
Descriptions
Specifications
Physical Size
Information
Related
Documentation
Page 7 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
List AC: -48V Distribution Panel (with Return Busbar) and List AD: -48V Distribution Panel
(without Return Busbar), (4) GJ/218 Circuit Breaker Positions ..................................................................... 30
List AE: -48V Distribution Panel, (2) TPH Fuse Positions (without Shunts) (without Return Busbar) .......... 31
List AF: -48V Distribution Panel, (2) TPH Fuse Positions (with Shunts) (without Return Busbar) ............... 32
List AG: -48V Distribution Panel, (4) TPH Fuse Positions (without Shunts) (without Return Busbar) .......... 33
List AH: -48V Distribution Panel, (4) TPH Fuse Positions (with Shunts) (without Return Busbar) ............... 34
List AJ: -48V Distribution Panel, (4) TPL-B Fuse Positions (without Shunts) (without Return
Busbar) ........................................................................................................................................................... 35
List AK: -48V Distribution Panel, (4) TPL-B Fuse Positions (with Shunts) (without Return Busbar) ............ 36
Dual Voltage Distribution Panels ..................................................................................................................... 37
List DA: -48V/+24V Distribution Panel, (17) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and (4) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return
Busbar) ........................................................................................................................................................... 37
List DB: -48V/+24V Distribution Panel, (13) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and (8) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return
Busbar) ........................................................................................................................................................... 38
List DC: -48V/+24V Distribution Panel, (9) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and (12) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return
Busbar) ........................................................................................................................................................... 39
List DD: -48V/+24V Distribution Panel, (5) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and (16) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return
Busbar) ........................................................................................................................................................... 40
Battery Disconnect Distribution Panels .......................................................................................................... 41
List BA: Battery Disconnect Distribution Panel (with Return Busbar) and List BB: Battery Disconnect Distribution Panel (without Return Busbar), (24) Bullet/TPS/TLS Circuit Breaker/Fuse
Battery Disconnect Positions ......................................................................................................................... 41
List BC: Battery Disconnect Distribution Panel (with Return Busbar) and List BD: Battery Disconnect Distribution Panel (without Return Busbar), (4) GJ/218 Circuit Breaker Battery
Disconnect Positions ...................................................................................................................................... 42
List BE: Battery Disconnect Distribution Panel, (2) TPH Fuse Battery Disconnect Position (without
Shunts) (without Return Busbar) .................................................................................................................... 43
List BF: Battery Disconnect Distribution Panel, (2) TPH Fuse Battery Disconnect Positions (with
Shunts) (without Return Busbar) .................................................................................................................... 44
List BG: Battery Disconnect Distribution Panel, (4) TPH Fuse Battery Disconnect Positions
(without Shunts) (without Return Busbar) ...................................................................................................... 45
List BH: Battery Disconnect Distribution Panel, (4) TPH Fuse Battery Disconnect Positions (with
Shunts) (without Return Busbar) .................................................................................................................... 46
Return Bar Panel ............................................................................................................................................... 47
List GA: Return Bar Panel ............................................................................................................................. 47
Battery Disconnect Contactors ........................................................................................................................ 48
List CA: 600A Battery Disconnect Contactor ................................................................................................ 48
List CB: 1200A Battery Disconnect Contactor .............................................................................................. 48
List CC: 2000A Battery Disconnect Contactor .............................................................................................. 48
Low Voltage Disconnect Options .................................................................................................................... 49
List LB: Low Voltage Battery Disconnect (LVBD) ......................................................................................... 49
List LL: Low Voltage Load Disconnect (LVLD) ............................................................................................. 49
Manual Battery Disconnect Option.................................................................................................................. 49
List MB: Manual Battery Disconnect ............................................................................................................. 49
ACCESSORY DESCRIPTIONS ............................................................................................................................... 50
ACU+ (Advanced Control Unit Plus) Controller, P/N 1M820DNA ................................................................. 50
Optional ACU+ EIB (Extended Interface Board), P/N 548120 ........................................................................ 50
Optional SM-DU+ Shunt Monitoring, P/N 548078 ........................................................................................... 51
Optional Temperature Probes .......................................................................................................................... 51
Optional SM-Temp Temperature Concentrator, P/N 547490 ......................................................................... 52
Rectifiers ............................................................................................................................................................ 53
Page 8 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000 Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Rectifier Module, P/N 1R483500E ................................................................................................................. 53
Rectifier Module, P/N 1R483200E ................................................................................................................. 53
Rectifier Module, P/N 1R483200 .................................................................................................................... 53
Rectifier Module, P/N 1R482000E3 ............................................................................................................... 53
Converters .......................................................................................................................................................... 54
DC-DC Converter Module, P/N 1C400483500E ............................................................................................ 54
DC-DC Converter Module, P/N 1C48241500 ................................................................................................ 54
Module Mounting Position Blank Cover Panel, P/N 21140440 ..................................................................... 54
Converter Interface Components (for Spec. No. 588705300) ....................................................................... 55
Relay Racks and Shipping Brackets ............................................................................................................... 56
Transition Plates to Mount Relay Rack on Top of GNB Absolyte IIP Batteries .......................................... 57
Batteries ............................................................................................................................................................. 58
Optional Battery Tray Battery Disconnect Circuit Breaker and Housing Kits ............................................ 59
Optional Battery Tray Front Battery Cover Kits ............................................................................................. 60
Crimp Lugs ......................................................................................................................................................... 61
Standard Crimp Lug Tables ........................................................................................................................... 61
Special Application Crimp Lug / Strap Combination Table ............................................................................ 62
Lug Adapters ..................................................................................................................................................... 63
Busbar for 125A, 150A, and 200A Bullet Nose Type Circuit Breaker, P/N 520989 ....................................... 63
Busbar for 125A, 150A, and 200A Bullet Nose Type Circuit Breaker, P/N 522786 ....................................... 63
Lug Adapter Busbar Kit for 125A, 150A, and 200A Bullet Nose Type Circuit Breaker, P/N 534449 ............. 63
Busbar for 250A Bullet Nose Type Circuit Breaker, P/N 514717 ................................................................... 63
Lug Adapter Busbar Kit for 250A Bullet Nose Type Circuit Breaker, P/N 514714 ......................................... 64
Lug Hardware Kits ............................................................................................................................................. 64
1/4-20 Hardware Kit, P/N 541084 .................................................................................................................. 64
3/8-16 Hardware Kit, P/N 548184 .................................................................................................................. 64
3/8-16 Hardware Kit, P/N 548185 .................................................................................................................. 64
Battery Busbar Extension Kit (P/N 554541) .................................................................................................... 65
Battery Landing Busbar Kit (P/N 553584) ....................................................................................................... 65
Battery Landing Busbar Kit (P/N 555478) ....................................................................................................... 65
Distribution Devices .......................................................................................................................................... 66
Bullet Nose Type Circuit Breakers and Bullet Nose Type Fuseholders e/w TPS/TLS Fuses ....................... 66
Optional Bullet Nose Type 6-Position GMT Distribution Fuse Block, P/N 550224, (6) GMT Fuse
Positions ......................................................................................................................................................... 71
GMT Type Load Distribution Fuses ............................................................................................................... 72
GJ/218 Type Circuit Breakers ........................................................................................................................ 73
TPH Type Fuses ............................................................................................................................................ 74
TPL-B Type Fuses ......................................................................................................................................... 75
Replacement Alarm, Reference, and Control Fuses ...................................................................................... 76
Replacement Assemblies ................................................................................................................................. 76
Replacement Bay-to-Bay Interconnect Cable ................................................................................................ 76
Wiring Illustrations and Notes ......................................................................................................................... 77
Relay Rack Frame Grounding Requirements ................................................................................................ 77
AC Input ......................................................................................................................................................... 78
400V DC Input ................................................................................................................................................ 87
Field Installed Module Mounting Shelves ...................................................................................................... 93
External Alarm, Reference, Monitoring .......................................................................................................... 93
Load Distribution .......................................................................................................................................... 101
Battery Input ................................................................................................................................................. 103
Wire Size and Lug Selection Tables for Load and Battery Connections to TPS/TLS Fuses and
Bullet Nose Type Circuit Breakers ............................................................................................................... 109
Wire Size and Lug Selection Tables for Load and Battery Connections to TPH Fuses, TPL-B
Fuses, and GJ/218 Type Circuit Breakers or Battery Branch Circuits ......................................................... 111
SPECIFICATIONS .................................................................................................................................................. 113
1.1 Output Ratings .......................................................................................................................................... 113
Page 9 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
1.2 Input Ratings ............................................................................................................................................. 113
1.3 Environmental Ratings ............................................................................................................................. 113
1.4 Compliance Information ........................................................................................................................... 114
1.5 IB2 and EIB (ACU+ Interface Board) Ratings ......................................................................................... 114
PHYSICAL SIZE INFORMATION .......................................................................................................................... 115
Overall Dimensions ......................................................................................................................................... 115
List 21 (One-Row Distribution Cabinet) ....................................................................................................... 116
List 22 (Two-Row Distribution Cabinet) ....................................................................................................... 117
List 23 (Three-Row Distribution Cabinet) ..................................................................................................... 118
List 24 (Four-Row Distribution Cabinet) ....................................................................................................... 119
List 93 (Battery Tray) .................................................................................................................................... 120
Weights ............................................................................................................................................................. 121
RELATED DOCUMENTATION .............................................................................................................................. 124
BATTERY MANUFACTURER INFORMATION .................................................................................................... 124
REVISION RECORD .............................................................................................................................................. 125
Page 10 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
LIST DESCRIPTIONS (582127000) List Numbers (582127000)

List 1: Main Bay Common Equipment (Power and Distribution)

Features
Provides common equipment for one “power and distribution” bay rated for up to 2000 amperes of
distribution.
Accepts one (1) distribution cabinet (options are 1-row, 2-row, 3-row, or 4-row cabinet).
Accepts one (1) ACU+ Controller.
Includes the IB2 ACU+ interface board.
Accepts up to six (6) module mounting shelves Spec. No. 588705000 (including expansion shelves).
or Accepts up to six (6) module mounting shelves Spec. No. 588705300 (including expansion shelves).
Restrictions
When the system is equipped with a List 40, 41, 42, 45, 46, or 47 front access Input Termination Assembly, refer to the restrictions under these list descriptions.
Ordering Notes
1) Order a relay rack or shipping brackets per “Relay Racks and Shipping Brackets” under ACCESSORY DESCRIPTIONS. If required, order relay rack transition plates per “Transition Plates to Mount Relay
Rack on Top of GNB Absolyte IIP Batteries” under ACCESSORY DESCRIPTIONS.
2) Order one (1) List 21, 22, 23, or 24 distribution cabinet. a) Order up to four (4) (per the capacity of the distribution cabinet ordered) distribution panels, battery
disconnect panels, and/or return bar panel as required per “Single Voltage Distribution Panel”, “Dual
Voltage Distribution Panel”, “Battery Disconnect Distribution Panel”, and “Return Bar Panel” under
LIST DESCRIPTIONS.
b) Order battery disconnect contactors and low voltage disconnect options as required per “Battery
Disconnect Contactors” and “Low Voltage Disconnect Options” under LIST DESCRIPTIONS.
c) Order one (1) ACU+ controller, P/N 1M820DNA. d) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY
DESCRIPTIONS. e) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring
Notesunder ACCESSORY DESCRIPTIONS.
f) Order a distribution cabinet top shield as required per List 29. g) Order a battery shunt as required per List 90, 91, or 92.
3) 588705000 Rectifier Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 30. Order field expansion module mounting shelf(s) per List 31. Order module mounting shelf(s) per PD588705000 (choices are 58870500021, 58870500022, 58870500031,
58870500032). a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 if module mounting shelf
58870500021 ordered (or order module mounting shelves with AC line cords or terminal blocks,
58870500022, 58870500031, 58870500032). b) Order rectifier modules as required, P/N 1R483500E, 1R483200E, or 1R483200. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
4) 588705000 Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 34. Order field expansion module mounting shelf(s) per List 35. Order module mounting shelf(s) per PD588705000 (choices are 58870500040, 58870500041, 58870500042).
Page 11 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
a) Order the front access DC Input Termination Assembly per List 45, 46, or 47 if module
mounting shelf 58870500040 ordered (or order module mounting shelves with terminal
blocks, 58870500041, 58870500042). b) Order converter modules as required, P/N 1C400483500E. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
5) 588705300 Rectifier/Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705300 as required per List 32. Order field expansion module mounting shelf(s) per List 33. Order module mounting shelf(s) per PD588705300.
a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 (or order module
mounting shelves with AC input cable assemblies, see PD588705300). b) Order rectifier modules as required, P/N 1R482000E3. c) Order optional converter interface components per List 60. d) Order optional DC-DC converter modules as required, P/N 1C48241500.
6) Order battery trays as required per List 93. a) Order batteries as required per “Batteries” under ACCESSORY DESCRIPTIONS. b) Order “Optional Battery Tray Battery Disconnect Circuit Breaker and Housing Kits” as required. c) Order “Optional Battery Tray Front Battery Cover Kits” as required.
st
List 2: 1
Supplemental Bay Common Equipment (Power and Distribution or Distribution Only),
Located In-Line with Main Bay
Features
Provides common equipment for one bussed “power and distribution or distribution only” bay rated for up
to 2000 amperes of distribution. Includes interbay power busbars and communications cable.
Mounts to either left or right side of List 1 Main Bay.
Accepts one (1) distribution cabinet (options are 3-row or 4-row cabinet).
Includes SM-DU (provides bay interface to ACU+ Controller).
Accepts up to six (6) module mounting shelves Spec. No. 588705000 (including expansion shelves).
or Accepts up to six (6) module mounting shelves Spec. No. 588705300 (including expansion shelves).
Restrictions
When the system is equipped with a List 40, 41, 42, 45, 46, or 47 front access Input Termination Assembly, refer to the restrictions under these list descriptions.
Will not accept List 21 and 22 distribution cabinet. (List 21 and 22 are not provided with connection points for interbay busbars.)
Will not accept List 60 converter interface components. Will not accept dual voltage distribution panels.
Order maximum of one (1) List 2 or List 5 per Power System. Cannot be used when List 5 is ordered. Order List 2 or List 5, not both.
Rear access required for installation of inter-bay busbars. If low voltage disconnect (List LL or List LB) is to be included, the Main Bay (List 1) of the system must also
have low voltage disconnect (List LL or List LB).
Ordering Notes
1) Order a relay rack or shipping brackets per “Relay Racks and Shipping Brackets” under ACCESSORY DESCRIPTIONS. If required, order relay rack transition plates per “Transition Plates to Mount Relay
Rack on Top of GNB Absolyte IIP Batteries” under ACCESSORY DESCRIPTIONS.
2) Order one (1) List 23 or 24 distribution cabinet.
Page 12 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
a) Order up to four (4) (per the capacity of the distribution cabinet ordered) distribution panels,
battery disconnect panels, and/or return bar panel as required per “Single Voltage
Distribution Panel”, “Battery Disconnect Distribution Panel”, and “Return Bar Panel” under LIST
DESCRIPTIONS.
b) Order battery disconnect contactors and low voltage disconnect options as required per “Battery
Disconnect Contactors” and “Low Voltage Disconnect Options” under LIST DESCRIPTIONS.
c) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY
DESCRIPTIONS.
d) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring
Notes” under ACCESSORY DESCRIPTIONS.
e) Order a distribution cabinet top shield as required per List 29. f) If distribution only, order a bottom rear distribution cabinet cover per List 4. g) Order a battery shunt as required per List 90, 91, or 92.
3) 588705000 Rectifier Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 30. Order field expansion module mounting shelf(s) per List 31. Order module mounting shelf(s) per PD588705000 (choices are 58870500021, 58870500022, 58870500031,
58870500032). a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 if module mounting shelf
58870500021 ordered (or order module mounting shelves with AC line cords or terminal blocks,
58870500022, 58870500031, 58870500032). b) Order rectifier modules as required, P/N 1R483500E, 1R483200E, or 1R483200. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
4) 588705000 Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 34. Order field expansion module mounting shelf(s) per List 35. Order module mounting shelf(s) per PD588705000 (choices are 58870500040, 58870500041, 58870500042).
a) Order the front access DC Input Termination Assembly per List 45, 46, or 47 if module mounting shelf
58870500040 ordered (or order module mounting shelves with terminal blocks, 58870500041,
58870500042). b) Order converter modules as required, P/N 1C400483500E. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
5) 588705300 Rectifier/Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705300 as required per List 32. Order field expansion module mounting shelf(s) per List 33. Order module mounting shelf(s) per PD588705300.
a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 (or order module
mounting shelves with AC input cable assemblies, see PD588705300). b) Order rectifier modules as required, P/N 1R482000E3. c) Order optional converter interface components per List 60. d) Order optional DC-DC converter modules as required, P/N 1C48241500.
6) Order battery trays as required per List 93. a) Order batteries as required per “Batteries” under ACCESSORY DESCRIPTIONS. b) Order “Optional Battery Tray Battery Disconnect Circuit Breaker and Housing Kits” as required. c) Order “Optional Battery Tray Front Battery Cover Kits” as required.
Page 13 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List 3: 2nd Supplemental Bay Common Equipment (Power and Distribution or Distribution Only), Located In-Line with Main Bay

Features
Provides common equipment for one bussed “power and distribution or distribution only” bay rated for up
to 2000 amperes of distribution. Includes interbay power busbars and communications cable.
Mounts to either left or right side of List 2 Supplemental Bay.
Accepts one (1) distribution cabinet (options are 3-row or 4-row cabinet).
Includes SM-DU (provides bay interface to ACU+ Controller).
Accepts up to six (6) module mounting shelves Spec. No. 588705000 (including expansion shelves).
or Accepts up to six (6) module mounting shelves Spec. No. 588705300 (including expansion shelves).
Restrictions
When the system is equipped with a List 40, 41, 42, 45, 46, or 47 front access Input Termination Assembly, refer to the restrictions under these list descriptions.
Will not accept List 21 and 22 distribution cabinet. (List 21 and 22 are not provided with connection points for interbay busbars.)
Will not accept List 60 converter interface components. Will not accept dual voltage distribution panels.
Order maximum of one (1) List 3 or List 6 per Power System. Cannot be used when List 6 is ordered. Order List 3 or List 6, not both.
Rear access required for installation of inter-bay busbars. If low voltage disconnect (List LL or List LB) is to be included, the Main Bay (List 1) of the system must also
have low voltage disconnect (List LL or List LB).
Ordering Notes
1) Order a relay rack or shipping brackets per “Relay Racks and Shipping Brackets” under ACCESSORY DESCRIPTIONS. If required, order relay rack transition plates per “Transition Plates to Mount Relay
Rack on Top of GNB Absolyte IIP Batteries” under ACCESSORY DESCRIPTIONS.
2) Order one (1) List 23 or 24 distribution cabinet. a) Order up to four (4) (per the capacity of the distribution cabinet ordered) distribution panels, battery
disconnect panels, and/or return bar panel as required per “Single Voltage Distribution Panel”, “Battery Disconnect Distribution Panel”, and “Return Bar Panel” under LIST DESCRIPTIONS.
b) Order battery disconnect contactors and low voltage disconnect options as required per “Battery
Disconnect Contactors” and “Low Voltage Disconnect Options” under LIST DESCRIPTIONS.
c) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY
DESCRIPTIONS.
d) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring
Notes” under ACCESSORY DESCRIPTIONS.
e) Order a distribution cabinet top shield as required per List 29. f) If distribution only, order a bottom rear distribution cabinet cover per List 4. g) Order a battery shunt as required per List 90, 91, or 92.
3) 588705000 Rectifier Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 30. Order field expansion module mounting shelf(s) per List 31. Order module mounting shelf(s) per PD588705000 (choices are 58870500021, 58870500022, 58870500031,
58870500032). a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 if module mounting shelf
58870500021 ordered (or order module mounting shelves with AC line cords or terminal blocks, 58870500022, 58870500031, 58870500032).
b) Order rectifier modules as required, P/N 1R483500E, 1R483200E, or 1R483200.
Page 14 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
4) 588705000 Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 34. Order field expansion module mounting shelf(s) per List 35. Order module mounting shelf(s) per PD588705000 (choices are 58870500040, 58870500041, 58870500042).
a) Order the front access DC Input Termination Assembly per List 45, 46, or 47 if module mounting shelf
58870500040 ordered (or order module mounting shelves with terminal blocks, 58870500041,
58870500042). b) Order converter modules as required, P/N 1C400483500E. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
5) 588705300 Rectifier/Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705300 as required per List 32. Order field expansion module mounting shelf(s) per List 33. Order module mounting shelf(s) per PD588705300.
a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 (or order module
mounting shelves with AC input cable assemblies, see PD588705300). b) Order rectifier modules as required, P/N 1R482000E3. c) Order optional converter interface components per List 60. d) Order optional DC-DC converter modules as required, P/N 1C48241500.
6) Order battery trays as required per List 93. a) Order batteries as required per “Batteries” under ACCESSORY DESCRIPTIONS. b) Order “Optional Battery Tray Battery Disconnect Circuit Breaker and Housing Kits” as required. c) Order “Optional Battery Tray Front Battery Cover Kits” as required.

List 4: Distribution Only Bay Distribution Cabinet Bottom Rear Cover

Features
Bottom rear cover shield for use when a
supplemental bay is configured for “distribution only” (no module mounting shelf).
Restrictions
Module mounting shelf(s) cannot be mounted in a bay when List 4 is installed.
Ordering Notes
1) Order when a supplemental distribution bay is configured for “distribution only” (no module mounting shelf).
st
List 5: 1
Supplemental Bay Common Equipment (Power and Distribution or Distribution Only),
Located Remote from Main Bay
Features
Provides common equipment for one remote “power and distribution or distribution only” bay rated for up
to 2000 amperes of distribution. Includes interbay communications cabling.
Accepts one (1) distribution cabinet (options are 1-row, 2-row, 3-row, or 4-row cabinet).
Includes SM-DU (provides bay interface to ACU+ Controller).
Accepts up to six (6) module mounting shelves Spec. No. 588705000 (including expansion shelves).
or Accepts up to six (6) module mounting shelves Spec. No. 588705300 (including expansion shelves).
Page 15 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Restrictions
When the system is equipped with a List 40, 41, 42, 45, 46, or 47 front access Input Termination Assembly, refer to the restrictions under these list descriptions.
Will not accept List 60 converter interface components. Will not accept dual voltage distribution panels.
Order maximum of one (1) List 2 or List 5 per Power System. Cannot be used when List 2 is ordered. Order List 2 or List 5, not both.
Interbay power cabling is not included, and must be separately provided per site requirements. If low voltage disconnect (List LL or List LB) is to be included, the Main Bay (List 1) of the system must also
have low voltage disconnect (List LL or List LB).
Ordering Notes
1) Order a relay rack or shipping brackets per “Relay Racks and Shipping Brackets” under ACCESSORY DESCRIPTIONS. If required, order relay rack transition plates per “Transition Plates to Mount Relay
Rack on Top of GNB Absolyte IIP Batteries” under ACCESSORY DESCRIPTIONS.
2) Order one (1) List 21, 22, 23, or 24 distribution cabinet. a) Order up to four (4) (per the capacity of the distribution cabinet ordered) distribution panels, battery
disconnect panels, and/or return bar panel as required per “Single Voltage Distribution Panel”, “Battery Disconnect Distribution Panel”, and “Return Bar Panel” under LIST DESCRIPTIONS.
b) Order battery disconnect contactors and low voltage disconnect options as required per “Battery
Disconnect Contactors” and “Low Voltage Disconnect Options” under LIST DESCRIPTIONS.
c) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY
DESCRIPTIONS.
d) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring
Notes” under ACCESSORY DESCRIPTIONS.
e) Order a distribution cabinet top shield as required per List 29. f) If distribution only, order a bottom rear distribution cabinet cover per List 4. g) Order a battery shunt as required per List 90, 91, or 92.
3) 588705000 Rectifier Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 30. Order field expansion module mounting shelf(s) per List 31. Order module mounting shelf(s) per PD588705000 (choices are 58870500021, 58870500022, 58870500031,
58870500032). a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 if module mounting shelf
58870500021 ordered (or order module mounting shelves with AC line cords or terminal blocks,
58870500022, 58870500031, 58870500032). b) Order rectifier modules as required, P/N 1R483500E, 1R483200E, or 1R483200. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
4) 588705000 Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 34. Order field expansion module mounting shelf(s) per List 35. Order module mounting shelf(s) per PD588705000 (choices are 58870500040, 58870500041, 58870500042).
a) Order the front access DC Input Termination Assembly per List 45, 46, or 47 if module mounting shelf
58870500040 ordered (or order module mounting shelves with terminal blocks, 58870500041,
58870500042). b) Order converter modules as required, P/N 1C400483500E. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
5) 588705300 Rectifier/Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705300 as required per List 32. Order field expansion module mounting shelf(s) per List 33. Order module mounting shelf(s) per PD588705300.
Page 16 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 (or order
module mounting shelves with AC input cable assemblies, see PD588705300). b) Order rectifier modules as required, P/N 1R482000E3. c) Order optional converter interface components per List 60. d) Order optional DC-DC converter modules as required, P/N 1C48241500.
6) Order battery trays as required per List 93. a) Order batteries as required per “Batteries” under ACCESSORY DESCRIPTIONS. b) Order “Optional Battery Tray Battery Disconnect Circuit Breaker and Housing Kits” as required. c) Order “Optional Battery Tray Front Battery Cover Kits” as required.
nd
List 6: 2
Supplemental Bay Common Equipment (Power and Distribution or Distribution Only),
Located Remote from Main Bay
Features
Provides common equipment for one remote “power and distribution or distribution only” bay rated for up
to 2000 amperes of distribution. Includes interbay communications cabling.
Accepts one (1) distribution cabinet (options are 1-row, 2-row, 3-row, or 4-row cabinet).
Includes SM-DU (provides bay interface to ACU+ Controller).
Accepts up to six (6) module mounting shelves Spec. No. 588705000 (including expansion shelves).
or Accepts up to six (6) module mounting shelves Spec. No. 588705300 (including expansion shelves).
Restrictions
When the system is equipped with a List 40, 41, 42, 45, 46, or 47 front access Input Termination Assembly, refer to the restrictions under these list descriptions.
Will not accept List 60 converter interface components. Will not accept dual voltage distribution panels.
Order maximum of one (1) List 3 or List 6 per Power System. Cannot be used when List 3 is ordered. Order List 3 or List 6, not both.
Interbay power cabling is not included, and must be separately provided per site requirements. If low voltage disconnect (List LL or List LB) is to be included, the Main Bay (List 1) of the system must also
have low voltage disconnect (List LL or List LB).
Ordering Notes
1) Order a relay rack or shipping brackets per “Relay Racks and Shipping Brackets” under ACCESSORY DESCRIPTIONS. If required, order relay rack transition plates per “Transition Plates to Mount Relay
Rack on Top of GNB Absolyte IIP Batteries” under ACCESSORY DESCRIPTIONS.
2) Order one (1) List 21, 22, 23, or 24 distribution cabinet. a) Order up to four (4) (per the capacity of the distribution cabinet ordered) distribution panels, battery
disconnect panels, and/or return bar panel as required per “Single Voltage Distribution Panel”, “Battery Disconnect Distribution Panel”, and “Return Bar Panel” under LIST DESCRIPTIONS.
b) Order battery disconnect contactors and low voltage disconnect options as required per “Battery
Disconnect Contactors” and “Low Voltage Disconnect Options” under LIST DESCRIPTIONS.
c) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY
DESCRIPTIONS.
d) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring
Notes” under ACCESSORY DESCRIPTIONS.
e) Order a distribution cabinet top shield as required per List 29. f) If distribution only, order a bottom rear distribution cabinet cover per List 4. g) Order a battery shunt as required per List 90, 91, or 92.
Page 17 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
3) 588705000 Rectifier Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 30. Order field expansion module mounting shelf(s) per List
31. Order module mounting shelf(s) per PD588705000 (choices are 58870500021, 58870500022,
58870500031, 58870500032). a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 if module mounting shelf
58870500021 ordered (or order module mounting shelves with AC line cords or terminal blocks,
58870500022, 58870500031, 58870500032). b) Order rectifier modules as required, P/N 1R483500E, 1R483200E, or 1R483200. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
4) 588705000 Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705000 as required per List 34. Order field expansion module mounting shelf(s) per List 35. Order module mounting shelf(s) per PD588705000 (choices are 58870500040, 58870500041, 58870500042).
a) Order the front access DC Input Termination Assembly per List 45, 46, or 47 if module mounting shelf
58870500040 ordered (or order module mounting shelves with terminal blocks, 58870500041,
58870500042). b) Order converter modules as required, P/N 1C400483500E. c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
5) 588705300 Rectifier/Converter Option: Order interface components for module mounting shelf(s) Spec. No. 588705300 as required per List 32. Order field expansion module mounting shelf(s) per List 33. Order module mounting shelf(s) per PD588705300.
a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 (or order module
mounting shelves with AC input cable assemblies, see PD588705300). b) Order rectifier modules as required, P/N 1R482000E3. c) Order optional converter interface components per List 60. d) Order optional DC-DC converter modules as required, P/N 1C48241500.
6) Order battery trays as required per List 93. a) Order batteries as required per “Batteries” under ACCESSORY DESCRIPTIONS. b) Order “Optional Battery Tray Battery Disconnect Circuit Breaker and Housing Kits” as required. c) Order “Optional Battery Tray Front Battery Cover Kits” as required.

List 21: One-Row Distribution Cabinet

Features
Accepts one (1) distribution panel.
Rated for up to 600 amperes of distribution.
Restrictions
For use in List 1, List 5, and List 6 bays. Cannot be ordered with List 1 if it is to be used with a List 2. Not available for List 2 and List 3 bays (no interbay busbar landings available). Battery disconnect panels cannot be ordered for use in a List 21.
Ordering Notes
1) Order one (1) distribution panel as required per “Single Voltage Distribution Panel” and “Dual Voltage
Distribution Panel” under LIST DESCRIPTIONS.
2) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY DESCRIPTIONS.
3) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring Notes” under ACCESSORY DESCRIPTIONS.
Page 18 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
4) Order battery contactor, battery shunt, and low voltage disconnect options as required.

List 22: Two-Row Distribution Cabinet

Features
Accepts up to two (2) total distribution panels, battery disconnect
distribution panels, and/or return bar panel.
Rated for up to 1200 amperes of distribution.
Restrictions
For use in List 1, List 5, and List 6. Cannot be ordered with List 1 if it is to be used with a List 2. Not available for List 2 and List 3 bays (no interbay busbar landings available).
Ordering Notes
1) Order up to two (2) distribution panels as required per “Single Voltage Distribution Panel”, “Dual Voltage
Distribution Panel”, “Battery Disconnect Distribution Panel”, and “Return Bar Panel” under LIST
DESCRIPTIONS.
2) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY DESCRIPTIONS.
3) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring Notes” under ACCESSORY DESCRIPTIONS.
4) Order battery contactor, battery shunt, and low voltage disconnect options as required.

List 23: Three-Row Distribution Cabinet

Features
Accepts up to three (3) total distribution panels, battery disconnect
distribution panels, and/or return bar panel.
Rated for up to 1800 amperes of distribution.
Restrictions
For use in List 1, List 2, List 3, List 5, and List 6.
Ordering Notes
1) Order up to three (3) distribution panels as required per “Single Voltage
Distribution Panel”, “Dual Voltage Distribution Panel”, “Battery Disconnect Distribution Panel”, and “Return Bar Panel” under LIST DESCRIPTIONS.
2) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY DESCRIPTIONS.
3) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring Notes” under ACCESSORY DESCRIPTIONS.
4) Order battery contactor, battery shunt, and low voltage disconnect options as required.
Page 19 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
F
o
r
U
s
e
w
/
2
-
R
o
w
C
a
b
i
n
e
t
F
o
r
U
s
e
w
/
1
-
R
o
w
C
a
b
i
n
e
t
F
i
r
s
t
S
e
t
f
o
r
U
s
e
w
/
(
1
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
f
S
e
c
o
n
d
S
e
t
f
o
r
U
s
e
w
/
(
2
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
v
e
s
T
h
i
r
d
S
e
t
f
o
r
U
s
e
w
/
(
3
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
v
e
s
F
o
u
r
t
h
S
e
t
f
o
r
U
s
e
w
/
(
4
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
v
e
s
F
i
f
t
h
S
e
t
f
o
r
U
s
e
w
/
(
5
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
v
e
s
F
o
r
U
s
e
w
/
3
-
o
r
4
-
-
R
o
w
C
a
b
i
n
e
t
SAG582127000 System Application Guide Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721

List 24: Four-Row Distribution Cabinet

Features
Accepts up to four (4) total distribution panels, battery disconnect
distribution panels, and/or return bar panel.
Rated for up to 2000 amperes of distribution.
Restrictions
For use in List 1, List 2, List 3, List 5, and List 6.
Ordering Notes
1) Order up to four (4) distribution panels as required per “Single Voltage
Distribution Panel”, “Dual Voltage Distribution Panel”, “Battery Disconnect Distribution Panel”, and “Return Bar Panel” under LIST DESCRIPTIONS.
2) Order fuses and/or circuit breakers as required per “Distribution Devices” under ACCESSORY DESCRIPTIONS.
3) Order input and load distribution lugs, lug adapters, and lug hardware kits as required per “Wiring Notes” under ACCESSORY DESCRIPTIONS.
4) Order battery contactor, battery shunt, and low voltage disconnect options as required.

List 29: Top Shield for Distribution Cabinet

Features
Plastic shield covers all wiring access openings in top of
distribution cabinet. Individual cutouts can be removed for wiring as required for specific installation.
Ordering Notes
1) Where closed top cover is required, order one (1) List 29 for each List 21, 22, 23, and 24 ordered.

List 30: Module Mounting Shelf Interface Components (for Spec. No. 58870500021, 58870500022, 58870500031, 58870500032)

Features
Provides components to add one (1) to five (5)
module mounting shelf(s) (Spec. No. 58870500021, 58870500022, 58870500031,
58870500032) to a Main or Supplemental Bay.
Refer to Power Data Sheet PD588705000 for
module mounting shelf information.
Restrictions
Includes 'module mounting shelf-to-power system/distribution cabinet' interconnect components only. The module mounting shelf(s) must be ordered separately (choices are 58870500021, 58870500022, 58870500031, 58870500032).
Each bay (when used with a List 40 or 42) can be equipped with a maximum of five (5) module mounting shelves (see List 31 for expansion shelves).
Each bay (when used with a List 41) can be equipped with either two (2) or four (4) module mounting shelves (see List 31 for expansion shelves).
Ordering Notes
1) Order one (1) List 30 per module mounting shelf(s)
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Spec. No. 588705000 to be installed in the bay
Page 20 of 125
NPBB)
System Application Guide SAG582127000
Shelf M
o
un
t
in
g H
a
rd
wa
r
e
Bu
sba
r Mounting Hardware
In
te
r
co
nn
e
ct
i
ng
Bu
sbars
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
with these interconnect components (one to five) and specify the number of rows in the distribution cabinet so correct busbars can be provided.
2) Order module mounting shelf(s) as required per PD588705000 (choices are 58870500021, 58870500022, 58870500031, 58870500032). (58870500021 required when List 40, 41, or 42 ordered with the system.)
3) Order rectifier modules as required per P/N 1R483500E, 1R483200E, or 1R483200.
4) Order a module mounting position blank cover panel, P/N 21140440, for each empty module mounting position in the system, as desired.

List 31: Module Mounting Shelf Field Expansion Kit (for Spec. No. 58870500022, 58870500031, 58870500032)

Features
Provides busbars and mounting hardware to tie the DC
output busbars in a field installed module mounting shelf Spec. No. 58870500022, 58870500031, 58870500032 to the system’s DC busbars or between two (2) module expansion shelves.
Restrictions
Maximum of two (2) List 31 per bay. AC inputs MUST be wired directly to the expansion shelf(s).
Ordering Notes
1) Order List 31 for a module mounting shelf Spec. No. 588705000 to be added in the field.
2) Order a module mounting shelf as required per PD588705000 (choices are 58870500022, 58870500031,
58870500032).
3) Order rectifier modules as required per P/N 1R483500E,
1R483200E, or 1R483200.
4) Order a module mounting position blank cover panel, P/N 21140440, for each empty module mounting position in the system, as desired.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 21 of 125
SAG582127000 System Application Guide
F
o
r U
se
w/ 3
- or
4- Ro
w Ca
bin
et
F
o
r U
se
w
/ 1
-R
o
w C
ab
i
ne
t
Fo
r
Us
e w
/
2-
Ro
w
C
a
b
i
n
e
t
F
or
Us
e
w/
(1
)
Re
c
ti
fi
e
r S
he
l
f
F
or
U
s
e
w/
(5)
Rec
tifi
er S
hel
ves
Fo
r U
s
e w
/ (
2
) R
ec
t
if
i
er
Sh
e
lv
es
Fo
r
Us
e w
/
(3
) R
e
c
t
i
f
i
e
r
Sh
e
lv
e
s
Fo
r
U
s
e
w
/ (
4
)
R
e
c
t
i
f
i
e
r S
h
e
l
ve
s
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List 32: Module Mounting Shelf Interface Components (for Spec. No. 588705300)

Features
Provides components to add one (1) to five (5) module
mounting shelf(s) (Spec. No. 588705300) to a Main or Supplemental Bay.
Refer to Power Data Sheet PD588705300 for module
mounting shelf information.
Restrictions
Includes 'module mounting shelf-to-power system/distribution cabinet' interconnect components only. The module mounting shelf(s) must be ordered separately. Refer to List 60 if converters are to be used in the module mounting shelf (main bay only).
Each bay (when used with a List 40 or 42) can be equipped with a maximum of five (5) module mounting shelves (see
List 33 for expansion shelves).
Each bay (when used with a List 41) can be equipped with either two (2) or four (4) mounting shelves (see List 33 for expansion shelves).
Ordering Notes
1) Order one (1) List 32 per module mounting shelf(s) Spec. No. 588705300 to be installed in the bay with these interconnect components (one to five) and specify the number of rows in the distribution cabinet so correct busbars can be provided.
2) Order module mounting shelf(s) as required per PD588705300.
3) Order rectifier modules as required per P/N 1R482000E3.
4) Order optional DC-DC converter modules as required, P/N 1C48241500 (Main Bay Only). Requires List 60 to be installed in Main Bay.

List 33: Module Mounting Shelf Field Expansion Kit (for Spec. No. 588705300)

Features
Provides a field expansion module mounting shelf
Spec. No. 588705300.
Restrictions
Maximum of two (2) List 33 per bay. AC inputs MUST be wired directly to the expansion
shelf(s).
Ordering Notes
1) Order List 33 for a module mounting shelf Spec. No. 588705300 to be added in the field.
2) Order rectifier modules as required per P/N 1R482000E3.
3) Order optional DC-DC converter modules as required, P/N 1C48241500 (Main Bay Only). Requires List 60 to be installed in Main Bay.
Page 22 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Shel
f Mount
ing Hard
ware
Busbar Mounting Ha
rdware
Inter
connecting Busbars
Home
F
o
r
U
s
e
w
/
2
-
R
o
w
C
a
b
i
n
e
t
F
o
r
U
s
e
w
/
1
-
R
o
w
C
a
b
i
n
e
t
F
i
r
s
t
S
e
t
f
o
r
U
s
e
w
/
(
1
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
f
S
e
c
o
n
d
S
e
t
f
o
r
U
s
e
w
/
(
2
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
v
e
s
T
h
i
r
d
S
e
t
f
o
r
U
s
e
w
/
(
3
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
v
e
s
F
o
u
r
t
h
S
e
t
f
o
r
U
s
e
w
/
(
4
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
v
e
s
F
i
f
t
h
S
e
t
f
o
r
U
s
e
w
/
(
5
)
M
o
d
u
l
e
M
o
u
n
t
i
n
g
S
h
e
l
v
e
s
F
o
r
U
s
e
w
/
3
-
o
r
4
-
-
R
o
w
C
a
b
i
n
e
t
System Application Guide SAG582127000 Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

List 34: Module Mounting Shelf Interface Components (for Spec. No. 58870500040, 58870500041, 58870500042)

Features
Provides components to add one (1) to five (5)
module mounting shelf(s) (Spec. No. 58870500040, 58870500041, 58870500042) to a Main or Supplemental Bay.
Refer to Power Data Sheet PD588705000 for
module mounting shelf information.
Restrictions
Includes 'module mounting shelf-to-power system/distribution cabinet' interconnect components only. The module mounting shelf(s) must be ordered separately (choices are 58870500040, 58870500041,
58870500042).
Each bay (when used with a List 45 or 47) can be equipped with a maximum of five (5) module mounting shelves (see List 35 for expansion shelves).
Each bay (when used with a List 46) can be equipped with either two (2) or four (4) module mounting shelves (see List 35 for expansion shelves).
Ordering Notes
1) Order one (1) List 34 per module mounting shelf(s) Spec. No. 588705000 to be installed in the bay with these interconnect components (one to five) and specify the number of rows in the distribution cabinet so correct busbars can be provided.
2) Order module mounting shelf(s) as required per PD588705000 (choices are 58870500040, 58870500041, 58870500042). (58870500040 required when List 45, 46, or 47 ordered with the system.)
3) Order converter modules as required, P/N 1C400483500E.
4) Order a module mounting position blank cover panel, P/N 21140440, for each empty module mounting position in the system, as desired.

List 35: Module Mounting Shelf Field Expansion Kit (for Spec. No. 58870500041, 58870500042)

Features
Provides busbars and mounting hardware to tie the DC
output busbars in a field installed module mounting shelf Spec. No. 58870500041, 58870500042 to the system’s DC busbars or between two (2) module expansion shelves.
Restrictions
Maximum of two (2) List 35 per bay. DC inputs MUST be wired directly to the expansion shelf(s).
Ordering Notes
1) Order List 35 for a module mounting shelf Spec. No. 588705000 to be added in the field.
2) Order a module mounting shelf as required per PD588705000 (choices are 58870500041, 58870500042).
3) Order converter modules as required, P/N 1C400483500E.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 23 of 125
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
4) Order a module mounting position blank cover panel, P/N 21140440, for each empty module mounting position in the system, as desired.

List 40: Front Access AC Input Termination Assembly (1 AC Feed per 1 Rectifier, Single Phase, 1-5 Shelves)

Features
Provides AC input terminal blocks for connection of single phase 208/240 volts AC input feeds for all
rectifier positions in the bay. One (1) AC input feed required per one (1) rectifier position. Refer to “AC Input Connections to AC Input Termination Assembly List 40, 41, 42 Illustration when used with 588705000 or 588705300 Module Mounting Shelves with Rectifiers (Nominal 208/240 Volts AC)” on page 84 for specific wiring details.
Restrictions
For use with 58870500021 or 588705300 module mounting shelf only. Factory installed only. For initial installation only. Initial module mounting shelves are factory wired to List 40. If a field expansion
module mounting shelf is added to the system, AC inputs MUST be wired directly to the shelf.
Ordering Notes
1) Order either List 40, 41, or 42 for each bay (or order module mounting shelves with AC input line cords, AC input cable assemblies, or AC input terminal blocks). See PD588705000 or PD588705300.

List 41: Front Access AC Input Termination Assembly (1 AC Feed per 2 Rectifiers, Single Phase, 2 or 4 Shelves)

Features
Provides AC input terminal blocks for connection of single phase 208/240 volts AC input feeds for all
rectifier positions in the bay. One (1) AC input feed required per two (2) rectifier positions. Refer to “AC Input Connections to AC Input Termination Assembly List 40, 41, 42 Illustration when used with 588705000 or 588705300 Module Mounting Shelves with Rectifiers (Nominal 208/240 Volts AC)” on page 84 for specific wiring details.
Restrictions
For use with 58870500021 or 588705300 module mounting shelf only. Factory installed only. For initial installation only. Initial module mounting shelves are factory wired to List 41. If a field expansion
module mounting shelf is added to the system, AC inputs MUST be wired directly to the shelf. List 41 can only be used with either two (2) or four (4) module mounting shelves.
Ordering Notes
1) Order either List 40, 41, or 42 for each bay (or order module mounting shelves with AC input line cords, AC input cable assemblies, or AC input terminal blocks). See PD588705000 or PD588705300.

List 42: Front Access AC Input Termination Assembly (1 AC Feed per 3 Rectifiers, 3-Phase, 1-5 Shelves)

Features
Provides AC input terminal blocks for connection of three phase 208/240 volts AC input feeds for all
rectifier positions in the bay. One (1) AC input feed required per three (3) rectifier positions. Refer to “AC Input Connections to AC Input Termination Assembly List 40, 41, 42 Illustration when used with 588705000 or 588705300 Module Mounting Shelves with Rectifiers (Nominal 208/240 Volts AC)” on page 84 for specific wiring details.
Restrictions
For use with 58870500021 or 588705300 module mounting shelf only.
Page 24 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Factory installed only. For initial installation only. Initial module mounting shelves are factory wired to List 42. If a field
expansion module mounting shelf is added to the system, AC inputs MUST be wired directly to the shelf.
Ordering Notes
1) Order either List 40, 41, or 42 for each bay (or order module mounting shelves with AC input line cords, AC input cable assemblies, or AC input terminal blocks). See PD588705000 or PD588705300.

List 45: Front Access DC Input Termination Assembly (1 DC Feed per 1 Converter, 1-5 Shelves)

Features
Provides DC input terminal blocks for connection of 400 volts DC input feeds for all converter positions in
the bay. One (1) DC input feed required per one (1) converter position. Refer to “400V DC Input Connections to DC Input Termination Assembly List 45, 46, 47 Illustration when used with 588705000 Module Mounting Shelves with Converters” on page 90 for specific wiring details.
Restrictions
For use with 58870500040 module mounting shelf only. Factory installed only. For initial installation only. Initial module mounting shelves are factory wired to List 45. If a field expansion
module mounting shelf is added to the system, DC inputs MUST be wired directly to the shelf.
Ordering Notes
1) Order either List 45, 46, or 47 for each bay (or order module mounting shelves with DC input terminal blocks). See PD588705000.

List 46: Front Access DC Input Termination Assembly (1 DC Feed per 2 Converters, 2 or 4 Shelves)

Features
Provides DC input terminal blocks for connection of 400 volts DC input feeds for all converter positions in
the bay. One (1) DC input feed required per two (2) converter positions. Refer to “400V DC Input Connections to DC Input Termination Assembly List 45, 46, 47 Illustration when used with 588705000 Module Mounting Shelves with Converters” on page 90 for specific wiring details.
Restrictions
For use with 58870500040 module mounting shelf only. Factory installed only. For initial installation only. Initial module mounting shelves are factory wired to List 46. If a field expansion
module mounting shelf is added to the system, DC inputs MUST be wired directly to the shelf. List 46 can only be used with either two (2) or four (4) module mounting shelves.
Ordering Notes
1) Order either List 45, 46, or 47 for each bay (or order module mounting shelves with DC input terminal blocks). See PD588705000.

List 47: Front Access DC Input Termination Assembly (1 DC Feed per 3 Converters, 1-5 Shelves)

Features
Provides DC input terminal blocks for connection of 400 volts DC input feeds for all converter positions in
the bay. One (1) DC input feed required per three (3) converter positions. Refer to “400V DC Input Connections to DC Input Termination Assembly List 45, 46, 47 Illustration when used with 588705000 Module Mounting Shelves with Converters” on page 90 for specific wiring details.
Page 25 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
For Use w/ (1)
Rectifier/Converter Shelf
For Use w/ (2
Rectifier/Converter Shelves
For Use w/ (3)
Rectifier/Converter Shelves
For Use w/ (4)
Rectifier/Converter Shelves
For Use w/ (5)
Rectifier/Converter Shelves
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Restrictions
For use with 58870500040 module mounting shelf only. Factory installed only. For initial installation only. Initial module mounting shelves are factory wired to List 47. If a field expansion
module mounting shelf is added to the system, DC inputs MUST be wired directly to the shelf.
Ordering Notes
1) Order either List 45, 46, or 47 for each bay (or order module mounting shelves with DC input terminal blocks). See PD588705000.

List 60: Converter Interface Components (for Spec. No. 588705300)

Features
Provides components to interface
converters in Spec. No. 588705300 module mounting shelves to the distribution cabinet.
Restrictions
Must be used in systems equipped with Spec. No. 588705300 module mounting shelves.
Must be installed in main bay only.
Must be used in conjunction with a dual voltage bus distribution panel.
Ordering Notes
1) Order List 60 as required. Quantity of List 60 must equal the quantity of module mounting shelf(s) Spec. No. 588705300 installed in the bay with a maximum of four (4) List 60. Note that if five (5) shelves are in the bay, the quantity of List 60 is still four (4).
2) Specify the number of module mounting shelf(s) Spec. No. 588705300 installed in the bay (one to five) so correct busbars can be provided.
3) Order up to three (3) converter modules, P/N 1C48241500, per module mounting shelf. Each List 60 allows the three right-most shelf positions (when viewed from the front) to accept either converter or rectifier modules.

List 90: Optional Battery Shunt, 800A

Features
Provides an 800A battery shunt.
Restrictions
For use with List 21 only. Cannot be used with low voltage load disconnect (LVLD) in a List 21. Must be ordered with List CA.
Ordering Notes
1) Order as required.
2) Also order List CA (600A Battery Disconnect Contactor) and either List LB (Low Voltage Battery Disconnect) or List MB (Manual Battery Disconnect) or both.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 26 of 125
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

List 91: Optional Battery Shunt, 2000A

Features
Provides a 2000A battery shunt.
Restrictions
For use with List 22 only.
Ordering Notes
1) Order as required.

List 92: Optional Battery Shunt, 2500A

Features
Provides a 2500A battery shunt.
Restrictions
For use with List 23 and 24 only.
Ordering Notes
1) Order as required.
Page 27 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List 93: Optional Battery Tray, Pre-Cabled

Features
Each List 93 provides one (1) battery tray factory
mounted in the 23” wide system relay rack specified when ordered. Each battery tray holds four (4) 12V front terminal valve regulated lead acid (VRLA) batteries. Battery cabling is factory provided and connected to the system’s main busbars. Batteries are configured as one (1) 48V string per tray.
Battery trays can be ordered with or without a battery
disconnect circuit breaker. When a circuit breaker is ordered, it is provided in the -48V lead of each battery string (1 circuit breaker per tray).
Battery tray dimensions are 21.3” wide X 24.4” deep. Refer to “List 93 (Battery Tray)” under PHYSICAL
SIZE INFORMATION for a typical battery tray arrangement.
Battery spacers included.
Restrictions
Designed to accommodate the batteries listed under “Batteries” in the ACCESSORY DESCRIPTIONS section.
A single battery tray must mount at bottom of relay rack. Multiple battery trays must mount starting at bottom of relay rack and working upward. Factory spaces battery trays 6RU, 7RU, or 8RU apart as determined by battery selected. If no battery selected, factory spaces battery trays 8RU apart. Spacing can be increased above that required for the battery selected up to a maximum of 8RU.
Cable size for each tray is 2AW G for optional battery disconnect circuit breaker selected up to 100A and 1/0AWG for circuit breaker selected over 100A or if circuit breaker is not selected.
Maximum number of List 93 per relay rack is four (4). Not a stand-alone battery system. Must be used as part of a power system that includes a List 1 (List 2, List
3, List 5, or List 6) with a List 21, 22, 23, or 24 and a List 30.
Ordering Notes
1) Order up to four (4) battery trays per relay rack, as required.
2) Order battery cable termination kit, one per bay. P/N 553584 for use with List 21, P/N 555478 for use with Lists 22, 23 and 24.
3) Order batteries separately. See “Batteriesin the ACCESSORY DESCRIPTIONS section. Battery cables and lugs factory provided and connected.
4) If optional battery tray battery disconnect circuit breaker is desired, order per “Optional Battery Tray
Battery Disconnect Circuit Breaker and Housing Kits” in the ACCESSORY DESCRIPTIONS section.
5) If optional battery tray front battery cover is desired, order per “Optional Battery Tray Front Battery Cover
Kits” in the ACCESSORY DESCRIPTIONS section.
P/N 553584 P/N 555478
Page 28 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Loa
d
Connections
Lo
ad Return
Con
necti
ons
LOAD AND LOAD RETURN CONNECTIONS 1/4-20 Studs on 5/8” Centers (Cu
sto
mer
must supply or order addit
ional hardwa
re)
Maximum
Lug
Width
: 0.625 inches.
Return Busbar (not included with List AB)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Single Voltage Distribution Panels

List AA: -48V Distribution Panel (with Return Busbar) and List AB: -48V Distribution Panel (without Return Busbar), (24) Bullet/TPS/TLS Circuit Breaker/Fuse Positions

Features
(24) -48V Load Distribution Fuse / Circuit Breaker Mounting Positions:
3A to 100A TPS/TLS Type Fuses, 1A to 250A Bullet Nose Type Circuit Breakers, or accepts “Optional Bullet Nose Type 6-Position GMT Distribution Fuse Block (P/N 550224)”.
List AA includes a Return Busbar; List AB does not include a Return Busbar.
600A Maximum Capacity.
Restrictions
Can be installed in any row 1-4 of a 1-, 2-, 3-, or 4-row distribution cabinet. Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the
highest capacity and working to the lowest capacity. 125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions.
225A and 250A circuit breakers occupy three mounting positions.
Caution: A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
Maximum lug width, 0.625 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL per panel as required.
3) List AB: To terminate load returns within the distribution cabinet, order List GA as required.
4) Order circuit breakers as required per Table 10 or Table 11.
5) Order fuses as required per Table 12. Also order one (1) P/N 117201 bullet nose type fuseholder per fuse ordered. Order replacement alarm fuses (18/100A) per Table 17.
6) Order 6-position GMT fuse block P/N 550224 and fuses per Table 13 as required.
7) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 27.
8) Order lug hardware kit (P/N 541084) as required. Lug hardware kit provides thirty-two (32) sets of 1/4-20 hardware (nuts, flat washers, and lock washers), enough for sixteen (16) lug landing points.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 29 of 125
SAG582127000 System Application Guide
Load
Connections
Load Return C
onn
ections
LOAD AND LOAD RETURN
CON
NECTIONS
3/8-16 Cap
tiv
e Nuts on 1” Centers
(
Customer must supply or order add
itio
nal
hardware)
Ma
ximu
m Lug Width: 1.375 inches.
Return Bus
bar
(no
t inc
lud
ed with List AD)
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List AC: -48V Distribution Panel (with Return Busbar) and List AD: -48V Distribution Panel (without Return Busbar), (4) GJ/218 Circuit Breaker Positions

Features
(4) -48V Load Distribution Circuit Breaker Mounting Positions:
100A to 800A GJ/218 Type Circuit Breakers.
List AC includes a Return Busbar; List AD does not include a Return Busbar.
600A Maximum Capacity.
Maximum current rating of each landing point is 360A.
Restrictions
Can be installed in any bus row 1-4 of a 1-, 2-, 3-, or 4-row distribution cabinet. Maximum lug width, 1.375 inches. For an 800A circuit breaker, load must not exceed 600A.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL per panel as required.
3) List AD: To terminate load returns within the distribution cabinet, order List GA as required.
4) Order circuit breakers and associated jumper kits as required per Table 14.
5) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
6) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 30 of 125
System Application Guide SAG582127000
Load
Connections
LOAD CONNECTIONS 3/8-16 Captive Nuts on 1” Centers (Customer must supply or order additional hardware)
Maximum Lug Width: 1.88 inches.
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

List AE: -48V Distribution Panel, (2) TPH Fuse Positions (without Shunts) (without Return Busbar)

Features
(2) -48V Distribution Fuse Mounting Positions:
70A to 800A TPH Type Fuses.
Does NOT include Shunts.
Does NOT include a Return Busbar.
600A Maximum Capacity.
Restrictions
Can be installed in any row 1-4 of a 1-, 2-, 3-, or 4-row distribution cabinet. Maximum lug width, 1.88 inches. For an 800A fuse, load must not exceed 600A.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL per panel as required.
3) To terminate load returns within the distribution cabinet, order List GA as required.
4) Order fuses as required per Table 15. Order replacement alarm fuses (1/4A) per Table 17.
5) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
6) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 31 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Loa
d
Co
nnections
LOAD CONNECTIONS 3/8-16 Captive Nuts on 1” Centers (Customer must supply or order additional hardware)
Maximum Lug Width: 1.88 inches.
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List AF: -48V Distribution Panel, (2) TPH Fuse Positions (with Shunts) (without Return Busbar)

Features
(2) -48V Distribution Fuse Mounting Positions:
70A to 800A TPH Type Fuses.
Includes Shunts, 800A / 25mV. Each shunt is equipped with 10’ jumpers for connection to monitoring
device. If the system is equipped with an SM-DU+, the leads are trimmed and connected to the SM-DU+ (internal to the distribution cabinet).
Does NOT include a Return Busbar.
600A Maximum Capacity.
Restrictions
Can be installed in any row 1-4 of a 1-, 2-, 3-, or 4-row distribution cabinet. Maximum lug width, 1.88 inches. For an 800A fuse, load must not exceed 600A.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL per panel as required.
3) To terminate load returns within the distribution cabinet, order List GA as required.
4) Order fuses as required per Table 15. Order replacement alarm fuses (1/4A) per Table 17.
5) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
6) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 32 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
L
oa
d
C
o
nn
e
ct
io
n
s
L
OAD C
ONN
EC
TI
ON
S
3
/8
-1
6
Ca
pt
i
v
e
N
ut
s o
n 1” C
ent
ers
(
Cus
tom
er m
ust
su
pp
l
y o
r o
r
de
r a
d
d
i
ti
o
na
l ha
rdwa
re)
Ma
ximu
m Lu
g Wi
dt
h:
1.
7
5 i
nc
h
es
.
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

List AG: -48V Distribution Panel, (4) TPH Fuse Positions (without Shunts) (without Return Busbar)

Features
(4) -48V Distribution Fuse Mounting Positions:
70A to 400A TPH Type Fuses.
Does NOT include Shunts.
Does NOT include a Return Busbar.
600A Maximum Capacity.
Restrictions
Can be installed in any row 1-4 of a 1-, 2-, 3-, or 4-row distribution cabinet. Maximum lug width, 1.75 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL per panel as required.
3) To terminate load returns within the distribution cabinet, order List GA as required.
4) Order fuses as required per Table 15. Order replacement alarm fuses (1/4A) per Table 17.
5) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
6) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 33 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
L
oad
C
o
n
n
e
ct
i
ons
LOAD CONNECTIONS 3/8-16 Captive Nuts on 1” Centers (Customer must supply or order additional hardware)
Maximum Lug Width: 1.75 inches.
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List AH: -48V Distribution Panel, (4) TPH Fuse Positions (with Shunts) (without Return Busbar)

Features
(4) -48V Distribution Fuse Mounting Positions:
70A to 400A TPH Type Fuses.
Includes Shunts, 600A / 25mV. Each shunt is equipped with 10’ jumpers for connection to monitoring
device. If the system is equipped with an SM-DU+, the leads are trimmed and connected to the SM-DU+ (internal to the distribution cabinet).
Does NOT include a Return Busbar.
600A Maximum Capacity.
Restrictions
Can be installed in any row 1-4 of a 1-, 2-, 3-, or 4-row distribution cabinet. Maximum lug width, 1.75 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL per panel as required.
3) To terminate load returns within the distribution cabinet, order List GA as required.
4) Order fuses as required per Table 15. Order replacement alarm fuses (1/4A) per Table 17.
5) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
6) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 34 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Loa
d
Conn
ect
ions
LOAD
CON
NEC
TIONS
3/8
-16 S
tud
s on 1” Centers
(Cus
tom
er must supply or order addition
al h
ardw
are)
Max
imum Lug Width: 1.5 inches.
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

List AJ: -48V Distribution Panel, (4) TPL-B Fuse Positions (without Shunts) (without Return Busbar)

Features
(4) -48V Distribution Fuse Mounting Positions:
70A to 250A TPL-B Type Fuses.
Does NOT include Shunts.
Does NOT include a Return Busbar.
600A Maximum Capacity.
Restrictions
Can be installed in any row 1-4 of a 1-, 2-, 3-, or 4-row distribution cabinet. Maximum lug width, 1.50 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL per panel as required.
3) To terminate load returns within the distribution cabinet, order List GA as required.
4) Order fuses as required per Table 16. Order replacement alarm fuses (18/100A) per Table 17.
5) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
6) Order lug hardware kit (P/N 548185) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (nuts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 35 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Load
Connections
L
OAD
CONNECTIONS
3/
8-1
6 St
uds on 1” Centers
(Cust
ome
r must supply or ord
er a
ddit
i
onal h
ardw
are
)
Maxi
mum
Lug
Width: 1.5 inc
hes
.
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List AK: -48V Distribution Panel, (4) TPL-B Fuse Positions (with Shunts) (without Return Busbar)

Features
(4) -48V Distribution Fuse Mounting Positions:
70A to 250A TPL-B Type Fuses.
Includes Shunts, 300A / 25mV. Each shunt is equipped with 10’ jumpers for connection to monitoring
device. If the system is equipped with an SM-DU+, the leads are trimmed and connected to the SM-DU+ (internal to the distribution cabinet).
Does NOT include a Return Busbar.
600A Maximum Capacity.
Restrictions
Can be installed in any row 1-4 of a 1-, 2-, 3-, or 4-row distribution cabinet. Maximum lug width, 1.50 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL per panel as required.
3) To terminate load returns within the distribution cabinet, order List GA as required.
4) Order fuses as required per Table 16. Order replacement alarm fuses (18/100A) per Table 17.
5) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
6) Order lug hardware kit (P/N 548185) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (nuts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 36 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Load
Connections
Load Return Connections
LOAD AND LOAD RETURN CONNECTIONS 1/4-20 Studs on 5/8” Centers (Customer must supply or order additional hardware)
Maximum Lug Width:
0.625 inches.
-
4
8
V
D
i
s
t
r
i
b
u
t
i
o
n
+
2
4
V
D
i
s
t
r
i
b
u
t
i
o
n
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Dual Voltage Distribution Panels

List DA: -48V/+24V Distribution Panel, (17) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and (4) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar)

Features
(17) -48V Load Distribution Fuse / Circuit Breaker Mounting Positions:
(4) +24V Load Distribution Fuse / Circuit Breaker Mounting Positions: 3A to 100A TPS/TLS Type Fuses, 1A to 250A Bullet Nose Type Circuit Breakers.
Includes a Return Busbar.
600A Maximum Total Capacity:
600A Maximum -48V Distribution Capacity. 256A Maximum +24V Distribution Capacity.
Restrictions
Cannot be used in a supplemental bay. Limit two (2) dual voltage distribution panels (List DA, DB, DC, or DD) per power system. If two dual voltage
distribution panels are ordered, they must be mounted in adjacent rows and must be the same List Number. Can be installed in rows 1 to 2 of a 1-, 2-, 3-, or 4-row distribution cabinet. Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the
highest capacity and working to the lowest capacity. 125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions.
225A and 250A circuit breakers occupy three mounting positions.
Caution: A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
Maximum lug width, 0.625 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL (for 24V positions) as required.
3) Order circuit breakers as required per Table 10 or Table 11.
4) Order fuses as required per Table 12. Also order one (1) P/N 117201 bullet nose type fuseholder per fuse ordered. Order replacement alarm fuses (18/100A) per Table 17.
5) Order 6-position GMT fuse block P/N 550224 and fuses per Table 13 as required.
6) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 27.
7) Order lug hardware kit (P/N 541084) as required. Lug hardware kit provides thirty-two (32) sets of 1/4-20 hardware (nuts, flat washers, and lock washers), enough for sixteen (16) lug landing points.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 37 of 125
SAG582127000 System Application Guide
L 1 ( o h
M 0
+
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List DB: -48V/+24V Distribution Panel, (13) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and (8) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar)

Features
(13) -48V Load Distribution Fuse / Circuit Breaker Mounting Positions:
(8) +24V Load Distribution Fuse / Circuit Breaker Mounting Positions: 3A to 100A TPS/TLS Type Fuses,
1A to 250A Bullet Nose Type Circuit Breakers.
Includes a Return Busbar.
600A Maximum Total Capacity:
600A Maximum -48V Distribution Capacity. 500A Maximum +24V Distribution Capacity.
Restrictions
Cannot be used in a supplemental bay. Limit two (2) dual voltage distribution panels (List DA, DB, DC, or DD) per power system. If two dual voltage
distribution panels are ordered, they must be mounted in adjacent rows and must be the same List Number. Can be installed in rows 1 to 2 of a 1-, 2-, 3-, or 4-row distribution cabinet. Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the
highest capacity and working to the lowest capacity. 125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions.
225A and 250A circuit breakers occupy three mounting positions.
Caution: A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
Maximum lug width, 0.625 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL (for 24V positions) as required.
3) Order circuit breakers as required per Table 10 or Table 11.
4) Order fuses as required per Table 12. Also order one (1) P/N 117201 bullet nose type fuseholder per fuse ordered. Order replacement alarm fuses (18/100A) per Table 17.
5) Order 6-position GMT fuse block P/N 550224 and fuses per Table 13 as required.
6) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 27.
7) Order lug hardware kit (P/N 541084) as required. Lug hardware kit provides thirty-two (32) sets of 1/4-20 hardware (nuts, flat washers, and lock washers), enough for sixteen (16) lug landing points.
2
4V
D
i
OAD AND LOAD RETURN CONNECTIONS /4-20 Studs on 5/8” Centers
Customer must supply
r order additional ardware)
aximum Lug Width:
.625 inches.
Load Return Connections
Load
Connections
s
tr
i
bu
t
i
on
-
4
8V
D
i
s
tr
i
bu
ti
on
Page 38 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Load
Connections
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS 1/4-20 Studs on 5/8” Centers (Customer must supply or order additional hardware)
Maximum Lug Width:
0.625 inches.
-
4
8V
D
i
s
t
r
i
bu
ti
on
+
2
4
V
D
i
s
t
r
i
bu
ti
o
n
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

List DC: -48V/+24V Distribution Panel, (9) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and (12) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar)

Features
(9) -48V Load Distribution Fuse / Circuit Breaker Mounting Positions:
(12) +24V Load Distribution Fuse / Circuit Breaker Mounting Positions: 3A to 100A TPS/TLS Type Fuses,
1A to 250A Bullet Nose Type Circuit Breakers.
Includes a Return Busbar.
600A Maximum Total Capacity:
576A Maximum -48V Distribution Capacity. 500A Maximum +24V Distribution Capacity.
Restrictions
Cannot be used in a supplemental bay. Limit two (2) dual voltage distribution panels (List DA, DB, DC, or DD) per power system. If two dual voltage
distribution panels are ordered, they must be mounted in adjacent rows and must be the same List Number. Can be installed in rows 1 to 2 of a 1-, 2-, 3-, or 4-row distribution cabinet. Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the
highest capacity and working to the lowest capacity. 125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions.
225A and 250A circuit breakers occupy three mounting positions.
Caution: A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
Maximum lug width, 0.625 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL (for 24V positions) as required.
3) Order circuit breakers as required per Table 10 or Table 11.
4) Order fuses as required per Table 12. Also order one (1) P/N 117201 bullet nose type fuseholder per fuse ordered. Order replacement alarm fuses (18/100A) per Table 17.
5) Order 6-position GMT fuse block P/N 550224 and fuses per Table 13 as required.
6) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 27.
7) Order lug hardware kit (P/N 541084) as required. Lug hardware kit provides thirty-two (32) sets of 1/4-20 hardware (nuts, flat washers, and lock washers), enough for sixteen (16) lug landing points.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 39 of 125
SAG582127000 System Application Guide
Load
Connections
-
4
8V
D
i
s
tr
i
b
u
ti
o
n
+
2
4V
D
i
s
t
r
i
b
uti
on
Load Return Connections
LOAD AND LOAD RETURN CONNECTIONS 1/4-20 Studs on 5/8” Centers (Customer must supply or order additional hardware)
Maximum Lug Width:
0.625 i
nches.
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List DD: -48V/+24V Distribution Panel, (5) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and (16) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar)

Features
(5) -48V Load Distribution Fuse / Circuit Breaker Mounting Positions:
(16) +24V Load Distribution Fuse / Circuit Breaker Mounting Positions: 3A to 100A TPS/TLS Type Fuses,
1A to 250A Bullet Nose Type Circuit Breakers.
Includes a Return Busbar.
600A Maximum Total Capacity:
320A Maximum -48V Distribution Capacity. 500A Maximum +24V Distribution Capacity.
Restrictions
Cannot be used in a supplemental bay. Limit two (2) dual voltage distribution panels (List DA, DB, DC, or DD) per power system. If two dual voltage
distribution panels are ordered, they must be mounted in adjacent rows and must be the same List Number. Can be installed in rows 1 to 2 of a 1-, 2-, 3-, or 4-row distribution cabinet. Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the
highest capacity and working to the lowest capacity. 125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions.
225A and 250A circuit breakers occupy three mounting positions.
Caution: A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
Maximum lug width, 0.625 inches.
Ordering Notes
1) Specify row for panel location(s).
2) Order low voltage load disconnect List LL (for 24V positions) as required.
3) Order circuit breakers as required per Table 10 or Table 11.
4) Order fuses as required per Table 12. Also order one (1) P/N 117201 bullet nose type fuseholder per fuse ordered. Order replacement alarm fuses (18/100A) per Table 17.
5) Order 6-position GMT fuse block P/N 550224 and fuses per Table 13 as required.
6) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 27.
7) Order lug hardware kit (P/N 541084) as required. Lug hardware kit provides thirty-two (32) sets of 1/4-20 hardware (nuts, flat washers, and lock washers), enough for sixteen (16) lug landing points.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 40 of 125
System Application Guide SAG582127000
B
att
er
y
Co
nnecti
ons
Battery
Ret
urn
Con
nect
i
on
s
BA
TTER
Y A
ND
BA
TTER
Y RE
TURN C
ONN
ECTI
ON
S
1
/4-
20 St
uds
o
n 5
/8”
Cen
ter
s Max
imu
m Lu
g
Wi
dth
: 0.
625
inches.
(
Cu
st
o
mer m
ust
supply
o
r or
der additiona
l
hardwa
re)
Retu
rn B
u
sb
ar
(
not
inc
lud
ed with List BB)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Battery Disconnect Distribution Panels

List BA: Battery Disconnect Distribution Panel (with Return Busbar) and List BB: Battery Disconnect Distribution Panel (without Return Busbar), (24) Bullet/TPS/TLS Circuit Breaker/Fuse Battery Disconnect Positions

Features
(24) -48V Battery Disconnect Fuse / Circuit Breaker Mounting Positions:
3A to 100A TPS/TLS Type Fuses, 1A to 250A Bullet Nose Type Circuit Breakers.
List BA includes a Return Busbar; List BB does not include a Return Busbar.
600A Maximum Capacity.
Restrictions
Cannot be used with List 21. Must be installed in top row only (limit one battery disconnect distribution panel per distribution cabinet). Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the
highest capacity and working to the lowest capacity. 125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions.
225A and 250A circuit breakers occupy three mounting positions.
Caution: A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
Maximum lug width, 0.625 inches.
Ordering Notes
1) Order circuit breakers as required per Table 10 or Table 11.
2) Order fuses as required per Table 12. Also order one (1) P/N 117201 bullet nose type fuseholder per fuse ordered. Order replacement alarm fuses (18/100A) per Table 17.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 27.
4) Order lug hardware kit (P/N 541084) as required. Lug hardware kit provides thirty-two (32) sets of 1/4-20 hardware (nuts, flat washers, and lock washers), enough for sixteen (16) lug landing points.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 41 of 125
SAG582127000 System Application Guide
Batt
ery
Connection
s
Ba
tter
y Return
C
o
nne
ctio
ns
BAT
TERY A
ND
BA
T
TER
Y RE
TURN
CON
NECTION
S
3/8-
16 C
apt
ive N
uts
on 1” Cen
t
er
s
(Custome
r
mu
st
s
upp
ly
or or
der
add
iti
onal
hardwa
re
)
Maxim
um
L
ug
Widt
h:
1
.37
5 in
ches.
Re
tur
n Bu
sbar
(not
in
c
lu
ded
wit
h List BD)
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List BC: Battery Disconnect Distribution Panel (with Return Busbar) and List BD: Battery Disconnect Distribution Panel (without Return Busbar), (4) GJ/218 Circuit Breaker Battery Disconnect Positions

Features
(4) -48V Battery Disconnect Circuit Breaker Mounting Positions:
100A to 800A GJ/218 Type Circuit Breakers.
List BC Includes a Return Busbar; List BD does not include a Return Busbar.
600A Maximum Capacity.
Maximum current rating of each landing point is 360A.
Restrictions
Cannot be used with List 21. Must be installed in top row only (limit one battery disconnect panel per distribution cabinet). Maximum lug width, 1.375 inches. For an 800A circuit breaker, load must not exceed 600A.
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Table 14.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
3) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 42 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Battery
Connections
BATTERY CONNECTIONS 3/8-16 Captive Nuts on 1” Centers Maximum Lug Width: 1.8
8 inches. (Customer must supply or order additional hardware)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

List BE: Battery Disconnect Distribution Panel, (2) TPH Fuse Battery Disconnect Position (without Shunts) (without Return Busbar)

Features
(2) -48V Battery Disconnect Fuse Mounting Positions:
70A to 800A TPH Type Fuses.
Does NOT include Shunts.
Does NOT include a Return Busbar.
1200A Maximum Capacity.
Restrictions
Cannot be used with List 21. Must be installed in top row only (limit one battery disconnect panel per distribution cabinet). Maximum lug width, 1.88 inches. For an 800A fuse, load must not exceed 600A.
Ordering Notes
1) Order fuses as required per Table 15. Order replacement alarm fuses (1/4A) per Table 17.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
3) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 43 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
BATTERY CONNECTIONS
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List BF: Battery Disconnect Distribution Panel, (2) TPH Fuse Battery Disconnect Positions (with Shunts) (without Return Busbar)

Features
(2) -48V Battery Disconnect Fuse Mounting Positions:
70A to 800A TPH Type Fuses.
Includes Shunts, 800A / 25mV. Each shunt is equipped with 10’ jumpers for connection to monitoring
device. If the system is equipped with an SM-DU+, the leads are trimmed and connected to the SM-DU+ (internal to the distribution cabinet).
Does NOT include a Return Busbar.
1200A Maximum Capacity.
Restrictions
Cannot be used with List 21. Must be installed in top row only (limit one battery disconnect panel per distribution cabinet). Maximum lug width, 1.88 inches. For an 800A fuse, load must not exceed 600A.
Ordering Notes
1) Order fuses as required per Table 15. Order replacement alarm fuses (1/4A) per Table 17.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
3) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
3/8-16 Captive Nuts on 1” Centers Maximum Lug Width: 1.88 inches. (Customer must supply or order additional hardware)
Battery
Connections
Page 44 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Ba
tter
y
Conne
cti
ons
BATTERY CONNECTIONS 3/
8-16 Captive Nuts on 1” Cent
ers
Maximum Lug Width: 1.7
5 inches. (Customer must supply or o
rder additional
har
dwa
re)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

List BG: Battery Disconnect Distribution Panel, (4) TPH Fuse Battery Disconnect Positions (without Shunts) (without Return Busbar)

Features
(4) -48V Battery Disconnect Fuse Mounting Positions:
70A to 400A TPH Type Fuses.
Does NOT include Shunts.
Does NOT include a Return Busbar.
1200A Maximum Capacity.
Restrictions
Cannot be used with List 21. Must be installed in top row only (limit one battery disconnect panel per distribution cabinet). Maximum lug width, 1.75 inches.
Ordering Notes
1) Order fuses as required per Table 15. Order replacement alarm fuses (1/4A) per Table 17.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
3) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 45 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Bat
ter
y
Conne
cti
ons
BATTERY CONNECTIONS 3
/8-
16 Captive Nuts on 1” Cen
ter
s Maximum Lug Width: 1.7
5 inc
hes.
(Cu
stomer must supply
or or
der additional
har
dwa
re)
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

List BH: Battery Disconnect Distribution Panel, (4) TPH Fuse Battery Disconnect Positions (with Shunts) (without Return Busbar)

Features
(4) -48V Battery Disconnect Fuse Mounting Positions:
70A to 400A TPH Type Fuses.
Includes Shunts, 600A / 25mV. Each shunt is equipped with 10’ jumpers for connection to monitoring
device. If the system is equipped with an SM-DU+, the leads are trimmed and connected to the SM-DU+ (internal to the distribution cabinet).
Does NOT include a Return Busbar.
1200A Maximum Capacity.
Restrictions
Cannot be used with List 21. Must be installed in top row only (limit one battery disconnect panel per distribution cabinet). Maximum lug width, 1.75 inches.
Ordering Notes
1) Order fuses as required per Table 15. Order replacement alarm fuses (1/4A) per Table 17.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 28.
3) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Page 46 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
L
oa
d a
n
d/or Battery
Return Connectio
ns
LO
A
D A
N
D/
OR
B
A
T
T
E
RY
RE
T
URN CONNECTION
S
3/8-16
Cap
tiv
e Nut
s on 1”
Ce
n
te
rs
(C
us
t
ome
r mu
st s
upp
ly or
ord
er a
ddit
i
on
a
l h
ar
dw
are
)
Ma
ximu
m Lu
g Wi
dth
: 1
.
38
inc
hes
.
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Return Bar Panel

List GA: Return Bar Panel

Features
Return bar panel for use with distribution panels when internal load returns are required.
1200A Maximum Capacity.
Restrictions
Cannot be used in a 1- row distribution cabinet. Can be installed in any row 1-4 of a 2-, 3-, or 4-row distribution cabinet. Maximum lug width, 1.38 inches.
Ordering Notes
1) Specify row for panel location(s).
2) To terminate load and/or battery returns within the distribution cabinet, order List GA as required.
3) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 47 of 125
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Battery Disconnect Contactors

List CA: 600A Battery Disconnect Contactor

Features
Provides a battery disconnect contactor which is mounted within the main bay distribution cabinet.
Restrictions
Main bay only. Must be used with List 90. Must be used with List LB, MB, or both. For use with List 21 only. Can only use LVLD or LVBD on List 21, not both.
Ordering Notes
1) Order as required.

List CB: 1200A Battery Disconnect Contactor

Features
Provides a battery disconnect contactor which is mounted within the main bay distribution cabinet.
Restrictions
Main bay only. Must be used with List LB, MB, or both. For use with List 22, 23, or 24 only. If used in List 23 or 24, system capacity is reduced to 1200A.
Ordering Notes
1) Order as required.

List CC: 2000A Battery Disconnect Contactor

Features
Provides a battery disconnect contactor which is mounted within the main bay distribution cabinet.
Restrictions
Main bay only. Must be used with List LB, MB, or both. For use with List 22, 23, or 24 only.
Ordering Notes
1) Order as required.
Page 48 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Low Voltage Disconnect Options

List LB: Low Voltage Battery Disconnect (LVBD)

Features
Adds Low Voltage Battery Disconnect (LVBD) to the system.
Adds LVD Driver circuit card P/N 540972 or LVD Driver Lite circuit card P/N 547873 to the main bay
distribution cabinet.
Restrictions
Must be used with List CA, CB, or CC. Installed in main bay only.
Ordering Notes
1) Order if low voltage battery disconnect (LVBD) is required.
2) Can be combined with manual battery disconnect (List MB) if required.

List LL: Low Voltage Load Disconnect (LVLD)

Features
Adds low voltage load disconnect (LVLD) to a distribution panel.
Adds LVD Driver circuit card P/N 540972 (main bay) / 547702 (supplemental bay) or LVD Driver Lite
circuit card P/N 547873 (main bay) / 547874 (supplemental bay) to a distribution cabinet, one per distribution cabinet.
Restrictions
Must be used with List AA through AK and DA through DD.
Ordering Notes
1) Order low voltage load disconnect (LVLD) per load distribution panel (one per row) as required. Specify by row.

Manual Battery Disconnect Option

List MB: Manual Battery Disconnect

Features
Adds manual battery disconnect to the system.
Adds manual disconnect circuit card P/N 540973 to the system.
Restrictions
Must be used with List CA, CB, or CC. Installed in main bay only.
Ordering Notes
1) Order if manual battery disconnect is required.
2) Can be combined with low voltage battery disconnect (List LB) if required.
Page 49 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
ACCESSORY DESCRIPTIONS ACU+ (Advanced Control Unit Plus) Controller, P/N 1M820DNA
Features
Provides one (1) Model M820DNA, Spec. No. 1M820DNA system controller.
Factory programmed with the configuration file required for the system
configuration ordered.
Note: For custom ACU+ configurations, contact Emerson.
Restrictions
Only one (1) controller per power system is required. Mounts in the main bay (List 1) distribution cabinet. Cannot be installed in a List 2, List 3, List 5, or List 6 supplemental bay.
Ordering Notes
1) Order one (1) ACU+ controller (P/N 1M820DNA) per power system.
2) Order optional ACU+ EIB (ACU+ Extended Interface Board) as required, P/N 548120.
3) Order optional SM-DU+ Shunt Monitoring (P/N 548078) for any fuse panel with shunts (Lists AF, AH, AK, BF, or BH) or any GJ/218 panels (Lists AC, AD, BC, or BD) that are equipped with shunted breakers. (The SM-DU+ is factory-wired to the shunts.)
4) Order up to four (4) optional temperature probes for ambient and battery temperature monitoring, as required. The temperature probe(s) may also be used for the battery charge temperature compensation feature and BTRM (Battery Thermal Runaway Management). Refer to “Optional Temperature Probes” for additional information.
5) Order optional supervisory modules as desired (shipped loose).
SM-TEMP (Supervisory Module for Temperature Probes).
Note: A system can have up to (8) SM-Temp modules for a total of sixty-eight (68) temperature
probes that can be used in the power system for ambient and battery monitoring.

Optional ACU+ EIB (Extended Interface Board), P/N 548120

Features
Provides additional connection points for temperature probes, voltage and current
inputs, and programmable relay outputs.
The base system contains interface board IB2 which provides eight (8)
programmable form C- relay outputs, eight (8) programmable binary inputs, and two (2) temperature inputs. The EIB option provides five (5) programmable form-C relay outputs, two (2) temperature inputs, three (3) shunt inputs. and eight (8) battery midpoint inputs.
Restrictions
Only one (1) EIB per power system. Must be installed in the main bay.
Ordering Notes
1) Order by P/N 548120 as required. Must be ordered if ordering converters. Also order up to two (2) additional temperature probes, as desired. See “Optional Temperature Probes”.
Page 50 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Optional SM-DU+ Shunt Monitoring, P/N 548078

Features
Provides twenty-five (25) shunt monitoring inputs.
Ordering Notes
1) Order optional SM-DU+ Shunt Monitoring for any fuse panel with shunts (Lists AF, AH, AK, BF, or BH) or any GJ/218 panels (Lists AC, AD, BC, or BD) that are equipped with shunted breakers. (The SM-DU+ is factory-wired to the shunts.) Order by P/N 548078 as required.

Optional Temperature Probes

Features
Up to two (2) temperature probes can be connected to the IB2 (ACU+ Interface Board). Up to two (2)
additional temperature probes can be connected to the optional EIB (ACU+ Extended Interface Board). Any combination of the four (4) temperature probes can be programmed to monitor ambient temperature and/or battery temperature. A temperature probe set to monitor battery temperature can also be used for the rectifier battery charge temperature compensation feature, or the battery charge temperature compensation feature can be programmed to use the average or highest value of all battery temperature probes. The battery charge temperature compensation feature allows the controller to automatically increase or decrease the output voltage of the system to maintain battery float current as battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. A temperature probe set to monitor battery temperature can also be used for the BTRM (Battery Thermal Runaway Management) feature. The BTRM feature lowers output voltage when a high temperature condition exists to control against battery thermal runaway.
The temperature sensor end of the probe contains a tab with a 5/16” clearance hole for mounting.
Temperature probes can also be used with the optional SM-Temp Temperature Concentrator.
Restrictions
A temperature probe programmed to monitor battery temperature should be mounted on the negative post of a battery cell to sense battery temperature. A temperature probe used for battery charge temperature compensation or BTRM (Battery Thermal Runaway Management) should also be mounted on the negative post of a battery cell. A temperature probe programmed to monitor ambient temperature should be mounted in a convenient location, away from direct sources of heat or cold.
Ordering Notes
1) Order temperature probes as required. Note that each temperature probe consists of two pieces which plug together to make a complete probe (see the following illustration). For a complete temperature probe, order one (1) P/N 552992 (10.3 meters) or one (1) P/N 556155 (3.3 meters). If additional length is required, order temperature probe extension cable P/N 04119122 (10 meters).
2) If more probes are desired, order one or more SM-Temp Temperature Concentrator, P/N 547490. See SM-Temp Temperature Concentrator.
Page 51 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Tem
p P
rob
e Kits
P/N 552992
(inclu
des P
/Ns 552822 and 55282
3)
P/N 556155 (inc
lude
s P/Ns 5
5282
2 and 556154)
t
o
AC
U+Con
tr
o
ll
e
r
I
nt
er
f
ac
e B
o
ar
d
P/
N
55
2
82
3 (
1
0 m
et
e
r l
en
g
th
,
a
p
pr
o
x.33fe
e
t)
T
em
p P
r
ob
e
C
ont
roll
er S
ide
Cable or P/N 556154 (3 mete
r length, approx. 10 feet) Temp Probe C
ontroller Side Cable
P/
N 0
4
11
91
2
2
(1
0
me
te
r
le
ng
t
h,
approx. 3
3 f
e
et
)
optional Temp Pr
o
be
E
x
te
ns
i
on
Cable
P/N
552
822
(0.3 meter leng
th,
a
pprox. 1 feet)
Tem
p Pr
obe
with
Sho
rt Ca
ble
t
o T
em
p
Pr
o
be
or Temp Prob
e E
x
te
ns
i
on
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Optional SM-Temp Temperature Concentrator, P/N 547490

Features
Allows for multiple temperature probes to be used for ambient
temperature monitoring, battery temperature monitoring, temperature compensation, and/or BTRM (Battery Thermal Runaway Management).
Provides (8) temperature probe inputs per SM-Temp.
Can cascade up to (8) SM-Temp modules, connecting up to sixty-four
(64) temperature probes.
The SM-Temp Concentrator is connected at the end of the ACU+ CAN bus. Via the CAN Bus, the ACU+
reads each temperature probe from each SM-Temp Concentrator.
Restrictions
Requires ACU+ version 3.02 or later when SM-Temp is connected into the ACU+ CAN bus.
Ordering Notes
1) Order SM-Temp Temperature Concentrator, P/N 547490, as required.
2) Order up to (8) temperature probes for each concentrator. See “Optional Temperature Probe” above.
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 52 of 125
System Application Guide SAG582127000
Home Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Rectifiers

Rectifier Module, P/N 1R483500E

Features
Provides one (1) Model R48-3500e, Spec. No. 1R483500E,
3500 watt / -48 volt rectifier module.
Refer to the Rectifier Instructions (UM1R483500E) for more information.
Restrictions
For use in Spec. No. 58870500021, 58870500022, 58870500031, 58870500032 rectifier module mounting shelf.
Ordering Notes
1) Order by P/N 1R483500E as required. Each Spec. No. 588705000 rectifier module mounting shelf holds up to six (6) rectifier modules.

Rectifier Module, P/N 1R483200E

Features
Provides one (1) Model R48-3200e, Spec. No. 1R483200E,
3200 watt / -48 volt rectifier module.
Refer to the Rectifier Instructions (UM1R483500E) for more information.
Restrictions
For use in Spec. No. 58870500021, 58870500022, 58870500031, 58870500032 rectifier module mounting shelf.
Ordering Notes
1) Order by P/N 1R483200E as required. Each Spec. No. 588705000 rectifier module mounting shelf holds up to six (6) rectifier modules.

Rectifier Module, P/N 1R483200

Features
Provides one (1) Model R48-3200, Spec. No. 1R483200,
3200 watt / -48 volt rectifier module.
Refer to the Rectifier Instructions (UM1R483500E) for more information.
Restrictions
For use in Spec. No. 58870500021, 58870500022, 58870500031, 58870500032 rectifier module mounting shelf.
Ordering Notes
1) Order by P/N 1R483200 as required. Each Spec. No. 588705000 rectifier module mounting shelf holds up to six (6) rectifier modules.

Rectifier Module, P/N 1R482000E3

Features
Provides one (1) Model R48-2000e3, Spec. No. 1R482000E3,
2000 watt / -48 volt rectifier module.
Refer to the Rectifier Instructions (UM1R482000E3) for more information.
Restrictions
For use in Spec. No. 588705300 module mounting shelf.
Page 53 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Ordering Notes
1) Order by P/N 1R482000E3 as required. Each Spec. No. 588705300 module mounting shelf holds up to six (6) rectifier modules.

Converters

DC-DC Converter Module, P/N 1C400483500E

Features
Provides one (1) Model C400/48-3500e, Spec. No. 1C400483500E,
3500 watt / 400 to -48 volt DC-DC converter module.
Refer to the Converter Instructions (UM1C400483500E) for more
information.
Restrictions
For use in Spec. No. 58870500040, 58870500041, 58870500042 module mounting shelf.
Ordering Notes
1) Order by P/N 1C400483500E as required. Each Spec. No. 588705000 module mounting shelf holds up to six (6) converter modules.

DC-DC Converter Module, P/N 1C48241500

Features
Provides one (1) Model C48/24-1500, Spec. No. 1C48241500, 1500 watt
/ -48V to +24V converter module.
Refer to the Converter Instructions (UM1C48241500) for more
information.
Restrictions
For use in Spec. No. 588705300 module mounting shelf. Converters can be installed in main bay only. Must be used with List 60.
Ordering Notes
1) Order by P/N 1C48241500 as required. Each Spec. No. 588705300 module mounting shelf holds up to three (3) converter modules (far right three mounting positions as viewed from the front).

Module Mounting Position Blank Cover Panel, P/N 21140440

Features
Covers one (1) unused module mounting position.
Restrictions
For use in Spec. No. 588705000 module mounting shelf.
Ordering Notes
1) Order by P/N 21140440 as required. Order a module mounting position blank cover panel for each empty module mounting position in the system, as desired.
Page 54 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
For Use w/ (1)
Rectifier/Converter Shelf
For Use w/ (2
Rectifier/Converter Shelves
For Use w/ (3)
Rectifier/Converter Shelves
For Use w/ (4)
Rectifier/Converter Shelves
For Use w/ (5)
Rectifier/Converter Shelves
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Converter Interface Components (for Spec. No. 588705300)

Features
Provides components to interface
converters in Spec. No. 588705300 module mounting shelves to the distribution cabinet.
Restrictions
Must be used in systems equipped with Spec. No. 588705300 module mounting shelves.
Must be installed in main bay only.
Must be used in conjunction with a dual voltage bus distribution panel.
Ordering Notes
1) Order the components listed in Table 1 to add converter capability to a system in the field that was not originally ordered with the List 60 Converter Option.
2) Order up to three (3) converter modules, P/N 1C48241500, per module mounting shelf.
Component Part Number Quantity
Converter Jumper 556228
555264 when there are five (5) rectifier/converter shelves in the system.
Order one (1) per rectifier/converter shelf in the system, up to a maximum of four (4).
555730 when there are four (4) rectifier/converter shelves in the system.
555733 when there are
+24V Busbar
three (3) rectifier/converter
Order one (1) from the part numbers listed.
shelves in the system.
555736 when there are two (2) rectifier/converter shelves in the system.
555739 when there are one (1) rectifier/converter shelves in the system.
1/4-20 x 3/4” Bolt 227640400 Order two (2) per converter jumper ordered.
1/4-20 x 1” Bolt 227640600 Order two (2) per converter jumper ordered.
1/4” Flat Washer 214110100 Order six (6) per converter jumper ordered.
1/4” Lock Washer 215111100 Order four (4) per converter jumper ordered.
1/4-20 Nut 228557100 Order two (2) per converter jumper ordered.
Table 1
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 55 of 125
SAG582127000 System Application Guide
543159
21.625”H x 24.376”W x 15”D
11RU
Seismic (Notes 1 and 2)
543151
25.656”H x 24.376”W x 15”D
13RU
Seismic (Notes 1 and 2)
543154
39.656”H x 24.376”W x 15”D
21RU
Seismic (Notes 1 and 2)
543155
43.156”H x 24.376”W x 15”D
23RU
Seismic (Notes 1 and 2)
543161
72.000”H x 24.375”W x 15”D
37RU
Welded
543162
84.000”H x 24.375”W x 15”D
45RU
Welded
543163
90.000”H x 24.375”W x 15”D
48RU
Welded
543164
96.000”H x 24.375”W x 15”D
51RU
Welded
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Relay Racks and Shipping Brackets

Features
The system is factory mounted to the relay rack or shipping brackets specified when ordered.
Relay racks (except P/N 541340) are 23” standard mounting with 3” deep uprights.
P/N 541340 is 23” standard mounting with 6” deep upright.
When ordered with shipping brackets, the system is mounted on shipping brackets bolted to a shipping
skid. The shipping brackets can mount a system up to 22U high.
Ordering Notes
1) Order from relay racks and shipping brackets listed in Table 2.
Part
Number
509638 509639
Size
Shipping Brackets 22RU --
Available Mounting
Positions (1RU = 1-3/4”)
Notes
543152 27.406”H x 24.376”W x 15”D 14RU Seismic (Notes 1 and 2)
543153 36.156”H x 24.376”W x 15”D 19RU Seismic (Notes 1 and 2)
543156 51.906”H x 24.376”W x 15”D 28RU Welded
543157 71.156”H x 24.376”W x 15”D 39RU Welded
541340 84.000”H x 25.800”W x 18”D 45RU Seismic (Notes 1 and 2)
547862 85.750”H x 24.375”W x 15”D 46RU Welded
Note 1: Complies with Bellcore Seismic Zone 4 requirements. Note 2: Seismic (Zone 4) compliant ONLY when system DOES NOT contain any of the
following components: List 93 Battery Tray.
Table 2
Available Relay Racks and Shipping Brackets
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 56 of 125
System Application Guide SAG582127000
Tra
ns
i
ti
on
Pl
at
e
s
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Transition Plates to Mount Relay Rack on Top of GNB Absolyte IIP Batteries

Features
Transition Plate Kits can be ordered to mount relay rack P/Ns 543151, 543152, 543153, 543154, 543155,
or 543156 on top of GNB Absolyte IIP batteries.
Each kit consists of two transition plates with three hole patterns and hardware (3/8") to mount the plates
to the above listed relay racks. Customer must supply hardware to mount the transition plates to the battery.
Restrictions
Used with relay rack P/Ns 543151, 543152, 543153, 543154, 543155, or 543156 only.
Ordering Notes
1) Order P/N 509819 for a Transition Plate Kit to mount relay rack on top of a GNB 3-100A19, GNB 3-100A27, or GNB 3-100A33 battery.
2) Order P/N 514596 for a Transition Plate Kit to mount relay rack on top of a GNB 6-90A09 battery.
3) Order P/N 514880 for a Transition Plate Kit to mount relay rack on top of a GNB 3-100A21, GNB 3-100A25, or GNB 3-100A31 battery.
Page 57 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
C&D
TEL12-160F
140456
157
4.95 x 22.01 x 11.14
7
115
528236
528237
C&D
TEL12-180F
--
181
4.95 x 22.01 x 12.60
8
131
528236
528237
C&D
TEL12-210F
554579
202
4.90 x 22.00 x 12.80
8
132
528236
528237
Deka
12AVR-170ET
541381
170
4.91 x 22.16 x 12.60
8
120
528234
528235
Deka
HR5500ET
--
152
4.90 x 22.00 x 11.75
8
120
528234
528235
Douglas
DSN12-170F
127691
171
4.92 x 22.05 x 12.60
8
129.6
528234
528235
Enersys
12TX105F
--
100
4.90 x 22.10 x 9.30
6
105.8
528234
528235
Enersys
12V100F
--
100
4.90 x 22.00 x 9.00
6
104.7
528234
528235
Enersys
12V170F
--
170
4.90 x 22.10 x 12.40
8
147.7
528234
528235
Enersys
12VX100F
--
100
4.90 x 22.00 x 9.00
6
104.7
528234
528235
Enersys
SBS 170F
--
170
4.90 x 22.10 x 11.10
7
115.7
528234
528235
FIAMM
12FAT100
--
100
4.96 x 21.97 x 9.06
6
90.39
528234
528235
FIAMM
12UMTX100FT
--
100
4.96 x 21.97 x 9.06
6
83.6
528234
528235
FIAMM
12UMTX140FT
--
140
4.96 x 21.97 x 10.67
7
110
528234
528235
FIAMM
12UMTX170FT
--
170
4.96 x 21.97 x 12.64
8
132
528234
528235
FIAMM
12UMTX180FT
--
180
4.96 x 21.97 x 12.64
8
134
528234
528235
GNB
M12V155FT
112795
155
4.88 x 22.01 x 11.14
7
118.4
528234
528235
Northstar
NSB12-600FT
--
(600W)
4.90 x 22.10 x 12.60
8
131.2
528234
528235
Northstar
NSB170FT
126111
171
4.92 x 22.05 x 12.60
8
131.2
528234
528235
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Batteries

Restrictions
For use in List 93 battery trays.
Ordering Notes
1) Order batteries from Table 3, as required.
Dimension
Manufacturer* Manufacturer P/N
C&D TEL12-105F 514368 100 4.94 x 22.51 x 9.00 6 84.9 528234 528235
Deka 12AVR-150ET 122018 150 4.90 x 22.00 x 11.75 8 115 528234 528235
Douglas DSN12-110F -- 110 4.92 x 22.05 x 8.94 6 86.4 528234 528235
Douglas DST12-170F -- 170 4.96 x 21.97 x 12.64 8 132 528234 528235
Enersys 12V155FS 122010 155 4.90 x 22.10 x 11.10 7 125.6 528234 528235
Enersys 12VF105F -- 107 4.90 x 22.10 x 9.30 6 101.4 528234 528235
Enersys SBS 190F -- 190 4.90 x 22.10 x 12.40 8 132.3 528234 528235
FIAMM 12FAT125 -- 125 4.96 x 21.97 x 10.67 7 110.23 528234 528235
FIAMM 12FAT155 -- 155 4.96 x 21.97 x 12.64 8 132.28 528234 528235
Emerson P/N (12V Module)
Capacity
(A-Hr)
W x L x H
(Inches)
(per 12V Module)
Min
Tray
Spacing
(RU)
Weight
(lb) (per 12V Module)
Lug Kit
2AW G
Lug Kit
1/0AW G
Northstar NSB110FT -- 110 4.92 x 22.05 x 8.94 6 91.3 528234 528235
Northstar NSB155FT -- 148 4.92 x 22.05 x 11.14 7 131.2 528234 528235
* See Battery Manufacturer Information
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
FIAMM 12UMTX110FT -- 110 4.96 x 21.97 x 9.06 6 90.39 528234 528235
FIAMM 12UMTX155FT -- 155 4.96 x 21.97 x 12.64 8 129.8 528234 528235
GNB M12V125FT 123617 125 4.88 x 22.01 x 11.14 7 104.7 528234 528235
GNB M12V180FT -- 180 4.88 x 22.01 x 12.50 8 133 528234 528235
Table 3
Batteries and Battery Lug Kits
Page 58 of 125
System Application Guide SAG582127000
50
256694300
60
256694700
70
256695100
75
256695500
100
256695900
125
100762
150
100763
200
121810
condition.
528500
Single Pole, Right Side Mounted
528501
Single Pole, Left Side Mounted
528502
Double Pole, Right Side Mounted
528503
Double Pole, Left Side Mounted
Optional Circuit
Breaker Guard
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Optional Battery Tray Battery Disconnect Circuit Breaker and Housing Kits

Features
Provides a battery disconnect circuit breaker
housing factory mounted on the left or right side of the List 93 battery tray. Selected circuit breaker factory installed and wired.
Restrictions
For use in List 93 battery trays. Factory wires battery trays with 2AWG cables for
battery disconnect circuit breaker selected up to 100A and 1/0AWG cables for circuit breaker selected over 100A.
Ordering Notes
1) For each battery tray, order one (1) circuit breaker from Table 4.
2) For each double-pole circuit breaker ordered, order an optional circuit breaker guard P/N 548014, if desired, to block front access to circuit breaker handle.
3) For each battery tray ordered, order one (1) battery circuit breaker housing kit from Table 5.
Ampere
Rating
Electrical/Mechanical Trip
P/N
(Black Handle)
1
No. of Poles
1-Pole
2-Pole
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip
Table 4
Battery Tray Battery Disconnect Circuit Breakers
Part Number Description
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Table 5
Battery Tray Battery Disconnect Circuit Breaker Housing Kits
Page 59 of 125
SAG582127000 System Application Guide
Optional Battery Cover
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Optional Battery Tray Front Battery Cover Kits

Features
Provides a front battery cover to the List 93
battery tray.
Restrictions
For use in List 93 battery trays.
Ordering Notes
1) Order one (1) kit per tray from Table 6, as required.
Part Number Height
548020 8U
548021 7U
548022 6U
Table 6
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 60 of 125
System Application Guide SAG582127000
14-10 AWG
245342300
8 AWG
245390200
6 AWG
245346700
4 AWG
245346800
2 AWG
245346900
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Crimp Lugs

Standard Crimp Lug Tables

Lead Size Part Number
Table 7
Crimp Lug
Two-Hole, 1/4” Bolt Clearance Hole, 5/8” Centers
Lead Size Part Number
6 AWG 245349900
4 AWG 245350000
2 AWG 245348200
1/0 AWG 245347100
2/0 AWG 245347200
3/0 AWG 245347300
4/0 AWG 245347400
250 kcmil 245347500
300 kcmil 245347600
350 kcmil 245347700
400 kcmil 245347800
500 kcmil 245347900
600 kcmil 245348000
750 kcmil 245348100
Table 8
Crimp Lug
Two-Hole, 3/8” Bolt Clearance Hole, 1” Centers
Page 61 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
1/0 AWG
245393500
2/0 AWG
245393600
3/0 AWG
245393700
4/0 AWG
245393800
250 kcmil
514872
350 kcmil
514873
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Special Application Crimp Lug / Strap Combination Table

Features
Straps two fuseholder/circuit breaker wiring positions together, and provides a crimp-type lug which
allows distribution wiring up to 350 kcmil size (maximum size of wire to be connected to a single position is 2 AWG). Designed for use with 125A and larger bullet nose-type circuit breakers or TPS/TLS-type fuses, which require at least two mounting positions.
Restrictions
If used with bullet nose-type circuit breakers or TPS/TLS-type fuses smaller than 125A, an empty mounting position is required adjacent to the distribution device.
Ordering Notes
1) Specify part number from Table 9 for desired lead size.
Lead Size Part Number
Table 9
Special Application Crimp Lug / Strap Combination
(Two-Hole Lug, 1/4” Bolt Clearance Hole, 5/8” Centers)
Page 62 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Lug Adapters

Busbar for 125A, 150A, and 200A Bullet Nose Type Circuit Breaker, P/N 520989

Features
Provides a busbar that mounts on the two lug landing positions of a 125A, 150A, or 200A
bullet nose circuit breaker, and allows for use of one standard two-hole lug having 1/4" bolt clearance holes on 5/8" centers.
Ordering Notes
1) Order one (1) Part No. 520989 per 125A, 150A, and 200A bullet nose circuit breaker ordered, as desired. See also P/Ns 522786 and 534449 in this section.

Busbar for 125A, 150A, and 200A Bullet Nose Type Circuit Breaker, P/N 522786

Features
Provides a busbar that mounts on the two lug landing positions of a 125A, 150A, or 200A
bullet nose circuit breaker, and provides a landing for one standard two-hole lug having 3/8" bolt clearance holes on 1" centers.
Ordering Notes
1) Order one (1) Part No. 522786 per 125A, 150A, and 200A bullet nose circuit breaker ordered, as desired. See also P/Ns 520989 and 534449 in this section.

Lug Adapter Busbar Kit for 125A, 150A, and 200A Bullet Nose Type Circuit Breaker, P/N 534449

Features
Includes one (1) busbar that mounts on the two lug landing positions of a 125A, 150A, or
200A bullet nose circuit breaker, and provides a landing for one standard two-hole lug having 3/8" bolt clearance holes on 1" centers. Also includes one (1) busbar that mounts on two landings of the associated ground return bar (if furnished), and provides one landing for a standard two-hole lug having 3/8" bolt clearance holes on 1" centers. All busbar and lug mounting hardware is included.
Ordering Notes
1) Order one (1) Part No. 534449 per 125A, 150A, and 200A bullet nose circuit breaker ordered, as desired. See also P/Ns 520989 and 522786 in this section.

Busbar for 250A Bullet Nose Type Circuit Breaker, P/N 514717

Features
Provides a busbar that mounts on the three lug landing positions of a 250A bullet nose
circuit breaker, and allows for use of a Special Application Crimp Lug / Strap Combination lug listed in Table 9.
Ordering Notes
1) Order one (1) P/N 514717 per 250A bullet nose circuit breaker ordered, as desired (see also Lug Adapter Busbar Kit for 250A Bullet Nose Type Circuit Breaker, P/N 514714 for another option).
Page 63 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Lug Adapter Busbar Kit for 250A Bullet Nose Type Circuit Breaker, P/N 514714

Features
Includes one (1) busbar that mounts on the three lug landing positions of a 250A bullet
nose circuit breaker, and provides one landing for a standard two-hole lug having 3/8" bolt clearance holes on 1" centers. Also includes one (1) busbar that mounts on three landings of the associated ground return bar (if furnished), and provides one landing for a standard two-hole lug having 3/8" bolt clearance Holes on 1" centers. All busbar and lug mounting hardware is included.
Ordering Notes
1) Order one (1) Part No. 514714 per 250A bullet nose circuit breaker ordered, as desired (see also Busbar for 250A Bullet Nose Type Circuit Breaker, P/N 514717 for another option).

Lug Hardware Kits

1/4-20 Hardware Kit, P/N 541084

Features
Lug hardware kit provides thirty-two (32) sets of 1/4-20 hardware for bullet nose distribution panels. Kit
includes (32) 1/4-20 Nuts, (32) 1/4" Flat Washers, and (32) 1/4" Lock Washers.
Ordering Notes
1) Order Kit P/N 541084, as required.

3/8-16 Hardware Kit, P/N 548184

Features
Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware for GJ/218 distribution panels, TPH
distribution panels, return bar panels, and battery busbars. Kit includes (16) 3/8-16 x 1-1/4" Bolts, (16) 3/8" Flat Washers, and (16) 3/8" Lock Washers.
Ordering Notes
1) Order Kit P/N 548184, as required.

3/8-16 Hardware Kit, P/N 548185

Features
Lug hardware kit provides sixteen (16) sets of 3/8-16 hardware for TPL-B distribution panels. Kit includes
(16) 3/8-16 Nuts, (16) 3/8" Flat Washers, and (16) 3/8" Lock Washers.
Ordering Notes
1) Order Kit P/N 548185, as required.
Page 64 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Battery Busbar Extension Kit (P/N 554541)

Features
Provides busbar extension plates and mounting hardware for extending battery
busbars through the top of a distribution cabinet. Each busbar extension plate provides three pairs of clearance holes for 3/8” hardware on 1” centers. Allows back-to-back lug landing for up to six lugs per polarity. See "Battery Input Illustrations" on page 104.
Ordering Notes
1) Order one (1) kit P/N 554541 per bay, as required.

Battery Landing Busbar Kit (P/N 553584)

Features
Provides a Battery Landing Busbar Kit that attaches to the distribution cabinet’s
battery busbars and hangs off the back of the cabinet. Six (6) battery landing positions are provided (per polarity) (1/4-20 x 0.875” studs on 0.625” centers). See "Battery Input Illustrations" on page 104.
Restrictions
For use with List 21. CANNOT be used with List 2 or List 3.
Ordering Notes
1) Order one (1) kit P/N 553584 per bay, as required.

Battery Landing Busbar Kit (P/N 555478)

Features
Provides a Battery Landing Busbar Kit that attaches to the distribution
cabinet’s battery busbars and hangs off the back of the cabinet. Four (4) battery landing positions are provided (per polarity) for connection of up to eight (8) battery leads (back-to-back) (per polarity) (1/4-20 x 0.875” studs on 0.625” centers). See "Battery Input Illustrations" on page 104.
Restrictions
For use with Lists 22, 23, and 24. CANNOT be used with List 2 or List 3.
Ordering Notes
1) Order one (1) kit P/N 555478 per bay, as required.
Page 65 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Distribution Devices

Bullet Nose Type Circuit Breakers and Bullet Nose Type Fuseholders e/w TPS/TLS Fuses

Features
Each circuit breaker (as listed in Table 10 and Table 11) plugs into one, two, or three mounting position(s)
on a distribution panel containing bullet nose type distribution positions.
A single fuseholder provides for installation of a 3A to 100A Bussmann TPS type or Littelfuse TLS type
fuse (as listed in Table 12). This fuseholder plugs into a single mounting position on a distribution panel containing bullet nose type distribution positions. This fuseholder provides a GMT-A alarm type fuse, which operates open to provide an alarm indication if the associated distribution fuse opens.
Restrictions
For use in Lists AA, AB, BA, BB, DA, DB, DC, and DD. Load should not exceed 80% of device rating. Install distribution devices from left to right, starting with the highest capacity and working to the lowest
capacity.
Caution: A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
Ordering Notes
1) Order circuit breakers as required per Table 10 or Table 11.
2) Order fuses as required per Table 12. For each fuse ordered, also order one (1) P/N 117201 bullet nose type fuseholder.
3) See Table 27 for recommended load distribution wire sizes and lugs.
4) When ordering 125A, 150A, 200A, or 250A circuit breakers; associated crimp lugs may be ordered from
Table 9.
When ordering 125A, 150A, or 200A circuit breakers; lug adapter busbar P/N 520989, lug adapter busbar P/N 522786, or lug adapter busbar kit P/N 534449 may be ordered per circuit breaker (see Lug Adapters in this section).
When ordering 250A circuit breakers; lug adapter busbar P/N 514714 or lug adapter busbar kit 514717 may be ordered per circuit breaker (see Lug Adapters in this section).
Page 66 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Toggle Handle
Bullet Nose Circuit Breaker
Bullet Nose Fuseholder Rocker Handle
Bullet Nose Circuit Breaker
Fuse Carrier
Fuseholder Body
TPS/TLS Fuse
Polarizing Keyway Matches Key on Bottom of Fuse Carrier
Bullet Nose Fuseholder Assembly Exploded View
Bullet Nose Fuseholder Assembly (P/N 117201) includes body & carrier, alarm fuse, and alarm fuse safety cover.
GMT-X
Safety Fuse Cover
(Replacement
P/N 248898700)
GMT-18/100A Alarm Fuse (Replacement P/N 248610301)
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 67 of 125
SAG582127000 System Application Guide
Home
1 1 1
102272
101596
3 1 1
102273
101597
5 1 1
102274
101598
10 1 1
102275
101599
15 1 1
102276
101600
20 1 1
102277
101601
25 1 1
102278
101602
30 1 1
102279
101603
35 1 1
102280
101604
40 1 1
102281
101605
45 1 1
121998
121997
50 1 1
102282
101606
60 1 1
102283
101607
70 1 1
102284
101608
75 1 1
102285
101609
80 1 1
121996
121995
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Part Number
Electrical/
Mechanical Trip
(Black Handle)
2
Ampere
Rating
Number of Poles
Number of
Mounting Positions Required
Electrical Trip1 (White Handle)
90 1 1 138887 138888
100 1 2 102286 101610
125 2 3 516991 516838
150 2 3 516993 516839
175 2 3 144883 144884
200 2 3 121831 121832
225 3 4 144885 144886
250 3 4 121835 121836
See Table 27 for recommended load distribution wire sizes and lugs.
When ordering 125A, 150A, 175A, 200A, 225A or 250A circuit breakers; associated crimp lugs may be ordered from Table 9.
When ordering 125A, 150A, 175A or 200A circuit breakers; lug adapter busbar kit P/N 520989, 522786, or 534449 may be ordered per circuit breaker (see Lug Adapters in this section).
When ordering 225A or 250A circuit breakers; lug adapter busbar kit P/N 514714 or 514717 may be ordered per circuit breaker (see Lug Adapters in this section).
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Note: Electrical Trip only circuit breakers are not typically used for battery
disconnect circuit breakers.
Table 10
Toggle Handle Bullet Nose Type Circuit Breakers
Page 68 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
1 1 1
142856
142878
3 1 1
142857
142879
5 1 1
142858
142880
10 1 1
142859
142881
15 1 1
142861
142882
20 1 1
142862
142883
25 1 1
142863
142884
30 1 1
142864
142885
35 1 1
142865
142886
40 1 1
142866
142887
45 1 1
142867
142888
50 1 1
142868
142889
60 1 1
142869
142890
70 1 1
142870
142891
75 1 1
142871
142892
80 1 1
142872
142901
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Ampere
Rating
Number
of Poles
Number of
Mounting Positions
Required
Part Number
Electrical Trip1 (White Handle)
Electrical/
Mechanical Trip
(Black Handle)
2
100 1 2 142873 142902
125 2 3 142874 142903
150 2 3 142875 142904
200 2 3 142876 142905
250 3 4 142877 142906
See Table 27 for recommended load distribution wire sizes and lugs.
When ordering 125A, 150A, 200A, or 250A circuit breakers; associated crimp lugs may be ordered from Table 9.
When ordering 125A, 150A, or 200A circuit breakers; lug adapter busbar kit P/N 520989, 522786, or 534449 may be ordered per circuit breaker (see Lug Adapters in this section).
When ordering 250A circuit breakers; lug adapter busbar kit P/N 514714 or 514717 may be ordered per circuit breaker (see Lug Adapters in this section).
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Note: Electrical Trip only circuit breakers are not typically used for battery
disconnect circuit breakers.
Table 11
Rocker Handle Bullet Nose Circuit Breakers
Page 69 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Ampere
Rating
Part
Number
Bussmann
P/N
3 248230900 TPS-3 TLS003
5 248231000 TPS-5 TLS005
6 248231200 TPS-6 TLS006
10 248231500 TPS-10 TLS010
15 248231800 TPS-15 TLS015
20 248232100 TPS-20 TLS020
25 248232400 TPS-25 TLS025
30 248232700 TPS-30 TLS030
40 248233300 TPS-40 TLS040
50 248233900 TPS-50 TLS050
60 248234200 TPS-60 TLS060
70 248234500 TPS-70 TLS070
80 118413 -- TLS080
90 118414 -- TLS090
100 118415 -- TLS100
P/N 117201 (Includes Fuseholder,
Bullet Nose Type Fuseholder
18/100A GMT-A Alarm Fuse, and GMT-X Safety Fuse Cover)
Littelfuse
P/N
See Table 27 for recommended load distribution wire sizes and lugs.
Table 12
Bullet Nose Type Fuseholders and TPS/TLS Fuses
Page 70 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Optional Bullet Nose Type 6-Position GMT Distribution Fuse Block, P/N 550224, (6) GMT Fuse Positions

Features
Provides six (6) load distribution fuse positions
(1/4A to 15A GMT alarm-type fuses).
Single voltage distribution (-48V or +24V).
Mounts in two (2) distribution positions of any “bullet nose” distribution panel.
Screw clamp type load and load return terminals provided.
Includes six (6) dummy fuses equipped with safety fuse covers.
Restrictions
Can be used in a List AA, AB, DA, DB, DC, and DD distribution panel only. Occupies two (2) bullet device mounting positions. Can only be installed in the 1-2, 3-4, 17-18, 19-20, 21-22, and 23-24 positions of the
distribution panel. Terminal block wire size capacity: 24 to 14 AWG. 35A maximum capacity per block. Maximum GMT fuse size is 15A.
Ordering Notes
1) Order optional Bullet Nose Type 6-Position GMT Fuse Block (P/N 550224) as required.
2) Order fuses as required per Table 13.
Page 71 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
18/100 (GMT-A)
248610301
---
1/4
248610200
VIOLET
1/2
248610300
RED
3/4
248610500
BROWN
1-1/3
248610700
WHITE
2
248610800
ORANGE
3
248610900
BLUE
5
248611000
GREEN
7-1/2
248611300
BLACK-WHITE
10
248611200
RED-WHITE
15
248611500
RED-BLUE
Replacement Replacement
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

GMT Type Load Distribution Fuses

Features
An optional “Bullet Nose Type 6-Position GMT Distribution Fuse Block, P/N 550224” is available for
additional load distribution.
Restrictions
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 amp fuses, for which load should not exceed 70% of device rating.
Ordering Notes
1) Order fuses as required per Table 13.
Ampere Rating Part Number Fuse Color
Safety Fuse
Cover (GMT-Y)
Dummy Fuse
102774 ---
248872600 ---
Table 13
GMT Fuses
Page 72 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
rated load) 3
100 1 256621700
256621300
503787
123580
516184
513731
125 1 256621600
256621400
503787
123631
516187
513731
150 1 256621800
256622400
503787
123632
516185
513731
175 1 256621900
256622500
503787
123633
516186
513731
200 1 256622200
256622600
503787
123634
516188
513731
225 1 256622900
256622700
503787
123635
516189
513731
250 1 256623500
256623400
503787
123636
516190
513731
300 2 256625300
103572
513961
550250
550253
554092
400 2 256626200
256626300
513961
550251
550254
554092
600 3 256628200
103571
513957
550252
550255
554093
800 4 121657
121658
554091
--
550249
554094
See Table 28 for recommended load distribution wire sizes and lugs.
Home
GJ/218 Circuit Breakers
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

GJ/218 Type Circuit Breakers

Restrictions
For use in Lists AC, AD, BC, and BD. Load should not exceed 80% of device rating. Refer to Table 14 for required distribution row
mounting positions.
Ordering Notes
1) Order circuit breakers as required per
Table 14.
2) Order a jumper kit as required for each circuit breaker per Table 14.
3) See Table 28 for recommended load distribution wire sizes and lugs.
P/N
Electrical/
with
Internal Shunt
(25mV @ full
P/N
Electrical Trip
with
Internal Shunt
(25mV @ full
rated load)
Ampere
Rating
No. of
Positions
P/N
Electrical/
Mechanical Trip1
without Internal
Shunt
P/N
Electrical Trip
without
Internal
Shunt
Breaker
2
Mounting
(without
Shunt)
Mechanical Trip1
Kit
2
3
Breaker
Mounting
Kit (with
Shunt)
1, 2
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
2
3
Extended shunt leads are 22 AWG stranded wire, approximately 7-10 ft. long from exit point at bottom of
Provides an alarm during an electrical trip condition only.
distribution cabinet. Each shunt lead is equipped with a 49.9 ohm current limiting resistor. Shunt leads are factory wired to SM-DU+ (if ordered).
Note: Electrical Trip only circuit breakers are not typically used for battery disconnect circuit breakers.
Table 14
GJ/218 Circuit Breakers
Page 73 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
70
119437
100
119440
150
119581
225
119583
250
119584
400
119586
500
119587
800
A7000199
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

TPH Type Fuses

Restrictions
For use in Lists AE, AF, AG, AH, BE, BF, BG, and BH. Load should not exceed 80% of device rating.
Ordering Notes
1) Order fuses as required per Table 15.
2) See Table 28 for recommended load distribution wire sizes and lugs.
Ampere Rating Part Number
80 119438
200 119582
300 119585
600 119588
See Table 28 for recommended load distribution wire sizes and lugs.
Table 15
TPH Fuses
Page 74 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
F
use
Case
Open Fuse Case View
TPL Fuse
Fuse Installed in Open
Fus
e Cas
e
(rea
r vie
w)
Fuse Installed in Clos
ed Fuse Case
(rear view)
Fuseb
lock
(P/N 516241)
GMT-18/100A Alarm Fuse
(P/N 248610301) and
GMT-X Safety Fuse Cover
(P/N 2
48
8
98700)
(Both are provided
w/ fuseblock)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

TPL-B Type Fuses

Restrictions
For use in Lists AJ and AK. Load should not exceed 80% of device rating.
Ordering Notes
1) Order fuses as required per Table 16.
2) See Table 28 for recommended load distribution wire sizes and lugs.
Ampere Rating Part Number
70 248251500
80 248252000
100 248252600
150 248253300
200 248254000
225 248254500
250 248255000
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
See Table 28 for recommended load distribution wire sizes and lugs.
Table 16
TPL-B Fuses
Page 75 of 125
SAG582127000 System Application Guide
(GMT-X)
FA
Fuse Alarm
18/100
Bussmann GMT-A
248610301
(GMT-X)
547873 (Main Bay) and
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

Replacement Alarm, Reference, and Control Fuses

Ordering Notes
1) Order replacement fuses as required per Table 17.
Assembly Desig. Function
Distribution Panel with
TPH Fuse Block(s)
FA Fuse Alarm 1/4 Bussmann GMT 248610200
-- -- --
TPS/TLS Fuseholders
(P/N 117201)
-- -- --
Size
(Amperes)
Type Part No.
Safety Fuse Cover
Safety Fuse Cover
(GMT-X)
248898700
248898700
FA Fuse Alarm 18/100 Bussmann GMT-A 248610301
TPL-B Fuseholders
-- -- --
Safety Fuse Cover
248898700
Table 17
Replaceable Alarm, Reference, and Control Fuses

Replacement Assemblies

Ordering Notes
1) Refer to the following table. Refer to the separate rectifier and converter descriptions in this section for their part numbers.
Item Part Number
ACU+ Controller 1M820DNA
SM-DU SMDU
System Interface Circuit Card 556166
ACU+ IB2 Interface Board MA4C5U31
ACU+ EIB Extended Interface Board 548120
SM-DU+ with Shunt Interface Board 548078
LVD Driver Circuit Card
540972 (Main Bay) and 547702 (Supplemental Bay)
LVD Driver Lite Circuit Card
Manual Battery Disconnect Circuit Card 540973

Replacement Bay-to-Bay Interconnect Cable

Ordering Notes
1) For a replacement cable, order P/N 514640 (25’ Cat5 communications cable terminated in RJ-45 connectors).
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
547874 (Supplemental Bay)
Page 76 of 125
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Wiring Illustrations and Notes

Relay Rack Frame Grounding Requirements

For relay rack grounding requirements, refer to the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NPFA) National Electrical Code (NEC), applicable local codes, and your specific site requirements.
A customer's grounding network lead can be attached to the top of each relay rack. Provision is made for installing a lead with a two-hole lug that has 1/4" bolt clearance holes on 5/8" centers. Refer to Table 7 for lug selection.
Page 77 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
208 VAC
17.3A
25A
(2)
10 AWG
3/4”
240 VAC
15.0A
20A
12 AWG
1/2”
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)

AC Input

AC Input Branch Circuit Protection and Wire Size Selection for AC Input Termination Assembly List 40, 41, 42 when used with 588705000 Module Mounting Shelves with Rectifiers (Nominal 208/240 Volts AC)
Refer to the following tables for recommended wire sizes and branch circuit protection.
AC INPUT TO LIST 40 AC INPUT TERMINATION ASSEMBLY
(Nominal 208/240 Volts AC, Single Phase, 50/60 Hz)
Provides “1 AC Feed per 1 Rectifier” Single Phase Input Terminations
(System with Spec. No. 588705000 Rectifier Shelves)
40°C Ambient
Temperature
(3) (4) (6)
Conduit
(7) (8)
Size
Input
Voltage
Input
Current
(5)
Overcurrent
Protection
(1)
Wire
1
The AC input branch circuit protective device should be of the time-delay or high inrush type.
2
Maximum over current protection device is 30A.
3
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
4
Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf. Frame
ground terminals must be connected to earth ground, not power system neutral. Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
5
Input current based on R48-3500e rectifier module.
6
THHN 90°C Wire.
7
System with Four (4) Spec. No. 588705000 Rectifier Shelves: Conduit sized for six (6) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for three (3) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
8
System with Five (5) Spec. No. 588705000 Rectifier Shelves / Shelf #6 is Expansion Shelf: Conduit sized for
eight (8) current carrying conductors and one (1) ground conductor per conduit (based on NEC recommendations), for four (4) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
Table 18
Recommended AC Input Branch Circuit Protection and Wire Size when Using
List 40 “1 AC Feed per 1 Rectifier – Single Phase” AC Input Termination Assembly,
System with Spec. No. 588705000 Rectifier Shelves
Page 78 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
(2)
(7) (8)
(7)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
AC INPUT TO LIST 41 AC INPUT TERMINATION ASSEMBLY
(Nominal 208/240 Volts AC, Single Phase, 50/60 Hz)
Provides “1 AC Feed per 2 Rectifiers” Single Phase Input Terminations
(System with Spec. No. 588705000 Rectifier Shelves)
40°C Ambient
Input
Voltage
Input
Current
(5)
Overcurrent
Protection
(1)
Wire
Temperature
(3) (4) (6)
Conduit
Size
208 VAC 34.6A 45A
240 VAC 30.0A 40A 8 AW G
1
The AC input branch circuit protective device should be of the time-delay or high inrush type.
2
Maximum over current protection device is 60A.
3
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
6 AWG 1”
3/4”
1”
(8)
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
4
Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf. Frame
ground terminals must be connected to earth ground, not power system neutral. Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
5
Input current based on R48-3500e rectifier module.
6
THHN 90°C Wire.
7
System with Four (4) Spec. No. 588705000 Rectifier Shelves: Conduit sized for four (4) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for four (4) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
8
System with Four (4) Spec. No. 588705000 Rectifier Shelves / Shelf #5 and #6 are Expansion Shelves: Conduit
sized for six (6) current carrying conductors and one (1) ground conductor per conduit (based on NEC recommendations), for six (6) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
Table 19
Recommended AC Input Branch Circuit Protection and Wire Size when Using
List 41 “1 AC Feed per 2 Rectifiers – Single Phase” AC Input Termination Assembly,
System with Spec. No. 588705000 Rectifier Shelves
Page 79 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
(2)
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
AC INPUT TO LIST 42 AC INPUT TERMINATION ASSEMBLY
(Nominal 208/240 Volts AC, Three Phase, 50/60 Hz)
Provides “1 AC Feed per 3 Rectifiers” 3 Phase Input Terminations
(System with Spec. No. 588705000 Rectifier Shelves)
40°C Ambient
Input
Voltage
Input
Current
(5)
Overcurrent
Protection
(1)
Wire
Temperature
(3) (4) (6)
Conduit
(7) (8)
Size
208 VAC 29.3A 40A 8 AW G 3/4”
240 VAC 25.5A 35A
1
The AC input branch circuit protective device should be of the time-delay or high inrush type.
2
Maximum over current protection device is 40A.
3
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
8 AWG 3/4”
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
4
Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf. Frame
ground terminals must be connected to earth ground, not power system neutral. Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
5
Input current based on R48-3500e rectifier module.
6
THHN 90°C Wire.
7
System with Four (4) Spec. No. 588705000 Rectifier Shelves: Conduit sized for three (3) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for three (3) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
8
System with Five (5) Spec. No. 588705000 Rectifier Shelves / Shelf #6 is Expansion Shelf: Conduit sized for six
(6) current carrying conductors and one (1) ground conductor per conduit (based on NEC recommendations), for six (6) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
Table 20
Recommended AC Input Branch Circuit Protection and Wire Size when Using
List 42 “1 AC Feed per 3 Rectifiers – Three Phase” AC Input Termination Assembly,
System with Spec. No. 588705000 Rectifier Shelves
Page 80 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
AC Input Branch Circuit Protection and Wire Size Selection for AC Input Termination Assembly List 40, 41, 42 when used with 588705300 Module Mounting Shelves with Rectifiers (Nominal 208/240 Volts AC)
Refer to the following tables for recommended wire sizes and branch circuit protection.
AC INPUT TO LIST 40 AC INPUT TERMINATION ASSEMBLY
(Nominal 208/240 Volts AC, Single Phase, 50/60 Hz)
Provides “1 AC Feed per 1 Rectifier” Single Phase Input Terminations
(System with Spec. No. 588705300 Rectifier Shelves)
40°C Ambient
Input
Voltage
Input
Current
(7)
Overcurrent
Protection
(1)
Wire
Temperature
(2) (3) (4)
Conduit
(5) (6)
Size
208 VAC 10A 15A 14 AWG 3/4”
240 VAC 8.8A 15A 14 AWG 3/4”
1
The AC input branch circuit protective device should be of the time-delay or high inrush type.
2
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
3
Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf. Frame
ground terminals must be connected to earth ground, not power system neutral. Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
4
THHN 90°C Wire.
5
System with Four (4) Spec. No. 588705300 Rectifier Shelves: Conduit sized for twelve (12) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for six (6) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
6
System with Five (5) Spec. No. 588705300 Rectifier Shelves / Shelf #6 is Expansion Shelf: Conduit sized for six
(6) current carrying conductors and one (1) ground conductor per conduit (based on NEC recommendations), for six (6) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
7
Input current based on R48-2000e3 rectifier module.
Table 21
Recommended AC Input Branch Circuit Protection and Wire Size when Using
List 40 “1 AC Feed per 1 Rectifier – Single Phase” AC Input Termination Assembly,
System with Spec. No. 588705300 Rectifier Shelves
Page 81 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
(2)
(2)
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
AC INPUT TO LIST 41 AC INPUT TERMINATION ASSEMBLY
(Nominal 208/240 Volts AC, Single Phase, 50/60 Hz)
Provides “1 AC Feed per 2 Rectifiers” Single Phase Input Terminations
(System with Spec. No. 588705300 Rectifier Shelves)
40°C Ambient
Input
Voltage
Input
Current
(8)
Overcurrent
Protection
(1)
Wire
Temperature
(3) (4) (5)
Conduit
(6) (7)
Size
208 VAC 20A 25A
240 VAC 17.5A 25A
1
The AC input branch circuit protective device should be of the time-delay or high inrush type.
2
Maximum over current protection device is 30A.
3
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
10 AWG 3/4”
10 AWG 3/4”
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
4
Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf. Frame
ground terminals must be connected to earth ground, not power system neutral. Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
5
THHN 90°C Wire.
6
System with Four (4) Spec. No. 588705300 Rectifier Shelves: Conduit sized for four (4) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for four (4) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
7
System with Four (4) Spec. No. 588705300 Rectifier Shelves / Shelf #5 and #6 are Expansion Shelves: Conduit
sized for six (6) current carrying conductors and one (1) ground conductor per conduit (based on NEC recommendations), for six (6) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
8
Input current based on R48-2000e3 rectifier module.
Table 22
Recommended AC Input Branch Circuit Protection and Wire Size when Using
List 41 “1 AC Feed per 2 Rectifiers – Single Phase” AC Input Termination Assembly,
System with Spec. No. 588705300 Rectifier Shelves
Page 82 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
(6)
(2)
(6) (7)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
AC INPUT TO LIST 42 AC INPUT TERMINATION ASSEMBLY
(Nominal 208/240 Volts AC, Three Phase, 50/60 Hz)
Provides “1 AC Feed per 3 Rectifiers” 3 Phase Input Terminations
(System with Spec. No. 588705300 Rectifier Shelves)
40°C Ambient
Temperature
(3) (4) (5)
Conduit
Size
1/2”
(7)
3/4”
Input
Voltage
Input
Current
(8)
Overcurrent
Protection
208 VAC 17.5A 25A
(1)
Wire
(2)
10 AWG
240 VAC 15A 20A
1
The AC input branch circuit protective device should be of the time-delay or high inrush type.
2
Maximum over current protection device is 30A.
3
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
12 AWG 1/2”
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
4
Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf. Frame
ground terminals must be connected to earth ground, not power system neutral. Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
5
THHN 90°C Wire.
6
System with Four (4) Spec. No. 588705300 Rectifier Shelves: Conduit sized for three (3) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for three (3) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
7
System with Five (5) Spec. No. 588705300 Rectifier Shelves / Shelf #6 is Expansion Shelf: Conduit sized for six
(6) current carrying conductors and one (1) ground conductor per conduit (based on NEC recommendations), for six (6) PCUs. For operation in countries where the NEC is not recognized, follow applicable codes.
8
Input current based on R48-2000e3 rectifier module.
Table 23
Recommended AC Input Branch Circuit Protection and Wire Size when Using
List 42 “1 AC Feed per 3 Rectifiers – Three Phase” AC Input Termination Assembly,
System with Spec. No. 588705300 Rectifier Shelves
Page 83 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
(4
-Row
Ca
binet Shown,
O
ther
s S
imil
ar)
F
ro
nt Do
or Re
moved in
Illustration fo
r C
lari
ty
AC INPUT CONNECTIONS, 1 FEED P
ER
1 REC
TIFI
ER, SINGLE PHASE
(
5821
2700
0 LIST 40)
NOTE
:
WIRING TO A
FIEL
D I
NSTA
LLED
SHELF IS DONE AT THE REA
R
OF TH
E S
HELF
.
AC Wireway
Cover
AC Wireway Cover
AC Input
Connec
to
r Cov
er
Inside View
Lef
t Sid
e
Inside View Right Side
GND GND GND GND
AC 2AC
1
PCU 1
AC 2AC 1
PCU 2
AC 2AC 1
PC
U 3
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 1 RECTIFIER (PCU)
208-2
40VAC
, 50/60Hz
, SING
LE PHASE
SHELF 1
AC 2AC 1
PCU 1
AC 2AC 1
PCU 2
AC 2AC 1
PCU 3
AC 2AC 1
PCU 1
AC 2
AC 1
PCU 2
AC 2A
C 1
PCU 3
RECTIFIER (PCU) AC INPUT
FEEDS
1 FEED PER 1 RECTIFIER (PCU)
208-240VAC, 50/60Hz, SINGLE PHASE
SHELF 3 SHELF 2
AC 2AC 1
PCU 1
AC 2AC 1
PCU 2
AC 2AC 1
PCU 3
AC 2AC 1
PCU 1
AC 2AC 1
PCU 2
AC 2AC 1
PCU 3
RECTIFIER (PCU) AC INP
UT F
EEDS
1 FEED P
ER 1
RECTIFIER (PCU)
208-240VAC, 50/60Hz, SINGLE PHASE
SHELF 5 SHELF 4
AC 2AC 1
PCU 4
AC 2
AC 1
PCU 5
AC 2A
C 1
PCU 6
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 1 RECTIFIER (PCU)
208-240
VAC, 50/6
0Hz, S
INGLE PH
ASE
SHELF 1
AC 2AC 1
PCU 4
AC 2AC 1
PC
U 5
AC 2AC 1
PCU 6
AC 2AC 1
PCU 4
AC 2AC 1
PCU 5
AC 2AC 1
PCU 6
RECTIFIER (PCU) AC INPUT FEED
S
1 FEED PER1 RECTIFIER (PCU)
208-24
0VAC, 50/60Hz, SINGLE PHASE
SHELF 2 SHELF 3
AC 2AC 1
PCU 4
AC 2AC 1
PCU 5
AC 2AC 1
PCU 6
AC 2AC 1
PCU 4
AC 2AC 1
PCU 5
AC 2AC 1
PCU 6
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 1 RECTIFI
ER (
PCU)
208-
240VAC, 50/60Hz, SINGLE PHASE
SHELF 4 SHELF 5
Rectifier Module (PCU) Mounting Slo
ts
Shelf #1
Rect.
(PC
U)
1
Rect.
(P
CU
)
2
Rec
t.
(P
CU
)
3
Rec
t.
(P
CU
)
4
Rec
t.
(P
CU
)
5
Rec
t.
(PCU)
6
R
ect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect. (PCU)
5
Rect.
(PCU)
6
Rect.
(
PCU)
1
Rect.
(PCU
)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect. (PCU)
5
Rect.
(PCU)
6
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect. (PCU)
5
Rect.
(PCU)
6
Rect.
(
PC
U)
1
Rect.
(P
CU)
2
Rect.
(
PC
U)
3
Rect.
(P
CU
)
4
Rect. (PCU)
5
Rect.
(PCU)
6
Shelf #2
Shelf #3
Shelf #4
Shelf #5
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
AC Input Connections to AC Input Termination Assembly List 40, 41, 42 Illustration when used with 588705000 or 588705300 Module Mounting Shelves with Rectifiers (Nominal 208/240 Volts AC)
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 84 of 125
System Application Guide SAG582127000
Home
(4-Row Cabinet Shown,
Others Similar)
Front Door Removed in
Illustration for Clarity
AC INPUT CONNECTIONS, 1 FEED PER 2 RECTIFIERS, SINGLE PHASE (582127000 LIST 41)
Inside View
Left Side
Inside View Right Side
NOTE: WIRING TO A FIELD INSTALLED SHELF IS DONE AT THE REAR OF THE SHELF.
GND GND GND GND
AC 2AC 1
PCU 1
AC 2AC 1
PCU 2
AC 2AC 1
PCU 3
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 2 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, SINGLE PHASE
SHELVES 1 AND 2
AC 2AC 1
PCU 4
AC 2AC 1
PCU 5
AC 2AC 1
PCU 6
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 2 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, SINGLE PHASE
SHELVES 1 AND 2
AC 2AC 1
PCU 1
AC 2AC 1
PCU 2
AC 2AC 1
PCU 3
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 2 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, SINGLE PHASE
SHELVES 3 AND 4
AC 2AC 1
PCU 4
AC 2AC 1
PCU 5
AC 2AC 1
PCU 6
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 2 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, SINGLE PHASE
SHELVES 3 AND 4
AC Wireway
Cover
AC Wireway Cover
AC Input
Connector Cover
Rectifier Module (PCU) Mounting Slots
Shelf #1
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect. (PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Shelf #2
Shelf #3
Shelf #4
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Page 85 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
(4-Row Cabinet Shown,
Others Similar)
Front Door Removed in
Illustration for Clarity
AC INPUT CONNECTIONS, 1 FEED PER 3 RECTIFIERS, THREE PHASE (582127000 LIST 42)
Inside View
Left Side
Inside View Right Side
NOTE: WIRING TO A FIELD INSTALLED SHELF IS DONE AT THE REAR OF THE SHELF.
GND GND
GND GND
AC Wireway
Cover
AC Wireway Cover
AC Input
Connector Cover
A B C
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 3 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, THREE PHASE
SHELF 1 - PCUs #1 - #3
A B C
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 3 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, THREE PHASE
SHELF 3 - PCUs #1 - #3
A B C
SHELF 2 - PCUs #1 - #3
A B C
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 3 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, THREE PHASE
SHELF 5 - PCUs #1 - #3
A B C
SHELF 4 - PCUs #1 - #3
C B A
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 3 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, THREE PHASE
SHELF 1 - PCUs #4 - #6
C B A
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 3 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, THREE PHASE
SHELF 2 - PCUs #4 - #6
C B A
SHELF 3 - PCUs #4 - #6
C B A
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 3 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, THREE PHASE
SHELF 4 - PCUs #4 - #6
C B A
SHELF 5 - PCUs #4 - #6
Rectifier Module (PCU) Mounting Slots
Shelf #1
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
Shelf #2
Shelf #3
Shelf #4
Shelf #5
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Page 86 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
(4)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

400V DC Input

DC Input Branch Circuit Protection and Wire Size Selection for DC Input Termination Assembly List 45, 46, 47 when used with 588705000 Module Mounting Shelves with Converters (input voltage range: 290V DC to 400V DC)
Refer to the following tables for recommended wire sizes and branch circuit protection.
DC INPUT TO LIST 45 DC INPUT TERMINATION ASSEMBLY
(400 Volts DC)
Provides “1 DC Feed per 1 Converter” Input Terminations
(System with Spec. No. 58870500040 Converter Shelves)
40°C Ambient
Input
Voltage
Input
Current
Overcurrent
Protection
Wire
400V DC 11A
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
(7)
15A 14 AWG
Temperature
(1) (2) (3) (6)
Conduit
Size
1/2”
(5)
3/4”
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Equipment grounding conductors must be provided with the DC input conductors supplied to the shelf.
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
3
THHN 90°C Wire.
4
System with Four (4) Spec. No. 588705000 Converter Shelves: Conduit sized for six (6) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for three (3) converters. For operation in countries where the NEC is not recognized, follow applicable codes.
5
System with Five (5) Spec. No. 588705000 Converter Shelves: Conduit sized for twelve (12) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for three (3) converters. For operation in countries where the NEC is not recognized, follow applicable codes.
6
Maximum loop length is 100 meters (328 feet). Loop length is the sum of the lengths of the positive and
negative leads.
7
10.8Adc maximum input current @ 336V DC, 3500W output.
Table 24
Recommended DC Input Branch Circuit Protection and Wire Size when Using
List 45 “1 DC Feed per 1 Converter” DC Input Termination Assembly,
System with Spec. No. 588705000 Converter Shelves
Page 87 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
(4)
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
DC INPUT TO LIST 46 DC INPUT TERMINATION ASSEMBLY
(400 Volts DC)
Provides “1 DC Feed per 2 Converters” Input Terminations
(System with Spec. No. 58870500040 Converter Shelves)
40°C Ambient
Input
Voltage
Input
Current
Overcurrent
Protection
Wire
Temperature
(1) (2) (3) (5)
Conduit
Size
400V DC 22A 30A 10 AWG 1/2”
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Equipment grounding conductors must be provided with the DC input conductors supplied to the shelf.
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
3
THHN 90°C Wire.
4
System with Four (4) Spec. No. 588705000 Converter Shelves: Conduit sized for four (4) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for four (4) converters. For operation in countries where the NEC is not recognized, follow applicable codes.
5
Maximum loop length is 100 meters (328 feet). Loop length is the sum of the lengths of the positive and
negative leads.
Table 25
Recommended DC Input Branch Circuit Protection and Wire Size when Using
List 46 “1 DC Feed per 2 Converters” DC Input Termination Assembly,
System with Spec. No. 588705000 Converter Shelves
Page 88 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582127000
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
DC INPUT TO LIST 47 DC INPUT TERMINATION ASSEMBLY
(400 Volts DC)
Provides “1 DC Feed per 3 Converters” Input Terminations
(System with Spec. No. 58870500040 Converter Shelves)
40°C Ambient
Input
Voltage
Input
Current
Overcurrent
Protection
(4)
Wire
Temperature
(1) (2) (3) (7)
Conduit
(5) (6)
Size
400V DC 33A 45A 6 AWG 1”
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Equipment grounding conductors must be provided with the DC input conductors supplied to the shelf.
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
3
THHN 90°C Wire.
4
Maximum over current protection device is 60A at 40°C.
5
System with Four (4) Spec. No. 588705000 Converter Shelves: Conduit sized for two (2) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for three (3) converters. For operation in countries where the NEC is not recognized, follow applicable codes.
6
System with Five (5) Spec. No. 588705000 Converter Shelves: Conduit sized for four (4) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for six (6) converters. For operation in countries where the NEC is not recognized, follow applicable codes.
7
Maximum loop length is 100 meters (328 feet). Loop length is the sum of the lengths of the positive and
negative leads.
Table 26
Recommended DC Input Branch Circuit Protection and Wire Size when Using
List 47 “1 DC Feed per 3 Converters” DC Input Termination Assembly,
System with Spec. No. 588705000 Converter Shelves
Page 89 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
(4-Row Cabinet Shown,
Others Similar)
Front Door Removed in
Illustration for Clarity
DC INPUT CONNECTIONS, 1 FEED PER 1 CONVERTER (582127000 LIST 45)
NOTE: WIRING TO A FIELD INSTALLED SHELF IS DONE AT THE REAR OF THE SHELF.
DC Wireway
Cover
DC Wireway Cover
DC Input
Connector Cover
Inside View
Left Side
Inside View Right Side
GND GND
GND GND
Converter Module Mounting Slots
Shelf #1
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Shelf #2
Shelf #3
Shelf #4
Shelf #5
Conv. 1
Conv. 2
Conv. 3
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 1 CONVERTER
SHELF 1
Conv. 1
Conv. 2 Conv. 3 Conv. 1
Conv. 2 Conv. 3
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 1 CONVERTER
SHELF 3
SHELF 2
+ - + - + -
+ - + - + -
+ - + - + -
Conv. 1 Conv. 2 Conv. 3 Conv. 1 Conv. 2 Conv. 3
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 1 CONVERTER
SHELF 5
SHELF 4
+ - + - + - + - + - + -
Conv. 4 Conv. 5
Conv. 6
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 1 CONVERTER
SHELF 1
Conv. 4
Conv. 5 Conv. 6 Conv. 4 Conv. 5
Conv. 6
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 1 CONVERTER
SHELF 2
SHELF 3
+ - + - + -
+ - + - + -
+ - + - + -
Conv. 4 Conv. 5 Conv. 6 Conv. 4 Conv. 5 Conv. 6
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 1 CONVERTER
SHELF 4
SHELF 5
+ - + - + - + - + - + -
CONV4
+ -
CONV5
+ -
CONV6
+ -
CONV4
+ -
CONV5
+ -
CONV6
+ -
CONV4
+ -
CONV5
+ -
CONV6
+ -
CONV4
+ -
CONV5
+ -
CONV6
+ -
CONV4
+ -
CONV5
+ -
CONV6
+ -
CONV1
+ -
CONV2
+ -
CONV3
+ -
CONV1
+ -
CONV2
+ -
CONV3
+ -
CONV1
+ -
CONV2
+ -
CONV3
+ -
CONV1
+ -
CONV2
+ -
CONV3
+ -
CONV1
+ -
CONV2
+ -
CONV3
+ -
Home
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
400V DC Input Connections to DC Input Termination Assembly List 45, 46, 47 Illustration when used with 588705000 Module Mounting Shelves with Converters
NPBB)
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 90 of 125
System Application Guide SAG582127000
Home
(4-Row Cabine
t
Sh
own,
Others Similar)
Front Door R
em
o
ved in
Illustration for Clarity
DC INPUT CONNECTIONS, 1 F
E
ED PER 2 CONVERTERS
(582127000 LIST 46)
Inside View
Left Side
Inside View Right Side
NOTE: W
IR
ING TO
A FIELD INSTALLED
SHELF IS DONE AT T
HE
R
EAR
OF
TH
E SHELF.
GND GND GND GND
DC Wireway
Cover
D
C Wireway
Cover
DC Input
Connector Cover
Converter Module M
o
un
ti
n
g Slots
Shelf #1
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
C
on
v.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1C
on
v.2Conv.3Conv.4Conv.5Conv.
6
Shelf #2
Shelf #3
Shelf #4
Conv. 1 Co
nv. 2 Conv. 3
400VDC CONV
ERTER DC INPUT FEEDS
1 FEED PER 2 CONVERTERS
SHELVES 1 AND 2
+ - + - + -
Conv. 1 Conv. 2 Conv. 3
400VDC CONVERTER DC INPU
T FEEDS
1 FEED PER 2 CONVERTERS
SHELVES 3 AND 4
+ - + - + -
Conv. 4 Conv. 5 Conv. 6
400VDC CONVERTER DC
INP
UT FEEDS
1 FEED PER 2
CONVERTERS
SHELVES 1 AND 2
+ - + - + -
Conv. 4 Conv. 5 Conv. 6
4
00VDC CONVERTER DC INPUT FEEDS
1 FEED PER 2 CONVERTERS
SHELVES 3 AND 4
+ - + - + -
CONV 4
+ -
CONV
5
+ -
CONV 6 + -
CONV 1
+ -
CONV 2
+
-
CONV 3
+ -
CONV 4
+ -
CONV 5 + -
CONV 6 + -
CONV 1 + -
CO
NV 2
+ -
CONV 3
+ -
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 91 of 125
SAG582127000 System Application Guide
Home
(4-Row Cabinet Shown,
Others Similar)
Front Door Removed in
Illustration for Clarity
DC INPUT CONNECTIONS, 1 FEED PER 3 CONVERTERS (582127000 LIST 47)
Inside View
Left Side
Inside View Right Side
NOTE: WIRING TO A FIELD INSTALLED SHELF IS DONE AT THE REAR OF THE SHELF.
GND GND GND GND
DC Wireway
Cover
DC Wireway Cover
DC Input
Connector Cover
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 3 CONVERTERS
SHELF 1: Conv. #1 - #3
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 3 CONVERTERS
SHELF 3: Conv. #1 - #3 SHELF 2: Conv. #1 - #3
Converter Module Mounting Slots
Shelf #1
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Conv.1Conv.2Conv.3Conv.4Conv.5Conv.
6
Shelf #2
Shelf #3
Shelf #4
Shelf #5
+ -
+ - + -
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 3 CONVERTERS
SHELF 5: Conv. #1 - #3 SHELF 4: Conv. #1 - #3
+ - + -
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 3 CONVERTERS
SHELF 1: Conv. #4 - #6
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 3 CONVERTERS
SHELF 2: Conv. #4 - #6 SHELF 3: Conv. #4 - #6
+ -
+ - + -
400VDC CONVERTER DC INPUT FEEDS
1 FEED PER 3 CONVERTERS
SHELF 4: Conv. #4 - #6 SHELF 5: Conv. #4 - #6
+ - + -
SHELF 1 CONV4-6
SHELF 2 CONV4-6 SHELF 3 CONV4-6
SHELF 4 CONV4-6 SHELF 5 CONV4-6
SHELF 1 CONV1-3
SHELF 3 CONV1-3 SHELF 2 CONV1-3
SHELF 5 CONV1-3 SHELF 4 CONV1-3
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 92 of 125
System Application Guide SAG582127000
Optional SM-DU+ and Shunt Interface Board
4-Row Cabinet Shown,
Others Similar
(Front Door Removed in
Illustration for Clarity)
System Interface
Circuit Card
OR
Optional Manual Battery Disconnect Circuit Card (Main Bay Only)
Optional LVD
Driver Circuit Card
Optional LVD Driver
Lite Circuit Card
ACU+ Controller
(Main Bay)
SM-DU
(Supplemental Bays)
Mounting Position
IB2 (Main Bay Only)
(ACU+ Interface Board)
(located on inside side panel)
Optional EIB (Main Bay Only)
(ACU+ Extended Interface Board)
(located on inside side panel)
Home
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014

Field Installed Module Mounting Shelves

Input Branch Circuit Protection, Wire Size Selection, and Wiring Illustration (when wiring to Field Installed Module Mounting Shelves)
Refer to Power Data Sheet PD588705000 or PD588705300.

External Alarm, Reference, Monitoring

External Alarm, Reference, Monitoring, and Control Wire Sizes
Recommended wire size is 22 AWG for loop lengths up to 200 ft. and 18-20 AWG for loop lengths over 200 ft.
External Alarm, Reference, Monitoring, and Control Illustrations
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 93 of 125
SAG582127000 System Application Guide
Home
S
y
s
t
e
m
I
n
t
e
r
f
a
c
e
C
i
r
c
ui
t
Ca
r
d
J1
, J
2
, J3, J4
D
is
t
ri
b
u
t
i
o
n
P
a
n
e
l
s
F
A
I
n
p
u
t
s
J
8
(
M
a
i
n
B
a
y
O
n
l
y
)
S
e
le
ct
s
to
p
ow
er Controller
from “Battery Power” or
n
ot
.
No
Ba
tt
e
ry
Pwr
Ba
t
te
r
y
Pwr
E
xte
rna
l Internal
J
8
J
1
0
1 2 3
7 8 9
J1
0
(M
ain B
ay O
nly
)
B
a
tt
er
y
Mo
ni
t
ori
ng Ex
ter
nal
/ In
ternal
(s
ee T
B1-4 a
nd
TB
1
-5
fo
r
ex
ter
nal m
oni
tor
ing
points)
J5 C
AN
TP
3 (+) an
d TP4 (-)
Ba
y Load
Shunt
Moni
tori
ng
TP1 (
+) and
TP2 (
-)
Ba
y Volt
age
M
onitori
ng
TB1-
1:
Ba
tt
ery Tra
y FA
TB
1-2: Ex
ter
nal
Battery
FA
TB
1-3:
Ext
ernal S
ystem
FA
TB
1-4: E
xte
rnal Ba
ttery Mo
nit
ori
ng (-)
TB1
-5: Ex
ternal B
atte
ry M
onitori
ng (+)
1
1A
2A 3
A
1
B 2B
3B
5
RS4
85 C
onn
ecti
on
TB2
1A:
RS4
85+
TB2
2A:
RS
48
5-
R
S
23
2
Con
nec
tio
n
T
B2 1B
: C
G
ND
TB2
2B: T
XD23
2
TB
2 3
B:
RXD
232
S
hort
ing
Jumper
1 2 3
7 8 9
Sh
o
rt
in
g Ju
mpe
r
J
1
J
2
J3
J4
J
8
T
B
2
T
B1
TP1
TP2 TP3 TP
4
J10
J5
TB
1
TB1-2, TB
1-3
, TB1-
4, TB1-5 Ma
in Bay
Only.
W
ire
Size Ca
pacity: 22
-12 AW
G.
R
ecommended
Torq
ue: 3.0 in-lbs.
FA Signal
s: Bat
tery applied to
the te
rminal
tu
rns in an alar
m.
TB
2 3
A
: I
n
ter
nal
ly
u
sed b
y s
y
st
e
m.
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 94 of 125
System Application Guide SAG582127000
Home
Switch settings must be in this position
to
in
t
er
f
ac
e w
i
th
th
e
AC
U+
C
on
tr
o
ll
e
r
* The ACU+ relay assigned to “Critical Summary” alarm (relay 1 by default)
will operate in the “Fail Safe Mode”. “Fail Safe Mode” means Relay 1 is de-energized during an alarm condition, opening the contacts between the C and NO terminals, and closing the contacts between the C and NC terminals.
The ACU+’s remaining seven (7) relays energize during an alarm condition, closing the contacts between the C and NO terminals, and opening the contacts between the C and NC terminals
.
Not all I/O points are available for customer connection (some are used for factory system connections).
J3-J9: Wire Size Capacity: 16-26 AWG. Recommended Torque: 2.2 in-lbs.
M A4
C 5U
3 1
IB2
DI1-
DI1+
DI2-
DI2+
DI3-
DI3+
J3
J4
J5
J6
J7
J8
J9
DI4-
DI4+
DI5-
DI5+
DI6-
DI6+
DI7-
DI7+
DI8-
DI8+
DO1_NC
DO2_NC DO1_COM DO2_COM
DO1_NO DO2_NO
DO3_NC
DO4_NC DO3_COM DO4_COM
DO3_NO DO4_NO
DO5_NC
DO6_NC DO5_COM DO6_COM
DO5_NO DO6_NO
DO7_NC
DO8_NC DO7_COM DO8_COM
DO7_NO DO8_NO
J
11 1
J1
1 2
J
11 3
J12 1
J1
2 2
J1
2 3
2
4
3
1
J2
6 5 4 3
2 1 6
5 4 3
2 1 6
5 4 3 2
1 6 5
4 3 2
1 6 5 4
3 2 1 6 5
4 3 2 1 6 5
4 3 2
1
STUPTUO
YALER
STUPNILAT
IGID
Schematic Diagram of IB2 Board
IB2 TEMP PROBE 1
IB2 TEMP
PROBE 2
-
J1
2
*
RE
L
A
Y
S
W
1
7
J2
J
11
5
3
1
R
el
ay
O
ut
pu
t
Te
rm
i
na
l
Bl
oc
k
s
D
ig
i
ta
l I
n
pu
t
Te
rm
i
na
l B
l
oc
ks
J9
J8
J
7
J
6
J
5
J4
J
3
8
6
4
2
8
7
6 5
4 3
2
1
+
I
B
2
B
o
a
r
d
(
T
o
p
V
i
e
w
)
N
O
C
N
C
NO
C
NC
N
O
C
N
C
NO
C
NC
N
O
C
N
C
NO
C N
C
N
O
C
N
C
NO
C N
C
5 3 1
46 2
5
3 1
46 2
5
3
1
46
2
5
3
1
46
2
5
3
1
4
6
2
5
3
1
4
6
2
5
3
1
4
6
2
C
o
n
n
e
c
t
o
r
to
AC
U
+
IB
2
TE
M
P
P
R
O
B
R
E 1
IB
2 TE
MP
PR
O
BE
2
IB2 Board Assembly
IB2
(ACU+ Interface Board)
(located on inside side
panel of Main Bay)
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 95 of 125
SAG582127000 System Application Guide
Home
Optional EIB
(ACU+ Extended Interface Board)
(located on inside side
panel of Main Bay)
MA455U41
EIB
SH1-
SH1+
SH2-
SH2+
SH3-
SH3+
J5
J6 J7
J8 J9
DCV1
DCV2
DCV3
DCV4
DCV5
DCV6
DCV7
DO5_NC
DCV8
DO5_COM
DO1_NC
DO2_NC
DO1_COM
DO2_COM
DO1_NO
DO2_NO
DO3_NC
DO4_NC
DO3_COM
DO4_COM
DO3_NO
DO4_NO
J3 1
J3 2
J3 3
J4 1
J4 2
J4 3
2 4
3 1
J2
DO5_NO
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
SHUNT
INPUTS
VOLTAGE
INPUTS
RELAY OUTPUTS
EIB TEMP
PROBE 2
EIB TEMP
PROBE 1
Schematic Diagram of EIB Board
J5-J9 Wire Size Capacity: 16-26 AWG. Recommended Torque: 2.2 in-lbs.
EIB Board
J5 J6 J7 J8 J9
2
4
6
31 5
2
4
6
31 5
2
4
6
31 5
2
4
6
31 5
2
4
6
31 5
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 96 of 125
System Application Guide SAG582127000
SM-DU+ and Shunt
Interface Board
TB1 - TB2 Wire Size Capacity: 16-26 AWG. Recommended Torque: 2.2 in-lbs.
Shunt Interface Board
SMDU+
2 1
J3
1 2
J1
SHUNT INPUTS
541127 SHUNT
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
J1
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
J2
SHUNT25+ SHUNT25­SHUNT24+ SHUNT24­SHUNT23+ SHUNT23­SHUNT22+ SHUNT22­SHUNT21+ SHUNT21­SHUNT20+ SHUNT20­SHUNT19+ SHUNT19­SHUNT18+ SHUNT18­SHUNT17+ SHUNT17­SHUNT16+ SHUNT16­SHUNT15+ SHUNT15­SHUNT14+ SHUNT14-
TB2
25A 25B 24A 24B 23A 23B 22A 22B 21A 21B 20A 20B 19A 19B 18A 18B 17A 17B 16A 16B 15A 15B 14A 14B
SHUNT12+ SHUNT12-
SHUNT13+ SHUNT13-
SHUNT11+ SHUNT11­SHUNT10+ SHUNT10­SHUNT9+ SHUNT9­SHUNT8+ SHUNT8­SHUNT7+ SHUNT7­SHUNT6+ SHUNT6­SHUNT5+ SHUNT5­SHUNT4+ SHUNT4­SHUNT3+ SHUNT3­SHUNT2+ SHUNT2­SHUNT1+ SHUNT1-
TB1
12A 12B
13A 13B
11A 11B 10A 10B
9A 9B 8A 8B 7A 7B 6A 6B 5A 5B 4A 4B 3A 3B 2A 2B 1A 1B
3
INTERFACE
1A
1B
TB1 TB2
J2J1
Schematic Diagram of SM-DU+ and Shunt Interface Board
-
+
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Page 97 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Optional LVD
Driver Circuit Card
LVD Inhibit Switch
Momentary UP / Middle / Down Momentary UP Position: Closes all LVD Contactors (inhibit mode). Middle Position: OFF (ACU+ DOES NOT control LVD’s) (inhibit mode). DOWN Position: ON (ACU+ controls LVD’s).
LVD Inhibit Active Indicator
Notes:
1. Connects up to (4) LVLD and (1) LVBD contactors.
2. Switch and indicator located on circuit card installed in Main Bay only.
J6
J5
J4
J3 J2 J1
J7
S1
J1, J2, J3 To LVLD contactor, uses ACU+ LVD1 control setting (Level 1).
J4, J5, J6 To LVLD contactor, uses ACU+ LVD2 control setting (Level 2).
J7 To LVBD contactor, uses ACU+ LVD2 control setting (Level 2).
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 98 of 125
System Application Guide SAG582127000
Home
Optional LVD Driver
Lite Circuit Card
LVD Inhibit Switch
LVD Inhibit Active Indicator
Momentary UP / Middle / Down Momentary UP Position: Closes all LVD Contactors (inhibit mode). Middle Position: OFF (ACU+ DOES NOT control LVD’s) (inhibit mode). DOWN Position: ON (ACU+ controls LVD’s).
J1J3
J2
Notes:
1. Connects up to (2) LVD contactors rated at 600A or less.
2. Only one (1) contactor per level
can be accommodated. J2 and J3 are on Level 2, only one (1) of these connectors can be used at a time.
3. Switch and indicator located
on circuit card installed in Main Bay only.
J1 To LVLD contactor, uses ACU+ LVD1 control setting (Level 1).
J3 To LVLD contactor, uses ACU+ LVD2 control setting (Level 2).
J2 To LVBD contactor, uses ACU+ LVD2 control setting (Level 2). Can only be used if it is contained in a List 21 (1-row) cabinet.
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Page 99 of 125
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582127000 System Application Guide
Home
Op
ti
o
na
l Manua
l B
a
tt
er
y
D
is
co
n
ne
ctCirc
ui
t
Ca
rd
(M
ai
n
Ba
y O
nl
y
)
Mom
enta
ry U
P / M
iddle /
Mom
ent
ary
D
own Momentary UP Postion:Closes Battery Disconnect Contactor Middle Position: Normal Operation Momentary DOWN Postion: Opens Battery Disconnect Contactor